1 Assessment of H2S Complaints Casey Middle School 3 High Street Boulder, Colorado Project Report March 25, 25 For: Boulder Valley School District 65 Arapahoe Rd Boulder, CO 833 (33) 447- By: Indoor Air Diagnostics Tulsa, Oklahoma Environmental Building Sciences, Inc. PO Box 364 Las Vegas, NM

2 March 25, 25 2 / OVERVIEW In response to reports of hydrogen sulfide (H2S) odors and health complaints in the Casey Middle School, Dr. Richard Shaughnessy of Indoor Air Diagnostics (IAD) and Mr. Brad Turk of Environmental Building Sciences, Inc. (EBSI) have conducted an assessment of the school. This work included a review of investigations and measurements conducted by others, consultation with BVSD staff and administration, site visits to assess pressure differences in the building and sewer pipes and to spot check H2S levels, and to provide recommendations for corrective action. These activities focused on indoor air quality problems related to, and assuming that, H2S was the source of the odors and complaints. FINDINGS H2S Spot Measurements During the site visit on February 27 and 28, 25, spot measurements of H2S were made in and around the building, and results are summarized in Table. A Jerome 63, with a lower detection limit of 3 ppb, was used to conduct all but one of the measurements. A Gray Wolf monitor was employed to sample the higher levels in the sewer pipe in the mechanical crawlspace. Two to four consecutive measurements of approximately 3 seconds in durations were made at each location. Measurements at all indoor locations were below the detection limit of the Jerome. The outdoor and garage measurements are at, or slightly above, the detection limit but the manufacturer of the instrument states that these results may be uncertain because of the cold temperature conditions. Building Pressure Measurements To confirm preliminary indications that the building was operating under a negative pressure with respect to outdoors, differential pressure measurements were made across the building enclosure at several locations, and under different operating conditions. Results are presented in Table 2. The results indicate that the HVAC systems do not overcome the natural depressurization of the building (due to stack effect, with HVAC systems off) on the first and second floors. The situation is aggravated slightly when exhaust fans (restroom fans, kitchen and lab exhaust hoods, etc.) are operated. Note that when classroom doors are open to the hallways, depressurization in the classrooms is often increased significantly implying that the supply and return/exhaust air flows in the hallways are unbalanced. The large, resulting depressurization can be a contributing factor in H2S migrating from minor leaks in sewer pipes. It can also cause undesirable air flow into the building, for example from the adjoining parking garage or from open windows that might be down-wind of sewer vent pipes on the roof. Sewer Vent Pipe Pressure Testing The District had previously installed air admittance valves (studor vents) and carbon scrubbers on the vent pipes on the roof. During the site visit in February, 25, some valves and scrubbers were found to have been impaired by frozen moisture that had collected in the devices.

3 March 25, 25 3 / To evaluate the impact on pressures in the vent pipes, pressure measurements were made at four cleanout locations in the building and at the top of the vent pipes, as valves and scrubbers were sequentially removed. As seen in Table 3, sewer pipes were found to be pressurized (with respect to indoors) at all test locations, including in the mechanical crawlspace, with all of the valves and scrubbers installed. With the pipes pressurized, H2S would be pushed from the pipes into the building (with any minute breach within the sewer pipes). This condition was gradually reversed (sewer pipes depressurized) as more valves and scrubbers were removed. With all of the devices removed, the vents operated as intended, driven by the stack effect and open top to produce negative pressures in the pipes at lower elevations and positive pressures near the tops of the highest vents, allowing the warm, buoyant, and H2S-laden air to release into the atmosphere. Note that because of the difference in roof elevations, with all vents open, the vent pipes on the lower roofs were slightly depressurized by the vent pipes on the taller roofs (C-wing). These pressures would likely change under different outdoor temperature and wind conditions. It appeared that, with vents open, the current locations of the vent pipes could allow re-entrainment of vented gases into outdoor air intakes for HVAC systems, and open windows and doors. RECOMMENDATIONS The following recommendations are primarily based on observations, tests, and findings during the site visits conducted in January 25 by IAD and in February by IAS and EBSI. The investigation focused on air quality problems related to migration of H2S into the building. ) Remove Carbon Scrubbers and Air Admittance Valves (studor vents) from roof-top plumbing vent pipes to relieve pressure build-up. Scrubbers and valves had problems with cold weather conditions, and appeared to permit pressure to build within the sewer lines running within the school boundaries. This, in combination with the building and underfloor space pressures running negative with respect to outdoors, could create unwanted entry of H2S from any minute breach, existing or future, in the sewer lines within the school boundaries. 2) Gang Together and Extend Plumbing Vent Pipes on the Roof. Keep discharge away from doors and operable windows and ventilation system outdoor air intakes. Overall design, decisions on location and length of extensions of vent pipes, and actual installation for optimal venting of sewer gases including H2S, should be overseen and engineered by professional Plumbing/Mechanical Engineering firm. 3) Keep Floor Drains and Other Traps Filled or Install Drain Check Valves. Mineral oil or other compatible fluid should be used in conjunction with water in the drains to slow drying out of traps. 4) Re-Balance HVAC System for the Entire Building and Underfloor Spaces (including mechanical spaces and crawlspaces), so as to achieve a very slight overpressurization with respect to outdoors. This will help assure that ) in combination with # and #2, above, H2S leakage from sewer pipes is minimized, 2) entry of outdoor air into the building is controlled to be through the HVAC equipment, and 3) entry of possible contaminants in the air from the open soil crawlspaces is reduced. Provide independent engineering oversight of test and balance process.

