Overview of a Year of Battery Fire Testing by DNV GL for Con Ed, NYSERDA and FDNY

Size: px
Start display at page:

Download "Overview of a Year of Battery Fire Testing by DNV GL for Con Ed, NYSERDA and FDNY"

Transcription

1 2017 NFPA Conference & Expo Overview of a Year of Battery Fire Testing by DNV GL for Con Ed, NYSERDA and FDNY Presented by: Nick Warner, Sr. Test Engineer, DNV GL Dalan Zartman, President, Rescue Methods Fire Safety Testing Overview With the Cooperation of: 2 1

2 Introduction Test Setup Toxicity and Ventilation How bad are these things? How should I size my ventilation? What other less obvious risks exist? Extinguishing Are other agents effective? Reignition and cascading. Is it real? Ventilation and extinguishing Overhaul and firefighting operations 3 Test Setup 4 2

3 Test Setup, Cell Level Gas sampling was performed three ways: GasmetDX4000 FTIR collected: O2, CO, NO, CO2, NO2, SO2, CH4, Ethylene, Benzene, Toluene, Propane, Ethane, HCl, HF, HCN Based on DNV GL s ARPAeAMPED work MSA Ultima Sensors recorded: O2, H2, F2/Cl2, LEL Gas bag sampling was performed minimally as gas bag data aligned with FTIR data Besides gas sampling, a thermopile of eight thermocouples was built around the battery in addition to inlet and outlet temperatures, ambient chamber temps, and thermocouples placed directly on the battery Batteries were heated by x4 1kW ceramic radiant heaters. In cases where batteries vented but did not ignite, two hot point ignitors were placed in the upper chamber that triggered at 50% LEL. 5 Test Setup, Cell Level Morning Pride PPE swatches were placed in the unit as well to assess effect of battery fire on the gear. This material was to FDNY spec (A full set of turnout gear was also placed on a mannequin during a module test burn) Occasional surface swabs were taken from inside the chamber as well. Testing showed typical fire residue as well as trace amounts of nickel, cobalt, and manganese (as would be expected from NCM batteries). No swabs were taken after LTO or LFP tests, but results were not expected to differ (Fe and Tiare less toxic as well) Direction of misting nozzle from extinguisher Approximately 25% of the cells tested did not conflagrate or generate enough gas to burn as a result of chemistry, SOC, constraint, or overall size. Thus testing focused on those that did. 6 3

4 12/05/2017 Examples of Cell Fires 1 Flashover (triggered by ignitors) after venting with no self ignition 3 2 Images 1-3 show a pouch cell as it swells, vents and self ignites (pictures approximately 3 seconds apart) 7 Module Fire Burn Room Setup Two Firecams and a thermal imaging camera were placed inside the room, an additional camera and thermal imaging camera were setup outside The FTIR sensor probe was put through the wall to record off gas, while two other MSA Altair 5 gas sensors were placed around the unit. All firefighters around the unit wore MSA Altair 4 gas sensors Thermocouples were placed up one side of the wall to record thermal layers Thermocouples 8 4

5 Module Fire Burn Room Ventilation In addition to video and data acquisition as well as extinguishing, we were also interested in qualitatively testing certain ventilation strategies To accomplish this, five ~1sqft holes cut into the room, high and low on each side of the room and one on the roof. In addition, we mostly test negative ventilation, but also supplemented with positive ventilation in some instances. 9 Module Burn Example Data 10 5

6 Module Scale Testing Pictures *One mannequin and one fan were thoroughly harmed in the making of these videos 11 Ventilation 12 6

7 Ventilation Considerations Of primary interest were flammable and toxic gases. The limits of the FTIR were such that most flammable gases could not be measured reliably in their LEL ranges. Though all were reliably measured through their IDLH ranges A catalytic bead LEL with nonspecific cal was used for LEL measurements The primary toxic gases monitored were CO, HCl, HF, HCN, Benzene, Toluene Gas were observed in DNV GL s ARPAeAMPED testing project Ultimately the fires showed similar or less output of those gases than a plastics fire of comparable mass Though peak values are high because of the nature of the failures/fires, they are short lived and longer term values are lower than equal masses of plastic HClis the main driver for ventilation requirements based on IDLH but CO is produced in greater quantities and poses a longer term risk (minutes to hours) 13 Example Off Gas Data Representative Gas Sample 1 CO HCl HF HCN Very similar batteries, very different results Representative Gas Sample 2 CO HCl HF HCN time (s) 2000 Different form factor, chemistry and much larger than 1 and 2, mixed results in terms of similarity Representative Gas Sample time (s) time (s) CO HCl HF HCN Ultimately normalizing for mass and Whmade more sense than trying to distinguish by chemistry and form factor. Electrolyte and plastics are the larger driver of off gas and exist equally regardless of electrode chemistry 14 7

8 What We Looked For Concentration (ppm unless otherwise noted) NFPA Codes (F=flammability, H=health, R=reactivity, S=special) Chemistry Relevant Detected LEL (Lower IDLH Solubility in Auto Ig. F H R S Ref. Batteries State Explosion (Immediately Water Temp (deg Limit) Dangerous to (mg/l) C) Life and Health) Methane CH 4 Li-ion Gas 50,000 5, NJ DOH Carbon CO All Gas 12,500 1, CDC.gov Monoxide Benzene All except Gas 12,000 3, CDC.gov PbA Ethane Vanadium Gas 30, CDC.gov Redox Ethylene C 2H 4 Li-ion Gas 27, Matheson MSDS Hydrogen H2S Pb Acid, Liion Gas 40, CDC.gov Hydrogen H2S VR, PbA Gas 4, , CDC.gov Sulfide Hydrogen HF All except Gas - 30 miscible CDC.gov Fluoride PbA Hydrogen HCl All Gas CDC.gov Chloride SO2 SO2 VR, PbA Gas , CDC.gov Hydrogen HCN All except Gas - 50 miscible CDC.gov Cyanide PbA Nickel Ni Li-ion Residue / Powder Manganese Mn Li-ion Residue / Powder Cobalt Co Li-ion Residue / - - Insoluble Powder Lithium Li Li-ion Residue / W Powder V2O5 Dust V2O5 VR Residue - 35 mg/m^ CDC.gov Pb Vapor, Pb PbA Residue mg/m^3 10^-5 to CDC.gov salts, dust Battery Peak Gas Release In many cases, cells generated large amounts of gas both flammable and toxic internally before venting. As soon as the batteries vented, a large, but short lived, burst of gases was detected. These bursts caused high peak values of a range of toxic gases including HCl, HF, CO and HCN. Again though, these bursts were short lived (on the order of seconds to one minute). 16 8

