Report on Proposals June 2013 NFPA 70

Size: px
Start display at page:

Download "Report on Proposals June 2013 NFPA 70"

Transcription

1 14-1 Log #1170m NEC-P14 Russell LeBlanc, The Peterson School In articles 90 through 830, if the wording is not already there, then add the words (or other structure(s)) after the word BUILDING(S) wherever the intent of the requirement is to also include STRUCTURES as well as buildings. There is a flaw in the NEC. The term "building" is used over 1000 times in the NEC, and in most of the cases the words "or other structure" should follow and apply the same requirements to bridges, billboards, towers, tanks, and other structures that are by definition NOT BUILDINGS. One specific example I can use is section Wiring on Buildings. I believe that this section is also intended to be applied structures, but the wording "or other structures" is not in the heading or the paragraph. There are literally thousands of other instances throughout the code that this same problem exists. This can easily be seen by doing an electronic search for the word "building". In some cases the words "or other structure" (or similar wording) are present, but in the vast majority where the requirements should also be applied to structures other than buildings, the wording is not there. The submitter has not provided specific proposed text for his proposal in accordance with 4.3.3(c) of the Regulations Governing Committee Projects Log #921m NEC-P14 Joe Tedesco, Boston, MA The term "adequate" and "adequately" and "inadequately" and "inadequate" should be replaced with terms that can be properly enforced and understood. Terms are not defined and are considered vague and unenforceable per Table in the NEC Style Manaual. They are all "incorrect" 148 times in the NEC. The submitter has not provided specific proposed text for his proposal in accordance with 4.3.3(c) of the Regulations Governing Committee Projects. 1

2 14-3 Log #2638e NEC-P14 John R. Kovacik, Underwriters Laboratories Inc. Update the references to UL Standards in the Informational Notes as shown below: Equipment enclosed in a case that is capable of withstanding an explosion of a specified gas or vapor that may occur within it and of preventing the ignition of a specified gas or vapor surrounding the enclosure by sparks, flashes, or explosion of the gas or vapor within, and that operates at such an external temperature that a surrounding flammable atmosphere will not be ignited thereby. Informational Note: For further information, see ANSI/UL , For purposes of Articles 500 through 504 and Articles 510 through 516, the following definitions apply. Equipment enclosed in a manner that excludes dusts and does not permit arcs, sparks, or heat otherwise generated or liberated inside of the enclosure to cause ignition of exterior accumulations or atmospheric suspensions of a specified dust on or in the vicinity of the enclosure. Informational Note: For further information on dustignitionproof enclosures, see Type 9 enclosure in ANSI/NEMA ,, and ANSI/UL ,. Informational Note: For further information, see ANSI/UL ,. Informational Note No. 2: Female NPT threaded entries use a modified National Standard Pipe Taper (NPT) thread with thread form per ANSI/ASME B ,. See ANSI/UL ,. A circuit in which any spark or thermal effect is incapable of causing ignition of a mixture of flammable or combustible material in air under prescribed test conditions. Informational Note: Test conditions are described in ANSI/UL ,. For purposes of this article, the following definitions apply. Equipment enclosed in a manner that excludes dusts and does not permit arcs, sparks, or heat otherwise generated or liberated inside of the enclosure to cause ignition of exterior accumulations or atmospheric suspensions of a specified dust on or in the vicinity of the enclosure. Informational Note: For further information on dustignitionproof enclosures, see Type 9 enclosure in ANSI/NEMA ,, and ANSI/UL ,. References to UL Standards in the NEC should reflect the current edition. Accept all amendments to the publication dates of the referenced documents, but do not accept the deletion of "1203" in Informational Note 2 of 500.2(1). The panel notes that the submitter accidentally deleted the document number. 2

3 14-4 Log #1611 NEC-P14 James F. Williams, Fairmont, WV That portion of a property where liquids are received by tank vessel, pipelines, tank car, or tank vehicle and are stored or blended in bulk for the purpose of distributing such liquids by tank vessel, pipeline, tank car, tank vehicle, portable tank, or container. [ ] Informational Note: For further information, see NFPA ,. That portion of a property where liquids are received by tank vessel, pipelines, tank car, or tank vehicle and are stored or blended in bulk for the purpose of distributing such liquids by tank vessel, pipeline, tank car, tank vehicle, portable tank, or container. [ ] Informational Note: For further information, see NFPA ,. The defined term is referenced in several articles of the NEC:,,,,, & In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the. The Tables cited in the submitter s substantiation contain references to Chapter 5 articles. The term bulk plant appears only in Article 515. The present location of the definition is correct. 3

4 14-5 Log #1609 NEC-P14 James F. Williams, Fairmont, WV Equipment with electrical components suitable to be moved only with mechanical aids or is provided with wheels for movement by person(s) or powered devices. Equipment with electrical components suitable to be moved by a single person without mechanical aids Equipment with electrical components suitable to be moved only with mechanical aids or is provided with wheels for movement by person(s) or powered devices. Equipment with electrical components suitable to be moved by a single person without mechanical aids The defined term is referenced in several articles of the NEC:,,,,,,,,,,, (3),,,,,,, (2),, 513.2, & 513.,,, (8),,,,,, (1), (5),,, (6),,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, & In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the. The submitter did not provide substantiation to support the correctness of the proposed definitions. This is not in accordance with 4.3.3(d) of the Regulations Governing Committee Projects. Panel 14 also notes that portable and movable vary from product to product, and are defined in the various product standards. 4

5 14-6 Log #1610 NEC-P14 James F. Williams, Fairmont, WV That portion of a property where motor fuels are stored and dispensed from fixed equipment into the fuel tanks of motor vehicles or marine craft or into approved containers, including all equipment used in connection therewith. [ ] Informational Note: Refer to Articles 510 and 511 with respect to electrical wiring and equipment for other areas used as lubritoriums, service rooms, repair rooms, offices, salesrooms, compressor rooms, and similar locations. That portion of a property where motor fuels are stored and dispensed from fixed equipment into the fuel tanks of motor vehicles or marine craft or into approved containers, including all equipment used in connection therewith. [ ] Informational Note: Refer to Articles 510 and 511 with respect to electrical wiring and equipment for other areas used as lubritoriums, service rooms, repair rooms, offices, salesrooms, compressor rooms, and similar locations. The defined term is referenced in several articles of the NEC:,,,,,,,,,, & In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the. The Tables cited in the submitter s substantiation contain references to Chapter 5 articles. The term motor fuel dispensing facility appears only in Article 514. The present location of the definition is correct Log #2894 NEC-P14 James F. Williams, Fairmont, WV Equipment with electrical components intended to be moved from one place to another. Equipment with electrical components suitable to be moved by a single person without mechanical aids. The defined term is referenced in several articles of the NEC: 100 I Electric Sign, 110, 210, 250, 368, 400, 430, 490, 500, 501, 505, 511, 513, 514, 515, 516, 517, 518, 520, 525, 530, 545, 600, 640, 668, 680 It is defined in 513.2, 520.2, 530.2, 640.2, & Suggest that a single definition in 100 I is better. In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the. The submitter did not provide substantiation to support the correctness of the proposed definition. This is not in accordance with 4.3.3(d) of the Regulations Governing Committee Projects. Panel 14 also notes that the meaning of portable varies from Article to Article. The panel notes that the proposed change in the definition would have unintended and unsubstantiated changes to the application of portable equipment in aircraft hangars. 5

6 14-8 Log #1612 NEC-P14 James F. Williams, Fairmont, WV An enclosure or insert within a larger room used for spray/coating/dipping applications. A spray booth may be fully enclosed or have open front or face and may include separate conveyor entrance and exit. The spray booth is provided with a dedicated ventilation exhaust but may draw supply air from the larger room or have a dedicated air supply. An enclosure or insert within a larger room used for spray/coating/dipping applications. A spray booth may be fully enclosed or have open front or face and may include separate conveyor entrance and exit. The spray booth is provided with a dedicated ventilation exhaust but may draw supply air from the larger room or have a dedicated air supply. The defined term is referenced in several articles of the NEC: (3)(2),, & In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the. The citation of 500.5(B)(3) by the submitter in the substantiation is an Informational Note, not in the Code text. This does not justify moving the definition from Article 516 to Article 100, as Article 516 is the only Article containing provisions for spray booths. 6

