Case Study 2 Production and Storage. SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB)
|
|
- Eustace Gallagher
- 5 years ago
- Views:
Transcription
1
2 Case Study 2 Production and Storage SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB)
3 So What Are You We Going to Show You? A lot of tables, simplified methods etc. this is how our legal system works at the moment! Some performance engineering mainly connected with the design of SHEVS A bit of paradox when it comes to ESFR sprinklers and SHEVS, we are in quite of a trouble
4 Engineering Methods in Use, Related to Industrial Buildings Type Software / model CFD Evacuation Hand calculations FDS, ANSYS, Phoenix, Smartfire, AutodeskCFD Pathfinder, Evac, buildingexodus Popularity high high Application CFD analysis form the base of most of SHEV design, are widely used in evaluation of environmental conditions for users, Often referred as the valid method for estimation of ASET time Usually combined with CFD analysis as the method for estimation of RSET, but usually not as a part of industrial building design Fire Load Density high Requirements for industrial buildings rely on Fire Load Density, thus this element is part of every industrial design Explosion Risk high Risk of explosion will increase the requirements for the building Sizing SHEVS NFPA, PB, DIN, TR high Hand calculations are always part of the SHEVS design, and often the only dimensioning approach used
5 Engineering Methods in Use, Related to Industrial Buildings Type Software / model Popularity Application Zone Modeling CFAST, Brisk, fireplatform.eu medium Used in preliminary design, rarely part of the building design permit application Radiation modeling fireplatform.eu, FDS, ANSYS low Used in the derogation process for the possible separation between the buildings, may be used for the design of separation between storage areas in storage facility FEM FVM ANSYS, Robot low Used in structural design of some buildings (for fire conditions)
6 Tenant 1 High bay storage with 2 levels of catwalks at levels of 4 and 8 m (document archive), additional office mezzanine above loading bay Tenant 2 High bay storage with man-up system (car parts warehouse) Tenant 3 Production of furniture with raw material storage and ready products storage, 2 floor office building
7 Estimation of Fire Load Density Fire load density is a key parameter in determination of safety requirements for industrial buildings The most popular methods for estimation of the fire load density are inventory methods involving survey of fire materials in a building. Such methods require an estimation of the amount of each flammable material, that adds up to the sum of fire load within the area It is uncommon in Poland to use performance engineering or more advanced fire load estimation methods (ie. NFPA 557) Qd fire load density [MJ/m2] Qci x Gi Heat of combustion x mass F - Area
8 Estimation of Fire Load Density tenant 1 tenant 2 tenant 3 Type Storage/Archive High storage car parts (plastics?) Medium storage, production Materials Paper, evenly packed in closed Metals (20%), plastics (PE - 25%, PCV 25%), foams (PU) (30%) Multplier 0,2 - - Heat of combustion [MJ/kg] 16 24,25 19,85 Estimated mass Fire Load Density approx t of paper 312 MJ/m² Q < 500 MJ/m² approx. mass of t of stored goods MJ/m² Q > 4000 MJ/m² Wood (30%) and cellulose materials (15%), upholstery (15%) packaged goods (40%) 105 t of stored materials 15 t of goods in the production line 324 t of stored goods MJ/m² 1000 MJ/m² < Q < 2000 MJ/m²
9 Fire Risk Classes of the Building If sprinklers are used risk class E relating to lowest requirements If no sprinklers or SHEVS are used: tenant 1 class E tenant 2 class A tenant 3 class C
10 Fire Resistance Building risk class Main structure of the building Required fire resistance class for structure elements roof structure roof external walls internal walls roof covering "A" R 240 R 30 REI 120 EI 120(o i) EI 60 RE 30 "C" R 60 R 15 REI 60 EI 30 (o i) EI 154) RE 15 "E" (-) (-) (-) (-) (-) (-) Class A and C give requirements so high for an industrial building, that it is not economically reasonable to not use sprinklers!
