RETOS Y TENDENCIAS DESARROLLO DE INFRAESTRUCTURA EN AUSTRIA. Leonardo Rosas Sánchez Bogotá Agosto 9 de 2018

Size: px
Start display at page:

Download "RETOS Y TENDENCIAS DESARROLLO DE INFRAESTRUCTURA EN AUSTRIA. Leonardo Rosas Sánchez Bogotá Agosto 9 de 2018"

Transcription

1

2 RETOS Y TENDENCIAS DESARROLLO DE INFRAESTRUCTURA EN AUSTRIA Leonardo Rosas Sánchez Bogotá Agosto 9 de 2018

3 Table of content 1. Safety standards for road and railway tunnels 2. Upgrading the Alrberg Tunnel to current safety standards 3. Conclusions

4 1. Safety standards for road and railway tunnels 1.1 Dramatc events Mont Blanc Tunnel: Aftermath of dramatic events in tunnel, safety measures seemed to be inadequate Safety is approached in engineering terms through a logical sequence of analyses and evaluation, mainly of a numerical and quantitative type. On 24 March 1999, a HGV traveling through the tunnel from France to Italy caught fire, possible due to the engine overheating St. Gotthard Tunnel: On 24 October 2001, two heavy good vehicles (HGVs) that were traveling through the tunnel in the Swill Alps had an accident Shortly after collision, a fire broke out on one of the HGVs, and it spread rapidly to the other vehicle

5 1. Safety standards for road and railway tunnels 1.2 Fire in Mont Blanc Tunnel Operation problem: A HGV stopped 6 km into the tunnel (L = 11,600 m), when the driver became aware of the fire Within minutes the tunnel operators were aware of the fire 29 vehicles entered the tunnel before it was closed Four HGVs managed to pass, but the other 25 vehicles became trapped Nobody traveling in any of those vehicles survived Ventilation problem: Due to the prevailing wind direction (from the south) and the different ventilation regimes at either end of the tunnel, virtually all the smoke from the fire was carried out towards France As the airflow velocity was more than 1 m/s, the smoke did not remain stratified, and within minutes there was no fresh air in the tunnel downstream of the fire

6 1. Safety standards for road and railway tunnels 1.2 Fire in Mont Blanc Tunnel Size and impact of the fire: At the height of the fire, the blaze was estimated to have been about 190 MW in size, with temperatures dealt with after 5 days: Thirty-eight tunnel users and one firefighter died as a result of the fire, 27 in their vehicles, two in an emergency shelter (designated to protect life in the event of a fire) and the rest on the roadway trying to reach the France portal This was the greatest ever loss of life in any road-tunnel fire (except the Salang fire in 1982, which involved an explosion as well as a fire)

7 1. Safety standards for road and railway tunnels 1.3 Fire in St. Gothard Tunnel Safety concept: The tunnel (L = m) comprises a single roadway with two lanes, bored on a north-south axis, bored from Airolo in the South to Göschenen in the North A safety gallery runs parallel to the main tunnel on the east side Refuges are spaced every 250 m along the length of the tunnel, and these connect the tunnel to the safety gallery

8 1. Safety standards for road and railway tunnels 1.3 Fire in St. Gothard Tunnel Complexity of the ventilation system: It could be longitudinal, i.e. with supply and exhaust systems switched off Semi-transverse, i.e. with only air supply or only exhaust operating; or fully transverse, i.e. with both supply and exhaust operating In fire mode the ventilation system was set to fully transverse, having been in longitudinal mode before the fire

9 1. Safety standards for road and railway tunnels 1.3 Fire in St. Gothard Tunnel Failure of the ventilation system: Fresh air was drawn into the air ducts at the portals at both ends of the tunnel, while the polluted air was extracted at ceiling height On the eastern carriageway, the ceiling was still intact in places, but had partially collapsed and was supported by the concrete walls of the tunnel lining Smoke, toxic gases and a considerable amount of the heat produced by the fire were directed northwards along the tunnel The fire burned for approximately 24 hours After the fire was brought under control, the bodies of 11 people were found among the debris to the north of the incident location

10 1. Safety standards for road and railway tunnels 1.4 Safety Engineering Transport infrastructures constructed a decade or more ago are unsuited to meeting the demands of the increase in passenger and freight transport This leads to infrastructure safety-related problems: (1) dramatic cases: (2) investigations at levels that have not been reached in the past Dealing with infrastructure safety now calls for the introduction of risk analysis The scientific approach that allows the evaluation of all risk factors: the identification, monitoring and reduction of accidents Infrastructure safe operations will focus primarily on preventing accidents and secondarily on protection (reduce effects on users) New infrastructure: New infrastructures the safety criteria become rules for the definition of project input and performance standards Existing infrastructures: 1) Adaptation of the infrastructure from a structural and/or functional point of view 2) Operative procedures aimed primarily at guaranteeing steady performance levels over time and throughout the year 3) The adoption of systems to reduce the risk of harmful events and incorrect behavior