4 March 25, 25 4 / 5) Adjust or Modify ERV Wheel Wipers to reduce cross-contamination between fresh incoming air stream and stale air exhaust air stream (consult with manufacturer). 6) Assure that ERV Defrost Mode Rarely Occurs. To keep frost from accumulating and blocking air flow through the heat exchange wheel during very cold weather, ERVs will enter a defrost mode that stops cold incoming supply air, while maintaining exhaust flow thorough the wheel. This mode creates unbalanced air flows and depressurization of the building. The temperature setting for initiation of defrost mode should be carefully selected to avoid frozen wheels, yet minimize the period of time that exhaust air flows are greater than supply flows. 7) Increase Supply of Outdoor Air in order to ensure meeting ASHRAE recommendations. Earlier measurements of CO2 in classrooms suggest that the amount of outdoor air being provided to some areas of the building are below ASHRAE recommendations. The additional ventilation air is intended to flush and dilute indoor air pollutants to levels acceptable to the majority of occupants. 8) Consult with 3 rd Party Toxicologists and Health Professionals to ) evaluate possible causative agents for symptoms reported by staff and students, and 2) establish target indoor concentrations of potentially offending air pollutants. The target range established by health professionals is to be used as a basis to develop an air quality monitoring schedule within the school. In addition, a long-term maintenance program is to be put into effect to ensure the proper operation of the system and all modifications to be intact for the life of the occupied school building. 9) Implement a District-wide IEQ Program that includes a formal process for reporting IEQ complaints and responding to problems.

5 March 25, 25 5 / Table. Spot Measurements of Hydrogen Sulfide with HVAC Systems Operating, 2/28/5 Spot Measurement Location Displayed Concentration (ppb) () Outdoors, N-S Access Road East of School 3 to 5 (2) Parking Garage 4 (2) ERV OA Intake (Courtyard) 3 to 4 (2) ERV Exhaust (Courtyard) to 2 (2) Under Garage Slab Soil Air (3) : Loc T Loc T2 Loc T3 Crawlspace (3) : General Ground-source Heat Pumps Sewer Pipe at Cleanout 25 Crawlspace 2 (3) : General Crawlspace 3 (3) : General Crawlspace 4 (3) : General Electric Room at Floor Drain Non-Complaint Rooms (4) : Custodial Office B2 B35 Complaint Rooms (4) : C-wing st Flr Hall C2 C4 C-wing 2 nd Flr Hall C23 C24 C-wing 3 rd Flr Hall C33 C335 2 ()Jerome 63, with reported lower detection limit of 3 ppb, for all locations except sewer pipe in Crawlspace. (2)Outdoor air temperature at time of measurement approx. 24 F, wind ENE (5 th & High St.). Note that Arizona Instruments, manufacturer of Jerome 63, was not certain of the effect of cold outdoor temperatures at time of measurement on the sensor response and instrument accuracy. (3)See floor plan (Figure ) for approximate locations (4)Complaint and Non-complaint rooms as reported by BVSD Maintenance

6 March 25, 25 6 / Table 2. Building Pressure Difference Measurements (Pascals), 2/27/5 and 2/28/5 Location HVAC Off HVAC On HVAC On + All Exhaust On Exhaust Off Pressure / Door To Hall Pressure / Door To Hall st Floor West Door to Hall West Door by Grease Trap North Door to Hall East Door to Parking Garage C /Open -- C /Closed -4.3 /Open C /Closed -7.8 /Open C to -6. /Closed -- C /Closed -9. /Open C /Open -4.7 /Closed -.2 /Open C /Closed -6.8 /Open Door from Hall to Crawlspace nd Floor B25 Door to Courtyard C to +3. /Closed -3. /Open -- C /Open -- 3 rd Floor South Access Door to Roof to to +2.6 B /Open +.8 to +.2 /Open C /Closed +6.2 /Open -- C to +5. /Closed +3. to +5. /Open -- Note: All pressure measurements made with respect to outdoors, except for Crawlspace which is referenced to hall. Negative pressure difference values indicate space is depressurized, while positive values indicate pressurization.

7 March 25, 25 7 / Table 3. Sewer Vent Pipe Pressure Testing (Pascals), 2/28/5 Vent ID Opened (order of opening) (A) Cleanout in Crawlspace (Mech) (B) Cleanout in Mech. Rm. By Grease Trap Pressure Test Location (C) Cleanout in Hall by Garage (D) Cleanout in 3 rd Flr. Hall As Vents Opened (E) At Vent on Rooftop () All Vents Open All Open + Exh Fans On All Vents Capped (first) to to to to to A -.3 to to to (last) -3. to All Vents Open + All Exhaust Fans On to () Measurement at top of vent pipe, with top sealed to make pressure measurement (breezy conditions) Notes:. HVAC systems operating 2. Breezy conditions 3. All pressure measurements inside sewer pipe made with respect to inside of building (B-D), mechanical space in Crawlspace (A), or outdoors for vents on rooftop (E). See floor plan (Figure 2) for identification and approximate locations.

8 March 25, 25 8 / Figure. Plan showing location of crawlspaces and parking garage slab test holes.

9 March 25, 25 9 / Figure 2. Plan of sewer roof vent and pressure test locations and IDs.

10 March 25, 25 / WARRANTY Indoor Air Diagnostics (IAD) and Environmental Building Sciences, Inc. (EBSI) make no representation or warranty expressed or implied, with respect to its services, test results or findings, recommendations or results, and expressly disclaim the same. IAD and EBSI warrant that their services rendered are performed in accordance with procedures and practices generally understood in IAD s and EBSI s business to be careful and professional.

