Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering

Size: px
Start display at page:

Download "Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering"

Transcription

1 Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015 Peter McDonnell, PE, LEED AP BD+C McClure Engineering

2 UL DAMPER TEST STANDARDS UL FIRE DAMPERS UL555S SMOKE DAMPERS UL555C CEILING DAMPERS UL2043 DAMPER ACTUATORS (Plenums)

3 UL CERTIFICATION The Label Certifies the Product meets stringent testing and performance requirements Covered by UL s Follow Up Service Indicates Damper Type & Rating/s Assembly Temp.

4 Types of Dampers Fire Damper UL555 Smoke Damper Combination Fire & Smoke Damper

5 FIRE TEST VIDEO

6 Fire Dampers How do they work? Curtain Type Style A, B, C Multi-Blade Type V-Grove or Airfoil Static Vs. Dynamic

7 Curtain Type Style A Fire Damper

8 FIRE DAMPER FRAME STYLES A B C R O G

9 Dynamic Closure Rating HVAC system fire dampers are rated for: static (fans off) or dynamic (fans on) It is a matter of airflow through the damper.

10 Smoke Dampers How do they work? Multi-Blade Type V-Grove or Airfoil Static Vs. Dynamic

11 Airfoil Blade V-groove Blade Round

12 Smoke Damper Selection The process of selecting a smoke damper involves the following considerations: 1. Leakage Rating Classes 1, 2, or Elevated Temperature Rating 250 F or 350 F 3. Operational Ratings 2,000 fpm, 3,000 fpm or 4,000 fpm and 4 in. w.g., 6 in. w.g. or 8 in. 4. Blade Design Airfoil or triple v groove.

13 Leakage Rating UL Standard 555S identifies four leakage classes as follows: Maximum Leakage in CFM/Sq. Ft. Leakage w.g. Class I Class II Class III

14 Typical Smoke Damper Application & Installation Actuator Smoke Barrier Smoke detector 24 max. from wall

15 FIRE AND SMOKE PROTECTION FEATURES (Which Damper Type Do I Use?) Exterior Walls Fire Damper Fire Walls Fire Smoke Damper Fire Barriers Fire Smoke Damper Shaft Enclosures - Fire Smoke Damper Elevator Lobbies - Fire Smoke Damper Fire Partitions Fire Smoke Damper Corridors Fire Smoke Damper Smoke Barriers - Fire Smoke Damper Smoke Partitions - Smoke Damper Horizontal Assemblies Fire Damper / CFD

16 Combination Fire/ Smoke Dampers How do they work? Multi-Blade Type V-Grove or Airfoil Static Vs. Dynamic

17 Typical Combination Fire & Smoke Damper Application & Installation Sleeve Break away connections Damper within the plane of fire barrier Fire barrier EFL (Electronic Fuse Link) Actuator Mounting angles

18 Typical Combination Fire & Smoke Damper Application & Installation Sleeve Break away connections Damper in fire barrier EFL (Electronic Fuse Link) Mounting angles

19 Fire/Smoke Damper Selection The process of selecting a FSD damper involves the following considerations: 1. Fire Resistance Rating or 3 hours based on code requirements. 2. Leakage Rating Classes I, II & III (IBC requires minimum Class II). 3. Temperature Rating 250 F or 350 F 4. Operational Ratings Min w.g. or higher. 5. Blade Design Airfoil, triple v-groove and low-profile aerodynamic design.

20 FIRE SMOKE DAMPER RATINGS Leakage Class I or II Rated 1 ½ Hr & 3 Hr Assembly Rating 250⁰F or 350⁰F

21 Temperature and Operational Ratings

22 DAMPER INSTALLATION Fire & Fire/Smoke

23 Installation Good or Bad?

24 Installation Good or Bad?

25 Typical Framed Wall Partition Steel or Wood Stud Framing Openings MUST be framed Framing Details shown on damper Installation Instructions

26 FD or FSD in Rated Wall Opening The FSD stops the passage of flame and smoke at opening and maintains barrier integrity FSD shown in rated steel stud gypsum wallboard opening

27 FD or FSD in Rated Wall Opening Retaining angle fastened to ONE side of wall/floor only Size 90 x 48 and smaller Barriers rated less than 3 hr Fasteners are attached through both wall and damper sleeve 90 x 48 and larger requires

28 Opposite Side of Wall Shown Opening Clearance No FILL material required Retaining Angle/s secure damper in opening and cover clearance gap

29 FD or FSD in plane of Rated Wall Sleeve length depends on application, damper size & components Closed blade MUST stay within the plane of barrier 17 and 20 sleeve length are standard Actuator side sleeve length up to 16 max. Non-actuator side 6 max.

