Practical problems of applying performance-based structural fire engineering in building design

Size: px
Start display at page:

Download "Practical problems of applying performance-based structural fire engineering in building design"

Transcription

1 Practical problems of applying performance-based structural fire engineering in building design Piotr Smardz INBEPO Sp. z o.o. ul. Domeyki 9a, Wrocław, Poland INTRODUCTION The introduction of structural Eurocodes, which form a comprehensive set of design codes covering various aspects of structural design including fire safety has made it easier for engineers in Europe to apply performance-based approach to this particular element of building design. The relevant parts of the Eurocodes cover the topic of thermal actions on structures exposed to fire as well as the mechanical response of the structure, as appropriate for the structural material in question. In many countries in Europe the design of building structures for fire resistance was until recently largely based on a prescriptive approach. Therefore the introduction of much more advanced and complex design methods requires not only changes in the regulations, but also a proper education process for both the designers as well as the approving authorities. The engineering literature available so far is usually limited to relatively simple examples, which are not applicable to reallife situations. Structural fire design often relies on complex design tools such as CFD models for assessing thermal conditions within the fire compartment and/or FEM models for heat transfer and mechanical response analysis. This makes it quite difficult for the approving authorities to verify the validity of the design approach adopted. One of the practical problems facing structural and fire safety engineers who are trying to implement a performance-based approach to structural fire design is the lack of commonly accepted design fires to be used as basis for the natural fire model. In this respect the Eurocodes provide only limited guidance. On the other hand the design fires which can be found in the literature and design standards relevant to smoke control design are not necessarily appropriate for structural fire engineering. Even for such a relatively standardized fire load array as an open car park there is no uniformly accepted design fire curve. The problem is further exacerbated by quick pace of change in the forms and materials used in building design, as well as in building content which may constitute the fire load think for example of the many changes that have occurred in the design of cars and other vehicles over the last twenty years. Unfortunately there is not enough publicly available fire test data which would allow an informed decision by the designer as regards selecting a reasonable design fire growth curve.

2 A similar situation exists as regards thermal properties for certain fire protection systems such as intumescent paints, for which there are no widely available data on proxy thermo-physical properties of the protective layer. The discussion in this paper is based predominantly on the experiences of the author on projects carried out in Poland, with some limited references to other European countries. However, it is believed that similar problems are experienced by fire safety engineers in other EU countries and indeed elsewhere in the world. DESIGN FIRES In order to carry out an analysis of thermal actions on structural elements exposed to fire, it is first necessary to select a design fire. The design fire defines the rate of heat release of the fire as a function of time. This is necessary as an input parameter for the advanced fire models (e.g. twozone or CFD models) which are used to predict temperature and thermal radiation levels in the vicinity of the structural element being examined. The design fire can either be described by a simple formulae (e.g. an t 2 fire) or by a set of discrete values of HRR vs. time, often presented graphically. In order to accurately describe the fire in the fire analysis, it is also necessary to describe the area involved, thus an assumption must be made as to the heat release rate of fire per unit area. The relevant part of Eurocode 1 [1] provides some guidance on fire growth rates only for a limited number of occupancy types including dwellings, hospitals, hotels, offices, school classrooms and shopping centres. A slightly more extensive set of values can be found in some National Annexes to EN (e.g. in the Irish NA to EN ). However, no data is provided for commonly encountered occupancies such as restaurants, sports halls, bus and train stations (platform areas) or car parks. In the absence of direct guidance from EN it is necessary to refer to other available guidance documents and technical papers. Data describing design fires for various occupancies can be found for example in technical literature and standards relating to the design of smoke control systems. However such data was often developed with consideration only for the initial stages of the fire (pre-flashover) when the occupants of the building evacuate, i.e. covering the first minutes of the fire. The question arises if such design fires can be safely used as input data for structural fire engineering purposes. The problem with design parameters which are not explicitly stated in one of the recognized national standards (such as in case of Poland - the PN EN standards) is that they are often held in less esteem by the approving authority. The design parameters sourced from European Norms (EN) which often also have the status of Polish Norms (PN) are perceived as official values and are therefore least questioned. This is clearly very superficial approach, as many of the coefficients and design parameters specified in the Eurocodes are a matter of fierce debate between the scientist and professionals involved in the field.

3 Open car parks Let us consider as an example the issue of design fires for multi-storey open-sided car parks. The required period of fire resistance for the elements of structure comprising such car parks varies between different European countries, from no specified fire resistance to 90 minutes FR. In many cases of such open car parks more economical design solutions can be achieved if the fire resistance of the structure is assessed with reference to the actual predicted thermal conditions in case of fire rather than the standard (ISO) curve which is representative of a fully developed fire in an enclosed compartment, with large amount of fuel present. For open sided car parks most available European publications refer to the design fires developed on the basis of real scale fire tests carried out in France in The results of those tests are publicly available in technical steel research reports published by the European Commission [2,3]. A design fire curve for a single medium-sized car (referred to as class 3) is presented in figure 1. Fig. 1 HRR curve of a single burning class 3 car [2] In a real car park configuration with many vehicles parked in a row it is assumed that fire spread to subsequent cars occurs at 12 minute intervals. The HRR curve for the subsequent cars is slightly different, due to the pre-heating of those cars. The peak HRR value is the same at 8,3 MW however the period of initial burning is shorter and more intense (see figure 2). For the purpose of design calculations it is assumed that the fire spreads to involve three, four or even five vehicles, depending on the configuration of the parked cars in relation to the structural element being analysed either a beam or a column. In this respect there is no uniformly-accepted set of scenarios which should be considered by the designer.

