COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

Size: px
Start display at page:

Download "COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN"

Transcription

1 COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps

2 PRESENTATION OVERVIEW BUILDING DESCRIPTION STRUCTURAL DESIGN ALARM AND DETECTION EGRESS SPRINKLER SYSTEM ANALYSIS PERFORMANCE BASED ANALYSIS Photo credit to FrenchiesGigiandLola via youtube

3 BUILDING OVERVIEW Area: 122,000 sq.ft. Ceiling Height: 30 ft. Open floor plan Mixed Occupancy Construction Mercantile High Piled Storage Restaurant Kitchen, Bakery Office Concrete slab Exposed, noncombustible 3 PLAN NORTH TRUE NORTH Satellite Image courtesy of Google Maps Photo courtesy of Google Maps

4 A LOOK INSIDE Ventilation Steel deck Steel open web truss 4 Draft curtains Steel wide flange beam Rack storage Presented by Ian Levine Winter 2016 Wide flange steel column Concrete floor Wide aisles Photo courtesy of Google Maps Details shown typical of all Costco stores

5 STRUCTURAL DESIGN: What type of construction is allowed for this 122,000 sq.ft. structure? 5 Building Area: 122,000 sq.ft. Factor of increase based on frontage and automatic fire protection: 3.48 Maximum floor area per IBC 2012 Table 503: 35,000 sq.ft. Allowable construction type: I-A, I-B Presented by Ian Levine Winter 2016 California Building Code 2012 Photo courtesy of Google Maps

6 FIRE RESISTANCE RATINGS SUMMARY 6 IBC 2012 Tables 601 & 602; code & 716.5

7 WHAT IF?

8 DETECTION AND ALARM - OVERVIEW 7 Combination heat/ smoke detector Horn Strobe Notification Appliance Emergency Response Automatic fire sprinkler system Fire alarm control panel Backup power source Central monitoring station

9 ALARM AND DETECTION SYSTEM LAYOUT 8 PLAN NORTH TRUE NORTH

10 DETECTION RESPONSE ANALYSIS HEAT RELEASE RATES OF POTENTIAL FUEL LOADS 9 SOURCES: SFPE Handbook, 4 th ed; AIAA

11 HEAT DETECTOR RESPONSE DETACT Input Parameters 10 DETACT Results Response Time = 53s HRR = 1250 kw Note: Sprinkler response time = 95s Manual pull stations are required Is this layout cost effective?

12 NOTIFICATION 12 Required NA sound level: 40 db + 15 db = 55 db (15 dba above ambient) Requirement met using 99 dba alarm (6 dba Rule) Required strobe candela intensity per NFPA 72, Table (b) Note: EVACS is not recommended for this building

13 EGRESS CAPACITY 13 EGRESS CAPACITY > TOTAL OCCUPANT LOAD = OK!

14 EXIT PLAN 14 DEAD END: 98 ft PLAN NORTH Maximum travel distance: 225 ft (250 ft limit)

15 DECISION MAKING DURING EGRESS Recognition: Become aware of some danger. (smoke, alarm, seeing fire) 2. Validation: Gather more information (talk to others, look for smoke/fire) 3. Definition: Assess the threat, understand its seriousness 4. Evaluation: Decide how to respond (behaviors of others? Exit locations?) 5. Commitment: Take action 6. Reassessment: If necessary, take additional action. Stress levels rise. NFPA Fire Protection Handbook, ed. 20

16 EXPECTED EVACUATION TIME 16 Actual 1 story department store data

17 OCCUPANCY MAP 17

18 SYSTEM AREA MAP 18

19 SPRINKLER RESPONSE DETACT 11 TYCO ELO-231 Standard Spray Upright 11.2 k-factor ¾ orifice Response Time = 95s HRR = 4500 kw

20 PRESCRIPTIVE APPROACH SUMMARY STRUCTURAL: Fire resistance ratings requirements are satisfied Foams sprays, protective membranes, concrete wraps if additional protection is required A&D: Heat/Smoke detectors not required Manual pull stations o Occupancy > 500 Horn-strobes spaced to 68 ft o 6 db rule Heat detection by sprinklers o 53s vs. 95s response time EGRESS: Occupant load = 3,208 Egress capacity = 4,340 Total exit time = 4 min SPRINKLERS: 4 systems Extremely high demand Large orifice sprinklers System redesign to lower pressure and flow required from the source Pump with secondary water source if necessary

21 PERFORMANCE BASED DESIGN (PBD) Past vs. Future Specific to building, location, occupancy, and use NFPA 101 Life Safety Code (LSC) Goals and Objectives Prescriptive: o Protection of occupants not intimate with initial fire development o Improvement of survivability of occupants intimate with initial fire development o Added benefit to non-fire emergencies and crowd movement o Provide occupant protection during time to evacuate, relocate, or defend in place o Maintain structural integrity

