Construction Innovation Center Building 186

Size: px
Start display at page:

Download "Construction Innovation Center Building 186"

Transcription

1 Construction Innovation Center Building 186 FPE 596 Professors Presented Culminating Experience in Fire Protection Engineering Christopher Pascual & Frederick W. Mowrer Christopher Torres

2 Objective / Overview Prescriptive Analysis Approach Structure Fire Protection Performance based Analysis Approach Tenability Analysis: NFPA 101 / Method 2 Means of Egress B Fire Alarm System Fire Suppression System Codes & Standards during Construction Codes & Standards being Analyzed 2001 CBC 2001 CFC 1999 NFPA NFPA 72 C 2013 CBC 2013 CFC 2013 NFPA NFPA 72 Available Safe Egress Time (ASET) Time from ignition until building becomes untenable Required Safe Egress Time (RSET) Time needed for occupants to evacuate from the building 2

3 General Building Description A Construction Innovation Center was completed in 2008 B B Dedicated to the Construction Management Department C Divided into 3 individual buildings (A B C) 7 laboratories, 12 classrooms & lecture halls, and faculty offices Sprinklered throughout Group B Occupancy 3

4 Building Location San Luis Obispo, California B California Polytechnic State University South West of Campus C 4

5 Fire Apparatus Access Fire department vehicle must approach within 150 feet of any point along the exterior wall Minimum Unobstructed Horizontal Clearance 20 feet Minimum Unobstructed Vertical Clearance 13 feet 6 inches 5

6 Building Existing Dimensional Characteristics A Floors Building A Building B Building C Total Basement 1,770 SF 0 SF 0 SF 1,770 SF First 5,384 SF 8,178 SF 3,004 SF 21,498 SF Second 5,384 SF 8,184 SF 3,054 SF 17,488 SF Third 2,525 SF 8,264 SF 3,054 SF 14,573 SF Total 15,144 SF 24,626 SF 9,122 SF 48,882 SF B C B A Building A Existing Height 46 feet B 46 feet C 58 feet 6

7 Color Coded Floor Plans First Floor A B 7

8 Color Coded Floor Plans Second Floor A B 8

9 Color Coded Floor Plans Third Floor A B 9

10 Construction Type Classification A Construction Type of IIA Building elements listed in CBC Table 601 are of noncombustible materials Adopted provision CBC Table 601 Footnote d Buildings of only type IIA construction are permitted Automatic sprinkler system 1 hour rated substitution System is not used for allowable height and area increase Building Elements Minimum Fire Resistance Rating Existing Fire Resistance Rating Primary Structural Frame 1 hour 0 hour Exterior Bearing walls a 1 hour 1 hour Interior Bearing walls 1 hour 0 hour Exterior Nonbearing walls and partitions a CBC Table hour Interior Nonbearing walls and partitions 0 hour 0 hour Floor Construction and Associated Secondary Members Roof Construction and Associated Secondary Members 1 hour 0 hour 1 hour 0 hour a the 1-hour substitution for the fire resistance of exterior walls is not permitted under CBC Table 601 Note d 10

11 Fire Separation Distance A 187 Fire separation distance is the distance from the exterior wall of the building to an imaginary line between two buildings on the property. 76 Fire Separation Distance = X (feet) Type of Construction Group B Occupancy X < 5 IIA 1 hour 5 X < 10 IIA 1 hour 10 X < 30 IIA 1 hour X 30 IIA 0 hour 11

12 Occupant Load The occupant load factor establishes minimum occupant densities based on the function or actual use of the space, and not group classification Function Waiting Area Conference Office Lecture Laboratory Occupancy Load Factor 15 SF/Person 15 SF/Person 100 SF/Person 20 SF/Person 50 SF/Person Floor Building A Building B Building C Total amount of Occupants First 100 Persons 124 Persons 148 Persons 372 Persons Second 96 Persons 125 Persons 141 Persons 362 Persons Third 20 Persons 130 Persons 145 Persons 295 Persons Total 216 Persons 397 Persons 434 Persons 1029 Persons 12

13 Exit Access Exterior Exit Access Balcony The same requirements as corridors for width, headroom, dead ends, and projections [CBC Section ] Width Headroom Dead Ends a, b Minimum Provided Minimum Provided Minimum Provided a. 20 feet in length without sprinklers & 50 feet in length with sprinklers b. Dead-ends are permitted to be limited in length, where the length is less than 2.5 times its width (existing width = 20 feet) Projections Fire Separation Distance (FSD) Minimum Distance from Line used to Determined FSD 0 feet to less than 2 feet Projections not permitted 2 feet to less than 5 feet 24 inches 5 feet or greater 40 inches 13

