Culminating Project. Fire Protection and Life Safety Engineering Analysis. Cal Poly. Center for Science and Mathematics. Fire Protection Engineering

Size: px
Start display at page:

Download "Culminating Project. Fire Protection and Life Safety Engineering Analysis. Cal Poly. Center for Science and Mathematics. Fire Protection Engineering"

Transcription

1 Culminating Project Fire Protection and Life Safety Engineering Analysis Fire Protection Engineering California Polytechnic State University Center for Science and Mathematics Cal Poly San Luis Obispo, CA Orelvis Gonzalez March 20 th, 2015

2 Presentation Outline Building Characteristics and Regulatory Framework Prescriptive-based Structural Fire Protection Flammability Assessment. Means of Egress Fire Alarm and Detection Systems Fire Suppression Systems Performance-based Egress Analysis and Tenability Conditions Assessment RSET vs ASET Analysis Conclusions and Recommendations

3 Building Characteristics Project Name Location Const. Type Total Floor Area Actual Height Center for Science and Mathematics (CSM) California Polytechnic State University, San Luis Obispo, CA 1B, Fire-Resistive 188,372 G.S.F. 108 ft. Defined Height Building Occupancy 64 ft. Non High-rise building Group B, Business Occupancy High-Rise Building: Having floor used for human occupancy located more than 75 feet above the lowest floor level having building access

4 Building Characteristics

5 Building Characteristics Fire Department access provided within 150 feet of all portions of the building. (IFC, 2007, Section ) South facing side require approval from the fire code official.

6 Regulatory Framework Main Applicable Codes California Building Code (CBC), 2007 Ed. California Plumbing Code (CPC), 2007 Ed. California Mechanical Code (CPC), 2007 Ed. National Electric Code (NFPA 70), 2005 Ed. Life Safety Code (NFPA 101), 2006 Ed. California Fire Code (CFC), 2007 Ed. National Fire Alarm Code (NFPA 72), 2007 Ed. NFPA 13, Standard for the Inst. of Sprinkler Systems, 2007 Ed.

7 Prescriptive Structural Fire Protection CONSTRUCTION TYPE 1B, Fire-Resistive The building elements are not combustible material (IBC, 2007, Section 602). FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (CBC, 2007 Table 601) Building Element FIRE-RESISTANCE RATING (Hours) Primary Structural Frame 2 * Bearing Walls (Exterior) 2 Bearing Walls (Interior) 2 * No Bearing Walls (Interior) 0 Floor Construction and Associated Secondary Members 2 Roof Construction and Associated Secondary Members 1 * 1-hour permitted where supporting a roof only

8 Prescriptive Structural Fire Protection CONSTRUCTION TYPE 1B, Fire-Resistive The building elements are not combustible material (IBC, 2007, Section 602). FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (CBC, 2007 Table 601) Building Element FIRE-RESISTANCE RATING (Hours) Primary Structural Frame 2 * Bearing Walls (Exterior) 2 Bearing Walls (Interior) 2 * No Bearing Walls (Interior) 0 Floor Construction and Associated Secondary Members 2 Roof Construction and Associated Secondary Members 1 * 1-hour permitted where supporting a roof only

9 Prescriptive Structural Fire Protection Six-level (5 stories) central structure devoted to offices and student spaces with wings on either side that house classrooms and laboratories I (or W) shapes fire proofed with SFRM Girders and beams Columns Reinforced C. walls in levels 1 and 2

10 Prescriptive Structural Fire Protection BUILDING OCCUPANCY Uses and Occupancies Group B, Business Occupancy An occupancy used for the transaction of business other than mercantile (NFPA , Section ) Lobbies/Lecture - Occupant Load >50: (A-3) Office: (B) Conference Rooms - Less than 50 occupants: (B) Laboratories: (B) Electrical and Telephone Data: (S-2) Mechanical Rooms: (S-1) Storage: (H-3 and S-2)

11 Prescriptive Structural Fire Protection REQUIRED SEPARATION FOR OCCUPANCIES (CBC, 2007 Table ) OCCUPANCY FIRE-RESISTANCE RATING (Hours) B A 1 B H-3 1 B S-1 N B S-2 1 S-1 H-3 1 S-1 S-2 1 N: No separation requirement

12 Prescriptive Structural Fire Protection REQUIRED SEPARATION FOR OCCUPANCIES (CBC, 2007 Table ) OCCUPANCY FIRE-RESISTANCE RATING (Hours) B A 1 B H-3 1 B S-1 N B S-2 1 S-1 H-3 1 S-1 S-2 1 CBC Exception 3: A Fire Barrier is not required between the atrium and the adjoining spaces of any three floors of the atrium provided such spaces are accounted for in the design of the smoke control system.

13 Prescriptive Flammability Assessment Max. Flame Spread Classification (Class) Interior Finishes : (CBC, 2007 Table 803.5) Group Exit enclosures and exit passageways (Sprinklered) Corridors (Sprinklered) Rooms and enclosed spaces (Sprinklered) A-3 B B C B B C C S-1 C C C S-2 C C C Class B: Flame Spread index 26-75, smoke developed index Class C: Flame Spread index , smoke developed index 0-450

14 Prescriptive Mean of Egress At least 3 exits required (NFPA 101, 2006 Section ) Occupant Load more than 500 but no more than 1000 At least 2 exits required (NFPA 101, 2006 Section ) Occupant Load less than 500. No less than two separate exits shall be provided on every story.