Put the V back in HVAC

Put the V back in HVAC Put the V back in HVAC V is for Ventilation A system or means of providing fresh air. Webster New Collegiate Dictionary Benjamin Franklin so unwholesome as air in a closed room that has been often breathed

More information

Ventilation for New Low-Rise Residential Buildings July 20, 2015

Ventilation for New Low-Rise Residential Buildings July 20, 2015 Ventilation for New Low-Rise Residential Buildings July 20, 2015 BSC Standard 01 2015 Building Science Corporation 3 Lan Drive, Suite 102 Westford, MA 01886 www.buildingscience.com Contents 1. PURPOSE...3

More information

Executive Summary

Executive Summary Prepared by: Proctor Engineering Group, Ltd. San Rafael, CA 94901 (415) 451-2480 Investigation of Coil Failures - A Whole Systems Approach Prepared for: Geothermal Heat Pump Consortium Final Report July

More information

MECHANICAL VENTILATION

MECHANICAL VENTILATION MECHANICAL VENTILATION Natural and Mechanical Systems Four (4) possible combinations of natural and mechanical ventilations tions are as follows; Natural inlet and outlet; utilizing open able windows,

More information

Ventilation Techniques. Topic 5 - Audio 53

Ventilation Techniques. Topic 5 - Audio 53 Topic 5 - Audio 53 Increasing Fresh Air Increasing fresh air make-up to a building can dilute radon and other indoor air contaminants. Increasing make-up air can reduce the negative pressures within a

More information

Displacement Ventilation

Displacement Ventilation Displacement Ventilation Displacement Ventilation Displacement Ventilation vs. Dilution Ventilation Characteristics Design Considerations Layout and Selection Product Overview Casino Case Study Dilution

More information

PLAN THE INSTALLATION Planning the installation first requires selecting the most appropriate installation approach. The chart below offers suggestion

PLAN THE INSTALLATION Planning the installation first requires selecting the most appropriate installation approach. The chart below offers suggestion AUTOMATIC MAKE-UP AIR DAMPER WITH To register this product visit: www.broan.com MODELS MD6T MD8T MD10T READ AND SAVE THESE INSTRUCTIONS FOR RESIDENTIAL USE ONLY Page 1 WARNING TO REDUCE THE RISK OF FIRE,

More information

Ventilation. ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce.

Ventilation. ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce. Ventilation ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce /NDCommerce /NDCommerce /NDCommerce /NDCommerce WHATS NEW IN ASHRAE 62.2 2016 Controls (Override) Shutoff for maintenance

More information

e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings)

e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings) 1. Ground Level Indoor Inspection a. Univents are on and air discharge grills are free of obstructions. If false, send email to building principal and facilities director asking staff to be instructed

More information

e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings)

e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings) 1. Ground Level Indoor Inspection a. Univents are on and air discharge grills are free of obstructions. If false, send email to building principal and facilities director asking staff to be instructed

More information

e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings)

e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings) 1. Ground Level Indoor Inspection a. Univents are on and air discharge grills are free of obstructions. If false, send email to building principal and facilities director asking staff to be instructed

More information

AUTOMATIC MAKE-UP AIR DAMPER WITH TRANSFORMER READ AND SAVE THESE INSTRUCTIONS

AUTOMATIC MAKE-UP AIR DAMPER WITH TRANSFORMER READ AND SAVE THESE INSTRUCTIONS AUTOMATIC MAKE-UP AIR DAMPER WITH READ AND SAVE THESE INSTRUCTIONS FOR RESIDENTIAL USE ONLY Page 1 WARNING TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: 1. Installation

More information

How can you reduce radon in a home?

How can you reduce radon in a home? Lesson 10: How can you reduce radon in a home? Lesson overview This lesson provides a brief overview of radon mitigation. Lesson objectives By the end of this lesson, the learners will be able to: Describe

More information

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee Gil Rossmiller In the construction industry for over 30 years ICC IRC Plumbing & Mechanical Code Development Committee ICC- IECC Commercial Energy Code Development Committee Building Official Parker, Colorado

More information

Spray Polyurethane Foam and Open-Combustion Appliances

Spray Polyurethane Foam and Open-Combustion Appliances Spray Polyurethane Foam and Open-Combustion Appliances Before applying SPF (spray foam polyurethane) insulation in an attic or crawl space it is important to determine if there are any appliances present,

More information

Civil Engineering Building

Civil Engineering Building Continuous Commissioning Report For the Civil Engineering Building Building 492 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

CRAWL SPACE MOISTURE CONTROL - A Fundamental Misunderstanding By Peter Carpenter, member ASHRAE, SBCCI

CRAWL SPACE MOISTURE CONTROL - A Fundamental Misunderstanding By Peter Carpenter, member ASHRAE, SBCCI CRAWL SPACE MOISTURE CONTROL - A Fundamental Misunderstanding By Peter Carpenter, member ASHRAE, SBCCI A crawl space needs to be ventilated with outside air. Without ventilation there will be growth of

More information

Heat Recovery Ventilation Systems OWNER S GUIDE

Heat Recovery Ventilation Systems OWNER S GUIDE Heat Recovery Ventilation Systems OWNER S GUIDE U.S. Registered Trademark Copyright 2002 All Rights Reserved 69-1657 CONTENTS Introduction.........................................................3 Feeling