7 14-9 Log #1999 NEC-P14 Eliana Brazda, ISA Add new text to read as follows: Electromagnetic radiation at wavelengths in vacuum between the region of transition to X-rays and the region of transition to radio waves, that is approximately between 1 nm and 1,000 ìm. Informational Note: For additional information on types of protection that can be applied to minimize the risk of ignition in explosive gas atmospheres from optical radiation in the wavelength range from 380 nm to 10 µm, see ANSI/ISA TR , Type of protection to minimize the risk of ignition in explosive gas atmospheres from optical radiation where visible or infrared radiation is incapable of producing sufficient energy under normal or specified fault conditions to ignite a specific hazardous atmospheric mixture. Informational Note: See ANSI/ISA TR , Type of protection to minimize the risk of ignition in explosive gas atmospheres from optical radiation where radiation is confined inside optical fibre or other transmission medium under normal constructions or constructions with additional mechanical protection based on the assumption that there is no escape of radiation from the confinement. Informational Note: See ANSI/ISA TR , Type of protection to minimize the risk of ignition in explosive gas atmospheres from optical radiation where radiation is confined inside protected or unprotected optical fibre or other transmission medium with interlock cut-off provided to reliably reduce the unconfined beam strength to safe levels within a specified time. Informational Note: See ANSI/ISA TR , Optical fibre cable protected from releasing optical radiation into the atmosphere during normal operating conditions and foreseeable malfunctions by additional armouring, conduit, cable tray or raceway. Informational Note: See ANSI/ISA TR , The 2011 edition of the NEC does not address the potential for optical radiation to cause ignition in an explosive atmosphere. It does address optical fiber cables, but not from the perspective of the potential to cause ignition. ANSI/ISA-TR ,, contains published US national requirements that address the potential risk of ignition associated with optical radiation in Division classified areas. This ANSI/ISA standard is aligned with harmonized with ANSI/ISA ( ),, and IEC/EN :2006,, for Zone classified areas. ANSI/ISA-TR defines three types of protection that can be applied to address the potential for optical radiation to cause ignition in potentially explosive atmospheres. These types of protection are: 1) inherently safe optical radiation; 2) protected optical radiation; and 3) optical system with interlock. This proposal introduces these types of protection, along with the general term optical radiation and one of the more common applications of optical radiation in explosive atmospheres, protected optical fiber cable. Additional proposals are being submitted to introduce related, supporting text under and It should be noted that the sources of the optical radiation are electrical equipment. Therefore this proposal is necessary for inclusion in the NEC. There is no need to define terms that are not used in the Code. 7

8 14-10 Log #2007 NEC-P14 Eliana Brazda, ISA Dusttight Informational Note: ANSI/ISA , ANSI/ISA , Electrical and Electronic Equipment: ISA-RP , ANSI/ISA ,. Hermetically Sealed Informational Note: ANSI/ISA , ANSI/ISA , Nonincendive Circuit Informational Note: ANSI/ISA , ANSI/ISA , Nonincendive Component Informational Note: ANSI/ISA , ANSI/ISA , Nonincendive Equipment Informational Note: ANSI/ISA ANSI/ISA , Nonincendive Field Wiring Apparatus Informational Note: ANSI/ISA , ANSI/ISA , Remove the ISA standards date of publication to allow application of all appropriate versions. Accept the changes proposed by the submitter, but include the appropriate publication dates of The two references will read: ANSI/ISA , and ANSI/ISA , Paragraph of the Regulations Governing Committee Projects requires dated references to Standards. The current publication dates for ISA and are

9 14-11 Log #1219 NEC-P14 Marcelo M. Hirschler, GBH International Apparatus in which the circuits are not necessarily nonincendive themselves but that affect the energy in nonincendive field wiring circuits and are relied upon to maintain nonincendive energy levels. Associated nonincendive field wiring apparatus may be either of the following: (1) Electrical apparatus that has an alternative type of protection for use in the appropriate hazardous (classified) location (2) Electrical apparatus not so protected that shall not be used in a hazardous (classified) location Associated nonincendive field wiring apparatus has designated associated nonincendive field wiring apparatus connections for nonincendive field wiring apparatus and may also have connections for other electrical apparatus. : Associated nonincendive field wiring apparatus may be either of the following: (1) Electrical apparatus that has an alternative type of protection for use in the appropriate hazardous (classified) location (2) Electrical apparatus not so protected that shall not be used in a hazardous (classified) location The NFPA Manual of Style requires definitions to be in single sentences. The information provided in the subsequent sentences is not really a part of the definition; it is further information that is best placed in an informational note. Paragraph of the NFPA Manual of Style does not require definitions in the form of a single sentence; it requires definitions in the form of a single paragraph unit. The NEC Style Manual does not modify this a Log #CP1411 NEC-P14 Code-Making Panel 14, In replace the current definition of Combustible Dust with the following: Combustible Dust. Dust particles of 500 microns or smaller (material passing a U.S. No. 35 Standard Sieve as defined in ASTM E 11, Standard Specification for Wire Cloth and Sieves for Testing Purposes) are considered to present a dust fire or dust explosion hazard unless determined otherwise. (See ASTM E 1226 or ISO 6184/1). [499:3.3.3] revised. Definition is extracted from NFPA 499 and the definition in the 2012 Edition of NFPA 499 has been 14-11b Log #CP1402 NEC-P14 Code-Making Panel 14, Add a new definition to 500.2, 505.2, and to read: Cord Connector. A fitting intended to terminate a cord to a box or similar device and reduce the strain at points of termination and may include an explosionproof, a dust ignition proof, or a flameproof seal. The existing term "cord connector" has different meanings in other places, which has caused confusion. The inclusion of this definition in these three articles makes it clear as to the meaning of the term as a mechanical device, not as an electrical device, and is based on the product standard ANSI/UL 514B. 9

10 14-12 Log #1220 NEC-P14 Marcelo M. Hirschler, GBH International A component having contacts for making or breaking an incendive circuit and the contacting mechanism is constructed so that the component is incapable of igniting the specified flammable gas air or vapor air mixture. The housing of a nonincendive component is not intended to exclude the flammable atmosphere or contain an explosion. For further information, see ANSI/ISA , : The housing of a nonincendive component is not intended to exclude the flammable atmosphere or contain an explosion. The NFPA Manual of Style requires definitions to be in single sentences. The information provided in the subsequent sentences is not really a part of the definition; it is further information that is best placed in an informational note. Paragraph of the NFPA Manual of Style does not require definitions in the form of a single sentence; it requires definitions in the form of a single paragraph unit. The NEC Style Manual does not modify this Log #1221 NEC-P14 Marcelo M. Hirschler, GBH International Wiring that enters or leaves an equipment enclosure and, under normal operating conditions of the equipment, is not capable, due to arcing or thermal effects, of igniting the flammable gas air, vapor air, or dust air mixture. Normal operation includes opening, shorting, or grounding the field wiring. : Normal operation includes opening, shorting, or grounding the field wiring. The NFPA Manual of Style requires definitions to be in single sentences. The information provided in the subsequent sentences is not really a part of the definition; it is further information that is best placed in an informational note. Paragraph of the NFPA Manual of Style does not require definitions in the form of a single sentence; it requires definitions in the form of a single paragraph unit. The NEC Style Manual does not modify this Log #3186 NEC-P14 Stephen Crimaudo, American Petroleum Institute Replace "1997" date reference to ANSI/API RP500 to "2012" as indicated below. ANSIAPI RP , I, This and the companion proposals propose to update the date references to ANSI/API RP 500. The latest edition of ANSI/API RP 500 has been approved for publication and is expected to be published by API in early The 2012 edition of the referenced document has not been published yet. 10

11 14-15 Log #3187 NEC-P14 Stephen Crimaudo, American Petroleum Institute Replace "1997" date reference to ANSI/API RP500 to "2012" as indicated below., Informational Note No. 4: For further information on ventilation, see NFPA , and API RP This and the companion proposals propose to update the date references to ANSI/API RP 500. The latest edition of ANSI/API RP 500 has been approved for publication and is expected to be published by API in early The 2012 edition of the referenced document has not been published yet a Log #CP1413 NEC-P14 Code-Making Panel 14, Classifications of Locations (A) Classifications of Locations. Locations shall be classified depending on the properties of the flammable gas, flammable liquid-produced vapor, combustible-liquid produced vapors, combustible dusts, or fibers/flyings that may be present, and the likelihood that a flammable or combustible concentration or quantity is present. Where pyrophoric materials are the only materials used or handled, these locations shall not be classified. Each room, section, or area shall be considered individually in determining its classification. Where pyrophoric materials are the only materials used or handled, these locations are outside the scope of this article. The language is being updated to be consistent with current language found in Section 506.5(A) and consistent with the fact that neither NFPA 497 or NFPA 499 currently address the use of pyrophoric materials. 11