11 1. Safety standards for road and railway tunnels 1.5 Road Tunnel Safety Directve 54/2004/EC) On 29th April 2004, the Directive 2004/54/EC was adopted, relating to the Minimum Safety requirements for tunnels on the Trans-European Road Network Initiative for the improvement of road safety in tunnels: uniform outlook on safety and common safety levels within the European Union Directive s purposes: 1) Minimum safety requirements for all tunnels belonging to the trans-european road network longer than 500 m 2) Harmonization of tunnel safety organization in Member States, defining the roles and responsibilities of the various subjects involved; 3) Harmonization of road signs and marking

12 1. Safety standards for road and railway tunnels 1.5 Road Tunnel Safety Directve 54/2004/EC) Contribution of Alpine countries: Clear strategic lines and safety objectives Each technical rule is based on technical-scientific criteria (without details) For existing tunnels, risk analysis can be used to satisfy technical requirements

13 1. Safety standards for road and railway tunnels 1.6 Railway Tunnel Safety New standards: Clear reference standard for the objective and quantitative analysis of railway tunnel safety Transition from a logic of rigidly preset standards to that of quantified system safety objectives Optimal balance between the safety objectives to be satisfied and the relative technical and economic consequences Sufficiency of minimum requirements: Successful evacuation of passengers (self-rescue) in the hypothesis of a central fire and advance of the smoke wall through the tunnel Safety conditions are determined: Trend of the concentrations of toxic products from combustion Concentration of oxygen Visibility along the tunnel and passenger evacuation times

14 1. Safety standards for road and railway tunnels 1.6 Railway Tunnel Safety Risk analysis for railway tunnel safety: Risk analysis is proposed: (1) probability of occurrence; and (2) indicator of gravity Measures and devices for the reduction of the risk to be adopted, the analysis is repeated in order to analyze the residual risk Safety measures and devices that aim to reduce risk must distinguish (ref. UIC document Codex Safety in Railway Tunnels ) between: Prevention measures Protection measures Measures facilitating the escape from hazard sites (self-escape) Measures facilitating rescue operations

15 2. Upgrading the Arlberg Tunnel to current safety standards 2.1 Current situaton The Arlberg road tunnel has a length of some 15.5 km and is in operation for more than 35 years: It is a single tube tunnel operated with bidirectional traffic, but carries a quite low traffic volume Hence, the construction of a second tube is not really cost effective The tunnel is equipped with a transversal ventilation system with remotely controlled smoke extraction dampers providing smoke extraction every 100 m The maximum distance between egress possibilities to a save environment is some 1500 m After 35 years in operation: Upgrading for the electromechanical installations is needed to meet the requirements of the EU directive and the state of the art of safety systems defined in the Austrian guidelines (RVS , 2014; RVS , 2014) According to the EU directive, the maximum distance between aggress must not exceed 500 m

16 2. Upgrading the Arlberg Tunnel to current safety standards 2.2 Tunnel system The Arlberg railway tunnel runs almost in parallel to the road tunnel: This railway tunnel is part of the TransEuropean (Rail) Network (TEN) and had also to fulfill the minimum safety requirements for such railway tunnels These regulations however require egress possibility to a safe environment every 1700 m The fulfillment of the national and international directives requires a construction of additionally 37 egress ways An erection of further cross passages between the rail and road tunnel proved to be not cost effective due to the high distance between two tunnels (up to 300 m)

17 2. Upgrading the Arlberg Tunnel to current safety standards 2.3 Evacuaton concept Based on the feasibility study the following solution was chosen: Between the existing cross passages to the railway tunnel the fresh air ducts will serve in future as egress ways: New egress possibility from the road level up into the egress way in the fresh air duct The chosen solution minimizes construction costs, it has big implications on existing vital systems like ventilation In addition special fire protection has to be foreseen for the false ceiling between road and fresh air duct mist system was selected to serve for this purpose

18 2. Upgrading the Arlberg Tunnel to current safety standards 2.4 Ventlaton current situaton The tunnel is currently equipped with a full-transverse ventilation system with six ventilations sections, two vertical shafts (736 and 218 m) and two portal stations: Each section is currently ventilated by one fresh and one exhaust air fan The ventilation scheme, where VS1 to VS6 denote the ventilation sections, F1 to F6 and E1 to E6, denote the fresh and the exhaust air fans

19 2. Upgrading the Arlberg Tunnel to current safety standards 2.5 Ventlaton future situaton Ventilation design is driven by the needs for ventilation in incident situations with fire (fire ventilation): Hence the driver parameter for ventilation design is the required smoke extraction rate during incidents with fire The usage of the existing fresh air fans for air injection is appropriate This requires the installation of Saccado type fresh air injection dampers (FAID) and sealing door within the fresh air duct The scheme of the upgraded ventilation system with the FAIDs and three additional jet fans (JF1 to JF3)

