Minimum design pressure (bar) small; bare; sunshield; insulated

Size: px
Start display at page:

Download "Minimum design pressure (bar) small; bare; sunshield; insulated"

Transcription

1 UN Portable Tank Table for Liquefied Compressed Gases. The UN Portable Tank Table for Liquefied Compressed Gases is referenced in (c)(7)(iii) of this subchapter for portable tanks that are used to transport liquefied compressed gases. The table applies to each liquefied compressed gas that is identified with Special Provision T50 in Column (7) of the Table. In addition to providing the UN identification number and proper shipping name, the table provides maximum allowable working pressures, bottom opening requirements, pressure relief device requirements, and degree of filling requirements for liquefied compressed gas permitted for transportation in a T50 portable tank. In the minimum test pressure column, small means a portable tank with a diameter of 1.5 meters or less when measured at the widest part of the shell, sunshield means a portable tank with a shield covering at least the upper third of the shell, bare means no sunshield or insulation is provided, and insulated means a complete cladding of sufficient thickness of insulating material necessary to provide a minimum conductance of not more than 0.67 w/m 2 /k. In the pressure relief requirements column, the word Normal denotes that a frangible disc as specified in (e)(3) of this subchapter is not required. UN Portable Tank Table for Liquefied Compressed Gases UN No. Non-refrigerated liquefied compressed gases Minimum design pressure (bar) small; bare; sunshield; insulated Openings below liquid level Pressure relief requirements ( See (e)) 1005 Ammonia, anhydrous 29.0 Allowed (e)(3) Bromotrifluoromethane or Refrigerant 38.0 Allowed Normal 1.13 gas R 13B Butadienes, stabilized 7.5 Allowed Normal Butane Allowed Normal Butylene 8.0 Allowed Normal 0.53 Maximum filling density (kg/l)

2 1017 Chlorine 19.0 Not (e)(3) Chlorodifluoromethane or Refrigerant gas R Chloropentafluoroethane or Refrigerant gas R Chloro-1,2,2,2-tetrafluoroethane or Refrigerant gas R Allowed Allowed Normal Allowed Normal Allowed Normal Cyclopropane 18.0 Allowed Normal Dichlorodifluoromethane or Refrigerant 16.0 Allowed Normal 1.15 gas R Dichlorofluoromethane or Refrigerant gas Allowed Normal 1.23 R ,1-Difluoroethane or Refrigerant gas R 16.0 Allowed Normal a Dimethylamine, anhydrous Allowed Normal 0.59

3 1033 Dimethyl ether 15.5 Allowed Normal Ethylamine Allowed Normal Ethyl chloride Allowed Normal Ethylene oxide with nitrogen up to a total Only Not Allowed (e)(3) 0.78 pressure of 1MPa (10 bar) at 50 C authorized in 10 bar insulated portable tanks 1041 Ethylene oxide and carbon dioxide See MAWP Allowed Normal See (f) mixture with more than 9% but not more than 87% ethylene oxide 1055 Isobutylene 8.1 Allowed Normal Methyl acetylene and propadiene 28.0 Allowed Normal 0.43 mixture, stabilized Methylamine, anhydrous 10.8 Allowed Normal Methyl bromide Not Allowed (e)(3) Methyl chloride or Refrigerant gas R Allowed Normal 0.81

4 Methyl mercaptan Not Allowed (e)(3) Dinitrogen tetroxide Not Allowed (e)(3) Petroleum gas, liquefied See MAWP Allowed Normal See (f) 1077 Propylene 28.0 Allowed Normal Refrigerant gas, n.o.s. See MAWP Allowed Normal See (f) 1079 Sulphur dioxide 11.6 Not Allowed (e)(3) Trifluorochloroethylene, stabilized or 1 Not Allowed (e)(3) 1.13 Refrigerant gas R Trimethylamine, anhydrous Allowed Normal Vinyl bromide, stabilized Allowed Normal Vinyl chloride, stabilized 10.6 Allowed Normal

5 Vinyl methyl ether, stabilized Allowed Normal Chloropicrin and methyl bromide mixture Not Allowed (e)(3) Chloropicrin and methyl chloride mixture 19.2 Not Allowed (e)(3) Hexafluoropropylene compressed or Refrigerant gas R Methyl chloride and methylene chloride mixture NA, 1954 Insecticide gases, flammable, n.o.s ,2-Dichloro-1,1,2,2-tetrafluoroethane or Refrigerant gas R Allowed Normal Allowed Normal See MAWP Allowed Normal (f) Allowed Normal Hydrocarbon gas, mixture liquefied, n.o.s. See MAWP (a) Allowed Normal See (f) 1969 Isobutane 8.5 Allowed Normal

6 1973 Chlorodifluoromethane and chloropentafluoroethane mixture with fixed boiling point, with approximately 49% chlorodifluoromethane or Refrigerant gas R Chlorodifluorobromomethane or Refrigerant gas R 12B Octafluorocyclobutane or Refrigerant gas RC Allowed Normal Allowed Normal Allowed Normal Propane 22.5 Allowed Normal Chloro-2,2,2-trifluoroethane or Allowed Normal 1.18 Refrigerant gas R 133a ,1,1-Trifluoroethane compressed or 31.0 Allowed Normal 0.76 Refrigerant gas R 143a Octafluoropropane or Refrigerant gas R 23.1 Allowed Normal Chloro-1,1-difluoroethane or 8.9 Allowed Normal 0.99 Refrigerant gas R 142b 7.8