More information

Green Building Practice Summary 3/10/2011

Green Building Practice Summary 3/10/2011 Green Building Practice Summary 3/10/2011 Sector: Residential Category/Practice: IEQ / Safer Combustion Appliances: New Construction Proposed GB Practice Description Most natural draft combustion appliances

More information

RK Carbon Monoxide Transmitter Operator s Manual

RK Carbon Monoxide Transmitter Operator s Manual 65-2335RK Carbon Monoxide Transmitter Operator s Manual Part Number: 71-0177RK Revision: 0 Released: 4/12/11 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual

More information

Smoke Management in High-Rise Structures

Smoke Management in High-Rise Structures Smoke Management in High-Rise Structures Most modern building codes define a high-rise structure as a building greater than 75 feet in height from the lowest level of fire department vehicle access to

More information

LEED for Homes Points

LEED for Homes Points LEED for Homes Points This document is a guideline of the maximum potential points American ALDES ventilation products can contribute to obtaining certification under the US Green Building Council s (USGBC)

More information

Multnomah Education Service District

Multnomah Education Service District Cascade Radon, Inc. 12839 NE Airport Way Bldg.9 Testing, Mitigation, Portland, Oregon 97230 Systems Design Phone: (503) 421-4813 CCB 180537 / CASCARI927C1 Fax: (503) 281-6170 Office@CascadeRadon.com Radon

More information

Bill McCullough. Director ERV Products. Dallas, TX

Bill McCullough. Director ERV Products. Dallas, TX Bill McCullough Director ERV Products Dallas, TX TOPICS 1. ERV Definition & Benefit 2. Indoor Air Quality 3. Energy Efficiency 4. ERV Technology & Operation 5. Stand-Alone ERVs 6. Compact ERVs What is

More information

2012 International Mechanical Code Significant Changes. About the Significant Changes

2012 International Mechanical Code Significant Changes. About the Significant Changes Significant Changes to the International Mechanical Code and the International Fuel Gas Code With Louisiana Amendments Copyright Materials This presentation is protected by US and International Copyright

More information

2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code

2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code 2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code Welcome! Shawn Strausbaugh Director PMG Technical Resources ICC Government Relations sstrausbaugh@iccsafe.org

More information

SAFETY AND INSTALLATION MANUAL MODEL 8100

SAFETY AND INSTALLATION MANUAL MODEL 8100 SAFETY AND INSTALLATION MANUAL ENERGY RECOVERY VENTILATORS MODEL 8100 Provides year-round fresh air Recovers 77% of the apparent heating or cooling energy from the exhausted air See Warnings Page 3 Table

More information

THE EVALUATION OF MULTI-ZONE AIR FLOW PATTERN AND VENTILATION RATES WITH TRACER GAS METHODS IN APARTMENT HOUSE

THE EVALUATION OF MULTI-ZONE AIR FLOW PATTERN AND VENTILATION RATES WITH TRACER GAS METHODS IN APARTMENT HOUSE THE EVALUATION OF MULTI-ZONE AIR FLOW PATTERN AND VENTILATION RATES WITH TRACER GAS METHODS IN APARTMENT HOUSE DW Yoon 1, JY Sohn 2, SD Kim 3 and HS Kim 4 1 Dept. of Building Equipment and System Engineering,

More information

SMART ERV Energy Recovery Ventilator. Build It Tight / Ventilate It Right!

SMART ERV Energy Recovery Ventilator. Build It Tight / Ventilate It Right! SMART ERV Energy Recovery Ventilator SMART air & energy solutions SMART products include Indoor Air Quality (IAQ) and Energy efficiency products Primarily targeting the residential market Products include:

More information

Walkthrough Inspection Checklist

Walkthrough Inspection Checklist Walkthrough Inspection Checklist Name: School: Room or Area: Date Completed: Signature: Instructions 1. Read the IAQ Backgrounder and the Background Information for this checklist. 2. Keep the Background

More information

RK-02 Multi Point Detector Operator s Manual

RK-02 Multi Point Detector Operator s Manual 65-2485RK-02 Multi Point Detector Operator s Manual Part Number: 71-0237RK Revision: A Released: 11/26/14 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual

More information

Indoor Air Quality Product Brochure.

Indoor Air Quality Product Brochure. Indoor Air Quality Product Brochure Ventilation: A vital system for a healthy home All homes require adequate ventilation for the safety of their occupants and to remove excess humidity, airborne pollutants

More information

An Introduction to Energy Efficient and Effective Whole-House Ventilation

An Introduction to Energy Efficient and Effective Whole-House Ventilation 0 An Introduction to Energy Efficient and Effective Whole-House Ventilation 1 The 1973 energy crisis caused people to look for ways to reduce the cost of heating and cooling their homes. The building industry

More information

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA CITY OF DANA POINT COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 33282 Golden Lantern, Suite 209 Dana Point, CA 92629 949 248 3594 www.danapoint.org INDOOR AIR QUALITY B011 AIR 2013 CALIFORNIA CODES CODE

More information

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available. PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the

More information

RK/ RK Carbon Monoxide Detector Operator s Manual

RK/ RK Carbon Monoxide Detector Operator s Manual 65-2496RK/65-2499RK Carbon Monoxide Detector Operator s Manual Part Number: 71-0156RK Revision: 0 Released: 2/16/11 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating

More information

Residential Air Leakage (Blower Door) Testing for Florida Code Compliance

Residential Air Leakage (Blower Door) Testing for Florida Code Compliance June 2018 Residential Air Leakage (Blower Door) Testing for Florida Code Compliance Infiltration or uncontrolled air leakage into buildings is a result of the number and size of cracks and gaps in the