12 14-16 Log #265 NEC-P14 Billy Breitkreutz, Fluor Corporation Add an Informational Note No. 3 to read as follows: Informational Note No. 3: Pyrophoric materials should be in containment systems designed to prevent contact between the pyrophoric material and air. The pyrophoric material might escape in very small amounts and combine with air at a level and temperature that would not cause spontaneous combustion. Ignition might be avoided if electrical equipment in the area is suitable for a classified location. Silane (SiH 4 ) is a pyrophoric gas that will not spontaneously ignite when mixed with air at a low level and temperature. Silane must be loaded into containers for transportation using a connection that might leak a very small quantity and mix with air at such a low level and temperature. Code Section 505.5(A) prohibits classification of the area. The Code does not prohibit installation of equipment suitable for a hazardous area in the non-hazardous area. The proposed change will make clear that installation of equipment suitable for a hazardous area in this non-hazardous is a recognized practice. The methods of protection identified in Articles 500, 505, and 506 do not provide a sufficient degree of protection for pyrophoric material. Pyrophoric materials are specifically excluded from the scopes of NFPA 497,., and NFPA 499, Log #2167 NEC-P14 Marcelo M. Hirschler, GBH International ASTM D3175: new date is 2011 Standards update. This is extracted text and cannot be altered by Panel Log #3188 NEC-P14 Stephen Crimaudo, American Petroleum Institute Change "ignition temperature" to "autoignition temperature". API RP 500, API RP 505, NFPA 497 and NFPA 499 define the term "Autoignition Temperature" or (AlT). The term "ignition temperature" is often used synonymously with autoignition temperature, but sometimes incorrectly. This proposal, along with its companion proposals, attempt to promote consistency of the terms between the standards. The term "autoignition temperature" is used when referring to the material property of flammable liquids and vapors, which is consistent with how the term is used in NFPA 497. The term "ignition temperature" is used when referring to the material property of combustible dusts, which is consistent with how the term is used in NFPA

13 14-19 Log #2689 NEC-P14 Jeremy Neagle, US Bureau of Alcohol, Tobacco, Firearms & Explosives Informational Note No. 3: Certain dusts may require additional precautions due to chemical phenomena that can result in the generation of ignitible gases. See ANSI/IEEE C ,, Section 127A, Coal Handling Areas. IEEE is the organization responsible for the development of the National Electrical Safety Code. The current edition is This document is referenced in various sections throughout the NEC as either ANSI C2 or ANSI/IEEE C2. I suggest the NEC Technical Correlating Committee review these sections (110.31, , 225.1, , , , , , 500.6, , , , , ) and update as appropriate. 13

14 14-20 Log #2000 NEC-P14 Eliana Brazda, ISA Add new text to read as follows: This protection technique shall be permitted for equipment in Class I, Division 1 or 2 locations, for which it is identified. The identified Division depends upon the number of faults applied as part of the protection technique evaluation. This protection technique shall be permitted for equipment in Class I, Division 1 or 2 locations, for which it is identified. The identified Division depends upon whether or not additional mechanical protection is provided as part of the protection technique evaluation. This protection technique shall be permitted for equipment in Class I, Division 1 or 2 locations, for which it is identified. The identified Division depends upon the confinement construction and upon the shut-down time in which the unconfined beam strength is reliably reduced to safe levels. The 2011 edition of the NEC does not address the potential for optical radiation to cause ignition in an explosive atmosphere. It does address optical fiber cables, but not from the perspective of the potential to cause ignition. ANSI/ISA-TR ,, contain published US national requirements that address the potential risk of ignition associated with optical radiation in Division classified areas. This ANSI/ISA standard is aligned with harmonized with ANSI/ISA ( ),, and IEC/EN :2006,, for Zone classified areas. ANSI/ISA-TR defines three types of protection that can be applied to address the potential for optical radiation to cause ignition in potentially explosive atmospheres. These types of protection are: 1) inherently safe optical radiation; 2) protected optical radiation; and 3) optical system with interlock. This proposal introduces these types of protection, along with the general term optical radiation and one of the more common applications of optical radiation in explosive atmospheres, protected optical fiber cable. Additional proposals are being submitted to introduce related, supporting text under and It should be noted that the sources of the optical radiation are electrical equipment. Therefore this proposal is necessary for inclusion in the NEC. The technical report referenced in the substantiation does not establish that the testing criteria provided are indicative of typical installations in hazardous (classified) locations and there is no evidence that existing equipment in use should be tested to these additional standards. 14

15 14-21 Log #1171 NEC-P14 Jon D. Miller, Detector Electronics Corp. Change the text to the following : (1) Inadequate Ventilation. In a Class I, Division 1 location that is so classified due to inadequate ventilation, electrical equipment suitable for Class I, Division 2 locations shall be permitted. Combustible gas detection equipment shall be listed for Class I, Division 1, for the appropriate material group, and for the detection of the specific gas or vapor to be encountered for which it is intended. ( 2) Interior of a Building. In a building located in, or with an opening into, a Class I, Division 2 location where the interior does not contain a source of flammable gas or vapor, electrical equipment for unclassified locations shall be permitted. Combustible gas detection equipment shall be listed for Class I, Division 1 or Class I, Division 2, for the appropriate material group, and for the detection of the specific gas or vapor to be encountered for which it is intended. ( 3) Interior of a Control Panel. In the interior of a control panel containing instrumentation utilizing or measuring flammable liquids, J gases, or vapors, electrical equipment suitable for Class I, Division 2 locations shall be permitted. Combustible gas detection equipment shall be listed for Class I, Division 1, for the appropriate material group, and for the detection of the specific gas or vapor to be encountered for which it is intended. The listing of the gas detector would include the gasses or vapors for which the detector is intended (not "encountered"). A Methane gas detector encounters Nitrogen (within air), but the Methane gas detector is not listed for Nitrogen. Gas detection equipment can be intended to detect, for example, a noncombustible gas or a combustible gas other than the one to be encountered, and that would not fulfill the requirements of using gas detection as a method of protection Log #3189 NEC-P14 Stephen Crimaudo, American Petroleum Institute Change "ignition temperature" to "autoignition temperature". API RP 500, API RP 505, NFPA 497 and NFPA 499 define the term "Autoignition Temperature" or (AlT). The term "ignition temperature" is often used synonymously with autoignition temperature, but sometimes incorrectly. This proposal, along with its companion proposals, attempt to promote consistency of the terms between the standards. The term "autoignition temperature" is used when referring to the material property of flammable liquids and vapors, which is consistent with how the term is used in NFPA 497. The term "ignition temperature" is used when referring to the material property of combustible dusts, which is consistent with how the term is used in NFPA 499. The more general term "ignition temperature" is appropriate here, since this section addresses gases, vapors, dusts, and fibers/flyings. 15

16 14-23 Log #3190 NEC-P14 Stephen Crimaudo, American Petroleum Institute Change "ignition temperature" to "autoignition temperature". API RP 500, API RP 505, NFPA 497 and NFPA 499 define the term "Autoignition Temperature" or (AlT). The term "ignition temperature" is often used synonymously with autoignition temperature, but sometimes incorrectly. This proposal, along with its companion proposals, attempt to promote consistency of the terms between the standards. The term "autoignition temperature" is used when referring to the material property of flammable liquids and vapors, which is consistent with how the term is used in NFPA 497. The term "ignition temperature" is used when referring to the material property of combustible dusts, which is consistent with how the term is used in NFPA Log #2056 NEC-P14 Edward M. Briesch, Underwriters Laboratories Inc. The marking shall specify the temperature class or operating temperature at a 40 C ambient temperature, or at the higher ambient temperature if the equipment is rated and marked for an ambient temperature of greater than 40 C. For equipment installed in a Class II, Division 1location, the temperature class or operating temperature shall be based on operation of the equipment when blanketed with dust. The temperature class, if provided, shall be indicated using the temperature class (T Codes) shown in Table 500.8(C). Equipment for Class I and Class II shall be marked with the maximum safe operating temperature, as determined by simultaneous exposure to the combinations of Class I and Class II conditions. The current text is not clear as to if this temperature is based on operation of the equipment in free air or when the equipment is blanketed with dust. In a Class II, Division 1 location, it would be expected that a dust blanket could exist under normal operating conditions. Equipment temperatures under a dust blanket will be considerably higher than in free air due to the insulating effect of the dust blanket and may very well exceed the ignition temperature of the dust when in free air they would not. The ANSI standards for the equipment, ANSI/UL1203 for example, require the temperature be determined with a dust blanket. The marking shall specify the temperature class or operating temperature at a 40 C ambient temperature, or at the higher ambient temperature if the equipment is rated and marked for an ambient temperature of greater than 40 C. For equipment installed in a Class II, Division 1 location, the temperature class or operating temperature shall be based on operation of the equipment when blanketed with the maximum amount of dust that can accumulate on the equipment. The temperature class, if provided, shall be indicated using the temperature class (T Codes) shown in Table 500.8(C). Equipment for Class I and Class II shall be marked with the maximum safe operating temperature, as determined by simultaneous exposure to the combinations of Class I and Class II conditions. The proposed text has been amended to provide a quantifiable measure of a blanket of dust. 16