7 2602 Dichlorodifluoromethane and difluoroethane azeotropic mixture with approximately 74% dichlorodifluoromethane or Refrigerant gas R Allowed Normal Trifluoroacetyl chloride 14.6 Not allowed (e)(3) Ethylene oxide and 14.0 Allowed (e)(3) 1.09 dichlorodifluoromethane mixture with not more than 12.5% ethylene oxide Perfluoro (methyl vinyl ether) 14.3 Allowed Normal ,1,1,2-Tetrafluoroethane or Refrigerant 17.7 Allowed Normal 1.04 gas R 134a Liquefied gas, flammable, n.o.s. See MAWP Allowed Normal (f) 3163 Liquefied gas, n.o.s. See MAWP Allowed Normal (f) 3220 Pentafluoroethane or Refrigerant gas R 34.4 Allowed Normal Difluoromethane or Refrigerant gas R Allowed Normal

8 3296 Heptafluoropropane or Refrigerant gas R Ethylene oxide and chlorotetrafluoroethane mixture, with not more than 8.8% ethylene oxide 3298 Ethylene oxide and pentafluoroethane mixture, with not more than 7.9% ethylene oxide 3299 Ethylene oxide and tetrafluoroethane mixture, with not more than 5.6% ethylene oxide Allowed Normal Allowed Normal Allowed Normal Allowed Normal Ammonia solution, relative density less See MAWP Allowed (e)(3) (f) than at 15 C in water, with more than 50% ammonia 3337 Refrigerant gas R 404A 31.6 Allowed Normal Refrigerant gas R 407A 31.3 Allowed Normal Refrigerant gas R 407B 33.0 Allowed Normal Refrigerant gas R 407C 29.9 Allowed Normal

9 [69 FR 76174, Dec. 20, 2004, as amended at 70 FR 34399, June 14, 2005]

REFRIGERATION CHAPTER 11

REFRIGERATION CHAPTER 11 CHAPTER 11 REFRIGERATION SECTION 1101 GENERAL 1101.1 Scope. This chapter shall govern the design, installation, construction and repair of refrigeration systems that vaporize and liquefy a fluid during

More information

REFRIGERATION CHAPTER 11

REFRIGERATION CHAPTER 11 CHAPTER 11 REFRIGERATION SECTION 1101 GENERAL 1101.1 Scope. This chapter shall govern the design, installation, construction and repair of refrigeration systems that vaporize and liquefy a fluid during

More information

Intelligent combined sensor for Air Quality (VOC) + Humidity (rh) + Temperature (T) with analogue outputs, Modbus and LCD display. Features.

Intelligent combined sensor for Air Quality (VOC) + Humidity (rh) + Temperature (T) with analogue outputs, Modbus and LCD display. Features. Features To measure and take control of indoor air quality Three noses in same unit Air Quality (VOC), Humidity (rh) and Temperature (T) Selectable outputs 0-10 Vdc, 4-20 ma or 0-5 Vdc via jumpers on pcb

More information

REFRIGERATION CHAPTER 11

REFRIGERATION CHAPTER 11 CHAPTER 11 REFRIGERATION SECTION 1101 GENERAL 1101.1 Scope. This chapter shall govern the design, installation, construction and repair of refrigeration systems that vaporize and liquefy a fluid during

More information

REFRIGERATION CHAPTER 11

REFRIGERATION CHAPTER 11 CHAPTER 11 REFRIGERATION SECTION 1101 GENERAL 1101.1 Scope. This chapter shall govern the design, installation, construction and repair of refrigeration systems that vaporize and liquefy a fluid during

More information

CHAPTER 11 REFRIGERATION

CHAPTER 11 REFRIGERATION CHAPTER 11 REFRIGERATION 1101.0 Scope General. 1101.1 Applicability. Part I of this chapter covers refrigeration systems. Refrigeration systems, equipment, and devices, including the replacement of parts,

More information

The Ozone-depleting Substances Control Regulations

The Ozone-depleting Substances Control Regulations 1 The Ozone-depleting Substances Control Regulations being Chapter O-8.1 Reg 1 (effective July 20, 1993) as amended by Saskatchewan Regulations 84/94. NOTE: This consolidation is not official. Amendments

More information

ESD3000 ESD200 Combustible / Toxic Gas Detector

ESD3000 ESD200 Combustible / Toxic Gas Detector ESD3000 ESD200 Combustible / Toxic Gas Detector Combustible and toxic gas leakage inspection instrument in industrial application Ex-proof certificate Exd ⅡC T6 Gb/Ex d ib ⅡC T6 Gb Dust Ex-proof certificate

More information

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter X X X X X X Adopt Entire Chapter as amended (amended sections listed below) X X X X X

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter X X X X X X Adopt Entire Chapter as amended (amended sections listed below) X X X X X CALIFORNIA MECHANICAL CODE MATRIX ADOPTION TABLE CHAPTER 11 REFRIGERATION (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency authority and building

More information

ULTIMA XIR ULTIMA X 3 ULTIMA XE. ULTIMA X Series. [ State-of-the-Art Gas Monitoring]

ULTIMA XIR ULTIMA X 3 ULTIMA XE. ULTIMA X Series. [ State-of-the-Art Gas Monitoring] ULTIMA XIR ULTIMA X 3 ULTIMA XE ULTIMA X Series [ State-of-the-Art Gas Monitoring] ULTIMA X Gas Monitors [ Providing a unique Range of Capabilities] ULTIMA X are state-of-the-art gas monitors for continuous

More information

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM 1 of 11 1/18/2016 5:43 PM First Revision No. 2-NFPA 51-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) CGA C-7 Guide to Precautionary Labelling

More information

TECHNICAL NOTE. Response Factors for Flame Ionization Detector Operation FLAME IONIZATION DETECTOR OPERATION BASICS