22 PBD - OVERVIEW Meet prescriptive goals and objectives Limit exposure to instantaneous or cumulative untenable conditions (4 methods) Establish design specifications, inputs, assumptions, building safety features Determine design fire o o Realistic Challenging with respect to initial fire location, early rate of growth in fire severity, and/or smoke generation Design Fire Scenarios (8 Scenarios)

23 PBD FIRE SCENARIO Performance Criteria: Method 2, LSC o Complete building evacuation before hot gas layer extends less than 6 ft above floor (ASET > RSET?) Design Scenario: Scenario 2, LSC o Ultrafast-developing fire in the primary means of egress with interior doors open at the start of the fire o Focus on reduction in number of means of egress o Can all occupants escape before being exposed to smoke? Design Fire: electronics section in front of primary entrance and exit

24 PBD EGRESS: NFPA CALCULATION Increase by 100: confusion, searching for new exit Decrease to 0 due to inaccessibility Methodology and data from NFPA Handbook, 20 th edition

25 PBD EGRESS: PATHFINDER Calculation of movement time, not including premovement time 3208 occupants randomly spread throughout room Single doors: 36 Double doors: 72 Walls placed around tables, displays, and racks as obstructions All interior doors open OCCUPANTS FIRE BLOCKING EXIT t = 0s

26 PBD EGRESS: PATHFINDER Occupants moving toward doors Jams occurring at doors OCCUPANTS FIRE BLOCKING EXIT t = 30s

27 PBD EGRESS: PATHFINDER Most occupants have reached an escape route OCCUPANTS FIRE BLOCKING EXIT t = 60s

28 PBD EGRESS: PATHFINDER All occupants are experiencing jamming at doors Floor is completely cleared FIRE BLOCKING EXIT t = 120s

29 PBD EGRESS: PATHFINDER Very few occupants remain Maximum egress time: 191s t = 180s

30 PBD EGRESS: PATHFINDER RESULTS Occupants Occupants Inside Costco During Evacuation OBSERVATIONS Evacuation complete 3.2 min after begins Including 1.7 min maximum pre-movement time and 1.2 factor of safety, total time = 5.3 minutes Close agreement with NFPA method results (5.5 min) Note: linear evacuation rate supports egress time is limited by exit capacity of exits rather than travel time to exits Time (s)

31 PBD CFAST ENVIRONMENT & LAYOUT SINGLE-WIDE AND DOUBLE- WIDE EMERGENCY EXITS AROUND PERIMETER DETECTION DEVICES LOCATION OF FIRE MAIN ENTRY AND EXIT

32 DESIGN FIRE FIRE INPUT PARAMETERS P6 FIRE Full scale test 2 pallets of 12 boxed computer monitors 1m x 1m x 1m, side by side Soot and CO yields from polystyrene Ignition using kw line burner Modeled as t 2 fire reaching steady burning after 25s SFPE Handbook Table

33 PBD DETECTION AND ALARM 700 Heat Detector Temperatures in Design Fire - CFAST Temperature (⁰C) PEAK HRR REACHED STEADY STATE BURNING Hot Gas Heat Detector 1 Heat Detector 2 Heat Detector 3 Heat Detector HEAT DETECTOR ACTUATION = 5s Delay has negligible impact on 1.7 min pre-movement time Time (s)

34 DESIGN FIRE CFAST SIMULATION T = 0s T = 10s Initial temperature at 22 ⁰C Plume develops quickly Hot gas layer forms immediately

35 DESIGN FIRE CFAST SIMULATION T = 20s T = 30s Hot gas layer has reached ceiling Smoke already gathering at the ceiling Peak HRR is reached Temperature of hot gas layer rapidly increasing Interface height: 8.87m

36 DESIGN FIRE CFAST SIMULATION T = 60s T = 120s Temperature of hot gas layer continues to increase Interface height: 8.67m Smoke layer remains high Interface height: 8.3m Alarm and pre-movement time periods have passed. Occupants are now moving to exits. Some have exited already.

37 DESIGN FIRE CFAST SIMULATION T = 240s T = 300s Average lower layer temperature increasing (29 ⁰C) Interface height: 7.63m Interface height: 7.32m After 5 minutes, all occupants have reached an exit and are evacuating

38 DESIGN FIRE CFAST SIMULATION Hot Gas Layer Height and Layer Temperatures in Design Fire 1 - CFAST Simulation T = 330s Layer Height (m) Temperature (C) All occupants have exited building Final interface height: 7.18m Final lower layer temperature: 32.2 ⁰C Time (s) Layer Height Upper Layer Temperature Lower Layer Temperature

39 PERFORMANCE BASED DESIGN SUMMARY ASET > RSET: SUCCESS Extremely rapid heat and smoke production offset by massive volume of compartment Impact of smoke development unlikely to put occupants at risk Overall performance from life safety perspective: very good ASSUMPTIONS Sprinklers do not activate demonstrate safe egress is possible given worst case scenario Peak HRR maintained during steady burning period o Fuel source large enough to supply continuous burning for entire duration of building egress Occupants spread evenly to all available exits during egress o If gathering occurs near one exit with another exit available, occupants travel to available exit

40 CONCLUSION Prescriptive requirements for structural design, alarm and detection system, egress, and sprinkler system were considered. Structural, A&D, egress requirements were satisfied Recommendations made for sprinkler compliance (system redesign, pump, secondary water source) Performance-based analysis using Pathfinder egress modeling software and CFAST 7 with real-life (albeit, exaggerated) fire test data showed that the life safety criteria of ASET>RSET was satisfied with large margin, even with highly challenging design fire.

