ELEVATORS. Integration of Codes between Fire Alarm, Sprinklers, and Elevators 12/5/2017

Size: px
Start display at page:

Download "ELEVATORS. Integration of Codes between Fire Alarm, Sprinklers, and Elevators 12/5/2017"

Transcription

1 12/5/ ELEVATORS Integration of Codes between Fire Alarm, Sprinklers, and Elevators Encore Electric Inc. Prepared By John McGovern and Jeffrey Engelstad

2 12/5/2017 Encore Electric Inc. 2 Agenda Basics Elevator Types and Design Considerations Using the Codes Fire Alarm/Sprinkler Requirements

3 12/5/2017 Encore Electric Inc. 3 Elevator Types Basic Types: Hydraulic Traction

4 12/5/2017 Encore Electric Inc. 4 Hydraulic Elevators

5 12/5/2017 Encore Electric Inc. 5 Traction Elevators

6 12/5/2017 Encore Electric Inc. 6 Machine Room Less Elevators

7 12/5/2017 Encore Electric Inc. 7 Basic Elevator Design Rules of Thumb Commercial Office Buildings One Elevator per 50,000 GSF One Elevator per floors served One Elevator for persons Hotels One Passenger Elevator per 100 Rooms Minimum of 2 Passenger Elevators 2 Service Elevators up to 300 Rooms - 3 Service Elevators up to 500 Rooms Residential One Passenger Elevator per 150 Units One Service Elevator per 300 Units Service Elevators 4,000 Pound Capacity Minimum Deeper than Wide Office Building : >300,000 GSF = Dedicated Service Elevator; Add Additional Elevator for each incremental 400,000 GSF

8 12/5/2017 Encore Electric Inc. 8 Applicable Codes ASME (ANSI) ASME A17.1 National Elevator Code ASME A17.2 Inspection of Elevators ASME A17.3 Existing Elevators

9 12/5/2017 Encore Electric Inc. 9 Applicable Codes -International International Building Code (IBC) Chapter 30 Fire Service Access Elevators (FSAE) International Fire Code (IFC)

10 12/5/2017 Encore Electric Inc. 10 Applicable Codes: NFPA NFPA NFPA NFPA 70 (NEC) NFPA 101

11 12/5/2017 Encore Electric Inc. 11 Applicable Codes: Need to Use Them All IBC / IFC Local, State and City Codes NFPA 70, 72, 101 & 13 ASME A17.1

12 12/5/2017 Encore Electric Inc. 12 Elevators and Fire Alarm High-rise fires cause the most injury and property damage During a Fire, Elevators play key roles: Modern Elevators move 12.5% of occupants in 5 minutes (40 min to empty) Firefighters gear weighs +65 lbs. plus an additional 65 lbs. in hose Ultra High-rises are utilizing elevators as a means of egress (OEE) Elevators provide speed during an emergency but must be kept safe!

13 12/5/2017 Encore Electric Inc. 13 Elevator Hoistways Built as shafts using fire barrier construction 1 hr. for < 4 stories (2 hr. for 4 or more) Maximum of 4 cars per shaft when serve the same building area (IBC ) Elevators shall not be in a common enclosure with a stairway (IBC ) No plumbing or mechanical systems (IBC )

14 12/5/2017 Encore Electric Inc. 14 Elevator Cab Requirements Where elevators are provided in buildings four or more stories above, or four or more stories below, grade plane, not fewer than one elevator shall be provided for fire department emergency access to all floors. The elevator car shall be of such a size and arrangement to accommodate an ambulance stretcher 24 inches by 84 inches with not less than 5-inch radius corners, in the horizontal, open position This is not the Fire Service Access Elevator

15 12/5/2017 Encore Electric Inc. 15 Fire Service Access Elevators Where required by Section (IBC), every floor of the building shall be served by fire service access elevators (FSAE) complying with Sections through (IBC). Min. number of FSAE was increased from 1 to 2 for Bldgs. over 120 ft.. (2009 IBC to 2012 IBC, same for 2015 IBC) FSAE if > 120 ft..

16 12/5/2017 Encore Electric Inc. 16 FSAE Requirements Fire Service Access Lobby: Formed by 1-hr smoke barriers with smoke/draft doors Direct access to stairway > 150 sf with a dimension not less than 8 ft.. Standby power and protection of power: Power the equipment, lights, ventilation Cables outside the hoistway or machine room need protection commensurate with the shaft rating (2012 IBC / 2015 IBC ) Monitored in the Fire Command Center

17 12/5/2017 Encore Electric Inc. 17 FSAE Requirements Protection Against Water: Machine Rooms CANNOT be sprinklered (NO Shunt Trip) An approved method to prevent water from infiltrating into the hoistway enclosure from the operation of the automatic sprinkler system outside the enclosed fire service access elevator lobby shall be provided