30 FD or FSD Duct Connections Duct connects to damper sleeve (Break-away or Rigid) Typical ducted application

31 OPTIONAL SEALANT

32 OPTIONAL FIRESTOP CLIPS USED IN LIEU OF RETAINING ANGLES

33 OVER-SIZED OPENINGS What happens when opening exceeds largest UL damper size? Example: Wall opening is 20 X 8 FSD 120 x 96 max. UL assembly (vertical) Rated structural member (by others) required to separate (or sub-divided) the TWO damper assemblies into TWO openings Qty x 96

34 Shaft Applications PNC Tower (downtown) Pittsburgh, PA

35 CEILING DAMPER INSTALLATION Ceiling membrane CFD2

36 SURFACE MOUNT CFDR7T

37 LAY-IN CEILING

38 CORRIDOR INSTALLATION

39 CONTROL & ELECTRICAL INTERFACE

40 Smoke Dampers Control damper which is activated when smoke is detected Fire Alarm System Remote Sensor Actuators must be factory installed to meet UL Typically specified with control dampers in division 25

41 Test Results Certified Letter from Manufacturer

42 Active Smoke Control Systems Smoke Control / Management Systems Atrium An opening connecting 2 or more stories (IBC says 2-story atrium is an exception) Design fire size and plume height dictate quantity of exhaust Smoke interface layer required to be 6 above top occupied floor Makeup Requirements < 200 FPM High Rise Buildings (~75 tall) Require either smoke management or breakout windows Maintain pressure differentials across smoke barrier ( ) Exhaust involved floor, Pressurize floors above and below

43 Active Smoke Control Systems Stairwell & Elevator Pressurization High rise buildings are required to have this Pressurize egress stairs to keep smoke out Inject air every 3 floors to evenly pressurize and counteract buoyancy of air

44 Smoke Dampers and Fire Alarm Control Applicable Codes IMC Smoke Damper actuation methods NFPA Smoke Detectors for Control of Smoke Spread NFPA Heating, Ventilating, and Air Conditioning Systems. NFPA 90A 6.4 Smoke Detection for automatic control

45 Smoke detector placement IMC Smoke Damper actuation methods The smoke damper shall close upon actuation of a listed smoke detector or detectors in accordance with one of the following methods, as applicable Where a damper is installed within a duct, a smoke detector shall be installed in the duct within 5 feet with no air outlets or inlets between detector and damper. Other than in mechanical smoke control systems, dampers shall be closed upon fan shutdown where local smoke detectors require a minimum velocity to operate. Where a damper is installed within an unducted opening in a wall, a spot type detector listed for releasing service shall be installed within 5 feet horizontally of the damper. Where a total coverage smoke detector system is provided within all areas (corridor) served by an HVAC system, dampers shall be permitted to be controlled by the smoke detection system.

46 Smoke Dampers Control methods Duct smoke detector with integral relay. Programmable versus non-programmable Separate fire alarm system control relay

47 HVAC system interface Smoke evacuation Coordinate end switches and control wiring of equipment affected by the damper operation and fire alarm panel. Manual override of damper required at fire alarm panel

48 Smoke Control System Damper

49 Typical Enlarged Damper Override Detail

50 Integration with Smoke Control Systems Monitored dampers need to be a part of the Fire Fighters Smoke Control Station (FSCS). These are required for high-rise buildings. FSCS is part of the fire alarm system that details a diagram of the building elevation. Each fan, damper, or other device is indicated on diagram with indicator lights and override switching for Fireman control.

51

52 Atria Refer to NFPA 92. Atrium detection is typically accomplished by beam smoke detectors. Manual override for dampers is required at the Smoke Control Station. Coordinate with Architect and Mechanical Engineer for any requirements for door control.