41 RECOMMENDATIONS Determine if pump is required for sprinkler system Examine impact of staff trained to help with egress Explore more complex modeling in Pathfinder: response times, seeking new exits, travel speeds Compare CFAST and FDS smoke height interface results Performance based design for protection of property and valuables FDS to model alternative suppression systems, examine cost impact

42 THANK YOU!

Will Clay Spring 2014

Will Clay Spring 2014 Will Clay Spring 2014 1. Project Overview 2. Prescriptive Requirements 3. Existing Requirements 4. Performance Evaluation 5. Conclusions RJA-Houston since 2010 Hired as FP/LS consultants by architect in

More information

By: Russell Bainbridge March 18th, 2016 FPE 596

By: Russell Bainbridge March 18th, 2016 FPE 596 By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse

More information

Construction Warehouse. FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson

Construction Warehouse. FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson Construction Warehouse FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson 1 Statement of Disclaimer This project report is a result of a class assignment;

More information

Fire Hazard Analysis of Technical Area 53 Building 1

Fire Hazard Analysis of Technical Area 53 Building 1 Fire Hazard Analysis of Technical Area 53 Building 1 June 11, 2015 LA-UR-15-23589 Slide 1 Introduction Brett Noakes Los Alamos National Laboratory Los Alamos, New Mexico Slide 2 Outline Background of the

More information

CULMINATING EXPERIENCE IN FIRE PROTECTION ENGINEERING ANALYSIS OF COSTCO, SAN FRANCISCO

CULMINATING EXPERIENCE IN FIRE PROTECTION ENGINEERING ANALYSIS OF COSTCO, SAN FRANCISCO CALIFORNIA POLYTECHNIC STATE UNIVERSITY, SAN LUIS OBISPO CULMINATING EXPERIENCE IN FIRE PROTECTION ENGINEERING ANALYSIS OF COSTCO, SAN FRANCISCO PREPARED BY: IAN LEVINE 380 4 TH AVE SAN FRANCISCO, CA 94118

More information

Culminating Project. Fire Protection and Life Safety Engineering Analysis. Cal Poly. Center for Science and Mathematics. Fire Protection Engineering

Culminating Project. Fire Protection and Life Safety Engineering Analysis. Cal Poly. Center for Science and Mathematics. Fire Protection Engineering Culminating Project Fire Protection and Life Safety Engineering Analysis Fire Protection Engineering California Polytechnic State University Center for Science and Mathematics Cal Poly San Luis Obispo,

More information

Construction Innovation Center Building 186

Construction Innovation Center Building 186 Construction Innovation Center Building 186 FPE 596 Professors Presented Culminating Experience in Fire Protection Engineering Christopher Pascual & Frederick W. Mowrer Christopher Torres Objective / Overview

More information

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE Human Factors - Egress Analysis for High Hazard Occupancies Presented by: Michael J. Klemenz, PE, SFPE Group H Other SFPE presenters today discussed issues relevant to Group H This presentation addresses

More information

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada

More information

Fire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett

Fire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett Fire Protection System and Life Safety Evaluation of Building X Presented by Anthony W. Sublett Culminating Project Master of Science in Fire Protection Engineering California Polytechnic State University

More information

Prescriptive and Performance Analysis of Cold Machine Shop FPE 596 Culminating Project

Prescriptive and Performance Analysis of Cold Machine Shop FPE 596 Culminating Project Prescriptive and Performance Analysis of Cold Machine Shop FPE 596 Culminating Project John Kline 8/8/2018 Statement of Disclaimer This project report is a result of a class assignment; it has been graded

More information

Tunnel Fire Dynamics and Evacuation Simulations

Tunnel Fire Dynamics and Evacuation Simulations Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation

More information

Statue of Liberty: A Risk Analysis

Statue of Liberty: A Risk Analysis Statue of Liberty: A Risk Analysis Bruce Campbell, FSFPE VP DOE Services National Park Service Agenda Overview of Project Scope Evaluation Steps Task 1 Code Analysis Task 2 Fire Modeling Task 3 Egress

More information

FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING. Fabio Mazza June 2016

FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING. Fabio Mazza June 2016 FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING Fabio Mazza June 2016 Introduction Codes & Standards Building description Performance based design Prescriptive based design Structural