TECHNICAL NOTE. Response Factors for Flame Ionization Detector Operation FLAME IONIZATION DETECTOR OPERATION BASICS TECHNICAL NOTE s for Flame Ionization Detector Operation FLAME IONIZATION DETECTOR OPERATION BASICS The DataFID and MicroFID II are portable flame ionization detectors designed to monitor volatile organic

More information

ESD500. ESD500 Combustible / Toxic Gas Detector

ESD500. ESD500 Combustible / Toxic Gas Detector ESD500 ESD500 Combustible / Toxic Gas Detector Combustible and toxic gas leakage inspection instrument in industrial application Ex-proof certificate Exd ⅡC T6 Gb/Ex d ib ⅡC T6 Gb Dust Ex-proof certificate

More information

Shepherd FTIR. Laboratory Quality Results. Continuous, real time portable monitoring of 385 individual species of gas: 100+ HAPs. ...

Shepherd FTIR. Laboratory Quality Results. Continuous, real time portable monitoring of 385 individual species of gas: 100+ HAPs. ... Shepherd FTIR Portable FTIR Multi-gas Analyzer Laboratory Quality Results Acids VOCs, SVOCs Continuous, real time portable monitoring of 385 individual species of gas: 100+ HAPs. Fluorocarbons, CFCs Solvents

More information

Thermodynamics II Chapter 5 Refrigeration

Thermodynamics II Chapter 5 Refrigeration Thermodynamics II Chapter 5 Refrigeration Mohsin Mohd Sies Fakulti Kejuruteraan Mekanikal, Universiti Teknologi Malaysia Objectives Introduce the concepts of refrigerators and heat pumps and the measure

More information

Chapter 2. Alternatives to HCFCs and their Characteristics

Chapter 2. Alternatives to HCFCs and their Characteristics Alternatives to HCFCs and their Characteristics Refrigerant - General Chemical used in a cooling system, such as an air conditioner or refrigerator, as the heat carrier which changes from vapour to liquid

More information

AirSentry FTIR Multi-gas Open Path FTIR Analyzer

AirSentry FTIR Multi-gas Open Path FTIR Analyzer AirSentry FTIR Multi-gas Open Path FTIR Analyzer Multi-Component Gas Analysis... The Cerex AirSentry FTIR Multi-gas Open Path Analyzer: The standard for multi-gas open path monitoring. Regulatory Compliant

More information

Item #: 76. NFPA International RECOMMENDATION: Revise text as follows: Appliances in Attics.

Item #: 76. NFPA International RECOMMENDATION: Revise text as follows: Appliances in Attics. Item #: 76 UMC 2009- - (904.11 ): Theodore C. Lemoff NFPA International Revise text as follows: 904.11 Appliances in Attics. 904.11.1 Attic Access. An attic in which an appliance is installed shall be

More information

INDUSTRIAL REFRIGERATION. Position on refrigerant selection

INDUSTRIAL REFRIGERATION. Position on refrigerant selection INDUSTRIAL REFRIGERATION Position on refrigerant selection 1 Which Options door do you choose today? Retrofit HFC 2 Industrial customers What is of vital importance to industrial customers? The reliability

More information

ESD3000IR ESD3000IR. Infrared Gas Detector

ESD3000IR ESD3000IR. Infrared Gas Detector ESD3000IR ESD3000IR Infrared Gas Detector Infrared gas sensor Ex-proof certificate Exd ⅡC T6 Gb Dust Ex-proof certificate Ex td A21 IP66 T80 Site LCD display HART communication Replaceable sensor design

More information

SAFETY APPROVED FLASHLIGHTS: UNDERSTANDING THE REQUIREMENTS INTRODUCTION & OVERVIEW

SAFETY APPROVED FLASHLIGHTS: UNDERSTANDING THE REQUIREMENTS INTRODUCTION & OVERVIEW SAFETY APPROVED FLASHLIGHTS: UNDERSTANDING THE REQUIREMENTS INTRODUCTION & OVERVIEW Any flashlight that is intended to be used in a hazardous location must be tested and approved for that use because it

More information

Explosion Proof Speaker, Ringer & Speaker/Ringer

Explosion Proof Speaker, Ringer & Speaker/Ringer Explosion Proof Speaker, Ringer & Speaker/Ringer Models SR40 and SR60 Installation & Operation P004562 Rev. G 150831 8/31/2015 11:06 AM Ph: 403.258.3100 \ email:info@guardiantelecom.com \ www.guardiantelecom.com

More information

Explosion-proof Duct Heaters

Explosion-proof Duct Heaters Safety INDEECO explosion-proof ULTRA-SAFE and EP2 duct heaters are Factory Mutual (FM) and CSA Approved. The ULTRA-SAFE duct heater has the only standard product offering and features the industry s lowest

More information

11/22/2014. (c) DR.A.M.SURENDRA KUMAR

11/22/2014. (c) DR.A.M.SURENDRA KUMAR 11/22/2014 (c) DR.A.M.SURENDRA KUMAR 1 HISTORY A substance capable of absorbing heat from another required substance(space) can be used as Refrigerant. Air was used as refrigerant in olden days in many

More information

Type SP87300 SAFE-T SHP9 Explosion Proof Stirring Hot Plate

Type SP87300 SAFE-T SHP9 Explosion Proof Stirring Hot Plate Type SP87300 SAFE-T SHP9 Explosion Proof Stirring Hot Plate OPERATION MANUAL SERIES 873 UL Listed for Class I, Group C and D Hazardous Locations Model # Voltage Description SP87325 120 9.13 X 9.13 (23.2