17 14-25 Log #3191 NEC-P14 Stephen Crimaudo, American Petroleum Institute Change "ignition temperature" to "autoignition temperature". API RP 500, API RP 505, NFPA 497 and NFPA 499 define the term "Autoignition Temperature" or (AlT). The term "ignition temperature" is often used synonymously with autoignition temperature, but sometimes incorrectly. This proposal, along with its companion proposals, attempt to promote consistency of the terms between the standards. The term "autoignition temperature" is used when referring to the material property of flammable liquids and vapors, which is consistent with how the term is used in NFPA 497. The term "ignition temperature" is used when referring to the material property of combustible dusts, which is consistent with how the term is used in NFPA Log #3192 NEC-P14 Stephen Crimaudo, American Petroleum Institute Change "ignition temperature" to "autoignition temperature". API RP 500, API RP 505, NFPA 497 and NFPA 499 define the term "Autoignition Temperature" or (AlT). The term "ignition temperature" is often used synonymously with autoignition temperature, but sometimes incorrectly. This proposal, along with its companion proposals, attempt to promote consistency of the terms between the standards. The term "autoignition temperature" is used when referring to the material property of flammable liquids and vapors, which is consistent with how the term is used in NFPA 497. The term "ignition temperature" is used when referring to the material property of combustible dusts, which is consistent with how the term is used in NFPA

18 14-27 Log #56 NEC-P14 Richard A. Janoski, Finleyville, PA (1) For equipment provided with threaded entries for NPT threaded conduit or fittings, listed conduit, listed conduit fittings, or listed cable fittings shall be used. As 500.8(E)(1) is presented in the 2008 NEC, a grammatical error leaves the conduit fittings and the cable fittings without a rule that requires them to be listed. The word listed is only preceding the word conduit, therefore it only applies to the conduit. The addition of the word listed preceding the conduit fittings, and the cable fittings will add the necessary listing requirement. This will also provide continuity between the proposed text for 500.8(E)(1) and 500.8(E)(2). 18

19 14-28 Log #2467 NEC-P14 Donald W. Ankele, Underwriters Laboratories Inc. Metric threaded entries into explosionproof equipment shall have a class of fit of at least 6g/6H and shall be madeup with at least five threads fully engaged for Group C and Group D, and at least eight threads fully engaged for Group A and Group B. and thread engagement as shown in Table 500.8(E)(3). *** Insert Table 500.9(E)(3) here*** Revise the class of fit to align with the requirements in ANSI standards for explosionproof equipment and to provide gauging requirements for field tapping of entries into unlisted equipment. standards. The panel has determined that it would be best to address this issue in the individual product 19

20 14-29 Log #2370 NEC-P14 James F. Williams, Fairmont, WV Add text to read as follows: (a) (6) In industrial establishments with restricted public access, where the conditions of maintenance and supervision ensure that only qualified persons service the installation and where metallic conduit (RMC) does not provide sufficient corrosion resistance, listed reinforced thermosetting resin conduit (RTRC), factory elbows, and associated fittings, all marked with the suffix -XW, and Schedule 80 PVC conduit, factory elbows, and associated fittings shall be permitted. Where seals are required for boundary conditions as defined in (A)(4), the Division 1 wiring method shall extend into the Division 2 area to the seal, which shall be located on the Division 2 side of the Division 1 Division 2 boundary. In each conduit run passing from a Class I, Division 2 location into an unclassified location. The sealing fitting shall be permitted on either side of the boundary of such location within 3.05 m (10 ft) of the boundary. Rigid metal conduit (RMC) or threaded steel intermediate metal conduit shall be used between the sealing fitting and the point at which the conduit leaves the Division 2 location, and a threaded connection shall be used at the sealing fitting. Except for listed reducers at the conduit seal, there shall be no union, coupling, box, or fitting between the conduit seal and the point at which the conduit leaves the Division 2 location. Conduits shall be sealed to minimize the amount of gas or vapor within the Division 2 portion of the conduit from being communicated to the conduit beyond the seal. Such seals shall not be required to be explosion-proof but shall be identified for the purpose of minimizing passage of gases under normal operating conditions and shall be accessible. The cross-sectional area of the conductors permitted in a seal shall not exceed 25 percent of the cross-sectional area of a rigid metal conduit (RMC) of the same trade size unless it is specifically identified for a higher percentage of fill. Pendant luminaires shall be suspended by and supplied through threaded rigid metal conduit (RMC) stems or threaded steel intermediate conduit stems, and threaded joints shall be provided with set-screws or other effective means to prevent loosening. For stems longer than 300 mm (12 in.), permanent and effective bracing 20

21 against lateral displacement shall be provided at a level not more than 300 mm (12 in.) above the lower end of the stem, or flexibility in the form of a fitting or flexible connector identified for the Class I, Division 1 location shall be provided not more than 300 mm (12 in.) from the point of attachment to the supporting box or fitting. Pendant luminaires shall be suspended by threaded rigid metal conduit (RMC) stems, threaded steel intermediate metal conduit stems, or other approved means. For rigid stems longer than 300 mm (12 in.), permanent and effective bracing against lateral displacement shall be provided at a level not more than 300 mm (12 in.) above the lower end of the stem, or flexibility in the form of an identified fitting or flexible connector shall be provided not more than 300 mm (12 in.) from the point of attachment to the supporting box or fitting. "Rigid Metal Conduit" is also referred to as RMC Metallic Conduit Suggest that "RMC" be added to all references. This will make finding all references to "Rigid Metal Conduit" easier and more reliable. There was no technical substantiation provided with the proposal to justify the insertion of the acronym in each location within this article where the wiring method is used. Section of the NEC Style Manual permits, but does not require, an acronym to be used within an article. Adding the acronym to the wiring method does not increase usability or reliability. 21

22 14-30 Log #2398 NEC-P14 James F. Williams, Fairmont, WV Add text to read as follows: (a) (6) In industrial establishments with restricted public access, where the conditions of maintenance and supervision ensure that only qualified persons service the installation and where metallic conduit (IMC) does not provide sufficient corrosion resistance, listed reinforced thermosetting resin conduit (RTRC), factory elbows, and associated fittings, all marked with the suffix -XW, and Schedule 80 PVC conduit, factory elbows, and associated fittings shall be permitted. Where seals are required for boundary conditions as defined in (A)(4), the Division 1 wiring method shall extend into the Division 2 area to the seal, which shall be located on the Division 2 side of the Division 1 Division 2 boundary. In each conduit run passing from a Class I, Division 2 location into an unclassified location. The sealing fitting shall be permitted on either side of the boundary of such location within 3.05 m (10 ft) of the boundary. Rigid metal conduit or threaded steel intermediate metal conduit (IMC) shall be used between the sealing fitting and the point at which the conduit leaves the Division 2 location, and a threaded connection shall be used at the sealing fitting. Except for listed reducers at the conduit seal, there shall be no union, coupling, box, or fitting between the conduit seal and the point at which the conduit leaves the Division 2 location. Conduits shall be sealed to minimize the amount of gas or vapor within the Division 2 portion of the conduit from being communicated to the conduit beyond the seal. Such seals shall not be required to be explosion-proof but shall be identified for the purpose of minimizing passage of gases under normal operating conditions and shall be accessible. Pendant luminaires shall be suspended by and supplied through threaded rigid metal conduit stems or threaded steel intermediate conduit (IMC) stems, and threaded joints shall be provided with set-screws or other effective means to prevent loosening. For stems longer than 300 mm (12 in.), permanent and effective bracing against lateral displacement shall be provided at a level not more than 300 mm (12 in.) above the lower end of the stem, or flexibility in the form of a fitting or flexible connector identified for the Class I, Division 1 location shall be provided not more than 300 mm (12 in.) from the point of attachment to the supporting box or fitting. 22