More information

Case Study 1 Underground Car Park

Case Study 1 Underground Car Park Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building

More information

Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel

Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Virtual : An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Xiaolei Chen, PhD California State University, Los Angeles, United States Ning (Frank) Wang, P.E. Jensen Hughes,

More information

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Fire Science and Technorogy Vol.24 No.4(2005) 165-178 165 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Jun-ichi Yamaguchi 1, Takeyoshi Tanaka 2 1 Technical Research

More information

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c Table 1015.1 EXIT ACCESS TRAVEL DISTANCE a WITHOUT SPRINKLER WITH SPRINKLER OCCUPANCY SYSTEM SYSTEM A, E, F-1, I-1, M, 200 250 b,d R, S-1 B 200 300 c F-2, S-2, U 300 400 c No Change to Other Entries in

More information

Fire Protection System and Life Safety Evaluation. Building X. Anthony W. Sublett. Culminating Project

Fire Protection System and Life Safety Evaluation. Building X. Anthony W. Sublett. Culminating Project Fire Protection System and Life Safety Evaluation Of Building X By Anthony W. Sublett Culminating Project Presented to the Faculty of the Graduate School of California Polytechnic State University in Partial

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN , Volume 4, Number 2, p.73-83, 2003 SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN K.H. Yang and C.S. Yang Mechanical Engineering Department, National Sun Yat-Sen

More information

Considerations in the Design of Smoke Management Systems for Atriums

Considerations in the Design of Smoke Management Systems for Atriums Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke

More information

Today's Topics & Sustainability Themes

Today's Topics & Sustainability Themes 2012 Chicago Symposium Fire Safety Design and Sustainable Buildings: Challenges and Opportunities Research Efforts in Fire Protection Engineering are Contributing to Sustainability Goals Dan O Connor,

More information

Performance Based Design: Fire Alarm Visual Notification Appliances - Mathematical Guide. Ernesto Vega Jánica, EE, MSc, MEng

Performance Based Design: Fire Alarm Visual Notification Appliances - Mathematical Guide. Ernesto Vega Jánica, EE, MSc, MEng Performance Based Design: Fire Alarm Visual Notification Appliances - Mathematical Guide Ernesto Vega Jánica, EE, MSc, MEng 1 Performance Based Design Introduction Change on Philosophy 1999-2002-2007-2010-2013

More information

EVACUATION MODELING DEPENDENCE ON INPUT PARAMETERS

EVACUATION MODELING DEPENDENCE ON INPUT PARAMETERS PROCEEDINGS, Fire and Evacuation Modeling Technical Conference 211 Baltimore, Maryland, August 15-16, 211 EVACUATION MODELING DEPENDENCE ON INPUT PARAMETERS Brian Salyers, Bevan Jones Holmes Fire 13 Sutter

More information

El Reno Fire Department Fire Alarm Plan Review Worksheet

El Reno Fire Department Fire Alarm Plan Review Worksheet El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us

More information

Potential Impact of New UL Fire Test Criteria

Potential Impact of New UL Fire Test Criteria Potential Impact of New UL Fire Test Criteria Thomas G. Cleary Fire Research Division National Institute of Standards and Technology March 7, 2014 Outline Background Recent History Task Group Progress

More information

Fire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of the Florida Building Code

Fire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of the Florida Building Code Walker Engineering, Inc. 833 Rockingham Road Birmingham Alabama 35235-2625 205-854-0160 205-854-0160 (Fax) Fire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of

More information

Case Study of Underground Car Park. Team Japan

Case Study of Underground Car Park. Team Japan 11th Conference on Performance Based Codes and Fire Safety Design Methods Case Study of Underground Car Park Team Japan We focused on the characteristics of the fire behavior of car fire. Car fire is not

More information

Challenges of Fire Protection Upgrades in Existing Libraries. Campus Fire Safety Forum

Challenges of Fire Protection Upgrades in Existing Libraries. Campus Fire Safety Forum Challenges of Fire Protection Upgrades in Existing Libraries Campus Fire Safety Forum November 6, 2013 Presentation Overview Code Requirements Goals of Fire Protection Systems Life Safety Property Protection

More information

ROBERT E. KENNEDY LIBRARY CAL POLY, SAN LUIS OBISPO FIRE PROTECTION ANALYSIS FPE CULMINATING PROJECT. Prepared For:

ROBERT E. KENNEDY LIBRARY CAL POLY, SAN LUIS OBISPO FIRE PROTECTION ANALYSIS FPE CULMINATING PROJECT. Prepared For: ROBERT E. KENNEDY LIBRARY Page i ROBERT E. KENNEDY LIBRARY CAL POLY, SAN LUIS OBISPO Prepared For: Dr. Frederick W. Mowrer & Dr. Christopher Pascual California Polytechnic State University College of Engineering

More information

Fire and Life Safety Analysis

Fire and Life Safety Analysis Fire and Life Safety Analysis Grant M. Brown Engineering Building #41 California Polytechnic State University, San Luis Obispo Daniel Gregory Blanchat June 12 th, 2014 1 B l a n c h a t 1 Statement of