14 Exit Stair #1 (Required) Stair #2 (Required) Stair #3 Stair #4 4 3 Occupancy One Egress Doorway Two Exits B Rooms or floors that require a minimum of two exit must have a separation distance of not less than 1/3 of the length of the maximum overall diagonal dimension of the space 2 14

15 Fire Alarm Control Panel A single smoke detector must be provided at the location of each fire alarm control panel [CBC Section ] Notifier NFS-640 Intelligent Fire Alarm Control Unit First Floor Plan Space 110 (Building A) & Room B110 (Building B) 15

16 Initiating Devices Notifier NBG 12LX Addressable Fire Alarm Box Notifier FAPT-851 Addressable Acclimate Plus Multi Sensor Detector Notifier FST 851 Addressable Heat Detector Notifier FSD-751P Air Duct Smoke Detector Detector Type Features Multiple Sensors (photoelectric &thermal sensing) Acclimate Plus Multi Sensor Adjust its sensitivity & alarm thresholds Multiple Alarm Signal Mathematical Evaluation if alarm is necessary Other Initiating Devices : Sprinkler Tamper Switch (FBO) & Sprinkler Waterflow Switch (FBO) 16

17 Notification Appliances Gentex EH24 R Horn Gentex Waterproof Gasket for Horn Gentex GEC3 24WR Multi Candela Horn/Strobe Gentex GES3 24WR Multi Candela Strobe Other Notification Appliances : Sprinkler Waterflow Bell (FBO) 17

18 Automatic Fire Sprinkler System TYCO Series TY-FRB Wet Pipe Fire Sprinkler System Quick Response Sprinklers 5.6 K Factor Actuation Temperatures: 155 F (1, 2, 3 Floor) & 280 F (Basement) Function Occupancy Density Total Combined Inside & Outside Hose Mechanical Rooms Service Rooms Storage Rooms Office Rooms General Building Areas Laboratory Rooms Ordinary Group Hazard Group 1 Ordinary Group Hazard Group GPM/ 250 GPM 0.15 GPM/ 250 GPM Light Hazard 0.10 GPM/ 100 GPM Ordinary Group Hazard Group GPM/ 250 GPM 18

19 Performance Based Analysis NFPA 101 / Tenability Analysis (Method 2) Available Safe Egress Time (ASET) Tenability Criteria Tenability Limits Reasons Visibility a 5.18 m Temperature 60 C Combustion Gas Toxicity 2,590 ppm a. SFPE Fire Protection Engineering 3rd Edition, Babrauskas For small enclosures and travel distances Thermal burns to the respiratory tract concentration of CO that causes incapacitation For each design fire scenario, the design team must demonstrate that each room or area will be fully evacuated before the smoke and toxic gas layer in that space descends to a level lower than 6 feet above the floor. Required Safe Egress Time (RSET) Total Evacuation Time = Activation Time + Notification Time + Reaction Time + Pre-Evacuation Time + Movement Time ASET > RSET 19

20 Design Fire Scenarios Building A: Space A101A, Seating Area The space is used for people to sit and wait until they are called upon from the receptionist A Fire occurring on couch closest to the door; blocking exit door Building B: Room B203, Construction Management Lab Lecture Format The room is used for students to work on various projects such as miniature architectural wood modeling B Fire occurring on a wooden model due to a faulty glue gun C Building C: Not selected as part of the tenability analysis This is due to time constraint and low existing ignition sources compared to Buildings A and B. 20

21 Fire Scenario in Building A Chair Tests Mass Padding Material Fabric Frame F21 T19, T kg California Foam Polyolefin Wood F22 T kg FR Cotton Batting Cotton Wood F23 T kg FR Cotton Batting Polyolefin Wood F24 T kg California Foam Cotton Wood F25 T kg Non- California Foam Polyolefin Wood Upholstered Furniture Heat Release Rate: Measurements and Estimation 21

22 Tenability Criteria for Fire Scenario in Building A 22

23 Evacuation Time for Fire Scenario in Building A Time: 0.0 / 49.0 seconds Time: 12.0 / 49.0 seconds Time: 24.0 / 49.0 seconds Occupant Evacuation Time Explanation Results Activation Time Detact-QS (Sprinkler) 150 sec Notification Time NFPA 72 Section sec Reaction Time Medium Alert 3 sec Pre Evacuation Time Packing of Office Supplies 10 sec Movement Time Pathfinder 49 sec Total Evacuation Time 222 sec (3.7 min) 23

24 Tenability Criteria for Fire Scenario in Building A Visibility 304 / 500 seconds (1.5 to 31.5m) Tenability Criteria a Tenability Limits FDS Results Visibility 5.18 m Pass Temperature 60 C Pass Toxicity 2,590 ppm Pass a. The tenability criteria are evaluated at 6 feet above the top of finished floor Temperature / 500 seconds (20 to 27.5 C) Toxicity / 500 seconds (0 to 9 ppm) 24