20 2. Upgrading the Arlberg Tunnel to current safety standards 2.6 Jet fans The advantage of this system is that existing fans can be used and structural adaptations inside the tunnel can be reduced to a minimum: Normally such big fans should be mounted in ventilation niches on both sides of the tunnel However, in the special case of the Arlberg tunnel it was considered that the opening of the tunnel lining which would be required for constructing the fan niches would be too risky and costly due to possible drainage and structural problems Hence a positioning of the fans at the ceiling in the region of the extraction duct proved to be an appropriate solution

21 2. Upgrading the Arlberg Tunnel to current safety standards 2.7 Ventlaton control concept As the tunnel is equipped with a fully transverse ventilation system smoke extraction will be performed by opening remotely controlled dampers in close proximity to the fire location: Smoke will be extracted in to the exhaust gas duct. However, smoke confinement needs active control of the air/smoke movement inside the tunnel On the basis of numerical simulations fire ventilation scenarios were simulated and the system capability checked: The design fire size for ventilation was chosen in accordance to the Austrian guideline RVS with a heat release rate of 30 MW The numerical simulations were performed with a 1D model based on the conservation of mass, momentum and heat

22 2. Upgrading the Arlberg Tunnel to current safety standards 2.8 Ventlaton control numerical simulaton It is shown a scenario for a fire in ventilation section VS6: Close to the fire location a mass flow of 144 kg/s smoke/air is to be extracted In order to achieve symmetrical flow from both portals towards the extraction location the usage of the FAID1 and FAID2 as well as of the jet fans JF1 and JF2 is needed In addition air extraction is required in section VS6 In this particular case, various exhaust air and fresh air supply fans as well as the jet fans are needed at the same time in order to reach the required ventilation goal The remaining fresh air fans are needed to vent the escape route vie the fresh air duct

23 2. Upgrading the Arlberg Tunnel to current safety standards 2.9 Fire protecton of the structure The erection of an egress way to close to a possible fire source at road level poses the requirement of special protection of the structure: Various measures for structure protection are available Starting from application of fire resistant slabs to installation of water based systems The requirement for action as structure protection is given in the Austrian guideline (RVS , 2006) Basic design parameters are given in the Austrian guideline RVS , 2014: The system has to be designed in order to operate over a time of 120 minutes

24 2. Upgrading the Arlberg Tunnel to current safety standards 2.10 High pressure water mist systems High pressure water mist systems have proven to be an effective mean for fire suppression: The high pressure water mist system enables the water mist to penetrate into a fire in liquid form and result in cooling due to evaporation at specific locations High pressure water mist also effectively tills up the protected space and provides superior cooling, hence protecting surrounding equipment and structures

25 3. Conclusions 1. After dramatic events in various long tunnels, safety measures seemed inadequate. Thus, the European Directive 54/2004/EC represents a turning point in the field of safety in the use of transport infrastructures and tunnels in particular. 2. A scientific approach was implemented that allows evaluation of all rias factors (in terms of intensity and probability) for the identification, monitoring and reduction of accidents. 3. Due to Austria has developed many of its transportation infrastructure before the Directive, the challenges and tendency for the coming years are to upgrade the existing infrastructure in order to satisfy the minimum requirements based on economical feasibility. 4. The upgrading of the existing Arlberg tunnel has to fulfill the requirements posed in the EU directive on minimum safety of road tunnels. In addition, the upgrading has to be done under the focus of limitations of civil works. 5. For the development of new infrastructure in Austria, risk management has been used for the very beginning of a design process. Risk management and risk control are very useful

26 MUCHAS GRACIAS POR LA ATENCIÓN

27

Impact of quick incident detection on safety in terms of ventilation response

Impact of quick incident detection on safety in terms of ventilation response Impact of quick incident detection on safety in terms of ventilation response P. J. Sturm 1) ; C. Forster 2) ; B. Kohl 2) ; M. Bacher 1) 1) Institute for Internal Combustion Engines and Thermodynamics

More information

Road tunnel safety rules in Italy: the tunnel country

Road tunnel safety rules in Italy: the tunnel country Safety and Security Engineering II 317 Road tunnel safety rules in Italy: the tunnel country M. Guarascio, M. Lombardi, G. Rossi & G. Sciarra Safety Engineering Sapienza, Rome University, Italy Abstract

More information

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION - 165 - CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT

More information

Tunnels, Risks & Design Mitigation

Tunnels, Risks & Design Mitigation Safe roads, Reliable journeys, Informed travellers Tunnels, Risks & Design Mitigation Eamonn Colgan HA Senior Project Manager & John Celentano Mouchel Ltd, Tunnel Technical Director Introduction Eamonn