More information

ISO/TR TECHNICAL REPORT. Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people

ISO/TR TECHNICAL REPORT. Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people TECHNICAL REPORT ISO/TR 16738 First edition 2009-08-01 Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people Ingénierie de la sécurité incendie Informations

More information

ENFP 102: Engineering and Testing Creative Fire Safe Building Designs

ENFP 102: Engineering and Testing Creative Fire Safe Building Designs ENFP 102: Engineering and Testing Creative Fire Safe Building Designs Instructors: Jim Milke, Ph.D., P.E., milke@umd.edu, Room 3104B JMP, 301-405-3995 Ken Isman, P.E., kisman@umd.edu, Room 3104L JMP, 301-405-

More information

American Fire Sprinkler Association. An Introduction to the IBC and IFC

American Fire Sprinkler Association. An Introduction to the IBC and IFC American Fire Sprinkler Association Presents An Introduction to the IBC and IFC October 13, 2005 Speaker Roland Huggins, P.E. Vice President of Engineering and Technical Services American Fire Sprinkler

More information

Prepared for: Professor Frederick W. Mowrer, PhD, P.E. Professor Christopher Pascual, PhD, P.E

Prepared for: Professor Frederick W. Mowrer, PhD, P.E. Professor Christopher Pascual, PhD, P.E Fire and Life Safety Analysis of The Production Facility (PF) - 870 Sandia National Laboratories, Albuquerque, New Mexico USA November 3, 2017 FPE596 Culminating Final Project Report By Nolan J. Baker,

More information

Case Study 2 Production and Storage. SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB)

Case Study 2 Production and Storage. SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB) Case Study 2 Production and Storage SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB) So What Are You We Going to Show You? A lot of tables, simplified methods

More information

Figure 1. Structure Used For the Simulations.

Figure 1. Structure Used For the Simulations. OVERVIEW: Vent, Enter, Search (VES) is one of the most talked about tactics in the fire service today. When used correctly, its positive impact can be measured by the lives it saves. The VES method is

More information

F I R E A L A R M R E C O G N I T I O N A N D E X I T C H O I C E I N U N D E R G R O U N D S TAT I O N S

F I R E A L A R M R E C O G N I T I O N A N D E X I T C H O I C E I N U N D E R G R O U N D S TAT I O N S F I R E A L A R M R E C O G N I T I O N A N D E X I T C H O I C E I N U N D E R G R O U N D S TAT I O N S 19 th January 2016 P R E S E N TAT I O N O V E R V I E W 1. Introduce fire alarm and its importance

More information

Smoke Alarm Research at NIST

Smoke Alarm Research at NIST Smoke Alarm Research at NIST Thomas G. Cleary Fire Research Division National Institute of Standards and Technology Smoke Alarm Summit March 31, 2015 Outline Supporting ANSI/UL 217 268 Task Group on adding

More information

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design June 15, 2017 Building Description Applicable Codes & Standards Prescriptive Requirements Structural Fire Protection Fire Sprinkler Fire Alarm Means of Egress Performance Based Design 2 3 Semiconductor

More information

Life Safety Report. XYZ Office Building. Denver Colorado. Prepared by: Keith Dix Monday, June 3, 2013

Life Safety Report. XYZ Office Building. Denver Colorado. Prepared by: Keith Dix Monday, June 3, 2013 Life Safety Report XYZ Office Building Denver Colorado Figure 1 - XYZ Building West Side Prepared by: Keith Dix Monday, June 3, 2013 Culminating Project FPE 596 California Polytechnic University, San Luis

More information

A New Zealand Case Study Building Design 11 th International Conference on Performance

A New Zealand Case Study Building Design 11 th International Conference on Performance A New Zealand Case Study Building Design 11 th International Conference on Performance Prof Charles Fleischmann University of Canterbury Dept. Civil and Nat Res Eng. Christchurch, New Zealand Carol Caldwell

More information

and Sprinkler System in Resalat Tunnel of Tehran

and Sprinkler System in Resalat Tunnel of Tehran CFD Simulation of Water Mist and Sprinkler System in Resalat Tunnel of Tehran Motivation Resalat tunnel is the first road tunnel in Tehran one of most crowded tunnels of Tehran my every day route, home

More information

Fire Protection Engineering Culminating Project. Analysis of the Seattle Customer Delivery Center. Prepared by Cynthia Wernet

Fire Protection Engineering Culminating Project. Analysis of the Seattle Customer Delivery Center. Prepared by Cynthia Wernet Fire Protection Engineering Culminating Project Analysis of the Seattle Customer Delivery Center Prepared by Cynthia Wernet California Polytechnic State University at San Luis Obispo June 9, 2016 Cynthia

