Smoke Control Design and Activation. CFAA NCA Technical Seminar 2015
|
|
- Alicia Short
- 6 years ago
- Views:
Transcription
1 Smoke Control Design and Activation CFAA NCA Technical Seminar 2015
2 2 Overview Principles of smoke control Codes CACF controls Programming Commissioning Testing Goals To provide an introduction to smoke control To share best practices Format Open format. Questions and comments are welcome during the presentation.
3 3 Principles of smoke control Maintain tenability for occupant evacuation and firefighting activities - Occupant Evacuation... shall be designed so that, during a period of 2 h after the start of a fire will not contain more than 1% by volume of contaminated air from the fire floor, assuming an outdoor temperature equal to the January design temperature on a 2.5% basis... Contaminated air is taken to mean air with products of combustion The difference in temperature between the outside and inside of a building affects the pressure difference between contaminated air and clear air.» affects the maximum height that a system can maintain both a minimum and maximum pressure difference across doorway boundaries.
4 4 Why is Smoke Control required in buildings? Smoke spreads quickly in a fire - Station Nightclub (2003) Recreation with sprinklers Recreation without sprinklers Smoke affects occupants remote from a fire - MGM Grand (1980) 68 of 85 deaths at levels stories above the fire How are we doing with implementation? Not well understood Not well implemented Poorly maintained
5 5 How is smoke control implemented? Compartmentation Dilution Pressurization Buoyancy Airflow Compartmentation Design rooms and floor areas with a limited amount of leakage and the strength to withstand pressures developed in a fire. Dilution Exhaust contaminated air and introduce fresh air into a space - Used for interconnected floor spaces - Used for venting by firefighters after extinguishment
6 6 How is smoke control implemented (cont.)? Dilution Example - How long would it take to reduce the concentration of contaminated air to 1% of its post fire concentration using a flow rate of 6 air changes per hour? t = 1 α ln C 0 C t Where a = air changes per minute t = time in minutes C t = concentration at time t C 0 = initial concentration t = ln = 46 minutes
7 7 How is smoke control implemented (cont.)? Pressurization Use fans to keep protected spaces and higher pressures than fire areas. Buoyancy Smoke shafts open to the exterior that depend on the buoyancy of smoke. Airflow Maintain minimum air flow speeds to overcome the buoyant forces developed by a fire and keep smoke from spreading. Used in tunnels
8 8 Codes High Buildings [subsection 3.2.6] - Stair pressurization - Elevator/Shaft protection - Zoned smoke management - Smoke venting Interconnected Floor Areas [subsection 3.2.8] Both prescriptive and performance options are available to designers
9 9 Code prescriptive requirements High Buildings [subsection 3.2.6] OBC Supplementary Standard SB-4, NBCC Appendix B - Below grade stair pressurization [SB-4 & (2)] At the bottom with 0.47 m 3 /s for each storey served by stair Vent at the top with 0.1 m 2 of vent area for each storey served by stair Vent area reduced by the number of doors open to stair. - Above grade stair venting [ (3)] At the bottom to be opened manually and remain open 0.05 m 2 per door opening into the stair but not less than 1.8 m 2 in area
10 10 More code prescriptive requirements High Buildings [subsection 3.2.6] OBC Supplementary Standard SB-4, NBCC Appendix B - Connected buildings [ (1)] Vented to outdoors or pressurized to maintain min DP 12 Pa - Venting to aid firefighting [ ] Windows, panels, dedicated smoke shafts or the building HVAC system can be used Where HVAC system used, 6 air changes per hour from any floor to be maintained during venting operations (example previous slide) Where smoke shaft is used, smoke detector in shaft to operate opening to exterior at the top of the shaft. Smoke damper into shaft on fire floor controlled at CACF.
11 11 Even more code prescriptive requirements Interconnected Floor Spaces [subsection 3.2.8] - Smoke exhaust at 4 to 6 air changes per hour - Makeup air speed 1 m/s (4000 cfm/door) - Stair venting for lower buildings (18m + ) - Stair vestibules vented or pressurized for higher buildings (75 m + ) - Group B sleeping room vestibules pressurized - Zoned smoke exhaust at 6 air changes per hour option Permits reduction in volume of smoke exhaust in atrium Parking garage vestibule ventilation [ (4)] - Naturally with vent to the outdoors, with min area of 0.4m 2, or - Mechanically with 14m 3 /h flow for each m 2 of vestibule floor area Smoke protected seating areas [ (14)] Vertically separated buildings [ (6) SB-4 Measure K] - For unsprinklered buildings - Vestibules for firefighters elevators - Areas of refuge
12 12 Code performance options Zoned smoke control - Pressurize non-fire floors (either all or just those adjacent) - Exhaust fire floor causing negative pressure and therefore, relative positive pressure on non-fire floors Stair pressurization instead of venting - Pressure modulation using barometric dampers, or variable flow fans Smoke layer height management - For large volume spaces like arenas - Maintain smoke layer height above the highest level of occupants not protected from smoke.