4 Fig. 2 HRR curves of three burning class 3 cars [2] Figure 3 shows a cumulative HRR curve for a design fire involving three cars, which was used by the author as input for the CFD analysis for four open multi-storey steel car parks recently designed and built in Poland. An example of one such car park is presented in picture 1. Due to the period of fire resistance required under Polish regulations for such a car park, the analysis covered the time period of 30 minutes. For this reason it was decided that a design fire involving three cars is sufficiently onerous, as during the time period considered in the analysis the burning of two cars has already reached its peak. Fig. 3 Cumulative HRR curve for a fire involving three class 3 cars

5 Pic. 1 Example of an open-sided car park in Poland designed on the basis of natural (localised) fire It must be stressed that in the absence of design data relating to open car parks in EN it is advisable to discuss the design fire adopted for the analysis with the authority which is ultimately approving the design (e.g. the fire brigade) prior to carrying out the calculations. One issue commonly raised in the discussions concerning design fires for car parks is whether design values based on fire tests conducted over 20 years ago are applicable to modern (or indeed future) cars which tend to have more combustible material in their construction. Furthermore, it is worth noting that in the recent proposals for the upgrade programme of the Eurocodes [4] the lack of up-to-date design data (i.e. a recommended design fire curve) for opensided car parks was identified as one of the obvious shortcoming of the current version of EN Other occupancies Another type of occupancy for which selecting a design fire for structural fire resistance calculations may prove problematic is a shopping centre with many individual retail units and a large common mall. Such premises are normally protected with a sprinkler system, so a fire within a retail unit will more than likely be a localized phenomenon and should not lead to a fully developed fire (post flash-over). A fire in a small kiosk or retail stand within the mall will also be a localized fire, even in the case of a mall / atrium with large floor-to-ceiling height where the sprinklers are unlikely to activate quickly or indeed where they may be omitted in the design. In the latter case the fire size (and hence its HRR) will be governed by the physical size of the stand, which will normally be quite small relative to the overall volume of the mall. Removal of heat will be further

6 enhanced by a Smoke and Heat Exhaust Ventilation System (SHEVS), which is normally provided in a shopping mall. In the circumstances described above the analysis of thermal actions on structural elements (either for the main loadbearing elements or the roof) will in most cases focus on the effects of a localized fire either using as simplified model described in annex C of EN or using an advanced CFD model. Annex E of provides some guidance as to the characteristics of the fire growth rate and the rate of heat release per unit floor area (RHR f ) for retail premises. The suggested value of RHR f =250 kw/m 2 for shopping centres seems to be relatively low, which would be conservative for smoke control calculations (i.e. it would result in a larger fire perimeter for a given heat output). However, it may not necessarily be conservative for structural fire resistance calculations, as it would result in lower flame heights and hence lower temperatures above the fire. In the background paper to the UK national Annex to EN [5] the rate of heat release rate per unit area suggested for a more general occupancy category shops is 550 kw/m 2. The same value is given for shops in the Irish National Annex to EN Pic. 2 Results of CFD analysis carried out to estimate temperature in the vicinity of roof elements in a railway station The shortage of design fire data in EN is not limited to car parks or retail premises. Other examples encountered by the author include transportation hubs (i.e. bus terminals, railway stations) as well as industrial sites (e.g. a large roof structure over bulk storage of coal). INFLUCENCE OF VENTILATION CONDITIONS In any analysis of thermal actions on structural elements which is based either on simplified or advanced model, one of the most important input parameters is the amount of available ventilation. Breakage of glass in the windows or glazed facade of the building will on the one hand allow inflow of fresh air to sustain combustion, but on the other if sufficient amount of openings is created will allow effective dissipation of heat and hence lower temperatures within the fire compartment.

7 For calculations based on parametric temperature-time curves (annex A of EN ) or estimations based on the equivalent time of fire exposure (annex F of EN ) the code sets minimum and maximum limits for the amount of openings in the façade which can be taken into account, relative to the floor area of the compartment. However, it does not provide any guidance on the percentage of glazing that can be assumed to break and fall out during a fire. The same problem exists where the analysis is carried out using an advanced model such as a two-zone model or a CDF model. With the current high requirements for energy conservation it is typical that double and triple glazing systems are used in commercial buildings. An assumption that 100% of such glazing will be destroyed during a fire is clearly unrealistic, although EN seems to suggest that this is the case, as it simply refers to the area of windows. Assuming unrealistically high areas of ventilation openings during a fire can in most cases lead to un-safe results - either in terms of the temperature curve or the estimated equivalent time of fire exposure. Some guidance on maximum percentages of glazing which can be realistically assumed to fail under high temperature caused by a fire can be found in design recommendations and standards published by member-states of the EU. A guidance document published in 2012 in Luxemburg [6] generally relates the amount of failed glazing with the temperature reached within the compartment. It suggests two scenarios to consider: Scenario 1 is for 90% of the glazing area to be open since the beginning of the fire Scenario 2 sets the following percentages of failed glazing for various glazing types: Simple glazing: 50% open at 100 o C and 90% open at 250 o C Double glazing: 50% open at 200 o C and 90% open at 400 o C Triple glazing: 50% open at 300 o C and 90% open at 500 o C Another document with recommendations on maximum areas of glazing which can be taken into account as ventilation openings for heat in a fire situation is German standard DIN [7]. This document relates the maximum percentage of glazing which can be assumed to fail to the expected duration of the fire. For single glazing up to 80% can be assumed to fail during the first 15 minutes and up to 100% if the time exceeds 30 minutes. For double glazing the values are 35%, 50% and 100% for time intervals of 15 min, 30 min and above 30 min respectively. SUMMARY The Eurocodes are a comprehensive set of standards for structural design. They provide a far more detailed guidance as regards the behaviour of structures under fire conditions, than was previously provided in the National Standards of the individual member states (except maybe for those with long tradition in applying performance-based fire safety solutions such as the UK).