More information

Smoke Layer Height and Heat Flow through a Door

Smoke Layer Height and Heat Flow through a Door Smoke Layer Height and Heat Flow through a Door 2018 Smoke Layer Height and Heat Flow through a Door In this tutorial you will simulate a growing fire in the corner of a 5m x 5m room. The room has a 1m

More information

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

ZONE MODEL VERIFICATION BY ELECTRIC HEATER , Volume 6, Number 4, p.284-290, 2004 ZONE MODEL VERIFICATION BY ELECTRIC HEATER Y.T. Chan Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Selecting

More information

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea 5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea PRACTICAL APPLICATIONS OF FIRE MODELING IN INDUSTRIAL APPLICATIONS By James M. Dewey, Advisor Risk Management

More information

Fire Protection Analysis DCI Data Center Building

Fire Protection Analysis DCI Data Center Building Fire Protection Analysis DCI Data Center Building California Polytechnic State University FPE 596 Culminating Experience in Fire Protection Engineering Bryan Hathaway M.S. Fire Protection Engineering -

More information

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION - 165 - CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT

More information

A case study for integrated modelling of personnel evacuation with pool fire simulation to increase safety in design for offshore oil and gas projects

A case study for integrated modelling of personnel evacuation with pool fire simulation to increase safety in design for offshore oil and gas projects A case study for integrated modelling of personnel evacuation with pool fire simulation to increase safety Davood Afshari 1 Richard Welsh 2 Maryam Moghaddas 3 Sara Afsharikia 1 Amir Tavakoli 4 1 Lead Technical

More information

Releasing Systems. Rob Mennie Senior Consultant Gage-Babcock & Associates Ltd.

Releasing Systems. Rob Mennie Senior Consultant Gage-Babcock & Associates Ltd. Releasing Systems Rob Mennie Senior Consultant Gage-Babcock & Associates Ltd. Releasing Systems What is a releasing system? System designed to detect a fire Causes release of an extinguishing system in

More information

A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK. James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA

A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK. James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA Presentation Objective Compare fire alarm system design methods

More information

FIRE AND LIFE SAFETY ANALYSIS

FIRE AND LIFE SAFETY ANALYSIS FIRE AND LIFE SAFETY ANALYSIS AF Child Development Center Standard Design Judy Biddle Acknowledgements Special thanks for support and guidance over that past 2.5 years to: Professor Fred Mowrer Professor

More information

Fire Protection as the Underpinning of Good Process Safety Programs

Fire Protection as the Underpinning of Good Process Safety Programs Fire Protection as the Underpinning of Good Process Safety Programs Key Words: fires; protection, fire; building Background James Milke, Ph.D., P.E., Professor and Chair Department of Fire Protection Engineering

More information

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS Prepared for Smoke Safety Council 6775 SW 111 th Avenue, Suite 10 Beaverton, OR 97008 Prepared by Jesse J. Beitel Alison J. Wakelin Craig L.

More information

Fire Protection Engineering

Fire Protection Engineering Fire Protection Engineering FPE-596-FINAL REPORT NAME: MICHAEL STEWART DATE: JUNE 6, 2014 Contents Statement of Disclaimer... 5 Acknowledgement... 6 Building Overview & Description... 6 Building Construction

More information

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES 1 WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES TABLE 2.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF (1) ASSEMBLIES (Applies to each fire zone)

More information

DEALING WITH FIRE SAFETY

DEALING WITH FIRE SAFETY DEALING WITH FIRE SAFETY Personal Care Homes And Assisted Living Facilities Presented by: Harold D. Hicks, P.E., FSFPE Fire Protection Engineer 1 Atlantic Code Consultants 2 Our Objectives Recognize the

More information

Building Fire Safety in New York City s Existing Office Buildings

Building Fire Safety in New York City s Existing Office Buildings www.goldmancopeland.com Building Fire Safety in New York City s Existing Office Buildings Daniel Colombini, PE, LEED AP Principal, Director of Plumbing/Fire Protection Director of Plumbing and Fire Protection

More information

12F052 ADVANCED FLORIDA (MULTIPLE OCCUPANCY BUILDINGS)

12F052 ADVANCED FLORIDA (MULTIPLE OCCUPANCY BUILDINGS) 11I058 ALLOWABLE HEEIGHTS AND AREAS IN THE INTERNATIONAL BUILDING CODE 12F052 ADVANCED FLORIDA BUILDING CODE (MULTIPLE OCCUPANCY BUILDINGS) www.codeaccess.net 2 AIA HSW LUH S AIA COURSE NUMBER 12F052 FLORIDA

More information

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Y Liu, J Munro Parsons Brinckerhoff Australia B Dandie Thiess Pty Ltd., Australia ABSTRACT Emergency smoke ventilation

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

Natural Ventilation A Green Smoke Control Approach

Natural Ventilation A Green Smoke Control Approach Natural Ventilation A Green Smoke Control Approach Presented By: William Koffel, P.E., FSFPE Adam Graybeal, P.E. Authored by: Erik Anderson, P.E Koffel Associates Background New Engineering, Aviation,

