On Estimating Heat Release Rate for a Design Fire in Sprinkler Protected Area

Size: px
Start display at page:

Download "On Estimating Heat Release Rate for a Design Fire in Sprinkler Protected Area"

Transcription

1 2005 Asia-Pacific Conference on Risk Management and Safety 1-22 December 2005, Hong Kong On Estimating Heat Release Rate for a Design Fire in Sprinkler Protected Area 20 min Presentation Professor W.K. Chow Areas of Strength: Fire Safety Engineering Research Centre for Fire Engineering The Hong Kong Polytechnic University Hong Kong, China HKARMS3.ppt

2 In implementing engineering approach for fire safety design (in fact performance-based design) in Hong Kong, heat release rate for a design fire has to be estimated. Results are then applied to determine the fire safety provisions. For example, design fire is a key factor in sizing the dynamic smoke exhaust systems. Much higher exhaust rates are required for high heat release rates. 2

3 For areas protected by sprinkler, the sprinkler activation time is deduced from a thermal balance equation based on the ceiling jet equation. The heat release rate is commonly determined from some reported functions such as the NFPA t 2 -fire, by assuming that the fire can be controlled at a certain value. 3

4 Sprinkler heads 4

5 Operation Mechanism of Sprinkler Head Temperature rating 68 o C The sprinkler was heated by a gas fire The bulb exploded after 15 sec Sprinkler head after the thermal sensing element exploded 5

6 Sprinkler head Cooling the smoke layer Ceiling jet Water spray Displacement of oxygen Smoke layer Cooling the fuel Fire source Prewetting to prevent fire spread 6

7 Direct Cooling 7

8 However, activating the sprinkler system might not necessarily control the fire at that instance. The fire would still be burning to give much higher heat release rates. Note that a low fire load density might give high release rates, depending on the ventilation provision. There might be problems in deciding the time at which the fire can be controlled. This point will be discussed in this paper. Data measured from full-scale burning tests on fires with and without sprinkler are used to support the argument. Fire hazard assessment on the risk impact will also be discussed. 8

9 Topics to cover in this talk Performance-Based Design Importance of Heat Release Rate Extinguishment, Suppression and Control Estimation of Heat Release Rate Full-scale Burning Tests Importance on Hazard Assessment Conclusion 9

10 1. Performance-Based Design Local approval of fire safety designs and inspection of buildings upon completion are held responsible by the Buildings Department (BD) and Fire Services Department (FSD). Normally, the building design shall be submitted to BD for checking against all fire aspects for approval; and the requirements and installation of fire protection system shall be determined by FSD. The prescriptive codes are basically on passive construction checked by BD on the fire resistance construction (FRC), means of escape (MoE) for occupants, means of access (MoA) for firefighting, and active firefighting systems or called fire services installation (FSI) checked by FSD. 10

11 The prescriptive codes, basically on BS5588? MoE Codes MoA Codes FRC Codes FSI Codes may not be sufficient for providing fire safety in some buildings with special designs. 11

12 These codes are demonstrated to work for traditional buildings, such as those of height up to 40 levels. However, they may not be sufficient for providing fire safety in some buildings with special designs. Supertall buildings are obvious examples in having total evacuation time longer than half an hour even in using lifts for escape. 12

13 How can those codes apply to ultra highrise building? Might be OK for these! 13

14 There are no engineering performance-based fire codes (EPBFC) in Hong Kong yet. Fire engineering approach FEA for passive fire safety designs is accepted by the authority (i.e. BD) since

15 New project PBC design following MoE, MoA, FRC codes FSI design following FSI code FEA Design revised Y Submission to BD Submission to FSD Design revised Y FEA? N Opportunities for revision? N Approved? Approved? N Opportunities for revision? Y Evaluation by fire consultant N Y Y N Considered by FSC, BD Design rejected Design rejected Opportunities for revision? N Approved? Y N Design rejected Proceed to construction Proceed to installation Process for Approving Fire Safety Designs 15

16 This is basically performance-based design on demonstrating adequate safety. It is useful for buildings with special hazards requiring individual design considerations but not yet included in the prescriptive codes. But doing this without strong scientific fire research for local safety provisions is impossible. For projects considered in the past, FEA is basically to demonstrate that the safety of the design is equivalent to those specified in the existing codes. 16

17 Knowledge of fire science and engineering was applied together with practical experience under local conditions. Mathematical fire models, either zone models or field models (application of Computational Fluid Dynamics CFD or Numerical Heat Transfer NHT), had been used to analyze potential fire scenarios. Full-scale burning tests, scale models studies and site measurements on evacuation pattern might be required to demonstrate the safety of the design. 17

18 There are not yet standard methods for assessing those designs. A government consultancy project on reviewing the code started a few years ago. However, it took 10 years to develop some guides useful for performance-based designs in the U.K. There, most of the buildings are not so complicated, their living style is much well-organized and the consultancy team developing the guides has published numerous papers. 18

19 It appears to be rather difficult for Hong Kong to work out such EPBFC within a few years supported by in-depth research including relevant full-scale burning tests. There are so many complicated buildings and the living style is very different. In-depth research is necessary for working out something meaningful. The heat release rate is important in fire hazard assessment. This point will be discussed in this paper. 19

20 2. Importance of Heat Release Rate The heat release rate of a design fire has to be estimated in applying Fire Engineering Approach for projects having difficulties to comply with the prescriptive codes. There had been lots of arguments on the heat release rate of a design fire. Very low values down to 0.5 MW for normal scenarios were suggested, though 2 MW was used eventually. But as pointed out by FSD, what they encountered in big fires, accidental or arson, were not under normal conditions. 20

21 A flashover fire with a long duration in a restaurant. Used to be taken as example by FSD on showing how big the fire is. Restaurant fire due to flashover (Apple Daily, 7 January, 2005) Examples on fire outbreak 21

22 The big Garley Building fire is a painful lesson to learn. The Big Garley Building Fire (South China Morning Post, 21 November, 1996) Examples on fire outbreak 22