9 Battery Average Gas Release However, over the total event duration, the average levels of the gases were much lower In many cases literature did not provide sufficient data, so representative samples of plastics were burned to compare them to the batteries In many cases, the average long term exposure over several minutes, when normalized for mass, is higher in pure plastics fires. For that reason, in many cases, recommended ventilation requirements are not higher than those already recommended for similar scenarios 17 Example Ventilation Requirements These tables show the projected required air change overs per hour during events of varying sizes and for different sized environments In many cases, the existing regulations for similar systems call for ventilation that is sufficient for smaller failures Though CO is typically generated in greater quantities, HClis next and has a lower IDLH, making it the main driver for ventilation requirements 18 9

10 Extinguishing 19 Cell Level Extinguishing Test Setup A 2.5gal pressurized water can was controlled via an electronic solenoid valve. The extinguisher was typically filled with 1 gallon of agent, mixed to manufacturer specs, and the valve was opened the until the extinguisher exhausted itself All manufacturers approved of the extinguisher setup and specs An eight second pulse of water was used in one test to verify a theory about gas management All testing was done on pouch cells as they proved best at sustaining a fightable fire. Cells were unconstrained and left exposed, as opposed to being constrained as they would in regular systems Unconstrained cells did show higher volatility than constrained cells in testing without extinguishing 20 10

11 Cell Level Findings Summary All agents were effective at immediately knocking out the fire All water based agents that were deployed fully (~30 seconds) experienced flashover mid cycle. The 8 second pulse put out the fire but did not experience the flashover It is known from previous testing that cells, even when extinguished, continue to generate gas while hot It is believed that this fact, coupled with the direction of the extinguisher, drove flammable gas toward the top of the chamber, which was unsuppressed, and triggered the ignitors It is not believed this will be an issue in actual applications, as there should not be an ignition source in those scenarios However, it is important to note that flammable gas generation remains an issue during extinguishing 21 Extinguishing Agent Effectiveness Top of Cell Bottom of Cell Again, all agents extinguished the fire, but water showed marginally better performance than the other agents at continued cooling after the fact. This was reflected on different cell types. Water also showed better cooling ability 22 11

12 Recommended Water Usage for Sprinklers Based on heat release rate, expected propagation of fire through the system, the deployment of sufficient cascading protections and the aggressive & proactive deployment of suppression, sizing of sprinklers in large scale systems can be as small as.2gpm/kg of battery 23 Required Water Use for Fire Fighting: Worst Case Scenario Why is this so much worse than expected? 24 12

13 Need for Cascading Protection: Reignition Insufficient cascading protection allowed a hot, deep seated core to remain as the surface was cooled. Lack of cascading protection allowed this heat to rapidly spread back through the battery and reignite remaining active mass. It took far more water than usual to cool the battery and flame had to be put out several times. Once the battery completely cooled though, it remained stable for weeks. This reignition took place on the order of seconds to minutes, not hours and days HOWEVER:Based on literature review and project experience, batteries do not magically reignite on their own once properlycooled. Previous examples of reigntion ALWAYS involve external electrical, thermal or mechanical stimuli 25 Need for Cascading Protection: Proof These are results from a gas phase extinguishing agent test. Two pouch cells were stacked together. Though the fire did extinguish, the hot battery continued to generate flammable gas. At one point, enough oxygen seeped into the bottom of the chamber for a small flash to occur in the lower part of the chamber. This verified discussions with fire services that even if the fire is out, the reintroduction of oxygen into the gas filled space would pose a flashover/backdraft risk. DNV GL recommends any system equipped with an inert gas/clean agent system that has not demonstrated sufficient cascading protection be supported by a water based sprinkler system 26 13

14 Four Tile Video As the video will show, the effectiveness of extinguishing is somewhat dependent on ventilation and it becomes difficult in this case to extinguish this battery with sprinklers when ventilation is not operating 27 Firefighting Operation and Overhaul 28 14

15 Overall Lessons Learned and Recommendations During testing, especially module testing, a handful of important points were discovered that should be shared with all first responders: Ventilation is key. It was demonstrated time and again that batteries will continue to generate flammable gas so long as they stay hot, but a key component of that gas is CO, which is generated until the batteries are completely cooled through to their core While storing batteries in the back 30 of the trailer, after placing four or five batteries, CO levels hit over 100ppm even with a small man door open Batteries were submerged to test the effectiveness of that method for cooling and neutralizing damaged cells. Batteries continued to off gas CO for extended periods while submerged. May also have included H2. For these reasons, DNV GL recommends SCBA be worn during all stages of the fire, including overhaul, and that ventilation be maintained through overhaul as well, especially in confined areas 29 Does Submerging Batteries Help? Submerging batteries after they burned seemed to prove effective at cooling the batteries and neutralizing the thermal threat. However, even after submerging batteries, many continued to show voltage across surviving cells, suggesting they remain electrically active Also, during submersion, batteries continued to off gas, mostly CO, but possibly also H2. Though no where near LEL or even IDLH levels, submerging several batteries in a confined space may prove problematic without ventilation During submersion, ph typically dropped to ~6, however, one severely burned battery increased ph to 11 after several hours and to 13 after several days It is still not clear what occurred differently 30 15

16 Residual Battery Voltages After Fire Some of these voltage measurements were taken after submersion. Besides the obvious risks associated with AC connections, which can be easily cut and verified, DC voltage risks may remain in systems that are partially damaged or destroyed where stranded energy can not be discharged or isolated 31 Surviving Live Batteries Even after severe fire and while looking heavily destroyed, there may be live cells remaining in the pack For that reason, DNV GL recommends against the use of piercing nozzles and irons and advises great caution when cutting on battery systems Damaged batteries arced and in some cases nearly self welded themselves to the steel test grate when trying to move them from the trailer to the pool. Extreme caution should be advised if this method is to be applied, and should be done after verifying the system is truly electrically neutralized Cells are still intact and live Special thanks to Franklin County Bomb Squad for X-Ray images 32 16