25 Fire Scenario in Building B Particle board tested in the cone calorimeter at two irradiances Test Specimen Thickness Density Ignition Time Rigid Polyurethane Foam 30 mm 30 kg/m 3 1sec Insulating Fiberboard 13 mm 250 kg/m 3 28 sec Expanded Polystyrene 50 mm 20 kg/m sec Medium Density Fiberboard 12 mm 600 kg/m 3 88 sec Particle Board 10 mm 750 kg/m 3 87 sec Prediction of Heat Release Rate of Surface Materials in Large Scale Fire Test Based on Cone Calorimeter Results 25

26 Tenability Criteria for Fire Scenario in Building B 26

27 Evacuation Time for Fire Scenario in Building B Time: 0.0 / 28.0 seconds Time: 9.3 / 28.0 seconds Time: 17.8 / 28.0 seconds Occupant Evacuation Time Explanation Results Activation Time Detact-QS (Sprinkler) 175 sec Notification Time NFPA 72 Section sec Reaction Time Medium Alert 3 sec Pre Evacuation Time Packing of School Supplies 10 sec Movement Time Pathfinder 28 sec Total Evacuation Time 226 sec (3.8 min) 27

28 Tenability Criteria for Fire Scenario in Building B Tenability Criteria a Tenability Limits FDS Results Visibility 5.18 m Pass Temperature 60 C Pass Toxicity 2,590 ppm Pass a. The tenability criteria are evaluated at 6 feet above the top of finished floor Visibility / 500 seconds (0.5 to 30 m) Temperature / 500 seconds (0 to 35 C) Toxicity / 500 seconds (0 to 200 ppm) 28

29 Acknowledgement A Christopher Torres would like to acknowledge and thank the following individuals for their assistance and guidance during the Fire Protection Engineering Master Program. The results of this endeavor would not have been possible without you. Professor Frederick Mowrer B Professor Christopher Pascual Dr. Chris Lautenberger Dr. David Rich Professor Lonnie Simonian Associate Professor Thomas Korman Professor Frederick Mowrer C Professor Kevin Dong Dr. Francisco Joglar Mr. Morgan Hurley Architect Rex Wolf Ivy Rose Jose Ando Professor Christopher Pascual

Fire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett

Fire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett Fire Protection System and Life Safety Evaluation of Building X Presented by Anthony W. Sublett Culminating Project Master of Science in Fire Protection Engineering California Polytechnic State University

More information

Will Clay Spring 2014

Will Clay Spring 2014 Will Clay Spring 2014 1. Project Overview 2. Prescriptive Requirements 3. Existing Requirements 4. Performance Evaluation 5. Conclusions RJA-Houston since 2010 Hired as FP/LS consultants by architect in

More information

Culminating Project. Fire Protection and Life Safety Engineering Analysis. Cal Poly. Center for Science and Mathematics. Fire Protection Engineering

Culminating Project. Fire Protection and Life Safety Engineering Analysis. Cal Poly. Center for Science and Mathematics. Fire Protection Engineering Culminating Project Fire Protection and Life Safety Engineering Analysis Fire Protection Engineering California Polytechnic State University Center for Science and Mathematics Cal Poly San Luis Obispo,

More information

By: Russell Bainbridge March 18th, 2016 FPE 596

By: Russell Bainbridge March 18th, 2016 FPE 596 By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse

More information

ROBERT E. KENNEDY LIBRARY CAL POLY, SAN LUIS OBISPO FIRE PROTECTION ANALYSIS FPE CULMINATING PROJECT. Prepared For:

ROBERT E. KENNEDY LIBRARY CAL POLY, SAN LUIS OBISPO FIRE PROTECTION ANALYSIS FPE CULMINATING PROJECT. Prepared For: ROBERT E. KENNEDY LIBRARY Page i ROBERT E. KENNEDY LIBRARY CAL POLY, SAN LUIS OBISPO Prepared For: Dr. Frederick W. Mowrer & Dr. Christopher Pascual California Polytechnic State University College of Engineering

More information

Fire and Life Safety Analysis

Fire and Life Safety Analysis Fire and Life Safety Analysis Grant M. Brown Engineering Building #41 California Polytechnic State University, San Luis Obispo Daniel Gregory Blanchat June 12 th, 2014 1 B l a n c h a t 1 Statement of