23 Cause of that fire is still under debate, whether the building management or the authorities should do more is another issue. Anyway, temporary fire protection should be provided while removing all lift doors for replacing new lift for a rather long time. 23

24 This concern is in fact on assessing the heat release rate to answer a common question on hazard assessment: How big is a fire? The heat release rate gives the most important information on how much heat will be released in burning the combustibles. Once the heat release rate is known, the resulted fire environment such as smoke temperature, smoke layer thickness, smoke flow rate, radiation heat flux, possibility to flashover, and the effects on adjacent combustibles and construction elements in the office, and hence the building as a whole, can all be estimated with empirical expressions or fire models. 24

25 Heat release rates of burning combustibles in typical building arrangements should be measured experimentally in a full-scale burning facility with and without discharging the fire suppressing agent. The results can then be applied for scenario analysis in performance-based design. 25

26 Factory Mutual, USA Hazard Calculations, SFPE handbook of fire protection engineering. Quincy, Mass. : National Fire Protection Association ; Bethesda, Md. : Society of Fire Protection Engineers, 3rd ed. (2002). 26

27 INDUSTRY Calorimeter: at SP, Sweden 27

28 3MW From: Quintiere, J.G., Principles of fire behavior, Delmar Publishers, Albany, N.Y.,

29 4. Extinguishment, Suppression and Control However, activating the sprinkler does not mean the fire can be controlled at that certain value immediately. The three terms control, suppression and extinguishment have to be understood by following NFPA 13 and NFPA 750: Fire control in NFPA 13 means limiting the size of a fire by distribution of water so as to decrease the heat release rate and pre-wet adjacent combustibles, while controlling ceiling gas temperatures to avoid structural damage. Fire extinguishment in NFPA 750 means the complete suppression of a fire until there are no burning combustibles. Fire suppression in NFPA 13 means sharply reducing the heat release rate of a fire and preventing its regrowth by means of direct and sufficient application of water through the fire plume to the burning fuel surface. 29

30 All these can be illustrated by plotting the heat release rate against time. Uncontrolled fire Heat release rate Operating the active protection system Another possibility Control Extinguishment Suppression Time 30

31 It is obvious that it would take time to control the heat release rate at a certain value. The value can be much higher than that estimated from equation (3), depending on the scenario concerned. Note that the design fire scenario is one of the primary uncertainties in fire safety engineering. A design fire depends on the geometry and use of the building; the combustibles used and stored; and most importantly, the ventilation provision. It cannot be decided without understanding the above. Recent results indicated that a very low combustible content can give very high heat release rates, though the fire might only last for a shorter time. 31

32 3. Estimation of Heat Release Rate Data on heat release rate available in the literature are very limited, even fewer on products used and manufactured in the Far East. There are no reliable data on local products for determining a design fire. Different values were used by the designers for different purposes in the past in designing fire protection systems for terminal halls; shopping malls; atria; and train compartments. Very low values of 0.3 MW to 0.5 MW were estimated in some designs. The same value was accepted in one project, but rejected in another similar project. This is due to the lack of a database for local products. 32

33 A site is needed for full-scale burning test! to get a database A full-scale burning facility is just developed by Chow at Lanxi, Harbin, Heilongjiang, China for measuring heat release rate 33

34 Harbin 哈爾濱 Beijing 北京 Hong Kong 香港 34

35 哈尔滨市街区 Harbin 35

36 呼蘭河之西 Lanxi 蘭西 Harbin 哈爾濱市 黑龍江省 Heilongjiang Province 36

37 ISO9705 實驗測試間 煙氣收集罩 風機 Exhaust hood ISO-Room Corner Fire Test 37

38 Preparation 38

39 Retail shop fire 39

40 No Budget to Burn Money! No Money No Talk! 40

41 In estimating the probable heat release rate for a design fire in a sprinkler protected area, a common practice is to apply an empirical equation for the maximum ceiling jet temperature rise ΔT max at a ceiling height H (in m) due to a fire of convective heat release rate Q & (in kw): c ΔT max = 16.9Q& H 3 / 2 c 5 / 3 (1) 41

42 Results will be combined with a thermal balance equation on relating the activation temperature of the thermal sensing element of the sprinkler heads with a certain Response Time Index (RTI). The activation time t a will be calculated based on RTI from a heat balance equation. Upon activation of sprinkler, the heat release rate is assumed to be kept at a constant value. 42

43 For example, a t 2 -fire with a heat release rate Q & (t) (in kw) at time t (in s) given by the equation through a constant t g : () Q& t = 1000 t t g 2 (2) where t g is 75 s, 150 s, 300 s and 600 s respectively for ultra-fast, fast, medium and slow t 2 -fire. The heat release rates Q & des of the design fire were estimated in many projects by: Q& des = 1000 t t a g 2 43 (3)

44 The objective of putting in sprinkler is to control the heat release rate at a certain value at steady state. The maximum possible heat removed by the sprinkler water spray depends on the volumetric flow rate of the sprinkler system and latent heat of vaporization. 44

45 Heat release rate Operating the active protection system Time for hot smoke to reach activation temperature Time to take action ΔHRR Any effect? Time 45

46 5. Full-scale Burning Tests To assess how sprinkler would control a fire, fullscale burning tests were carried out. Office fire scenarios with and without the operation of sprinkler were considered. A full-scale burning facility known as the Chinese Assembly Calorimeter was developed by the author with strong support from the Harbin Engineering University. This facility is located at the remote area Lanxi at about 150 km from Harbin, Heilongjiang, China. Flashover office fires were studied in the summer of

47 An office scenario is considered. Exhaust gases 2.4 m 2.4 m 2.4 m 2 m 0.8 m (a) Room calorimeter 3.6 m (b) Office fire scenario Office fire test 47

48 There were a chair, a desk with paper and books on top, a computer box and a cupboard were placed in a burn room. This setup was burnt under an accidental fire to give flashover for determining the heat release rate. Tests were then repeated by operating a sprinkler system at pressure 0.52 bar and flow rate 60 litres/min. 48