17 Additional DC Electrical Risks Besides the obvious AC risks and risks associated with stranded DC energy, a large scale burn conducted by DNV GL and RM separate from this project showed other weaknesses in systems that should be addressed Though this large scale system performed incredibly well when exposed to fire, and the design extended time to battery ignition significantly, the cables in the unit saw their insulation degrade, leading to arcing in a high temperature environment that may already be generating gas. This may also pose electrical risks in partially damaged systems that are less apparent and not subject to just handling of the batteries 33 QUESTIONS? Nick Warner Nicholas.warner@dnvgl.com SAFER, SMARTER, GREENER 34 17

18 2017 NFPA Conference & Expo CEUs: To receive CEUs for this session, scan your badge at the back of the room before leaving Evaluation: Complete a session evaluation on the mobile app. (Search app store for NFPA 2017 C&E. ) Handouts: Handouts will be available via the mobile app and at nfpa.org/conference Recordings: Audio recordings of all sessions will be available free of charge via NFPA Xchange. 18

Li-ion Tamer Improved monitoring for lithium-ion battery health & safety. SUPDET ESS Design Challenge November 30 th, 2018

Li-ion Tamer Improved monitoring for lithium-ion battery health & safety. SUPDET ESS Design Challenge November 30 th, 2018 Li-ion Tamer Improved monitoring for lithium-ion battery health & safety SUPDET ESS Design Challenge November 30 th, 2018 Overview What is off-gas monitoring? Stages of a Battery Failure Early Warning

More information

Fire Dynamics Research Applied to. Fire Investigation. Overview

Fire Dynamics Research Applied to. Fire Investigation. Overview 2017 NFPA Conference & Expo Fire Dynamics Research Applied to Fire Investigations Presented by: Daniel Madrzykowski Research Engineer UL Firefighter Safety Research Institute Fire Investigation What is

More information

Rooftop Photovoltaic (PV) Systems Examining the Risks and Researching the Options

Rooftop Photovoltaic (PV) Systems Examining the Risks and Researching the Options 2016 NFPA Conference & Expo Rooftop Photovoltaic (PV) Systems Examining the Risks and Researching the Options Presented by: Joel Sipe Senior Managing Engineer Exponent Inc. Outline Project Background Fire

More information

Operate the Mutli-Gas Monitor PID

Operate the Mutli-Gas Monitor PID TASK: Operate the Multi-Gas Monitor Learning Objective CONDITION: In a classroom environment, given a fully charged Multi-gas Monitor with the manufacturer operator s manual, all monitor components/accessories,

More information

NJSP HMRU. Module 5 B HM Operations 1

NJSP HMRU. Module 5 B HM Operations 1 THE MATERIAL PRESENTED IN THIS MODULE IS INTENDED AS AN OVERVIEW. SPECIFIC INFORMATION ON CALIBRATION, OPERATION, AND INTERPRETATION OF RESULTS SHOULD BE OBTAINED FROM EQUIPMENT MANUFACTURERS. IDENTIFYING

More information

1. Chemical Product and Company Identification

1. Chemical Product and Company Identification INR18650 Lithium-Ion Battery LG CHEMICAL LIMITED 1. Chemical Product and Company Identification Product Identification INR18650 Lithium-Ion Battery ( All models manufactured by LG Chem. ) Manufacturer

More information

Electrical Energy Storage (EES) Systems veiligheid, systeemaanpak en testen

Electrical Energy Storage (EES) Systems veiligheid, systeemaanpak en testen Electrical Energy Storage (EES) Systems veiligheid, systeemaanpak en testen IEC Technische Commissie TC 120 Jos van der Burgt 22 October 2018 1 DNV GL 22 October 2018 SAFER, SMARTER, GREENER Electrical

More information

Hazardous Material Safety Program

Hazardous Material Safety Program Hazardous Material Safety Program Lithium Battery History and Testing Presented By: Date: Discussion Topics Challenges for mitigating lithium battery risks as technology advances What do we know from research

More information

5 Operating Modes GX Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots

5 Operating Modes GX Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots 5 Operating Modes GX-6000 Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots GX-6000 5 Operating modes Normal Leak Check Inert Bar hole Snap Log Monitor up to

More information

5 Operating Modes GX Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots

5 Operating Modes GX Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots 5 Operating Modes GX-6000 Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots CONFINED SPACE ENTRY Monitor LEL, O2, CO, and H2S Internal sample pump Pull samples

More information

Dust Hazard Assessments

Dust Hazard Assessments 2017 NFPA Conference & Expo Dust Hazard Assessments The Importance of DHAs in Establishing Work Practices and Facilities Presented by: Jason Reason, CIH, CSP, CHMM Lewellyn Technology, LLC Learning Objectives

More information

NGD8800 USER S MANUAL

NGD8800 USER S MANUAL NGD8800 USER S MANUAL COMBUSTIBLE GAS DETECTOR Please read this manual carefully and thoroughly before using this product. CONTENT Page 1. GENERAL INFORMATION ------------------ 2 2. FEATURES -----------------------------------------

More information

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS FIRE EXTINGUISHING INSTALLATIONS SECTION POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS Version 1 29-09-04 0 Eurofeu position paper on water mist for fire fighting applications 1 Scope The

More information

Large Airports Maintaining Fire Safety through the years

Large Airports Maintaining Fire Safety through the years 2017 NFPA Conference & Expo through the years Presented by: Panos Samaras Fire Safety Officer Athens International Airport Greece 1 Main Points Part 1 Identify Regulatory Environment Recent Fires in Airports

More information

LESSON ONE FIREFIGHTER I Fire Behavior

LESSON ONE FIREFIGHTER I Fire Behavior LESSON ONE FIREFIGHTER I Fire Behavior OBJECTIVE PAGE DOMAIN: COGNITIVE LEVEL OF LEARNING: KNOWLEDGE MATERIALS IFSTA Essentials 4th edition; overhead projector or laptop computer and multi media projector;

More information

AGT 1 Confined Space. Authorised Gas Tester 1. Scienco Limited. Authorised Gas Tester 1 1

AGT 1 Confined Space. Authorised Gas Tester 1. Scienco Limited. Authorised Gas Tester 1 1 Scienco Limited AGT 1 Confined Space Authorised Gas Tester 1 Instructor: Gary Taylor E-Mail: gary@scienco.com Phone: +44 117 971 0001 Office: 10 Chapel Way, Bristol UK BS4 4EU Office Hours: 08:30 to 17:00

More information

Artificial Trees and Fire Performance

Artificial Trees and Fire Performance 2017 NFPA Conference & Expo Artificial Trees and Fire Performance Presented by: Dwayne Sloan Manager, Principal Engineers Building Materials & Suppression UL LLC Learning Objectives Frame the Fire Problem

More information

Safe Operation Manual. Honeywell IQ Force Gas Detector

Safe Operation Manual. Honeywell IQ Force Gas Detector Safe Operation Manual Honeywell IQ Force Gas Detector Honeywell Analytics 800-663-4164 403-248-9226 Fax 403-575-3708 03JUN2012 P/N 50105843-047 Version 01 http://www.honeywell.com HONEYWELL IQ Force PERSONAL

More information

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification 1.0 This specification details the attributes and operating characteristics of the MSA Ultima X Series sensors/transmitters.