11 Fire Zone Area Allowed Fire load Q > < Q Q 500 Maximum area of the fire zone (single floor building) basic + SHEVS + Sprinkler + Sprinkler + SHEVS unlimited unlimited unlimited
12 Separation Distances Distance between buildings of given classes Human occupation (ie. office) Human occupation (ie. office) Livestock building Production/storage Q < Q Q > Livestock building Production/storage Q Production/storage < Q Production/storage Q >
13 Evacuation From any point in the building to an exit to an evacuation route, other fire zone or outside of the building, from 100 to 175 m (dependant on choice of fire protection features) Length of evacuation route (corridors, staircases etc.): Type of fire zone single direction Length of evacuation route shortest route, when two directions or more are available (length for 2nd direction) Industrial, Q > 500 MJ/m² 30* 60 (120) Industrial, Q < 500 MJ/m² 60* 100 (200) ZL III (offices) 30* 60 (120) * not more than 20 m on a horizontal route
14 Potential Problem Office above Loading Bay Real solution in Poland the legal downside of an office within industrial fire zone is too big for any investor to allow it simpler solution is to move this part into other building
15 Potential Problem Separation Distance in Unsprinklered Zone (Tenant 1) 5 MW 10 MW
16 Potential Problem Max. Area of the Fire Zone, Tenant 2
17 Potential Problem Functional Separation of Smoke Zones in Tenant 3 Zone as a Protection for Fragile Production Equipment a Need for a Shevs Overdesign
18 The Main Use of Performance Engineering in Poland Design of Smoke and Heat Exhaust System
19 Design example the design of NSHEV system of the tenant 1 zone. The goal is to allow safe evacuation, limit the spread of fire and the damage done to the archive, and allow rescue operations.
20 There are mezzanine levels in the zone, so the evacuation from top tier (+8,00 m) must be possible. The office must be separated from the smoke zone of archive, by at least a smoke curtain.
21 Standard approach PN-B Max area of smoke zone 2 600m² Min. Height of smoke curtain 3,075 m, which makes smoke free height of ~ 9,00 m (does not guarantee safe evacuation!)
22 Aerodynamic area of smoke ventilators in each smoke zone 1,50% of the zone area, which relates to 39 m²
23 Mass density of smoke (0,00 0,20 g/m3) t = 10 min, 5 MW fire Temperature ( K) t = 10 min, 5 MW fire
24 Mass density of smoke (0,00 0,20 g/m3) t = 10 min, 10 MW fire Temperature ( K) t = 10 min, 10 MW fire
25 Replacing PN-B approach with NFPA 204. The fire for an archive may be considered as slow. The calculated aerodynamic free area of the ventilators is 39,6 m²
26 Mass density of smoke (0,00 0,20 g/m3) t = 10 min, 5 MW fire Temperature ( K) t = 10 min, 5 MW fire
27 Mass density of smoke (0,00 0,20 g/m3) t = 10 min, 5 MW fire Temperature ( K) t = 10 min, 5 MW fire
28 Can We Further Optimize the System with Computational Fluid Dynamics Tools? The search for the minimum area of ventilators
29 Mass density of smoke (0,00 0,20 g/m3) t = 10 min, 5 MW fire Temperature ( K) t = 10 min, 5 MW fire
30 Mass density of smoke (0,00 0,20 g/m3) t = 10 min, 10 MW fire Temperature ( K) t = 10 min, 10 MW fire
31 What about the Adverse Influence of Wind on the System Performance?
32 Combined wind and fire analysis: 1. Wind coefficient analysis 2. Fire performance of NSHEV 3. Optimization
33 Wind pressure coefficient, for Uref = 4,67 m/s, at Zref = 10 m
34 Wind pressure coefficient, for Uref = 10,00 m/s, at Zref = 10 m
35 HRR = 5 MW, α = 135, A = 26 m² for Uref = 1,0 m/s for Uref = 4,67 m/s for Uref = 10,0 m/s
36 HRR = 10 MW, α = 135, A = 26 m² for Uref = 1,0 m/s for Uref = 4,67 m/s for Uref = 10,0 m/s
37 Real Application Example
38 Tenant 2 the Problems with ESFR Sprinklers and SHEVS
39 Issue with ESFR Sprinklers and Ventilation For the benefits shown in the beginning of the presentation, combination of SHEVS and sprinklers is required SHEVS system has to be automatic (by law), while most standards require SHEVS in manual control ie. automatic solution is not allowed by VdS 2815 : Solution is to provide high-temperature actuators (140 C, 182 C) for the ventilator, that allow sprinklers to operate long before the SHEVS, but at the same time, if for some case sprinklers do not actuate, the SHEVS system can
40 120 s, HRR = 2701 kw 180 s, HRR = 6078 kw 240 s, HRR = kw
41 Temperature ( C) H = 11,00 m 180 s, HRR = 6078 kw 240 s, HRR = kw
42 Mass density of smoke at the time of firefighter approach (t = 600 s) Required free area of ventilators for smoke clearence less than 10 m²