13 13 Equipment for smoke control - Fire alarm controls
14 14 Equipment for smoke control - ULC listed for smoke control [category UUKLC]. - Testing criteria are ULC-S527, Control Units for Fire Alarm Systems, and ULC/ORD-C100-13, Smoke Control System Equipment. Supervision of inputs and outputs Confirmation of operation
15 15 Equipment for smoke control Is one better than the other? - Fire alarm for simple on/off controls - Automation equipment for everything else - Example HVAC used for venting to aid firefighting
16 M3-32 PRIMARY C10W1 G10 ELEVATOR RECALL RELAY M6-3 PRIMARY C10WB J8 ELEV MACH. RM - RECALL M3-92 RELAY C10W1 ELEVATOR MACH. ROOM M6-6 RELAY C10WB J9 ELEV MACH. ROOM M1-97 RELAY C10E1 B19 CONTROL GND EAST NORTH SMK EXH M7-54 RELAY C10E1 C16 GND EAST NORTH SMK EXH#15 M1-96 RELAY C10E1 E23 GND EAST SOUTH SMK EXH#19 ON M1-98 RELAY C10E1 D19 CONTROL GND EAST SOUTH SMK EXH M5-101 RELAY C10WP J4 SMOKE EXHAUST EF-20 START-UP M8-55 RELAY C10W1 G5 LIEBERT SHUTDOWN M3-45 RELAY C10W1 K5 AC UNITS SOUTH SIDE FAN S/DOWN M3-46 RELAY C10W1 M5 EXHAUST SOUTH SIDE START-UP M3-80 RELAY C10W1 H5 RM 1079 NORTH HI TEMP DC S/DOWN M3-81 RELAY C10W1 H5 RM 1079 SOUTH HI TEMP DC S/DOWN M2-79 RELAY C10EP D16 A03- AHU01,A03-RAF01 SHUTDOWN M2-91 RELAY C10EP D20 A03- RAF01,A03-AHU02 SHUTDOWN M5-77 RELAY C10WP K5 A01- RAF01,A01-AHU01 SHUT DOWN M5-81 RELAY C10WP K8 A01- RAF02,A01-AHU02 SHUTDOWN Smoke Control Design and Activation 16 Programming for smoke control Specifications Control Matrix (don t forget the manual controls) Don t wait until installation to test the matrix ADDRESS ELEV RECALL SMOKE EXHAUST DC SHUT AHU SHUTDOWN ALARM &SMOKE CONTROL OPERATION SYSTEM RESET OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF L18 GENERAL FIRE ALARM L18 ACTIVE ACTIVE M3-31 C10W1 G10 ELEV.MACHINE RM SMOKE M3-31 ACTIVE M6-2 C10WB J8 ELEV MACH. RM SMOKE M6-2 ACTIVE LAB 10 EAST NORTH MANUAL SMOKE EXH SWITH LAB 10 PULL STATION EAST NORTH UP/DOWN ON/OFF ON/OFF ` M1-80,M7-20,M7-36 ANY TWO FIRE IN LIST144 L144 ON ON LAB 10 EAST SOUTH MANUAL SMOKE EXH UP/DOWN ON/OFF ON/OFF SWITH LAB 10 PULL STATION EAST SOUTH M1-70,M1-26 ON ON ANY TWO FIRE IN LIST145 L145 ON ON LAB 10 WEST NORTH MANUAL SMOKE EXH UP/DOWN ON/OFF ON/OFF SWITH M3-65,M8-56, LAB 10 PULL STATION WEST NORTH ON ON M8-57,M8-63 ANY TWO FIRE IN LIST146 WEST NORTH L146 ON ON ACTIVE LAB 10 WEST SOUTH MANUAL SMOKE EXH UP/DOWN ON/OFF ON/OFF SWITH LAB 10 PULL STATION WEST SOUTH M3-49 M3-67 ON ON ANY TWO FIRE IN LIST147 WEST SOUTH L147 ON ON ACTIVE M2-81 C10EP C16 DUCT SMOKE A03-RAF01 M2-81 ACTIVE ON M2-89 C10EP C20 DUCT SMOKE A03-RAF01 M2-89 ACTIVE M5-76 C10WP J4 A01-AHU01 DUCT SMOKE M5-76 ACTIVE ON M5-80 C10WP J8 A01-AHU02 DUCT SMOKE M5-80 ACTIVE
17 17 Commissioning for smoke control Integration with other systems to be commissioned together [ ] CAN/ULC S , Standard for Integrated Systems Testing of Fire Protection and Life Safety Systems Fan # Operation During Alarm Point # Occupied Operation Location Supply Return Supply Rtrn. Supply Return West 1 st Floor M1-1 On On Shut down West - 23 n/a M1-36 On On Shut down Mezzanine West - 2 nd Floor M1-57 On On Off Shut Down West 3 rd Floor M1-91 On On Shut On Down West 11 th Floor M4-61 Off On West 12 th Floor Smoke Evac. * On Shut Down of both fans, supply should have remained operational West 12 th Floor M5-1 On Shut Down both fans West - Penthouse 52 M5-61 Off Started West - Penthouse 50, 51 M5-62 Off Started x 2