15 Prescriptive Mean of Egress Travel distance shall not exceed 300 ft. (NFPA 101, 2006, Section )

16 Prescriptive Mean of Egress Structural Fire Prot. Level 1 15 ft 2 /person 300 ft 2 /person 15 ft 2 /person TD = 149 OCCUPANT LOAD: 703 EXITS DOORS EXITS STAIRS CORRIDORS ELEVATORS/LOBBIES BUSINESS ASSEMBLY STORAGE HAZARD TRAVEL DISTANCE At least 3 exits required: Occupant Load more than 500 but no more than 1000 Travel distance must not exceed 300 ft. Business

17 Prescriptive Mean of Egress Structural Fire Prot. Level 2 OCCUPANT LOAD: 523 TD = 184 EXITS DOORS EXITS STAIRS CORRIDORS ELEVATORS/LOBBIES BUSINESS ASSEMBLY STORAGE HAZARD TRAVEL DISTANCE At least 3 exits required: Occupant Load more than 500 but no more than 1000 Travel distance must not exceed 300 ft. Business

18 Prescriptive Mean of Egress Structural Fire Prot. Level 3 OCCUPANT LOAD: 701 TD = 185 EXITS DOORS EXITS STAIRS CORRIDORS ELEVATORS/LOBBIES BUSINESS ASSEMBLY STORAGE HAZARD TRAVEL DISTANCE At least 3 exits required: Occupant Load more than 500 but no more than 1000 Travel distance shall not exceed 300 ft. Business

19 Prescriptive Mean of Egress Structural Fire Prot. Level 4 OCCUPANT LOAD: 463 EXITS DOORS EXITS STAIRS CORRIDORS ELEVATORS/LOBBIES BUSINESS ASSEMBLY STORAGE HAZARD TRAVEL DISTANCE TD = 185 At least 2 exits required Occupant Load less than 500. Travel distance shall not exceed 300 ft. Business

20 Prescriptive Mean of Egress Structural Fire Prot. Level 5 OCCUPANT LOAD: 263 TD = 152 EXITS DOORS EXITS STAIRS CORRIDORS ELEVATORS/LOBBIES BUSINESS ASSEMBLY STORAGE HAZARD TRAVEL DISTANCE At least 2 exits required Occupant Load less than 500. Travel distance shall not exceed 300 ft. Business

21 Prescriptive Mean of Egress Structural Fire Prot. Level 6 OCCUPANT LOAD: 252 TD = 152 EXITS DOORS EXITS STAIRS CORRIDORS ELEVATORS/LOBBIES BUSINESS ASSEMBLY STORAGE HAZARD TRAVEL DISTANCE At least 2 exits required Occupant Load less than 500. Travel distance shall not exceed 300 ft. Business

22 Prescriptive Mean of Egress - Summary Summary: Number of Exits Level Occupant Load Number of Exits (Required by Codes) Number of Exits (Existing in CSM) Compliance Status

23 Prescriptive Mean of Egress - Summary

24 Prescriptive Fire Detection and Alarm Systems The building is a PROTECTED PREMISE. Signals sent to the University Police Department's Communications Center which is staffed 24 hours a day, 7 days (supervising station). Fire alarm system: Proprietary supervising station alarm system. Emergency communication system : One-way Fire Emergency Voice/Alarm Communications (EVACS). Two-way Emergency communication System (Telephone System).

25 Prescriptive Fire Detection and Alarm Systems System Type : Class B, Addressable and Manual Detection Performance of Notification Appliance Circuits (NACs). Performance Signaling Line Circuits (SLCs). Alm: Alarm. Trbl: Trouble. ARC: Alarm receipt capability during abnormal conditions. R: Required capabilities. X: Indication required at protected premises

26 Prescriptive Fire Detection and Alarm Systems FACU location in Room 122. Honeywell Notifier

27 Prescriptive Fire Detection and Alarm Systems The building IS NOT classified as a high-rise building and it is equipped throughout with an automatic sprinkler system: Requirements: Partial or Selective Coverage. Code (NFPA ) A fire alarm system for occupancies with an atrium connecting more than two stories (CBC ) A fire-fighter's smoke control panel (CBC ) An two-way FD communication system (CBC ) Detectors : Detectors for Elevator Recall for Fire Fighters Service (NFPA ) Detectors for Door Releasing Service (NFPA ). Detectors for Automatic Shutoffs of Air-Moving systems (CMC )

28 Prescriptive Fire Detection and Alarm Systems Automatic and manual detection devices Automatic smoke detectors: Spot type smoke detectors. Duct smoke detector. Beam smoke detectors Automatic supervisory signal devices: Sprinkler water flow device. Pump activation. Supervisory signal devices : Control valve tamper switch /Smoke Fire Damper position indicator. Manual devices: Manual fire alarm boxes (pull station).