8 However - as was discussed in this paper - a designer undertaking fire engineering analysis with the scope of establishing thermal actions on structural elements may find that the Eurocodes do not yet provide a complete guidance on the various aspects of analysis which needs to be carried out. Based on the limited information available in the public domain it can be assumed that work has just commenced on a comprehensive update program of the European structural design codes, with the view of completing the process by The aim is to simplify the Eurocodes so as to enhance their use, reduce the number of Nationally Determined Parameters (NDPs) and also to provide new guidance and design methods where necessary. All the above goals are to be applauded. It is not known however if the second generation of Eurocodes will include new information on issues discussed earlier in this paper i.e. design fires or destruction of window glazing at high temperatures (in the context of its influence on ventilation conditions within fire compartment). REFERENCES 1. EN :2002 Eurocode 1 Actions on structures. Actions on structures exposed to fire 2. Joyeux D., Kruppa J., Cajot L., Schleich J., de Leur P., Twilt L., Demonstration of real fire tests in car parks and high buildings, European Commission, Final report, Schleich, J.B., Cajot, L.G., Franssen, J.M., Kruppa, J., Joyeux, D., Twilt, L., Van Oerle, J., Aurtenetxe, G. Development of design rules for steel structures subjected to natural fires in closed car parks, CEC Agreement 7210-SA/211/318/518/620/933, Final report Wald F., Burgess I., Outinen J., Vila Real P., Horova K., Fire Eurocodes The Future?, COST Action TU 0904, CTU Publishing House, PD :2007 Background paper to the UK National Annex to BS EN , BSI 6. ITM-SST Etude de stabilité au feu à l aide d une approche performancielle, DIN : Baulicher Brandschutz im Industriebau - Teil 1: Rechnerisch erforderliche Feuerwiderstandsdauer (Structural fire protection in industrial buildings - Part 1: Analytically required fire resistance time)

Research on fire protection methods and a case study "Futurum"

Research on fire protection methods and a case study Futurum Available online at www.sciencedirect.com Procedia Engineering 40 (2012 ) 339 344 Steel Structures and Bridges 2012 Research on fire protection methods and a case study "Futurum" J. Outinen a *, J. Samec

More information

Fire Resistance - Implications for regulations and standards of the September 11th terrorist attacks on the world trade centre Tom Lennon, FRS, BRE

Fire Resistance - Implications for regulations and standards of the September 11th terrorist attacks on the world trade centre Tom Lennon, FRS, BRE Fire Resistance - Implications for regulations and standards of the September 11th terrorist attacks on the world trade centre Tom Lennon, FRS, BRE Malaysia May 2003 Questions What is fire resistance?

More information

CHANCES AND LIMITS OF THE TIME-EQUIVALENCE-METHOD IN STRUCTURAL FIRE DESIGN

CHANCES AND LIMITS OF THE TIME-EQUIVALENCE-METHOD IN STRUCTURAL FIRE DESIGN CHANCES AND LIMITS OF THE TIME-EQUIVALENCE-METHOD IN STRUCTURAL FIRE DESIGN ABSTRACT P. Schaumann and S. Hothan University of Hannover, Institute for Steel Construction Appelstraße 9a, D-3167 Hannover,

More information

DS/EN DK NA:2011

DS/EN DK NA:2011 National Annex to Eurocode 1: Actions on structures - Part 1-2: General actions Actions on structures exposed to fire Foreword This national annex (NA) is a revision of EN 1991-1-2 DK NA:2008 and entered

More information

Case Study 1 Underground Car Park

Case Study 1 Underground Car Park Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building

More information

This document is a preview generated by EVS

This document is a preview generated by EVS TECHNICAL REPORT ISO/TR 15657 First edition 2013-06-15 Fire resistance tests Guidelines for computational structural fire design Essais de résistance au feu Lignes directrices sur la conception statistique

More information

Fire Severity for Structural Design

Fire Severity for Structural Design Fire Severity for Structural Design A UK Perspective Susan Deeny, PhD 2 Broadgate Phase 8 3 5 Shaping a better world Experience of working in Abu Dhabi 6 UAE 7 Fire Severity for Structural Analysis Building

More information

PART 1 THERMAL & MECHANICAL ACTIONS. DIF SEK Part 1: Thermal & Mechanical Actions 0/ 50

PART 1 THERMAL & MECHANICAL ACTIONS. DIF SEK Part 1: Thermal & Mechanical Actions 0/ 50 DIF SEK PART 1 THERMAL & MECHANICAL ACTIONS DIF SEK Part 1: Thermal & Mechanical Actions 0/ 50 Background of the RFCS Project DIFISEK+ This project is funded by the European Commission in the frame of

More information

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015?