43 Thank You for Your Attention!
CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION
- 165 - CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT
More informationCase Study 1 Underground Car Park
Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building
More informationCOSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN
COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING
More informationCase Study 1 Underground car park
Case Study 1 Underground car park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, INBEPO Wroclaw, Poland 1. Introduction
More informationStatue of Liberty: A Risk Analysis
Statue of Liberty: A Risk Analysis Bruce Campbell, FSFPE VP DOE Services National Park Service Agenda Overview of Project Scope Evaluation Steps Task 1 Code Analysis Task 2 Fire Modeling Task 3 Egress
More informationA New Zealand Case Study Building Design 11 th International Conference on Performance
A New Zealand Case Study Building Design 11 th International Conference on Performance Prof Charles Fleischmann University of Canterbury Dept. Civil and Nat Res Eng. Christchurch, New Zealand Carol Caldwell
More informationFIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING. Fabio Mazza June 2016
FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING Fabio Mazza June 2016 Introduction Codes & Standards Building description Performance based design Prescriptive based design Structural
More informationand Sprinkler System in Resalat Tunnel of Tehran
CFD Simulation of Water Mist and Sprinkler System in Resalat Tunnel of Tehran Motivation Resalat tunnel is the first road tunnel in Tehran one of most crowded tunnels of Tehran my every day route, home
More informationInteraction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS)
Fire Protection Leaflet Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS) 0 General Regulations and recommendations missing from this leaflet do not entitle
More informationCase Study of Underground Car Park. Team Japan
11th Conference on Performance Based Codes and Fire Safety Design Methods Case Study of Underground Car Park Team Japan We focused on the characteristics of the fire behavior of car fire. Car fire is not
More informationThird Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG
1 Third Runway Project APM Depot Fire Engineering Design Presented by Ir Wilson Sau-kit TSANG 1 2 Presentation Overview 1. Project Background and Depot Overview 2. Building Information and Challenge for
More informationREVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS
REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS Nikola TANASIĆ, Tomislav SIMONOVIĆ, Miloš IVOŠEVIĆ, Branislav
More informationCase Study 2 (Production and Storage Buildings) - Spain
Case Study 2 (Production and Storage Buildings) - Spain OBJECTIVE Developed by the SFPE Spanish Chapter Editor: Jimmy Jönsson, JVVA Fire & Risk The objective of this case study is to show how a project
More informationTunnel Fire Dynamics and Evacuation Simulations
Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation
More informationGeneral Principles of Smoke Control
AMCA International General Principles of Smoke Control Patrick Janssens, Sales Manager Colt International www.coltinco.co.uk or www.coltinfo.be Air System Engineering & Technology (ASET) Conference Europe
More informationWATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS
WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,
More informationSimple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings
Fire Science and Technorogy Vol.24 No.4(2005) 165-178 165 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Jun-ichi Yamaguchi 1, Takeyoshi Tanaka 2 1 Technical Research
More informationHeat Release Rate of an Open Kitchen Fire of Small Residential Units in Tall Buildings
2014 Purdue Compressor/Refrigeration and Air Conditioning and High Performance Buildings Conference West Lafayette, IN, USA 14-17 July 2014 Heat Release Rate of an Open Kitchen Fire of Small Residential
More informationThe Science Behind Water Mist Protection of Typical Building Hazards
The Science Behind Water Mist Protection of Typical Building Hazards SUPDET 2014 Zachary Magnone, P.E. Zachary.Magnone@tycofp.com Presentation Goals What is water mist? How does it work? How is it tested
More informationNFPA-APSEI Fire & Security 2010