23 Pendant luminaires shall be suspended by threaded rigid metal conduit stems, threaded steel intermediate metal conduit (IMC) stems, or other approved means. For rigid stems longer than 300 mm (12 in.), permanent and effective bracing against lateral displacement shall be provided at a level not more than 300 mm (12 in.) above the lower end of the stem, or flexibility in the form of an identified fitting or flexible connector shall be provided not more than 300 mm (12 in.) from the point of attachment to the supporting box or fitting. "Intermediate Metal Conduit" is also referred to as IMC Metallic Conduit Suggest that "IMC" be added to all references. This will make finding all references to Intermediate Metal Conduit" easier and more reliable. See panel action and statement on Proposal

24 14-31 Log #2468 NEC-P14 Donald W. Ankele, Underwriters Laboratories Inc. Wiring methods shall comply with (A) or (B). (a) In Class I, Division 1 locations, the wiring methods in (a) through (d) shall be permitted. (b) Type MI cable shall be installed and supported in a manner to avoid tensile stress at the termination fittings. (c) where the conditions of maintenance and supervision ensure that only qualified persons service the installation, Type MC-HL cable listed for use in Class I, Zone 1 or Division 1 locations, with a gas/vaportight continuous corrugated metallic sheath, an overall jacket of suitable polymeric material, and a separate equipment grounding conductor(s) in accordance with , and terminated with fittings listed for the application. Type MC-HL cable shall be installed in accordance with the provisions of Article 330, Part II. (d) where the conditions of maintenance and supervision ensure that only qualified persons service the installation, Type ITC-HL cable listed for use in Class I, Zone 1 or Division 1 locations, with a gas/vaportight continuous corrugated metallic sheath and an overall jacket of suitable polymeric material, and terminated with fittings listed for the application, and installed in accordance with the provisions of Article 727. Informational Note: For further information on construction, testing and marking of cables, cable fittings, and cord connectors, see UL 2225,. Where necessary to employ flexible connections, as at motor terminals, flexible fittings listed for the location, or flexible cord in accordance with the provisions of terminated with cord connectors listed for the location, shall be permitted. Informational Note: For further information on construction, testing and marking of cables, cable fittings, and cord connectors, see UL 2225,. All boxes and fittings shall be approved for Class I, Division 1. In Class I, Division 2 locations, the following wiring methods shall be permitted: (1) All wiring methods permitted in (A). (2) Enclosed gasketed busways and enclosed gasketed wireways. (3) Type PLTC and Type PLTC-ER cable in accordance with the provisions of Article 725, including installation in cable tray systems. The cable shall be terminated with listed fittings. (4) Type ITC and Type ITC-ER cable as permitted in and terminated with listed fittings. (5) Type MC, MV, or TC cable, including installation in cable tray systems. The cable shall be terminated with listed fittings. where the conditions of maintenance and supervision ensure that only qualified persons service the installation and where metallic conduit does not provide sufficient corrosion resistance, listed reinforced thermosetting resin conduit (RTRC), factory elbows, and associated fittings, all marked with the suffix -XW, and Schedule 80 PVC conduit, factory elbows, and associated fittings shall be permitted. Where seals are required for boundary conditions as defined in (A)(4), the Division 1 wiring method shall extend into the Division 2 area to the seal, which shall be located on the Division 2 side of the Division 1 Division 2 boundary. 24

25 (2) Flexible Connections. Where provision must be made for limited flexibility, one or more of the following shall be permitted: (1) Listed flexible metal fittings. (2) Flexible metal conduit with listed fittings. (3) Liquidtight flexible metal conduit with listed fittings. (4) Liquidtight flexible nonmetallic conduit with listed fittings. (5) Flexible cord listed for extra-hard usage and terminated with listed fittings. A conductor for use as an equipment grounding conductor shall be included in the flexible cord. Informational Note 1: See (B) for grounding requirements where flexible conduit is used. Revise to add an Informational Note regarding the requirements for cables, cable fittings and cord connectors. There have been several instances of confusion regarding these Code requirements with respect to termination of cables with cable fittings. Accept the addition of two informational notes as follows: Informational Note: For entry into enclosures required to be explosionproof, see further information on construction, testing and marking of cables, explosionproof cable fittings, and explosionproof cord connectors in ANSI/UL , Cables and Cable-Fittings for Use in Hazardous (Classified) Locations. The first addition is intended to follow (A)(3) and the second is intended to follow (B)(4). The text was amended to clarify when the informational note is relevant and relocated to the appropriate sections. The title of the referenced document has been corrected to indicate ANSI approval and the publication date has been added, in accordance with Paragraph of the Regulations Governing Committee Projects Log #2607 NEC-P14 Richard A. Holub, The DuPont Company, Inc. Add new text to read as follows: (e) Fiber Optic cables of the types OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, and OFC shall be permitted to be installed in raceways as stated in (A). These Fiber Optic cables shall be sealed in accordance with These proposals are a result of an ad-hoc task team consisting of members of CMP3, CMP14, and CMP16, along with industry representatives. Members of this task team included Rich Holub, Dave Wechsler, Bob Potter, Bob Walsh, Harry Ohde, Terry Coleman, and Will Miller. Section 770.3(A) currently permits the use of Fiber Optic cables in hazardous (classified) locations if sealed in accordance with Sections , , , and This proposal adds the requirements in Chapter 5 for correlation as Chapter 7 is not allowed to modify Chapter 5, per Section Similar proposals are submitted for Articles 502, 505, and 506 accordingly. 25

26 14-33 Log #2962 NEC-P14 Robert L. Seitz, Artech Engineering Modify existing text. (1) General. In Class I, Division 1 locations, the wiring methods in (a) through (d)(e) shall be permitted. Add new text. (e) In industrial establishments with restricted public access, where the conditions of maintenance and supervision ensure that only qualified persons service the installation, and where the cable is not subject to physical damage,shipboard Cable with braided metallic armor, that complies with the crush and impact requirements of Type MC-HL cable and is identified for such use with the marking, a separate equipment grounding conductor(s) in accordance with , and terminated with fittings listed for the application. Braided armor Shipboard cable, shall be installed in accordance with the provisions for TC-ER cable found in Article336. Power cables of smaller conductor size, shielded pairs and triads and control cables with small number of conductors are often connected to devices that must be removed or moved to permit maintenance activities to be performed, or for alterations to process piping. A cable that has greater flexibility than MC-HL would benefit this activity as the MC-HL cable cannot be moved out of the way of the work area sufficiently, so is generally subject to damage by the work effort that take place. A more flexible cable installed in small size wire basket tray can be moved further out of the way than can conduit or MC-HL installation. Line (pipe) mounted devices are subject to movement as pipes expand and contract with temperature changes and to vibration caused by pumps and flow through the lines, so flexibility better than that provided by MC-HL cable or MI cable is needed. NEC (B) requires MC (thus MC-HL) cable to be supported within 12 inches of cable termination when cable has 4 or fewer conductors no larger than 10awg, which is often very difficult to provide support at line mounted devices. While extra hard usage cord is permitted where flexible connection is required, the extra hard usage cord is not available in configurations with shielded pairs or triads or for controls connections to valves and other devices. So a flexible cable type is necessary that will satisfy the needs for instrumentation and control. MC-HL has severe requirements imposed as it can be installed outside of cable tray, and as not continuously supported. If braided armor Shipboard cable is installed, generally, in cable tray and otherwise continuously supported, with up to 6 ft unsupported between cable tray and utilization equipment it would be well protected for its length and exposed no more than would extra hard usage cord. Permitting braided armor Shipboard cable would not decrease the safety of Class I, Zone 1 electrical installations and would enhance the maintainability, simply some installations, reduce risk of damage to cables during work around within the facilities where it is used. Braided armor shipboard cable is not a wiring method that is permitted in Chapter 3. The substantiation identifies cable of smaller conductor size, but the proposed language does not limit the conductor size. The wording of the proposal is confusing with respect to marking. The substantiation references Zone 1 locations, yet the proposed wording is for Division 1 locations. Panel 14 recommends a multi-panel task group, to include Panel 6 and/or Panel 7, to address the submitter's concerns. 26