More information

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING

More information

FIRE AND LIFE SAFETY ANALYSIS PRESCRIPTIVE AND PERFORMANCE BASED APPROACH

FIRE AND LIFE SAFETY ANALYSIS PRESCRIPTIVE AND PERFORMANCE BASED APPROACH FIRE AND LIFE SAFETY ANALYSIS PRESCRIPTIVE AND PERFORMANCE BASED APPROACH CAL POLY RECREATION CENTER BUILDING # 43 SAN LUIS OBISPO, CALIFORNIA CULMINATING PROJECT REPORT CAL POLY FIRE PROTECTION ENGINEERING

More information

Construction Warehouse. FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson

Construction Warehouse. FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson Construction Warehouse FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson 1 Statement of Disclaimer This project report is a result of a class assignment;

More information

Fire Protection Analysis DCI Data Center Building

Fire Protection Analysis DCI Data Center Building Fire Protection Analysis DCI Data Center Building California Polytechnic State University FPE 596 Culminating Experience in Fire Protection Engineering Bryan Hathaway M.S. Fire Protection Engineering -

More information

Fire Protection System and Life Safety Evaluation. Building X. Anthony W. Sublett. Culminating Project

Fire Protection System and Life Safety Evaluation. Building X. Anthony W. Sublett. Culminating Project Fire Protection System and Life Safety Evaluation Of Building X By Anthony W. Sublett Culminating Project Presented to the Faculty of the Graduate School of California Polytechnic State University in Partial

More information

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE Human Factors - Egress Analysis for High Hazard Occupancies Presented by: Michael J. Klemenz, PE, SFPE Group H Other SFPE presenters today discussed issues relevant to Group H This presentation addresses

More information

Fire Hazard Analysis of Technical Area 53 Building 1

Fire Hazard Analysis of Technical Area 53 Building 1 Fire Hazard Analysis of Technical Area 53 Building 1 June 11, 2015 LA-UR-15-23589 Slide 1 Introduction Brett Noakes Los Alamos National Laboratory Los Alamos, New Mexico Slide 2 Outline Background of the

More information

Life Safety Report. XYZ Office Building. Denver Colorado. Prepared by: Keith Dix Monday, June 3, 2013

Life Safety Report. XYZ Office Building. Denver Colorado. Prepared by: Keith Dix Monday, June 3, 2013 Life Safety Report XYZ Office Building Denver Colorado Figure 1 - XYZ Building West Side Prepared by: Keith Dix Monday, June 3, 2013 Culminating Project FPE 596 California Polytechnic University, San Luis

More information

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951) Riverside County Fire Department Office of the Fire Marshal 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4777 Fax (951) 955-4886 Guideline Title: Residentially Based Care Facilities Group

More information

Potential Impact of New UL Fire Test Criteria

Potential Impact of New UL Fire Test Criteria Potential Impact of New UL Fire Test Criteria Thomas G. Cleary Fire Research Division National Institute of Standards and Technology March 7, 2014 Outline Background Recent History Task Group Progress

More information

For additional information regarding R-3.1 residential care facilities please contact (951)

For additional information regarding R-3.1 residential care facilities please contact (951) Riverside County Fire Department Fire/Life Safety Inspection Division Riverside Office: 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4823 Fax (951) 955-4886 Palm Desert Office: 77-933 Las

More information

Prepared for: Professor Frederick W. Mowrer, PhD, P.E. Professor Christopher Pascual, PhD, P.E

Prepared for: Professor Frederick W. Mowrer, PhD, P.E. Professor Christopher Pascual, PhD, P.E Fire and Life Safety Analysis of The Production Facility (PF) - 870 Sandia National Laboratories, Albuquerque, New Mexico USA November 3, 2017 FPE596 Culminating Final Project Report By Nolan J. Baker,

More information

Smoke Alarm Research at NIST

Smoke Alarm Research at NIST Smoke Alarm Research at NIST Thomas G. Cleary Fire Research Division National Institute of Standards and Technology Smoke Alarm Summit March 31, 2015 Outline Supporting ANSI/UL 217 268 Task Group on adding

More information

FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING. Fabio Mazza June 2016

FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING. Fabio Mazza June 2016 FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING Fabio Mazza June 2016 Introduction Codes & Standards Building description Performance based design Prescriptive based design Structural

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

Culminating Project U.S. Federal Courthouse FPE Spring 2013

Culminating Project U.S. Federal Courthouse FPE Spring 2013 Culminating Project U.S. Federal Courthouse FPE 596 - Spring 2013 Joshua W. Elvove, PE, CSP, FSFPE NOT FOR PUBLIC DISTRIBUTION Statement of Disclaimer This project report is a result of a class assignment;

More information

FIRE AND LIFE SAFETY ANALYSIS

FIRE AND LIFE SAFETY ANALYSIS FIRE AND LIFE SAFETY ANALYSIS AF Child Development Center Standard Design Judy Biddle Acknowledgements Special thanks for support and guidance over that past 2.5 years to: Professor Fred Mowrer Professor