NFPA-APSEI Fire & Security 2010 Smoke control in industrial buildings Paul Compton, Colt International Ltd A brief introduction Private British Company founded in 1931 Owned by O Hea family and the Colt
More informationFire and smoke management in a uni-directional road tunnel for a congested traffic condition
Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Y Liu, J Munro Parsons Brinckerhoff Australia B Dandie Thiess Pty Ltd., Australia ABSTRACT Emergency smoke ventilation
More informationWill Clay Spring 2014
Will Clay Spring 2014 1. Project Overview 2. Prescriptive Requirements 3. Existing Requirements 4. Performance Evaluation 5. Conclusions RJA-Houston since 2010 Hired as FP/LS consultants by architect in
More informationModule 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements
Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why
More informationConstruction Warehouse. FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson
Construction Warehouse FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson 1 Statement of Disclaimer This project report is a result of a class assignment;
More informationBasic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency
Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency Haiye Lou TurboMoni Applied Dynamics Lab Abstract It is often happened, when a project
More informationRecent Advances in Fire Suppression Modeling Issues & Perspectives of Fire Safety Engineering Applications
Recent Advances in Fire Suppression Modeling Issues & Perspectives of Fire Safety Engineering Applications Pianet Grégoire Studies and modelling section manager Fire and Environmental Department, CNPP
More informationConsiderations in the Design of Smoke Management Systems for Atriums
Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke
More informationComparative Evaluation Method for Fire Safety Design of Large Storage Spaces
Comparative Evaluation Method for Fire Safety Design of Large Storage Spaces ZHENKUN WU 1,2, HAIHANG LI 1, YAPING HE 3, DECHUANG ZHOU 1, JIAN WANG 1 1 State Key Laboratory of Fire Science, University of
More informationHow to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs
How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada
More informationHuman Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE
Human Factors - Egress Analysis for High Hazard Occupancies Presented by: Michael J. Klemenz, PE, SFPE Group H Other SFPE presenters today discussed issues relevant to Group H This presentation addresses
More informationPlan Submittal Checklist
City of Aurora Public Works Department HIGH-PILED COMBUSTIBLE STORAGE Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420 Fax: 303-739-7551 Project
More information5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea
5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea PRACTICAL APPLICATIONS OF FIRE MODELING IN INDUSTRIAL APPLICATIONS By James M. Dewey, Advisor Risk Management
More informationKings County Jail Expansion Phase 3 Rational Analysis of Smoke Control System
Kings County Jail Expansion Phase 3 Rational Analysis of Smoke Control System Kings County Jail Phase 3 Page 2 RATIONAL ANALYSIS OF SMOKE CONTROL SYSTEM PER 2013 CBC 909.4 General Description: The project
More informationLevel I Chapter 1 Worksheet
Chapter 1 Worksheet 1. When the present code requires certain safety to life requirements for existing buildings, those requirements shall. a. be void b. apply c. be approved d. be grand-fathered 2. The
More informationOpen to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP
Open to Below: A Discussion of Allowed Floor Openings Kevin S. Hastings, P.E., LEED AP Jay A. Ierardi, Ph.D., P.E., LEED AP R.W. Sullivan Engineering (617) 523-8227, Fax (617) 523-8016 http://www.rwsullivan.com
More informationFire Hazard Analysis of Technical Area 53 Building 1
Fire Hazard Analysis of Technical Area 53 Building 1 June 11, 2015 LA-UR-15-23589 Slide 1 Introduction Brett Noakes Los Alamos National Laboratory Los Alamos, New Mexico Slide 2 Outline Background of the
More informationCFD Analysis of Fire Characteristics on Subway Junction Station
ISGSR27 First International Symposium on Geotechnical Safety & Risk Oct. 18~19, 27 Shanghai Tongji University, China CFD Analysis of Fire Characteristics on Subway Junction Station G. H. Wu, X. Han, Q.Q.
More informationOPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE
OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE 1 RU ZHOU, 2 WEI ZHANG 1 School of Urban Construction and Safety Engineering, Nanjing University of Technology, Nanjing
More informationPractical problems of applying performance-based structural fire engineering in building design
Practical problems of applying performance-based structural fire engineering in building design Piotr Smardz INBEPO Sp. z o.o. ul. Domeyki 9a, 53-209 Wrocław, Poland INTRODUCTION The introduction of structural
More informationPerformance-based Fire Design of Air-supported Membrane Coal Storage Shed
Available online at www.sciencedirect.com Procedia Engineering 52 ( 2013 ) 593 601 Performance-based Fire Design of Air-supported Membrane Coal Storage Shed ZHANG Lei a,b, ZHU Guo-qing a,b,*, ZHANG Guo-wei
More informationOBC INDUSTRIAL CLASSIFICATION OBOA ANNUAL MEETING AND TRAINING SESSIONS LONDON ON OCTOBER 4, 2011
OBC INDUSTRIAL MAJOR OCCUPANCY CLASSIFICATION OBOA ANNUAL MEETING AND TRAINING SESSIONS LONDON ON OCTOBER 4, 2011 Randal Brown & Associates Ltd. 2011 1 PRESENTERS RANDAL BROWN P.ENG., PE, BDS, FSPFE PRESIDENT
More informationtechnical specification smoke venting systems
technical specification smoke venting systems An Introduction to FDS FDS sets the standards the rest of the industry follows Providing a complete service for all of your smoke ventilation system needs.
More information2015 SFPE Europe Conference on Fire Safety Engineering
2015 SFPE Europe Conference on Fire Safety Engineering THE FSE APPROACH FOR A HISTORICAL BUILDING IN LIGHT OF THE ITALIAN STANDARDS. Simonetto Sacco Luciano Nigro HUGHES ASSOCIATES EUROPE, srl FIRE SCIENCE
More informationConstruction Innovation Center Building 186
Construction Innovation Center Building 186 FPE 596 Professors Presented Culminating Experience in Fire Protection Engineering Christopher Pascual & Frederick W. Mowrer Christopher Torres Objective / Overview
More informationEmergency Ventilation System Design - Preliminary Report Shishir Gupta
Emergency Ventilation System Design - Preliminary Report Shishir Gupta (shishir@mechartes.com), Abstract The existing stations and tunnels of Metro Railway, Kolkata are not equipped with effective emergency
More informationEVACUATION MODELING DEPENDENCE ON INPUT PARAMETERS
PROCEEDINGS, Fire and Evacuation Modeling Technical Conference 211 Baltimore, Maryland, August 15-16, 211 EVACUATION MODELING DEPENDENCE ON INPUT PARAMETERS Brian Salyers, Bevan Jones Holmes Fire 13 Sutter
More informationFire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett
Fire Protection System and Life Safety Evaluation of Building X Presented by Anthony W. Sublett Culminating Project Master of Science in Fire Protection Engineering California Polytechnic State University
More informationNew DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE
DEPARTMENT OF HEALTH & HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - AMBULATORY SURGICAL CENTERS Medicare 1. (A) PROVIDER NUMBER Identifying information as shown in
More informationAUTOMATIC FIREFIGHTING SYSTEMS IN PAINT BOOTHS
SPECIAL HAZARDS PROTECTION AUTOMATIC FIREFIGHTING SYSTEMS IN PAINT BOOTHS Hazard type The risks considered, according to existing regulations, are Class A risk: solids fire. Class B risk: fire of flammable
More informationFire safety engineering applied to high-rise building facades
MATEC Web of Conferences 46, 04002 (2016) DOI: 10.1051/matecconf/20164604002 C Owned by the authors, published by EDP Sciences, 2016 Fire safety engineering applied to high-rise building facades Samuele
More informationPROPOSAL BALLOT DUE BY: Thursday, September 18, 2008
PROPOSAL BALLOT DUE BY: Thursday, September 18, 2008 NFPA 204 SMO-AAA Standard for Smoke and Heat Venting Staff Liaison: Return Completed Ballot To: Jill McGovern E-Mail to jmcgovern@nfpa.org Fax to 617-984-7110
More informationincorporating Contractors guide to car park ventilation A no-nonsense guide to the safe ventilation of underground and covered car parks
incorporating Contractors guide to car park ventilation A no-nonsense guide to the safe ventilation of underground and covered car parks Car park ventilation What are the regulations? Ventilation of car
More informationNFPA 45 NFPA 211 NFPA 1600
NFPA 45 NFPA 211 NFPA 1600 Prepared by: William E. Koffel, P.E., FSFPE Expertly Engineering Safety From Fire 1 Objectives Overview of the NFPA process Understand the scope and application of NFPA 45, NFPA
More informationBuilding & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!
Building & Fire Code Academy Building Better With Our Greatest Resource Education Welcome! Understanding the Sprinkler System Design Alternatives in the 2015 International Why inspect, test and maintain?