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015? Plumis White Paper April 2017 How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015? As with the introduction of every new formal product category through

More information

COMPARISON OF CFD MODELLING WITH FIRE TESTS Comparison of CFD Modelling with Results of Full Scale Compartment Fire Tests in a Residential Unit

COMPARISON OF CFD MODELLING WITH FIRE TESTS Comparison of CFD Modelling with Results of Full Scale Compartment Fire Tests in a Residential Unit Application of Structural Fire Engineering, 19-20 April 2013, Prague, Czech Republic COMPARISON OF CFD MODELLING WITH FIRE TESTS Comparison of CFD Modelling with Results of Full Scale Compartment Fire

More information

Considerations in the Design of Smoke Management Systems for Atriums

Considerations in the Design of Smoke Management Systems for Atriums Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke

More information

Are we using the wrong design fires for tall building fire strategies, in light of recent full height fires?

Are we using the wrong design fires for tall building fire strategies, in light of recent full height fires? Are we using the wrong design fires for tall building fire strategies, in light of recent full height fires? Tall Building Fire Safety Network meeting & seminar FIREX, London, 22 nd June 2016 Eoin O Loughlin

More information

Effectiveness of sprinklers in residential premises:

Effectiveness of sprinklers in residential premises: Effectiveness of sprinklers in residential premises: Section 7: Other considerations and Recommendations for further work Project report number 204505 Dr Corinne Williams and Dr Jeremy Fraser-Mitchell

More information

PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT

PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT DAVID CHARTERS DEAN MCGRAIL Arup Fire, 78 East Street, Leeds, LS9

More information

Current Research at University of Naples

Current Research at University of Naples TRAINING SCHOOL, June 6-9 213, Naples Current Research at University of Naples Structural behaviour of composite steel-concrete buildings in fire Simplified fire design methods for steel-concrete composite

More information

Loss Prevention Standards

Loss Prevention Standards Introduction Fire compartmentation is an essential part of an effective fire safety design of a building. The primary objective of fire compartmentation or passive fire protection is to prevent a building

More information

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING

More information

Seminar on Standardisation in Research and Innovation Practical tools for the dissemination and implementation of research results

Seminar on Standardisation in Research and Innovation Practical tools for the dissemination and implementation of research results Seminar on Standardisation in Research and Innovation Practical tools for the dissemination and implementation of research results Brussels - 10 th November 2011 - Louis-Guy CAJOT DIFISEK & DIFISEK + DIssemination

More information

Fire Engineering in the UK

Fire Engineering in the UK COST Action C26 Urban Habitat Constructions Under Catastrophic Events Malta, 23-25 October 2008 Fire Engineering in the UK A Fire Officer s Perspective Steve Beckley Chief Fire Officers Association and

More information

SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE

SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE - 249 - SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE Urs Welte Amstein + Walthert AG, Switzerland ABSTRACT The paper aims at a detailed analysis of the current know-how in the construction of tunnel cabling

More information

technical specification smoke venting systems

technical specification smoke venting systems technical specification smoke venting systems An Introduction to FDS FDS sets the standards the rest of the industry follows Providing a complete service for all of your smoke ventilation system needs.

More information

The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD

The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD BFS 2011:27 with amendments up to BFS 2013:12 The

More information

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM , Volume 11, Number 2, p.43-48, 2012 NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM Q. Kui Institute of Building Fire Research, China Academy of Building Research, Beijing,

More information

Test One: The Uncontrolled Compartment Fire

Test One: The Uncontrolled Compartment Fire The University of Edinburgh BRE Centre for Fire Safety Engineering One Day Symposium on The Dalmarnock Fire Tests: Experiments & Modelling Test One: The Uncontrolled Compartment Fire Cecilia Abecassis

More information

Copy of article submitted to Fire Safety Engineering for publication January/February 2009

Copy of article submitted to Fire Safety Engineering for publication January/February 2009 Copy of article submitted to Fire Safety Engineering for publication January/February 2009 Metal faced sandwich panels with plastic foam cores - a challenge to fire safety by Gordon Cooke Confusion, misleading

More information

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION - 165 - CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT

More information

Case Study 1 Underground car park

Case Study 1 Underground car park Case Study 1 Underground car park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, INBEPO Wroclaw, Poland 1. Introduction

More information

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada

More information

General Principles of Smoke Control

General Principles of Smoke Control AMCA International General Principles of Smoke Control Patrick Janssens, Sales Manager Colt International www.coltinco.co.uk or www.coltinfo.be Air System Engineering & Technology (ASET) Conference Europe

More information

WG 1: Fire Engineering V. Strategy and guidelines for damage prevention Fire design in Europe

WG 1: Fire Engineering V. Strategy and guidelines for damage prevention Fire design in Europe WG 1: Fire Engineering V. Strategy and guidelines for damage prevention Fire design in Europe Tampere University of Technology, Finland Cost C26 Conference 1 Contents of the presentation: In what extent

More information

Technical reference Reference & design

Technical reference Reference & design The requirement for emergency lighting originates from the Fire Precautions Act 1971 and was further enforced by the Fire Precautions (Workplace) Regulations 1997 (Amended 1999). The Regulatory Reform

More information

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER , Volume 9, Number 1, p.38-58, 2007 ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER C.W. Leung and W.K. Chow Department of Building Services Engineering, The Hong Kong

More information

Fact File 75. Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems

Fact File 75. Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems Fact File 75 Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems INTRODUCTION... 3 BACKGROUND...