53 TAKE AWAYS: (1) Basic Requirements Behind Fire/Smoke Separations in Buildings (from Tech Session) (2) When Fire and Smoke Rated Dampers are Required in these Separations (Tech Session) (3) Applications/Requirements of Fire and Smoke Dampers (4) Interface Between Fire/Smoke Dampers and the Electrical Systems.

54 Acknowledgements My Thanks to the following: Josiah Wiley Michael Knipple Members of TC 5.6 STL Chapter Program Committee

55 Questions??

Life Safety Dampers Selection and Application Manual

Life Safety Dampers Selection and Application Manual Life Safety Dampers Selection and Application Manual Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers August 2016 1 2 Table of Contents HOW TO USE THIS MANUAL DAMPER

More information

FIRE & SMOKE DAMPERS. Meeting tomorrow's requirements for fire and smoke protection today.

FIRE & SMOKE DAMPERS. Meeting tomorrow's requirements for fire and smoke protection today. FIRE & SMOKE DAMPERS Meeting tomorrow's requirements for fire and smoke protection today. LATEST TECHNOLOGY For more than 40 years Ruskin has led the HVAC industry in the manufacture of dampers and louvers.

More information

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems 233100 AIR DISTRIBUTION PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 230700 HVAC Insulation B. Section 237300 Air Handling C. Section 230900 Building Automation and Control System Guidelines D. Section

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter except as otherwise

More information

Fire, Smoke, and Combination Fire Smoke Dampers

Fire, Smoke, and Combination Fire Smoke Dampers Fire, Smoke, and Combination Fire Smoke Dampers Mark Belke Director Damper Products-Greenheck Chairman of Code Action Review Committee (CARC) California Building Code work group NFPA 80A, 90A, 92B, 101,

More information

Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com

Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC 262-945-4567 Lauzon.lsc@gmail.com Web: Lauzon-LSC.com 1 Wis Professional Engineer Experienced Facility Director Experienced AHJ WHEA Code

More information

WHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS

WHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS WHITE PLAINS SMOKE CONTROL CODE a. Application of Code. PART 1. GENERAL REQUIREMENTS The following uniform standards and procedures shall apply to the design, installation and testing of new smoke purge

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter

More information

Shut Down The Fan: A Reprise by Dean K. Wilson, P.E.

Shut Down The Fan: A Reprise by Dean K. Wilson, P.E. Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Shut Down The Fan: A Reprise by Dean K. Wilson, P.E. Question: My grandfather passed away last summer. He had spent many years as a fire fighter. Among

More information

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome! Building & Fire Code Academy Building Better With Our Greatest Resource Education Welcome! Understanding the Sprinkler System Design Alternatives in the 2015 International Why inspect, test and maintain?

More information

3/6/2018. Design Tips For Fire and Smoke Barriers. Professional Development Hours (PDH) Certificates. Copyright Materials

3/6/2018. Design Tips For Fire and Smoke Barriers. Professional Development Hours (PDH) Certificates. Copyright Materials AMCA International Design Tips For Fire and Smoke Barriers William E. Koffel, P.E., FSFPE President, Koffel Associates, Inc. www.koffel.com Air System Engineering & Technology (ASET) Conference US San

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION AIR DUCT ACCESSORIES

SECTION AIR DUCT ACCESSORIES SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control

More information

Prescriptive Requirement for Smoke Control

Prescriptive Requirement for Smoke Control HKIE CPD Training Course (II) 7July 2009 Organization by The Hong Kong Institution of Engineers Fire Division Co-organized by the Association of Registered Fire Services Installation contractors of Hong

More information

Common Building Code Misinterpretations

Common Building Code Misinterpretations Common Building Code Misinterpretations Presented by: Ron Melucci, P.E. Technical Manager, FP Division Engineering Planning and Management, Inc. rbm@epm inc.com www.epm inc.com 508 875 2121 Engineering

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary SECTION 909 SMOKE CONTROL SYSTEMS 909.1 Scope and purpose. This section applies to mechanical or passive smoke control systems when they are required for new buildings or portions thereof by provisions

More information

Tunnel Transit Dampers Heavy Duty Tunnel Transit Life Safety

Tunnel Transit Dampers Heavy Duty Tunnel Transit Life Safety Tunnel Transit Dampers Heavy Duty Tunnel Transit Life Safety November 2017 Heavy Duty/Industrial Tunnel Dampers Applications Dampers in subway tunnels and transit systems serve three primary functions,