More information

FIRE RESISTANCE OF ROLLING STOCK ELEMENTS STANDARD AND SPECIAL CASE OF TUNNELS

FIRE RESISTANCE OF ROLLING STOCK ELEMENTS STANDARD AND SPECIAL CASE OF TUNNELS FIRE RESISTANCE OF ROLLING STOCK ELEMENTS 45545-3 STANDARD AND SPECIAL CASE OF TUNNELS www.efectis.com May 2016 1 SUMMARY EN 45545-3 What is a fire barrier? Requirements regarding fire resistance Tests

More information

Sprinklers Modeling for Tunnel Road Fire Fighting

Sprinklers Modeling for Tunnel Road Fire Fighting Sprinklers Modeling for Tunnel Road Fire Fighting P. Ciambelli, M.G. Meo, P. Russo, S. Vaccaro Department of Chemical and Food Engineering, University of Salerno - ITALY 1. INTRODUCTION Loss of lives and

More information

Gerd Koffmane, Henrik Hoff, AP Sensing GmbH, Böblingen

Gerd Koffmane, Henrik Hoff, AP Sensing GmbH, Böblingen Linear Heat Series Under Test: Extensive fire tests prove Distributed Temperature Sensing (DTS) enables fast and reliable control of fire protection systems in road and rail tunnels Gerd Koffmane, Henrik

More information

The first tunnel fire. Benefits of fire

The first tunnel fire. Benefits of fire Benefits of fire suppression Quantifying the effects of suppression on energy release. This article by Fathi Tarada, managing director of fire safety, risk management, ventilation and CFD consultant Mosen

More information

FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS

FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS - 203 - FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS Hofer R., IBS Institute for Technical Fire Protection and Safety Research, Linz / Austria

More information

Ventilation for Smoke Control, Fire Control & Life Safety in Tunnels. Dr. Ricky Carvel BRE Centre for Fire Safety Engineering University of Edinburgh

Ventilation for Smoke Control, Fire Control & Life Safety in Tunnels. Dr. Ricky Carvel BRE Centre for Fire Safety Engineering University of Edinburgh Ventilation for Smoke Control, Fire Control & Life Safety in Tunnels Dr. Ricky Carvel BRE Centre for Fire Safety Engineering University of Edinburgh Tunnel Ventilation? Tunnel ventilation was invented

More information

PHASED CONSTRUCTION AND SAFETY IN MALA KAPELA TUNNEL

PHASED CONSTRUCTION AND SAFETY IN MALA KAPELA TUNNEL - 119 - ABSTRACT: PHASED CONSTRUCTION AND SAFETY IN MALA KAPELA TUNNEL Darko Šaric Civil Engineering Institute of Croatia Croatia, 10.000 Zagreb, J. Rakuše 1 e-mail: dsaric@zg.igh.hr Goran Legac Croatian

More information

Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel

Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel Safety and Security Engineering VI 73 Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel M. Lombardi & G. Rossi Dipartimento di Ingegneria Chimica

More information

Full-scale Experiment of Longitudinal Ventilation Smoke Control System and Central Smoke Exhaust System in City Underwater Tunnel

Full-scale Experiment of Longitudinal Ventilation Smoke Control System and Central Smoke Exhaust System in City Underwater Tunnel Available online at www.sciencedirect.com Procedia Engineering 52 ( 2013 ) 330 335 Full-scale Experiment of Longitudinal Ventilation Smoke Control System and Central Smoke Exhaust System in City Underwater

More information

EXPERIENCE WITH THE SAFETY AND VENTILATION DESIGN IN OPERATION OF THE PLABUTSCH TUNNEL

EXPERIENCE WITH THE SAFETY AND VENTILATION DESIGN IN OPERATION OF THE PLABUTSCH TUNNEL - 313 - EXPERIENCE WITH THE SAFETY AND VENTILATION DESIGN IN OPERATION OF THE PLABUTSCH TUNNEL Waltl A. 1 and Michelitsch F. 2 1 Styrian Government, Department for Technical Equipment (FA 189 Landhausgasse

More information

International Seminar on Long Tunnels - October 17-19, 2012 CHILE Santiago World Road Association (PIARC )

International Seminar on Long Tunnels - October 17-19, 2012 CHILE Santiago World Road Association (PIARC ) TUNNEL MANAGEMENT IN QUEBEC (CANADA) Maintenance, Operation and Safety Management of urban Road Tunnels in Canada INTERNATIONAL SEMINAR ON LONG TUNNELS Chile, Santiago (October 17-19, 2012) Alexandre Debs,

More information

Impact of Tunnel Ventilation on Tunnel Fixed Fire Suppression System

Impact of Tunnel Ventilation on Tunnel Fixed Fire Suppression System Impact of Tunnel Ventilation on Tunnel Fixed Fire Suppression System Igor Maevski, PhD, PE Jacobs Engineering, ASHRAE Member Raymond C. Klein, PE Jacobs Engineering, ASHRAE Member ABSTRACT Recently there