18 18 Commissioning for smoke control Integration with other systems to be commissioned together [ ] CAN/ULC S , Standard for Integrated Systems Testing of Fire Protection and Life Safety Systems
19 19 Testing for smoke control NBC and OBC [ ], NFC and OFC [Part 7] Establish requirements for prescriptive solutions Where alternate measures are implemented - NFC leaves it to the fire safety plan - OFC requires professional engineer or architect who designed the system to seal the testing procedure Caution: don t let the design professional get away without developing a test protocol to be sealed and included in the fire safety plan
20 20 Further reading SFPE Handbook of Fire Protection Engineering (fifth edition to be published soon). Principles of Smoke Management, J.H. Klote + J.A. Milke Questions? William Kuffner, M.A.Sc., P.Eng, PMP Director, Fire Protection Engineering william.kuffner@wspgroup.com (613) ext 19247
COMMISSIONING OF LIFE SAFETY AND FIRE PROTECTION SYSTEMS: WHAT, WHERE AND HOW?
COMMISSIONING OF LIFE SAFETY AND FIRE PROTECTION SYSTEMS: WHAT, WHERE AND HOW? By: Ark Tsisserev, P.Eng. Senior Technical Manager Applied Engineering Solutions Ltd. CFAA Technical Seminar April 15, 2015
More information2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014
2012 OBC Changes Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014 2012 OBC New Sentence 3.2.4.2(6) Buildings interconnected by walkways permitted in Articles
More informationCFAA Technical Seminar Ontario Building Code Updates to 2015
CFAA Technical Seminar Ontario Building Code Updates to 2015 October 28, 2015 2015 Fire Alarm Updates Ontario Building Code Glenn Somerton P.Eng. Senior Code Specialist Morrison Hershfield Limited gsomerton@morrisonhershfield.com
More informationBOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015
Exam ID Examination Code Part BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015 BC3-7 Level III Exam 7 BCBC Part 3 (Part 3 Buildings Classification & Construction) BC3-8 Level III Exam 8 BCBC
More informationENERGY EFFICIENCY AFTER DECEMBER 31, 2016
MODULE 2 Energy Efficiency INTRODUCTION In this module the requirements for energy efficiency in buildings is examined with particular attention to the Supplementary Standard to the OBC, SB-10, Energy
More informationMODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces
MODULE 8 Tying the Systems Together: Emergency Control Functions and Interfaces 1 OVERVIEW OF MODULE 8 In this module we will: Describe all components, their arrangements and how the systems work Describe
More informationCAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS
RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY
More informationSmoke Management in High-Rise Structures
Smoke Management in High-Rise Structures Most modern building codes define a high-rise structure as a building greater than 75 feet in height from the lowest level of fire department vehicle access to
More informationANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS
ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS Prepared for Smoke Safety Council 6775 SW 111 th Avenue, Suite 10 Beaverton, OR 97008 Prepared by Jesse J. Beitel Alison J. Wakelin Craig L.
More informationCAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning
CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) National Capital Region
More informationRecent Revisions and Proposed Key Changes to Fire Code
Recent Revisions and Proposed Key Changes to Fire Code 2014 CFAA Presentation Kim Bailey - Office of the Fire Marshal and Emergency Management New Section 9.7 Buildings with a Care Occupancy or Retirement
More informationEdward K. Budnick Hughes Associates, Inc. Wheaton, Maryland, U.S.A SUMMARY. that is entrained or otherwise mixed into the mass.
THE CAPABILITIES OF SMOKE CONTROL: FUNDAMENTALS AND ZONE SMOKE CONTROL John H. Klote Center for Fire Research National Institute of Standards and Technology Gaithersburg, Maryland, U.S.A. 20899 Edward
More information150 Elgin - Office Tower and Grant House Renovations
APPLICATION OF THE ONTARIO BUILDING CODE 150 Elgin - Office Tower and Grant House Renovations 150 Elgin Street Ottawa, Ontario Presented to: Mr. Brandon Donnelly Morguard Investments Limited c/o Mr. Harry
More informationFire Signal Receiving Centres vs. Proprietary Fire Signal Receiving Centres CAN/ULC-S561 ALAN CAVERS ULC
Fire Signal Receiving Centres vs. Proprietary Fire Signal Receiving Centres CAN/ULC-S561 ALAN CAVERS ULC Reliable Fire Alarm Monitoring Why is it important? Codes and Standards? What is a fire alarm monitoring?
More informationCOURSE SYLLABUS HVAC AND MECHANICAL CONSIDERATIONS FOR PART 3 BUILDINGS CORRESPONDENCE COURSE
COURSE SYLLABUS HVAC AND MECHANICAL CONSIDERATIONS FOR PART 3 BUILDINGS CORRESPONDENCE COURSE 100126 The course is organized into three bands. Band A covers HVACrelated building components and other types
More informationCAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS
2013 Randal Brown & Associates Engineering Ltd. 1 RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001-11 INTEGRATED
More informationELEVATORS AND FIRE ALARM SYSTEM INTERFACES CANADIANFIRE ALARM ASSOCIATION 2011 ONTARIO ANNUAL TECHNICAL SEMINAR
ELEVATORS AND FIRE ALARM SYSTEM INTERFACES CANADIANFIRE ALARM ASSOCIATION 2011 ONTARIO ANNUAL TECHNICAL SEMINAR 1 PRESENTED BY SIMON CROSBY, CET, CFPS RANDAL BROWN & ASSOCIATESLTD. 416-492-5886 X234 SCROSBY@RBACODES.COM
More information2014 Alberta Building Code. Part 9 changes relating to Smoke and CO Alarms
2014 Alberta Building Code Part 9 changes relating to Smoke and CO Alarms 9.32.3.9 Carbon Monoxide Alarms What has not changed: 4) & 6) In a residential occupancy containing a fuel burning appliance or
More informationLife Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering
Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015 Peter McDonnell, PE, LEED AP BD+C McClure Engineering UL DAMPER TEST STANDARDS UL 555 - FIRE DAMPERS UL555S SMOKE DAMPERS UL555C CEILING
More informationTechnical Information
How to design easily a smoke management system? Mechanical smoke extraction for enclosed car park Car park: specificity of the smoke extraction system Car parks are nowadays integrated directly inside
More informationAir Change, Ventilation, and Dehumidification for Multi-family Buildings
Air Change, Ventilation, and Dehumidification for Multi-family Buildings Armin Rudd Corp www.buildingscience.com for Acknowledgments: USDOE Building America Joseph Lstiburek, Peter Baker, Kohta Ueno--BSC
More informationModule 7. Control of Smoke & Highlights of Code Requirements
Module 7 Control of Smoke & Highlights of Code Requirements 1 Module 7 Overview This module will cover: 1. The requirements of smoke control in the Ohio Building Code Section 909 2. The differences between
More informationICC CODE CORNER 2012 IFC Code & Commentary
SECTION 909 SMOKE CONTROL SYSTEMS 909.1 Scope and purpose. This section applies to mechanical or passive smoke control systems when they are required for new buildings or portions thereof by provisions
More informationOBC INDUSTRIAL CLASSIFICATION OBOA ANNUAL MEETING AND TRAINING SESSIONS LONDON ON OCTOBER 4, 2011
OBC INDUSTRIAL MAJOR OCCUPANCY CLASSIFICATION OBOA ANNUAL MEETING AND TRAINING SESSIONS LONDON ON OCTOBER 4, 2011 Randal Brown & Associates Ltd. 2011 1 PRESENTERS RANDAL BROWN P.ENG., PE, BDS, FSPFE PRESIDENT
More information2012 B.C. Building Code Compliance Review (Division B Part 3)
Planning and Building Department 2012 B.C. Building Code Compliance Review PROJECT NAME:.. CIVIC ADDRESS:...... PERMIT APPLICATION NO.:. DATE:... I,, have: 1. reviewed the design, plans and supporting