More information

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] 4.3.11.5.5 Materials within a raised floor plenum exposed to the airflow shall be (a) noncombustible or (b) exhibit a maximum flame spread index of 25

More information

Open to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP

Open to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP Open to Below: A Discussion of Allowed Floor Openings Kevin S. Hastings, P.E., LEED AP Jay A. Ierardi, Ph.D., P.E., LEED AP R.W. Sullivan Engineering (617) 523-8227, Fax (617) 523-8016 http://www.rwsullivan.com

More information

DACC Health Sciences Building Air Handler Assessment/Study

DACC Health Sciences Building Air Handler Assessment/Study DACC Health Sciences Building Air Handler Assessment/Study NMSU Facilities and Services Department P.O. Box 30001 Las Cruces, NM 88003-8001 June 14, 2016 Final Submittal 1065 S. Main St., Bldg. D, Ste.

More information

Chilled Water DOAS Fan Powered Terminal Units

Chilled Water DOAS Fan Powered Terminal Units Chilled Water DOAS Fan Powered Terminal Units CHILLED WATER DOAS FAN POWERED TERMINAL UNITS DOAS TERMINAL UNITS FEATURES AND BENEFITS MINIMUM VENTILATION CONTROL The DOAS unit provides the Designer, Owner

More information

Louvers & Dampers April Product Guide Specification SECTION COMBINATION FIRE SMOKE DAMPERS

Louvers & Dampers April Product Guide Specification SECTION COMBINATION FIRE SMOKE DAMPERS Louvers & Dampers April 2008 P.O. Box 606 7435 Industrial Road Florence, Kentucky, 41042 Phone: (859) 647-2299 Fax: (859) 647-7810 Web Site: www.louvers-dampers.com Product Guide Specification SECTION

More information

Displacement Ventilation

Displacement Ventilation Displacement Ventilation Displacement Ventilation Displacement Ventilation vs. Dilution Ventilation Characteristics Design Considerations Layout and Selection Product Overview Casino Case Study Dilution

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary SECTION 910 SMOKE AND HEAT VENTS 910.1 General. Where required by this code or otherwise installed, smoke and heat vents or mechanical smoke exhaust systems and draft curtains shall conform to the requirements

More information

The project scope work is 90% new construction and 10% remodel in Esslinger Hall.

The project scope work is 90% new construction and 10% remodel in Esslinger Hall. CREIGHTON ENGINEERING INC. FIRE PROTECTION CONSULTING ENGINEERS 210 N. University Road, Suite 100 Spokane Valley, WA 99206 TEL: 509.921.9755 FAX: 509.921.9806 WEB: www.creightoneng.com SCOTT R. CREIGHTON,

More information

Part 3 BUILDING CODE MYTHS & INTERPRETATIONS

Part 3 BUILDING CODE MYTHS & INTERPRETATIONS Part 3 BUILDING CODE MYTHS & INTERPRETATIONS November 18, 2016 Frank Durante, RBO Building Inspector District of Mission Phone 604 820 3729 Wendy Morrison, AScT, BCQ GHL CONSULTANTS LTD Fire Science and

More information

Access door These are required for maintenance of fire and smoke dampers and duct smoke detectors.

Access door These are required for maintenance of fire and smoke dampers and duct smoke detectors. Glossary & Frequently Asked Questions See Page 11 for Specific Belimo Actuator Questions Contacts: Mike Bracero at (203) 749-3107 [michael.bracero@us.belimo.com] Larry Felker at (775) 857-4243 x 5205 [larry.felker@us.belimo.com]

More information

Tunnel Transit Dampers. Heavy Duty Tunnel Transit Life Safety

Tunnel Transit Dampers. Heavy Duty Tunnel Transit Life Safety Tunnel Transit Dampers Heavy Duty Tunnel Transit Life Safety November 2011 Heavy Duty/Industrial Tunnel Dampers Applications Dampers in subway tunnels and transit systems serve three primary functions,

More information

Module 7. Control of Smoke & Highlights of Code Requirements

Module 7. Control of Smoke & Highlights of Code Requirements Module 7 Control of Smoke & Highlights of Code Requirements 1 Module 7 Overview This module will cover: 1. The requirements of smoke control in the Ohio Building Code Section 909 2. The differences between