29 Prescriptive Fire Detection and Alarm Systems Automatic and manual detection devices

30 Prescriptive Fire Detection and Alarm Systems Audible and visible notifications appliances Strobes. Speakers. Speaker/Strobe combination. Bells Annunciators

31 Prescriptive Fire Detection and Alarm Systems Audible and visible notifications appliances

32 Prescriptive Fire Detection and Alarm Systems OPERATION MATRIX

33 Prescriptive System Type: Fire Suppression System Wet Pipe System Design Criteria: Density/area method and the occupancy classification Light Hazard (Lobbies, Lecture, Office, and Conference Rooms) Ordinary Hazard Group 1 (Labs, Mechanical, Storage and Elect. Rooms) Water Supply: Fire Pump: Piping: Public Water Main 1 fire pump rated 750 gpm w/electric motor Black steel sch. 10 and sch. 40 Sprinklers installed in accordance with NFPA 13, 2007 (CBC )

34 Prescriptive Fire Suppression System Fire Hydrant Flow Test

35 Prescriptive Fire Suppression System Rated 750 gpm The sprinkler system is supplied by a public water main The fire pump feeds four (4) standpipe systems (one in each stair) and 6 sprinkler systems (6 risers, one for each floor). The system can also be supplied by a Fire Department Connection (FDC)

36 Prescriptive Fire Suppression System Design Criteria : Occupancy Classification: OCCUPANCY HAZARD Protection Area (Sprinkler - ft 2 ) DESIGN A-3 Lobbies/Lectures Light Hazard gpm/ft ft 2 B Office/Conference Room Light Hazard gpm/ft ft 2 B Laboratories O.H. GR gpm/ft ft 2 S-1 Storage/Mech./ Electric Room O.H. GR gpm/ft ft 2

37 Prescriptive Fire Suppression System Sprinklers Layout Level 1 Sprinklers were mainly recessed pendent sprinkler installed in Lecture, Conference, Office and Laboratory Room. Some upright sprinklers used in Mechanical rooms, Elevator Mach. Room, Electrical Room, Telecommunication/Data Room and Stairs, and Horizontal Sidewall Sprinklers were used in elevator wells

38 Prescriptive Fire Suppression System Sprinklers Layout Level 1 Designer Calculation: HydraCAD Hand Calculation 1-1

39 Prescriptive Fire Suppression System Sprinklers Calculations Level 1 (Area 1-1) Hand Calculation Area 1-1

40 Prescriptive Sprinklers Calculations Fire Suppression System The design criteria is reduced 39.25% for Remote Areas 3-1, 3-2, 6-2 & 6-3. The reduction is based on: Design area reduction for quick response sprinklers : No unprotected ceiling pockets, Ceiling heights of Ordinary Hazard Group 1 (Laboratories) CBC 2007 Reduction is not permitted in CBC 2013

41 Prescriptive Fire Suppression System Sprinklers Calculations The design criterion is reduced 39.25% for Remote Areas 3-1, 3-2, 6-2 & 6-3.

42 Performance Based Performance Criteria Any occupant who is not intimate with ignition shall not be exposed to instantaneous or cumulative untenable conditions.(nfpa ) A Fire Barrier is not required between the atrium and the adjoining spaces of any three floors of the atrium, provided such spaces are accounted for in the design of the smoke control system (CBC-2007, Section 405.5, Exception 3)

43 Performance Based Performance Criteria Ref. SFPE, Guide to PBD

44 Performance Based Performance Criteria ASET > RSET ASET Time from ignition until the building becomes untenable RSET Time to evacuate from the room/ space/ building Detection time (t d ) Notification time (t n ) Pre-movement time (t p-e ) Travel time (t e )

45 Performance Based RSET td (detection time) RSET = t d + t n + t p-e + t e t n (notification time) t p-e (pre-movement time) t e (travel time) Travel Time (t e ) Time when all occupants are evacuated out of Zone 1 (Atrium). - Hydraulic model of emergency egress (SFPE Handbook) - Compare with STEPS Computer Evacuation Model - PATHFINDER

46 Performance Based RSET RSET = t d + t n + t p-e + t e Parameter Time (s) t d + t n Justification Open atrium, Primary detection: Building occupants seeing smoke rise through the atrium t p-e Reference: Proulx, SFPE Handbook, Table Scenario W1: Live directives using a voice communication system from a control room with closed-circuit television facility, or live directives in conjunction with well-trained, uniformed staff that can be seen and heard by all occupants in the space. 180 Scenario W2: Nondirective voice messages (prerecorded) and/or informative warning visual display with trained staff.

47 Performance Based RSET RSET = t d + t n + t p-e + t e Level Occupant Load (# persons) Atrium Exit Area (ft 2 ) Density: D (persons/ft 2 ) Movement Speed (ft/min) m/s Travel Distance (ft) t e SFPE Handbook t e STEPS Computer Evacuation Model

48 Performance Based RSET RSET = t d + t n + t p-e + t e Level Occupant Load (# persons) Atrium Exit Area (ft 2 ) Density: D (persons/ft 2 ) Movement Speed (ft/min) m/s Travel Distance (ft) t e SFPE Handbook t e STEPS Computer Evacuation Model

49 Performance Based RSET - Pathfinder Travel Time : Age Demographics Age OCCUPANCY Percent (%) Young Middle Doubled Old All ages Disable 6 Doubled 12 * Reference: Assessment of Photo-luminescent Material during Office Evacuation, 1999, Table 5 and Smoke Management Study- Atrium Smoke Control, 2009

50 Performance Based RSET - Pathfinder Occupant Walking Speeds (m/s) Occupant Type Horizontal Down Stairs Up Stairs References Young Fruin, 1987 and Fahy, 2001 Middle Fruin, 1987 and Fahy, 2001 Old Fruin, 1987 Disable Fruin, 1987 and Boyce, Shields, and Silcock, 1999 Reference: Smoke Management Study- Atrium Smoke Control, 2009

51 Performance Based RSET - Pathfinder Occupant Load/level

52 Performance Based RSET - Pathfinder

53 Performance Based RSET - Pathfinder Level t e SFPE Handbook t e STEPS * RSET = t d + t n + t p-e + t e t e PATHFINDER 6% Disabled Go to Any Exit Scenario A t e PATHFINDER 6% Disabled Go to Refuge A Scenario B t e PATHFINDER 12% Disabled Go to Any Exit Scenario C * 27* 24* * The 1-hour fire rated walls are considered adequate to retain occupants within the student work spaces.