More information

Life Safety - Means of Egress/Exits NFPA 101

Life Safety - Means of Egress/Exits NFPA 101 Life Safety - Means of Egress/Exits NFPA 101 Properly designed exits provide a safe path of escape from a fire or other emergency environment. The means of egress (exits) should be arranged to permit all

More information

January 1, 2014 Mandatory Effective Date

January 1, 2014 Mandatory Effective Date 2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective

More information

Recommendations for a Model Curriculum for a BS Degree in Fire Protection Engineering (FPE) April 15, 2010

Recommendations for a Model Curriculum for a BS Degree in Fire Protection Engineering (FPE) April 15, 2010 Recommendations for a Model Curriculum for a BS Degree in Fire Protection Engineering (FPE) April 15, 2010 Society of Fire Protection Engineers (SFPE) Acknowledgement: SFPE would like to acknowledge the

More information

Fire Protection Engineering Culminating Project. Analysis of the Seattle Customer Delivery Center. Prepared by Cynthia Wernet

Fire Protection Engineering Culminating Project. Analysis of the Seattle Customer Delivery Center. Prepared by Cynthia Wernet Fire Protection Engineering Culminating Project Analysis of the Seattle Customer Delivery Center Prepared by Cynthia Wernet California Polytechnic State University at San Luis Obispo June 9, 2016 Cynthia

More information

CULMINATING EXPERIENCE IN FIRE PROTECTION ENGINEERING ANALYSIS OF COSTCO, SAN FRANCISCO

CULMINATING EXPERIENCE IN FIRE PROTECTION ENGINEERING ANALYSIS OF COSTCO, SAN FRANCISCO CALIFORNIA POLYTECHNIC STATE UNIVERSITY, SAN LUIS OBISPO CULMINATING EXPERIENCE IN FIRE PROTECTION ENGINEERING ANALYSIS OF COSTCO, SAN FRANCISCO PREPARED BY: IAN LEVINE 380 4 TH AVE SAN FRANCISCO, CA 94118

More information

Residential Based Care Facility Guidelines

Residential Based Care Facility Guidelines Moreno Valley Fire Department Fire Prevention Bureau Residential Based Care Facility Guidelines Approved and Authorized By: Randall Metz, Fire Marshal Issued: January 1, 2011 Residential Based Care Facilities

More information

Safety Manual Section 7 Fire/Life Safety

Safety Manual Section 7 Fire/Life Safety 7. FIRE/LIFE SAFETY The following sections provide fire/life safety guidelines and procedures. This section covers the following topics: Topic Page 7.1 General... 7-2 A. The Effects of a Fire... 7-2 B.

More information

Prescriptive and Performance Analysis of Cold Machine Shop FPE 596 Culminating Project

Prescriptive and Performance Analysis of Cold Machine Shop FPE 596 Culminating Project Prescriptive and Performance Analysis of Cold Machine Shop FPE 596 Culminating Project John Kline 8/8/2018 Statement of Disclaimer This project report is a result of a class assignment; it has been graded

More information

The project scope work is 90% new construction and 10% remodel in Esslinger Hall.

The project scope work is 90% new construction and 10% remodel in Esslinger Hall. CREIGHTON ENGINEERING INC. FIRE PROTECTION CONSULTING ENGINEERS 210 N. University Road, Suite 100 Spokane Valley, WA 99206 TEL: 509.921.9755 FAX: 509.921.9806 WEB: www.creightoneng.com SCOTT R. CREIGHTON,

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963) INFORMATION BULLETIN / PUBLIC - MECHANICAL CODE REFERENCE NO.: LAMC 91.8604 Effective: 6-20-84 DOCUMENT NO. P/MC 2002-005 Revised: 6-15-00 Previously Issued As: MGD #74 FIRE SAFETY REQUIREMENTS FOR PRE-

More information

Plan Review Check List Fire Alarm System

Plan Review Check List Fire Alarm System Plan Review Check List Fire Alarm System EXCELSIOR FIRE DISTRICT 241OO SMITHTOWN ROAD SHOREWOOD, MN 55331 Alarm system must be installed according to NFPA 72, 2010 Edition, National Fire Alarm and Signaling

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

Tunnel Fire Dynamics and Evacuation Simulations

Tunnel Fire Dynamics and Evacuation Simulations Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation

More information

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

NFPA 101 Code Update from 2012 Edition to the 2015 Edition NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls

More information

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES 1 WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES TABLE 2.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF (1) ASSEMBLIES (Applies to each fire zone)

More information

Fire Protection Engineering

Fire Protection Engineering Fire Protection Engineering FPE-596-FINAL REPORT NAME: MICHAEL STEWART DATE: JUNE 6, 2014 Contents Statement of Disclaimer... 5 Acknowledgement... 6 Building Overview & Description... 6 Building Construction

More information

Statue of Liberty: A Risk Analysis

Statue of Liberty: A Risk Analysis Statue of Liberty: A Risk Analysis Bruce Campbell, FSFPE VP DOE Services National Park Service Agenda Overview of Project Scope Evaluation Steps Task 1 Code Analysis Task 2 Fire Modeling Task 3 Egress

More information

Large Family Daycare Guideline

Large Family Daycare Guideline Moreno Valley Fire Department Fire Prevention Bureau Large Family Daycare Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 10, 2017 Large Family Daycare Guideline Purpose

More information

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1.