More information

8 5.11: Finned-Tube Coils and Heat Exchangers : Humidifiers and Water Spray Systems : Access for Inspection, Cleaning, and Maintenance

8 5.11: Finned-Tube Coils and Heat Exchangers : Humidifiers and Water Spray Systems : Access for Inspection, Cleaning, and Maintenance Table of Contents 3 Executive Summary 4 Building Overview 5 Mechanical Systems Overview 6 ASHRAE Standard 62.1 2013 Evaluation 6 Section 5: Systems and Equipment 6 5.1: Ventilation Air Distribution 6 5.2:

More information

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School South Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

BUILDING VENTILATION GUIDE FOR LG HVAC SYSTEM INSTALLATION

BUILDING VENTILATION GUIDE FOR LG HVAC SYSTEM INSTALLATION BUILDING VENTILATION GUIDE FOR LG HVAC SYSTEM INSTALLATION PROPRIETARY DATA NOTICE This document, as well as all reports, illustrations, data, information, and other materials are the property of LG Electronics

More information

BEST PRACTICE RECOMMENDATIONS

BEST PRACTICE RECOMMENDATIONS Second and Delaware, Kansas City, MO BEST PRACTICE RECOMMENDATIONS PHIUS 1 OUTLINE VENTILATION & COMPONENT REQUIREMENTS UNDER PHIUS+ COMPARISON TO OTHER VENTILATION STANDARDS: ASHRAE 62.2 2016 ERV/HRV

More information

BUILDING VENTILATION GUIDE

BUILDING VENTILATION GUIDE BUILDING VENTILATION GUIDE PROPRIETARY DATA NOTICE This document, as well as all reports, illustrations, data, information, and other materials are the property of LG Electronics U.S.A., Inc., and are

More information

SYSTEM SOLUTIONS SCHOOLS

SYSTEM SOLUTIONS SCHOOLS SYSTEM SOLUTIONS SCHOOLS Indoor Air Quality that Makes the Grade ehpricedartmouth.com SYSTEM SOLUTIONS SCHOOLS Indoor Air Quality that Makes the Grade THEATRES 3 GYMNASIUMS 5 WOOD SHOPS 7 MECHANICAL SHOPS

More information

Smoke Control Design and Activation. CFAA NCA Technical Seminar 2015

Smoke Control Design and Activation. CFAA NCA Technical Seminar 2015 Smoke Control Design and Activation CFAA NCA Technical Seminar 2015 2 Overview Principles of smoke control Codes CACF controls Programming Commissioning Testing Goals To provide an introduction to smoke

More information

AHRI Guideline W (I-P) 2014 Guideline for Selecting, Sizing, & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment

AHRI Guideline W (I-P) 2014 Guideline for Selecting, Sizing, & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment AHRI Guideline W (I-P) 2014 Guideline for Selecting, Sizing, & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does

More information

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS Presented to: Presented by: Sargon Ishaya, PE www.pragmaticprofessionalengineers.com Introduction Today s Agenda Overview Review

More information

IMC Significant Changes Summary Tier I

IMC Significant Changes Summary Tier I 2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just

More information

MODELS TR & TRC TOTAL RECOVERY FOR ALL CLIMATES RESIDENTIAL OR COMMERCIAL APPLICATIONS

MODELS TR & TRC TOTAL RECOVERY FOR ALL CLIMATES RESIDENTIAL OR COMMERCIAL APPLICATIONS With S&P s TR & TRC (total recovery) Series for all climates, stale room air is exhausted and fresh outdoor air is brought back into the house. These two air streams are directed through a highly developed

More information

Twenty Examples of Design/Construction Issues Impacting IAQ

Twenty Examples of Design/Construction Issues Impacting IAQ Twenty Examples of Design/Construction Issues Impacting IAQ Dale Walsh, MS, CIH, LEED-AP BD+C Walsh Certified Consultants, Inc. Las Vegas, Nevada AIHA GBIAQ Management Planner Registry Team ASTM D22 Air

More information

Existing Conditions Assessment November 14, 2006 NORTH MIDDLESEX REGIONAL HIGH SCHOOL Townsend, MA L21366/ /Page 1

Existing Conditions Assessment November 14, 2006 NORTH MIDDLESEX REGIONAL HIGH SCHOOL Townsend, MA L21366/ /Page 1 L21366/101 090 00.00/Page 1 HVAC EXECUTIVE SUMMARY The North Middlesex Regional High School has received average maintenance of the HVAC systems over its occupied years. Even with adequate maintenance,

More information

Clearing the Air: Ventilation. RESNET Building Performance Conference San Diego, CA February 17 th, 2015

Clearing the Air: Ventilation. RESNET Building Performance Conference San Diego, CA February 17 th, 2015 Clearing the Air: Ventilation RESNET Building Performance Conference San Diego, CA February 17 th, 2015 Agenda Value of mechanical ventilation and indoor air quality. Three major components: Local mechanical

More information

CT-7 Series Toxic Gas Transmitter Operator s Manual

CT-7 Series Toxic Gas Transmitter Operator s Manual 65-2341 CT-7 Series Toxic Gas Transmitter Operator s Manual Part Number: 71-0424 Revision: P1 Released: 6/8/17 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction

More information

Indoor Air Quality Product Brochure.