More information

Smoke Management in High-Rise Structures

Smoke Management in High-Rise Structures Smoke Management in High-Rise Structures Most modern building codes define a high-rise structure as a building greater than 75 feet in height from the lowest level of fire department vehicle access to

More information

GreenJet Transfer Fans

GreenJet Transfer Fans GreenJet Transfer Fans Model GJX High Performance Axial Transfer Fan April 2018 GreenJet As cars park in an underground parking structure, carbon monoxide (CO) and other noxious fumes are emitted into

More information

The Residences at Christina Landing Wilmington, DE

The Residences at Christina Landing Wilmington, DE 5.0 FIRE PROTECTION EXISTING CONDITIONS 5.1 Project Specific Fire Protection Data Codes, Regulations, and Standards Building Officials and Code administrators (BOCA) National Building Code [1996] with

More information

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems FEMA Recommendations are based upon Live Fire Testing of Prep Stations

More information

Stairwell Pressurization Systems

Stairwell Pressurization Systems Course No: M05-022 Credit: 5 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774 info@cedengineering.com Introduction

More information

BUILDING CODE OF THE CITY OF NEW YORK. New York City Department of Buildings 4 June 2007

BUILDING CODE OF THE CITY OF NEW YORK. New York City Department of Buildings 4 June 2007 BUILDING CODE OF THE CITY OF NEW YORK New York City Department of Buildings 4 June 2007 Fatma Amer, PE, Deputy Commissioner, Technical Affairs James Colgate, RA, Executive Architect John Lee, RA Keith

More information

An Overview to Designing Smoke-Control Systems

An Overview to Designing Smoke-Control Systems The following article was published in ASHRAE Journal, June, 2002. Copyright 2002 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes

More information

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March GENERAL: 1. This section provides criteria for the design and installation of air handling units. DESIGN GUIDELINES: Design General 1. Location 1.1. For new construction, and existing buildings where possible,

More information

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated

More information

Fire, Smoke and Control Dampers

Fire, Smoke and Control Dampers MANUAL Fire, Smoke and Control Dampers v100 Issue Date: 04/02/15 2015 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Maintenance, Testing and Inspection Recommendations Recommended Maintenance

More information

FIRE/SMOKE BARRIER FUNDAMENTALS

FIRE/SMOKE BARRIER FUNDAMENTALS FIRE/SMOKE BARRIER FUNDAMENTALS William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com Expertly Engineering Safety From Fire OBJECTIVE Identify the different

More information

Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016

Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016 Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016 Ohio Administrative Code Rule Number OMC Section IMC origin Reason for proposed 4101:2-2-01 Air, Makeup 2015 Modified definition Air,

More information

NFPA Changes

NFPA Changes Chapter 21, Emergency Control Functions and Interfaces Summary. Chapter 21 is new. These requirements were formerly found in Chapter 6, Protected Premises Fire Alarm Systems. The term fire safety function

More information

Linear Floor Heaters

Linear Floor Heaters Linear Floor Heaters The Price Linear Floor Heater family provides ultimate flexibility in terms of style, performance, and ease of installation. Using room-side heat virtually eliminates the requirement

More information

incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications

incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications Smoke shafts - an overview Scope of this guide Smoke shaft is the common term for

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016 Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the

More information

1) Height Limit: About seven stories

1) Height Limit: About seven stories ICC - CTC - Summary of s: of Lobbies and Hoistways January 16, 2011 - Initial draft issued - Clawson January 20, 2011 - D added - Clawson (input from Siu) January 21, 2011 - Edits and H added - Siu February

More information

Edward K. Budnick Hughes Associates, Inc. Wheaton, Maryland, U.S.A SUMMARY. that is entrained or otherwise mixed into the mass.