More information

compact detector Detection of more than 200 flammable and toxic gases iso 9001:2008

compact detector Detection of more than 200 flammable and toxic gases iso 9001:2008 iso 9001:2008 Quality Management Systems Systéme de Qualité www.sgs.com possibility of additional functions detection of critical temperature detection of flooding electrochemical sensor catalytic sensor

More information

IMPORTANCE of FIREGROUND VENTILATION PRACTICES and DYNAMICS IN FIREFIGHTING (PART I)

IMPORTANCE of FIREGROUND VENTILATION PRACTICES and DYNAMICS IN FIREFIGHTING (PART I) IMPORTANCE of FIREGROUND VENTILATION PRACTICES and DYNAMICS IN FIREFIGHTING (PART I) By Lt. Mike Mason As we have stated previously there are two prominent areas that drive every fire ground and that is

More information

Carbon Monoxide Poisoning

Carbon Monoxide Poisoning National Grid Group Training Exercise #4 This training reflects industry best practices but does not replace your organization s SOPs/SOGs. This material can be utilized to provide a perspective as you

More information

Micro III (Models G203, G203S, and G213) Operation Manual

Micro III (Models G203, G203S, and G213) Operation Manual Micro III (Models G03, G03S, and G13) Operation Manual Worldwide Manufacturer of Gas Detection Solutions Table of contents Page Introduction... 3 For your safety... 3 Application and use... 3 General

More information

GAS DETECTOR ST400EC PART.NO

GAS DETECTOR ST400EC PART.NO DATA SHEET 1(7) GAS DETECTOR ST400EC PART.NO. 004461-004467 DETECTION OF TOXIC GASES AND OXYGEN SYSTEM GS5000, GS3000, SW2020, BUCONTROL / BUTOUCH GENERAL DESCRIPTION Detection of toxic gases and Oxygen

More information

MiniCO, MiniH 2 S, MiniOX, MiniOX Remote, MiniCl 2. , and MiniClO 2. Responder Detectors Instruction Manual "! WARNING

MiniCO, MiniH 2 S, MiniOX, MiniOX Remote, MiniCl 2. , and MiniClO 2. Responder Detectors Instruction Manual ! WARNING MiniCO, MiniH 2 S, MiniOX, MiniOX Remote, MiniCl 2 TM, and MiniClO 2 TM Responder Detectors Instruction Manual "! WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE

More information

Monitores Personales. Personal Monitor

Monitores Personales. Personal Monitor Monitores Personales Personal Monitor Micro IV Full Featured Personal Monitor Micro IV Single-gas Detector Highly configurable smart sensor design Wide range of sensors including O 2, H 2 S, CO, NH 3,

More information

Confined Space Monitoring. Leak Investigation. Functions 4. Bar Hole Sampling. Line Purge Testing. Actual Size GX-2012

Confined Space Monitoring. Leak Investigation. Functions 4. Bar Hole Sampling. Line Purge Testing. Actual Size GX-2012 Confined Space Monitoring Leak Investigation 1 Functions 4 Bar Hole Sampling Line Purge Testing Actual Size GX-2012 3 Operating Modes Internal sample draw pump with 50 range Low flow alarm 3 bright visual

More information

Lithium Ion Battery Off-Gas Monitoring for Battery Health and Safety

Lithium Ion Battery Off-Gas Monitoring for Battery Health and Safety Lithium Ion Battery Off-Gas Monitoring for Battery Health and Safety Scott Swartz, Steve Cummings, Nick Frank, and Bill Dawson Nexceris, LLC 47 th Power Sources Conference Orlando, Florida (June 13, 2016)

More information

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS WITH LOCAL DIGITAL DISPLAY

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS WITH LOCAL DIGITAL DISPLAY REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS WITH LOCAL DIGITAL DISPLAY FEATURES TXGARD & FLAMGARD PLUS Digital display with flexible output options Wide range of long life sensors Non-intrusive one-man

More information

Lamorinda CERT - Unit 2 09/15/2016

Lamorinda CERT - Unit 2 09/15/2016 Contra Costa County CERT Program Unit 2 Fire Safety Released: 15 September 2016 Community Emergency Response Team Personal safety is ALWAYS the number one priority Work as a team Wear personal protective

More information

Many different instruments Many different operating principles including: May sample many different gases & vapour From relatively simple to complex

Many different instruments Many different operating principles including: May sample many different gases & vapour From relatively simple to complex Part 2 Direct Reading Instrumentation Direct Reading Instruments Many different instruments Many different operating principles including: Electrochemical Photoionisation Flame ionisation Chemiluminescence

More information

Detection of explosive gases, toxic gases or oxygen. Infrared XP version. SIL 2 high reliability IP 66. Certifications. The Fixed Gas Detection People

Detection of explosive gases, toxic gases or oxygen. Infrared XP version. SIL 2 high reliability IP 66. Certifications. The Fixed Gas Detection People Fixed Gas Detector Detection of explosive gases, toxic gases or oxygen Infrared XP version SIL 2 high reliability IP 66 Certifications The Fixed Gas Detection People The OLC/OLCT CT range of fixed ddetectors

More information

ESD500. ESD500 Combustible / Toxic Gas Detector

ESD500. ESD500 Combustible / Toxic Gas Detector ESD500 ESD500 Combustible / Toxic Gas Detector Combustible and toxic gas leakage inspection instrument in industrial application Ex-proof certificate Exd ⅡC T6 Gb/Ex d ib ⅡC T6 Gb Dust Ex-proof certificate