49 The resultant heat release rate curves for the scenario with and without sprinkler : 1.8 Peak 1.8 MW 1.6 Heat release rate / MW Jump of 0.5 MW Value at sprinkler activation About 1 MW 0.2 With sprinkler No sprinkler Operation of sprinkler Time t / s Heat release rate with and without sprinkler 49

50 It is observed that operating the sprinkler could control the fire for this scenario. However, the heat release rate did not stay at the value once the sprinkler was activated, but moved up to 1.5 MW. Note that the value was about 1 MW at the time of discharging water. There is a jump of 50% of the value at sprinkler activation. It is not too wrong to say, though local data is insufficient, that even operating the sprinkler will give 1.5/1.8 or over 80% of the possible maximum heat release rate! Note that this scenario gave a small fire of peak heat release rate less than 1.8 MW, only burning for about half an hour. 50

51 6. Impact on Hazard Assessment As defined in ASTM , fire hazard is the potential for harm associated with fire. Fire hazard assessment is a process for measuring or calculating the potential for harm created by the presence of a material, product, or assembly in the relevant fire scenarios. 51

52 Procedures for fire hazard assessment were further proposed to include at least seven steps: Step 1: Defining the scope. Step 2: Identifying the measure of harm to be assessed. Step 3: Identifying and describing the scenarios of concern. Step 4: Identifying the test methods or calculation procedures needed to produce the measures of fire hazard. Step 5: Using the scenarios to define key parameters of the test method or calculation procedures. Step 6: Identifying the types and sources of data required to support the test methods or calculation procedures. Step 7: Identifying the criteria or procedures for evaluating the fire hazard measures relative to the degree of harm. 52

53 Following this procedure with the above measured results, the heat release rate for the scenario with sprinkler protection should be 50% higher than that estimated from the cut-off value when sprinkler is activated. The hazard measures due to the extra heat released will give a quicker smoke filling rate and higher temperature distribution. In view of the heat release rate curve of the office fire scenario as shown in Figure 5, generating an additional 0.5 MW of heat release rate is quite dangerous. Adjacent items might be ignited to further generate much more heat. 53

54 7. Conclusion It is observed that even under a small office fire as in the above test, the heat release rate cannot be controlled at the value once the sprinkler system is activated. The heat release rate can be up to 80% of the maximum value, and about 50% higher than the value at the time of discharging water. Therefore, in estimating the heat release rate for sprinkler protected area with a t 2 -fire, the cut-off value at activation time should not be taken as the design figure. Much higher heat release rates will be resulted, depending on the scenario. 54

55 More full-scale burning tests on different scenarios are required to confirm the result as the probable heat release rate depends on the scenario. Sprinkler can control the fire at a value, but how much is unknown. It is no good to copy something from the literature for a scenario that does not quite match with the actual design. Performing an actual fire test is necessary to demonstrate safety. 55

56 Acknowledgement This paper is partly funded by a research grant on Fire safety provisions for workplaces in nonindustrial sectors by the Occupational Safety and Health Council, Hong Kong. 56

A Brief on Performance- Based Design for Building Fire Safety

A Brief on Performance- Based Design for Building Fire Safety International Conference on Safety & Security Management and Engineering Technology 2009 (ICSSMET2009) 17-18 December 2009, Taiwan A Brief on Performance- Based Design for Building Fire Safety Professor

More information

Heat Release Rate of an Open Kitchen Fire of Small Residential Units in Tall Buildings

Heat Release Rate of an Open Kitchen Fire of Small Residential Units in Tall Buildings 2014 Purdue Compressor/Refrigeration and Air Conditioning and High Performance Buildings Conference West Lafayette, IN, USA 14-17 July 2014 Heat Release Rate of an Open Kitchen Fire of Small Residential

More information

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER , Volume 9, Number 1, p.38-58, 2007 ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER C.W. Leung and W.K. Chow Department of Building Services Engineering, The Hong Kong

More information

Hot Issues in Fire Engineering 28 February 2012

Hot Issues in Fire Engineering 28 February 2012 Hot Issues in Fire Engineering 28 February 2012 A Note on Cabin Fire Design for Protecting Large Halls W.K. Chow Research Centre for Fire Engineering, Department of Building Services Engineering The Hong

More information

ASPECTS OF FIRE SAFETY IN ULTRA HIGHRISE BUILDINGS

ASPECTS OF FIRE SAFETY IN ULTRA HIGHRISE BUILDINGS , Volume 6, Number 2, p.47-52, 2004 ASPECTS OF FIRE SAFETY IN ULTRA HIGHRISE BUILDINGS W.K. Chow Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China (Received

More information

Considerations in the Design of Smoke Management Systems for Atriums

Considerations in the Design of Smoke Management Systems for Atriums Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke

More information

Comment on Hawker Stall Fires

Comment on Hawker Stall Fires Comment on Hawker Stall Fires Started: 28 April 2013 Revised: 26 December 2013 In-depth version: 3 May 2014 Final: 16 June 2014 W.K. Chow, JP FHKEng Fellow Elected, Hong Kong Academy of Engineering Sciences

More information

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM , Volume 11, Number 2, p.43-48, 2012 NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM Q. Kui Institute of Building Fire Research, China Academy of Building Research, Beijing,

More information

SURVEY ON FIRE SERVICE INSTALLATIONS FOR OFFICE BUILDINGS IN HONG KONG

SURVEY ON FIRE SERVICE INSTALLATIONS FOR OFFICE BUILDINGS IN HONG KONG SURVEY ON FIRE SERVICE INSTALLATIONS FOR OFFICE BUILDINGS IN HONG KONG E.C.L. Pang and W.K. Chow Research Centre for Fire Engineering, Area of Strength: Fire Safety Engineering The Hong Kong Polytechnic

More information

ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER

ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER , Volume 6, Number 3, p.122-154, 2004 ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER C.W. Leung, W.K. Chow Department of Building Services Engineering, The Hong Kong