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1. EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD STANDARD #F-003 EFFECTIVE 06-03-2009 PURPOSE To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified

More information

Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel

Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Virtual : An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Xiaolei Chen, PhD California State University, Los Angeles, United States Ning (Frank) Wang, P.E. Jensen Hughes,

More information

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design June 15, 2017 Building Description Applicable Codes & Standards Prescriptive Requirements Structural Fire Protection Fire Sprinkler Fire Alarm Means of Egress Performance Based Design 2 3 Semiconductor

More information

How design fires can be used in fire hazard analysis

How design fires can be used in fire hazard analysis How design fires can be used in fire hazard analysis Yung, D.T.; Bénichou, N. NRCC-44511 A version of this document is published in / Une version de ce document se trouve dans : Fire Technology, v. 38,

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST TENANT IMPROVEMENTS Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved w/comments;

More information

NFPA 45 NFPA 211 NFPA 1600

NFPA 45 NFPA 211 NFPA 1600 NFPA 45 NFPA 211 NFPA 1600 Prepared by: William E. Koffel, P.E., FSFPE Expertly Engineering Safety From Fire 1 Objectives Overview of the NFPA process Understand the scope and application of NFPA 45, NFPA

More information

CALIFORNIA POLYTECHNIC SLO

CALIFORNIA POLYTECHNIC SLO CALIFORNIA POLYTECHNIC SLO FIRE PROTECTION ENGINEERING PROGRAM CULMINATING PROJECT SUMMER 2014 ROCK TOLER Statement of Disclaimer This project report is a result of a class assignment; it has been graded

More information

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome! Building & Fire Code Academy Building Better With Our Greatest Resource Education Welcome! Understanding the Sprinkler System Design Alternatives in the 2015 International Why inspect, test and maintain?

More information

MEDIUM-DENSITY HOUSING # 7. Fire safety

MEDIUM-DENSITY HOUSING # 7. Fire safety BRANZ FACTS MEDIUM-DENSITY HOUSING # 7 Fire safety Moving from low-density to medium-density housing (MDH) involves people living in closer proximity. This has a number of implications for fire safety

More information

A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK. James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA

A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK. James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA Presentation Objective Compare fire alarm system design methods

More information

CAFAA S 22 nd ANNUAL STATE AGENCY FORUM 09/28/17

CAFAA S 22 nd ANNUAL STATE AGENCY FORUM 09/28/17 STEVE SCHWARTZ (Consolidated Fire Protection) Q-01 NFPA 72 Chapter 18 Section 18.4.2.4, The standard evacuation signal shall be synchronized within a notification zone. We have been taught that a floor

More information

Case Study of Underground Car Park. Team Japan

Case Study of Underground Car Park. Team Japan 11th Conference on Performance Based Codes and Fire Safety Design Methods Case Study of Underground Car Park Team Japan We focused on the characteristics of the fire behavior of car fire. Car fire is not

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work

More information

A Comparison of Carbon Monoxide Gas Sensing to Particle Smoke Detection in Residential Fire Scenarios

A Comparison of Carbon Monoxide Gas Sensing to Particle Smoke Detection in Residential Fire Scenarios A Comparison of Carbon Monoxide Gas Sensing to Particle Smoke Detection in Residential Fire Scenarios Thomas Cleary, Amy Mensch National Institute of Standards and Technology, Gaithersburg, MD, USA Abstract

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

Moving Target: A Case Study in Providing Fire Protection Below a Reconfigurable Concert Hall Seating System. Part 1: Concept Design

Moving Target: A Case Study in Providing Fire Protection Below a Reconfigurable Concert Hall Seating System. Part 1: Concept Design Moving Target: A Case Study in Providing Fire Protection Below a Reconfigurable Concert Hall Seating System Part 1: Concept Design 2 Amy L. Porter, P.E. (TX,VA, NM) AND Michael Wojcik, P.E. (AZ, CO, MA,

More information

St. John s University

St. John s University St. John s University Fire Safety Plan Bent Hall Παγε 1 St. John s University Fire Safety Plan Part 1-Building Information Section Bent Hall 8000 Utopia Parkway Jamaica NY 11439 Fire Safety Director: Robert

