First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes
|
|
- Marybeth Townsend
- 6 years ago
- Views:
Transcription
1 First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] 1.3 Application This standard shall apply to all systems for the movement of environmental air in structures that serve the following, except as described in : (1) One- or two-family dwellings (2) Spaces not exceeding 708 m 3 (25,000 ft 3 ) in volume in any occupancy This standard shall not apply to systems for the movement of environmental air in buildings of combustible construction over three stories in height, which shall comply with NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems. Submittal Date: Fri Nov 02 10:45:45 EDT 2012 Committee Currently 1.3 (3) denotes a condition where the Standard does not apply in a Statement: paragraph that indicates where the Standard does apply. It seems clearer to create another paragraph that describes where the Standard does not apply. See FR-2-NFPA 90B-2012 for language modified by the Committee. Public Input No. 4-NFPA 90B-2012 [Section No. 1.3] 1/9
2 First Revision No. 8-NFPA 90B-2012 [ Section No ] ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA ASTM C 411, Standard Test Method for Hot-Surface Performance of High-Temperature Thermal Insulation, ASTM D 93, Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester, a. ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, 2010b 2012b. ASTM E 136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 C, ASTM E 2231, Standard Practice for Specimen Preparation and Mounting of Pipe and Duct Insulation Materials to Assess Surface Burning Characteristics, ASTM E 2652, Standard Test Method for Behavior of Materials in a Tube Furnace with a Cone-shaped Airflow Stabilizer, at 750 C, ASTM E 2688, Standard Practice for Specimen Preparation and Mounting of Tapes to Assess Surface Burning Characteristics, ASTM E 2690, Standard Practice for Specimen Preparation and Mounting of Caulk s and Sealants to Assess Surface Burning Characteristics, 2010e2. Submittal Date: Fri Nov 02 15:28:19 EDT 2012 Committee Statement: Update referenced standards to most recent edition as indicated and add three new standards used in new text in the body. FR-8-NFPA 90B /9
3 First Revision No. 11-NFPA 90B-2012 [ Section No ] UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL ANSI/UL 94, Standard for Safety Test for Flammability of Plastic Materials for Parts in Devices and Appliances, 1996, revised ANSI/UL 181, Standard for Safety Factory-Made Air Ducts and Air Connectors, 2005, revised ANSI/UL 181A, Standard for Safety Closure Systems for Use with Rigid Air Ducts, 2005, revised ANSI/UL 181B, Standard for Safety Closure Systems for Use with Flexible Air Ducts and Air Connectors, 2005, revised ANSI/UL 723, Standard Test Method for Surface Burning Characteristics of Building Materials, 2008, revised ANSI/UL 900, Standard for Air Filter Units, 2004, revised Submittal Date: Mon Nov 05 08:00:40 EST 2012 Committee Statement: Update referenced standard to most recent edition as indicated. FR-11-NFPA 90B-2012 Public Input No. 2-NFPA 90B-2012 [Section No ] 3/9
4 First Revision No. 3-NFPA 90B-2012 [ Section No ] Noncombustible Material. A material that, in the form in which it is used and under the conditions anticipated, will not ignite, burn, support combustion, or release flammable vapors when subjected to fire or heat. Materials that are reported as passing ASTM E 136 are considered noncombustible materials. See Section 4.1. Submittal Date: Fri Nov 02 10:50:20 EDT 2012 Committee This change puts NFPA 90B in line with what was done for NFPA 101 (and many Statement: other documents) in the 2012 cycle. NFPA requirements are that definitions cannot contain requirements and the definitions of noncombustible and limited combustible contain requirements. Therefore this public input proposes to put simply a place holder in chapter 3 (definitions) and place the requirements into Chapter 4, just as was done in NFPA 101 and The proposed language is identical to the language in NFPA 101. If the technical committee wishes it can simply extract the language from NFPA 101. The corresponding sections are: would be extracted from and 4.1 would be extracted from FR-3-NFPA 90B-2012 Public Input No. 8-NFPA 90B-2012 [Section No ] First Revision No. 5-NFPA 90B-2012 [ Section No ] The connector shall be made of approved fabric meeting the flame propagation performance criteria contained in Test Method 1 or Test Method 2, as appropriate, of NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films, and shall not exceed 254 mm (10 in.) in length in the direction of airflow. 4/9