More information

NECESSITY OF CARRYING OUT FULL-SCALE BURNING TESTS FOR POST-FLASHOVER RETAIL SHOP FIRES

NECESSITY OF CARRYING OUT FULL-SCALE BURNING TESTS FOR POST-FLASHOVER RETAIL SHOP FIRES , Volume 5, Number 1, p.20-27, 2003 NECESSITY OF CARRYING OUT FULL-SCALE BURNING TESTS FOR POST-FLASHOVER RETAIL SHOP FIRES W.K. Chow Department of Building Services Engineering, The Hong Kong Polytechnic

More information

Experimental Room Fire Studies with Perforated Suspended Ceiling

Experimental Room Fire Studies with Perforated Suspended Ceiling Experimental Room Fire Studies with Perforated Suspended Ceiling FIONA S.C. TSUI 1, W.K. CHOW 1, N.K. FONG 1, Y. GAO 2, H. DONG 2, and G.W. ZOU 2 1 Research Centre for Fire Engineering Department of Building

More information

FIRE SAFETY ENGINEERING AND POTENTIAL APPLICATION OF FIRE MODELS

FIRE SAFETY ENGINEERING AND POTENTIAL APPLICATION OF FIRE MODELS , Volume 5, Number 4, p.92-102, 2003 FIRE SAFETY ENGINEERING AND POTENTIAL APPLICATION OF FIRE MODELS W.K. Chow Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong,

More information

Case Study for Performance-Based Design in Hong Kong

Case Study for Performance-Based Design in Hong Kong Paper presented at Society of Fire Protection Engineers 6th International Conference on Performance-Based Codes and Fire Safety Design Methods on 14-16 June 2006 by Professor W.K. Chow Case Study for Performance-Based

More information

A Monte Carlo Approach for the Design of Thermal Fire Detection System

A Monte Carlo Approach for the Design of Thermal Fire Detection System A Monte Carlo Approach for the Design of Thermal Fire Detection System Walter W. Yuen Department of Mechanical & Environmental Engineering University of California at Santa Barbara California, USA and

More information

FULL-SCALE BURNING TESTS FOR RETAIL SHOP FIRES: PRELIMINARY STUDIES

FULL-SCALE BURNING TESTS FOR RETAIL SHOP FIRES: PRELIMINARY STUDIES , Volume 6, Number 3, p.94-121, 24 FULL-SCALE BURNING TESTS FOR RETAIL SHOP FIRES: PRELIMINARY STUDIES W.K. Chow and Candy M.Y. Ng Department of Building Services Engineering, The Hong Kong Polytechnic

More information

SHOULD SMOKE MANAGEMENT SYSTEM BE PROVIDED IN KARAOKE ESTABLISHMENTS?

SHOULD SMOKE MANAGEMENT SYSTEM BE PROVIDED IN KARAOKE ESTABLISHMENTS? International Journal on Engineering Performance-ased Fire odes, Volume 4, Number 2, p.30-34, 2002 SHOULD SMOKE MNGEMENT SYSTEM E PROVIDED IN KROKE ESTLISHMENTS? W.K. how Department of uilding Services

More information

IFireSS International Fire Safety Symposium Coimbra, Portugal, 20 th -22 nd April 2015

IFireSS International Fire Safety Symposium Coimbra, Portugal, 20 th -22 nd April 2015 IFireSS International Fire Safety Symposium Coimbra, Portugal, 20 th -22 nd April 2015 SCALE MODEL EXPERIMENTS ON SMOKE MOVEMENT IN A TILTED TUNNEL photo Author 1 30 mm 40 mm photo Author 2 30 mm 40 mm

More information

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada

More information

Fire Safety Management System in Modern High-rise Buildings - Hong Kong Perspective

Fire Safety Management System in Modern High-rise Buildings - Hong Kong Perspective November 02-04, 2009,Tainan,Taiwan Fire Safety Management System in Modern High-rise Buildings - Hong Kong Perspective Lau Kwai-Wing 1 Wan-Ki Chow 2 ABSTRACT The erection of 7627 blocks of high-rise building

More information

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Fire Science and Technorogy Vol.24 No.4(2005) 165-178 165 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Jun-ichi Yamaguchi 1, Takeyoshi Tanaka 2 1 Technical Research

More information

NECESSITY OF IN-DEPTH EVALUATION OF LONG-THROW SPRINKLER INSTALLATION AT TALL ATRIA STORING HIGH AMOUNTS OF COMBUSTIBLES

NECESSITY OF IN-DEPTH EVALUATION OF LONG-THROW SPRINKLER INSTALLATION AT TALL ATRIA STORING HIGH AMOUNTS OF COMBUSTIBLES , Volume 11, Number 1, p.4-10, 2012 NECESSITY OF IN-DEPTH EVALUATION OF LONG-THROW SPRINKLER INSTALLATION AT TALL ATRIA STORING HIGH AMOUNTS OF COMBUSTIBLES W.K. Chow Research Centre for Fire Engineering,

More information

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN , Volume 6, Number 4, p.248-254, 04 RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN C.L. Choi Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Water

More information

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

ZONE MODEL VERIFICATION BY ELECTRIC HEATER , Volume 6, Number 4, p.284-290, 2004 ZONE MODEL VERIFICATION BY ELECTRIC HEATER Y.T. Chan Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Selecting

More information

Hot Issues in Fire Engineering July 2014

Hot Issues in Fire Engineering July 2014 Hot Issues in Fire Engineering July 2014 Crowded Railway Stations and Train Compartments to Watch Y.W. Ng and W.K. Chow, JP FHKEng Research Centre for Fire Engineering, Department of Building Services

More information

Simulation of Full-scale Smoke Control in Atrium

Simulation of Full-scale Smoke Control in Atrium Available online at www.sciencedirect.com Procedia Engineering 11 (2011) 608 613 The 5 th Conference on Performance-based Fire and Fire Protection Engineering Simulation of Full-scale Smoke Control in