More informationSprinklers Modeling for Tunnel Road Fire Fighting
Sprinklers Modeling for Tunnel Road Fire Fighting P. Ciambelli, M.G. Meo, P. Russo, S. Vaccaro Department of Chemical and Food Engineering, University of Salerno - ITALY 1. INTRODUCTION Loss of lives and
More informationEVALUATION OF EVACUATION AT FACULTY ENGINEERING
EVALUATION OF EVACUATION AT FACULTY ENGINEERING INTRODUCTION INTRODUCTION The seven story building fitted with three lifts lies partially on a lake. It houses offices for the Dean, Deputy Deans and eight
More informationEVACUATION MODELLING IN ROAD TUNNEL FIRES
Complex Underground Multipurpose Facilities: Safety Challenges and Solutions Workshop organised by the ITA-COSUF as part of the ITA-AITES World Tunnel Congress 2013 EVACUATION MODELLING IN ROAD TUNNEL
More informationVirtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel
Virtual : An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Xiaolei Chen, PhD California State University, Los Angeles, United States Ning (Frank) Wang, P.E. Jensen Hughes,
More informationA case study for integrated modelling of personnel evacuation with pool fire simulation to increase safety in design for offshore oil and gas projects
A case study for integrated modelling of personnel evacuation with pool fire simulation to increase safety Davood Afshari 1 Richard Welsh 2 Maryam Moghaddas 3 Sara Afsharikia 1 Amir Tavakoli 4 1 Lead Technical
More informationNUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM
, Volume 11, Number 2, p.43-48, 2012 NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM Q. Kui Institute of Building Fire Research, China Academy of Building Research, Beijing,
More informationHigh-Piled Combustible Storage
High-Piled Combustible Storage Presenters: Rob Neale & Scott Adams Tuesday, September 12, 2017 1:30 PM - 4:30 PM High-piled Combustible Storage Based on the 2015 International Fire Code ICC Annual Conference
More informationMoving Target: A Case Study in Providing Fire Protection Below a Reconfigurable Concert Hall Seating System. Part 1: Concept Design
Moving Target: A Case Study in Providing Fire Protection Below a Reconfigurable Concert Hall Seating System Part 1: Concept Design 2 Amy L. Porter, P.E. (TX,VA, NM) AND Michael Wojcik, P.E. (AZ, CO, MA,
More informationfor commercial kitchen ventilation
Energy efficient solutionszag Energy efficient solutions for commercial kitchen ventilation Andrey Livchak, Dr., Halton Introduction Restaurants are among commercial buildings with the highest energy consumption
More informationSmoke control in car parks
Smoke control in car parks The actual situation in CEN TC 191 SC1 WG9 Imagine the result Jean-Claude DE SMEDT MIFireE,MSFPE,MNFPA Senior Fire Safety Engineering Consultant @ ARCADIS Belgium Convener of
More informationBy: Russell Bainbridge March 18th, 2016 FPE 596
By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse
More informationPracticalities and Limitations of Coupling FDS with Evacuation Software
ABSTRACT Practicalities and Limitations of Coupling FDS with Evacuation Software Daniel Rådemar, WSP, Sweden Daniel Blixt, WSP, Sweden Brecht Debrouwere, WSP, Sweden Björn Grybäck Melin, WSP, Sweden Andrew
More informationAdrian Milford Sereca - a Jensen Hughes Company, Project Engineer Vancouver, BC, Canada
Transit Vehicle Design Standards and Risk Analysis on Fire Development in Rapid Transit Vehicles Adrian Milford Sereca - a Jensen Hughes Company, Project Engineer Vancouver, BC, Canada Motivation Design
More informationCulminating Project. Fire Protection and Life Safety Engineering Analysis. Cal Poly. Center for Science and Mathematics. Fire Protection Engineering
Culminating Project Fire Protection and Life Safety Engineering Analysis Fire Protection Engineering California Polytechnic State University Center for Science and Mathematics Cal Poly San Luis Obispo,
More informationMINISTERIO DE FOMENTO
Dirección General de Servicios de Alta Velocidad - Larga Distancia Real Scale Fire Tests in High-Speed Trains Convocatoria de Concesión de Ayudas a Agrupaciones o Consorcios de Investigación para la realización
More informationautomatic FiReFighTing SYSTeMS in PainT booths