18 12/5/2017 Encore Electric Inc. 18 Occupant Evacuation Elevators (OEE) IBC Section 3008 Primarily as an alternative to 3rd stair requirement in high rise provisions not mandatory Assign call priority prior to Phase I recall Automatic detection on floors: Smoke/heat, water flow Also manual initiation from Command Room (not manual pull stations) NOT active if Level of Exit Discharge is in alarm Establish evacuation zones Alarm floor and 2 floors above/floor below Multiple alarm floors provision (increased alarm group) with priority to highest floor Travel between priority floor(s) and discharge level in express mode

19 12/5/2017 Encore Electric Inc. 19 ASME A.17.1 Definitions Phase I Emergency Recall Operation: the operation of an elevator where it is automatically or manually recalled to the recall level and removed from normal service because of activation of firefighters emergency operation. Phase II Emergency In-Car Operation: the operation of an elevator by firefighters where the elevator is under their control. Designated Level: the main floor or other floor level that best serves the needs of emergency personnel for firefighting or rescue purposes identified by the building code or fire authority. Alternate Level: a floor level identified by the building code or fire authority, other than the designated level. Recall Level: the designated or alternate level that cars are returned to when Phase I Emergency Recall Operation is activated.

20 12/5/2017 Encore Electric Inc. 20 NFPA Recall and Shunt Trip COORDINATION REQUIRED Consider: Elevator Type OEE, FSAE, Freight, PassengerR Hydraulic, Traction, MRLR Construction Material (Cable, Cab, Fluids?) Sprinklered (NFPA 13)? Control Room/Space? Machine Room/Space?

21 12/5/2017 Encore Electric Inc. 21 NFPA Recall Provided by lobby heat or smoke detection which initiates a recall to a safe floor Designated primary and alternate Also provided by machine room detection and shaft detection if present Selection of primary and alternate should be based on AHJ determination and must be documented Recall on general alarm not required, except 2012 FSAE Lobby smoke within 21 ft. of the centerline of each elevator door in a bank One detector can serve multiple openings

22 12/5/2017 Encore Electric Inc. 22 Phase I Emergency Recall * A lobby smoke detector shall be located on the ceiling within 21 ft.. (6.4 m.) of the centerline of each elevator door within the elevator bank under control of the detector.

23 12/5/2017 Encore Electric Inc. 23 Recall: Fire Fighter Warning Activation of primary recall detectors SOLID HAT Activation of the elevator machine room, elevator machinery space, elevator control space, or elevator control room initiating devices identified in (2) or (2) FLASHING HAT Additional requirements for annunciation in Command Room (where provided) for FSAE and OEE Typically handled by elevator control panel

24 12/5/2017 Encore Electric Inc. 24 Shunt Trip In the presence of a sprinkler system, shunt trip kills power to critical equipment before sprinkler operation Top of shaft, elevator machine rooms and control rooms/spaces Recognized approaches Traditional: Heat detection with an activation temperature less than the activation temperature of the sprinkler heads Alternate: Zero-Retard (Non-field-settable) Flow Switch Or just get rid of sprinklers0

25 12/5/2017 Encore Electric Inc. 25 Basic FA: Hydraulic Elevators

26 12/5/2017 Encore Electric Inc. 26 Sprinklers Needed or Not? NFPA 13, 2010 Edition Sidewall heads shall be installed in the pit not more that 2 feet above the pit floor Sprinklers in above not required in non-combustible construction hoistway with no hydraulic fluids Sprinklers required in machine rooms Sprinklers required at the top of the hoistway Sprinklers not required at top of hoistway where hoistway is non-combustible construction Sprinklers required at top of hoistway where polyurethanecoated steel belts or other similar combustible material belt material.

27 12/5/2017 Encore Electric Inc. 27 Sprinklers Needed or Not? NFPA 13, 2013 & 16 Editions Automatic fire sprinklers shall not be required in elevator machine rooms, elevator machinery spaces, control spaces, or hoistwaysof traction elevators installed in accordance with the applicable provisions in NFPA 101, or the applicable building code, where all of the following conditions are met: (1) The elevator machine room, machinery space, control room, control space, or hoistway of traction elevator is dedicated to elevator equipment only. (2) The elevator machine room, machine room, machinery space, control room, control space, or hoistway of traction elevators are protected by smoke detectors, or other automatic fire detection, installed in accordance with NFPA72. (3)The elevator machinery space, control room, control space, or hoistway of traction elevators is separated from the remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having a fire resistance rating of not less than that specified by the applicable building code. (4) No materials unrelated to elevator equipment are permitted to be stored in elevator machine rooms, machinery spaces, control rooms, control spaces, or hoistways of traction elevators. (5) The elevator machinery is not of the hydraulic type.

28 12/5/2017 Encore Electric Inc. 28 Sprinklers Needed or Not? NFPA 13, 2013 & 16 Editions Upright, pendant, or sidewall spray sprinklers shall be installed at the top of elevator hoistways The sprinklers required at the top of the elevator hoistway by shall not be required where the hoistway for passenger elevators is non-combustible or limited combustible and the car enclosure materials meet the requirements of ASME A17.1, Safety Code for Elevators and Escalators.