54 Performance Based RSET - Pathfinder Level 2 3 Detection and Notification Time (s) t d + t n RSET Pre-movement and Action Time (s) T p-e Travel Time (s) t e RSET (s) 1.5X RSET (s) = t d + t n + t p-e + t CBC Section e * * The 1-hour fire rated walls are considered adequate to retain occupants within the student work spaces.

55 Performance Based ASET - Tenability Criteria Design Criteria (Limits) Tenability Limit Source Temperature 140 F(60 C) NFPA 130, Standard for Fixed Guideway and Passenger Rail Systems Visibility 42 feet (13 meters) Jin, SFPE Handbook, Table Radiant Flux Smoke Temperature 1.7 kw/m F (180 C) SFPE Engineering Guide, Predicting 1 st and 2nd Degree Skin Burns from Thermal Radiation Carbon Monoxide 1,000 ppm for 30 min NFPA 101, Life Safety Code

56 Performance Based Design Fire Scenarios ASET - FDS Qualitative Hazard Analysis: o Potential ignition/fuel sources based upon representative materials and equipment within various areas. Heat Release Rate Curves: o Fire scenarios quantified by assuming a fast t² fire, based upon the types of hazards likely in the building. Maximum Heat Release Rate. o Based upon the expected time for sprinkler activation and the maximum fire size of a given fuel package. Determination of Smoke Production. o Soot yields corresponding to polyurethane foam with some cellulosic material (effective yield of 5%).

57 Performance Based ASET - FDS Design Fire Scenarios *Heskestad and Delichastios Correlations ** FDS fire size Scenario Location Fire Control HRR Curve *HRR max (kw) **HRR max (kw) DF#1 Level 2, atrium center Sprinkler-controlled Fast t² 174 s 1500 DF#2 Level 2, high-bay space Fuel-controlled Fast t² FD#3 Level 4, student work space Sprinkler-controlled Fast t² 163 s 1300 DF#4 Level 5, atrium center Sprinkler-controlled Fast t² 174 s 1500

58 Performance Based ASET - FDS Current Project - Pathfinder Smoke Management Study, 2009 Level RSET (s) ASET (s) Results OK - OK FAIL - FAIL 3* OK - FAIL OK - FAIL OK - FAIL (240) FAIL - FAIL Level RSET (s) ASET (s) Results OK DF#1 OK DF#2 OK DF#3 OK (240) DF#4 FAIL (OK) *Level 3 excludes the student work spaces from evacuating because a 1- hour fire rated wall separates the atrium space from all other areas on this Level. The RSET calculations were performed with the software PATHFINDER considering pre-movement times of 60 and 180 seconds (W1 and W2).

59 Performance Based ASET - FDS Smoke Management Study Assumptions: HRR

60 Performance Based ASET - FDS Smoke Management Study Assumptions: HRR

61 Performance Based ASET - FDS Smoke Management Study Assumptions: Visibility C = 8 Light-emitting Sign (5 to 10) 13 m 13 m 13 m C = 3 Light-reflecting Sign (2 to 4) 7 m 5.3 m 6.7m

62 Performance Based ASET - FDS Smoke Management Study Assumptions: Visibility C = 3

63 Performance Based ASET Smoke Control System Exhaust Method NFPA 92 Design Fire : 3,120 kw Smoke Rate Production m = 156 kg/s Makeup Air Requirements (90 %) V = 117 m 3 /s. Supply vents A = 115 m 2 v < 1.02 m/s Maximum volumetric flow rate - plug-holing V max = 16.6 m 3 /s. Volumetric flow rate of smoke exhaust V = 133 m 3 /s Number of exhaust vents N Vents = exhaust vents A = 126 m 2

64 Performance Based ASET Smoke Control System Exhaust Method Design fires - Mechanical Smoke Control System Most severe cases Design Fire A (DFES-A): DF#2 HRR - 2,500 kw - Produces the most smoke and requires the highest exhaust rate. Design Fire B (DFES-B): DF#2 HRR - 3,120 kw - Produces the most smoke in the first stages of the fire. Design Fire D (DFES-C): DF#4 HRR - 1,500 kw - It makes fail the tenability criteria on Level 6 at 180 seconds, which is the worst ASET obtained in the study.

65 Performance Based ASET - RSET Smoke Control System Exhaust Method Design Fire D (DFES-C): DF#4 HRR - 1,500 kw Design Fire A (DFES-A): DF#2 HRR - 2,500 kw

66 Performance Based Conclusions - The CSM complies with the prescriptive requirements stated on the applicable codes. - The performance-based analysis, however, showed that different results might be obtained depending on the assumptions made for the evaluations. When the RSET STEPS, and t p-e is assumed to be 60 seconds, the ASET is greater than the RSET for all levels. When the RSET PATHFINDER, different results obtained depending on the t p-e assumed (60/180), and only Level 2 passed the tenability criteria regardless the t p-e considered.

67 Performance Based Conclusions - The Smoke Management Study assumed t p-e = 60 s on the basis that DF simulated are in relatively close proximity to the observe smoke and flames. occupied spaces, so the occupants would clearly be able to - The validity of this assumption may be challenged since: There are administrative offices and work spaces that subdivide the atrium space on Levels 2-6. The EVAC system installed operates through pre-recorded voice messages (W2) t p-e =180 s. - The simulation of the atrium with a Mechanical Smoke Control Systems showed that all levels in the atriums successfully pass the tenability criteria evaluated, regardless the pre-movement time considered.