More information

Date: Place: Technical University of Denmark. Knowledge FOr Resilient society

Date: Place: Technical University of Denmark. Knowledge FOr Resilient society Date: 27-06-2017 Place: Technical University of Denmark Knowledge FOr Resilient society 11B25 Smoke and temperature ACTION 11B04 11B12 fire development 11B01 Evacuation human behaviour building response

More information

PROPOSAL BALLOT DUE BY: Thursday, September 18, 2008

PROPOSAL BALLOT DUE BY: Thursday, September 18, 2008 PROPOSAL BALLOT DUE BY: Thursday, September 18, 2008 NFPA 204 SMO-AAA Standard for Smoke and Heat Venting Staff Liaison: Return Completed Ballot To: Jill McGovern E-Mail to jmcgovern@nfpa.org Fax to 617-984-7110

More information

Case Study 1 Underground car park

Case Study 1 Underground car park Case Study 1 Underground car park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, INBEPO Wroclaw, Poland 1. Introduction

More information

WORKSHEET 3-1 THE MANITOBA OFFICE OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

WORKSHEET 3-1 THE MANITOBA OFFICE OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES 1 WORKSHEET 3-1 THE MANITOBA OFFICE OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES TABLE 3.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF (1) ASSEMBLIES (Applies each fire zone) Building

More information

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015

More information

Fire Safety Strategies for Penthouse Designs

Fire Safety Strategies for Penthouse Designs ctbuh.org/papers Title: Authors: Subject: Keywords: Fire Safety Strategies for Penthouse Designs Hadrien Fruton, Fire Engineer, Hoare Lea Karl Wallasch, Associate, Hoare Lea Fire & Safety Fire Safety Residential

More information

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems FEMA Recommendations are based upon Live Fire Testing of Prep Stations

More information

High challenge warehouse case study Summary

High challenge warehouse case study Summary High challenge warehouse case study Summary February 19, 2010 Richard Gallagher Michael Gollner Zurich Services Corporation Objectives Review the results of the high challenge warehouse workshop Recognize

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls Journal of Mechanics Engineering and Automation 5 (2015) 465-471 doi: 10.17265/2159-5275/2015.08.007 D DAVID PUBLISHING Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

More information

2015 SFPE Europe Conference on Fire Safety Engineering

2015 SFPE Europe Conference on Fire Safety Engineering 2015 SFPE Europe Conference on Fire Safety Engineering THE FSE APPROACH FOR A HISTORICAL BUILDING IN LIGHT OF THE ITALIAN STANDARDS. Simonetto Sacco Luciano Nigro HUGHES ASSOCIATES EUROPE, srl FIRE SCIENCE

More information

F.R.A.M.E. EVENT NETWORKS used in "FRAME".

F.R.A.M.E. EVENT NETWORKS used in FRAME. EVENT NETWORKS used in "FRAME". In 2004, Dipl. Ing. Trond Maag wrote his doctorates' thesis "Risikobasierte Beurteilung der Personensicherheit von Wohnbauten im Brandfall unter Verwendung von Bayes'schen

More information

January 1, 2014 Mandatory Effective Date

January 1, 2014 Mandatory Effective Date 2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective

More information

Anatomy of a Fire. Christopher Crivello, MSFPE, PE. Douglas Nadeau, MSFPE, PE, CFPS, LEED AP

Anatomy of a Fire. Christopher Crivello, MSFPE, PE. Douglas Nadeau, MSFPE, PE, CFPS, LEED AP Anatomy of a Fire Douglas Nadeau, MSFPE, PE, CFPS, LEED AP President of RAN Fire Protection Engineering, PC Vice President of truvue Inspection Technology Christopher Crivello, MSFPE, PE Fire Protection

More information

FM Approval Standard For Cavity Walls And Rainscreens

FM Approval Standard For Cavity Walls And Rainscreens FM4411 - Approval Standard For Cavity Walls And Rainscreens Mark D. Tyrol, P.E. FM Approvals Air Barrier Association of America (ABAA) is a Registered Provider with The American Institute of Architects

More information

Third Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG

Third Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG 1 Third Runway Project APM Depot Fire Engineering Design Presented by Ir Wilson Sau-kit TSANG 1 2 Presentation Overview 1. Project Background and Depot Overview 2. Building Information and Challenge for

More information

Explosion Protection Engineering Principles

Explosion Protection Engineering Principles Handbook of Fire and Explosion Protection Engineering Principles for Oil, Gas, Chemical and Related Facilities Second edition Dennis P. Nolan ELSEVIER AMSTERDAM BOSTON HEIDELBERG LONDON NEW YORK OXFORD

More information

Research Needs for the Fire Safety Engineering Profession

Research Needs for the Fire Safety Engineering Profession Research Needs for the Fire Safety Engineering Profession Note: Items highlighted in RED are identified as the highest priority for each thread. Items highlighted in BOLD are identified as the highest