More information

PRELIMINARY STUDIES ON MECHANICAL SMOKE EXHAUSTS IN LARGE SPACE BUILDING FIRES

PRELIMINARY STUDIES ON MECHANICAL SMOKE EXHAUSTS IN LARGE SPACE BUILDING FIRES PRELIMINARY STUDIES ON MECHANICAL SMOKE EXHAUSTS IN LARGE SPACE BUILDING FIRES R. Huo a, Y. Li a, W. Fan a and W. Chow b a. State Key Laboratory of Fire Science, CHINA b. The Hong Kong Polytechnic University

More information

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A. International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.800(19) Magnus Arvidson SP Fire Research SP Technical Research Institute

More information

Tunnel Fire Dynamics and Evacuation Simulations

Tunnel Fire Dynamics and Evacuation Simulations Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation

More information

First Revision No. 6-NFPA [ Section No. 2.2 ]

First Revision No. 6-NFPA [ Section No. 2.2 ] Page 1 of 18 First Revision No. 6-NFPA 555-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 12, Standard on Carbon

More information

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea 5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea PRACTICAL APPLICATIONS OF FIRE MODELING IN INDUSTRIAL APPLICATIONS By James M. Dewey, Advisor Risk Management

More information

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,

More information

Anatomy of a Fire. Christopher Crivello, MSFPE, PE. Douglas Nadeau, MSFPE, PE, CFPS, LEED AP

Anatomy of a Fire. Christopher Crivello, MSFPE, PE. Douglas Nadeau, MSFPE, PE, CFPS, LEED AP Anatomy of a Fire Douglas Nadeau, MSFPE, PE, CFPS, LEED AP President of RAN Fire Protection Engineering, PC Vice President of truvue Inspection Technology Christopher Crivello, MSFPE, PE Fire Protection

More information

How design fires can be used in fire hazard analysis

How design fires can be used in fire hazard analysis How design fires can be used in fire hazard analysis Yung, D.T.; Bénichou, N. NRCC-44511 A version of this document is published in / Une version de ce document se trouve dans : Fire Technology, v. 38,

More information

SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS

SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS , Volume 11, Number 2, p.21-26, 212 SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS C.Y. Tso and W.K. Chow Research Centre for Fire Engineering,

More information

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS Prepared for Smoke Safety Council 6775 SW 111 th Avenue, Suite 10 Beaverton, OR 97008 Prepared by Jesse J. Beitel Alison J. Wakelin Craig L.

More information

Case Study 1 Underground Car Park

Case Study 1 Underground Car Park Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building

More information

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls Journal of Mechanics Engineering and Automation 5 (2015) 465-471 doi: 10.17265/2159-5275/2015.08.007 D DAVID PUBLISHING Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

More information

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings Justin A. Geiman, Noah L. Ryder Fire & Risk Alliance, Rockville, MD, USA André W. Marshall Custom Spray Solutions, Silver Spring,

More information

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION - 165 - CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT

More information

Recent Advances in Fire Suppression Modeling Issues & Perspectives of Fire Safety Engineering Applications

Recent Advances in Fire Suppression Modeling Issues & Perspectives of Fire Safety Engineering Applications Recent Advances in Fire Suppression Modeling Issues & Perspectives of Fire Safety Engineering Applications Pianet Grégoire Studies and modelling section manager Fire and Environmental Department, CNPP

More information

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN , Volume 4, Number 2, p.73-83, 2003 SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN K.H. Yang and C.S. Yang Mechanical Engineering Department, National Sun Yat-Sen

More information

OBSERVATION ON THE TWO RECENT BUS FIRES AND PRELIMINARY RECOMMENDATIONS TO PROVIDE FIRE SAFETY

OBSERVATION ON THE TWO RECENT BUS FIRES AND PRELIMINARY RECOMMENDATIONS TO PROVIDE FIRE SAFETY , Volume 5, Number 1, p.1-5, 2003 OBSERVATION ON THE TWO RECENT BUS FIRES AND PRELIMINARY RECOMMENDATIONS TO PROVIDE FIRE SAFETY W.K. Chow Department of Building Services Engineering, The Hong Kong Polytechnic

More information

The Science Behind Water Mist Protection of Typical Building Hazards

The Science Behind Water Mist Protection of Typical Building Hazards The Science Behind Water Mist Protection of Typical Building Hazards SUPDET 2014 Zachary Magnone, P.E. Zachary.Magnone@tycofp.com Presentation Goals What is water mist? How does it work? How is it tested

More information

Sprinklers Modeling for Tunnel Road Fire Fighting

Sprinklers Modeling for Tunnel Road Fire Fighting Sprinklers Modeling for Tunnel Road Fire Fighting P. Ciambelli, M.G. Meo, P. Russo, S. Vaccaro Department of Chemical and Food Engineering, University of Salerno - ITALY 1. INTRODUCTION Loss of lives and

More information

EXPERIMENTAL STUDIES ON THE EFFECT OF THE FIRE POSITION ON PLUME ENTRAINMENT IN A LARGE SPACE

EXPERIMENTAL STUDIES ON THE EFFECT OF THE FIRE POSITION ON PLUME ENTRAINMENT IN A LARGE SPACE , Volume, Number 4, p.138-14, 23 EXPERIMENTAL STUDIES ON THE EFFECT OF THE FIRE POSITION ON PLUME ENTRAINMENT IN A LARGE SPACE Yuanzhou Li, Ran Huo, Liang Yi and Guodong Wang State Key Laboratory of Fire

More information

Copy of article submitted to Fire Safety Engineering for publication January/February 2009

Copy of article submitted to Fire Safety Engineering for publication January/February 2009 Copy of article submitted to Fire Safety Engineering for publication January/February 2009 Metal faced sandwich panels with plastic foam cores - a challenge to fire safety by Gordon Cooke Confusion, misleading

More information

Yunyong P. Utiskul, Ph.D., P.E., CFEI

Yunyong P. Utiskul, Ph.D., P.E., CFEI Yunyong P. Utiskul, Ph.D., P.E., CFEI Managing Engineer Thermal Sciences 17000 Science Drive, Suite 200 Bowie, MD 20715 (301) 291-2544 tel yutiskul@exponent.com Professional Profile Dr. Utiskul applies