More informationSteven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION
Steven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION Mid-Rise Workshop, Coast Plaza Inn, Calgary, Feb. 4 th, 2016 Outline Overview of risks Regulations Changes to 2015 NFC for mid-rise
More informationAIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems
233100 AIR DISTRIBUTION PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 230700 HVAC Insulation B. Section 237300 Air Handling C. Section 230900 Building Automation and Control System Guidelines D. Section
More informationBall State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Smoke, Not Flame
SMOKE CONTROL Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Smoke, Not Flame The most significant cause of death in building fires is smoke, which accounted for 73% of fire-related deaths
More informationBCBC 2012 CHANGES TO PART 3
BCBC 2012 CHANGES TO PART 3 Focus on changes that will have an practical effect. Basic concepts reviewed details to be confirmed. Material from Part 3 and related material from Part 9 Generally a harmonization
More informationBUILDING CODE COMMISSION
Ruling No. 03-30-928 Application No. 2003-34 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.1.8.12.(1)
More informationCAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015
CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015 Fire Commissioning in Canadian Codes and Standards BACKGROUND Why Commissioning?
More informationOpen to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP
Open to Below: A Discussion of Allowed Floor Openings Kevin S. Hastings, P.E., LEED AP Jay A. Ierardi, Ph.D., P.E., LEED AP R.W. Sullivan Engineering (617) 523-8227, Fax (617) 523-8016 http://www.rwsullivan.com
More informationSMOKE CONTROL: ISSUES / APPROACHES. Smoke, Not Flame
SMOKE CONTROL: ISSUES / APPROACHES Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Smoke, Not Flame The most significant cause of death in building fires is smoke, which accounted for 73% of
More informationJCI - Smoke Control Systems Overview 10/27/2016
If the you can read this Click on the icon to choose a picture or To Reset: Right click on the slide thumbnail and select reset slide or choose the Reset button on the Home ribbon (next to the font choice
More informationFEO Initiation Devices Dean McLellan
FEO Initiation Devices Dean McLellan Enforcement Protocol 1. TSSAct 2. Ontario Regulation 209/01 3. Code Adoption Document (CAD) 4. Director s Orders 5. Applicable Code 1. Sub Codes (NBCC, CEC) A17/B44
More informationCAN/ULC-S561. To comply, or not to comply. actually it s not even a question! Underwriters Laboratories of Canada. By Alan Cavers & Brian McBain
CAN/ULC-S561 To comply, or not to comply. actually it s not even a question! By Alan Cavers & Brian McBain CAN/ULC-S561, Installation And Services For Fire Signal Receiving Centres And Systems is without
More informationSmoke Management Application Guide Rev. D
Smoke Management Application Guide 574-465 Rev. D Acknowledgements Acknowledgements Tyco Safety Products Westminster, gratefully acknowledges the contributions of the following organizations to this publication:
More informationCOST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS
, Volume 1, Number 3, p.123-128, 1999 COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS D. Yung and G.V. Hadjisophocleous Fire Risk Management Program, Institute for Research
More information2011 Manitoba Energy Code for Buildings (MECB) PART 5, Heating, Ventilating and Air-conditioning Systems
2011 Manitoba Energy Code for Buildings (MECB) PART 5, Heating, Ventilating and Air-conditioning Systems Dieter Bartel, Manitoba Hydro September 17 th, 2014 Outline Scope and compliance Prescriptive path
More informationClarification. Summary of Changes. Summary of Changes. Alan Cavers Area Manager Fire & Security Systems Group
Summary of Changes CAN/ULC-S524-06 Installation of Fire Alarm Systems Alan Cavers Area Manager Fire & Security Systems Group Course Title Rev Date: Summary of Changes Correct Deficiencies noted CAN/ULC-S524-01
More informationPart 3 BUILDING CODE MYTHS & INTERPRETATIONS
Part 3 BUILDING CODE MYTHS & INTERPRETATIONS November 18, 2016 Frank Durante, RBO Building Inspector District of Mission Phone 604 820 3729 Wendy Morrison, AScT, BCQ GHL CONSULTANTS LTD Fire Science and
More informationBuilding & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!