68 Performance Based Recommendations - Prepare and implement a Fire Safety Management Plan for the building, in conformity with the requirements of the IFC, Chapter 4, including: The location of furniture to be allowed in the atrium at its different levels. The procedures and requirements for a staged evacuation in the building, which allow occupants within close proximity of the fire to evacuate the building first. - Conduct a detailed study in the current conditions of the building, in order to ascertain more accurately the validity of the assumptions made in the previous Smoke Management Study.

69 Performance Based Recommendations - Make the decision of redesign or change the EVAC system currently operating through pre-recorded voice messages, for a W1 system (60 s). - Conduct a detailed cost-benefit analysis for determining the feasibility of: Installing a mechanical smoke control system in the atrium Improving/changing the current natural smoke controls systems - The analysis should revolve on conservative assumptions in order to rely on a system able to provide 1.5 times the RSET for the safe occupant evacuation

70 Performance Based Acknowledgments - My sincere gratitude to all in the Cal Poly s FPE program, in particular to Frederick W. Mowrer and Christopher C. Pascual for their support during the whole period of study. - I would also like to acknowledge the following persons/companies for providing documentation/information as well as support to this project: Kevin Fagan, CAL POLY, SLO. Rex Wolf, CAL POLY, SLO. Curtis Streeter, DEEP BLUE INTEGRATION, INC. Stacey Williams, ZGF ARCHITECTS LLP Brian McLaughlin, ARUP Antonio Campo, UTSA

71 Culminating Project Fire Protection and Life Safety Engineering Analysis Thank you Center for Science and Mathematics Cal Poly Questions? Orelvis Gonzalez March 20 th, 2015

Construction Innovation Center Building 186

Construction Innovation Center Building 186 Construction Innovation Center Building 186 FPE 596 Professors Presented Culminating Experience in Fire Protection Engineering Christopher Pascual & Frederick W. Mowrer Christopher Torres Objective / Overview

More information

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING

More information

ROBERT E. KENNEDY LIBRARY CAL POLY, SAN LUIS OBISPO FIRE PROTECTION ANALYSIS FPE CULMINATING PROJECT. Prepared For:

ROBERT E. KENNEDY LIBRARY CAL POLY, SAN LUIS OBISPO FIRE PROTECTION ANALYSIS FPE CULMINATING PROJECT. Prepared For: ROBERT E. KENNEDY LIBRARY Page i ROBERT E. KENNEDY LIBRARY CAL POLY, SAN LUIS OBISPO Prepared For: Dr. Frederick W. Mowrer & Dr. Christopher Pascual California Polytechnic State University College of Engineering

More information

By: Russell Bainbridge March 18th, 2016 FPE 596

By: Russell Bainbridge March 18th, 2016 FPE 596 By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse

More information

Construction Warehouse. FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson

Construction Warehouse. FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson Construction Warehouse FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson 1 Statement of Disclaimer This project report is a result of a class assignment;

More information

Fire Protection Analysis DCI Data Center Building

Fire Protection Analysis DCI Data Center Building Fire Protection Analysis DCI Data Center Building California Polytechnic State University FPE 596 Culminating Experience in Fire Protection Engineering Bryan Hathaway M.S. Fire Protection Engineering -

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING. Fabio Mazza June 2016

FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING. Fabio Mazza June 2016 FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING Fabio Mazza June 2016 Introduction Codes & Standards Building description Performance based design Prescriptive based design Structural

More information

Fire Protection Coffee Break Training May 2016

Fire Protection Coffee Break Training May 2016 Fire Protection Coffee Break Training May 2016 Introduction High-Rise Requirements Questions and Answers Agenda Overview Site Fire Access Aerial Access Power/Back-up Power Elevators and Access Sprinklers

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

Fire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett

Fire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett Fire Protection System and Life Safety Evaluation of Building X Presented by Anthony W. Sublett Culminating Project Master of Science in Fire Protection Engineering California Polytechnic State University

More information

Statue of Liberty: A Risk Analysis

Statue of Liberty: A Risk Analysis Statue of Liberty: A Risk Analysis Bruce Campbell, FSFPE VP DOE Services National Park Service Agenda Overview of Project Scope Evaluation Steps Task 1 Code Analysis Task 2 Fire Modeling Task 3 Egress

More information

FIRE AND LIFE SAFETY ANALYSIS

FIRE AND LIFE SAFETY ANALYSIS FIRE AND LIFE SAFETY ANALYSIS AF Child Development Center Standard Design Judy Biddle Acknowledgements Special thanks for support and guidance over that past 2.5 years to: Professor Fred Mowrer Professor

More information

Fire Hazard Analysis of Technical Area 53 Building 1

Fire Hazard Analysis of Technical Area 53 Building 1 Fire Hazard Analysis of Technical Area 53 Building 1 June 11, 2015 LA-UR-15-23589 Slide 1 Introduction Brett Noakes Los Alamos National Laboratory Los Alamos, New Mexico Slide 2 Outline Background of the

More information

Will Clay Spring 2014

Will Clay Spring 2014 Will Clay Spring 2014 1. Project Overview 2. Prescriptive Requirements 3. Existing Requirements 4. Performance Evaluation 5. Conclusions RJA-Houston since 2010 Hired as FP/LS consultants by architect in

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT

More information

Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel

Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Virtual : An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Xiaolei Chen, PhD California State University, Los Angeles, United States Ning (Frank) Wang, P.E. Jensen Hughes,

More information

Fire and Life Safety Analysis

Fire and Life Safety Analysis Fire and Life Safety Analysis Grant M. Brown Engineering Building #41 California Polytechnic State University, San Luis Obispo Daniel Gregory Blanchat June 12 th, 2014 1 B l a n c h a t 1 Statement of

More information

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome! Building & Fire Code Academy Building Better With Our Greatest Resource Education Welcome! Understanding the Sprinkler System Design Alternatives in the 2015 International Why inspect, test and maintain?