More information

Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants

Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants Mukesh K. Agrawal, Dr. Ashok G. Matani Abstract- The performance of heat transfer is one of the most important research

More information

Electron Microscopy Sciences

Electron Microscopy Sciences Electron Microscopy Sciences INSTRUCTIONAL MANUAL CAT. 72341-10 Explosion Proof Hot Plate Stirrer Model SF87325 P.O. Box 550 s1560 Industry Road s Hatfield PA 19440 1 Safety Symbols Used in this Instruction

More information

Silicon-Lined Canister Cleaning Practices and Blank VOC Concentrations. Jason S. Herrington, Gary Stidsen, Trent Sprenkle, Steve Kozel

Silicon-Lined Canister Cleaning Practices and Blank VOC Concentrations. Jason S. Herrington, Gary Stidsen, Trent Sprenkle, Steve Kozel Silicon-Lined Canister Cleaning Practices and Blank VOC Concentrations Jason S. Herrington, Gary Stidsen, Trent Sprenkle, Steve Kozel U.S. EPA Method TO-15 A guidance document for a Performance Based Method

More information

Explosion Proof Speaker, Ringer & Speaker/Ringer

Explosion Proof Speaker, Ringer & Speaker/Ringer Explosion Proof Speaker, Ringer & Speaker/Ringer Models SR40 and SR60 Installation & Operation P004562 Rev. H 180430 4/30/2018 12:24 PM Ph: 403.258.3100 \ email:info@guardiantelecom.com \ www.guardiantelecom.com

More information

CHARACTERISTICS OF REFRIGERANTS. By: Dr. Ralph C. Downing Freon Products Division E. I. du Pont de Nemours & Co. Inc.

CHARACTERISTICS OF REFRIGERANTS. By: Dr. Ralph C. Downing Freon Products Division E. I. du Pont de Nemours & Co. Inc. HISTORY Modern refrigeration methods, as distinguished from the use of ice and snow, go back to the early part of the 19th century. The following dates and events illustrate the development of the industry

More information

compact detector Detection of more than 200 flammable and toxic gases iso 9001:2008

compact detector Detection of more than 200 flammable and toxic gases iso 9001:2008 iso 9001:2008 Quality Management Systems Systéme de Qualité www.sgs.com possibility of additional functions detection of critical temperature detection of flooding electrochemical sensor catalytic sensor

More information

Refrigeration Lubricants: Transitioning to new refrigerants

Refrigeration Lubricants: Transitioning to new refrigerants CoVer story Dr. Neil Canter Refrigeration Lubricants: Transitioning to new refrigerants New technology is leading to products that are safer, longer-lasting and more environmentally friendly. KEY CONCEPTS

More information

ULTIMA XIR ULTIMA X 3 ULTIMA XE. ULTIMA X Series. [ State-of-the-Art Gas Monitoring]

ULTIMA XIR ULTIMA X 3 ULTIMA XE. ULTIMA X Series. [ State-of-the-Art Gas Monitoring] ULTIMA XIR ULTIMA X 3 ULTIMA XE ULTIMA X Series [ State-of-the-Art Gas Monitoring] ULTIMA X Gas Monitors [ Providing a unique Range of Capabilities] ULTIMA X are state-of-the-art gas monitors for continuous

More information

FACT SHEET Program: Lab Fire Safety

FACT SHEET Program: Lab Fire Safety REFRIGERATION/FREEZING OF FLAMMABLE LIQUIDS Fires and explosions can and do occur in either general-purpose laboratory or ordinary domestic refrigerators or freezers when these types of appliances are

More information

REFRIGERANT COMPLIANCE PLAN. Safeway Inc. April 11, 2007

REFRIGERANT COMPLIANCE PLAN. Safeway Inc. April 11, 2007 REFRIGERANT COMPLIANCE PLAN April 11, 2007 Table of Contents i Table of Contents Foreword Introduction Regulations Compliance Management Operating Procedures Appendix Refrigerant Mission Statement... A-10-1

More information

Quality. Water. Water Quality. Testing. Testing. Toxic Gas Detection. Toxic Gas. Detection. Air Quality. Monitoring. Monitoring. Monitoring.

Quality. Water. Water Quality. Testing. Testing. Toxic Gas Detection. Toxic Gas. Detection. Air Quality. Monitoring. Monitoring. Monitoring. Water Quality Labo- Soil/ Soil/ Sedi- Sam- & Air / Dust Toxic gases are present in a wide variety of industrial and civil installations and their detection and monitoring is crucial for the safe working

More information

Hazardous area descriptions

Hazardous area descriptions Hazardous area descriptions National Electrical Code (NEC) 500 Traditional standards used in North America. Example: Class I, Div 1, Group B, C, D, T4 Permitted Class Permitted Division Permitted Group

More information

ARTICLE 25. FUEL GAS CODE

ARTICLE 25. FUEL GAS CODE ARTICLE 25. Rule 1. Indiana Fuel Gas Code, 2003 Edition (Repealed) (Repealed by Fire Prevention and Building Safety Commission; filed Mar 18, 2008, 2:32 p.m.: 20080423-IR-675070479FRA, eff 90 days after

More information

APPLICATION DATA SHEET

APPLICATION DATA SHEET APPLICATION DATA SHEET S p e c i f i c a t i o n WWW.-..UK Control Systems Transmitters Sensors Accessories TOCSIN 700 D e t e c t o r C o n t r o l P a n e l Wall mounting 24V DC or 110/230vAC operation