29 12/5/2017 Encore Electric Inc. 29 Sprinklers Needed or Not? Sprinklers shall be installed at the top and bottom of elevator hoistways where elevators utilize combustible suspension means such as noncircular elastomeric-coated or polyurethane-coated steel belts The sprinklers in the elevator hoistway shall not be required when the suspension means provide not less than an FT-1 rating when tested to the vertical burn test requirements of UL 62, Flexible Cords and Cables, and UL 1581, Reference Standard for Electrical Wires, Cables, and Flexible Cords.

30 12/5/2017 Encore Electric Inc. 30

31 12/5/2017 Encore Electric Inc. 31

32 12/5/2017 Encore Electric Inc. 32

33 12/5/2017 Encore Electric Inc. 33 Basic FA: Traction Elevators

34 12/5/2017 Encore Electric Inc. 34 Basic FA: Traction Elevators NFPA 13??

35 12/5/2017 Encore Electric Inc. 35 Basic FA: MRL Elevators

36 12/5/2017 Encore Electric Inc. 36 Basic FA: MRL Elevators Control Room/Space???

37 12/5/2017 Encore Electric Inc. 37 Phase I Emergency Recall Key Phase I Emergency Recall Operation A three-position key-operated switch that will not change position without a deliberate action by the user, shall be (a)provided only at the designated level for each single elevator or for each group of elevators. (b) labeled FIRE RECALL and its positions marked RESET, OFF, and ON (in that order), with the OFF position as the center position. The FIRE RECALL letters shall be a minimum of 5 mm (0.25 in.) high. Text shall be either red on a background that contrasts with red, or a color that contrasts with red on a red background. (c) located in the lobby within sight of the elevator or all elevators in that group and shall be readily accessible.

38 12/5/2017 Encore Electric Inc. 38 Phase I Emergency Recall Device Phase I Emergency Recall Operation by Fire Alarm Initiating Devices (FAIDs) Rsmoke detectors or other automatic fire detectors in environments not suitable for smoke detectors (fire alarm initiating devices) used to initiate Phase I Emergency Recall Operation shall be installed in conformance with the requirements of NFPA 72, and shall be Located (a) at each elevator lobby served by the elevator (b) in the associated elevator machine room, machinery space containing a motor controller or driving machine, control space, or control room (c) in the elevator hoistway, when sprinklers are locatedin those hoistways

39 12/5/2017 Encore Electric Inc. 39 Phase I Emergency Recall NFPA * In facilities without a required building fire alarm system, fire alarm initiating devices used to initiate elevator Phase 1 Emergency Recall Operation shall be connected to either a non required building fire alarm system or a dedicated function fire alarm control unit that shall be designated as elevator recall control and supervisory control unit, permanently identified on the dedicated function fire alarm control unit and on the record drawings. Is this a Fire Alarm Panel?

40 12/5/2017 Encore Electric Inc. 40 Phase I Emergency Recall NFPA Unless otherwise required by the authority having jurisdiction, only the elevator lobby, elevator hoistway, elevator machine room, elevator control room, and elevator control space smoke detectors or other automatic fire detection as permitted by shall be used to initiate elevator Phase I Emergency Recall Operation.

41 12/5/2017 Encore Electric Inc. 41 Phase I Emergency Recall * If ambient conditions prohibit installation of automatic smoke detection used to initiate elevator Phase I Emergency Recall Operation, other automatic fire detection initiating devices shall be permitted.

42 12/5/2017 Encore Electric Inc. 42 Phase I Emergency Recall NFPA * Elevator Warning Signal. For each elevator or group of elevators, an output shall be provided to the elevator controller in response to any of the following: (1) Activation of the elevator machine room, elevator machinery space, elevator control space, or elevator control room initiating devices (2) Activation of the elevator hoistway initiating devices

43 12/5/2017 Encore Electric Inc. 43 Phase II Emergency Operation Phase II operation is an override meant for firefighters after Phase I has been activated. Under Phase II operation, firefighters can use a keyswitch to operate the elevator, provided the hoistway is clear of smoke and the elevator has electricity.

44 12/5/2017 Encore Electric Inc. 44 Shunt Trip Code: ASME A Rwhere elevator equipment is located or its enclosure is configured such that application of water from sprinklers could cause unsafe elevator operation, means shall be provided to automatically disconnect the main line power supply to the affected elevator and any other power supplies used to move the elevator upon or prior to the application of water. (a) This means shall be independent of the elevator control and shall not be self-resetting. (b) Heat detectors and sprinkler flow switches used to initiate main line elevator power shutdown shall comply with the requirements of NFPA 72. (c) The activation of sprinklers outside of such locations shall not disconnect the main line elevator power supply Smoke detectors shall not be used to activate sprinklers in these spaces or to disconnect the main line power supply.