More information

FIRE AND LIFE SAFETY ANALYSIS PRESCRIPTIVE AND PERFORMANCE BASED APPROACH

FIRE AND LIFE SAFETY ANALYSIS PRESCRIPTIVE AND PERFORMANCE BASED APPROACH FIRE AND LIFE SAFETY ANALYSIS PRESCRIPTIVE AND PERFORMANCE BASED APPROACH CAL POLY RECREATION CENTER BUILDING # 43 SAN LUIS OBISPO, CALIFORNIA CULMINATING PROJECT REPORT CAL POLY FIRE PROTECTION ENGINEERING

More information

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated

More information

Fire Protection System and Life Safety Evaluation. Building X. Anthony W. Sublett. Culminating Project

Fire Protection System and Life Safety Evaluation. Building X. Anthony W. Sublett. Culminating Project Fire Protection System and Life Safety Evaluation Of Building X By Anthony W. Sublett Culminating Project Presented to the Faculty of the Graduate School of California Polytechnic State University in Partial

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

Common Building Code Misinterpretations

Common Building Code Misinterpretations Common Building Code Misinterpretations Presented by: Ron Melucci, P.E. Technical Manager, FP Division Engineering Planning and Management, Inc. rbm@epm inc.com www.epm inc.com 508 875 2121 Engineering

More information

Prescriptive and Performance Analysis of Cold Machine Shop FPE 596 Culminating Project

Prescriptive and Performance Analysis of Cold Machine Shop FPE 596 Culminating Project Prescriptive and Performance Analysis of Cold Machine Shop FPE 596 Culminating Project John Kline 8/8/2018 Statement of Disclaimer This project report is a result of a class assignment; it has been graded

More information

HIGH-RISE RETROFIT ORDINANCES - NO and NO

HIGH-RISE RETROFIT ORDINANCES - NO and NO INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.

More information

El Reno Fire Department Fire Alarm Plan Review Worksheet

El Reno Fire Department Fire Alarm Plan Review Worksheet El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us

More information

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada

More information

Fire Protection Engineering Culminating Project. Analysis of the Seattle Customer Delivery Center. Prepared by Cynthia Wernet

Fire Protection Engineering Culminating Project. Analysis of the Seattle Customer Delivery Center. Prepared by Cynthia Wernet Fire Protection Engineering Culminating Project Analysis of the Seattle Customer Delivery Center Prepared by Cynthia Wernet California Polytechnic State University at San Luis Obispo June 9, 2016 Cynthia

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

American Fire Sprinkler Association. An Introduction to the IBC and IFC

American Fire Sprinkler Association. An Introduction to the IBC and IFC American Fire Sprinkler Association Presents An Introduction to the IBC and IFC October 13, 2005 Speaker Roland Huggins, P.E. Vice President of Engineering and Technical Services American Fire Sprinkler

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

rpsa FIRE PROTECTION ENGINEERS

rpsa FIRE PROTECTION ENGINEERS FIRE PROTECTION ENGINEERS R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator

More information

Prepared for: Professor Frederick W. Mowrer, PhD, P.E. Professor Christopher Pascual, PhD, P.E

Prepared for: Professor Frederick W. Mowrer, PhD, P.E. Professor Christopher Pascual, PhD, P.E Fire and Life Safety Analysis of The Production Facility (PF) - 870 Sandia National Laboratories, Albuquerque, New Mexico USA November 3, 2017 FPE596 Culminating Final Project Report By Nolan J. Baker,

More information

Culminating Project U.S. Federal Courthouse FPE Spring 2013

Culminating Project U.S. Federal Courthouse FPE Spring 2013 Culminating Project U.S. Federal Courthouse FPE 596 - Spring 2013 Joshua W. Elvove, PE, CSP, FSFPE NOT FOR PUBLIC DISTRIBUTION Statement of Disclaimer This project report is a result of a class assignment;

More information

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE Human Factors - Egress Analysis for High Hazard Occupancies Presented by: Michael J. Klemenz, PE, SFPE Group H Other SFPE presenters today discussed issues relevant to Group H This presentation addresses

More information

Case Study 1 Underground Car Park

Case Study 1 Underground Car Park Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building

More information

The Residences at Christina Landing Wilmington, DE

The Residences at Christina Landing Wilmington, DE 5.0 FIRE PROTECTION EXISTING CONDITIONS 5.1 Project Specific Fire Protection Data Codes, Regulations, and Standards Building Officials and Code administrators (BOCA) National Building Code [1996] with

More information

Tunnel Fire Dynamics and Evacuation Simulations

Tunnel Fire Dynamics and Evacuation Simulations Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation

More information

CALIFORNIA POLYTECHNIC SLO

CALIFORNIA POLYTECHNIC SLO CALIFORNIA POLYTECHNIC SLO FIRE PROTECTION ENGINEERING PROGRAM CULMINATING PROJECT SUMMER 2014 ROCK TOLER Statement of Disclaimer This project report is a result of a class assignment; it has been graded

