CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION
|
|
- Cameron Heath
- 6 years ago
- Views:
Transcription
1 CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT In Poland, a valid approach for fire ventilation of an underground metro station is to use a longitudinal system similar to the ventilation systems used in tunnels. Such system may provide similar environmental conditions to transverse systems on the station platform, while maintaining smoke free access through the station galleries. In order to do so, designer must carefully balance the air flow into the station, through mechanical and natural means. In this papers authors present results of short numerical study, on how to achieve this balance, along with their reflections after 6 months of performing hot smoke tests in a large underground metro system. Keywords: ventilation design, metro systems, longitudinal ventilation 1. INTRODUCTION An underground public transport system is one of the most commonly used solution in modern, overfilled with road traffic, cities. The main advantage of such system is the ability to move a large amount of people from one point of traffic network to another. With this benefits, comes an increased risk of fire, thus special care on the field of fire protection of such facility has to be taken into consideration. The underground stations are very specific form of construction work usually long compartments with low height and average of 2 3 escape routes. The fire scenarios connected to the fire of a train show, that growth of fire can be very fast and amounts of smoke produced big enough, to fill such a place in matter of minutes. To keep the evacuation routes safe from smoke, a smoke exhaust systems are developed, based on different approaches and different strategies, varying from longitudinal to transversal solutions. What is especially difficult, these systems have to take into account not only the station itself, but also the possible air-streams coming from adjacent tunnel network often difficult to assess at the design stage. In Polish legislation, the design of ventilation system in a metro system is described in Technical Guidelines for Metro Construction Works and Their Placement (Regulation no 859 D.U. 144, ) [1]. In the appendix 1 of the Act, there is a requirement for provision of a functional ventilation system, that is protecting the station, exits and other critical infrastructure from heat and smoke. More to that, the tunnels longer than 300 m shall also be fit with mechanical ventilation. For the design, a minimum HRR value of 15 MW shall be used (unless determined otherwise with engineering analysis). The same act also provides the designer with acceptance criteria: o temperature not higher than 60 C at a height of 1,80 m above evacuation route; o radiated heat flux not higher than 2,50 kw/m², for an exposition time of 30 s; o temperature of smoke and other combustion products not higher than 200 C at a height of 2,50 m above the evacuation route; o visibility range not lower than 10 m, at a height of 1,80 m above the evacuation route; o oxygen concentration not lower than 15%.
2 For the required safe evacuation time calculations, a minimum safety factor of 1,30 should be used. The evacuation route is considered safe, when the available safe evacuation time (ASET) is longer than the required safe evacuation time (RSET). 2. VENTILATION STRATEGY Authors determine three types of ventilation of a station, which can fulfil the requirements of [1]: o transverse ventilation system designed according to the building regulations, following the axisymmetric or spill plume assumption and according laws of physics that apply; o transverse ventilation system with compartmentation between the platform and a train, which can be used to limit the amount of smoke reaching the station; o longitudinal system using points of exhaust within the tunnels and at the ends of the station. Despite the fact these systems differ in their principles, all are able to provide sufficiently clear of smoke escape routes, limit the spread of smoke and heat through the station and its surroundings, and provide possibility for rescue services to operate within the station, as shown on figure 1. In the opinion of authors, the design of transverse systems, with and without comparmentation, is generally well described in the literature. References worth mention are [2], in which some general rules for building ventilation employing transverse smoke movement are presented, and [3, 4] in which results of various engineering analysis in this field are presented. Figure 1: Hot smoke test in a Metro station, with transverse (left) and longitudinal (right) system For a longitudinal station ventilation system, between many, this paper focuses on following three key aspects that have to be determined by the designer: o division of the station into detection zones; o points of smoke exhaust; o points of supply and their capacity, usage of natural station exits as the supply points, technical provisions to keep them free of smoke (i.e. smoke barriers) Separation of the station into detection zones In most tunnel ventilation systems, typical metro station allows a bi-directional flow of smoke, towards either of its portals. This allows for a natural division of the station into two virtual smoke zones. The line of separation may be symmetrical in the middle of the station, which in general is advised in most applications, or asymmetrical for example at one of the
3 station entrances (Figure 2). If the portals of the station are equipped with ventilation points in each of tubes, and allow to operate them independently, it might be possible to always use the point of exhaust in the tube corresponding to the track, on which engulfed train is detected, but this may require further subdivision of the detection zones. Figure 2: Bi-directional detection zoning axisymmetric (1) and asymmetric (2) and four zone detection zoning (3) The influence of separating the station smoke or detection zones should not be trivialised, as this design decision will determine the area of the station that may be filled with smoke in case of fire. This will be explained further in paragraphs 2.2 and 2.3. Designer must be also aware of possible detection methods: a) point detection (heat, smoke); b) linear heat or smoke detection; c) flame detection. In case of point detection, the fire location is pointed with great precision, unless the flow of smoke was affected or redirected away from the fire (in example by opening one door on other end of the burning metro car). In case of linear heat or smoke, or flame detection, the location is more an approximation within the detection area. In case of fire at the boundary of smoke detection zone, system is expected to operate in a way, that will provide necessary environmental conditions, despite the scenario that is activated. Physical barriers at the smoke zone boundaries could provide help, but may be impossible to fit within the architectural framework of a station Determination of points of exhaust location Due to typical division of a metro system into stations connected with tubes, typical layout of ventilation system will usually consist of multiple tunnel and station exhaust points, in various combinations (Figure 3). Presence of an exhaust point in the middle of a tunnel, and two points at each of it ends may seem as safe design, but usually will not provide other benefits beside limiting the length of tunnel that is filled with smoke. On the other side, having at least two separate exhaust points within one tunnel (ie. middle of the tunnel and one of its ends) may be worth, due to possibility of altering the supply airflow, and overcoming natural flows that can occur in the system.