More information

Xgard. Fixed detectors For flammable, toxic or oxygen gases

Xgard. Fixed detectors For flammable, toxic or oxygen gases Fixed detectors For flammable, toxic or oxygen gases Xgard Xgard Type 1: Xgard Type 2: Xgard Type 3: Xgard Type 4: Xgard Type 5: Xgard Type 6: Xsafe: Intrinsically safe toxic and oxygen gas detector Flameproof

More information

Hazardous Area Classification in Oil & Gas Industry. A Fire Prevention Tool

Hazardous Area Classification in Oil & Gas Industry. A Fire Prevention Tool Hazardous Area Classification in Oil & Gas Industry A Fire Prevention Tool SFPE ENGINEERING TECHNOLOGY CONFERENCE Oct 4, 2010 New Orleans, LA 1 Overview Oil and gas plants handle flammable materials 2

More information

Health Care Facility Rehabilitation

Health Care Facility Rehabilitation 2017 NFPA Conference & Expo Health Care Facility Rehabilitation Effective Application of NFPA 101 2012, Life Safety Code Chapter 43 Building Rehabilitation Ron Coté, P.E. NFPA Health Care Facility Rehabilitation

More information

Product Selection Guide Fixed Gas Detection Systems for Personnel & Equipment Safety

Product Selection Guide Fixed Gas Detection Systems for Personnel & Equipment Safety Product Selection Guide Fixed Gas Detection Systems for Personnel & Equipment Safety GDS Corp gas monitors, controllers and sensors satisfy today s needs for safety and reliability in critical gas detection

More information

6-1 Installing Batteries 6-2 Automatic Circuit/Reset Feature 6-3 Feature Sensitivity Adjustment

6-1 Installing Batteries 6-2 Automatic Circuit/Reset Feature 6-3 Feature Sensitivity Adjustment CONTENT Page 1. GENERAL INFORMATION ------------------ 2 2. FEATURES ---------------------------------------- 2 3. SPECIFICATION --------------------------------- 3 4. OPERATION GUIDE ---------------------------

More information

Fire Suppression Tests Using a Handheld Water Mist Extinguisher Designed for Spacecraft Applications

Fire Suppression Tests Using a Handheld Water Mist Extinguisher Designed for Spacecraft Applications National Aeronautics and Space Administration Fire Suppression Tests Using a Handheld Water Mist Extinguisher Designed for Spacecraft Applications SUPDET 2012 Phoenix, AZ Thierry Carriere (thierryc@adatech.com),

More information

BP MAINTENANCE WORK INSTRUCTIONS FREQUENTLY ASKED QUESTIONS

BP MAINTENANCE WORK INSTRUCTIONS FREQUENTLY ASKED QUESTIONS BP MAINTENANCE WORK INSTRUCTIONS FREQUENTLY ASKED QUESTIONS The following FAQ was last updated 30/3/2016. This material is guidance only. If any of the content contradicts with requirements within the

More information

EMERGENCY PHONE: or (651) (24 hours)

EMERGENCY PHONE: or (651) (24 hours) Material Safety Data Sheet Copyright, 2009, 3M Company. All rights reserved. Copying and/or downloading of this information for the purpose of properly utilizing 3M products is allowed provided that: (1)

More information

Portable Instrument Application Guide

Portable Instrument Application Guide Portable Instrument Application Guide Which Portable Gas Detector for which Industry/Application Because every life has a purpose... Gas Detection Instruments Advanced Technology Advanced technology employed

More information

EMERGENCY PHONE: or (651) (24 hours)

EMERGENCY PHONE: or (651) (24 hours) Material Safety Data Sheet Copyright, 2004, 3M Company. All rights reserved. Copying and/or downloading of this information for the purpose of properly utilizing 3M products is allowed provided that: (1)

More information

EAGLE 2. 6 Channel Capacity. Inlet fitting. Loud buzzer (95dB) IrDA communication port Low flow shutoff and alarm Alarm LED s with wide visibility

EAGLE 2. 6 Channel Capacity. Inlet fitting. Loud buzzer (95dB) IrDA communication port Low flow shutoff and alarm Alarm LED s with wide visibility EAGLE 2 Inlet fitting Loud buzzer (95dB) IrDA communication port Low flow shutoff and alarm Alarm LED s with wide visibility Internal / external hydrophobic filters Self healing polyurethane protective

More information

The Situation. Modeling Storage Occupancies Under Sloped Ceilings. Concerns (Elevation View) The Concerns 4/29/ NFPA Conference & Expo

The Situation. Modeling Storage Occupancies Under Sloped Ceilings. Concerns (Elevation View) The Concerns 4/29/ NFPA Conference & Expo 2014 NFPA Conference & Expo Modeling Storage Occupancies Under Sloped Ceilings Presented by: Kenneth E. Isman NFSA Victoria B. Valentine NFSA Andre Marshal CSS NFPA 13 defines a sloped ceiling as one where

More information

MultiRAE Lite. Wireless Portable Multi-Gas Monitor

MultiRAE Lite. Wireless Portable Multi-Gas Monitor MultiRAE Lite Wireless Portable Multi-Gas Monitor The MultiRAE Lite is an optimal one-to-six 4 -gas monitoring solution for personal protection (including confined space entry) and multi-gas leak detection

More information

The Combustion Process THE FIRE TETRAHEDRON FUEL TEMPERATURE

The Combustion Process THE FIRE TETRAHEDRON FUEL TEMPERATURE Worldwide Safety Services Fire Extinguisher Training D 1 Objectives Understand the combustion process and different fire classes. Understand d fire extinguisher i types, operating procedures, capabilities,

More information

SP-220. Features. Combustible handheld gas leakage detector

SP-220. Features. Combustible handheld gas leakage detector SP-220 Combustible handheld gas leakage detector The SP-220 gas leakage detector is a simple to operate unit with high sensitivity to a variety of gases. The SC version (SP-220SC) is able to detect super-toxic,

More information

Essentials of Fire Fighting 6 th Edition Firefighter I

Essentials of Fire Fighting 6 th Edition Firefighter I 1 Essentials of Fire Fighting 6 th Edition Firefighter I Chapter 5 Fire Behavior Replace with manual graphic on slide master Learning Objective 1 2 Explain the science of fire as it relates to energy,