More information

THERMAL EFFECT OF A LOCALIZED FIRE IN THE STEEL STRUCTURE OF AN OPEN CAR PARK

THERMAL EFFECT OF A LOCALIZED FIRE IN THE STEEL STRUCTURE OF AN OPEN CAR PARK Proceedings IRF2018: 6th International Conference Integrity-Reliability-Failure Lisbon/Portugal 22-26 July 2018. Editors J.F. Silva Gomes and S.A. Meguid Publ. INEGI/FEUP (2018); ISBN: 978-989-20-8313-1

More information

FAÇADE FIRE TESTS Towards a new European standard method

FAÇADE FIRE TESTS Towards a new European standard method FAÇADE FIRE TESTS Towards a new European standard method Lars Boström November 22, 2017 RISE Research Institutes of Sweden Safety Content Current state in Europe regarding façade fire tests History on

More information

ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC)

ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC) ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC) P. Van Hees and J. Axelsson, SP Sweden, S. J. Grayson and A. M. Green, Interscience Communications UK, H Breulet, ISSeP Belgium and U Vercellotti,

More information

ISO/TR TECHNICAL REPORT. Reaction-to-fire tests Full-scale room tests for surface products Part 2: Technical background and guidance

ISO/TR TECHNICAL REPORT. Reaction-to-fire tests Full-scale room tests for surface products Part 2: Technical background and guidance TECHNICAL REPORT ISO/TR 9705-2 First edition 2001-05-01 Reaction-to-fire tests Full-scale room tests for surface products Part 2: Technical background and guidance Essais de réaction au feu Essais dans

More information

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING Rebeca Barbosa 1, Martin Barták 1, Jan L. M. Hensen 1, 2, Marcel G. L. C. Loomans 2 1 Czech Technical

More information

Development of a European approach to assess the fire performance of facades

Development of a European approach to assess the fire performance of facades Development of a European approach to assess the fire performance of facades This presentation was made in Brussels on December 8, 2017, for EC, AGF and stakeholders Lars Boström, Roman Chiva, Anja Hofmann-Böllinghaus,

More information

Safety distance between waste containers and buildings. CFPA-E Guideline No 7:2011 F

Safety distance between waste containers and buildings. CFPA-E Guideline No 7:2011 F Safety distance between waste containers and buildings CFPA-E Guideline No 7:2011 F FOREWORD The European fire protection associations have decided to produce common guidelines in order to achieve similar

More information

ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER

ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER , Volume 6, Number 3, p.122-154, 2004 ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER C.W. Leung, W.K. Chow Department of Building Services Engineering, The Hong Kong

More information

Smoke control in car parks

Smoke control in car parks Smoke control in car parks The actual situation in CEN TC 191 SC1 WG9 Imagine the result Jean-Claude DE SMEDT MIFireE,MSFPE,MNFPA Senior Fire Safety Engineering Consultant @ ARCADIS Belgium Convener of

More information

9 Standards, Regulations and Authorities

9 Standards, Regulations and Authorities 9 9.1 Summary...283 9.2 Basics...284 9.3 Standards and how to Secure Adherence to Standards...285 9.3.1 Types of Standards...285 9.3.2 Hierarchy of Standards...285 9.3.3 Proof...286 9.3.4 Overview of the

More information

Fire protection documentation. CFPA-E Guideline No 13:2015 F

Fire protection documentation. CFPA-E Guideline No 13:2015 F Fire protection documentation CFPA-E Guideline No 13:2015 F FOREWORD The European fire protection associations have decided to produce common guidelines in order to achieve similar interpretation in the

More information

Fire safety engineering applied to high-rise building facades

Fire safety engineering applied to high-rise building facades MATEC Web of Conferences 46, 04002 (2016) DOI: 10.1051/matecconf/20164604002 C Owned by the authors, published by EDP Sciences, 2016 Fire safety engineering applied to high-rise building facades Samuele

More information

Guideline No 7:2005. European Guideline. Safety distances between waste containers and buildings. CFPA-E -Guidelines

Guideline No 7:2005. European Guideline. Safety distances between waste containers and buildings. CFPA-E -Guidelines Guideline No 7:2005 European Guideline Safety distances between waste containers and buildings CFPA-E -Guidelines Guideline No 7:2005 FOREWORD The European fire protection associations have decided to

More information

Unit 2 Fire Safety (Zone 2)

Unit 2 Fire Safety (Zone 2) IFE Level 3 Diploma in Fire Safety and Fire Science Unit 2 Fire Safety (Zone 2) Examiner Report March 2017 Introduction 21% of the candidates that sat the examination attained a pass. Candidates did not

More information

FIRE RESISTANCE LEVEL ASSESSMENTS AND DEVELOPMENT OF APPROPRIATE INPUT DATA

FIRE RESISTANCE LEVEL ASSESSMENTS AND DEVELOPMENT OF APPROPRIATE INPUT DATA FIRE RESISTANCE LEVEL ASSESSMENTS AND DEVELOPMENT OF APPROPRIATE INPUT DATA Andrew Barnett Fire Safety Engineer Scientific Fire Services Pty Ltd INTRODUCTION Co-authors: Mahmut Horasan, Scientific Fire

More information

Case Study 2 Production and Storage. SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB)

Case Study 2 Production and Storage. SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB) Case Study 2 Production and Storage SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB) So What Are You We Going to Show You? A lot of tables, simplified methods