4 Figure 3: Possible exhaust points locations in a longitudinal approach of station ventilation connected to a tunnel (top) and a crossway (bottom) The sizing of the exhaust points is out of the scope of this paper, although the designer has to acknowledge, that the combined efficiency of two exhaust points located in different parts of the system (portals, tunnel, ends of stations) may be worse than the efficiency of a single point with the same volumetric capacity Determination of supply air location and its balance For stations protected with longitudinal systems, the provision of fresh air is the most critical aspect, that influences the flow pattern of smoke within the protected volume. Air may be provided through (figure 4): o tunnel portals; o tunnel air supply points (reversed exhaust points); o station air supply points (reversed exhaust points); o station entrances. Figure 4: Possible supply points in axisymmetric (top) and asymmetric (bottom) longitudinal ventilation system The location of supply points does not solely determine the strategy of air supply within a system it may be different in stations at different depths or remote parts of metro system, as shown in the numerical study. This strategy should always be a result of an engineering approach with at least a 1-D flow simulation. Authors of the paper for this task employ a 3-D model of complete metro system with its surroundings, solved with a CFD model. The amount of air supplied into the system can be controlled by balancing the amount of air supplied and exhausted through mechanical points. Natural supply points, unless located in great depth, will act as free boundaries of the system, balancing the difference between the mechanical supply and exhaust. It must be noted, that in some cases natural flows may occur in the tunnel, that can strongly disturb the air balance in the ventilation system. In such case it is advised to use additional supply/exhaust points, even at great distance from the fire just to control the air velocity in remote areas of the system. In some scenarios, same effect may be reached with use of air curtains [5, 6].
5 NUMERICAL STUDY In order to visualize the importance of balancing supply and exhaust rates for different protection scenarios, authors have performed a series of numerical studies on an air flow in metro system in fire conditions, as shown in table 1. Scheme of the metro system with supply and exhaust points is presented on Figure 6. All of the stations of the system were connected to the exterior through a gallery, and were part of the same numerical domain. The numerical model is shown on Figure 7. Figure 6: Simplified schematic of numerical model used in the research, with the reference names for exhaust and supply points. Fire was located in the middle of station A2, that was assumed to be asymmetrically divided into two smoke zones. Three fire powers were analyzed 5 MW, 15 MW and 25 MW, and the assessment was performed 5 minutes after the peak power was reached (steady state conditions). System capacity was chosen as 300 m³/s, although some of the simulations were later rerun with capacity of 150 m³/s (out of the scope of this paper). All calculations were performed using ANSYS Fluent CFD model, for transient conditions. K-ε turbulence model (standard) was used for the turbulent flow, and P1 model for radiation. Walls were made from concrete, while train was made with insulated steel. Figure 7: Part of numerical model used in the analysis (station) Table 1: Scenario matrix Scenario Exhaust Supply Comment 1 A2W B2T 50% of supply through station A2 entrance 2 A2W + B3T B2T 50% of supply through station A2 entrance 3 B3T B2T 50% of supply through station A2 entrance 4 A2W B2T 10% of supply through station A2 entrance 5 B3T A2E + B2T 50% of supply through station A2 entrance 6 A2W (L) A2E + B2T exhaust only through one tube 7 B3T (L) A2E + B2T exhaust only through one tube
6 RESULT ANALYSIS In first three scenarios, Authors were investigating the influence of changing the exhaust point location, and combination of two different points, on the system performance. No difference on the system performance was observed in the station itself, although the flow within the adjacent tunnel tube and the galleries differed in each of the scenarios (Figure 8). In the scenarios using the tunnel exhaust point, the smoke did not move further than the exhaust point location, although in scenario 1 at fire power of 25 MW some smoke movement was observed into one of the tunnel tube. In all of the three compared scenarios, the gallery was free of smoke the smoke did stop at the smoke screen, and was pushed away from the entrance due to large flow of incoming air (Figure 9). In scenario 4, in which 90% of air was supplied through mechanical supply, smoke penetrated gallery of the station after approx. 5 minutes of the study, as shown in Figure 10. This may be directly dangerous to life and health of occupants, as they may not be expecting hot smoke to appear in such distance from the fire. Similar effect was observed in hot smoke tests, when the air balance did not allow natural air supply through station entrances. Figure 8: Comparison of local visibility of walls (0 20 m, and more) at height of 2,00 m above the platform for different scenarios, and different fire power within a chosen scenario Figure 9: The influence of the smoke screen on the flow of air at supply point, at 5 MW fire (left) and 25 MW fire (right) In scenario 5, the effect of incorrect fire detection was determined. As mentioned before in the text, the system is expected to cope with incorrect detection at the zone boundary, as it may be impossible to utilize physical comparmentation of the zones. In the simulation, for just the platform level, the system did remove the smoke through exhaust point B2T (Figure 11), although it must be noted that some smoke was observed at the gallery level for the fire of 25 MW. In this case, this might be accepted by the Authority, as the simulation did prove the robustness of the system design.