Edward K. Budnick Hughes Associates, Inc. Wheaton, Maryland, U.S.A SUMMARY. that is entrained or otherwise mixed into the mass. THE CAPABILITIES OF SMOKE CONTROL: FUNDAMENTALS AND ZONE SMOKE CONTROL John H. Klote Center for Fire Research National Institute of Standards and Technology Gaithersburg, Maryland, U.S.A. 20899 Edward

More information

Myth & Reality of Basement Ventilation

Myth & Reality of Basement Ventilation Myth & Reality of Basement Ventilation MYTH & REALITY ABOUT PARKING AND BASEMENT VENTILATION 1 TEAM 1. K.D. SINGH 2. ABHISHEK JAIN 3. MOHAMMAD ADNAN 4. CHITRESH MANGLA EFFECTIVE HEIGHT VIS-À-VIS TOTAL

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 30 ELEVATORS AND CONVEYING SYSTEMS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency

More information

Fire Rated Door Assemblies: Compliant Designs

Fire Rated Door Assemblies: Compliant Designs Fire Rated Door Assemblies: Compliant Designs Steel Door Institute www.steeldoor.org AIA Provider #G389 Course #: SDIFIRE 1 HSW CE hour 1 Credit(s) earned on completion of this course will be reported

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS

FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS FEMA RECOMMENDATIONS ARE BASED UPON LIVE FIRE TESTING OF PREP STATIONS

More information

Land Use and Environmental Service Agency (Code Enforcement) NC Mechanical Code. Table of Contents

Land Use and Environmental Service Agency (Code Enforcement) NC Mechanical Code. Table of Contents Table of Contents Chapter 1 Administration Chapter 2 Definitions Chapter 3 General Regulations Chapter 4 Ventilation. Chapter 5 Exhaust Systems Chapter 6 Duct Systems Chapter 7 Combustion Air Chapter 8

More information

Natural Ventilation A Green Smoke Control Approach

Natural Ventilation A Green Smoke Control Approach Natural Ventilation A Green Smoke Control Approach Presented By: William Koffel, P.E., FSFPE Adam Graybeal, P.E. Authored by: Erik Anderson, P.E Koffel Associates Background New Engineering, Aviation,

More information

GUIDELINES FOR HIGHRISE BUILDING CONSTRUCTION PROJECTS (MECHANICAL VENTILATION)

GUIDELINES FOR HIGHRISE BUILDING CONSTRUCTION PROJECTS (MECHANICAL VENTILATION) GUIDELINES FOR HIGHRISE BUILDING CONSTRUCTION PROJECTS (MECHANICAL VENTILATION) February, 2017 Contents Clauses Page 1. Basic Concepts 1 2. Design Considerations 1 3. Car Parks Ventilation 2 4. Kitchen

More information

IMC Significant Changes Summary Tier I

IMC Significant Changes Summary Tier I 2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT

More information

El Reno Fire Department Fire Alarm Plan Review Worksheet

El Reno Fire Department Fire Alarm Plan Review Worksheet El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us

More information

Replacement of pneumatic actuators on Ruskin negator spring dampers with Belimo FSxx Series

Replacement of pneumatic actuators on Ruskin negator spring dampers with Belimo FSxx Series WARNING! Before replacing actuator, damper must be inspected and determined to be fully functional. See NFPA checklists below. Contents Replacement of pneumatic actuators on Ruskin negator spring dampers

More information

Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS

Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS (630) 620-5750 Fax: (630) 629-2374 www.villageoflombard.org COMMERCIAL HOOD & DUCT SYSTEM PLAN REVIEW REQUIREMENTS International

More information

Air Change, Ventilation, and Dehumidification for Multi-family Buildings

Air Change, Ventilation, and Dehumidification for Multi-family Buildings Air Change, Ventilation, and Dehumidification for Multi-family Buildings Armin Rudd Corp www.buildingscience.com for Acknowledgments: USDOE Building America Joseph Lstiburek, Peter Baker, Kohta Ueno--BSC

More information

Fire Alarm System Fundamentals Presented By: Shamim Rashid-Sumar, Vice President Middle East Operations Rolf Jensen and Associates, Inc.

Fire Alarm System Fundamentals Presented By: Shamim Rashid-Sumar, Vice President Middle East Operations Rolf Jensen and Associates, Inc. Fire Alarm System Fundamentals Presented By: Shamim Rashid-Sumar, Vice President Middle East Operations Rolf Jensen and Associates, Inc. (RJA) Overview Understanding the Codes Fire Alarm Systems (Manual

More information

SMOKE DAMPERS SMOKE DAMPERS

SMOKE DAMPERS SMOKE DAMPERS MODEL SERIES 1210SS AIROIL BLADE STAINLESS STEEL Model Series 1210SS Stainless Steel Airfoil Blade Smoke Dampers are ideal for high humidity, mildly corrosive or, with optional Type 316 construction, more

More information

SECTION DUCTWORK

SECTION DUCTWORK SECTION 15890 DUCTWORK PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 07270 - Firestopping and Fire and Smoke Barrier Caulking. 2. 15260 - Vibration Isolation. 3. 15280 - Thermal Insulation (HVAC).