Building & Fire Code Academy Building Better With Our Greatest Resource Education Welcome! Understanding the Sprinkler System Design Alternatives in the 2015 International Why inspect, test and maintain?
More informationSmoke Control Requirements for New Railway Infrastructure. Ir Peter Law
Smoke Control Requirements for New Railway Infrastructure Ir Peter Law Overview Railway Development in Hong Kong Regulatory Regime for Railway Fire Safety Formulation of Fire Safety Requirements Smoke
More informationSECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL
SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division
More informationTunnel Fire Dynamics and Evacuation Simulations
Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation
More informationCommon Building Code Misinterpretations
Common Building Code Misinterpretations Presented by: Ron Melucci, P.E. Technical Manager, FP Division Engineering Planning and Management, Inc. rbm@epm inc.com www.epm inc.com 508 875 2121 Engineering
More informationStairwell Pressurization Systems
Course No: M05-022 Credit: 5 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774 info@cedengineering.com Introduction
More informationCOURSE SYLLABUS FIRE ALARM AND FIRE SUPPRESSION SYSTEMS CORRESPONDENCE COURSE
COURSE SYLLABUS FIRE ALARM AND FIRE SUPPRESSION SYSTEMS CORRESPONDENCE COURSE 100130 Description The first part of the course presents the requirements for fire alarm systems. It describes the buildings
More informationComputing Services Center
Continuous Commissioning Report for the Computing Services Center Building #516 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory
More informationFire Alarm System Fundamentals
Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom
More informationProject No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10
Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction
More informationThe project scope work is 90% new construction and 10% remodel in Esslinger Hall.
CREIGHTON ENGINEERING INC. FIRE PROTECTION CONSULTING ENGINEERS 210 N. University Road, Suite 100 Spokane Valley, WA 99206 TEL: 509.921.9755 FAX: 509.921.9806 WEB: www.creightoneng.com SCOTT R. CREIGHTON,
More informationShort Term Accommodations Fire Code Requirements
Short Term Accommodations Fire Code Requirements 1 Foreward The following is a comprehensive reference to Retrofit 9.3 of Division B of the Ontario Fire Code (OFC). Retrofit provisions were developed to
More informationFIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES
FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES 1. The major objective is to provide an acceptable degree of life safety from fire in existing senior citizen lodges. This document
More informationWORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES
1 WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES TABLE 2.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF (1) ASSEMBLIES (Applies to each fire zone)
More informationLABOUR PROGRAM. 14 TH ANNUAL OFNTSC TECHNICAL CONFERENCE AND TRADESHOW August 25, 2009
14 TH ANNUAL OFNTSC TECHNICAL CONFERENCE AND TRADESHOW August 25-27, 2009 National Building Code and National Fire Code Requirements for Schools and Arenas by Alexandra Chow, P.Eng. Fire Protection Engineering
More information2012 Ontario Building Code Update
2012 Ontario Building Code Update Presented to NORR Dec. 10, 2013 Alek Antoniuk, OAA 2013 Agenda Selected highlights of changes in the 2012 Ontario Building Code related to larger (Pt. 3) buildings O.
More informationLife Safety - Means of Egress/Exits NFPA 101
Life Safety - Means of Egress/Exits NFPA 101 Properly designed exits provide a safe path of escape from a fire or other emergency environment. The means of egress (exits) should be arranged to permit all
More informationAUSTIN FIRE DEPARTMENT SIA PROCEDURES FOR ANNUAL TESTING OF BUILDINGS WITH STAIRWELL AND VESTIBULE PRESSURIZATION SYSTEMS
AUSTIN FIRE DEPARTMENT SIA PROCEDURES FOR ANNUAL TESTING OF BUILDINGS WITH STAIRWELL AND VESTIBULE PRESSURIZATION SYSTEMS Building stairwell and vestibule pressurization systems must be retested and recertified
More informationCHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION
- 165 - CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT
More informationAir Moving Systems. Fire Safety Inspection and Testing of. NBSIR jan «1933. Washington, DC General Services Administration
National Bureau of Standards Gaithersburg, Maryland 2.0899 NBSIR 87-3660 jan «1933 Fire Safety Inspection and Testing of Air Moving Systems John H. Klote U.S. DEPARTMENT OF COMMERCE National Bureau of
More informationIs There A Need to ENCLOSE ELEVATOR LOBBIES IN TALL BUILDINGS?