More information

OVERCOMING EVACUATION LIMITATIONS OF THE UČKA TUNNEL BY IMPROVEMENT OF FIRE SAFETY MEASURES

OVERCOMING EVACUATION LIMITATIONS OF THE UČKA TUNNEL BY IMPROVEMENT OF FIRE SAFETY MEASURES - 119 - OVERCOMING EVACUATION LIMITATIONS OF THE UČKA TUNNEL BY IMPROVEMENT OF FIRE SAFETY MEASURES Drakulić M., Lozica M. Brodarski institute d.o.o., Zagreb, Croatia ABSTRACT This paper considers a possible

More information

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED - 133 - STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED Y. Mikame 1,2, N. Kawabata 1, M. Seike 1, M. Hasegawa 1 1 Kanazawa University, Japan 2 Metropolitan Expressway Company

More information

The investigation of accidents and incidents in complex railway tunnel systems

The investigation of accidents and incidents in complex railway tunnel systems The investigation of accidents and incidents in complex railway tunnel systems Some background The Rail Accident Investigation Branch (RAIB) has investigated two fires involving freight shuttles in the

More information

EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT TASK 363)

EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT TASK 363) EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT 20-07 TASK 363) Louis Ruzzi PennDOT District 11 Igor Maevski, PhD, PE - Jacobs Agenda AASHTO T20 Technical Committee Roadway Tunnels

More information

Fire Protection and Safety in Tunnels Conference Opening Remarks. Dr Fathi Tarada Secretary, PIARC Tunnel Operations Committee

Fire Protection and Safety in Tunnels Conference Opening Remarks. Dr Fathi Tarada Secretary, PIARC Tunnel Operations Committee Fire Protection and Safety in Tunnels Conference Opening Remarks Dr Fathi Tarada Secretary, PIARC Tunnel Operations Committee Agenda Background to the conference Key themes Recent tunnel fires Major infrastructure

More information

Tunnel Axial Flow Fan

Tunnel Axial Flow Fan Tunnel Axial Flow Fan TUNNEL AXIAL FLOW FAN Tunnel fans are an axial flow fans and moves an airstream along the axis of the fan. The air is pressurized by the aerodynamic lift generated by the fan blades,

More information

Safety Inspections of Road Tunnels.

Safety Inspections of Road Tunnels. Safety Inspections of Road Tunnels. G. Llopis. Road Department, Ministry of Public Works, Madrid, Spain. F. Portugués Geocontrol S.A., Madrid, Spain. ABSTRACT: Road tunnels have several systems to ensure

More information

The Mont Blanc tunnel project. Eric CESMAT, Sylvain DESANGHERE

The Mont Blanc tunnel project. Eric CESMAT, Sylvain DESANGHERE The Mont Blanc tunnel project Eric CESMAT, Sylvain DESANGHERE 24/09/2009 International water mist conference 2009 Fires in tunnel Car fire > 4 to 8 MW Van fire > 15 MW HGV fire > 30 MW Big HGV fire > 100

More information

SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM

SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM - 157 - SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM Kratzmeir S. FOGTEC Fire Protection, Research & Development, Germany Keywords: Fire Protection, Fire suppression,

More information

BUILDING INDUSTRY TUNNEL RAIL TUNNEL FIRE FIGHTING WITH HIGH PRESSURE WATER MIST

BUILDING INDUSTRY TUNNEL RAIL TUNNEL FIRE FIGHTING WITH HIGH PRESSURE WATER MIST BUILDING INDUSTRY TUNNEL RAIL TUNNEL FIRE FIGHTING WITH HIGH PRESSURE WATER MIST FIRE FIGHTING IS RESPONSIBILITY Fire monitoring Fire detection Fire suppression We are a leading international supplier

More information

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS Yunlong Liu*, Xijuan Liu and Bradley Paroz Fire Science and Technology Laboratory CSIRO Manufacturing and Infrastructure Technology

More information

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Y Liu, J Munro Parsons Brinckerhoff Australia B Dandie Thiess Pty Ltd., Australia ABSTRACT Emergency smoke ventilation

More information

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS Yunlong Liu*, Xijuan Liu and Bradley Paroz Fire Science and Technology Laboratory CSIRO Manufacturing and Infrastructure Technology PO Box 310 North

More information

EXPERIENCES ON THE SPECIFICATION OF ALGORITHMS FOR FIRE AND SMOKE CONTROL IN ROAD TUNNELS

EXPERIENCES ON THE SPECIFICATION OF ALGORITHMS FOR FIRE AND SMOKE CONTROL IN ROAD TUNNELS - 39 - EXPERIENCES ON THE SPECIFICATION OF ALGORITHMS FOR FIRE AND SMOKE CONTROL IN ROAD TUNNELS Espinosa, I.*; Fernández, S.*; Del Rey, I. + ; Alarcón, E. 2+ * FFII - CEMIM. Madrid. Spain. + ETSII-Universidad