More information

MERIDIAN UNIVERSAL GAS DETECTOR

MERIDIAN UNIVERSAL GAS DETECTOR MERIDIAN UNIVERSAL GAS DETECTOR MERIDIAN UNIVERSAL GAS DETECTOR The term universal is frequently used in the industry to characterize gas detectors that address both toxic and combustible gases, but it

More information

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

Effect of capillary diameter on the power consumption of VCRS using different refrigerants Effect of capillary diameter on the power consumption of VCRS using different refrigerants Dr. A. G. Matani 1, Mukesh K. Agrawal 2 1 Asso. Professor, Mechanical Engineering Department, Govt. College of

More information

ISO 7291 INTERNATIONAL STANDARD

ISO 7291 INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 7291 Third edition 2010-11-01 Gas welding equipment Pressure regulators for manifold systems used in welding, cutting and allied processes up to 30 MPa (300 bar) Matériel de

More information

Meridian. Universal Gas Detector. Description. Features. Minimal drift High specificity Digital ID Broader toxic gas detection

Meridian. Universal Gas Detector. Description. Features. Minimal drift High specificity Digital ID Broader toxic gas detection 3M TM Meridian Description Designed with safety and reliability in mind, the Meridian universal gas detector is suitable for use in SIL-2 and SIL-3-rated systems under the IEC 61508 standards, certified

More information

Hazardous Areas - EXPLOSIONPROOF SOLENOIDS

Hazardous Areas - EXPLOSIONPROOF SOLENOIDS Hazardous Areas - EXPLOSIONPROOF SOLENOIDS SOME HISTORY The classification of hazardous areas into zones established the level of protection required for electrical equipment installed in explosive gas

More information

Review of Current Automobile Refrigeration System on Basis of Refrigerants Used & Their Impact on Global Warming Potential.

Review of Current Automobile Refrigeration System on Basis of Refrigerants Used & Their Impact on Global Warming Potential. IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X PP. 82-87 www.iosrjournals.org Review of Current Automobile Refrigeration System on Basis of Refrigerants

More information

Thermodynamics I. Refrigeration and Heat Pump Cycles

Thermodynamics I. Refrigeration and Heat Pump Cycles Thermodynamics I Refrigeration and Heat Pump Cycles Dr.-Eng. Zayed Al-Hamamre 1 Content Introduction The Reversed Carnot Cycle The Ideal Compression Refrigeration Systems Deviation from the ICRS Selection

More information

Item Referenced and Amendments Building 1 Building 2 Analysis, Review and Remarks. Page 1 of 15

Item Referenced and Amendments Building 1 Building 2 Analysis, Review and Remarks. Page 1 of 15 N/A N/A 2015 International Fire Code 2015 International Building Code Codes Jurisdictions for Fire and Building Codes Source of Information Building Fire Plumbing Mechanical Electrical Energy Code Accessibility

More information

we will examine only the vapour compression systems transfers to the Carnot cycle can serve as the initial model of the ideal refrigeration cycle.

we will examine only the vapour compression systems transfers to the Carnot cycle can serve as the initial model of the ideal refrigeration cycle. Refrigeration Cycle Reading Problems 10-1 10-5, 10-7, 10-9 10-11, 10-14, 10-39 Definitions a refrigeration system removes thermal energy from a low-temperature region and transfers heat to a high-temperature

More information

Explosion protection Marijan Gorše, dipl. ing.

Explosion protection Marijan Gorše, dipl. ing. Explosion protection Marijan Gorše, dipl. ing. 1/18 Flammable Gas Atmosphere We Can Control Them Explosion hazards mostly arise from flammable gases and vapours. Instead of avoiding their ignition by explosion

More information

Fire Alarm System Accessories

Fire Alarm System Accessories UL, ULC Approved* Fire Alarm System Accessories Intrinsically Safe Devices Single and Dual Channel Isolated Barrier Modules Features Single or dual channel intrinsically safe, transformer isolated barrier

More information

Vacuum and Compressor Systems for the Chemical Process Industry

Vacuum and Compressor Systems for the Chemical Process Industry Vacuum and Compressor Systems for the Chemical Process Industry Proven technology built from experience Gardner Denver Nash has been serving process industries such as petroleum, chemical and pharmaceutical

More information

Tradition & Technology

Tradition & Technology Tradition & Technology Together. Working For You. Packaged Refrigeration Systems PACKAGED REFRIGERATION SYSTEMS Vilter offers packaged refrigeration systems to meet any need. These complete, factory-engineered

More information

The Problem of Counterfeit Refrigerants

The Problem of Counterfeit Refrigerants The Problem of Counterfeit Refrigerants James K Carson President, Commission C2, International Institute of Refrigeration Senior Lecturer, School of Engineering, University of Waikato j.carson@waikato.ac.nz

More information

Chapter 11 REFRIGERATION CYCLES

Chapter 11 REFRIGERATION CYCLES Thermodynamics: An Engineering Approach, 6 th Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2008 Chapter 11 REFRIGERATION CYCLES Wan Rosli Wan Sulaiman Copyright The McGraw-Hill Companies, Inc.