Indoor Air Quality Product Brochure. Indoor Air Quality Product Brochure Ventilation: A vital system for a healthy home All homes require adequate ventilation for the safety of their occupants and to remove excess humidity, airborne pollutants

More information

RK-05 Carbon Monoxide Detector Operator s Manual

RK-05 Carbon Monoxide Detector Operator s Manual 65-2433RK-05 Carbon Monoxide Detector Operator s Manual Part Number: 71-0189RK Revision: 0 Released: 5/17/11 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual

More information

2006 Building Science Press All rights of reproduction in any form reserved.

2006 Building Science Press All rights of reproduction in any form reserved. building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Building Science Digest 110 HVAC in Multifamily Buildings 2006-10-24 by Joseph Lstiburek Abstract: Are

More information

Dwelling Ventilation Strategies, Including ASHRAE 62.2 ASHRAE Ventilation for Acceptable Indoor Air Quality

Dwelling Ventilation Strategies, Including ASHRAE 62.2 ASHRAE Ventilation for Acceptable Indoor Air Quality Dwelling Ventilation Strategies, Including ASHRAE 62.2 National Weatherization Conference 2005 ASHRAE 62.1 2001 Ventilation for Acceptable Indoor Air Quality Rick Karg 2005 R.J. Karg Associates rjkarg@karg.com

More information

Home Performance Science

Home Performance Science Home Performance Science Symptoms of a Sick House Too hot/too cold rooms Respiratory problems Headaches/nausea Smoky fireplace Foggy windows Stuffy air and lingering odors Peeling paint Constant dust problems

More information

Office and classroom temperatures should average degrees when occupied.

Office and classroom temperatures should average degrees when occupied. Teacher/Staff Procedures Office and classroom temperatures should average 70-76 degrees when occupied. Staff members will be epected to properly manage their classrooms or work areas. This includes shutting

More information

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School North Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

Campus Middle School 4785 South Dayton Street Greenwood Village, Colorado 80111

Campus Middle School 4785 South Dayton Street Greenwood Village, Colorado 80111 Campus Middle School 4785 South Dayton Street Greenwood Village, Colorado 80111 Year Opened 1971 Current Square Footage 175,743 Site Acreage (included in CCHS) 87.22 campus.cherrycreekschools.org $2,441,170

More information

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

USEFUL RESOURCES: Applicability. Item o of section 150. Review-Definitions Section 101

USEFUL RESOURCES: Applicability. Item o of section 150. Review-Definitions Section 101 FUNDAMENTALS of ASHRAE 62.2 2007 VENTILATION AND ACCEPTABLE INDOOR AIR QUALITY IN LOW-RISE RESIDENTIAL BUILDINGS by Joe Kirkpatrick Deputy Building Official City of Irvine jkirkpatrick@ci.irvine.ca.us

More information

RK Hydrogen Sulfide Transmitter Operator s Manual

RK Hydrogen Sulfide Transmitter Operator s Manual 65-2331RK Hydrogen Sulfide Transmitter Operator s Manual Part Number: 71-0176RK Revision: B Released: 11/26/14 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction

More information

Technical Report Three

Technical Report Three Technical Report Three Existing Conditions for Mechanical Systems Contents Executive Summary...2 Building Overview...2 Mechanical Systems Overview...2 Mechanical System...3 Outdoor & Indoor Design Conditions...3

More information

2015 MECHANICAL CODE REQUIREMENTS

2015 MECHANICAL CODE REQUIREMENTS 2015 MECHANICAL CODE REQUIREMENTS ANTRIM COUNTY BUILDING DEPARTMENT PO BOX 188 205 CAYUGA STREET BELLAIRE, MI 49615 (231) 533-8373 FAX (231) 533-6041 Mechanical requirements for residential buildings per

More information

Ventilation System Description. September 8, 2000 HETA

Ventilation System Description. September 8, 2000 HETA September 8, 2000 HETA 99-0250 Harry Enoch, Ph.D. Director, Environmental Health and Safety University of Kentucky 252 East Maxwell Street Lexington, KY 40506-0314 Dear Dr. Enoch: On June 7, 1999, the

More information

Safety, Installation, and Operation Manual

Safety, Installation, and Operation Manual Automatic Steam Humidifier Control Safety, Installation, and Operation Manual READ COMPLETE INSTALLATION INSTRUCTIONS BEFORE STARTING. WARNING This product must be installed by a qualified heating and

More information

Ventilation and Indoor Air Quality

Ventilation and Indoor Air Quality Ventilation and Indoor Air Quality Funding Funding for this class was provided by the Alaska Housing Finance Corporation (AHFC). This course is designed to empower homeowners with the knowledge to live

More information

LIMITED MICROBIAL & IAQ SURVEY CLOSING REPORT SOUTHEASTERN SCHOOL DISTRICT 02/12/2015

LIMITED MICROBIAL & IAQ SURVEY CLOSING REPORT SOUTHEASTERN SCHOOL DISTRICT 02/12/2015 HOME OFFICE PO Box 326 MT AETNA PA 19544 MEMBERS OF: VOICE 717-933-9475 FAX 717-933-1403 TOLL FREE 877-255-0558 Web Page: proaccorp.com CLOSING REPORT SOUTHEASTERN DISTRICT 02/12/2015 PROJECT LOCATION:

More information

North Dakota State University Laser Safety

North Dakota State University Laser Safety North Dakota State University Laser Safety I. Introduction The laser represents a class of light emitting devices with unique characteristics. Some of these characteristics can result in significant hazards.