More information

2014 NFPA Conference & Expo

2014 NFPA Conference & Expo 2014 NFPA Conference & Expo NFPA Wildland Standards Development: Where We ve Been and Where We re Going Presented by: Ryan Depew NFPA Emergency Services Spc. OVERVIEW NFPA Technical Committees NFPA Wildland

More information

MASTER COURSE OUTLINE

MASTER COURSE OUTLINE A. FIRE 1100 Firefighter I B. COURSE DESCRIPTION: MASTER COURSE OUTLINE This course is designed to cover the necessary skills to perform the basic duties of firefighting including thought processes used

More information

Explosion Venting and Suppression of Bucket Elevator Legs, G90-990

Explosion Venting and Suppression of Bucket Elevator Legs, G90-990 Page 1 of 6 G90-990 Explosion Venting and Suppression of Bucket Elevator Legs Explosion vents and explosion suppression devices limit the danger and damage associated with grain dust explosions. This NebGuide

More information

Hazardous Gas Detection System. [ for Homeland Security ]

Hazardous Gas Detection System. [ for Homeland Security ] Hazardous Gas Detection System [ for Homeland Security ] Chemical Warfare Agent Detector Command Center Meteorological Weather Station Volatile Organic Compounds Monitor Toxic Gas Monitor Visual & Audible

More information

Battery Design Considerations

Battery Design Considerations Battery Design Considerations For general safety, and New York requirements Victoria Carey March 18, 2019 1 SAFER, SMARTER, GREENER DNV GL in Brief 155 350 14,000 2 DNV GL Energy Storage Expertise FEASIBILITY

More information

Operation and Maintenance Manual

Operation and Maintenance Manual Operation and Maintenance Manual GDS-48 Remote Bridge Sensor for Combustible Gases AUTHORIZED DISTRIBUTOR: GasDetectorsUSA.com - Houston, Texas USA sales@gasdetectorsusa.com - 832-615-3588 CAUTION: FOR

More information

Changes to NFPA 101A 2013 Edition for Health Care Facilities

Changes to NFPA 101A 2013 Edition for Health Care Facilities 2017 NFPA Conference & Expo Changes to NFPA 101A 2013 Edition for Health Care Facilities Presented by: William Koffel, P.E, FSFPE Lennon Peake, P.E. Koffel Associates Koffel Associates President Manager

More information

ESD3000 ESD200 Combustible / Toxic Gas Detector

ESD3000 ESD200 Combustible / Toxic Gas Detector ESD3000 ESD200 Combustible / Toxic Gas Detector Combustible and toxic gas leakage inspection instrument in industrial application Ex-proof certificate Exd ⅡC T6 Gb/Ex d ib ⅡC T6 Gb Dust Ex-proof certificate

More information

Using the QRAE Plus personal multigas monitor

Using the QRAE Plus personal multigas monitor Using the QRAE Plus personal multigas monitor Firmware v 1.10 QRAE Plus The Hazardous Environment Detection Company QRAE Plus features Turning on the QRAE Plus Recommended Daily Start-up Procedure User

More information

Sensors for Cell Phones

Sensors for Cell Phones 2021 Miller Drive, Suite B Longmont, CO 80501 www.synkera.com Sensors for Cell Phones SBIR Phase II Sep 25, 2009 to October 14, 2011 July 29th, 2010 Overview About Synkera Synkera Cell Sensor Vision SBIR

More information

INSTRUCTOR GUIDE COURSE: FIREFIGHTER PRE-BASIC SESSION REFERENCE: 1 TOPIC: ORIENTATION AND FIRE BEHAVIOR LEVEL OF INSTRUCTION:

INSTRUCTOR GUIDE COURSE: FIREFIGHTER PRE-BASIC SESSION REFERENCE: 1 TOPIC: ORIENTATION AND FIRE BEHAVIOR LEVEL OF INSTRUCTION: COURSE: FIREFIGHTER PRE-BASIC SESSION REFERENCE: 1 INSTRUCTOR GUIDE TOPIC: ORIENTATION AND FIRE BEHAVIOR LEVEL OF INSTRUCTION: TIME REQUIRED: THREE HOURS MATERIALS: APPROPRIATE AUDIO VISUAL AIDS REFERENCES:

More information

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 12 December 1996 Ref. T4/4.01 GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 1 The Maritime Safety

More information

IRwin. Methane Leak Detector INNOVATIVE METHANE DETECTOR SYSTEM QUALITY ASSURANCE IN THE AUTOMOTIVE INDUSTRY FOR EASY SURVEY OF GAS PIPELINES

IRwin. Methane Leak Detector INNOVATIVE METHANE DETECTOR SYSTEM QUALITY ASSURANCE IN THE AUTOMOTIVE INDUSTRY FOR EASY SURVEY OF GAS PIPELINES IRwin Methane Leak Detector INNOVATIVE METHANE DETECTOR SYSTEM QUALITY ASSURANCE IN THE AUTOMOTIVE INDUSTRY FOR EASY SURVEY OF GAS PIPELINES Innovation is a matter of difference FAST AND EASY GAS PIPELINE

More information

Full Scale Battery Tests

Full Scale Battery Tests Full Scale Battery Tests Aircraft response to fires involving large numbers of small lithium batteries Presented to: ALPA 60 th Air Safety Forum By: Harry Webster, FAA Fire Safety Br. Date: August 6, 2014

More information

3years. Detection of explosive gases, toxic gases and oxygen. Infrared XP IR version. SIL 2 high reliability IP 66.

3years. Detection of explosive gases, toxic gases and oxygen. Infrared XP IR version. SIL 2 high reliability IP 66. Fixed Gas Monitoring Solutions Detection of explosive gases, toxic gases and oxygen Infrared XP IR version SIL 2 high reliability IP 66 E n o r t c e l i c 3years W a r r a t n y Certifications: The Fixed

More information

ALTAIR 5X Multigas Detector Product Specification

ALTAIR 5X Multigas Detector Product Specification ALTAIR 5X Multigas Detector Product Specification PHYSICAL CHARACTERISTICS Gas delivery Size, pumped unit without IR Size, pumped unit with IR Weight Handling Case material Environmental protection Display

More information

Material Safety Data Sheet SECTION 1: PRODUCT AND COMPANY IDENTIFICATION SECTION 2: INGREDIENTS SECTION 3: HAZARDS IDENTIFICATION

Material Safety Data Sheet SECTION 1: PRODUCT AND COMPANY IDENTIFICATION SECTION 2: INGREDIENTS SECTION 3: HAZARDS IDENTIFICATION Material Safety Data Sheet Copyright, 2009, 3M Company. All rights reserved. Copying and/or downloading of this information for the purpose of properly utilizing 3M products is allowed provided that: (1)

More information

Chapter 17 Test. Directions: Write the correct letter on the blank before each question.