Is There A Need to ENCLOSE ELEVATOR LOBBIES IN TALL BUILDINGS? by Richard W. Bukowski, P.E., FSFPE Several proposals have been submitted in recent years to model building code organizations to require
More informationSmoke Management in Operating Room Renovations
Smoke Management in Operating Room Renovations Sandy Bonderman PE, LEED AP Sean Riley PE, LEED AP Brian Robinett PE, LEED AP Notkin Mechanical Engineers Overview Smoke Management in OR Renovations Why
More informationMajor Changes Nova Scotia Building Code 2011 Construction and Maintenance Regulatory Change Industry Briefing
Major Changes Nova Scotia Building Code 2011 Construction and Maintenance Regulatory Change Industry Briefing Ted Ross Labour & Advanced Education Gerard Donahoe Labour & Advanced Education Overview Where
More informationincorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications
incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications Smoke shafts - an overview Scope of this guide Smoke shaft is the common term for
More informationBuilding Code Act. Building Code. Standards
Constitution Law Building Code Act Building Code Standards 1983 1986 1990 1997 2006 1963 1. Designer s Qualifications 2. Existing or new? 3. Ventilation 4. Mechanical Layout 5. Fire safety 6. Energy efficiency
More informationPROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED
Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B-03-02-07 Ontario-NBC CODE REFERENCE: Division B / 3.2.4.22. and 3.2.4.23. DESCRIPTION
More informationConsiderations in the Design of Smoke Management Systems for Atriums
Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke
More informationGreat Lakes Building Systems, Inc.
FIRE ALARM DESIGN, INSPECTION & MAINTENANCE, CLOUD-BASED REPORTS SECURITY BURG, ACCESS CONTROL, CCTV & OTHER IP SOLUTIONS SUPPRESSION DATA CENTER/INDUSTRIAL, KITCHEN & FIRE EXTINGUISHERS Great Lakes Building
More informationPROJECT: CIVIC ADDRESS:... PERMIT APPLICATION NO.: DATE:... CRP:. Certified Professional:.
2012 B.C. Building Code Checklist (Division B Part 3) This checklist is provided as a reference only. The submission of this checklist with a Building Permit application should not be considered as a substitute
More informationSURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin
SURREY FIRE SERVICE Construction Fire Safety Plan Bulletin The B.C. Fire Code requires building owners/contractors to comply with the requirements of the BC Fire Code 5.6 Construction and Demolition Sites
More informationSt. John s University Fire Safety Plan
Fire Safety Plan Kelleher Center Kelleher Center page 2 St. John s University Fire Safety Plan Part 1-Building Information Section Kelleher Center 300 Howard Ave. Staten Island, N.Y. 10301 Fire Safety
More informationTABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2
Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2
More informationDate: February 22, 2005 Kimbalton DUSEL, Pre-S-2 Submittal CNA0402 PRELIMINARY CODE REVIEW. International Plumbing Code Edition
Kimbalton DUSEL Preliminary Code Study CNA0402 Date: Project: February 22, 2005 Kimbalton DUSEL, Pre-S-2 Submittal CNA0402 Note: Shaded Sections not complete. PRELIMINARY CODE REVIEW Building Code: International
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section
More informationAn Overview to Designing Smoke-Control Systems
The following article was published in ASHRAE Journal, June, 2002. Copyright 2002 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
More informationHOT AIR GENERATOR WITH GAS BURNER NA11.45 A GGS. Installation Operation Commissioning Maintenance
Installation Operation Commissioning Maintenance HOT AIR GENERATOR WITH GAS BURNER GGS NA11.45 A 06-2011 04-2011 CONTENTS 1. DESCRIPTION OF THE UNIT 2. INSTALLATION & CONNECTION 3. COMMISSIONING 4. CARE
More informationNFPA 101 Life Safety Code Culture change 2012
NFPA 101 Life Safety Code Culture change 2012 Produced by Kansas Fire Marshal April, 2012 On March 9, 2012 Centers for Medicare & Medicaid Services implements a policy where they have formally adopted
More informationType of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:
DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM
More informationCHAPTER 7 ALTERATIONS LEVEL
CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration
More informationREVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS
REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS Nikola TANASIĆ, Tomislav SIMONOVIĆ, Miloš IVOŠEVIĆ, Branislav
More information2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code
2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code Welcome! Shawn Strausbaugh Director PMG Technical Resources ICC Government Relations sstrausbaugh@iccsafe.org
More informationICC CODE CORNER 2012 IFC Code & Commentary
SECTION 910 SMOKE AND HEAT VENTS 910.1 General. Where required by this code or otherwise installed, smoke and heat vents or mechanical smoke exhaust systems and draft curtains shall conform to the requirements
More informationNISTIR Elevators at FAA Control Towers. Feasibility of Fire Evacuation by N0.5A45. Department of Commerce John H.