45 12/5/2017 Encore Electric Inc. 45 Shunt Trip Code: IBC Shunt trip. Where elevator hoistways, elevator machine rooms, control rooms and control spaces containing elevator control equipment are protected with automatic sprinklers, a means installed in accordance with Section 21.4 of NFPA 72 shall be provided to disconnect automatically the main line power supply to the affected elevator prior to the application of water. This means shall not be selfresetting. The activation of automatic sprinklers outside the hoistway, machine room, machinery space, control room or control space shall not disconnect the main line power supply.

46 12/5/2017 Encore Electric Inc. 46 Shunt Trip Code: NFPA Elevator Shutdown *Where heat detectors are used to shut down elevator power prior to sprinkler operation, the detector shall have both a lower temperature rating and a higher sensitivity as compared to the sprinkler * If heat detectors are used to shutdown elevator power prior to sprinkler operation, they shall be placed within 24 in. (610 mm) of each sprinkler and be installed in accordance with the requirements of Chapter *If pressure or waterflow switches are used to shutdown elevator power immediately upon, or prior to, the discharge of water from sprinklers, the use of devices with time-delay switches or timedelay capability shall not be permitted *Control circuits to shutdown elevator power shall be monitored for the presence of operating voltage. Loss of voltage to the control circuit for the disconnecting means shall cause a supervisory signal to be indicated at the control unit and required remote annunciators.

47 12/5/2017 Encore Electric Inc. 47 Shunt Trip Overview Heat Detectors Lower Temperature/Higher Sensitivity Heat detector must be within 24 in. of each sprinkler head Allows flow switch with no time delay Shunt trip relay power must be monitored Transmit supervisory if impaired

48 12/5/2017 Encore Electric Inc. 48 Shunt Trip: FSAE & OEE IBC 2015 [F] Exempt locations. Automatic sprinklers shall not be required in the following rooms or areas where such rooms or areas are protected with an approved automatic fire detection system in accordance with Section that will respond to visible or invisible particles of combustionr 4. Rooms or areas that are of noncombustible construction with wholly noncombustible contents. 5. Fire service access elevator machine rooms and machinery spaces. 6. Machine rooms, machinery spaces, control rooms and control spaces associated with occupant evacuation elevators designed in accordance with Section 3008.

49 12/5/2017 Encore Electric Inc. 49 Shunt Trip and Recall: FSAE NFPA 72 Section 21.5 The following conditions shall be continuously monitored and displayed: Normal and emergency power availability Status of the elevator(s), including location within the hoistway, direction of travel, and whether they are occupied Elevator management system shall provide Temperature and presence of smoke in associated lobbies and machine room (if provided) NFPA (2010) Standard Emergency Service Interface. Where required by the enforcing authority; governing laws, codes, or standards; or other parts of this code, annunciators, information display systems, and controls for portions of a system provided for use by emergency service personnel shall be designed, arranged, and located in accordance with the requirements of the organizations intended to use the equipment.

50 12/5/2017 Encore Electric Inc. 50 Shunt Trip and Recall: OEE? All of NFPA 72 Section 21.5 andr Notify Fire Command when the elevator is called into Occupant Evacuation Mode Ability to start total evacuation or selective evacuation based on an alarm signal received from a specific floor or by Fire Command Special alarm floor evacuation messages USE ElevatorR Safe Zone Messages by Alarm Groups

51 12/5/2017 Encore Electric Inc. 51 Lighting: FSAE For FSAE lighting must be provided within the hoistway (IBC ). 1 ft-cd minimum at top of the car of each FSAE Come on with Phase I Recall The light allows firefighters to check for fire, smoke or water in the hoistway and aids the firefighters escape through the top of the cab if the elevator stops.

52 12/5/2017 Encore Electric Inc. 52 Questions

Interfacing Fire Alarm, Sprinkler and Elevator Systems

Interfacing Fire Alarm, Sprinkler and Elevator Systems 1 Interfacing Fire Alarm, Sprinkler and Elevator Systems Rodger Reiswig, SET Director, Industry Relations SimplexGrinnell November 17, 2010 Interfacing to Elevators 2 ASME A17.1 Safety Code for Elevators

More information

rpsa FIRE PROTECTION ENGINEERS

rpsa FIRE PROTECTION ENGINEERS FIRE PROTECTION ENGINEERS R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator

More information

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 30 ELEVATORS AND CONVEYING SYSTEMS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency

More information

Presentation Material: The material will be presented in a PowerPoint format and available digitally/ paper.

Presentation Material: The material will be presented in a PowerPoint format and available digitally/ paper. This fire alarm seminar is an overview of elevator fire alarm system interfacing fundamentals and the current requirements. It covers the terminology, life safety functions, and correct application of

More information

MD-DC-VA Automatic Fire Alarm Association, Inc. Interfacing Fire Alarm, Sprinkler and Elevator Systems In Maryland, DC and Virginia

MD-DC-VA Automatic Fire Alarm Association, Inc. Interfacing Fire Alarm, Sprinkler and Elevator Systems In Maryland, DC and Virginia , Inc. Interfacing Fire Alarm, Sprinkler and Elevator Systems In Maryland, DC and Virginia Presented by: Andrew Roe, SET Alarm Tech Solutions, LLC Scope: The Purpose of Elevator Controls History of Elevator

More information

NFPA Changes

NFPA Changes Chapter 21, Emergency Control Functions and Interfaces Summary. Chapter 21 is new. These requirements were formerly found in Chapter 6, Protected Premises Fire Alarm Systems. The term fire safety function

More information

The Owner will provide the QEI inspection and certification services.