5 Submittal Date: Fri Nov 02 11:19:17 EDT 2012 Committee In 1989 the NFPA Technical Committee on Fire Tests eliminated the so-called Statement: small-scale test from NFPA 701 because the results had been shown not to represent a fire performance that corresponded to what happened in real scale. Instead of the small-scale test NFPA 701 now (and for over 20 years) contains two tests (Test 1 and Test 2), which apply to materials as indicated by the text of NFPA 701 (2010) that is shown at the bottom of this public input. However, a large number of manufacturers continue stating that the materials or products that they sell have been tested to NFPA 701, when they really mean the pre-1989 small-scale test in NFPA 701. That test no longer exists and materials or products meeting that test do not exhibit acceptable fire performance. Text of NFPA 701 (2010): Test Method 1 shall apply to fabrics or other materials used in curtains, draperies, or other window treatments. Vinyl-coated fabric blackout linings shall be tested according to Test Method Test Method 1 shall apply to single-layer fabrics and to multilayer curtain and drapery assemblies in which the layers are fastened together by sewing or other means. Vinyl-coated fabric blackout linings shall be tested according to Test Method Test Method 1 shall apply to specimens having an areal density less than or equal to 700 g/m2 (21 oz/yd2), except where Test Method 2 is required to be used by Test Method 2 (flat specimen configuration) shall be used for fabrics, including multilayered fabrics, films, and plastic blinds, with or without reinforcement or backing, with areal densities greater than 700 g/m2 (21 oz/yd2) Test Method 2 shall be used for testing vinylcoated fabric blackout linings and lined draperies using a vinyl-coated fabric blackout lining Test Method 2 shall be used for testing plastic films, with or without reinforcement or backing, when used for decorative or other purposes inside a building or as temporary or permanent enclosures for buildings under construction Test Method 2 shall apply to fabrics used in the assembly of awnings, tents, tarps, and similar architectural fabric structures and banners. Note also the following from the text of NFPA 701 (2010): 1.2* Purpose The purpose of Test Methods 1 and 2 shall be to assess the propagation of flame beyond the area exposed to the ignition source. A.1.1 A small-scale test method appeared in NFPA 701 until the 1989 edition. It was eliminated from the test method because it has been shown that materials that pass the test do not necessarily exhibit a fire performance that is acceptable. The test was not reproducible for many types of fabrics and could not predict actual full-scale performance. It should not, therefore, be used. A For the purposes of Test Method 1, the terms curtains, draperies, or other types of window treatments, where used, should include, but not be limited to, the following items: (1) Window curtains (2) Stage or theater curtains (3) Vertical folding shades (4) Roll-type window shades (5) Hospital privacy curtains (6) Window draperies (7) Fabric shades or blinds (8) Polyvinyl chloride blinds (9) Horizontal folding shades (10) Swags Examples of textile items other than window treatments to which Test Method 1 applies include: (1) Table skirts (2) Table linens (3) Display booth separators (4) Textile wall hangings (5) Decorative event tent linings not used in the assembly of a tent Note that this change was already approved by NFPA FUR for NFPA 101 and NFPA 5000 and was also approved for the IBC. FR-5-NFPA 90B-2012 Public Input No. 6-NFPA 90B-2012 [Section No ] 5/9
6 First Revision No. 4-NFPA 90B-2012 [ Section No ] Tape, where exposed to the air in the system, shall not be more combustible than fabric complying with NFPA 701 have a flame spread index not to exceed 25 and a smoke developed index of not more than 50 when tested to ASTM E 84 or ANSI/UL 723 using the test specimen preparation and mounting method in accordance with ASTM E Submittal Date: Fri Nov 02 11:03:18 EDT 2012 Committee In 1989 the NFPA Technical Committee on Fire Tests eliminated the so-called Statement: small-scale test from NFPA 701 because the results had been shown not to represent a fire performance that corresponded to what happened in real scale. Instead of the small-scale test NFPA 701 now (and for over 20 years) contains two tests (Test 1 and Test 2), which apply to materials as indicated by the text of NFPA 701 (2010) that is shown at the bottom of this public input. The committee has changed the proposed language to go directly to the proper tests without having to go thru another document. FR-4-NFPA 90B-2012 Public Input No. 7-NFPA 90B-2012 [Section No ] 6/9
7 First Revision No. 7-NFPA 90B-2012 [ New Section after ] Air Dispersion Systems. Air dispersion systems shall: Global FR-7 Hide Deleted (1) Be installed entirely in exposed locations (2) Be utilized in systems under positive pressure (3) Not pass through or penetrate fire-resistant-rated construction (4) Be listed and labeled in compliance with UL 2518 Submittal Date: Fri Nov 02 15:22:27 EDT 2012 Committee These products convey air and at the same time distribute air. They are commonly Statement: known as fabric air ducts or duct socks.this is consistent with the direction that UL desires to take for these products. FR-7-NFPA 90B /9