More information

An experimental study of the impact of tunnel suppression on tunnel ventilation

An experimental study of the impact of tunnel suppression on tunnel ventilation An experimental study of the impact of tunnel suppression on tunnel ventilation Yoon J. Ko and George Hadjisophocleous Civil and Environmental Engineering, Carleton University 1125 Colonel By Drive, Ottawa,

More information

Appendix SPAIN Madrid M30-Río-TUNNEL

Appendix SPAIN Madrid M30-Río-TUNNEL Appendix 2.17 - SPAIN Madrid M30-Río-TUNNEL 1. INTRODUCTION The M30-Río Tunnel is located in Madrid (Spain), a city of about 3,200,000 inhabitants. The M30 is the main ring road, linking all the neighbourhoods

More information

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE 1 RU ZHOU, 2 WEI ZHANG 1 School of Urban Construction and Safety Engineering, Nanjing University of Technology, Nanjing

More information

Tunnel Fire Dynamics and Evacuation Simulations

Tunnel Fire Dynamics and Evacuation Simulations Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation

More information

Hot Issues in Fire Engineering 12 March 2013

Hot Issues in Fire Engineering 12 March 2013 Hot Issues in Fire Engineering 12 March 2013 An Update on Design Fires of Vehicular Tunnels W.K. Chow Fellow, Hong Kong Academy of Engineering Sciences Research Centre for Fire Engineering, Department

More information

Appendix AUSTRIA Vienna Kaisermühlentunnel

Appendix AUSTRIA Vienna Kaisermühlentunnel Appendix 2.1 - AUSTRIA Vienna Kaisermühlentunnel 1. SUMMARY A NEW MULTIMODAL TUNNEL The Kaisermühlen tunnel is located in the city of Vienna (Austria). The Kaisermühlen tunnel is a motorway tunnel in Vienna

More information

Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS)

Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS) Fire Protection Leaflet Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS) 0 General Regulations and recommendations missing from this leaflet do not entitle

More information

The Use of Public Address System to Improve Tunnel Safety - Current Practices. Lim Hock Tay

The Use of Public Address System to Improve Tunnel Safety - Current Practices. Lim Hock Tay The Use of Public Address System to Improve Tunnel Safety - Current Practices Lim Hock Tay Content 1 Introduction 2 3 Overview of Survey Responses Discussion 4 Conclusion PIARC International Conference

More information

State of the Road Tunnel Safety Technology in Japan. Hideto Mashimo 1

State of the Road Tunnel Safety Technology in Japan. Hideto Mashimo 1 State of the Road Tunnel Safety Technology in Japan by Hideto Mashimo 1 ABSTRACT As more and more tunnels have been constructed to develop new road network through mountainous ranges or to avoid environmental

More information

TUNPROTEC. Active Tunnel Fire Protection

TUNPROTEC. Active Tunnel Fire Protection VID FIre KIll TUNPROTEC Active Tunnel Fire Protection 9 An Active Tunnel Fire General The tunnel structures are very valuable. Infrastructure tunnels, such as train tunnels and road tunnels represent very

More information

THE GOTTHARD BASE TUNNEL: FIRE / LIFE SAFETY SYSTEM

THE GOTTHARD BASE TUNNEL: FIRE / LIFE SAFETY SYSTEM 8.33 THE GOTTHARD BASE TUNNEL: FIRE / LIFE SAFETY SYSTEM The 6 th annual Tunnelling Conference Sydney 30 th & 31 st August 2004 by Davide Fabbri, Chief designer Engineering joint-venture Gotthard Base

More information

THE AUTOMATION OF THE VENTILATION RESPONSE IN THE CASE OF A FIRE IN A TUNNEL

THE AUTOMATION OF THE VENTILATION RESPONSE IN THE CASE OF A FIRE IN A TUNNEL - 9 - THE AUTOMATION OF THE VENTILATION RESPONSE IN THE CASE OF A FIRE IN A TUNNEL ABSTRACT E. Casalé, H. Biollay, B. Houseaux, J. Przeczewski Scetauroute Tunnelling Division Annecy, France In 999, the

More information

Effective Firefighting Operations in Road Tunnels

Effective Firefighting Operations in Road Tunnels Effective Firefighting Operations in Road Tunnels SP Technical Research Institute of Sweden Hak Kuen Kim, Anders Lönnermark and Haukur Ingason Fire Technology SP Report 2010:10 Effective Firefighting Operations

More information

EARLY FIRE DETECTION IN SWISS ROAD TUNNELS WITH MORE THAN FIREGUARD SENSORS

EARLY FIRE DETECTION IN SWISS ROAD TUNNELS WITH MORE THAN FIREGUARD SENSORS - 87 - EARLY FIRE DETECTION IN SWISS ROAD TUNNELS WITH MORE THAN 1 500 FIREGUARD SENSORS W.W. Schuldt SIGRIST-PHOTOMETER AG, Switzerland ABSTRACT Major fire incidents in road tunnels with a larger number