AGENDA. NEC Code-Making Panel 14. Report on Proposal Meeting. January 16-21, Hilton Head, SC

AGENDA. NEC Code-Making Panel 14. Report on Proposal Meeting. January 16-21, Hilton Head, SC National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NEC Code-Making Panel 14 Report on Proposal Meeting January 16-21,

More information

Report on Proposals June 2013 NFPA 70

Report on Proposals June 2013 NFPA 70 14-1 Log #1170m NEC-P14 Russell LeBlanc, The Peterson School In articles 90 through 830, if the wording is not already there, then add the words (or other structure(s)) after the word BUILDING(S) wherever

More information

AGENDA. NEC Code-Making Panel 14. Report on Comment Meeting. November 28-December 1, Redondo Beach, CA

AGENDA. NEC Code-Making Panel 14. Report on Comment Meeting. November 28-December 1, Redondo Beach, CA National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NEC Code-Making Panel 14 Report on Comment Meeting November 28-December

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 14 FROM: Kimberly Shea DATE:

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 14 From: Kimberly Shea, Project Administrator

More information

ORDINANCE NO

ORDINANCE NO ORDINANCE NO. 2017-08-031 AN ORDINANCE OF THE CITY OF LANCASTER, TEXAS, REPEALING THE NATIONAL ELECTRICAL CODE 2014 EDITION IN ITS ENTIRETY AND REPLACING IT WITH THE ADOPTION OF THE NATIONAL ELECTRICAL

More information

Report on Proposals June 2010 NFPA 70

Report on Proposals June 2010 NFPA 70 16-1 Log #4917o NEC-P16 Caleb M. Ferris, Chadwick Electric Add a diagram table after the scope of each article similar to the one in Article 430. For NEC user cost make the table layout diagram in 430.8

More information

CODE DIGEST CODE DIGEST. Solutions.Worldwide.TM Crouse-Hinds is a registered trademark of Cooper Industries, Inc. COOPER CROUSE-HINDS

CODE DIGEST CODE DIGEST. Solutions.Worldwide.TM Crouse-Hinds is a registered trademark of Cooper Industries, Inc. COOPER CROUSE-HINDS COOPER CROUSE-HINDS COOPER CROUSE-HINDS CODE DIGEST CODE DIGEST Article 500-516 of the National Electrical Code with product recommendations for use in hazardous (classified) areas. Distributed by: For

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin February 2014 CEC-18 [rev-11] Page 1 of 9 CANADIAN ELECTRICAL CODE SUBJECT: Section 18 Hazardous Locations Rule 18-006 Division of Class I Locations General For classification

More information

Overview of Hazardous Locations as They Relate to Solenoid Valves

Overview of Hazardous Locations as They Relate to Solenoid Valves Overview of Hazardous Locations as They Relate to Solenoid Valves Defined: Hazardous Location - "where fire or explosion hazards may exist due to flammable gases or vapors, flammable liquids, combustible

More information

August Process Industry Practices Electrical. PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification

August Process Industry Practices Electrical. PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification Electrical Engineering Guide for Determining Electrical Area Classification PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice

More information

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ] 8 of 93 11/6/2015 7:41 AM Public Input No. 52-NFPA 30-2015 [ Section No. 21.2 [Excluding any Sub-Sections] ] For the purpose of this chapter, the term in this section shall have the definitions given.

More information

First Revision No. 1-NFPA [ Chapter 2 ]

First Revision No. 1-NFPA [ Chapter 2 ] First Revision No. 1-NFPA 499-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this recommended practice

More information

NEC 2017 Changes and Their Effect Upon the ICT Industry

NEC 2017 Changes and Their Effect Upon the ICT Industry NEC 2017 Changes and Their Effect Upon the ICT Industry Today s Presenters John Kacperski, RCDD, OSP, CDT Chair of BICSI Standards BICSI Representative on NFPA 70-CMP 16 Richard S. Anderson, RCDD, CDT,

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin October 2007 Page 1 of 11 CANADIAN ELECTRICAL CODE SUBJECT: Section 18 Hazardous Locations Rule 18-006 Division of Class I Locations General For classification requirements

More information

PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification

PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification September 2016 Electrical PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry

More information

Products Solutions Services CT287. Hazardous Area Classifications and Protection Systems

Products Solutions Services CT287. Hazardous Area Classifications and Protection Systems Products Solutions Services CT287 Hazardous Area Classifications and Protection Systems Slide 1 Topics covered Types of Hazardous Area classifications with focus on North America Types of hazardous protection

More information

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 496-2014 [ Section No. 5.2.2 ] 5.2.2 Where When the enclosure has been opened or if the protective gas supply has failed to maintain the required positive pressure, the enclosure

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin June 2018 CEC-18 [rev-13] Page 1 of 6 CANADIAN ELECTRICAL CODE SUBJECT: Section 18 Hazardous locations Rule 18-006 Locations containing an explosive gas atmosphere

More information

Electrical Area Classification 101 An Introduction to Area Classification the Basics IEEE Houston CED

Electrical Area Classification 101 An Introduction to Area Classification the Basics IEEE Houston CED Electrical Area Classification 101 An Introduction to Area Classification the Basics IEEE Houston CED October 3rd, 2017 Vincent W. Wedelich, PE, MBA Project Manager Associate Electrical Engineer 10 Years

More information

HAZARDOUS AREA CLASSIFICATION AND SELECTION OF EQUIPMENT FOR SAFE USE THEREIN FROM AN ELECTRICAL VIEWPOINT

HAZARDOUS AREA CLASSIFICATION AND SELECTION OF EQUIPMENT FOR SAFE USE THEREIN FROM AN ELECTRICAL VIEWPOINT HAZARDOUS AREA CLASSIFICATION AND SELECTION OF EQUIPMENT FOR SAFE USE THEREIN FROM AN ELECTRICAL VIEWPOINT Olof Bekker Pr. Eng. BSc. Eng. BML S.MSAIEE, M.NACE Engineering Manager, Electrical COMMITMENT

More information

Fee $15 Course: NEC Changes 5 This course is valid for these credentials: Credential Description Cred Code Credit Hours

Fee $15 Course: NEC Changes 5 This course is valid for these credentials: Credential Description Cred Code Credit Hours www.garyklinka.com Page 1 of 9 Instructions: Fee $15 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

Electrical Safety Requirements

Electrical Safety Requirements Electrical Safety Requirements Purpose This document defines the minimum required control measures to reduce the risk of injury or illness related to electricity. Scope Applicable to all Coca-Cola system

More information

Second Revision No. 601 NFPA [ Section No [Excluding

Second Revision No. 601 NFPA [ Section No [Excluding Second Revision No. 601 NFPA 70 2015 [ Section No. 300.4 [Excluding any Sub Sections] ] Where subject to physical damage, conductors, raceways, and cables shall be protected. Informational Note: Minor

More information

Chapter 1 General... 5

Chapter 1 General... 5 About This Textbook...xi About the National Electrical Code...xv About the Authors and Illustrator...xix About the Team...xxi Article 90 Introduction to the National Electrical Code... 1 90.1 Purpose of

More information

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51 TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

ARTICLE 25. FUEL GAS CODE

ARTICLE 25. FUEL GAS CODE ARTICLE 25. Rule 1. Indiana Fuel Gas Code, 2003 Edition (Repealed) (Repealed by Fire Prevention and Building Safety Commission; filed Mar 18, 2008, 2:32 p.m.: 20080423-IR-675070479FRA, eff 90 days after

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Hot Work Operations

More information

Get it Right the First Time Avoid These Commonly Cited Errors

Get it Right the First Time Avoid These Commonly Cited Errors May 2014 Get it Right the First Time Avoid These Commonly Cited Errors By Mark Earley and Mark Hilbert Copyright 2014 National Fire Protection Association. All rights reserved. Good electrical contractors

More information

IDENTIFYING TRAY CABLES FOR YOUR NEXT INSTALLATION A WHITE PAPER

IDENTIFYING TRAY CABLES FOR YOUR NEXT INSTALLATION A WHITE PAPER IDENTIFYING TRAY CABLES FOR YOUR NEXT INSTALLATION A WHITE PAPER Published 3/23/2012 T hough rapidly increasing in popularity, tray cables are still a point of confusion for many. While the term tray cable