Chapter 17 Test. Directions: Write the correct letter on the blank before each question. Chapter 17 Test Name: Date: Directions: Write the correct letter on the blank before each question. Objective 1: Describe initial factors to consider when suppressing structure fires. 1. Which strategy

More information

CENTRAL STATE HOSPITAL PLAN SAFE USE HANDLING AND STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS

CENTRAL STATE HOSPITAL PLAN SAFE USE HANDLING AND STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS Page 1 of 6 CENTRAL STATE HOSPITAL PLAN SUBJECT: SAFE USE HANDLING AND STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS ANNUAL REVIEW MONTH: RESPONSIBLE FOR REVIEW: APRIL CSH SAFETY DIRECTOR LAST REVISION

More information

Aqua Balance. User s Information Manual. WMB-155C Wall Mount Gas-Fired Combination Boiler Heating and Domestic Hot Water

Aqua Balance. User s Information Manual. WMB-155C Wall Mount Gas-Fired Combination Boiler Heating and Domestic Hot Water Aqua Balance WMB-155C Wall Mount Gas-Fired Combination Boiler Heating and Domestic Hot Water User s Information Manual * Low Lead Content If the information in this manual is not followed exactly, a fire

More information

MSA Portable Gas Detection

MSA Portable Gas Detection Because every life has a purpose MSA Portable Gas Detection Marine Chemist Association Seminar 2015 Paul Jung Product Line Manager Portable Instruments Our Mission & Vision Mission to see to it that men

More information

Chapter 12 HOT WORK OPERATIONS. Purpose:

Chapter 12 HOT WORK OPERATIONS. Purpose: Chapter 12 Hot Work Operations Chapter 12 HOT WORK OPERATIONS Purpose: To provide written procedures to prevent the outbreak of fire, fire alarm activations, and smoke and odor migration in buildings resulting

More information

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions Smoke Characterization Study October 29, 2008 Paul E. Patty, P.E. Senior Research Engineer Northbrook, IL 847-664-2752

More information

TECHNICAL NOTE. Response Factors for Flame Ionization Detector Operation FLAME IONIZATION DETECTOR OPERATION BASICS

TECHNICAL NOTE. Response Factors for Flame Ionization Detector Operation FLAME IONIZATION DETECTOR OPERATION BASICS TECHNICAL NOTE s for Flame Ionization Detector Operation FLAME IONIZATION DETECTOR OPERATION BASICS The DataFID and MicroFID II are portable flame ionization detectors designed to monitor volatile organic

More information

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM User Instructions For The Model 5200 Gas Monitor System To completely customize the specifications to your exact application, modifications to the following

More information

HOME FIRE SPRINKLER SYSTEMS. fire safety. the future of. here today

HOME FIRE SPRINKLER SYSTEMS. fire safety. the future of. here today HOME FIRE SPRINKLER SYSTEMS the future of HFSC-FutureBro-17.indd 1 fire safety here today UNDERSTANDING FIRE SPRINKLER PROTECTION FOR HOMES Fire kills more people in the United States annually than all

More information

Model GD Instruction Manual. Combustible Gas Leak Detector. reedinstruments. www. com

Model GD Instruction Manual. Combustible Gas Leak Detector. reedinstruments. www. com Model GD-3300 Combustible Gas Leak Detector Instruction Manual reedinstruments com Introduction The Combustible Gas Leak Detector has a 16 gooseneck probe to find leaks in hard-to-reach areas. It s adjustable

More information

Firefighter Safety in Battery Energy Storage System Fires

Firefighter Safety in Battery Energy Storage System Fires Firefighter Safety in Battery Energy Storage System Fires Erik Archibald, P.E. Kevin Marr, PhD, P.E. NFPA SUPDET November 30, 2018 Core Team O.A. (DK) Ezekoye The University of Texas at Austin UTFRG Casey

More information

GasAlertMicroClip X3 Specifications

GasAlertMicroClip X3 Specifications GasAlertMicroClip X3 Specifications The instrument must satisfy the following: Physical Specifications Size (h x w x d) Physical size shall be no larger than 4.4 x 2.4 x 1.2 in. / 11.3 x 6.0 x 3.2 cm Weight

More information

Second Revision No. 1-NFPA [ Section No. 2.2 ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA [ Section No. 2.2 ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 1410-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 1500, Standard on Fire Department

More information

AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE PV APPLICATIONS CODES AND STANDARDS EMERGENCY RESPONSE

AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE PV APPLICATIONS CODES AND STANDARDS EMERGENCY RESPONSE AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE PV APPLICATIONS CODES AND STANDARDS EMERGENCY RESPONSE We are here to make a choice between the quick and the dead Bernard Baruch, U.N. Atomic Energy

More information

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM First Revision No. 1-NFPA 1403-2015 [ Section No. 1.2.1 ] 1.2.1 The purpose of this standard shall be to provide a process for conducting live fire training evolutions to ensure that they are conducted

More information

Survey of the Burning Behaviour of the Refrigerant HFO-1234yf Brief Report

Survey of the Burning Behaviour of the Refrigerant HFO-1234yf Brief Report D M T G m b H & C o. K G B u i l d i n g S a f e t y Expert Body for Fire Protection Tremoniastraße 13 44137 Dortmund GERMANY Phone +49 231-5333-0 Fax +49 231-5333-299 Emaill: gs@dmt.de http://www.dmt.de

More information

IRwin. Methane Leak Detector INNOVATIVE METHANE DETECTOR SYSTEM QUALITY ASSURANCE IN THE AUTOMOTIVE INDUSTRY FOR EASY SURVEY OF GAS PIPELINES

IRwin. Methane Leak Detector INNOVATIVE METHANE DETECTOR SYSTEM QUALITY ASSURANCE IN THE AUTOMOTIVE INDUSTRY FOR EASY SURVEY OF GAS PIPELINES IRwin Methane Leak Detector INNOVATIVE METHANE DETECTOR SYSTEM QUALITY ASSURANCE IN THE AUTOMOTIVE INDUSTRY FOR EASY SURVEY OF GAS PIPELINES Innovation is a matter of difference INNOVATIVE INSTRUMENT AND