More information

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle)

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Industrial and Medical Gases

More information

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement 1 of 7 3/4/2016 12:02 PM Second Revision No. 5-NFPA 56-2016 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by

More information

PURIFICATION DRYING SYSTEMS

PURIFICATION DRYING SYSTEMS PURIFICATION DRYING SYSTEMS Air Gas Liquid PSB INDUSTRIES INC. General Air Division Founded in 1951 within the shipyards of Lake Erie as Perry Ship Building, PSB Industries assistance in the construction

More information

P SERIES PURGEMETERS. Full Coverage for Semi-Conductor Processes for Built-IN Use for Equipment for General Industrial Processes

P SERIES PURGEMETERS. Full Coverage for Semi-Conductor Processes for Built-IN Use for Equipment for General Industrial Processes P SERIES PURGEMETERS Full Coverage for Semi-Conductor Processes for Built-IN Use for Equipment for General Industrial Processes P SERIES PURGEMETERS PRODUCTS INFORMATION P-100 P.3 P-200 P.5 P-300 P.7 P-400

More information

Gas Detection. - Disposable - Serviceable. Single Gas Detectors

Gas Detection. - Disposable - Serviceable. Single Gas Detectors Gas Detection Single Gas Detectors Introduction Portable single gas detectors are used for personal protection and have the ability to detect a single gas hazard. Typically they are small, lightweight

More information

Virginia St. Jean, CIH Industrial Hygienist/DPH Green Programs Manager SF Hazardous Materials Unified Program Agency

Virginia St. Jean, CIH Industrial Hygienist/DPH Green Programs Manager SF Hazardous Materials Unified Program Agency CARB Rule Changes- Affects on the Automotive Repair Industry Virginia St. Jean, CIH Industrial Hygienist/DPH Green Programs Manager SF Hazardous Materials Unified Program Agency Virginia.stjean@sfdph.org

More information

DEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR STATIONARY AC AND REFRIGERATION

DEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR STATIONARY AC AND REFRIGERATION Thomas Leck, PhD DuPont Fluorochemicals 2010 NEXT ACR Tokyo International Exchange Center 17 Feb 2010 DEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR STATIONARY AC AND REFRIGERATION

More information

Fire Alarm System Accessories

Fire Alarm System Accessories Approved by APPROVED Fire Alarm System Accessories FM Approved* Intrinsically Safe Devices Single and Dual Channel Isolated Barrier Modules Features Single or dual channel intrinsically safe, transformer

More information

Relays for use in hazardous locations. Class I, Division 2 and ATEX

Relays for use in hazardous locations. Class I, Division 2 and ATEX Relays for use in hazardous locations Class I, Division 2 and ATEX Explosion protection in North America azardous (classified) locations, as defined in the National Electric Code (NEC), are locations where

More information

Model FP-424C ma Combustible Gas Sensor (0-100% LEL) Operator s Installation & Instruction Manual. May 18, 2010 Document #2243T Version 3.

Model FP-424C ma Combustible Gas Sensor (0-100% LEL) Operator s Installation & Instruction Manual. May 18, 2010 Document #2243T Version 3. detcon inc. Model FP-424C 4-20 ma Combustible Gas Sensor (0-100% LEL) Operator s Installation & Instruction Manual May 18, 2010 Document #2243T Version 3.8 CAUTION: FOR SAFETY REASONS THIS EQUIPMENT MUST

More information

PYROS. Código: FT-PY01-I Revisión: TECHNICAL DATA. Polycarbonate tube of 4 mm. thickness LIGHT FITTING. Laquered steel painted white

PYROS. Código: FT-PY01-I Revisión: TECHNICAL DATA. Polycarbonate tube of 4 mm. thickness LIGHT FITTING. Laquered steel painted white . TECHNICAL DATA LIGHT FITTING REFLECTOR Polycarbonate tube of 4 mm. thickness Laquered steel painted white END CAPS Aluminium 2030 (polyester paint RAL 7047) POWER SOURCE LAMP TYPE 220-240V, 50/60Hz T8

More information

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage Copy Right By: Thomas T.S. Wan ) Dec. 28, 2012 All Rights Reserved Case Background: Ammonia is one of the important elements to

More information

Dräger PEX 3000 Flammable Gas Detection

Dräger PEX 3000 Flammable Gas Detection Dräger PEX 3000 Flammable Gas Detection The transmitter Dräger PEX 3000 detects flammable gases and vapors in concentrations below their Lower Explosion Limit Its DD-sensor provides a very long-term stable

More information

INSTRUCTION MANUAL Detcon Model FP-524D

INSTRUCTION MANUAL Detcon Model FP-524D INSTRUCTION MANUAL Detcon PGM 1 MODEL HOUSTON, TEXAS FP-524D MicroSafe TM LEL Gas Sensor ALM ALM FLT 1 2 CAL PGM 2 FP-524D Combustible Gas Sensor (0 100% LEL) DETCON, Inc. 4055 Technology Forest Blvd,

More information

Murco Core Product Guide Gas Leak Detection Solutions for all your building needs

Murco Core Product Guide Gas Leak Detection Solutions for all your building needs Murco Core Product Guide Gas Leak Detection Solutions for all your building needs Refrigerant Gases Toxic Gases Combustible Gases VOC s Legislation: F Gas Regulation, EH40 Standards: EN378 Lloyds Approval

More information

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR'S OFFICE CONSTRUCTION SAFETY STANDARDS

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR'S OFFICE CONSTRUCTION SAFETY STANDARDS DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR'S OFFICE CONSTRUCTION SAFETY STANDARDS (By authority conferred on the director of the department of licensing and regulatory affairs by sections

More information

INSTRUCTION MANUAL Detcon Model FP-524D-HRT

INSTRUCTION MANUAL Detcon Model FP-524D-HRT INSTRUCTION MANUAL Detcon Model FP-524D-HRT PGM 1 HOUSTON, TEXAS TM MicroSafe LEL Gas Sensor ALM ALM FLT 1 2 CAL PGM 2 FP-524D-HRT Combustible Gas Sensor (0 100% LEL) with HRT Bridge DETCON, Inc. 4055