The Owner will provide the QEI inspection and certification services. General The Owner will provide the QEI inspection and certification services. Elevators Electric operated traction elevators are preferred; holeless hydraulic oil operation may be considered where use

More information

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated

More information

Fire Protection Coffee Break Training May 2016

Fire Protection Coffee Break Training May 2016 Fire Protection Coffee Break Training May 2016 Introduction High-Rise Requirements Questions and Answers Agenda Overview Site Fire Access Aerial Access Power/Back-up Power Elevators and Access Sprinklers

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement Second Revision No. 5501-NFPA 5000-2016 [ New Section after 29.2.1.2 ] 29.2.1.3 Bathtubs, bathtub-shower combinations, and nonemergency showers shall be provided with grab bars in accordance with the provisions

More information

Division 28 - Electronic Safety and Security

Division 28 - Electronic Safety and Security Division 28 - Electronic Safety and Security 28 31 11 Fire Alarm Systems Fire alarm systems shall be installed in buildings when required by this section. 1. Purpose: The primary purpose of a fire alarm

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169 7471 Phone: 617 770 3000 Fax: 617 770 0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Means of Egress

More information

FIRE SERVICE FEATURES

FIRE SERVICE FEATURES CHAPTER 5 FIRE SERVICE FEATURES SECTION 501 GENERAL 501.1 Scope. Fire service features for buildings, structures and premises shall comply with this chapter. 501.2 Permits. A permit shall be required as

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

APPENDIX K MODIFIED INDUSTRY STANDARDS FOR ELEVATORS AND CONVEYING SYSTEMS

APPENDIX K MODIFIED INDUSTRY STANDARDS FOR ELEVATORS AND CONVEYING SYSTEMS APPENDIX K MODIFIED INDUSTRY STANDARDS FOR ELEVATORS AND CONVEYING SYSTEMS CHAPTER K1 MODIFICATIONS TO ASME A17.1-2000, SAFETY CODE FOR ELEVATORS AND ESCALATORS K101.1 General. As referenced by Chapter

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other

More information

The Residences at Christina Landing Wilmington, DE

The Residences at Christina Landing Wilmington, DE 5.0 FIRE PROTECTION EXISTING CONDITIONS 5.1 Project Specific Fire Protection Data Codes, Regulations, and Standards Building Officials and Code administrators (BOCA) National Building Code [1996] with

More information

Emergency Power & Fire Service Checklist

Emergency Power & Fire Service Checklist Emergency Power & Fire Service Checklist www.technicalsafetybc.ca contact@technicalsafetybc.ca Toll Free: 1 866 566 7233 The intended purpose of this form is to provide a mechanism for inspectors to be

More information

Port of Portland Conveying Equipment Guidelines

Port of Portland Conveying Equipment Guidelines Role: Consultant for the Port Design Guidelines Port of Portland Conveying Equipment Guidelines ELEVATOR, ESCALATOR, AND MOVING WALK DESIGN OVERVIEW The Division 14 specification sections include appropriate

More information

HIGH-RISE RETROFIT ORDINANCES - NO and NO

HIGH-RISE RETROFIT ORDINANCES - NO and NO INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT

More information

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing

More information

APPENDIX A International Building Code Amendments

APPENDIX A International Building Code Amendments APPENDIX A 2012 International Building Code Amendments The following sections, paragraphs, and sentences of the 2012 International Building Code are hereby amended as follows: Standard type is text from

More information

2.01 Fire Alarm Submittals (2016)

2.01 Fire Alarm Submittals (2016) 2.01 Fire Alarm Submittals (2016) Reference: 2016 SFBC, Section 907.1.1; 2016 NFPA 72, Chapter 7 & 10.4.1 The San Francisco Building Code, Section 1.11.1 requires that all fire alarm system installations,

More information

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016 Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the

More information

El Reno Fire Department Fire Alarm Plan Review Worksheet

El Reno Fire Department Fire Alarm Plan Review Worksheet El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

Consultant shall design elevators to comply with current ASME A117.1, ASME A117.2, UBC and NEC codes.