More information

Guideline No 11:2005. European guideline. Recommended Numbers of Fire Protection Trained Staff

Guideline No 11:2005. European guideline. Recommended Numbers of Fire Protection Trained Staff European guideline Recommended Numbers of Fire Protection Trained Staff EFSAC Endorsed CFPA-E -Guidelines Foreword The European fire protection associations have decided to produce common guidelines in

More information

Eurocode 9 Design of aluminium structures

Eurocode 9 Design of aluminium structures BRITISH STANDARD Eurocode 9 Design of aluminium structures BS EN 1999-1-2:2007 Incorporating corrigenda December 2008, March 2009 and October 2009 Part 1-2: Structural fire design ICS 91.010.30; 91.080.10;

More information

Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel

Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel Safety and Security Engineering VI 73 Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel M. Lombardi & G. Rossi Dipartimento di Ingegneria Chimica

More information

On Estimating Heat Release Rate for a Design Fire in Sprinkler Protected Area

On Estimating Heat Release Rate for a Design Fire in Sprinkler Protected Area 2005 Asia-Pacific Conference on Risk Management and Safety 1-22 December 2005, Hong Kong On Estimating Heat Release Rate for a Design Fire in Sprinkler Protected Area 20 min Presentation Professor W.K.

More information

Travelling Fires for CFD

Travelling Fires for CFD Travelling Fires for CFD JOAKIM SANDSTRÖM 1,2, XUDONG CHENG 1, MILAN VELJKOVIC 1, ULF WICKSTRÖM 1,3, and TIM HEISTERMANN 1 1 Department of Civil, Mining and Environmental Engineering Luleå University of

More information

Fixed fire protection solutions

Fixed fire protection solutions Risk Engineering Fixed fire protection solutions At a glance Fixed fire protection can reduce the severity of fire events and positively impact Risk Engineering Assessments. To provide an effective solution

More information

A Priori Modelling of Fire Test One

A Priori Modelling of Fire Test One A Priori Modelling of Fire Test One Authorship: Brave Users Guillermo Rein, José L. Torero, Wolfram Jahn, Jamie Stern-Gottfried, Noah L. Ryder, Sylvain Desanghere, Mariano Lázaro, Frederick Mowrer, Andrew

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60079-29-2 Edition 2.0 2015-03 Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen INTERNATIONAL

More information

Technical Seminar on the Code of Practice for Fire Safety in Buildings 2011

Technical Seminar on the Code of Practice for Fire Safety in Buildings 2011 Technical Seminar on the Code of Practice for Fire Safety in Buildings 2011 The Code of Practice for Fire Safety in Buildings 2011 The FS Code comprises 7 parts and 1 annex: Part A Introduction Part B

More information

Fire resistance design in Europe

Fire resistance design in Europe Fire resistance design in Europe Tampere University of Technology, Tampere, Finland 1 Description Europa has started to use Eurocodes EN standards include principal and application rules for fire design

More information

1.1. Design fires for structural engineering

1.1. Design fires for structural engineering 1.1. Design fires for structural engineering M. Gillie School of Engineering, University of Edinburgh, Edinburgh, UK F. Wald & K. Horová Czech Technical University in Prague, Czech Republic 1.1.1 THE NATURE

More information

BUSINESS PLAN CEN/TC 250 STRUCTURAL EUROCODES EXECUTIVE SUMMARY

BUSINESS PLAN CEN/TC 250 STRUCTURAL EUROCODES EXECUTIVE SUMMARY Page: 1 BUSINESS PLAN CEN/TC 250 STRUCTURAL EUROCODES EXECUTIVE SUMMARY Scope CEN/TC 250 covers the standardization of structural and geotechnical design rules for building and civil engineering works

More information

2C10 Design for Fire and Robustness Timisoara,

2C10 Design for Fire and Robustness Timisoara, 2C10 Design for Fire and Robustness Timisoara, 31.03-11.04.2014 European Erasmus Mundus Master Course Sustainable Constructions under Natural Hazards and Catastrophic Events 520121-1-2011-1-CZ-ERA MUNDUS-EMMC

More information

CEN standardization work on refrigerating systems, especially standard EN 378

CEN standardization work on refrigerating systems, especially standard EN 378 CEN standardization work on refrigerating systems, especially standard EN 378 Carsten Hoch Head of Refrigeration TÜV SÜD Industrie Service GmbH Ridlerstrasse 65, 80339 Munich carsten.hoch@tuev-sued.de

More information

ISO/TR TECHNICAL REPORT. Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people

ISO/TR TECHNICAL REPORT. Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people TECHNICAL REPORT ISO/TR 16738 First edition 2009-08-01 Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people Ingénierie de la sécurité incendie Informations

More information

Crossrail Project. Infrastructure design and construction Volume 5. Edited by Professor Rhys Vaughan Williams and Mike Black

Crossrail Project. Infrastructure design and construction Volume 5. Edited by Professor Rhys Vaughan Williams and Mike Black Crossrail Project Infrastructure design and construction Volume 5 Edited by Professor Rhys Vaughan Williams and Mike Black Crossrail Project: Infrastructure design and construction Volume 5 Williams and

More information

COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS

COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS , Volume 1, Number 3, p.123-128, 1999 COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS D. Yung and G.V. Hadjisophocleous Fire Risk Management Program, Institute for Research