More information

Emergency Ventilation System Design - Preliminary Report Shishir Gupta

Emergency Ventilation System Design - Preliminary Report Shishir Gupta Emergency Ventilation System Design - Preliminary Report Shishir Gupta (shishir@mechartes.com), Abstract The existing stations and tunnels of Metro Railway, Kolkata are not equipped with effective emergency

More information

IMPROVING VENTILATION AND PASSIVE PROTECTION WITH FFFS

IMPROVING VENTILATION AND PASSIVE PROTECTION WITH FFFS - 195 - IMPROVING VENTILATION AND PASSIVE PROTECTION WITH FFFS Rajko Rothe; IFAB, Berlin, Germany Max Lakkonen and Dirk Sprakel, FOGTEC Fire Protection, Cologne, Germany ABSTRACT This paper discusses the

More information

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles Peter Stahl Wagner Schweiz AG, Wallisellen, Switzerland Abstract Fire detection system and firefighting solutions are getting a

More information

VENTILATION AND SUPPRESSION SYSTEMS IN ROAD TUNNELS: SOME ISSUES REGARDING THEIR APPROPRIATE USE IN A FIRE EMERGENCY

VENTILATION AND SUPPRESSION SYSTEMS IN ROAD TUNNELS: SOME ISSUES REGARDING THEIR APPROPRIATE USE IN A FIRE EMERGENCY VENTILATION AND SUPPRESSION SYSTEMS IN ROAD TUNNELS: SOME ISSUES REGARDING THEIR APPROPRIATE USE IN A FIRE EMERGENCY Ricky Carvel, Guillermo Rein & José L. Torero BRE Centre for Fire Safety Engineering,

More information

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection Julio Toko, Martin Fromme, Bernd Horbach and Wieland Hill LIOS Technology GmbH, Cologne, Germany

More information

S. Fehleisen, ÖBB-Infrastruktur AG J. Frießnegg; ARGE KAT2, Austria

S. Fehleisen, ÖBB-Infrastruktur AG J. Frießnegg; ARGE KAT2, Austria - 21 - INCIDENT TESTED: RESCUE, EVACUATION AND FIRE PROTECTION AT THE KORALM TUNNEL 2 A REVIEW OF THE FIRE EVENT IN 2015 AND THE PRACTICAL IMPLEMENTATION OF THE CONCEPT IN THE EVENT OF AN INCIDENT S. Fehleisen,

More information

THE NECESSITY OF FIRE TESTS USING THE PASSÜR TUNNEL AS AN EXAMPLE

THE NECESSITY OF FIRE TESTS USING THE PASSÜR TUNNEL AS AN EXAMPLE - 287 - THE NECESSITY OF FIRE TESTS USING THE PASSÜR TUNNEL AS AN EXAMPLE Wolfgang Stroppa TIWAG - Tiroler Wasserkraft AG Eduard Wallnöfer Platz 2 A-6010 Innsbruck Fax no.: +43 / (0)512 / 506-2778 E-mail:

More information

Optimisation of ventilation systems costs by using fixed fire fighting systems (FFFS) in tunnels

Optimisation of ventilation systems costs by using fixed fire fighting systems (FFFS) in tunnels Optimisation of ventilation systems costs by using fixed fire fighting systems (FFFS) in tunnels Rajko Rothe IFAB Institute for applied fire safety research, Berlin, Germany Max Lakkonen, Tobias Hoffmann

More information

Road Tunnel Classification System for Fire Brigades Prof. Haukur Ingason SP

Road Tunnel Classification System for Fire Brigades Prof. Haukur Ingason SP Road Tunnel Classification System for Fire Brigades Prof. Haukur Ingason SP The presentation 1. Background and objectives 2. Exemples of tactics 3. The concept basis 4. The classification system 5. Conclusions

More information

Innovative Solutions for Active Fire Protection in Road/Rail Tunnels and Underground Facilities

Innovative Solutions for Active Fire Protection in Road/Rail Tunnels and Underground Facilities Innovative Solutions for Active Fire Protection in Road/Rail Tunnels and Underground Facilities Roger A. Dirksmeier, FOGTEC Fire Protection, Germany Fire Protection Conference Tel Aviv, 4 th of April 2016

More information

AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION

AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION Generals Caccialanza & C. developed in the last years some technologically very innovative products, aimed to provide a very

More information

Application of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall. Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia

Application of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall. Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia Application of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia A Challenging Application for the New Italian Fire Code