More information

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan Open Journal of Fluid Dynamics, 2017, 7, 205-218 http://www.scirp.org/journal/ojfd ISSN Online: 2165-3860 ISSN Print: 2165-3852 Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke

More information

PRELIMINARY EXPERIMENTAL STUDY OF DOUBLE-SKINNED FAÇADE

PRELIMINARY EXPERIMENTAL STUDY OF DOUBLE-SKINNED FAÇADE , Volume 6, Number 3, p.155-167, 2004 PRELIMINARY EXPERIMENTAL STUDY OF DOUBLE-SKINNED FAÇADE W.K. Chow and W.Y. Hung Department of Building Services Engineering, The Hong Kong Polytechnic University,

More information

Fire Safety in Tall Building: Performance-Based Solutions. Chris Jelenewicz, P.E., FSFPE

Fire Safety in Tall Building: Performance-Based Solutions. Chris Jelenewicz, P.E., FSFPE Fire Safety in Tall Building: Performance-Based Solutions Chris Jelenewicz, P.E., FSFPE Kingdom Tower -- Jeddah Central Park Tower Philadelphia, PA One Meridian Plaza February 23, 1991 SFPE/ICC Guide

More information

Simulation of Emergency Evacuation in the Arrival Hall of a Crowded Airport

Simulation of Emergency Evacuation in the Arrival Hall of a Crowded Airport Simulation of Emergency Evacuation in the Arrival Hall of a Crowded Airport W.K. CHOW, CANDY M.Y. NG, and N.K. FONG Research Centre for Fire Engineering Department of Building Services Engineering Area

More information

So, How do Fire Starts & Spreads? A question we need to understand and appreciate the dynamics of fire life cycle.

So, How do Fire Starts & Spreads? A question we need to understand and appreciate the dynamics of fire life cycle. So, How do Fire Starts & Spreads? A question we need to understand and appreciate the dynamics of fire life cycle. The figure on the right depicts a typical life cycle of a fire: its 4 stages of fire induction,

More information

ASSESSING FIRE SAFETY PROVISIONS FOR SATISFYING GREEN OR SUSTAINABLE BUILDING DESIGN CRITERIA: PRELIMINARY SUGGESTIONS

ASSESSING FIRE SAFETY PROVISIONS FOR SATISFYING GREEN OR SUSTAINABLE BUILDING DESIGN CRITERIA: PRELIMINARY SUGGESTIONS , Volume 4, Number 3, p.141-146, 2003 ASSESSING FIRE SAFETY PROVISIONS FOR SATISFYING GREEN OR SUSTAINABLE BUILDING DESIGN CRITERIA: PRELIMINARY SUGGESTIONS C.L. Chow and W.K. Chow Department of Building

More information

Recommendations for a Model Curriculum for a BS Degree in Fire Protection Engineering (FPE) April 15, 2010

Recommendations for a Model Curriculum for a BS Degree in Fire Protection Engineering (FPE) April 15, 2010 Recommendations for a Model Curriculum for a BS Degree in Fire Protection Engineering (FPE) April 15, 2010 Society of Fire Protection Engineers (SFPE) Acknowledgement: SFPE would like to acknowledge the

More information

Recent BRANZFIRE enhancements and validation

Recent BRANZFIRE enhancements and validation Recent BRANZFIRE enhancements and validation Michael Spearpoint University of Canterbury Summary BRANZFIRE is a multi-compartment fire zone model that has been under development since 1996 predominately

More information

REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS

REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS Nikola TANASIĆ, Tomislav SIMONOVIĆ, Miloš IVOŠEVIĆ, Branislav

More information

Fire Hazard Analysis of Technical Area 53 Building 1

Fire Hazard Analysis of Technical Area 53 Building 1 Fire Hazard Analysis of Technical Area 53 Building 1 June 11, 2015 LA-UR-15-23589 Slide 1 Introduction Brett Noakes Los Alamos National Laboratory Los Alamos, New Mexico Slide 2 Outline Background of the

More information

( )

( ) Course Title: Fire Dynamics (3087) Course Number: FST - 3087 Course Credit Hours: (3) Three Semester Hours Instructor Information: Bernard W. Becker, III, MS (937-751-7371) ccfdchiefbecker@yahoo.com Textbook:

More information

A Fire Safety Ranking System for Karaoke Establishments in Hong Kong

A Fire Safety Ranking System for Karaoke Establishments in Hong Kong A Fire Safety Ranking System for Karaoke Establishments in Hong Kong W. K. CHOW* AND GIGI C. H. LUI Department of Building Services Engineering The Hong Kong Polytechnic University Hung Hom, Kowloon Hong

More information

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015?

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015? Plumis White Paper April 2017 How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015? As with the introduction of every new formal product category through

More information

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment Hong-Zeng (Bert) Yu FM Global 16 th International Water Mist Conference September 21-22, 2016 Vienna,

More information

LONGITUDINAL VENTILATION FOR SMOKE CONTROL IN A TILTED TUNNEL BY SCALE MODELING

LONGITUDINAL VENTILATION FOR SMOKE CONTROL IN A TILTED TUNNEL BY SCALE MODELING LONGITUDINAL VENTILATION FOR SMOKE CONTROL IN A TILTED TUNNEL BY SCALE MODELING W.K. Chow, and W.Y. Chung Research Centre for Fire Engineering, Department of Building Services Engineering Area of Strength:

More information

Available online at ScienceDirect. Procedia Engineering 84 (2014 )

Available online at  ScienceDirect. Procedia Engineering 84 (2014 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 84 (2014 ) 553 557 2014ISSST, 2014 International Symposium on Safety Science and Technology Research on fire endurance of tempered

More information

DESIGN OF AIR-CONDITIONING SYSTEM FOR SARS WARDS. By Yuguo Li and SARS Busters * Background

DESIGN OF AIR-CONDITIONING SYSTEM FOR SARS WARDS. By Yuguo Li and SARS Busters * Background DESIGN OF AIR-CONDITIONING SYSTEM FOR SARS WARDS By Yuguo Li and SARS Busters * Background The hospital care workers (HCWs) have been the most severely affected professions during the SARS epidemics in