More information

Fire Safety Fire Resistant Building Components

Fire Safety Fire Resistant Building Components Fire Safety Fire Resistant Building Components NBN 713-020 1968 Fire fighting - Fire performance of building materials and products - Fire resistance of building materials NBN 713-020/A1 1982 Protection

More information

The Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex:

The Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex: The Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex: Mr. Junkers Lam Senior Building Surveyor of Buildings Department (9 Sept 2013) Part A Introduction Part B Means

More information

Design of Fire safety in Multi Occupancy Residential Accommodation

Design of Fire safety in Multi Occupancy Residential Accommodation Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability

More information

Legal Requirements. There is no general legal requirement to install sprinklers. in places of work

Legal Requirements. There is no general legal requirement to install sprinklers. in places of work 01 A sprinkler system is a pipework distribution system charged with water, with a network of heatsensitive sprinkler heads supplied via a tank/reservoir or a water main. If the temperature rises above

More information

Development of Seismic-induced Fire Risk Assessment Method for a Building

Development of Seismic-induced Fire Risk Assessment Method for a Building Development of Seismic-induced Fire Risk Assessment Method for a Building AI SEKIZAWA National Research Institute of Fire and Disaster 3-14-1, Nakahara, Mitaka, Tokyo 181-8633, Japan sekizawa@fri.go.jp

More information

Additional Requirements for Watermist Systems Protecting High-rise Buildings

Additional Requirements for Watermist Systems Protecting High-rise Buildings Guidance Note Additional Requirements for Watermist Systems Protecting High-rise Buildings Additional Requirements for Watermist Systems Protecting High-rise Buildings SCOPE... 3 DESIGN PARAMETERS... 3

More information

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES FIRE PROTECTIO FOR O-STORAGE OCCUPACIES WITH HIGH CEILIG CLEARACES SOOIL AM, ATOIO BRAGA, HSIAG-CHEG KUG, and JOA M. A. TROUP FM Global Research, 1151 Boston-Providence Turnpike, orwood, Massachusetts

More information

incorporating Contractors guide to car park ventilation A no-nonsense guide to the safe ventilation of underground and covered car parks

incorporating Contractors guide to car park ventilation A no-nonsense guide to the safe ventilation of underground and covered car parks incorporating Contractors guide to car park ventilation A no-nonsense guide to the safe ventilation of underground and covered car parks Car park ventilation What are the regulations? Ventilation of car

More information

FRAM-ini A qualitative fire risk assessment method FRAME Erik De Smet

FRAM-ini A qualitative fire risk assessment method FRAME Erik De Smet FRAM-ini A qualitative fire risk assessment method 13-3-2014 FRAME Erik De Smet FRAM-ini: A qualitative fire risk assessment method FRAM-ini: A qualitative fire risk assessment method... 1 Introduction....

More information

A fire safe future? Eindhoven University of technology: Fellow Fire Safety Engineering (Dept. Built Environment Unit BPS)

A fire safe future? Eindhoven University of technology: Fellow Fire Safety Engineering (Dept. Built Environment Unit BPS) A fire safe future? Influence of changing boundary conditions on the fire safety of buildings Ir. Ruud van Herpen MSc. FIFireE Ruud van Herpen Eindhoven University of technology: Fellow Fire Safety Engineering

More information

CFD Analysis of Fire Characteristics on Subway Junction Station

CFD Analysis of Fire Characteristics on Subway Junction Station ISGSR27 First International Symposium on Geotechnical Safety & Risk Oct. 18~19, 27 Shanghai Tongji University, China CFD Analysis of Fire Characteristics on Subway Junction Station G. H. Wu, X. Han, Q.Q.

More information

Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen

Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen IEC 60079-29-2 Edition 2.0 2015-03 REDLINE VERSION colour inside Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen

More information

How design fires can be used in fire hazard analysis

How design fires can be used in fire hazard analysis How design fires can be used in fire hazard analysis Yung, D.T.; Bénichou, N. NRCC-44511 A version of this document is published in / Une version de ce document se trouve dans : Fire Technology, v. 38,

More information

International Standards and their relevance to the Modern Built Environment

International Standards and their relevance to the Modern Built Environment International Standards and their relevance to the Modern Built Environment PROF. PATRICK VAN HEES, LUND UNIVERSITY, SWEDEN, CHAIR ISO TC92 FIRE SAFETY Overview TC 92 History of fire safety and Trends

More information

Schueco Fire and Smoke Protection Systems

Schueco Fire and Smoke Protection Systems Schueco Fire and Smoke Protection Systems Green Technology for the Blue Planet Clean Energy from Solar and Windows 02 Schueco Fire and Smoke Protection Systems Fire and Smoke Protection Systems Schueco

More information

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Fire Science and Technorogy Vol.24 No.4(2005) 165-178 165 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Jun-ichi Yamaguchi 1, Takeyoshi Tanaka 2 1 Technical Research

More information

Foundations of Fire Safety in Civil Engineering

Foundations of Fire Safety in Civil Engineering Foundations of Fire Safety in Civil Engineering Dan Diaconu-Şotropa Universitatea Tehnică Gh. Asachi din Iaşi Editura POLITEHNIUM Universitatea Tehnică Gh. Asachi din Iaşi 2014 i DE INTRODUS CIP ii FOREWORD

More information

Guideline No 6:2004. European Guideline. Fire safety in residential homes for the elderly. CFPA-E -Guidelines

Guideline No 6:2004. European Guideline. Fire safety in residential homes for the elderly. CFPA-E -Guidelines Guideline No 6:2004 European Guideline Fire safety in residential homes for the elderly CFPA-E -Guidelines Guideline No 6:2004 FOREWORD The European fire protection associations have decided to produce

More information

Appendix A: US Fire Statistics Tables

Appendix A: US Fire Statistics Tables Appendix A: US Fire Statistics Tables The following US fire statistics have been provided by Marty Ahrens and John R. Hall Jr. of the Fire Analysis and Research Division, National Fire Protection Association.