More information

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

NFPA 101 Code Update from 2012 Edition to the 2015 Edition NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

By: Russell Bainbridge March 18th, 2016 FPE 596

By: Russell Bainbridge March 18th, 2016 FPE 596 By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Dhanpur, Chapapur, Kotwali, Comilla COMILLA Chittagong The Alliance for Worker Safety Page 1/16 Introduction to the Report The following report contains a site profile and

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH)

FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH) FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH) Presented by: Alise Howlett, Assoc. AIA, CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT

More information

CHAPTER 7 MECHANICAL VENTILATION AND SMOKE CONTROL SYSTEMS 7.1 AIR CONDITIONING & MECHANICAL VENTILATION SYSTEMS

CHAPTER 7 MECHANICAL VENTILATION AND SMOKE CONTROL SYSTEMS 7.1 AIR CONDITIONING & MECHANICAL VENTILATION SYSTEMS CHAPTER 7 MECHANICAL VENTILATION AND SMOKE CONTROL SYSTEMS 7.1 AIR CONDITIONING & MECHANICAL VENTILATION SYSTEMS 7.1.1 General (a) Where air conditioning system is provided in lieu of mechanical ventilation

More information

FAQ. (Frequently Asked Questions) What is required to convert my unfinished basement to finished space?

FAQ. (Frequently Asked Questions) What is required to convert my unfinished basement to finished space? NEW CASTLE COUNTY DEPARTMENT OF LAND USE FAQ (Frequently Asked Questions) What is required to convert my unfinished basement to finished space? 1. To convert an unfinished basement to finished space, at

More information

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD. Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes Comparing the Codes: NFPA 101 Life Safety Code (2000) (NFPA) International Building Code (2012) (IBC) Chicago

More information

Kings County Jail Expansion Phase 3 Rational Analysis of Smoke Control System

Kings County Jail Expansion Phase 3 Rational Analysis of Smoke Control System Kings County Jail Expansion Phase 3 Rational Analysis of Smoke Control System Kings County Jail Phase 3 Page 2 RATIONAL ANALYSIS OF SMOKE CONTROL SYSTEM PER 2013 CBC 909.4 General Description: The project

More information

2012 B.C. Building Code Compliance Review (Division B Part 3)

2012 B.C. Building Code Compliance Review (Division B Part 3) Planning and Building Department 2012 B.C. Building Code Compliance Review PROJECT NAME:.. CIVIC ADDRESS:...... PERMIT APPLICATION NO.:. DATE:... I,, have: 1. reviewed the design, plans and supporting

More information

Smoke Control Design and Activation. CFAA NCA Technical Seminar 2015

Smoke Control Design and Activation. CFAA NCA Technical Seminar 2015 Smoke Control Design and Activation CFAA NCA Technical Seminar 2015 2 Overview Principles of smoke control Codes CACF controls Programming Commissioning Testing Goals To provide an introduction to smoke

More information

2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code

2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code 2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code Welcome! Shawn Strausbaugh Director PMG Technical Resources ICC Government Relations sstrausbaugh@iccsafe.org

More information

January 1, 2014 Mandatory Effective Date

January 1, 2014 Mandatory Effective Date 2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

ELEVATORS. Integration of Codes between Fire Alarm, Sprinklers, and Elevators 12/5/2017

ELEVATORS. Integration of Codes between Fire Alarm, Sprinklers, and Elevators 12/5/2017 12/5/2017 1 ELEVATORS Integration of Codes between Fire Alarm, Sprinklers, and Elevators Encore Electric Inc. Prepared By John McGovern and Jeffrey Engelstad 12/5/2017 Encore Electric Inc. 2 Agenda Basics

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

Smoke Management Application Guide Rev. D

Smoke Management Application Guide Rev. D Smoke Management Application Guide 574-465 Rev. D Acknowledgements Acknowledgements Tyco Safety Products Westminster, gratefully acknowledges the contributions of the following organizations to this publication:

More information

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas UFAD and Displacement Ventilation Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas UFAD and DV Systems, Objectives: Understand Differences between: Well Mixed, Partially Stratified and Fully

More information

SMOKE DAMPERS AIRFOIL STAINLESS STEEL

SMOKE DAMPERS AIRFOIL STAINLESS STEEL MODEL SERIES 1210M AIROIL BLADE MODULATING ACTUATOR Model Series 1210M Modulating Smoke Dampers are classified for use as a volume control damper in applications where building codes require a leakage

More information

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,

More information

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN , Volume 4, Number 2, p.73-83, 2003 SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN K.H. Yang and C.S. Yang Mechanical Engineering Department, National Sun Yat-Sen

More information

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

EST3 Smoke Management Application Manual

EST3 Smoke Management Application Manual EST3 Smoke Management Application Manual 270913 Rev 1.0 28JUL99 DEVELOPED BY COPYRIGHT NOTICE TRADEMARKS CREDITS Edwards Systems Technology 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4200 Copyright

More information

Short Term Accommodations Fire Code Requirements

Short Term Accommodations Fire Code Requirements Short Term Accommodations Fire Code Requirements 1 Foreward The following is a comprehensive reference to Retrofit 9.3 of Division B of the Ontario Fire Code (OFC). Retrofit provisions were developed to

More information

Air Moving Systems. Fire Safety Inspection and Testing of. NBSIR jan «1933. Washington, DC General Services Administration

Air Moving Systems. Fire Safety Inspection and Testing of. NBSIR jan «1933. Washington, DC General Services Administration National Bureau of Standards Gaithersburg, Maryland 2.0899 NBSIR 87-3660 jan «1933 Fire Safety Inspection and Testing of Air Moving Systems John H. Klote U.S. DEPARTMENT OF COMMERCE National Bureau of

More information

Richard B. Alpert, P.E. Senior FPE, Clark Nexsen

Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Clark Nexsen is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of

More information

INSTRUCTION SHEET - Replacement of Ruskin Phillips P150 to Belimo FSNF or FSAF Actuator

INSTRUCTION SHEET - Replacement of Ruskin Phillips P150 to Belimo FSNF or FSAF Actuator WARNING! Before replacing actuator, damper must be inspected and determined to be fully functional. INSTRUCTION SHEET - Replacement of Ruskin Phillips P150 to Belimo FSNF or FSAF Actuator Contents UL...

More information

C.E.P., C.E.M, C.I.P.E.

C.E.P., C.E.M, C.I.P.E. Subject What everyone needs to know about ASHRAE 90.1 J. Christopher Larry, P.E., C.E.P., C.E.M, C.I.P.E. Thursday, Joint ASHRAE AEE Meeting Cleveland, Ohio Introduction J. Christopher Larry P.E., C.E.P.,

More information

Square Ceiling Diffusers : All extruded aluminum constructions. Opposed blade damper is adjustable from face of diffuser. Available in square and

Square Ceiling Diffusers : All extruded aluminum constructions. Opposed blade damper is adjustable from face of diffuser. Available in square and Square Ceiling Diffusers : All extruded aluminum constructions. Opposed blade damper is adjustable from face of diffuser. Available in square and rectangular type with one, two, three or four way patterns.

More information

Smoke Management in Operating Room Renovations

Smoke Management in Operating Room Renovations Smoke Management in Operating Room Renovations Sandy Bonderman PE, LEED AP Sean Riley PE, LEED AP Brian Robinett PE, LEED AP Notkin Mechanical Engineers Overview Smoke Management in OR Renovations Why

More information

MODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces

MODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces MODULE 8 Tying the Systems Together: Emergency Control Functions and Interfaces 1 OVERVIEW OF MODULE 8 In this module we will: Describe all components, their arrangements and how the systems work Describe

More information

ENVIRO UNIT ENGINEERING MANUAL KES SERIES

ENVIRO UNIT ENGINEERING MANUAL KES SERIES ENVIRO UNIT ENGINEERING MANUAL KES SERIES The Cadexair INC. Enviro System (KES) and Recirculation System (KRS) have been designed and constructed specifically for a commercial kitchen exhaust. The units

More information