Consultant shall design elevators to comply with current ASME A117.1, ASME A117.2, UBC and NEC codes. DIVISION 14 - CONVEYING SYSTEMS Section 14000 - General Discussion Introduction The size, number, and location of elevators must be addressed at the earliest stages of the design, to ensure that neither

More information

PERFORMANCE COMPLIANCE METHODS

PERFORMANCE COMPLIANCE METHODS CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,

More information

2018 NICET Code Transition Changes

2018 NICET Code Transition Changes 2018 NICET Code Transition Changes NICET will be transitioning to newer codes accepted in their exams in mid-october 2018, specifically: NFPA 72 2016 NFPA 70 2014 IBC 2015 NFPA 101 2015 Here are some changes

More information

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes 2012 International Fire Code Significant Changes Andrew M. Schneider, P.E. Senior Fire Protection Engineer aschneider@koffel.com Koffel Associates, Inc. www.koffel.com Expertly Engineering Safety From

More information

CHINO VALLEY INDEPENDENT FIRE DISTRICT FIRE PROTECTION STANDARD

CHINO VALLEY INDEPENDENT FIRE DISTRICT FIRE PROTECTION STANDARD CHINO VALLEY INDEPENDENT FIRE DISTRICT FIRE PROTECTION STANDARD HIGH-RISE REQUIREMENTS STANDARD # 113 REVISED 02/03/1992 PAGES 16 Index Section 1: Section 2: Section 3: Section 4: Section 5: Section 6:

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

ELEVATORS AND FIRE SERVICE. CODE CHANGES in. Presenter: Eric Peterson, P. Eng.

ELEVATORS AND FIRE SERVICE. CODE CHANGES in. Presenter: Eric Peterson, P. Eng. ELEVATORS AND FIRE SERVICE CODE CHANGES in British Columbia Presenter: Eric Peterson, P. Eng. Principal, GUNN Consultants www.gunnconsultants.com Gunn Consultants Inc. Professional engineering team specialized

More information

Richard B. Alpert, P.E. Senior FPE, Clark Nexsen

Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Clark Nexsen is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title

More information

PERFORMANCE COMPLIANCE METHODS

PERFORMANCE COMPLIANCE METHODS CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter ((shall)) apply to the alteration, repair, addition and change of occupancy of existing structures,

More information

COMPLIANCE ALTERNATIVES

COMPLIANCE ALTERNATIVES CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

COMPLIANCE ALTERNATIVES

COMPLIANCE ALTERNATIVES CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare

More information

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome! Building & Fire Code Academy Building Better With Our Greatest Resource Education Welcome! Understanding the Sprinkler System Design Alternatives in the 2015 International Why inspect, test and maintain?

More information

GENERAL AREAS OF INSPECTION

GENERAL AREAS OF INSPECTION This information is intended to assist you in preparation for the annual high-rise inspection. This is not a complete list and the Inspector may identify other conditions or issues in the building that

More information

EXIT ROUTES, EMERGENCY ACTION PLANS, AND. FIRE PREVENTION PLANS. PART 1: INTRODUCTION

EXIT ROUTES, EMERGENCY ACTION PLANS, AND. FIRE PREVENTION PLANS. PART 1: INTRODUCTION EXIT ROUTES, EMERGENCY ACTION PLANS, AND FIRE PREVENTION PLANS PART 1: INTRODUCTION Applicability of This Module Use the following General Applicability Checklist to determine whether a rulebook and its

More information

DIVISION 14 - CONVEYING SYSTEMS. 1. Passenger Elevators 2. Vertical Platform and Inclined Wheelchair Lifts.

DIVISION 14 - CONVEYING SYSTEMS. 1. Passenger Elevators 2. Vertical Platform and Inclined Wheelchair Lifts. DIVISION 14 - CONVEYING SYSTEMS I. GENERAL A. This division contains: 1. Passenger Elevators 2. Vertical Platform and Inclined Wheelchair Lifts. B. Elevators in schools are for the disabled, furniture

More information

Overview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Edition

Overview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Edition Accreditation Overview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Primarily based on Section 907 Portions of Section 903 and 909 are included. Portions of Chapter 10 are included.

More information

Date: February 22, 2005 Kimbalton DUSEL, Pre-S-2 Submittal CNA0402 PRELIMINARY CODE REVIEW. International Plumbing Code Edition

Date: February 22, 2005 Kimbalton DUSEL, Pre-S-2 Submittal CNA0402 PRELIMINARY CODE REVIEW. International Plumbing Code Edition Kimbalton DUSEL Preliminary Code Study CNA0402 Date: Project: February 22, 2005 Kimbalton DUSEL, Pre-S-2 Submittal CNA0402 Note: Shaded Sections not complete. PRELIMINARY CODE REVIEW Building Code: International

More information

780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS

780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS 780 CMR: MASSACHUSETTS AMENDMENTS TO THE INTERNATIONAL BUILDING CODE 2009 CHAPTER 9: FIRE PROTECTION SYSTEMS 901.1 Add these notes: Note 1. Throughout Chapter 9, when reference to the International Plumbing

More information

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,

More information

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire

More information

IFC Significant Changes from the 2009 to the 2015 Edition Tier 1

IFC Significant Changes from the 2009 to the 2015 Edition Tier 1 IFC Significant Changes from the 2009 to the 2015 Edition Tier 1 Several medical care definitions were created and revised in Chapter 2 of the 2012 IBC, as well as through the occupancy descriptions, and

More information

Recommended Amendments to the 2003 International Fire Code North Central Texas Council of Governments region

Recommended Amendments to the 2003 International Fire Code North Central Texas Council of Governments region Recommended Amendments to the 2003 International Fire Code North Central Texas Council of Governments region The following sections, paragraphs, and sentences of the 2003 International Fire Code are hereby

More information

1301: Fire service features.