More information

3 Macurco Carbon Monoxide Detector CM-16A

3 Macurco Carbon Monoxide Detector CM-16A 3 Macurco Carbon Monoxide Detector CM-16A User Instructions for 3M Macurco Carbon Monoxide Detector (CO) CM-16A FOR MORE INFORMATION In United States, contact: Website: www.3m.com/occsafety Technical Assistance:

More information

ENERGY STAR SUMMIT DECEMBER 6, 2006 ENERGY STAR INDOOR AIR PACKAGE

ENERGY STAR SUMMIT DECEMBER 6, 2006 ENERGY STAR INDOOR AIR PACKAGE ENERGY STAR SUMMIT DECEMBER 6, 2006 ENERGY STAR INDOOR AIR PACKAGE OUTLINE What s s so important about IAQ? What is the Indoor Air Package? How does it work? Sales Tools WHAT ARE BUILDINGS FOR? People

More information

ASHRAE JOURNAL ON REHEAT

ASHRAE JOURNAL ON REHEAT Page: 1 of 7 ASHRAE JOURNAL ON REHEAT Dan Int-Hout Chief Engineer Page: 2 of 7 Overhead Heating: A lost art. March 2007 ASHRAE Journal Article Dan Int-Hout Chief Engineer, Krueger VAV terminals provide

More information

Trials of Vexo inhibitor in domestic central. heating systems

Trials of Vexo inhibitor in domestic central. heating systems Trials of Vexo inhibitor in domestic central heating systems by Rayner Mayer d25.03.2013 Executive summary A new type of inhibitor has been formulated by VEXO International to improve the efficiency of

More information

Maintenance Matters. Maintaining Your Heat Recovery Ventilation System

Maintenance Matters. Maintaining Your Heat Recovery Ventilation System NUMBER 16 Maintenance Matters BUILDING MAINTENANCE BULLETIN Maintaining Your Heat Recovery Ventilation System New homes are built to be airtight to reduce heat loss and potential moisture damage to the

More information

OPERATION, INSTALLATION AND MAINTENANCE INSTRUCTIONS SERIES INTERCEPTORS

OPERATION, INSTALLATION AND MAINTENANCE INSTRUCTIONS SERIES INTERCEPTORS OPERATION, INSTALLATION AND MAINTENANCE INSTRUCTIONS 5400-5500 SERIES INTERCEPTORS 5401 75 4NH 5500 50 3IPS INSTALLATION Place the Wade interceptor downstream of the drain which will supply the oil laden

More information

SYSTEM SOLUTIONS SCHOOLS

SYSTEM SOLUTIONS SCHOOLS SYSTEM SOLUTIONS SCHOOLS Indoor Air Quality that Makes the Grade ehpricehamilton.com ehpriceoshawa.com ehpriceottawa.com ehpricesouthwesternontario.com ehpricetoronto.com SYSTEM SOLUTIONS SCHOOLS Indoor

More information

Medical Gas Inspections and Maintenance Programs. HESNI Annual Conference NIU Conference Center May 10-11, 2018 Presented by Mathis Carlson

Medical Gas Inspections and Maintenance Programs. HESNI Annual Conference NIU Conference Center May 10-11, 2018 Presented by Mathis Carlson Medical Gas Inspections and Maintenance Programs HESNI Annual Conference NIU Conference Center May 10-11, 2018 Presented by Mathis Carlson Mathis Carlson I have worked for the last 15+ years in the Medical

More information

RK/ RK Oxygen Detector Operator s Manual

RK/ RK Oxygen Detector Operator s Manual 65-2494RK/65-2497RK Oxygen Detector Operator s Manual Part Number: 71-0179RK Revision: 0 Released: 2/16/11 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating detector.

More information

Heat Recovery Ventilator Model PVe Light Industrial Commercial Institutional

Heat Recovery Ventilator Model PVe Light Industrial Commercial Institutional Heat Recovery Ventilator Model PVe Light Industrial Commercial Institutional 1,000-6,000 cfm 2.0 in. wg External Static Pressure Aluminum Plate Heat Exchanger April 2017 Heat Recovery Ventilators Greenheck

More information

IT S HOT UP HERE! A STUDY OF THERMAL COMFORT IN THE LILLIS BUSINESS COMPLEX 4TH FLOOR OFFICES

IT S HOT UP HERE! A STUDY OF THERMAL COMFORT IN THE LILLIS BUSINESS COMPLEX 4TH FLOOR OFFICES IT S HOT UP HERE! A STUDY OF THERMAL COMFORT IN THE LILLIS BUSINESS COMPLEX 4TH FLOOR OFFICES Martha Bohm M.Arch Candidate 2006 University of Oregon Eugene, OR 97403 Will Henderson M.Arch Candidate 2006

More information

The Heating System and Ventilation and Combustion Air

The Heating System and Ventilation and Combustion Air The Heating System and Ventilation and Combustion Air Introduction Both you and your furnace need some fresh air coming into the house, but most Canadian homes have too much. In fact, 25 percent or more

More information

Topic: Mechanical Ventilation Refresher Reference #: DG Level of Instruction: In service personnel Time Required: 3 hours

Topic: Mechanical Ventilation Refresher Reference #: DG Level of Instruction: In service personnel Time Required: 3 hours Topic: Mechanical Ventilation Refresher Reference #: DG 14-07 Level of Instruction: In service personnel Time Required: 3 hours Instructor Preparation: The purpose of this drill is to conduct refresher

More information

Home Set-up and Maintenance. Maintenance

Home Set-up and Maintenance. Maintenance Home Set-up and Maintenance Home Set-up and Maintenance When moving into a resale home, there are some things that you will want to take care of. This list focuses on things related to the house, rather

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Balancing Air Systems: a. Constant-volume air systems. b. Variable-air-volume systems. 2.