More information

Fire Protection Engineering

Fire Protection Engineering Fire Protection Engineering FPE-596-FINAL REPORT NAME: MICHAEL STEWART DATE: JUNE 6, 2014 Contents Statement of Disclaimer... 5 Acknowledgement... 6 Building Overview & Description... 6 Building Construction

More information

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES 1 WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES TABLE 2.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF (1) ASSEMBLIES (Applies to each fire zone)

More information

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design June 15, 2017 Building Description Applicable Codes & Standards Prescriptive Requirements Structural Fire Protection Fire Sprinkler Fire Alarm Means of Egress Performance Based Design 2 3 Semiconductor

More information

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing

More information

Chapter 17, Initiating Devices

Chapter 17, Initiating Devices Chapter 17, Initiating Devices Summary. Chapter 17 was Chapter 5 in NFPA 72-2007. The term authority having jurisdiction is replaced in some sections by the term other governing laws, codes, or standards.

More information

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951) Riverside County Fire Department Office of the Fire Marshal 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4777 Fax (951) 955-4886 Guideline Title: Residentially Based Care Facilities Group

More information

IBC Committee Responsibility Matrix January 2017

IBC Committee Responsibility Matrix January 2017 IBC Committee Responsibility Matrix January 2017 Chapter 1 ADMIN same Chapter 3 High-Hazard Group H 307.1 same IFC same Uses Other Than Group H 307.1.1 same IFC same Hazardoss Materials 307.1.2 307.2 IFC

More information

Life Safety Report. XYZ Office Building. Denver Colorado. Prepared by: Keith Dix Monday, June 3, 2013

Life Safety Report. XYZ Office Building. Denver Colorado. Prepared by: Keith Dix Monday, June 3, 2013 Life Safety Report XYZ Office Building Denver Colorado Figure 1 - XYZ Building West Side Prepared by: Keith Dix Monday, June 3, 2013 Culminating Project FPE 596 California Polytechnic University, San Luis

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

Significant Changes to the 2012 IFC Semiconductor Fabrication Facilities. Scott Stookey Senior Technical Staff International Code Council, Austin TX

Significant Changes to the 2012 IFC Semiconductor Fabrication Facilities. Scott Stookey Senior Technical Staff International Code Council, Austin TX Significant Changes to the 2012 IFC Semiconductor Fabrication Facilities Scott Stookey Senior Technical Staff International Code Council, Austin TX Introduction This presentation reviews the significant

More information

Richard B. Alpert, P.E. Senior FPE, Clark Nexsen

Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Clark Nexsen is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of

More information

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,

More information

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities Fire Alarm and Signaling Code Overview NFPA 72-2010 usa.siemens.com/infrastructure-cities Siemens Building Technologies, Inc. is a Registered Provider with The American Institute of Architects Continuing

More information

Florida Building Code 2010

Florida Building Code 2010 Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with

More information

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016 Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the

More information

2018 NICET Code Transition Changes

2018 NICET Code Transition Changes 2018 NICET Code Transition Changes NICET will be transitioning to newer codes accepted in their exams in mid-october 2018, specifically: NFPA 72 2016 NFPA 70 2014 IBC 2015 NFPA 101 2015 Here are some changes

More information

NFPA Changes

NFPA Changes Chapter 21, Emergency Control Functions and Interfaces Summary. Chapter 21 is new. These requirements were formerly found in Chapter 6, Protected Premises Fire Alarm Systems. The term fire safety function

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

California Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19

California Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19 PART 3 Building and Equipment Design Features Chapters 5 through 19 Chapter 5 Fire Service Features No changes addressed Chapter 6 Building Services and Systems Chapter 7 Fire-Resistance-Rated Construction

More information

PLAN REVIEW SUBMITTAL GUIDE

PLAN REVIEW SUBMITTAL GUIDE PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide

More information

Case Study 2 Production and Storage. SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB)

Case Study 2 Production and Storage. SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB) Case Study 2 Production and Storage SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB) So What Are You We Going to Show You? A lot of tables, simplified methods

More information

FIRE PROTECTION SYSTEMS

FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS > SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation,

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

Residential-based Care Facility R-4 Guideline

Residential-based Care Facility R-4 Guideline Moreno Valley Fire Department Fire Prevention Bureau Residential-based Care Facility R-4 Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 7, 2017 Residential-based Care

More information

CULMINATING EXPERIENCE IN FIRE PROTECTION ENGINEERING ANALYSIS OF COSTCO, SAN FRANCISCO

CULMINATING EXPERIENCE IN FIRE PROTECTION ENGINEERING ANALYSIS OF COSTCO, SAN FRANCISCO CALIFORNIA POLYTECHNIC STATE UNIVERSITY, SAN LUIS OBISPO CULMINATING EXPERIENCE IN FIRE PROTECTION ENGINEERING ANALYSIS OF COSTCO, SAN FRANCISCO PREPARED BY: IAN LEVINE 380 4 TH AVE SAN FRANCISCO, CA 94118

More information

WORKSHEET 3-1 THE MANITOBA OFFICE OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

WORKSHEET 3-1 THE MANITOBA OFFICE OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES 1 WORKSHEET 3-1 THE MANITOBA OFFICE OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES TABLE 3.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF (1) ASSEMBLIES (Applies each fire zone) Building

More information

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER 7 ALTERATIONS LEVEL CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has