SPECIAL HAZARDS PROTECTION automatic FiReFighTing SYSTeMS in PainT booths hazard type The risks considered, according to existing regulations, are Class A risk: solids fire. Class B risk: fire of flammable
More informationFire and Smoke Management in a Uni-Directional Road Tunnel for a Congested Traffic Condition
International Journal of Ventilation ISSN 1473-3315 Volume 8 No 4 Fire and Smoke Management in a Uni-Directional Road Tunnel for a Congested Traffic Condition Y. Liu 1, J. Munro 1 and B. Dandie 2 1 Parsons
More informationSandeep V. Lutade 1, Krunal Mudafale 2, Ranjan Kishore Mallick 3 1, 2
A CFD Analysis of Smoke Movement in Steel Industry Sheds Sandeep V. Lutade 1, Krunal Mudafale 2, Ranjan Kishore Mallick 3 1, 2 Mechanical Dept. Dr.Babasaheb Ambedkar College of Engineering and Research,
More informationCOST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS
, Volume 1, Number 3, p.123-128, 1999 COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS D. Yung and G.V. Hadjisophocleous Fire Risk Management Program, Institute for Research
More informationActive & Passive Fire Protection System. Page 1 Kalidasan S BT IN SSP-OP
Active & Passive Fire Protection System Page 1 Kalidasan S BT IN SSP-OP Fire Protection - Introduction Introduction: The definition of fire protection of a building refers to the building ability to detect,
More informationTable EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c
Table 1015.1 EXIT ACCESS TRAVEL DISTANCE a WITHOUT SPRINKLER WITH SPRINKLER OCCUPANCY SYSTEM SYSTEM A, E, F-1, I-1, M, 200 250 b,d R, S-1 B 200 300 c F-2, S-2, U 300 400 c No Change to Other Entries in
More informationThe Residences at Christina Landing Wilmington, DE
5.0 FIRE PROTECTION EXISTING CONDITIONS 5.1 Project Specific Fire Protection Data Codes, Regulations, and Standards Building Officials and Code administrators (BOCA) National Building Code [1996] with
More informationSMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN
, Volume 4, Number 2, p.73-83, 2003 SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN K.H. Yang and C.S. Yang Mechanical Engineering Department, National Sun Yat-Sen
More informationICC CODE CORNER 2012 IFC Code & Commentary
SECTION 910 SMOKE AND HEAT VENTS 910.1 General. Where required by this code or otherwise installed, smoke and heat vents or mechanical smoke exhaust systems and draft curtains shall conform to the requirements
More informationA NETWORK MODEL OF SIMULATING SMOKE MOVEMENT IN BUILDINGS
, Volume 3, Number 4, p.151-157, 2001 A NETWORK MODEL OF SIMULATING SMOKE MOVEMENT IN BUILDINGS F. Liu and X.Z. Fu Faculty of Urban Construction and Environmental Engineering Chongqing University, Chongqing
More information2016/2017 Fee Schedule
Corporate Office 2420 Alft Lane Elgin, IL 60124 P: 847.697.1300 F: 847.697.1310 www.firesafetyfsci.com Specializing in Fire, Building, and Life Safety 2016/2017 Fee Schedule Regional Office 23650 Woodward
More informationNFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES
NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire
More informationENFP 102: Engineering and Testing Creative Fire Safe Building Designs
ENFP 102: Engineering and Testing Creative Fire Safe Building Designs Instructors: Jim Milke, Ph.D., P.E., milke@umd.edu, Room 3104B JMP, 301-405-3995 Ken Isman, P.E., kisman@umd.edu, Room 3104L JMP, 301-405-
More informationARCHIVED. C/VM2 Verification Method: Framework for Fire Safety Design For New Zealand Building Code Clauses C1-C6 Protection from Fire
C/VM2 Verification Method: Framework for Fire Safety Design For New Zealand Building Code Clauses C1-C6 Protection from Fire Using this Verification Method The Ministry of Business, Innovation and Employment
More informationSafety Manual: Emergency Response
Safety Manual: Emergency Response January, 2017 6.0 Emergency Preparedness Introduction This Chapter provides guidelines for dealing with Emergencies. Fires, no matter how small, must be reported to management
More informationANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS
ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS Prepared for Smoke Safety Council 6775 SW 111 th Avenue, Suite 10 Beaverton, OR 97008 Prepared by Jesse J. Beitel Alison J. Wakelin Craig L.