7 Figure 10: Smoke penetration of the station gallery in scenario 4 at 25 MW effect of too strong mechanical air supply into the station Figure 11: Effect of system starting in incorrect scenario mode In scenarios with single point of exhaust (only left or right) tube the positive effect of smoke filling of only a quarter of the station was only observed for the 5 MW fire. In larger fires, this effect diminished. The positive effect observed in simulation is in line with authors observations during hot smoke tests, although in real scale fires larger than 2 MW were not tested, Figure 13. For larger fires, smoke movement in second tunnel tube was observed towards adjacent station this was also observed in some of the full scale tests. In the simulation, after approx. 20 minutes of simulation, the smoke penetrated approx. 70% of the tunnel length (figure 12) in the full scale test similar effect was observed in time of 15 to 25 minutes. Figure 12: Upstream movement of smoke after 20 minutes of simulation (scenario 7)
8 Figure 13: Smoke movement in one quarter of the station in a hot smoke test and in simulation (scenario 7) 5. CONCLUSIONS Longitudinal system may be a valid solution in a simple metro station, although its design requires wide investigation of many system parameters such as supply air location, air balance or usage of physical boundaries (like smoke barriers). Even at fires of 25 MW power, longitudinal system was able to provide both safe approach for firefighters, and smoke-free galleries of the metro station. This was possible mainly due to fact, that large amount of air was supplied into the station through the connection with the gallery creating an air flow that prevented smoke movement into the gallery. This is consistent with observations of authors, done during full scale tests of complete metro system. The airflow pattern in the system, especially in the station galleries, changed with the growing HRR of the fire, which shows that just cold flow assessment is insufficient for this design task. Literature [1] Technical Guidelines for Metro Construction Works and Their Placement (Regulation no 859 D.U. 144, ) [2] Milke A.J., Smoke Control by Mechanical Exhaust or Natural Venting, in SFPE Handbook of Fire Protection Engineering, 5 th Edition, Springer 2016 [3] Na Meng, Longhua Hu, Long Wu, Lizhong Yang, Shi Zhu, Longfei Chen, Wei Tang, Numerical study on the optimization of smoke ventilation mode at the conjunction area between tunnel track and platform in emergency of a train fire at subway station, Tunnelling and Underground Space Technology Volume 40, February 2014, Pages [4] R. Harish, K. Venkatasubbaiah, Effects of buoyancy induced roof ventilation systems for smoke removal in tunnel fires, Tunnelling and Underground Space Technology Volume 42, May 2014, Pages [5] G. Krajewski, Air barriers used for separating smoke free zones in case of fire in tunnel, Proc. 7th International Conference Tunnel Safety and Ventilation Graz, 2014 [6] G. Krajewski, W. Węgrzyński, Air curtain as a barrier for smoke in case of fire: Numerical modelling, Bulletin of the Polish Academy of Sciences Technical Science, vol. 63, 2015
Sprinklers Modeling for Tunnel Road Fire Fighting
Sprinklers Modeling for Tunnel Road Fire Fighting P. Ciambelli, M.G. Meo, P. Russo, S. Vaccaro Department of Chemical and Food Engineering, University of Salerno - ITALY 1. INTRODUCTION Loss of lives and
More informationCase Study 1 Underground Car Park
Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building
More informationTunnel Fire Dynamics and Evacuation Simulations
Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation
More informationCase Study 2 Production and Storage. SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB)
Case Study 2 Production and Storage SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB) So What Are You We Going to Show You? A lot of tables, simplified methods
More informationOPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE
OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE 1 RU ZHOU, 2 WEI ZHANG 1 School of Urban Construction and Safety Engineering, Nanjing University of Technology, Nanjing
More informationCFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS
CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS Yunlong Liu*, Xijuan Liu and Bradley Paroz Fire Science and Technology Laboratory CSIRO Manufacturing and Infrastructure Technology
More informationCFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS
CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS Yunlong Liu*, Xijuan Liu and Bradley Paroz Fire Science and Technology Laboratory CSIRO Manufacturing and Infrastructure Technology PO Box 310 North
More informationImpact of quick incident detection on safety in terms of ventilation response
Impact of quick incident detection on safety in terms of ventilation response P. J. Sturm 1) ; C. Forster 2) ; B. Kohl 2) ; M. Bacher 1) 1) Institute for Internal Combustion Engines and Thermodynamics
More informationThird Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG
1 Third Runway Project APM Depot Fire Engineering Design Presented by Ir Wilson Sau-kit TSANG 1 2 Presentation Overview 1. Project Background and Depot Overview 2. Building Information and Challenge for
More informationCase Study of Underground Car Park. Team Japan
11th Conference on Performance Based Codes and Fire Safety Design Methods Case Study of Underground Car Park Team Japan We focused on the characteristics of the fire behavior of car fire. Car fire is not
More informationRETOS Y TENDENCIAS DESARROLLO DE INFRAESTRUCTURA EN AUSTRIA. Leonardo Rosas Sánchez Bogotá Agosto 9 de 2018
RETOS Y TENDENCIAS DESARROLLO DE INFRAESTRUCTURA EN AUSTRIA Leonardo Rosas Sánchez Bogotá Agosto 9 de 2018 Table of content 1. Safety standards for road and railway tunnels 2. Upgrading the Alrberg Tunnel
More informationSTUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED
- 133 - STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED Y. Mikame 1,2, N. Kawabata 1, M. Seike 1, M. Hasegawa 1 1 Kanazawa University, Japan 2 Metropolitan Expressway Company
More informationCFD Analysis of Fire Characteristics on Subway Junction Station
ISGSR27 First International Symposium on Geotechnical Safety & Risk Oct. 18~19, 27 Shanghai Tongji University, China CFD Analysis of Fire Characteristics on Subway Junction Station G. H. Wu, X. Han, Q.Q.
More informationHot Issues in Fire Engineering July 2014
Hot Issues in Fire Engineering July 2014 Crowded Railway Stations and Train Compartments to Watch Y.W. Ng and W.K. Chow, JP FHKEng Research Centre for Fire Engineering, Department of Building Services
More informationEmergency Ventilation System Design - Preliminary Report Shishir Gupta
Emergency Ventilation System Design - Preliminary Report Shishir Gupta (shishir@mechartes.com), Abstract The existing stations and tunnels of Metro Railway, Kolkata are not equipped with effective emergency
More informationFire and smoke management in a uni-directional road tunnel for a congested traffic condition
Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Y Liu, J Munro Parsons Brinckerhoff Australia B Dandie Thiess Pty Ltd., Australia ABSTRACT Emergency smoke ventilation
More informationAn experimental study of the impact of tunnel suppression on tunnel ventilation
An experimental study of the impact of tunnel suppression on tunnel ventilation Yoon J. Ko and George Hadjisophocleous Civil and Environmental Engineering, Carleton University 1125 Colonel By Drive, Ottawa,
More informationStudy of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan
Open Journal of Fluid Dynamics, 2017, 7, 205-218 http://www.scirp.org/journal/ojfd ISSN Online: 2165-3860 ISSN Print: 2165-3852 Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke
More informationConsiderations in the Design of Smoke Management Systems for Atriums
Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke
More informationHot Issues in Fire Engineering 12 March 2013
Hot Issues in Fire Engineering 12 March 2013 An Update on Design Fires of Vehicular Tunnels W.K. Chow Fellow, Hong Kong Academy of Engineering Sciences Research Centre for Fire Engineering, Department
More informationSimple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings
Fire Science and Technorogy Vol.24 No.4(2005) 165-178 165 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Jun-ichi Yamaguchi 1, Takeyoshi Tanaka 2 1 Technical Research
More informationFINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS
- 203 - FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS Hofer R., IBS Institute for Technical Fire Protection and Safety Research, Linz / Austria
More informationSCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS
, Volume 11, Number 2, p.21-26, 212 SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS C.Y. Tso and W.K. Chow Research Centre for Fire Engineering,
More informationSOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM
- 157 - SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM Kratzmeir S. FOGTEC Fire Protection, Research & Development, Germany Keywords: Fire Protection, Fire suppression,
More informationPerformance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Evaluation and Design Optimization of Refrigerated Display
More informationCOSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN
COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING
More informationCFD STUDY OF FIRE PROTECTION SYSTEMS IN TUNNEL FIRES
UDC 614.84 : 628.854 : 52-17 DOI: 10.7562/SE2011.1.01.03 Original article www.safety.ni.ac.rs DARKO ZIGAR 1 DESIMIR JOVANOVIĆ 2 MARTINA ZDRAVKOVIĆ 3 1-4 University of Niš, Faculty of Occupational Safety
More informationNUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM
, Volume 11, Number 2, p.43-48, 2012 NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM Q. Kui Institute of Building Fire Research, China Academy of Building Research, Beijing,
More informationUsing FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels
Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels Jack R. Mawhinney, P. Eng., FSFPE Javier J. Trelles, Ph.D. Authors & acknowledgement J. R. Mawhinney
More informationEMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT TASK 363)
EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT 20-07 TASK 363) Louis Ruzzi PennDOT District 11 Igor Maevski, PhD, PE - Jacobs Agenda AASHTO T20 Technical Committee Roadway Tunnels
More informationCase Study 1 Underground car park
Case Study 1 Underground car park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, INBEPO Wroclaw, Poland 1. Introduction
More informationSTACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING
STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING H. Kotani, R. Satoh, T. Yamanaka Dept. of Architectural Engineering, School of Engineering, Osaka University, Osaka, Japan ABSTRACT The purpose
More informationHow to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs
How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada
More informationComputational simulation of road tunnel fire protection by sprinklers
European Journal of Environmental and Safety Sciences 2014 2(2): 48-52 ISSN 1339-472X European Science and Research Institute (Original Research Paper) Computational simulation of road tunnel fire protection
More informationAPPLICATION OF CFD SIMULATIONS FOR LOCATING OUTDOOR UNITS ON HIGH RISE TOWER Basant Kumar Gupta 1, Anand Patil 2
APPLICATION OF CFD SIMULATIONS FOR LOCATING OUTDOOR UNITS ON HIGH RISE TOWER Basant Kumar Gupta 1, Anand Patil 2 1 Zeus Numerix Private Limited, Pune, India 2 Pankaj Dharkar & Associates, Mumbai, India
More informationModeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room
Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Y. Momoi 1, K. Sagara 1, T. Yamanaka 1 and H. Kotani 1 1 Osaka University, Graduate School of Eng., Dept.
More informationand Sprinkler System in Resalat Tunnel of Tehran
CFD Simulation of Water Mist and Sprinkler System in Resalat Tunnel of Tehran Motivation Resalat tunnel is the first road tunnel in Tehran one of most crowded tunnels of Tehran my every day route, home
More informationJapanese Case Study: How to maintain the fire safety in subway station and tunnel
Japanese Case Study: How to maintain the fire safety in subway station and tunnel Takashi Kusa Railway International Standards Center 12 October 2011 Contents About Railway International Standards Center
More informationStudy of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Abbreviations Keywords Abstract Introduction and Background
Study of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Siddharth Jain, Yogesh Deshpande, Atul Bokane, Arun Kumar Santharam, and Deepak Babar, Halliburton Abbreviations: Computational
More informationFire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel
Safety and Security Engineering VI 73 Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel M. Lombardi & G. Rossi Dipartimento di Ingegneria Chimica
More informationResearch on Mobile Water Spray Device Reducing the Temperature of Metro Fire
Applied Mechanics and Materials Online: 2012-05-14 ISSN: 1662-7482, Vols. 166-169, pp 2731-2734 doi:10.4028/www.scientific.net/amm.166-169.2731 2012 Trans Tech Publications, Switzerland Research on Mobile
More informationPerformance-based Fire Design of Air-supported Membrane Coal Storage Shed
Available online at www.sciencedirect.com Procedia Engineering 52 ( 2013 ) 593 601 Performance-based Fire Design of Air-supported Membrane Coal Storage Shed ZHANG Lei a,b, ZHU Guo-qing a,b,*, ZHANG Guo-wei
More informationNUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro
Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT Z. Stevanovic 1, T. Valentina 1, N. Kadic 1, Z. Markovic 1,
More informationLONGITUDINAL VENTILATION FOR SMOKE CONTROL IN A TILTED TUNNEL BY SCALE MODELING
LONGITUDINAL VENTILATION FOR SMOKE CONTROL IN A TILTED TUNNEL BY SCALE MODELING W.K. Chow, and W.Y. Chung Research Centre for Fire Engineering, Department of Building Services Engineering Area of Strength:
More informationTUNPROTEC. Active Tunnel Fire Protection
VID FIre KIll TUNPROTEC Active Tunnel Fire Protection 9 An Active Tunnel Fire General The tunnel structures are very valuable. Infrastructure tunnels, such as train tunnels and road tunnels represent very
More informationINFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS
INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS Staņislavs GENDELIS, Andris JAKOVIČS Laboratory for mathematical modelling of environmental
More informationGerd Koffmane, Henrik Hoff, AP Sensing GmbH, Böblingen
Linear Heat Series Under Test: Extensive fire tests prove Distributed Temperature Sensing (DTS) enables fast and reliable control of fire protection systems in road and rail tunnels Gerd Koffmane, Henrik
More informationISO/TR TECHNICAL REPORT. Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people
TECHNICAL REPORT ISO/TR 16738 First edition 2009-08-01 Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people Ingénierie de la sécurité incendie Informations
More informationANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS
ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS Prepared for Smoke Safety Council 6775 SW 111 th Avenue, Suite 10 Beaverton, OR 97008 Prepared by Jesse J. Beitel Alison J. Wakelin Craig L.