More information

DEALING WITH FIRE SAFETY

DEALING WITH FIRE SAFETY DEALING WITH FIRE SAFETY Personal Care Homes And Assisted Living Facilities Presented by: Harold D. Hicks, P.E., FSFPE Fire Protection Engineer 1 Atlantic Code Consultants 2 Our Objectives Recognize the

More information

Third Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG

Third Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG 1 Third Runway Project APM Depot Fire Engineering Design Presented by Ir Wilson Sau-kit TSANG 1 2 Presentation Overview 1. Project Background and Depot Overview 2. Building Information and Challenge for

More information

St. John s University

St. John s University St. John s University Fire Safety Plan Mahoney Hall St. John s University Mahoney Hall page 2 Fire Safety Plan Part 1-Building Information Section Mahoney Hall 300 Howard Ave. Staten Island, N.Y. 10301

More information

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions Smoke Characterization Study October 29, 2008 Paul E. Patty, P.E. Senior Research Engineer Northbrook, IL 847-664-2752

More information

Residential-based Care Facility R-4 Guideline

Residential-based Care Facility R-4 Guideline Moreno Valley Fire Department Fire Prevention Bureau Residential-based Care Facility R-4 Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 7, 2017 Residential-based Care

More information

LIFE SAFETY CODE ESSENTIALS PRESENTED BY: LARRY VIGIL, RISK CONSULTANT

LIFE SAFETY CODE ESSENTIALS PRESENTED BY: LARRY VIGIL, RISK CONSULTANT LIFE SAFETY CODE ESSENTIALS PRESENTED BY: LARRY VIGIL, RISK CONSULTANT INTRODUCTION 2007-11 5,690 Structure fires 75 Civilian Deaths $83 Million Direct Property Damage 71% in Nursery, Elementary, Middle

More information

(h) Pesticide Application.

(h) Pesticide Application. Fire Code Cannabis Amendment Section 13.20.066 is added to the Marysville Municipal Code to read in its entirety as follows: 13.20.066 Cannabis Growing, Processing, or Extraction Facilities (a) Application.

More information

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Fire Science and Technorogy Vol.24 No.4(2005) 165-178 165 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Jun-ichi Yamaguchi 1, Takeyoshi Tanaka 2 1 Technical Research

More information

Flammable Liquid Storage

Flammable Liquid Storage Published on UC Davis Safety Services (https://safetyservices.ucdavis.edu) Flammable Liquid Storage SafetyNet #: 523 Properties, Classification, Quantities, Cabinets, Containers and Refrigerators A. Summary

More information

NFPA 101 Life Safety Code Culture change 2012

NFPA 101 Life Safety Code Culture change 2012 NFPA 101 Life Safety Code Culture change 2012 Produced by Kansas Fire Marshal April, 2012 On March 9, 2012 Centers for Medicare & Medicaid Services implements a policy where they have formally adopted

More information

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER 7 ALTERATIONS LEVEL CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

The following are the Proposed Amendments to 2015 edition of the Life Safety Code (NFPA 101):

The following are the Proposed Amendments to 2015 edition of the Life Safety Code (NFPA 101): The following are the Proposed Amendments to 2015 edition of the Life Safety Code (NFPA 101): 1.1.1 Title. NFPA 101, Life Safety Code, shall be known as the Life Safety Code, is cited as such, and shall

More information

Ch. 54 GROUP B EDUCATIONAL 34 CHAPTER 54. GROUP B EDUCATIONAL OCCUPANCY GROUP

Ch. 54 GROUP B EDUCATIONAL 34 CHAPTER 54. GROUP B EDUCATIONAL OCCUPANCY GROUP Ch. 54 GROUP B EDUCATIONAL 34 CHAPTER 54. GROUP B EDUCATIONAL OCCUPANCY GROUP Sec. 54.1. Group B occupancies. 54.2. Classification. 54.3. Nursery schools, day care centers and the like. 54.4. Separation

More information

Considerations in the Design of Smoke Management Systems for Atriums

Considerations in the Design of Smoke Management Systems for Atriums Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke

More information

The Cannabis Industry: Fire Department Requirements

The Cannabis Industry: Fire Department Requirements The Cannabis Industry: Fire Department Requirements RVFD Standard 4.1 Rio Vista Fire Department 350 Main St. Rio Vista, CA. 94571 By: Jeff Armstrong, Fire Chief Updated December 2018 1 The purpose of this

More information

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015

More information

7.1 Smoke Detector Performance

7.1 Smoke Detector Performance 7.1 Smoke Detector Performance Paul E. Patty, P.E. Senior Research Engineer Northbrook X 42752 paul.e.patty@us.ul.com Smoke Detector Performance Smoke Characterization Project Quality of smoke Material