More information

WWW. W MARINEINVEST. T PL P

WWW. W MARINEINVEST. T PL P WWW.MARINEINVEST.PL All Rights Reserved. No part of this publication should be reproduced in any form or otherwise used without written permission from publisher. General Information Copyright by MARINE

More information

VSD AND SS DRIVING ATEX MOTORS February 2014

VSD AND SS DRIVING ATEX MOTORS February 2014 VSD AND SS DRIVING ATEX MOTORS February 2014 1 Introduction to ATEX 2 ATEX motor designation 3 VSD Sample Solutions 4 SS descriptions Introduction to ATEX EU territory define the use of electrical equipment

More information

INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET)

INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET) INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET) ISSN 976 634 (Print) ISSN 976 6359 (Online) Volume 4, Issue 2, March - April (23), pp. 2-26 IAEME: www.iaeme.com/ijmet.asp Journal

More information

NATURAL REFRIGERANTS FOR HEAT PUMPS AND AIR-CONDITIONING SYSTEMS. Bernard Thonon Greth

NATURAL REFRIGERANTS FOR HEAT PUMPS AND AIR-CONDITIONING SYSTEMS. Bernard Thonon Greth NATURAL REFRIGERANTS FOR HEAT PUMPS AND AIR-CONDITIONING SYSTEMS Bernard Thonon Greth bernard.thonon@greth.fr Artificial or Natural Refrigerants? Performances COP Capacity Cost Safety Pressure, Temperature

More information

ISSN: [Sachuthananthan * et al., 5(10): October, 2016] Impact Factor: 4.116

ISSN: [Sachuthananthan * et al., 5(10): October, 2016] Impact Factor: 4.116 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY A PERFORMANCE OF A WINDOW AIR CONDITIONER USING ALTERNATIVE REFRIGERANTS R22 AND R290 Dr. B. Sachuthananthan,*, T. Naresh Kumar,

More information

Technical supplement to WHO Technical Report Series, No. 961, 2011

Technical supplement to WHO Technical Report Series, No. 961, 2011 Supplement 16 Environmental management of refrigeration equipment Technical supplement to WHO Technical Report Series, No. 961, 2011 Annex 9: Model guidance for the storage and transport of time- and temperature-sensitive

More information

Main Anthropogenic Sources of Greenhouse Gases Refrigerants

Main Anthropogenic Sources of Greenhouse Gases Refrigerants Main Anthropogenic Sources of Greenhouse Gases Refrigerants Content Refrigerant definition Refrigerants Refrigerants as a source of GHG Refrigerant Definition A refrigerant is a substance or mixture, usually

More information

Xgard. Fixed detectors For flammable, toxic or oxygen gases

Xgard. Fixed detectors For flammable, toxic or oxygen gases Fixed detectors For flammable, toxic or oxygen gases Xgard Xgard Type 1: Xgard Type 2: Xgard Type 3: Xgard Type 4: Xgard Type 5: Xgard Type 6: Xsafe: Intrinsically safe toxic and oxygen gas detector Flameproof

More information

Page 1 of 33. Public Input No. 2-NFPA [ Chapter 2 ] Referenced Publications. 2.1 General.

Page 1 of 33. Public Input No. 2-NFPA [ Chapter 2 ] Referenced Publications. 2.1 General. of 32 5/3/2016 1:47 PM Public Input No. 2-NFPA 12-2015 [ Chapter 2 ] Chapter 2 2.1 General. Referenced Publications The documents or portions thereof listed in this chapter are referenced within this standard

More information

1. GENERAL TECHNICAL INFORMATION

1. GENERAL TECHNICAL INFORMATION 1. GENERAL TECHNICAL INFORMATION 1.1 EXPLOSIVE ATMOSPHERES: Every time that dangerous quantities and concentration of flammable gas, vapors mixture or dust clouds exists, risk of explosions may arise.

More information

Macurco Gas Detection Products

Macurco Gas Detection Products Macurco Gas Detection Products 1 Macurco 6-Series Detector, Controller and Transducer 2 Macurco 6-Series Detector, Controller and Transducer The Macurco 6-Series is the new platform for the Macurco commercial

More information

Knowledge Objectives (2 of 2) Fuel Gas Systems. Skills Objectives. Introduction. Fuel Gas Systems (1 of 6) 12/20/2013

Knowledge Objectives (2 of 2) Fuel Gas Systems. Skills Objectives. Introduction. Fuel Gas Systems (1 of 6) 12/20/2013 Fuel Gas Systems Knowledge Objectives (1 of 2) Explain the impact of fuel gases on fire and explosion investigations. Discuss the characteristics of fuel gases. Identify common fuel gas system components.

More information

Polytron 2. The smart gas detector

Polytron 2. The smart gas detector Polytron 2 The smart gas detector 2-951-95 Polytron 2 Highlights One universal transmitter for all electrochemical sensors Patented Plug & Play Sensor Technology Self-diagnostics of sensor and transmitter

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-8: ELECTRICAL EQUIPMENT ENCLOSURES AND HAZARDOUS LOCATIONS

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-8: ELECTRICAL EQUIPMENT ENCLOSURES AND HAZARDOUS LOCATIONS TSEWG TP-8: ELECTRICAL EQUIPMENT ENCLOSURES AND HAZARDOUS LOCATIONS ENCLOSURES. Select equipment enclosures to provide the following: To protect facility personnel from coming in contact with live parts.

More information

Chapter 11 REFRIGERATION CYCLES

Chapter 11 REFRIGERATION CYCLES Thermodynamics: An Engineering Approach Seventh Edition in SI Units Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2011 Chapter 11 REFRIGERATION CYCLES Mehmet Kanoglu University of Gaziantep Copyright

More information

Manufacturers of Explosion Proof, Corrosion Resistant and Severe Duty HVAC/R Systems, and Pressurization Equipment.