More informationEffects of Smoke on Evacuation Martin Lopušniak 1, a
Advanced Materials Research Online: 2014-02-27 ISSN: 1662-8985, Vol. 899, pp 539-542 doi:10.4028/www.scientific.net/amr.899.539 2014 Trans Tech Publications, Switzerland Effects of Smoke on Evacuation
More informationVirtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel
Virtual : An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Xiaolei Chen, PhD California State University, Los Angeles, United States Ning (Frank) Wang, P.E. Jensen Hughes,
More informationA New Zealand Case Study Building Design 11 th International Conference on Performance
A New Zealand Case Study Building Design 11 th International Conference on Performance Prof Charles Fleischmann University of Canterbury Dept. Civil and Nat Res Eng. Christchurch, New Zealand Carol Caldwell
More informationA Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space
Available online at www.sciencedirect.com Procedia Engineering 31 (2012) 734 738 International Conference on Advances in Computational Modeling and Simulation A Numerical study of the Fire-extinguishing
More informationEXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION
Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Liu Jing 1, Yoshihiro Aizawa 2, Hiroshi Yoshino 3 1 School of Municipal
More informationZONE MODEL VERIFICATION BY ELECTRIC HEATER
, Volume 6, Number 4, p.284-290, 2004 ZONE MODEL VERIFICATION BY ELECTRIC HEATER Y.T. Chan Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Selecting
More informationNumerical Simulation of Ventilation Efficiency in Commercial Kitchen
Numerical Simulation of Ventilation Efficiency in Commercial Kitchen Yasushi Kondo 1, Shin-ichi Akabayashi 2, Osamu Nagase 3 and Akihiko Matsuda 4 1 Dept of Architecture, Musashi Institute of Technology,
More informationand vent height on mechanical smoke exhaust efficiency
Experimental investigation on influence of smoke venting velocity and vent height on mechanical smoke exhaust efficiency Ji Jie a, Li Kaiyuan b, Zhong Wei c, *, Huo Ran a a State Key Laboratory of Fire
More informationincorporating Contractors guide to car park ventilation A no-nonsense guide to the safe ventilation of underground and covered car parks
incorporating Contractors guide to car park ventilation A no-nonsense guide to the safe ventilation of underground and covered car parks Car park ventilation What are the regulations? Ventilation of car
More informationFull-scale Experiment of Longitudinal Ventilation Smoke Control System and Central Smoke Exhaust System in City Underwater Tunnel
Available online at www.sciencedirect.com Procedia Engineering 52 ( 2013 ) 330 335 Full-scale Experiment of Longitudinal Ventilation Smoke Control System and Central Smoke Exhaust System in City Underwater
More informationCase Study 2 (Production and Storage Buildings) - Spain
Case Study 2 (Production and Storage Buildings) - Spain OBJECTIVE Developed by the SFPE Spanish Chapter Editor: Jimmy Jönsson, JVVA Fire & Risk The objective of this case study is to show how a project
More informationStatue of Liberty: A Risk Analysis
Statue of Liberty: A Risk Analysis Bruce Campbell, FSFPE VP DOE Services National Park Service Agenda Overview of Project Scope Evaluation Steps Task 1 Code Analysis Task 2 Fire Modeling Task 3 Egress
More informationIFireSS International Fire Safety Symposium Coimbra, Portugal, 20 th -22 nd April 2015
IFireSS International Fire Safety Symposium Coimbra, Portugal, 20 th -22 nd April 2015 SCALE MODEL EXPERIMENTS ON SMOKE MOVEMENT IN A TILTED TUNNEL photo Author 1 30 mm 40 mm photo Author 2 30 mm 40 mm
More informationUnit 2 Fire Safety (Zone 1)
IFE Level 3 Diploma in Fire Safety and Fire Science Unit 2 Fire Safety (Zone 1) Examiner Report March 2018 Introduction 42% of candidates attained a Pass. Half of the candidates that attained a Pass secured
More informationAdvantages and Disadvantages of Fire Modelling
Advantages and Disadvantages of Fire Modelling Dr Guillermo Rein School of Engineering University of Edinburgh & Imperial College London Dr Guillermo Rein 9 May 2012 Chief Fire Officers Association Annual
More informationRoad tunnel safety rules in Italy: the tunnel country
Safety and Security Engineering II 317 Road tunnel safety rules in Italy: the tunnel country M. Guarascio, M. Lombardi, G. Rossi & G. Sciarra Safety Engineering Sapienza, Rome University, Italy Abstract
More informationAmerican Society of Heating, Refrigerating and Air-Conditioning Engineers
Flow Pattern and Thermal Comfort in Office Environment with Active Chilled Beams Journal: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Manuscript ID: Draft Publication:
More informationShuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan
INDOOR CLIMATE DESIGN BASED ON FEEDBACK CONTROL OF HVAC COUPLED SIMULATION OF CONVECTON, RADIATION, AND HVAC CONTROL FOR ATTAINING GIVEN OPERATIVE TEMPERATURE Shuzo Murakami, Shinsuke Kato, and Taeyeon
More informationImpact of indirect evaporative air cooler type on the performance of desiccant systems
Impact of indirect evaporative air cooler type on the performance of desiccant systems Anna Pacak 1,*, Aleksandra Cichoń 1, Demis Pandelidis 1, and Sergey Anisimov 1 1 Wrocław University of Science and
More informationMobile ventilation units in tunnels
Mobile ventilation units in tunnels Xavier Deckers Mathieu Verpaele FIRE ENGINEERED SOLUTIONS GHENT BVBA (FESG) Oudenaardsesteenweg 32 G B - 9000 Gent T: +32 9 280 03 69 E: info@fesg.be W: www.fesg.be
More informationAvailable online at ScienceDirect. Procedia Engineering 135 (2016 )
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 135 (2016 ) 275 280 Numerical Simulation on Impacts of Longitudinal Ventilation on Tunnel Fire Detection Qi Li a, Zheng Fang
More informationThe first tunnel fire. Benefits of fire
Benefits of fire suppression Quantifying the effects of suppression on energy release. This article by Fathi Tarada, managing director of fire safety, risk management, ventilation and CFD consultant Mosen
More informationA comparison between emergency ventilation systems semi-transvers ventilation and natural ventilation in Road Tunnel A
A comparison between emergency ventilation systems semi-transvers ventilation and natural ventilation in Road Tunnel A Ludwig Jerräng Carlstedt Fire Protection Engineer, bachelor's level 2017 Luleå University
More information5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea
5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea PRACTICAL APPLICATIONS OF FIRE MODELING IN INDUSTRIAL APPLICATIONS By James M. Dewey, Advisor Risk Management
More informationVertical Distribution of Air Temperatures in Heated Dwelling Rooms
Vertical Distribution of Air Temperatures in Heated Dwelling Rooms Ondrej Sikula University of Technology Brno, Brno Corresponding email: sikula.o@fce.vutbr.cz SUMMARY The paper presents an experimental
More informationTRANSACTIONS ON ADVANCEMENTS IN SCIENCE AND TECHNOLOGY (TASTONLINE)
Optimization and Performance Analysis of Riser Tubes in Solar Flat Plate Collector H.Saravanan 1, S.Vignesh 2, S.V. Alagarsamy 2 1 PG Scholar (Engineering Design), Dept. of Mechanical Engineering, Mahath
More informationAnalysis of the influence of open door size on fire smoke diffusion law in protective engineering
Analysis of the influence of open door size on fire smoke diffusion law in protective engineering Abstract Zheli Xing a, Jinfeng Mao b, Chaofeng Li c and Jin Zhou d PLA University of Science and Technology,
More informationSmoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates
Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates Zhou Y., Fei Y.*, Hu S. Q. Nanjing Tech University, College of Fire Safety Science and Engineering &
More informationASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER
, Volume 9, Number 1, p.38-58, 2007 ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER C.W. Leung and W.K. Chow Department of Building Services Engineering, The Hong Kong
More informationFirefighting operations on multi-tiered vehicle stacking buildings F5-13 GD
DESIGNER S GUIDE Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD Introduction When to use Scope Use this chapter to provide a consistent Fire and Emergency New Zealand position
More informationSmoke control in car parks
Smoke control in car parks The actual situation in CEN TC 191 SC1 WG9 Imagine the result Jean-Claude DE SMEDT MIFireE,MSFPE,MNFPA Senior Fire Safety Engineering Consultant @ ARCADIS Belgium Convener of
More informationCOMPARISON OF CFD MODELLING WITH FIRE TESTS Comparison of CFD Modelling with Results of Full Scale Compartment Fire Tests in a Residential Unit
Application of Structural Fire Engineering, 19-20 April 2013, Prague, Czech Republic COMPARISON OF CFD MODELLING WITH FIRE TESTS Comparison of CFD Modelling with Results of Full Scale Compartment Fire
More informationDesign of Fire safety in Multi Occupancy Residential Accommodation
Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability
More informationA study for a fire spread mechanism of residential buildings with numerical modeling
Safety and Security Engineering IV 185 A study for a fire spread mechanism of residential buildings with numerical modeling C.-S. Ahn & J.-Y. Kim Fire Safety Research Division, Korea Institute of Construction