More information

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing

More information

UNIVERSITY OF RICHMOND HOUSING FIRE SAFETY POLICY

UNIVERSITY OF RICHMOND HOUSING FIRE SAFETY POLICY UNIVERSITY OF RICHMOND HOUSING FIRE SAFETY POLICY SFTY 2 May, 2002 Revised March, 2003 Revised August, 2004 Revised July, 2005 Revised March, 2006 Revised June, 2007 Revised April, 2008 Revised May, 2009

More information

El Reno Fire Department Fire Alarm Plan Review Worksheet

El Reno Fire Department Fire Alarm Plan Review Worksheet El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us

More information

Residential Care Facilities Requirements

Residential Care Facilities Requirements Development Services Department Building Division 311 Vernon Street Roseville, California 95678-2649 Residential Care Facilities Requirements SUBMITTAL REQUIREMENTS: Note: These requirements are in addition

More information

Occupancy Classification and Layout Guidelines

Occupancy Classification and Layout Guidelines Occupancy Classification and Layout Guidelines H3? S1? F1? B? U? H6? M? H7? A1? Presented to PIBA Seminar Group Todd LaBerge, P.E. Senior Fire Protection Engineer Presentation Overview Occupancy Groups

More information

Risk Management Department. Fire Extinguishers

Risk Management Department. Fire Extinguishers Risk Management Department Fire 1 Introduction to Fire Every school facility is equipped with fire extinguishers for staff to use to suppress fires. Used properly, a fire extinguisher can be an effective

More information

Fire Research and Education at the University of Maryland

Fire Research and Education at the University of Maryland Fire Research and Education at the University of Maryland J. G. Quintiere Department of Fire Protection Engineering March 7,8 2005 2nd Int. Symp. 21st Century Center of Excellence Program History of FPE

More information

FIRE SAFETY AND PREVENTION POLICY

FIRE SAFETY AND PREVENTION POLICY Effective Date: July 26, 2011 Supersedes /Amends: VRS-49/April 2006 Originating Office: Office of the Vice-President, Services Policy Number: VPS-49 PREAMBLE Concordia University (the University ) has

More information

St. John s University Fire Safety Plan

St. John s University Fire Safety Plan Fire Safety Plan Kelleher Center Kelleher Center page 2 St. John s University Fire Safety Plan Part 1-Building Information Section Kelleher Center 300 Howard Ave. Staten Island, N.Y. 10301 Fire Safety

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT

More information

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada

More information

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011 1.0 GENERAL: Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011 1.1 PURPOSE -The intent of this guideline is to provide the requirements for the protection

More information

Application of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall. Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia

Application of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall. Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia Application of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia A Challenging Application for the New Italian Fire Code

More information

St. John s University

St. John s University St. John s University Fire Safety Plan St John s Hall Παγε 1 St. John s University Fire Safety Plan Part 1-Building Information Section St. John s Hall 8000 Utopia Parkway Jamaica NY 11439 Fire Safety

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,

More information

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated

More information

2018 NICET Code Transition Changes

2018 NICET Code Transition Changes 2018 NICET Code Transition Changes NICET will be transitioning to newer codes accepted in their exams in mid-october 2018, specifically: NFPA 72 2016 NFPA 70 2014 IBC 2015 NFPA 101 2015 Here are some changes

More information

The six tests conducted included three smoldering and three fast flaming type tests.

The six tests conducted included three smoldering and three fast flaming type tests. The Mayfield Village Tests On May 9, May 12 and May 13, 2014 NEOFPA conducted six full-scale, real-world smoke alarm comparison tests in the city of Mayfield Village, Ohio. Tests 5 and 6 conducted on May

More information

Laboratories and Hazardous Materials. Company Overview

Laboratories and Hazardous Materials. Company Overview Laboratories and Hazardous Materials Don E. Contois, P.E. Sam Sinapi Company Overview R.W. Sullivan Engineering (RWS) was established in 1945 and currently has 95 employees. RWS is a full service engineering

More information

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

First Aspen Federal Regulation Set: K LSC 2000 Health Existing First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall

More information

2. Closed circuit television, design and installation.

2. Closed circuit television, design and installation. Company: AECO Systems, Inc. is a sound and communicator contractor, affiliated with NECA and IBEW. We specialize in commercial fire alarm systems, providing both sales and engineering. We are also involved

More information

Case Study 1 Underground Car Park

Case Study 1 Underground Car Park Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building

More information

School Fire Safety Checklist

School Fire Safety Checklist Community Risk Reduction The (SFSC) includes many of the most common fire prevention and life safety issues found in schools. The SFSC is not intended to be an all inclusive list, but rather highlights

More information