More information

2015 SFPE Europe Conference on Fire Safety Engineering

2015 SFPE Europe Conference on Fire Safety Engineering 2015 SFPE Europe Conference on Fire Safety Engineering THE FSE APPROACH FOR A HISTORICAL BUILDING IN LIGHT OF THE ITALIAN STANDARDS. Simonetto Sacco Luciano Nigro HUGHES ASSOCIATES EUROPE, srl FIRE SCIENCE

More information

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL? CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL? Marcelo M. Hirschler GBH International, USA ABSTRACT The results of three

More information

Sprinklers Modeling for Tunnel Road Fire Fighting

Sprinklers Modeling for Tunnel Road Fire Fighting Sprinklers Modeling for Tunnel Road Fire Fighting P. Ciambelli, M.G. Meo, P. Russo, S. Vaccaro Department of Chemical and Food Engineering, University of Salerno - ITALY 1. INTRODUCTION Loss of lives and

More information

Secretary of State determination under article 36 of the Fire Safety Order

Secretary of State determination under article 36 of the Fire Safety Order Fire and Rescue Service Circular Circular number 48/2009 Date issued 13 August 2009 This circular is For information and consideration Status This circular covers the outcome of a referral to the Secretary

More information

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles Peter Stahl Wagner Schweiz AG, Wallisellen, Switzerland Abstract Fire detection system and firefighting solutions are getting a

More information

DESCRIBING TRENDS IN URBAN DESIGN. Claire Jamieson and Professor Robert Adam for ADAM Urbanism

DESCRIBING TRENDS IN URBAN DESIGN. Claire Jamieson and Professor Robert Adam for ADAM Urbanism DESCRIBING TRENDS IN URBAN DESIGN Claire Jamieson and Professor Robert Adam for Urban design, in common with all other design disciplines, is a constantly evolving phenomenon. Developments in the discipline,

More information

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL / SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 60202 fpeschulte@aol.com 504/220-7475 A CRITIQUE OF HUGHES ASSOCIATES, INC. PAPER TITLED: Analysis of the Performance of Ganged

More information

Shipboard incinerators with capacities up to 4000 kw

Shipboard incinerators with capacities up to 4000 kw STANDARD FOR CERTIFICATION No. 2.9 Approval Programmes Type Approval Programmes for Marine Equipment Directive (MED) No. 431.90 - MED A.1/2.7 Shipboard incinerators with capacities up to 4000 kw JANUARY

More information

Cladding Screening Test Result

Cladding Screening Test Result Cladding Screening Test Result Submitting body Building address L&Q, One Kings Hall Mews, SE13 5JQ Flats 1-18, Burnell House, E20 1GY Organisation type: Contact details for test result Location of where

More information

Belcom Cable excellence engineered through quality. CPR Construction Products Regulation

Belcom Cable excellence engineered through quality. CPR Construction Products Regulation CPR Construction Products Regulation Index Construction Products Regulation... 3 What is the Construction Products Regulation (CPR)... 4 What is the objective of the CPR... 4 Who does the application of

More information

Experimental Room Fire Studies with Perforated Suspended Ceiling

Experimental Room Fire Studies with Perforated Suspended Ceiling Experimental Room Fire Studies with Perforated Suspended Ceiling FIONA S.C. TSUI 1, W.K. CHOW 1, N.K. FONG 1, Y. GAO 2, H. DONG 2, and G.W. ZOU 2 1 Research Centre for Fire Engineering Department of Building

More information

Fire Scenario Influence of Material of Boundary Condition on Results

Fire Scenario Influence of Material of Boundary Condition on Results Fire Scenario Influence of Material of Boundary Condition on Results HUGHES ASSOCIATES EUROPE, srl FIRE SCIENCE & ENGINEERING Luciano Nigro Andrea Ferrari Elisabetta Filippo Hughes Associates Europe srl

More information

Eurocode 2 - Design of concrete structures - Part 3: Liquid retaining and containment structures

Eurocode 2 - Design of concrete structures - Part 3: Liquid retaining and containment structures Irish Standard I.S. EN 1992-3:2006 Eurocode 2 - Design of concrete structures - Part 3: Liquid retaining and containment structures NSAI 2006 No copying without NSAI permission except as permitted by copyright

More information

Study and Design Considerations of HRSG Evaporators in Fast Start Combined Cycle Plants. Govind Rengarajan, P.E.CEM, Dan Taylor

Study and Design Considerations of HRSG Evaporators in Fast Start Combined Cycle Plants. Govind Rengarajan, P.E.CEM, Dan Taylor Study and Design Considerations of HRSG Evaporators in Fast Start Combined Cycle Plants Govind Rengarajan, P.E.CEM, Dan Taylor CMI Energy, Erie PA 1651 Bernd Pankow P.E, Pankow Engineering Abstract Combined

More information

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,

More information