More informationGeneral Principles of Smoke Control
AMCA International General Principles of Smoke Control Patrick Janssens, Sales Manager Colt International www.coltinco.co.uk or www.coltinfo.be Air System Engineering & Technology (ASET) Conference Europe
More informationA case study for integrated modelling of personnel evacuation with pool fire simulation to increase safety in design for offshore oil and gas projects
A case study for integrated modelling of personnel evacuation with pool fire simulation to increase safety Davood Afshari 1 Richard Welsh 2 Maryam Moghaddas 3 Sara Afsharikia 1 Amir Tavakoli 4 1 Lead Technical
More informationDeveloping a Fire Test Strategy for Storage Protection Under Sloped Ceilings
Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings Justin A. Geiman, Noah L. Ryder Fire & Risk Alliance, Rockville, MD, USA André W. Marshall Custom Spray Solutions, Silver Spring,
More informationWATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS
WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,
More informationTest One: The Uncontrolled Compartment Fire
The University of Edinburgh BRE Centre for Fire Safety Engineering One Day Symposium on The Dalmarnock Fire Tests: Experiments & Modelling Test One: The Uncontrolled Compartment Fire Cecilia Abecassis
More informationFire safety engineering applied to high-rise building facades
MATEC Web of Conferences 46, 04002 (2016) DOI: 10.1051/matecconf/20164604002 C Owned by the authors, published by EDP Sciences, 2016 Fire safety engineering applied to high-rise building facades Samuele
More informationREVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS
REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS Nikola TANASIĆ, Tomislav SIMONOVIĆ, Miloš IVOŠEVIĆ, Branislav
More informationApplication of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall. Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia
Application of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia A Challenging Application for the New Italian Fire Code
More informationThe Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *
Journal of Environmental Protection, 2013, 4, 638-646 http://dx.doi.org/10.4236/jep.2013.46073 Published Online June 2013 (http://www.scirp.org/journal/jep) The Research of Performance Comparison of Displacement
More informationUL268 7 th challenge with single infrared smoke detector
UL268 7 th challenge with single infrared smoke detector Hans Aebersold Siemens Schweiz AG, Building Technologies Division, Switzerland Abstract Coming up UL217 8th and UL268 7th edition with added new
More informationFull-Scale Measurement and Numerical Analysis of Liquefied Petroleum Gas Water Heaters with Ventilation Factors in Balcony
Journal of Civil Engineering and Architecture 9 (215) 1341-1353 doi: 1.17265/1934-7359/215.11.9 D DAVID PUBLISHING Full-Scale Measurement and Numerical Analysis of Liquefied Petroleum Gas Water Heaters
More informationLoss Prevention Standards
Introduction Fire compartmentation is an essential part of an effective fire safety design of a building. The primary objective of fire compartmentation or passive fire protection is to prevent a building
More informationSmoke Management in Subway Stations Due to Train Arson Fire Scenario
Smoke Management in Subway Stations Due to Train Arson Fire Yunlong Liu 1, Sean Cassady 1, Jerry Casey 1, Sanja Zlatanic 2 & Nasri Munfah 2 1. HNTB Corporation, 600 108 th Avenue NE STE 900, Bellevue,
More informationComputer Models For Fire and Smoke
Computer Models For Fire and Smoke Model Name: JASMINE Version: 3.1 Classification: Very Short Description: CFD or Field A CFD or field model for predicting consequences of fire to evaluate design issues
More informationSMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN
, Volume 4, Number 2, p.73-83, 2003 SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN K.H. Yang and C.S. Yang Mechanical Engineering Department, National Sun Yat-Sen
More informationComputer Simulation Investigation on the Effect of Channelled and Unchannelled Screens on Smoke Contamination in Atriums Upper Balconies
MATEC Web of Conferences 13, 27 (214) DOI: 1.151/ matecconf/ 21413 27 C Owned by the authors, published by EDP Sciences, 214 Computer Simulation Investigation on the Effect of Channelled and Unchannelled
More informationObjective based approach
Objective based approach Failure probabilities Introduction: fire safety objectives Example 1: personal safety Example 2: fire compartment 15-11-2017 1 Introduction RUUD VAN HERPEN Eindhoven University
More information