More information

Instructor Guide. Title: Tactical Approach to Chimney Fires. Time Required: 2 hours. Materials: PowerPoint presentation AV equipment

Instructor Guide. Title: Tactical Approach to Chimney Fires. Time Required: 2 hours. Materials: PowerPoint presentation AV equipment Instructor Guide Title: Tactical Approach to Chimney Fires Time Required: 2 hours Materials: PowerPoint presentation AV equipment Requisite Knowledge: Firefighter I Basic knowledge of company SOPs Requisite

More information

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist Andrew Kim and George Crampton Fire Research Program, National Research Council of Canada 1200 Montreal Road, Ottawa, Ontario,

More information

LD910. User Manual. Combustible Gas Leak Detector. Detects all Hydrocarbon and other Combustible Gases. Made in U.S.A. MSHA Approved Intrinsic Safety

LD910. User Manual. Combustible Gas Leak Detector. Detects all Hydrocarbon and other Combustible Gases. Made in U.S.A. MSHA Approved Intrinsic Safety LD910 Combustible Gas Leak Detector Detects all Hydrocarbon and other Combustible Gases User Manual MSHA Approved Intrinsic Safety Made in U.S.A. LeakDetectors-LD910-UserManual.indd 1 INTRODUCTION The

More information

Sirius MultiGas Detector

Sirius MultiGas Detector Sirius MultiGas Detector Operating Manual In North America, to contact your nearest stocking location, dial toll-free 1-800-MSA-2222 To contact MSA International, dial 1-412-967-3354 or 1-800-MSA-7777

More information

OXYGEN. 21% in air. Does not burn - Supports combustion. Increased oxygen will intensify burning

OXYGEN. 21% in air. Does not burn - Supports combustion. Increased oxygen will intensify burning FIRE Rapid self-sustaining oxidation of a fuel and oxygen in the presence of heat usually with the production of heat, light, and combustion byproducts OXYGEN 21% in air Does not burn - Supports combustion

More information

Fire Protection Guidelines for Handling and Storing PRB Coal

Fire Protection Guidelines for Handling and Storing PRB Coal June 3, 2013 Fire Protection Guidelines for Handling and Storing PRB Coal By Edward B. Douberly The Powder River Basin (PRB) Coal Users Group has developed recommended fire-prevention practices/guidelines

More information

Intelligent combined sensor for Air Quality (VOC) + Humidity (rh) + Temperature (T) with analogue outputs, Modbus and LCD display. Features.

Intelligent combined sensor for Air Quality (VOC) + Humidity (rh) + Temperature (T) with analogue outputs, Modbus and LCD display. Features. Features To measure and take control of indoor air quality Three noses in same unit Air Quality (VOC), Humidity (rh) and Temperature (T) Selectable outputs 0-10 Vdc, 4-20 ma or 0-5 Vdc via jumpers on pcb

More information

FIRE AND FIRE FITTING By Mr. Prashant Sansare

FIRE AND FIRE FITTING By Mr. Prashant Sansare FIRE AND FIRE FITTING By Mr. Prashant Sansare What is mean by fire? CASE STUDY What Happened? Late one evening, a large storage tank containing a flammable liquid began to overflow. It was not detected

More information

Detection of explosive gases, toxic gases or oxygen. Infrared XP version. SIL 2 high reliability IP 66. Aluminium or Stainless Steel version

Detection of explosive gases, toxic gases or oxygen. Infrared XP version. SIL 2 high reliability IP 66. Aluminium or Stainless Steel version Fixed Gas Detector Detection of explosive gases, toxic gases or oxygen Infrared XP version SIL 2 high reliability IP 66 Aluminium or Stainless Steel version Certifications Pending The Fixed Gas Detection

More information

incontrol Systems Inc. Flame and Gas Detection

incontrol Systems Inc. Flame and Gas Detection incontrol Systems Inc. Flame and Gas Detection Our flame and gas detectors are globally certified to the latest product approval standards Wherever toxic or combustible gases are part of an industrial

More information

Protecting Special Industrial Hazards with NFPA Codes & Standards

Protecting Special Industrial Hazards with NFPA Codes & Standards 2017 NFPA Conference & Expo Protecting Special Industrial Hazards with NFPA Codes & Standards Different Facilities & Similar Risks Presented by: Bruce H. Clarke, CFPS, UL- CRP Head of Global Property Engineering

More information

An Overview of Extinguishing Systems for Computer Equipment

An Overview of Extinguishing Systems for Computer Equipment Risk Solutions An Overview of Extinguishing Systems for Computer Equipment Various types of automatic suppression systems are available for protecting computer equipment. This report discusses the uses

More information

Gas Detection. - Disposable - Serviceable. Single Gas Detectors

Gas Detection. - Disposable - Serviceable. Single Gas Detectors Gas Detection Single Gas Detectors Introduction Portable single gas detectors are used for personal protection and have the ability to detect a single gas hazard. Typically they are small, lightweight

More information

SAFESITE Multi-Threat Detection System

SAFESITE Multi-Threat Detection System SAFESITE Multi-Threat Detection System The SAFESITE Multi-Threat Detection System simultaneously monitors and wirelessly communicates six potential threats: CWAs, VOCs, TICs, gamma radiation, combustible

More information

Micro IV Operation Manual

Micro IV Operation Manual Micro IV Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS Page Introduction...4 For Your Safety...4 Application and Use...4 General Description...4 Detection Principle...5

More information

Combustible and Toxic Gas Detection Solutions. Performance and Safety Beyond Compliance

Combustible and Toxic Gas Detection Solutions. Performance and Safety Beyond Compliance Combustible and Toxic Gas Detection Solutions Performance and Safety Beyond Compliance Reliable Solutions from Det-Tronics, Your Partner in Safety Trusted Response with the Utmost Confidence Our proven

More information

ALTAIR 5X Multigas Detector

ALTAIR 5X Multigas Detector ALTAIR 5X Multigas Detector With MSA XCell Sensor Technology IT S WHAT S INSIDE THAT COUNTS Now with advanced PID for VOC detection Because every life has a purpose... Save Time, Save Money, Save Lives

More information