1301: Fire service features. ACTION: Original DATE: 10/18/2018 11:42 AM 1301:7-7-05 Fire service features. (A) Section 501 General (1) 501.1 Scope. Fire service features for buildings, structures and premises shall comply with this

More information

C. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID

C. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - 2000 LIFE SAFETY CODE Intermediate Care Facilities for the Mentally Retarded LARGE PART I Figure

More information

PERFORMANCE COMPLIANCE METHODS

PERFORMANCE COMPLIANCE METHODS CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2015 International Existing

More information

Life Safety - Means of Egress/Exits NFPA 101

Life Safety - Means of Egress/Exits NFPA 101 Life Safety - Means of Egress/Exits NFPA 101 Properly designed exits provide a safe path of escape from a fire or other emergency environment. The means of egress (exits) should be arranged to permit all

More information

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 21 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0300 - Other

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,

More information

Review of Revisions to NFPA 1, 2015 Edition

Review of Revisions to NFPA 1, 2015 Edition James S Peterkin, PE, LEED AP Senior Fire Protection Engineer TLC Engineering for Architecture Anthony Apfelbeck, CFPS, CBO, CFO, FM, FIFireE, MPA Building and Fire Official City of Altamonte Springs,

More information

Recommended Amendments to the 2009 International Building Code North Central Texas Council of Governments region

Recommended Amendments to the 2009 International Building Code North Central Texas Council of Governments region Recommended Amendments to the 2009 International Building Code North Central Texas Council of Governments region The following sections, paragraphs, and sentences of the 2009 International Building Code

More information

A17 Standards Committee Interpretations Volume 3

A17 Standards Committee Interpretations Volume 3 A17 Standards Committee Interpretations Volume 3 Page Interpretations Approved at the September 2009 A17 Standards Committee Meeting 2 Interpretations Approved at the January 2010 A17 Standards Committee

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional

More information

Recommended Amendments to the 2015 International Building Code North Central Texas Council of Governments Region

Recommended Amendments to the 2015 International Building Code North Central Texas Council of Governments Region Recommended Amendments to the 2015 International Building Code North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2015 International Building Code

More information

Culminating Project U.S. Federal Courthouse FPE Spring 2013

Culminating Project U.S. Federal Courthouse FPE Spring 2013 Culminating Project U.S. Federal Courthouse FPE 596 - Spring 2013 Joshua W. Elvove, PE, CSP, FSFPE NOT FOR PUBLIC DISTRIBUTION Statement of Disclaimer This project report is a result of a class assignment;

More information

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963) INFORMATION BULLETIN / PUBLIC - MECHANICAL CODE REFERENCE NO.: LAMC 91.8604 Effective: 6-20-84 DOCUMENT NO. P/MC 2002-005 Revised: 6-15-00 Previously Issued As: MGD #74 FIRE SAFETY REQUIREMENTS FOR PRE-

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

Elevator Emergency Equipment Instructor s Guide

Elevator Emergency Equipment Instructor s Guide Table of Contents Overview.......4 Sensory Inspection 11 Emergency Equipment in Elevator Systems..14 Fire Service Phase I & II 24 Summary..35 1 Icons Used In This Guide Agenda Topic # Topic Title Duration

More information

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL fpeschulte.

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL fpeschulte. SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 60202 fpeschulte@aol.com fpeschulte.com 504/220-7475 BALANCED FIRE PROTECTION: THE ATRIUM PROVISIONS By Richard Schulte Schulte

More information

2012 SunTrust Center ERT Annual Review. 919 East Main St. Richmond, VA

2012 SunTrust Center ERT Annual Review. 919 East Main St. Richmond, VA 2012 SunTrust Center ERT Annual Review 919 East Main St. Richmond, VA 1 & 2 Purpose of Emergency Response Program Emergency Response Team, Members and Responsibilities Evacuation Procedures Other Emergency

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General Requirements

More information

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible.. This

More information

MODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces

MODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces MODULE 8 Tying the Systems Together: Emergency Control Functions and Interfaces 1 OVERVIEW OF MODULE 8 In this module we will: Describe all components, their arrangements and how the systems work Describe

More information

Recommended Amendments to the 2018 International Fire Code North Central Texas Council of Governments Region

Recommended Amendments to the 2018 International Fire Code North Central Texas Council of Governments Region Recommended Amendments to the 2018 International North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2018 International (IFC) are hereby amended as

More information

Fire Alarm, Water Flow Alarm & Signaling Systems

Fire Alarm, Water Flow Alarm & Signaling Systems Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA 92602 www.ocfa.org 714-573-6100 Fire Alarm, Water Flow Alarm & Signaling Systems Guideline D-03 Serving

More information

Are there any policies regarding outlets that contain USB ports?