Manufacturers of Explosion Proof, Corrosion Resistant and Severe Duty HVAC/R Systems, and Pressurization Equipment. Manufacturers of Explosion Proof, Corrosion Resistant and Severe Duty HVAC/R Systems, and Pressurization Equipment. COPYRIGHT 2011 Safe Air Technology LLC. All Rights Reserved Severe Duty Design for: Safe

More information

VAPOR COMPRESSION HEAT PUMP USING LOW TEMPERATURE GEOTHERMAL WATER: A CASE STUDY OF NORTHERN THAILAND

VAPOR COMPRESSION HEAT PUMP USING LOW TEMPERATURE GEOTHERMAL WATER: A CASE STUDY OF NORTHERN THAILAND VAPOR COMPRESSION HEAT PUMP USING LOW TEMPERATURE GEOTHERMAL WATER: A CASE STUDY OF NORTHERN THAILAND Fongsaward S. Singharajwarapan 1 and Nattaporn Chaiyat 2 1 Groundwater Technology Service Center, Chiang

More information

SP-220. Features. Combustible handheld gas leakage detector

SP-220. Features. Combustible handheld gas leakage detector SP-220 Combustible handheld gas leakage detector The SP-220 gas leakage detector is a simple to operate unit with high sensitivity to a variety of gases. The SC version (SP-220SC) is able to detect super-toxic,

More information

GAS DETECTOR TUBE SYSTEM. The Gastec Detector Tube System represents cutting edge technology and is used in a wide variety of fields.

GAS DETECTOR TUBE SYSTEM. The Gastec Detector Tube System represents cutting edge technology and is used in a wide variety of fields. GAS DETECTOR TUBE SYSTEM The Gastec Detector Tube System represents cutting edge technology and is used in a wide variety of fields. www.levitt-safety.com NATIONWIDE TOLL FREE: 888..888 The Gastec Detector

More information

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document of 79 1/27/2016 2:09 PM Public Input No. 1-NFPA 59-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/API and replace with API. (2) ANSI/UL

More information

VASTHI ENGINEERS. Vasthi Multi Gas Monitor/Analyzer. Sheet No. 1 of 4. Vasthi Multi Gas monitor/analyzer with alarm and Graphical Display.

VASTHI ENGINEERS. Vasthi Multi Gas Monitor/Analyzer. Sheet No. 1 of 4. Vasthi Multi Gas monitor/analyzer with alarm and Graphical Display. Sheet No. 1 of 4 monitor/analyzer with alarm and Graphical Display. Sheet No. 2 of 4 It specially designed to analyze any gas of your choice, its automatic operation, accurate measurement and crystal clear

More information

Model 950-ASH Arson Scanner Hydrocarbons and Accelerants Detector Operation and Maintenance

Model 950-ASH Arson Scanner Hydrocarbons and Accelerants Detector Operation and Maintenance Model 950-ASH Arson Scanner Hydrocarbons and Accelerants Detector Operation and Maintenance www.arsondetection.com M950-ASHTM1218 December 2018 Model 950-ASH Table of Contents Cover 1 Table of Contents

More information

Firefighting. It is the temperature at which a substance will continue to burn, when ignited.

Firefighting. It is the temperature at which a substance will continue to burn, when ignited. Firefighting 1. What is Flash Point? A lowest temperature of a substance, at which there is sufficient vapor to produce a flash momentarily, is called the Flash point of that substance. 2. What is Fire

More information

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS FEATURES Extremely wide range of sensors Easy installation and maintenance Low cost of ownership Replacement of sensors are simple Rugged and reliable

More information

New Refrigerants Designation and Safety Classifications

New Refrigerants Designation and Safety Classifications New Refrigerants Designation and Safety Classifications E360 Forum Raleigh, N.C. March 1, 2017 Stefanie Kopchick North America Marketing Manager, Refrigerants Chemours Greg Relue Manager, Regulatory Compliance/Product

More information

APPENDIX A FEES SECTION FC A01 CERTIFICATES A01.1

APPENDIX A FEES SECTION FC A01 CERTIFICATES A01.1 FEES SECTION FC A01 CERTIFICATES A01.1 Certificate fees. Applicants for certificates required pursuant to the provisions of this code or the rules shall pay the fees specified in this section. Fees for

More information

Hydrocarbons as refrigerants

Hydrocarbons as refrigerants Hydrocarbons as refrigerants Hydrocarbons convince with their environment-friendliness and economic feasibility. A developed society cannot function without refrigeration. At home, in food production and

More information

700 FP Series. Instruction Manual. Combustible Gas Detector OLCT 700 OLCT 710. The Fixed Gas Detection Experts The Fixed Gas Detection Experts

700 FP Series. Instruction Manual. Combustible Gas Detector OLCT 700 OLCT 710. The Fixed Gas Detection Experts The Fixed Gas Detection Experts Instruction Manual 700 FP Series Combustible Gas Detector OLCT 700 OLCT 710 Part Number: NP700FPIMEN Revision: C.0 The Fixed Gas Detection Experts The Fixed Gas Detection Experts OLCT 700/710 FP Instruction

More information

OLC(T) 100 FIXED GAS DETECTOR

OLC(T) 100 FIXED GAS DETECTOR Fixed Gas Detector OLC(T) FIXED GAS DETECTOR Detection of explosive gases, toxic gases or oxygen Infrared XP version SIL 2 high reliability IP 66 Aluminium or Stainless Steel version CERTIFICATIONS The

More information