More information

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL SECTION 15100 PART 1 GENERAL THIS IS A DESIGN GUIDE NOT A SPECIFICATION Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL HVAC SYSTEMS APPLICATIONS 1.1 SCOPE: The intent of this

More information

WORKSHOP VENTILATION- PSYCHROMETRICS-AHU

WORKSHOP VENTILATION- PSYCHROMETRICS-AHU Alkis Triantafyllopoulos Mechanical Engineer Member TEE, MASHRAE a.trianta@gmail.com WORKSHOP VENTILATION- PSYCHROMETRICS-AHU Based on ASHRAE 62 Purpose Set minimum Outdoor Air ventilation Rates Air Quality

More information

Chapter Eight RESNET Standards

Chapter Eight RESNET Standards Chapter Eight RESNET Standards Effective Date This chapter goes into effect on January 3, 2012 800 RESNET Standard for Performance Testing and Work Scope: Enclosure and Air Distribution Leakage Testing

More information

Our energy efficient experts and engineers have made ground breaking innovations in this field.

Our energy efficient experts and engineers have made ground breaking innovations in this field. Company Profile Introduction: We are pleased to introduce ourselves as MAFNA Air Technologies Inc., established in 1999. MAFNA Air Technologies Inc, is Canada's leading manufacturer and supplier of Air

More information

INDOOR AIR QUALITY ASSESSMENT. Department of Revenue Office 218 South Main Street Fall River, MA

INDOOR AIR QUALITY ASSESSMENT. Department of Revenue Office 218 South Main Street Fall River, MA INDOOR AIR QUALITY ASSESSMENT Department of Revenue Office 218 South Main Street Fall River, MA Prepared by: Massachusetts Department of Public Health Bureau of Environmental Health Indoor Air Quality

More information

Air Conditioning Refrigeration Electrical Work TEL: 0(204) (254)

Air Conditioning Refrigeration Electrical Work TEL: 0(204) (254) Quality is key INTRODUCTION We focus in; + Hotels and Leisure + Hospitals and Health clinics + Education institutions + Industrial zones + Government Institutions + Cultural and religious places HVAC REFRIGERATION

More information

RADON PLAN. Eugene School District 4J Facilities Management 715 West Fourth Avenue Eugene, OR

RADON PLAN. Eugene School District 4J Facilities Management 715 West Fourth Avenue Eugene, OR RADON PLAN The 2015 Legislature passed House Bill (HB) 2931 so that if elevated radon levels in Oregon schools existed they would be known. House Bill 2931 later became Oregon Revised Statute (ORS) 332.166-167.

More information

A Necessity for Preventing Unsafe Backdrafts and Unhealthy Air

A Necessity for Preventing Unsafe Backdrafts and Unhealthy Air Residential Make-up Air Unit A Necessity for Preventing Unsafe Backdrafts and Unhealthy Air Today s homes are tighter than ever before; as well they should be: Proper sealing yields efficiency and comfort

More information

Conducting and Assessing Radon Surveys in Schools & Commercial Buildings

Conducting and Assessing Radon Surveys in Schools & Commercial Buildings Conducting and Assessing Radon Surveys in Schools & Commercial Buildings CIHC 2015 Annual Conference December 7, 2015 Gustavo A. Delgado, Ph.D. California Radon Measurement Provider Forensic Analytical

More information

Level I Chapter 1 Worksheet

Level I Chapter 1 Worksheet Chapter 1 Worksheet 1. For applicability requirements of the Plumbing Code, refer to: a. Building Code b. Administration and Enforcement Code c. Plumbing Code d. Residential Code 2. The provisions of the

More information

RK Carbon Monoxide Transmitter Operator s Manual

RK Carbon Monoxide Transmitter Operator s Manual 65-2432RK Carbon Monoxide Transmitter Operator s Manual Part Number: 71-0070RK Revision: P1 Released: July 8, 2001 RKI Instruments, Inc. 1855 Whipple Road Hayward CA 94544 Phone: 800-754-5165 Fax: 510-441-5650

More information

RK Carbon Monoxide Transmitter Operator s Manual

RK Carbon Monoxide Transmitter Operator s Manual 65-2434RK Carbon Monoxide Transmitter Operator s Manual Part Number: 71-0061RK Edition: First, Revision C Released: December 2001 65-2434RK CO Transmitter 1 Product Warranty RKI Instruments, Inc., warranties

More information

RK-03 Hydrogen Detector Operator s Manual

RK-03 Hydrogen Detector Operator s Manual 61-1001RK-03 Hydrogen Detector Operator s Manual Part Number: 71-0371 Revision: P1 Released: 5/26/15 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating detector.

More information

WHOLE-HOUSE VENTILATION SYSTEMS

WHOLE-HOUSE VENTILATION SYSTEMS Technology Fact Sheet WHOLE-HOUSE VENTILATION SYSTEMS Improved control of air quality Buildings for the 21st Century Buildings that are more energy-efficient, comfortable, and affordable that s the goal

More information

MultiFamily Ventilation Updates: ASHRAE 62.2, Best Practices and Practical Applications RESNET Conference Atlanta, GA

MultiFamily Ventilation Updates: ASHRAE 62.2, Best Practices and Practical Applications RESNET Conference Atlanta, GA MultiFamily Ventilation Updates: ASHRAE 62.2, Best Practices and Practical Applications 2014 RESNET Conference Atlanta, GA Ray Ivy and Mike Barcik Southface 1 About Southface 2 Topics Covered How to use

More information