More information

Interfacing Fire Alarm, Sprinkler and Elevator Systems

Interfacing Fire Alarm, Sprinkler and Elevator Systems 1 Interfacing Fire Alarm, Sprinkler and Elevator Systems Rodger Reiswig, SET Director, Industry Relations SimplexGrinnell November 17, 2010 Interfacing to Elevators 2 ASME A17.1 Safety Code for Elevators

More information

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics. A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable

More information

Full Service Central Station Fire Alarm Listing Evaluation

Full Service Central Station Fire Alarm Listing Evaluation Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm

More information

University Design Standard Fire Alarm Systems

University Design Standard Fire Alarm Systems 1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

THE BASICS OF FIRE ALARM PLAN REVIEW

THE BASICS OF FIRE ALARM PLAN REVIEW THE BASICS OF FIRE ALARM PLAN REVIEW Art Shaw A Shaw & Associates, LLC. ashaw@arthurshaw.com 231.838.3269 Fire Protection System Plan Reviewer FP000006 NFPA Certified Plans Examiner 02-0005 NFPA Certified

More information

Preliminary Fire/Life Safety Assessment Task No (Submittal No. PH b14

Preliminary Fire/Life Safety Assessment Task No (Submittal No. PH b14 ` REGIONAL CONNECTOR TRANSIT CORRIDOR PROJECT Contract No. E0119 Preliminary Fire/Life Safety Assessment Task No. 7.1.1.2 (Submittal No. PH2.7.1.1.2.b14 Prepared for: Prepared by: The Connector Partnership

More information

New Construction Fire Inspection Process

New Construction Fire Inspection Process New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific

More information

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1 GENERAL: 1. All fire protection systems shall be installed in accordance with the International Fire Code and applicable NFPA standards. This guideline provides additional requirements for the design and

More information

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,

More information

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

NFPA 101 Code Update from 2012 Edition to the 2015 Edition NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls

More information

Case Study of Underground Car Park. Team Japan

Case Study of Underground Car Park. Team Japan 11th Conference on Performance Based Codes and Fire Safety Design Methods Case Study of Underground Car Park Team Japan We focused on the characteristics of the fire behavior of car fire. Car fire is not

More information

BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015

BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015 Exam ID Examination Code Part BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015 BC3-7 Level III Exam 7 BCBC Part 3 (Part 3 Buildings Classification & Construction) BC3-8 Level III Exam 8 BCBC

More information

The project scope work is 90% new construction and 10% remodel in Esslinger Hall.

The project scope work is 90% new construction and 10% remodel in Esslinger Hall. CREIGHTON ENGINEERING INC. FIRE PROTECTION CONSULTING ENGINEERS 210 N. University Road, Suite 100 Spokane Valley, WA 99206 TEL: 509.921.9755 FAX: 509.921.9806 WEB: www.creightoneng.com SCOTT R. CREIGHTON,

More information

For additional information regarding R-3.1 residential care facilities please contact (951)

For additional information regarding R-3.1 residential care facilities please contact (951) Riverside County Fire Department Fire/Life Safety Inspection Division Riverside Office: 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4823 Fax (951) 955-4886 Palm Desert Office: 77-933 Las

More information

The Cannabis Industry: Fire Department Requirements

The Cannabis Industry: Fire Department Requirements The Cannabis Industry: Fire Department Requirements RVFD Standard 4.1 Rio Vista Fire Department 350 Main St. Rio Vista, CA. 94571 By: Jeff Armstrong, Fire Chief Updated December 2018 1 The purpose of this

More information

BUILDING/FIRE CODE REFERENCES 2006 EDITION

BUILDING/FIRE CODE REFERENCES 2006 EDITION BUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform Fire The IBC references the IFC in 97 Code sections. This document

More information

January 1, 2014 Mandatory Effective Date

January 1, 2014 Mandatory Effective Date 2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective

More information

DEALING WITH FIRE SAFETY

DEALING WITH FIRE SAFETY DEALING WITH FIRE SAFETY Personal Care Homes And Assisted Living Facilities Presented by: Harold D. Hicks, P.E., FSFPE Fire Protection Engineer 1 Atlantic Code Consultants 2 Our Objectives Recognize the

More information

Osceola County Department of Fire Rescue and Emergency Medical Services

Osceola County Department of Fire Rescue and Emergency Medical Services St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner

More information

Considerations in the Design of Smoke Management Systems for Atriums

Considerations in the Design of Smoke Management Systems for Atriums Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke

More information

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 30 ELEVATORS AND CONVEYING SYSTEMS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency

More information

PERFORMANCE COMPLIANCE METHODS

PERFORMANCE COMPLIANCE METHODS CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,

More information

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL 3300 SUMMIT BOULEVARD WEST PALM BEACH, FLORIDA 33406 TEL (561) 688-7687 FAX (561) 688-7654 http://www.palmbeach.k12.fl.us/fm/bd/index.htm

More information

NFPA 45 NFPA 211 NFPA 1600

NFPA 45 NFPA 211 NFPA 1600 NFPA 45 NFPA 211 NFPA 1600 Prepared by: William E. Koffel, P.E., FSFPE Expertly Engineering Safety From Fire 1 Objectives Overview of the NFPA process Understand the scope and application of NFPA 45, NFPA

More information

COMPLIANCE ALTERNATIVES

COMPLIANCE ALTERNATIVES CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

COMPLIANCE ALTERNATIVES

COMPLIANCE ALTERNATIVES CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

Overview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Edition

Overview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Edition Accreditation Overview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Primarily based on Section 907 Portions of Section 903 and 909 are included. Portions of Chapter 10 are included.

More information