More information

Committee on NFPA 51A

Committee on NFPA 51A Committee on M E M O R A N D U M TO: FROM: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant DATE: May 6, 2010 SUBJECT: ROC Letter Ballot The ROC letter ballot

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

NFPA 33 Standard for Spray Applica4on Using Flammable or Combus4ble Materials

NFPA 33 Standard for Spray Applica4on Using Flammable or Combus4ble Materials NFPA 33 Standard for Spray Applica4on Using Flammable or Combus4ble Materials Fire Preven4on Officers Associa4on of Bri4sh Columbia 2013 Annual Seminar Kelowna, Bri4sh Columbia May 9, 2013 NFPA 33 Scope

More information

Approval Standard for Electrical Equipment for Use in Hazardous (Classified) Locations - General Requirements

Approval Standard for Electrical Equipment for Use in Hazardous (Classified) Locations - General Requirements Approval Standard for Electrical Equipment for Use in Hazardous (Classified) Locations - General Requirements Class Number 3600 December 2011 2011 FM Approvals LLC. All rights reserved. Foreword The FM

More information

Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on

Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on This list represents the membership at the time the Committee was balloted on the text of this edition. Since that time, changes

More information

Introduction to Hazardous Electrical Location Classifications

Introduction to Hazardous Electrical Location Classifications Introduction to Hazardous Electrical Location Classifications Introduction In North America the target audience for this white paper and the electrical code classification ratings for various types of

More information

Smoke detection in hazardous areas:

Smoke detection in hazardous areas: WHITE PAPER Smoke detection in hazardous areas: What you need to know Smoke detection in hazardous areas requires detectors that operate effectively and safely in explosive environments. Having the correct

More information

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM of 28 11/18/2016 2:25 PM First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] 1.6 Units and Formulas. 1.6.1 The units of measure in this standard are presented first in U.S. customary units (inch-pound

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,

More information

Approval Standard for Electric Equipment for use in Hazardous (Classified) Locations General Requirements

Approval Standard for Electric Equipment for use in Hazardous (Classified) Locations General Requirements Approval Standard for Electric Equipment for use in Hazardous (Classified) Locations General Requirements Class Number 3600 November 1998 2002 FM Approvals LLC. All rights reserved. Foreword FM Approvals

More information

Company, Inc. Location

Company, Inc. Location Electrical Company, Inc. Location Electrical Compliance Audit December 04, 2007 Solutions Corp. Electrical Solutions Corporation 2368 Eastman Ave, Suite 13, Ventura CA 93003 Greetings, On December 4, 2007,

More information

Part I Extraction Process Equipment

Part I Extraction Process Equipment 745 West Colfax Avenue Denver, CO 80204 p: 720.913.3474 f: 720.913.3596 www.denvergov.org/fire MARIJUANA EXTRACTION GUIDELINE FOR COMMERCIAL / LICENSED FACILITIES The information contained within this

More information

Electrical Tech Note 107

Electrical Tech Note 107 Electrical Tech Note 107 Biosystems & Agricultural Engineering Department Michigan State University Understanding the Construction Code Rules, Part 8 1 Based on the 2014 NEC and the 2015 MRC The State

More information

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document 1 of 19 10/21/2015 1:20 PM Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three ASME International, Two

More information

Articles , & National Electrical Code Review & Application Guide

Articles , & National Electrical Code Review & Application Guide Articles 500-506, 510-511 & 513-516 2011 National Electrical Code Review & Application Guide Established in 1913, Killark has become a global provider of harsh and hazardous location equipment. The Killark

More information

GASEOUS HYDROGEN SYSTEMS

GASEOUS HYDROGEN SYSTEMS CHAPTER 7 GASEOUS HYDROGEN SYSTEMS SECTION 701 GENERAL 701.1 Scope. The installation of gaseous hydrogen systems shall comply with this chapter and Chapters 30 and 35 of the Fire Compressed gases shall

More information

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Single Burner Boilers Patti Mucci, Technical Assistant II DATE: August 5, 2009 SUBJECT: NFPA ROP Letter Ballot The ROP letter

More information

Report on Public Input June 2014 NFPA 101

Report on Public Input June 2014 NFPA 101 101 PI# 115 SAF-FUR (10.2.1.2) 10.2.1.2 Materials applied directly to the surface of walls and ceilings in a total thickness of less than 1 / 28 in. (0.9 mm) shall not be considered interior finish and

More information

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

Continuing Education, For UDC Electrical Inspectors, Commercial Electrical Inspectors, Master Electricians and Journeyman Electricians.

Continuing Education, For UDC Electrical Inspectors, Commercial Electrical Inspectors, Master Electricians and Journeyman Electricians. Continuing Education, For UDC Electrical Inspectors, Commercial Electrical Inspectors, Master Electricians and Journeyman Electricians. The following test is for Continuing Education Credits for the abovementioned

More information

Page 1 of 19 Committee Input No. 14-NFPA 33-2013 [ Global Input ] Type your content here... Supplemental Information File Name IndoorDraftforCI.docx Description This committee input would be added to new

More information

UL Topic III. Converting European EEx Certificates. Into. North American Division Certificates

UL Topic III. Converting European EEx Certificates. Into. North American Division Certificates Note: While this material was originally prepared for presentation in February 1999, it has been updated to reflect the evolving technical requirements now applicable as of April 2003. UL Topic III Converting

More information

ELECTRIC and NEON SIGN STANDARDS. By Randy Wright RKW CONSULTING

ELECTRIC and NEON SIGN STANDARDS. By Randy Wright RKW CONSULTING SEMINAR 301 Part 1: Changes in the 2005 NEC SEMINAR RULES: There are no Rules All Questions need to be asked Stop at any time for an explanation SEMINAR PARTS: ELECTRIC and NEON SIGN STANDARDS By Randy

More information

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input Public Input No. 16-NFPA 211-2014 [ Section No. 2.3.1 ] 2.3.1 ASHRAE Publications. ASHRAE, Inc., 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. ASHRAE Handbook: HVAC Systems and Equipment, 2008 2012.

More information

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification Public Comment No. 2-NFPA 73-2014 [ Section No. 4.1.3 ] 4.1.3 Unused Openings. 4.1.3.1 Unused openings, other than those intended for the operation of equipment, those intended for mounting purposes, or

More information

Certificate of Compliance

Certificate of Compliance FF0 001 Certificate of Compliance Certificate: 70116284 (LR 064969_0_00) Issued to: Mine Safety Appliances Company North American Division 1000 Cranberry Woods Dr Cranberry Township, Pennsylvania 16066-5296

More information

Above Ground Fuel Tank Requirements

Above Ground Fuel Tank Requirements FIRE DEPARTMENT in cooperation with Above Ground Fuel Tank Requirements The purpose of this document is to provide information about general Fire Code requirements for above ground storage within the unincorporated

More information

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document of 79 1/27/2016 2:09 PM Public Input No. 1-NFPA 59-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/API and replace with API. (2) ANSI/UL

More information

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY Fire Department HEADQUARTERS 4410 Cathedral Oaks Road Santa Barbara, CA 93110-1042 (805) 681-5500 FAX: (805) 681-5563 Michael W. Dyer Fire Chief County Fire Warden Eric Peterson Deputy Fire Chief CODE

More information

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] 1.3 Application. 1.3.1 This standard shall apply to all systems for the movement of environmental air in structures that serve the following, except

More information

Certificate of Compliance

Certificate of Compliance FF0 001 Certificate of Compliance Certificate: 70116279 (LR 025993_0_000) Issued to: General Monitors, Incorporated 26776 Simpatica Circle Lake Forest, California 92630 USA Attention: Larry Vlagea The

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

Public Comment No. 13-NFPA [ Section No ]

Public Comment No. 13-NFPA [ Section No ] Public Comment No. 13-NFPA 30-2013 [ Section No. 2.3.3 ] 2.3.3 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM A 395/A395M, Standard

More information

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35 SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1 Overview of Low-Voltage and Power-Limited Systems...3 Chapter 4 Equipment for General Use...3 Chapter 5 Special Occupancies...3 Chapter 6 Special Equipment...4

More information

Special Occupancy Requirements

Special Occupancy Requirements Special Occupancy Requirements CHAPTER 2 0 AVIATION FACILITIES CHAPTER 2 1 DRY CLEANING CHAPTER 2 2 COMBUSTIBLE DUST-PRODUCING OPERATIONS Special Occupancies The objective of this module is to make the

More information

Desiccant. Breather Range

Desiccant. Breather Range Desiccant 127 Breather Range 128 HBP & HB Types Transformer Breather Units & Accessories Desiccant Breather Range Why Choose Hawke? When specifying products used in critical electrical supply applications

More information

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

Cable Connectors For Armored Cable, Flexible Metal Conduit, Interlocked AC-38 Cables, NM and SE Cable

Cable Connectors For Armored Cable, Flexible Metal Conduit, Interlocked AC-38 Cables, NM and SE Cable For Armored Cable, Flexible Metal Conduit, Interlocked AC-38 Cables, NM and SE Cable To ground and secure Armored Cable, Flexible Metal Conduit and Interlocked Metal Clad Cables to boxes and enclosures.