NISTIR 5445 Feasibility of Fire Evacuation by Elevators at FAA Control Towers John H. IGote Bernard M. Levin Norman E. Groner QC- 100.056 N0.5A45 1994 J.S. Department of Commerce technology Administration
More informationNFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities
Fire Alarm and Signaling Code Overview NFPA 72-2010 usa.siemens.com/infrastructure-cities Siemens Building Technologies, Inc. is a Registered Provider with The American Institute of Architects Continuing
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Plot No -246-249, Adamjee EPZ, Siddhirganj, Narayanganj Narayanganj 17 Jul 2016 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jul 2016 Introduction
More informationTechnical Analysis of the Need for Enclosed Elevator Lobbies
Technical Analysis of the Need for Enclosed Elevator Lobbies EXECUTIVE SUMMARY Prepared for the ICC CTC by the Elevator Lobby Study Group The ICC Executive Board directed the Code Technology Committee
More information2012 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata)
[F]TABLE 903.2.11.6 ADDITIONAL REQUIRED SUPPRESSION SYSTEMS SECTION SUBJECT 402.10 402.5 Covered and open mall buildings (Portions of table not show remain unchanged) 2012 International Building Code SEVENTH
More informationSCHEDULE. Essential Safety Measures taken from Schedule 9 of the Building Regulations PART 1 BUILDING FIRE INTEGRITY
SCHEDULE Essential s taken from Schedule 9 of the Building Regulations 2006 43 PART 1 BUILDING FIRE INTEGRITY 1 Building elements required to satisfy prescribed fire-resistance levels 2 Materials and assemblies
More informationPrescriptive Requirement for Smoke Control
HKIE CPD Training Course (II) 7July 2009 Organization by The Hong Kong Institution of Engineers Fire Division Co-organized by the Association of Registered Fire Services Installation contractors of Hong
More informationGROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES
[B] APPENDIX SR GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon SECTION SR101
More informationConstruction Requirements and the Ontario Building Code
Construction Requirements and the Ontario Building Code Thomas Pepper, P. Eng. October 20, 2017 OSBIE Toronto The Evolution of Construction Laws Building Regulations date back as far as 1900 B.C. to Babylonian
More informationGil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee
Gil Rossmiller In the construction industry for over 30 years ICC IRC Plumbing & Mechanical Code Development Committee ICC- IECC Commercial Energy Code Development Committee Building Official Parker, Colorado
More informationCase Study of Underground Car Park. Team Japan
11th Conference on Performance Based Codes and Fire Safety Design Methods Case Study of Underground Car Park Team Japan We focused on the characteristics of the fire behavior of car fire. Car fire is not
More informationNEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS
Mandatory Fire Safety Instruction NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS Reference A: Reference B: Approved Document B
More informationBUILDING CODE OF THE CITY OF NEW YORK. New York City Department of Buildings 4 June 2007
BUILDING CODE OF THE CITY OF NEW YORK New York City Department of Buildings 4 June 2007 Fatma Amer, PE, Deputy Commissioner, Technical Affairs James Colgate, RA, Executive Architect John Lee, RA Keith
More informationThe Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma
Objectives and Requirements For the Creative and Performing Arts High School (CAPA), the main objective of the mechanical design is to provide an energy efficient system that is easily maintainable and
More informationThe Residences at Christina Landing Wilmington, DE
5.0 FIRE PROTECTION EXISTING CONDITIONS 5.1 Project Specific Fire Protection Data Codes, Regulations, and Standards Building Officials and Code administrators (BOCA) National Building Code [1996] with
More information4. OVERVIEW OF MECHANICAL SYSTEM
4. OVERVIEW OF MECHANICAL SYSTEM The 87,000 SF SLCC is served by six (6) Trane M-Series Climate Changer Air Handing Units (AHUs). Each unit serves a distinct zone within the facility that is unique in
More information1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT
Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-1142 (510) 749-9135 Fax (510) 749-9136 LLC HVAC DESIGN INTENT PART 1 - GENERAL 1.1 Overview A. The project consists of a 3-story
More information