8 First Revision No. 10-NFPA 90B-2012 [ New Section after A ] A.4.1 Global FR-10 Hide Deleted The provisions of 4.1 do not require inherently noncombustible materials to be tested in order to be classified as noncombustible materials.[ 101: A ] Submittal Date: Fri Nov 02 15:57:42 EDT 2012 Committee This change puts NFPA 90B in line with what was done for NFPA 101 (and many Statement: other documents) in the 2012 cycle. NFPA requirements are that definitions cannot contain requirements and the definitions of noncombustible and limited combustible contain requirements. Therefore this public input proposes to put simply a place holder in chapter 3 (definitions) and place the requirements into Chapter 4, just as was done in NFPA 101 and The proposed language is identical to the language in NFPA 101. If the technical committee wishes it can simply extract the language from NFPA 101. The corresponding sections are: would be extracted from and 4.1 would be extracted from FR-10-NFPA 90B /9
9 First Revision No. 6-NFPA 90B-2012 [ Section No. B ] B UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL ANSI/UL 181, Standard for Safety Factory-Made Air Ducts and Air Connectors, 2005, revised Building Materials Directory, Submittal Date: Fri Nov 02 14:03:45 EDT 2012 Committee Statement: Update referenced standard to most recent edition as indicated. FR-6-NFPA 90B-2012 Public Input No. 3-NFPA 90B-2012 [Section No. B.1.2.3] 9/9
NFPA 101 SAF-RES PUBLIC COMMENTS
Page 134 of 195 Public Comment No. 3-NFPA 101-2013 [ Section No. 28.7.6.1 ] 28.7.6.1 New draperies, curtains, and other similar loosely hanging furnishings and decorations shall be flame resistant as demonstrated
More informationReport on Public Input June 2014 NFPA 101
101 PI# 115 SAF-FUR (10.2.1.2) 10.2.1.2 Materials applied directly to the surface of walls and ceilings in a total thickness of less than 1 / 28 in. (0.9 mm) shall not be considered interior finish and
More informationSecond Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement
Second Revision No. 1-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM C411, Standard
More informationPublic Input No. 1-NFPA 90B-2015 [ Chapter 2 ]
Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered
More informationFirst Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes
First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] 4.3.11.5.5 Materials within a raised floor plenum exposed to the airflow shall be (a) noncombustible or (b) exhibit a maximum flame spread index of 25
More informationResolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.
Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in
More informationReport on First Revision June 2014 NFPA 101
101 FR500 SAF-FUR (10.2.1.2 and 10.2.1.3) Recommendation: 10.2.1.2 The provisions of Section 10.2.1.1 shall not apply to mmaterials having a total thickness of less than 1/28 in (0.9 mm) that are applied
More informationSecond Revision No. 3-NFPA [ Section No. 2.3 ]
Second Revision No. 3-NFPA 804-2014 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990. ASME Boiler
More informationThroughout standard remove references to the following and replace with the following:
of 35 12/3/2015 7:13 AM Public Input No. 1-NFPA 90A-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/UL and replace with UL. (2) ANSI/ASHRAE
More informationPublic Comment No. 1-NFPA [ Section No ]
Page 1 of 7 Public Comment No. 1-NFPA 556-2014 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA, 19428-2959. ASTM D2859, Standard
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Merchant Vessels
More information1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input
Public Input No. 2-NFPA 259-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM D 5865, Standard Test Method
More information6/9/ :58 PM. First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement
First Revision No. 1-NFPA 259-2016 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM D5865, Standard Test Method
More informationPublic Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification
Public Input No. 4-NFPA 496-2014 [ Section No. 5.2.2 ] 5.2.2 Where When the enclosure has been opened or if the protective gas supply has failed to maintain the required positive pressure, the enclosure
More informationM E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169 7471 Phone: 617 770 3000 Fax: 617 770 0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Furnishings
More informationPublic Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item
Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method
More informationPublic Comment No. 32-NFPA 90A-2016 [ Section No ] Statement of Problem and Substantiation for Public Comment
of 53 11/9/2016 9:07 AM Public Comment No. 32-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA
More informationPublic Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document
1 of 19 10/21/2015 1:20 PM Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three ASME International, Two
More informationThis standard shall prescribe provisions based on minimum requirements for safety to life and property.