More information

Practicalities and Limitations of Coupling FDS with Evacuation Software

Practicalities and Limitations of Coupling FDS with Evacuation Software ABSTRACT Practicalities and Limitations of Coupling FDS with Evacuation Software Daniel Rådemar, WSP, Sweden Daniel Blixt, WSP, Sweden Brecht Debrouwere, WSP, Sweden Björn Grybäck Melin, WSP, Sweden Andrew

More information

Selecting appropriate egress strategies

Selecting appropriate egress strategies Selecting appropriate egress strategies The selection of an appropriate egress strategy requires a good understing of the building its occupants, the protection measures in place, the expected emergency

More information

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,

More information

Richard B. Alpert, P.E. Senior FPE, Clark Nexsen

Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Clark Nexsen is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of

More information

CALIFORNIA POLYTECHNIC SLO

CALIFORNIA POLYTECHNIC SLO CALIFORNIA POLYTECHNIC SLO FIRE PROTECTION ENGINEERING PROGRAM CULMINATING PROJECT SUMMER 2014 ROCK TOLER Statement of Disclaimer This project report is a result of a class assignment; it has been graded

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

The Physical Environment Portal: Module 5, LS Leadership

The Physical Environment Portal: Module 5, LS Leadership The Physical Environment Portal: Module 5, LS.02.01.10 - Leadership Fire Safety: Background Fire safety impacts both the lives of the occupants and the physical structures. In the early 1900 s many buildings

More information

Applying the New Zealand Performance Based Design Fire Framework to Buildings Designed in Accordance with NFPA5000

Applying the New Zealand Performance Based Design Fire Framework to Buildings Designed in Accordance with NFPA5000 Applying the New Zealand Performance Based Design Fire Framework to Buildings Designed in Accordance with NFPA5000 Submitted by Chin Hung (Marco) Yip Supervised by Assoc. Professor Charles Fleischmann,

More information

CLOUD CEILINGS: FIRE DYNAMICS AND CODE CONTEXT

CLOUD CEILINGS: FIRE DYNAMICS AND CODE CONTEXT Peterson Guadagnolo Consulting Engineers PC CLOUD CEILINGS: FIRE DYNAMICS AND CODE CONTEXT 1 November 7, 2016 AGENDA Introduction New York State Code - Update Ceiling Types Fire Dynamics Compartment Fire

More information

3.1 Introduction. 3.1 Introduction

3.1 Introduction. 3.1 Introduction DEPARTMENT OF ARCHITECTURE ABUBAKAR TAFAWA BALEWA UNIVERSITY, BAUCHI ARC 624: ADVANCED BUILDING SERVICES LESSON 3: FIRE DETECTION AND ALARM SYSTEMS IN BUILDINGS 3.1 Introduction 3.1 Introduction 3.2 Conventional

More information

Mass Notification and Intelligent Response TM The European Way

Mass Notification and Intelligent Response TM The European Way Mass Notification and Intelligent Response TM The European Way Infrastructure & Cities, Building Technologies, Innovation & Industry Affairs Peter J. Loeffler Siemens Switzerland Ltd. 2013. All rights

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary SECTION 910 SMOKE AND HEAT VENTS 910.1 General. Where required by this code or otherwise installed, smoke and heat vents or mechanical smoke exhaust systems and draft curtains shall conform to the requirements

More information

SUMMARY. Building receiving sprinkler credit: SPRINKLERED. Grade: 68. Percent of Building Sprinklered: 100% Sprinkler Demand Met: 91%

SUMMARY. Building receiving sprinkler credit: SPRINKLERED. Grade: 68. Percent of Building Sprinklered: 100% Sprinkler Demand Met: 91% 210 N CHURCH ST CHARLOTTE NC 28202-2256 MECKLENBURG COUNTY RISK ID: 32 NC99 040235 ON-SITE SURVEY: 4/1/2009 LAST UPDATE: 4/1/2009 SUMMARY Building receiving sprinkler credit: SPRINKLERED Grade: 68 Percent

More information

Significant Advancements in Water Based Fire Suppression for Storage Occupancies

Significant Advancements in Water Based Fire Suppression for Storage Occupancies Significant Advancements in Water Based Fire Suppression for Storage Occupancies Presented by: James Golinveaux Sr. Fellow Tyco Fire Protection Products Higher Faster - Further How high can we go? Ceiling

More information

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT LOCAL AMENDMENTS INTERNATIONAL FIRE CODE 2009 December 5, 2012 1 Chapter 1 Administration Chapter 5 Fire Service Features Chapter 9 Fire Protection Systems Chapter

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT 171-181, Baizid Bostami Road Nasirabad I/A, Chittagong Chittagong The Alliance for Bangladesh Worker Safety Page 1/14 Introduction to the Report The following

More information

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015?

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015? Plumis White Paper April 2017 How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015? As with the introduction of every new formal product category through

More information