More informationUnit 2 Fire Safety (Zone 2)
IFE Level 3 Diploma in Fire Safety and Fire Science Unit 2 Fire Safety (Zone 2) Examiner Report March 2017 Introduction 21% of the candidates that sat the examination attained a pass. Candidates did not
More informationNumerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand
Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand Mohammed Mutafi 1, Mohammad Nasif 1*, William Pao 1 and
More informationRichard B. Alpert, P.E. Senior FPE, Clark Nexsen
Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Clark Nexsen is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of
More information2018 KEPIC-Week, Busan ~31 화재사건과기술기준 - 건물화재에대한공학적분석 - Dr. Ing. Wee Kyong KIM
2018 KEPIC-Week, Busan 2018.8.28~31 화재사건과기술기준 - 건물화재에대한공학적분석 - Dr. Ing. Wee Kyong KIM Introduction and Fire Dynamics Ignition and Prevention Factors Fire Growth / Flame Spread Fire Suppression, Detection
More informationModule 7. Control of Smoke & Highlights of Code Requirements
Module 7 Control of Smoke & Highlights of Code Requirements 1 Module 7 Overview This module will cover: 1. The requirements of smoke control in the Ohio Building Code Section 909 2. The differences between
More informationPreview of the MA Building Code (780 CMR) 9 th edition
Preview of the MA Building Code (780 CMR) 9 th edition Presented by: Ron Melucci, P.E. Engineering Planning and Management, Inc rbm@epm inc.com www.epm inc.com 508 875 2121 Engineering Planning and Management,
More informationImpact of quick incident detection on safety in terms of ventilation response
Impact of quick incident detection on safety in terms of ventilation response P. J. Sturm 1) ; C. Forster 2) ; B. Kohl 2) ; M. Bacher 1) 1) Institute for Internal Combustion Engines and Thermodynamics
More informationIs Prescription the Future of Performance-Based Design?
Is Prescription the Future of Performance-Based Design? CHARLES M. FLEISCHMANN Department of Civil and Natural Resources Engineering University of Canterbury Christchurch, New Zealand ABSTRACT The popularity
More informationInterim Life Safety Measures. Healthcare Construction Certificate - Level 1
Interim Life Safety Measures Purpose of Interim Life Safety Management BASIC SAFETY: During renovations projects in healthcare occupancies, the basic level of protection for the occupants must be maintained
More informationBuilding Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design
June 15, 2017 Building Description Applicable Codes & Standards Prescriptive Requirements Structural Fire Protection Fire Sprinkler Fire Alarm Means of Egress Performance Based Design 2 3 Semiconductor
More informationChapter 17, Initiating Devices
Chapter 17, Initiating Devices Summary. Chapter 17 was Chapter 5 in NFPA 72-2007. The term authority having jurisdiction is replaced in some sections by the term other governing laws, codes, or standards.
More informationAn experimental study of the impact of tunnel suppression on tunnel ventilation
An experimental study of the impact of tunnel suppression on tunnel ventilation Yoon J. Ko and George Hadjisophocleous Civil and Environmental Engineering, Carleton University 1125 Colonel By Drive, Ottawa,
More informationFRAM-ini A qualitative fire risk assessment method FRAME Erik De Smet
FRAM-ini A qualitative fire risk assessment method 13-3-2014 FRAME Erik De Smet FRAM-ini: A qualitative fire risk assessment method FRAM-ini: A qualitative fire risk assessment method... 1 Introduction....
More informationCODE SUMMARY REQUIREMENTS (NEW CONSTRUCTION/TENANT IMPROVEMENT (TI))
Code Summary Handout - Last revised 09/30/2014 CODE SUMMARY REQUIREMENTS WASHINGTON COUNTY OREGON (NEW CONSTRUCTION/TENANT IMPROVEMENT (TI)) NOTE: Washington County Building Services requires all commercial
More informationFirefighting operations on multi-tiered vehicle stacking buildings F5-13 GD
DESIGNER S GUIDE Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD Introduction When to use Scope Use this chapter to provide a consistent Fire and Emergency New Zealand position
More information