NFPA STANDARDS DEVELOPMENT SITE FIRST DRAFT REPORT Closing Date: February 22, 2013 NOTE: All Public Comment must be received by 5:00 pm EST/EDST on the published Closing Date. NFPA 90B, Standard for the
More informationChange all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.
1 of 9 10/21/2015 1:22 PM First Revision No. 3-NFPA 99B-2015 [ Global Input ] Change all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.
More information2. Introduction of Committee Members and Guests. For a current committee roster, see page 02.
NFPA Technical Committee on Furnishings and Contents NFPA 101 and NFPA 5000 FIRST DRAFT MEETING AGENDA Thursday-Friday, May 24-25, 2012 Indianapolis Convention Center Room 128 Indianapolis, IN 1. Call
More informationFirst Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM
1 of 11 1/18/2016 5:43 PM First Revision No. 2-NFPA 51-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) CGA C-7 Guide to Precautionary Labelling
More informationStandard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101
Standard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101 For the Florida Building Commission And the Fire Code Advisory Council Introduction The scope
More informationPublic Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification
Public Input No. 1-NFPA 36-2013 [ Global Input ] Revise the document to eliminate the use of "Exception" text. The use of "Exception" text is inconsistent with the Manual of Style. Exception text should
More informationCommittee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM
1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:
More informationPage 1 of 9 First Revision No. 2-NFPA 99B-2012 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 10, Standard for Portable
More informationNFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting.
Input No. 7-NFPA 80-2013 [ Section No. 3.3.8 ] 3.3.8 Automatic Fire Detector. A device designed to detect the presence of a fire signature and to initiate action. For the purpose of this standard, automatic
More information(a) Flame shall not spread to the outer extremities of the sample on the 8 ft 12 ft (2440 mm 3660 mm) wall. Flashover shall not occur.
First Revision No. 1-NFPA 501-2015 [ Section No. 5.3.1.3 ] 5.3.1.3 The following conditions shall be met when an interior finish material is tested using the test protocol of NFPA 286, Standard Methods
More informationFirst Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM
of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide
More informationWORKING DRAFT OF COMMITTEE MEETING OUTPUT
WORKING DRAFT OF COMMITTEE MEETING OUTPUT CONTENT NOT FINAL SUBJECT TO REVISION PRIOR TO LETTER BALLOT AND PUBLICATION OF SECOND DRAFT REPORT Document: NFPA 221 Revision Cycle: A2014 Meeting Date: 5/20/2013
More information"Spray area" is the term that is used throughout the document. This change is for consistency.
of 78 5/30/2014 2:08 PM Public Comment No. 39-NFPA 33-2013 [ Global Input ] For Chapter 18, replace "spray paint area" with "spray area". "Spray area" is the term that is used throughout the document.
More informationFirst Revision No. 6-NFPA [ Section No. 2.2 ]
Page 1 of 18 First Revision No. 6-NFPA 555-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 12, Standard on Carbon
More informationReference to the Smoke Damage Index (SDI) is needed as it is part of the test method.
Public Input No. 4-NFPA 287-2014 [ Section No. 1.2.3.2 ] 1.2.3.2 Indices resulting from the test methods include critical heat flux (CHF), thermal response parameter (TRP), fire propagation index (FPI),
More informationM E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Helicopter Facilities
More informationFirst Revision No. 15-NFPA [ Chapter 2 ]
Page 1 of 28 First Revision No. 15-NFPA 91-2013 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard
More informationFirst Revision No. 1-NFPA 30A-2015 [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement
of 35 1/21/2016 7:56 AM First Revision No. 1-NFPA 30A-2015 [ Section No. 1.1.3 ] 1.1.3* This code shall not apply to those motor fuel dispensing facilities where only liquefied petroleum gas (LP-Gas),
More informationPage 1 of 13 Second Revision No. 1-NFPA 326-2014 [ Section No. 2.3.1 ] 2.3.1 ACGIH Publications. American Conference of Governmental Industrial Hygienists, 1330 Kemper Meadow Drive, Cincinnati, OH 45240-1634.