More information

Prescriptive Requirement for Smoke Control

Prescriptive Requirement for Smoke Control HKIE CPD Training Course (II) 7July 2009 Organization by The Hong Kong Institution of Engineers Fire Division Co-organized by the Association of Registered Fire Services Installation contractors of Hong

More information

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING

More information

Case Study 2 (Production and Storage Buildings) - Spain

Case Study 2 (Production and Storage Buildings) - Spain Case Study 2 (Production and Storage Buildings) - Spain OBJECTIVE Developed by the SFPE Spanish Chapter Editor: Jimmy Jönsson, JVVA Fire & Risk The objective of this case study is to show how a project

More information

Comparative Evaluation Method for Fire Safety Design of Large Storage Spaces

Comparative Evaluation Method for Fire Safety Design of Large Storage Spaces Comparative Evaluation Method for Fire Safety Design of Large Storage Spaces ZHENKUN WU 1,2, HAIHANG LI 1, YAPING HE 3, DECHUANG ZHOU 1, JIAN WANG 1 1 State Key Laboratory of Fire Science, University of

More information

UPHOLSTERED FURNITURE AND MATTRESSES IN NEW AND EXISTING BUILDINGS

UPHOLSTERED FURNITURE AND MATTRESSES IN NEW AND EXISTING BUILDINGS Page 20 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information

More information

WATER MIST CONVENTION AND EXHIBITION

WATER MIST CONVENTION AND EXHIBITION INTERNATIONAL WATER MIST ASSOCIATION IWMA SEMINARS S ON WATER MIST TECHNOLOGY DUBAI INTERNATIONAL CONVENTION AND EXHIBITION CENTRE Water mist fire protection: The most innovative fire fighting technology

More information

PART 1 THERMAL & MECHANICAL ACTIONS. DIF SEK Part 1: Thermal & Mechanical Actions 0/ 50

PART 1 THERMAL & MECHANICAL ACTIONS. DIF SEK Part 1: Thermal & Mechanical Actions 0/ 50 DIF SEK PART 1 THERMAL & MECHANICAL ACTIONS DIF SEK Part 1: Thermal & Mechanical Actions 0/ 50 Background of the RFCS Project DIFISEK+ This project is funded by the European Commission in the frame of

More information

6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea 6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea CONDUCTING A FULL-SCALE EXPERIMENT ON A RAIL PASSENGER CAR ABSTRACT N. White and V.P. Dowling CSIRO Fire

More information

Fire Severity for Structural Design

Fire Severity for Structural Design Fire Severity for Structural Design A UK Perspective Susan Deeny, PhD 2 Broadgate Phase 8 3 5 Shaping a better world Experience of working in Abu Dhabi 6 UAE 7 Fire Severity for Structural Analysis Building

More information

Mathematical Modeling of Fires

Mathematical Modeling of Fires Mathematical Modeling of Fires J. R. Mehaffey, editor # Special Technical Publication (STP) 983 1916 Race Street, Philadelphia, PA 19103 Library of Congress Cataloging-in-Publication Data Mathematical

More information

Chapter 17, Initiating Devices

Chapter 17, Initiating Devices Chapter 17, Initiating Devices Summary. Chapter 17 was Chapter 5 in NFPA 72-2007. The term authority having jurisdiction is replaced in some sections by the term other governing laws, codes, or standards.

More information

A NETWORK MODEL OF SIMULATING SMOKE MOVEMENT IN BUILDINGS

A NETWORK MODEL OF SIMULATING SMOKE MOVEMENT IN BUILDINGS , Volume 3, Number 4, p.151-157, 2001 A NETWORK MODEL OF SIMULATING SMOKE MOVEMENT IN BUILDINGS F. Liu and X.Z. Fu Faculty of Urban Construction and Environmental Engineering Chongqing University, Chongqing

More information

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space Available online at www.sciencedirect.com Procedia Engineering 31 (2012) 734 738 International Conference on Advances in Computational Modeling and Simulation A Numerical study of the Fire-extinguishing

More information

Advantages and Disadvantages of Fire Modelling

Advantages and Disadvantages of Fire Modelling Advantages and Disadvantages of Fire Modelling Dr Guillermo Rein School of Engineering University of Edinburgh & Imperial College London Dr Guillermo Rein 9 May 2012 Chief Fire Officers Association Annual

More information

Gothenburg dance hall, Sweden, 1998

Gothenburg dance hall, Sweden, 1998 Gothenburg dance hall, Sweden, 1998 The fire occurred on 28 October 1998 in a crowded dance hall in Gothenburg. 63 people died, 120 were injured and about 60 were rescued by the fire brigade. The hall

More information

Fire Resistance - Implications for regulations and standards of the September 11th terrorist attacks on the world trade centre Tom Lennon, FRS, BRE

Fire Resistance - Implications for regulations and standards of the September 11th terrorist attacks on the world trade centre Tom Lennon, FRS, BRE Fire Resistance - Implications for regulations and standards of the September 11th terrorist attacks on the world trade centre Tom Lennon, FRS, BRE Malaysia May 2003 Questions What is fire resistance?

More information

Evacuation Hazards in Crowded Subway Stations

Evacuation Hazards in Crowded Subway Stations Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2016 Evacuation Hazards in Crowded Subway Stations M.K. Ho The Hong Kong Polytechnic

More information

Predictions of Railcar Heat Release Rates

Predictions of Railcar Heat Release Rates Predictions of Railcar Heat Release Rates John Cutonilli & Craig Beyler Hughes Associates, Inc 361 Commerce Dr, Suite 817 Baltimore, MD 21227 USA Email: jcutonilli@haifire.com, cbeyler@haifire.com KEYWORDS:

More information

PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT

PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT DAVID CHARTERS DEAN MCGRAIL Arup Fire, 78 East Street, Leeds, LS9

More information

Fire Engineering in High Rise 15 November 2013

Fire Engineering in High Rise 15 November 2013 Fire Engineering in High Rise 15 November 2013 Neal Butterworth Arup UK www.arup.com Neal.Butterworth@arup.com Contents How do we protect against fire? How do we know this works? Why evacuate? What assumptions