Are there any policies regarding outlets that contain USB ports? Answers to the Questions Mark J. Blackburn, P.E., CFPS February, 2016 Question 1 Are there any policies regarding outlets that contain USB ports? There is no direct reference in code about these types

More information

Fire Alarm System Fundamentals Presented By: Shamim Rashid-Sumar, Vice President Middle East Operations Rolf Jensen and Associates, Inc.

Fire Alarm System Fundamentals Presented By: Shamim Rashid-Sumar, Vice President Middle East Operations Rolf Jensen and Associates, Inc. Fire Alarm System Fundamentals Presented By: Shamim Rashid-Sumar, Vice President Middle East Operations Rolf Jensen and Associates, Inc. (RJA) Overview Understanding the Codes Fire Alarm Systems (Manual

More information

Osceola County Department of Fire Rescue and Emergency Medical Services

Osceola County Department of Fire Rescue and Emergency Medical Services St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner

More information

FIRE SAFETY SURVEY REPORT 2000 CODE - HEALTH CARE Medicare Medicaid

FIRE SAFETY SURVEY REPORT 2000 CODE - HEALTH CARE Medicare Medicaid DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICES FIRE SAFETY SURVEY REPORT - HEALTH CARE Medicare Medicaid 1. (A) PROVER NUMBER PART I Life & Safety Code, New and Existing

More information

SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE

SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE Summary Guadalupe County requirements for the Permit Issuance and safe operation of a Temporary Special Amusement Occupancy. PURPOSE To

More information

Chapter 4: Fire Protection Systems

Chapter 4: Fire Protection Systems Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 41 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0011 - LIFE SAFETY CODE STANDARD If the building has a common wall with a nonconforming building, the common

More information

FEO Initiation Devices Dean McLellan

FEO Initiation Devices Dean McLellan FEO Initiation Devices Dean McLellan Enforcement Protocol 1. TSSAct 2. Ontario Regulation 209/01 3. Code Adoption Document (CAD) 4. Director s Orders 5. Applicable Code 1. Sub Codes (NBCC, CEC) A17/B44

More information

2012 B.C. Building Code Compliance Review (Division B Part 3)

2012 B.C. Building Code Compliance Review (Division B Part 3) Planning and Building Department 2012 B.C. Building Code Compliance Review PROJECT NAME:.. CIVIC ADDRESS:...... PERMIT APPLICATION NO.:. DATE:... I,, have: 1. reviewed the design, plans and supporting

More information

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,

More information

FINAL REPORT* OF THE MOTIONS COMMITTEE 2015 ASSOCIATION TECHNICAL MEETING JUNE 22-25, 2015 CHICAGO, IL

FINAL REPORT* OF THE MOTIONS COMMITTEE 2015 ASSOCIATION TECHNICAL MEETING JUNE 22-25, 2015 CHICAGO, IL FINAL REPORT* OF THE MOTIONS COMMITTEE 2015 ASSOCIATION TECHNICAL MEETING JUNE 22-25, 2015 CHICAGO, IL I. Introduction This is the second and Final Report* of the s Committee listing Certified Amending

More information

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

More information

Defend In Place 2012 IFC Overview of Institutional Occupancies

Defend In Place 2012 IFC Overview of Institutional Occupancies Defend In Place 2012 IFC Overview of Institutional Occupancies ICC Course No. ICC CEU s = 0.50 SCFA Course 8506-15-0 Nathan Ellis Cell: 864-812-5183 Nathan.Ellis@llr.sc.gov Institutional Occupancies Course

More information

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c Table 1015.1 EXIT ACCESS TRAVEL DISTANCE a WITHOUT SPRINKLER WITH SPRINKLER OCCUPANCY SYSTEM SYSTEM A, E, F-1, I-1, M, 200 250 b,d R, S-1 B 200 300 c F-2, S-2, U 300 400 c No Change to Other Entries in

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 75 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K0100 - General Requirements - Other Title General Requirements - Other General Requirements - Other List in the REMARKS

More information

K SURVEY FOR DATE OF PLAN APPROVAL SURVEY UNDER

K SURVEY FOR DATE OF PLAN APPROVAL SURVEY UNDER DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICES FIRE SAFETY SURVEY REPORT - HEALTH CARE Form Approved OMB No. 0938-0242 1. (A) PROVER NUMBER 1. (B) MEDICA I.D. NO. 1. HOSPITAL

More information

5123: information. The graphic plan shall include, but may not be limited to: (a) A primary and secondary means of exit from each floor;

5123: information. The graphic plan shall include, but may not be limited to: (a) A primary and secondary means of exit from each floor; ACTION: Original DATE: 09/30/2005 1:17 PM 5123:2-3-11 Fire safety and emergency response plans. (A) Purpose The purpose of this rule is to ensure the safety of individuals residing in residential facilities

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary SECTION 910 SMOKE AND HEAT VENTS 910.1 General. Where required by this code or otherwise installed, smoke and heat vents or mechanical smoke exhaust systems and draft curtains shall conform to the requirements

More information