More informationPage 1 of 126 First Revision No. 113-NFPA 45-2013 [ Global Input ] Change all references to Material Safety Data Sheets (MSDS) to Safety Data Sheets (SDS) Submittal Date: Thu May 09 11:40:44 EDT 2013 Response
More informationPublic Comment No. 2-NFPA [ Section No ]
Page 1 of 13 Public Comment No. 2-NFPA 703-2013 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959. ASTM D 2898, Standard
More informationMEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical on Laser Fire Protection Kimberly
More informationPage 1 of 19 Committee Input No. 14-NFPA 33-2013 [ Global Input ] Type your content here... Supplemental Information File Name IndoorDraftforCI.docx Description This committee input would be added to new
More informationFirst Revision No. 1-NFPA [ Chapter 2 ]
First Revision No. 1-NFPA 499-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this recommended practice
More informationPublic Input No. 3-NFPA [ Chapter 2 ]
Public Input No. 3-NFPA 655-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered
More informationPublic Input No. 107-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification
of 123 7/30/2015 1:48 PM Public Input No. 107-NFPA 96-2014 [ Section No. 1.3.2 ] 1.3.2 The authority having jurisdiction shall determine compliance with this standard and authorize equivalent deviations
More informationCommittee Input No. 28-NFPA 13R-2013 [ Global Input ]
Page 1 of 6 Committee Input No. 28-NFPA 13R-2013 [ Global Input ] 6.2.2 Outside Dwelling Units. 6.2.2.1 All sprinklers used outside of the dwelling units shall be in accordance with 6.2.2 7.2 and 7.3.
More informationAdobe Connect - Invitation to NFPA 385 Second Draft Web Conference
Matthews, Diane Subject: Location: Start: End: Show Time As: Recurrence: Meeting Status: Organizer: Required Attendees: Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference http://nfpa.adobeconnect.com/rpbmeet/
More informationPage 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input
Public Input No. 4-NFPA 111-2016 [ Section No. 1.1.4.1 ] 1.1.4.1 * This standard shall not cover the following: (1) Application of the SEPSS (2) Distribution wiring (3) Systems having total outputs less
More informationFirst Revision No. 7-NFPA [ Global Input ] Submitter Information Verification. Committee Statement
of 29 6/9/2016 1:42 PM First Revision No. 7-NFPA 289-2016 [ Global Input ] Add comman between "reconstruction or research" throughout the document as follows: "reconstruction, or research" Submittal Date:
More informationNFPA 37 Public Comment Responses Page 1 of 32
of 30 11/4/2016 3:05 PM Public Comment No. 6-NFPA 37-2016 [ New Section after 1.6 ] TITLE OF NEW CONTENT Type your content here... 1.7 Pressure Measurement. All pressures expressed in this document are
More informationM E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter
More informationSAF-BCF SECOND REVISIONS WITH STATEMENTS
Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level
More informationMEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants
More informationTech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5
INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5 5 Tech Notes TESTING PROTOCOL Fire Retardant Gel Coats Issue Date: 4/22/2010 Document ID: TN-TS-05A 2010 Interplastic Corporation Testing Protocol
More information12/21/2015 National Fire Protection Association Report
http://submittals.nfpa.org/terraviewweb/viewerpage.jsp?id=232 2012.ditamap&toc=false&draft=true 1/9 Public Comment No. 1 NFPA 232 2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents
More informationMeeting Agenda. Air Conditioning Technical Committee November 1, 2012 at 2:00pm Eastern. (11:00am Pacific, 12:00pm Mountain, 1:00pm Central)
Meeting Agenda Air Conditioning Technical Committee November 1, 2012 at 2:00pm Eastern (11:00am Pacific, 12:00pm Mountain, 1:00pm Central) Online Meeting from NFPA Headquarters Quincy, MA 1. Call to Order.