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 3 FROM: Kimberly Shea DATE:

More information

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -

More information

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method

More information

Executive Summary. Shell Offshore Inc. BY: Keith M. Gonzales Sr., P.E. Regulatory Requirements for Hazardous Locations

Executive Summary. Shell Offshore Inc. BY: Keith M. Gonzales Sr., P.E. Regulatory Requirements for Hazardous Locations Contents Executive Summary... 1 Regulatory Requirements in the Gulf of Mexico for Hazardous Locations... 2 Referenced Codes and Standards... 2 Memorandum of Agreement... 2 Bureau of Ocean Energy Management

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

An Urgent Bulletin from CSA Group

An Urgent Bulletin from CSA Group An Urgent Bulletin from CSA Group Hazardous Locations Products No. 28 (Supersedes Electrical Certification Notice No. 544A) Date: January 3, 2018 See Attachment 1 for Effective Dates. See Attachment 1

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-8: ELECTRICAL EQUIPMENT ENCLOSURES AND HAZARDOUS LOCATIONS

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-8: ELECTRICAL EQUIPMENT ENCLOSURES AND HAZARDOUS LOCATIONS TSEWG TP-8: ELECTRICAL EQUIPMENT ENCLOSURES AND HAZARDOUS LOCATIONS ENCLOSURES. Select equipment enclosures to provide the following: To protect facility personnel from coming in contact with live parts.

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

Installation guide for hazardous areas

Installation guide for hazardous areas Installation guide for hazardous areas This installation guide should not be used as the controlling document for the installation of devices in a hazardous area. This guide is NOT A CONTROL DRAWING. Any

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

Portable Equipment. Equipment with electrical components suitable to be moved by a single person without mechanical aids.

Portable Equipment. Equipment with electrical components suitable to be moved by a single person without mechanical aids. Portable Equipment. Equipment with electrical components suitable to be moved by a single person without mechanical aids. Power Outlet. An enclosed assembly that may include receptacles, circuit breakers,

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 8/1/17 Updated section on Manufacturers 3 1. 6/15/16 Updated division section from 16120 to 26 05 00, - mgl44

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS INDEECO Circulation Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.

More information

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement 1 of 7 3/4/2016 12:02 PM Second Revision No. 5-NFPA 56-2016 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by

More information

NFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda*

NFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda* NFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda* NFPA Standards presented for Action Wednesday, June 24, 2015 starting @ 2:00pm: NFPA 33, Standard for Spray Application Using Flammable or

More information

REGULATIONS EUROPEAN ATEX DIRECTIVE. INTERNATIONAL SCHEME: IECEx AREAS CLASSIFICATION DEFINED BY DIRECTIVE 1999/92/EC

REGULATIONS EUROPEAN ATEX DIRECTIVE. INTERNATIONAL SCHEME: IECEx AREAS CLASSIFICATION DEFINED BY DIRECTIVE 1999/92/EC EUROPEAN ATEX DIRECTIVE > European Directive 2014/34/EU ATEX Directive 2014/34/EU is a "new approach" directive that applies to protective systems against explosions as well as all equipment used in or

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 80601-2-13 First edition 2011-08-01 Medical electrical equipment Part 2-13: Particular requirements for basic safety and essential performance of an anaesthetic workstation Appareils

More information

Not For General Distribution. For Committee Ballot 4053 Use Only. Draft 6: 10/07/2016

Not For General Distribution. For Committee Ballot 4053 Use Only. Draft 6: 10/07/2016 This document is not an API Standard; it is under consideration within an API technical committee but has not Draft 6: 10/07/2016 Recommended Practice for Design, Installation, and Maintenance of Electrical

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 61779.6:2000 (Incorporating Amendment No. 1) AS/NZS 61779.6:2000 Australian/New Zealand Standard Electrical apparatus for the detection and measurement of flammable gases Part 6: Guide for the selection,

More information

PROPOSED CHANGE TO THE 2007 FIRE CODE (OFC)

PROPOSED CHANGE TO THE 2007 FIRE CODE (OFC) TO THE 2007 FIRE CODE (OFC) OFC Record Division: A Reference Number: 1.4.1.2. (dwelling unit) Corresponding NFC Change Division: A Reference Number: 1.4.1.2.(1) OFC Revise definition for Dwelling unit

More information

CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017

CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017 CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017 The City of Portsmouth adopts the State Building Code, which adopts by reference The National Electrical Code, 2017(NEC), as Chapter 15, Part IV, of the

More information

Numerical Standards Listing

Numerical Standards Listing Numerical Standards Listing ISA-RP2.1-1978 - Manometer Tables ISA-5.1-1984 (R1992) - Instrumentation Symbols and Identification (Formerly ANSI/ISA-5.1-1984 [R1992]) ISA-5.2-1976 (R1992) - Binary Logic

More information

J-PRO TM Cable Support System

J-PRO TM Cable Support System Frequently Asked Questions Cable Support System What references define how and where J-hooks are used? J-hooks are a horizontal pathway promoted in the BICSI TDM manual as a means to route small to medium

More information

SECTION GAS-FIRED RADIANT HEATERS

SECTION GAS-FIRED RADIANT HEATERS SECTION 23 55 23 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

SERIES & NO. SMI SUBJECT: SAFE CONSIDERATIONS FOR AN APPLICATION OF SPECIAL ELECTRICAL SYSTEMS

SERIES & NO. SMI SUBJECT: SAFE CONSIDERATIONS FOR AN APPLICATION OF SPECIAL ELECTRICAL SYSTEMS 1 of 4 SUBJECT: SAFE CONSIDERATIONS FOR AN APPLICATION OF I. PURPOSE To provide basic guidelines for identifying electrical systems required for special installations. II. REFERENCES National Electric

More information

Understanding. Combustible Dust Hazards: Basic Measures to Ensure the Safety of Combustible Dust Handling Operations

Understanding. Combustible Dust Hazards: Basic Measures to Ensure the Safety of Combustible Dust Handling Operations Understanding Combustible Dust Hazards: Basic Measures to Ensure the Safety of Combustible Dust Handling Operations Michigan Safety Conference April 11, 2017 Mike Snyder PE CSP CFPS Vice President Organizational

More information

First Revision No. 20-NFPA [ Section No ]

First Revision No. 20-NFPA [ Section No ] of 25 7/15/2015 8:30 AM First Revision No. 20-NFPA 56-2015 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by NFPA

More information

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts Guy R. Colonna, PE Division Manager, NFPA Combustible Dust Symposium Detroit, MI September 20, 2011 1 Objectives

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

INFRARED RADIANT HEATER RSCA SERIES CERAMIC HEATERS NATURAL GAS PROPANE GAS DATE: PROJECT: ARCHITECT/ENGINEER: CONTRACTOR: SUBMITTED BY:

INFRARED RADIANT HEATER RSCA SERIES CERAMIC HEATERS NATURAL GAS PROPANE GAS DATE: PROJECT: ARCHITECT/ENGINEER: CONTRACTOR: SUBMITTED BY: INFRARED RADIANT HEATER RSCA SERIES CERAMIC HEATERS NATURAL GAS (CHECK ONE) PROPANE GAS PROJECT: ARCHITECT/ENGINEER: NAME: ADDRESS: NAME: ADDRESS: DATE: CONTRACTOR: SUBMITTED BY: NAME: ADDRESS: EQUIPMENT

More information

2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016)

2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016) 2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016) Reference: Documents referenced for this bulletin are as follows: San

More information