More information

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c Table 1015.1 EXIT ACCESS TRAVEL DISTANCE a WITHOUT SPRINKLER WITH SPRINKLER OCCUPANCY SYSTEM SYSTEM A, E, F-1, I-1, M, 200 250 b,d R, S-1 B 200 300 c F-2, S-2, U 300 400 c No Change to Other Entries in

More information

SIMULATION OF A COMPARTMENT FLASHOVER FIRE USING HAND CALCULATIONS, ZONE MODELS AND A FIELD MODEL

SIMULATION OF A COMPARTMENT FLASHOVER FIRE USING HAND CALCULATIONS, ZONE MODELS AND A FIELD MODEL Reference : Spearpoint M J, Mowrer F W, McGrattan K. Simulation of a single compartment flashover fire using hand calculations, zone models and a field model. Proc. 3 rd International Conference on Fire

More information

The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD

The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD BFS 2011:27 with amendments up to BFS 2013:12 The

More information

CFD Model of a Specific Fire Scenario

CFD Model of a Specific Fire Scenario 16 th Australasian Fluid Mechanics Conference Crown Plaza, Gold Coast, Australia 2-7 December 27 CFD Model of a Specific Fire Scenario D. Mackay, T. Barber and E. Leonardi School of Mechanical and Manufacturing

More information

Case Study of Underground Car Park. Team Japan

Case Study of Underground Car Park. Team Japan 11th Conference on Performance Based Codes and Fire Safety Design Methods Case Study of Underground Car Park Team Japan We focused on the characteristics of the fire behavior of car fire. Car fire is not

More information

Uncertainty Analysis For Input Parameters Of Electrical Cabinet Fire Simulation By Coupling Latin Hypercube Sampling And CFAST

Uncertainty Analysis For Input Parameters Of Electrical Cabinet Fire Simulation By Coupling Latin Hypercube Sampling And CFAST Uncertainty Analysis For Input Parameters Of Electrical Cabinet Fire Simulation By Coupling Latin ypercube Sampling And CFAST Wanhong WANG a, Dahuan ZU b, ui BAO c, Yun GUO a, Changhong PENG a * a School

More information

LESSON ONE FIREFIGHTER I Fire Behavior

LESSON ONE FIREFIGHTER I Fire Behavior LESSON ONE FIREFIGHTER I Fire Behavior OBJECTIVE PAGE DOMAIN: COGNITIVE LEVEL OF LEARNING: KNOWLEDGE MATERIALS IFSTA Essentials 4th edition; overhead projector or laptop computer and multi media projector;

More information

Passive fire protection. 6 Passive fire protection. 6.1 Fire compartmentation. Passive fire protection

Passive fire protection. 6 Passive fire protection. 6.1 Fire compartmentation. Passive fire protection 6 Inside buildings there are two types of fire protection systems: Active Fire Protection and Passive Fire Protection. Both systems should actively work together in the event of a fire. 6.1.1 The four

More information

Investigating the Effects of Sprinkler Sprays on Fire-Induced Doorway Flows: A Two-Part Study. Jeremiah Crocker and Dr. Bin Xiao New Technology Team

Investigating the Effects of Sprinkler Sprays on Fire-Induced Doorway Flows: A Two-Part Study. Jeremiah Crocker and Dr. Bin Xiao New Technology Team Jeremiah Crocker and Dr. Bin Xiao New Technology Team Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved. The products and specifications published herein are for general evaluation

More information

TECHNICAL TRADE-OFFS USING FIXED FIRE FIGHTING SYSTEMS

TECHNICAL TRADE-OFFS USING FIXED FIRE FIGHTING SYSTEMS - 12 - TECHNICAL TRADE-OFFS USING FIXED FIRE FIGHTING SYSTEMS H. Ingason and Y.Z. Li, SP Technical Research Institute of Sweden ABSTRACT The increasing use of fixed fire-fighting system (FFFS) in tunnels

More information

Fire Research and Education at the University of Maryland

Fire Research and Education at the University of Maryland Fire Research and Education at the University of Maryland J. G. Quintiere Department of Fire Protection Engineering March 7,8 2005 2nd Int. Symp. 21st Century Center of Excellence Program History of FPE

More information

FIRE HAZARD ASSESSMENT IN SUPPORTING FIRE PROTECTION SYSTEM DESIGN OF A CHEMICAL PROCESS FACILITY ABSTRACT

FIRE HAZARD ASSESSMENT IN SUPPORTING FIRE PROTECTION SYSTEM DESIGN OF A CHEMICAL PROCESS FACILITY ABSTRACT FIRE HAZARD ASSESSMENT IN SUPPORTING FIRE PROTECTION SYSTEM DESIGN OF A CHEMICAL PROCESS FACILITY Ali Pezeshk, Joseph Chang, Dwight Hunt, and Peter Jahn Parsons Infrastructure & Technology Group, Inc.

More information

An experimental study of the impact of tunnel suppression on tunnel ventilation

An experimental study of the impact of tunnel suppression on tunnel ventilation An experimental study of the impact of tunnel suppression on tunnel ventilation Yoon J. Ko and George Hadjisophocleous Civil and Environmental Engineering, Carleton University 1125 Colonel By Drive, Ottawa,

More information

CFD Analysis of Fire Characteristics on Subway Junction Station

CFD Analysis of Fire Characteristics on Subway Junction Station ISGSR27 First International Symposium on Geotechnical Safety & Risk Oct. 18~19, 27 Shanghai Tongji University, China CFD Analysis of Fire Characteristics on Subway Junction Station G. H. Wu, X. Han, Q.Q.

More information

Hot Issues in Fire Engineering 12 March 2013

Hot Issues in Fire Engineering 12 March 2013 Hot Issues in Fire Engineering 12 March 2013 An Update on Design Fires of Vehicular Tunnels W.K. Chow Fellow, Hong Kong Academy of Engineering Sciences Research Centre for Fire Engineering, Department

More information