More information2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content
Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015
More informationCHAPTER 5: EXHAUST SYSTEMS
MOTORS, FANS AND FILTERS 503.1 General. Motors and fans shall be sized to provide the required air movement. Motors in areas that contain flammable vapors or dusts shall be of a type approved for such
More informationON FIRE OF QUALITY: SINCE 1972 A CONTINUUM
A CONTINUUM OF QUALITY: ON FIRE SINCE 1972 The Govmark Organization, Inc. Instrument Division (the largest USA manufacturer of fire and flammability test instrumentation worldwide) has been producing high
More informationSecond Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 6/23/ :34 AM
of 56 6/23/2016 11:34 AM Second Revision No. 1-NFPA 96-2016 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM
More informationPublic Comment No. 13-NFPA [ Section No ]
Public Comment No. 13-NFPA 30-2013 [ Section No. 2.3.3 ] 2.3.3 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM A 395/A395M, Standard
More informationFIF AAA (F2014) Second Draft Meeting Web/Teleconference Meeting Agenda March 18, :00 5:00 p.m. ET
NFPA 804, Standard for Fire Protection for Advanced Light Water Reactor Electric Generating Plants, NFPA 805, Performance Based Standard for Fire Protection for Light Water Reactor Electric Generating
More informationNFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda*
NFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda* NFPA Standards presented for Action Wednesday, June 24, 2015 starting @ 2:00pm: NFPA 33, Standard for Spray Application Using Flammable or
More informationThroughout standard remove references to the following and replace with the following:
of 105 1/21/2016 7:49 AM Public Input No. 2-NFPA 30A-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/UL and replace with UL. (2) ANSI
More informationIMC Significant Changes Summary Tier I
2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just
More information9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification
of 4 9/23/2016 10:20 AM Second Revision No. 6501-NFPA 5000-2016 [ Section No. 17.2.2.2.4 ] 17.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked
More informationMEMORANDUM. NFPA Technical Committee on Hazard and Risk of Contents and Furnishings. NFPA 556 First Draft TC FINAL Ballot Results (A2015)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Hazard and Risk of Contents
More informationPage 1 of 5 1/29/2016 4:08 PM. First Correlating Revision No. 3-NFPA [ Section No ] Submitter Information Verification
First Correlating Revision No. 3-NFPA 101-2016 [ Section No. 6.1.8.1.1 ] 6.1.8.1.1* Definition One- and Two-Family Dwelling Unit. A building that contains not more than two dwelling units, with independent
More informationReport on First Revisions with Statement June 2014 NFPA 101
101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,
More informationRemove the "Exception" text to be consistent with direction provided in the MOS.
of 37 1/11/2017 7:38 AM Public Input No. 9-NFPA 88A-2015 [ Global Input ] Remove the "Exception" text to be consistent with direction provided in the MOS. The current language in 88A has numerous section
More informationPublic Input No. 48-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input
of 62 8/4/17, 2:42 PM Public Input No. 48-NFPA 45-2017 [ Section No. 1.1.2 ] 1.1.2 This standard shall apply to all educational laboratory units and instructional laboratory units in which any quantity
More informationPage 1 of 31 Second Revision No. 1-NFPA 80-2014 [ Section No. 2.3.2 ] 2.3.2 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM A36/A36M,
More informationPublic Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification
Public Comment No. 2-NFPA 73-2014 [ Section No. 4.1.3 ] 4.1.3 Unused Openings. 4.1.3.1 Unused openings, other than those intended for the operation of equipment, those intended for mounting purposes, or
More informationPublic Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification
Public Input No. 4-NFPA 214-2013 [ Section No. 4.2 ] 4.2 * Fire Risk Analysis. A fire risk analysis shall be conducted. The following are some of the factors that shall be considered in determining the
More informationPublic Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input
Public Input No. 16-NFPA 211-2014 [ Section No. 2.3.1 ] 2.3.1 ASHRAE Publications. ASHRAE, Inc., 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. ASHRAE Handbook: HVAC Systems and Equipment, 2008 2012.
More informationReport on First Revisions with Statement June 2014 NFPA 101
101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance
More informationPublic Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]
8 of 93 11/6/2015 7:41 AM Public Input No. 52-NFPA 30-2015 [ Section No. 21.2 [Excluding any Sub-Sections] ] For the purpose of this chapter, the term in this section shall have the definitions given.
More informationSecond Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM
1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,
More information2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code
2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code Welcome! Shawn Strausbaugh Director PMG Technical Resources ICC Government Relations sstrausbaugh@iccsafe.org
More informationCODE TECHNOLOGIES COMMITTEE NURSING CARE FACILITIES WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B
CODE TECHNOLOGIES COMMITTEE NURSING CARE FACILITIES WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B This report includes 3 code change proposal from the CTC Nursing Care Facilities Coordination committee
More informationCommittee Input No. 1-NFPA [ Chapter 2 ]
of 35 11/4/2016 6:18 PM Committee Input No. 1-NFPA 80-2016 [ Chapter 2 ] The committee will review and update the editions of the referenced publications to the correct edition at the Second Draft meeting.
More informationSecond Revision No. 1 NFPA [ Chapter 2 ]
Second Revision No. 1 NFPA 232 2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be
More informationSecond Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement
1 of 7 3/4/2016 12:02 PM Second Revision No. 5-NFPA 56-2016 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by
More informationIn Search of Standard Reference Materials (SRMs) for ASTM E05 Fire Standards by. Norman Alvares & Harry Hasegawa
In Search of Standard Reference Materials (SRMs) for ASTM E05 Fire Standards by Norman Alvares & Harry Hasegawa First Paragraph of E-691 Tests performed on presumably identical materials in presumably
More informationFirst Revision No. 39-NFPA [ Chapter 2 ]
First Revision No. 39-NFPA 130-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be
More informationBuilding & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!
Building & Fire Code Academy Building Better With Our Greatest Resource Education Welcome! Understanding the Sprinkler System Design Alternatives in the 2015 International Why inspect, test and maintain?
More informationMEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Alternative Approaches to
More informationReport on First Revisions with Statement June 2014 NFPA 101
101 FR3002 SAF-HEA (18.1.3.2) Recommendation: 18.1.3.2 Atrium walls in accordance with 6.1.14.4.6 shall be permitted to serve as part of the separation required by 6.1.14.4.1 for creating separated occupancies
More informationNational Fire Protection Association
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M (AMENDMENT) TO: FROM: Technical Committee on Mercantile
More informationDUCT SYSTEMS CHAPTER 6
CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter
More informationNFPA 90A. Standard for the. Installation of Air Conditioning and Ventilating Systems Edition
NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems 2002 Edition Copyright 2002, National Fire Protection Association, All Rights Reserved This edition of NFPA 90A, Standard
More informationMEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Industrial and Medical Gases
More informationPublic Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input
of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August
More informationPublic Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document
National Fire Protection Association Report of 113 http://submittals.nfpa.org/terraviewweb/contentfetcher?commentpara... 2/9/2016 10:50 AM Public Input No. 1-NFPA 87-2015 [ Global Input ] Throughout standard
More information2. Add a new definition as and related annex note to read as follows:
NFPA 13D-2010 Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes TIA Log No.: 1012 Reference: 3.3.9.1 Premixed Antifreeze Solution (New), 4.1.4,
More informationPublic Comment No. 10-NFPA [ Chapter 2 ]
1 of 46 12/9/2015 8:16 AM Public Comment No. 10-NFPA 130-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within
More informationBenefiting Government, Industry and the Public Through Innovative Science and Technology. Barry L. Badders, Jr. P.E.
Benefiting Government, Industry and the Public Through Innovative Science and Technology Barry L. Badders, Jr. P.E. 7 December 2011 Part 1 Non-Combustibility Test Part 3 Test for A, B,, and F Class Divisions
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4
THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More information9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification
Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry
More informationResolution: FR-1-NFPA Statement: When tests are conducted for fire reconstruction or research the items excluded above can be included.
of 29 4/12/2016 9:32 AM Public Input No. 11-NFPA 289-2016 [ New Section after 1.1.5 ] 1.1.6 When tests are conducted for the purpose of forensic fire reconstruction or research, this test standard shall
More informationPage 1 of 37 Public Input No. 1-NFPA 30A-2012 [ New Section after 1.1.2 ] 1.1.3 This code shall not apply to aircraft fuel dispensing facilities. NFPA 30A is commonly referenced, in my opinion, incorrectly,