More information

Aspirating Gas Detection CFD Modelling Predicts Application Performance

Aspirating Gas Detection CFD Modelling Predicts Application Performance Aspirating Gas Detection CFD Modelling Predicts Application Performance Yun Jiang Xtralis, Bentleigh East, Australia Claudio Groppetti Xtralis, Avon, MA, USA Abstract Historically gas detection has utilized

More information

FIXED FIRE FIGHTING SYSTEMS IN TUNNELS INTEGRATION AND COMPENSATION

FIXED FIRE FIGHTING SYSTEMS IN TUNNELS INTEGRATION AND COMPENSATION FIXED FIRE FIGHTING SYSTEMS IN TUNNELS INTEGRATION AND COMPENSATION Stefan Kratzmeir*, IFAB Institute for applied fire safety research, Rostock, Germany Max Lakkonen, FOGTEC Fire Protection, Cologne, Germany

More information

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada

More information

1. PIARC Update 2. Tunnel System

1. PIARC Update 2. Tunnel System 1. PIARC Update 2. Tunnel System 2017 AASHTO T-20 Bijan Khaleghi WSDOT Bridge & Structures Office PIARC Update -1 PIARC: Technical Committee D.5 Road Tunnels Working Group 5: Large underground interconnected

More information

Jonathan Redding Area Sales Manager FOGTEC Fire Protection Cologne, Germany

Jonathan Redding Area Sales Manager FOGTEC Fire Protection Cologne, Germany Making rail systems more efficient by using on-board Fire Protection Systems Jonathan Redding Area Sales Manager FOGTEC Fire Protection Cologne, Germany Key Presentation Take-Aways Holistic approach to

More information

Crossrail. Clare Hebden; September 2012

Crossrail. Clare Hebden; September 2012 Crossrail Clare Hebden; 12-13 September 2012 The Route Fire Safety challenges of building 21km railway under a busy city Functional, safe and affordable railway Finding and obtaining space for : Stations,

More information

CFD STUDY OF FIRE PROTECTION SYSTEMS IN TUNNEL FIRES

CFD STUDY OF FIRE PROTECTION SYSTEMS IN TUNNEL FIRES UDC 614.84 : 628.854 : 52-17 DOI: 10.7562/SE2011.1.01.03 Original article www.safety.ni.ac.rs DARKO ZIGAR 1 DESIMIR JOVANOVIĆ 2 MARTINA ZDRAVKOVIĆ 3 1-4 University of Niš, Faculty of Occupational Safety

More information

Tunnel. Neumarkt. Stationary Fire Protection Case Study

Tunnel. Neumarkt. Stationary Fire Protection Case Study Tunnel Neumarkt Stationary Fire Protection Case Study Rosenbauer Tunnel Case Study Every second counts in an emergency. Tunnel extinguishing systems from Rosenbauer. Making tunnels safer. The catastrophic

More information

INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS

INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS SUMMARY Ammonia odours were reported in the community close to the time of the incident (Appendix D) and firefighters reported

More information

Research on Mobile Water Spray Device Reducing the Temperature of Metro Fire

Research on Mobile Water Spray Device Reducing the Temperature of Metro Fire Applied Mechanics and Materials Online: 2012-05-14 ISSN: 1662-7482, Vols. 166-169, pp 2731-2734 doi:10.4028/www.scientific.net/amm.166-169.2731 2012 Trans Tech Publications, Switzerland Research on Mobile

More information

Increasing Fire Safety of Cologne Main Station by High Pressure Water Mist

Increasing Fire Safety of Cologne Main Station by High Pressure Water Mist Increasing Fire Safety of Cologne Main Station by High Pressure Water Mist Dipl.-Ing. Rüdiger Kopp FOGTEC Fire Protection ruediger.kopp@fogtec.com 1 Background of this Presentation In recent years the

More information

EUROPEAN BUREAU. EuroTAP European Tunnel Assessment Programme

EUROPEAN BUREAU. EuroTAP European Tunnel Assessment Programme EUROPEAN BUREAU EuroTAP European Tunnel Assessment Programme Piedicastello Brennero History: 1999: 20 tunnels tested 2000: 25 tunnels tested 2001: 16 tunnels tested 2002: 31 tunnels tested 2003: 25 tunnels

More information

Considerations in the Design of Smoke Management Systems for Atriums

Considerations in the Design of Smoke Management Systems for Atriums Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke

More information

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,

More information

VENTILATION & FIRE SAFETY

VENTILATION & FIRE SAFETY VENTILATION & FIRE SAFETY CONTENTS Company: ANALISIS-DSC Case Studies: Metro Station (Fire). Parking (Fire). Tunnel (Fire). Intermodal Facility (Ventilation) Contact ANALISIS-DSC ANALISIS-DSC is The reference

More information

Fire Protection and Safety in Tunnels 2017 Overview of tunnelling and technology challenges

Fire Protection and Safety in Tunnels 2017 Overview of tunnelling and technology challenges Overview of tunnelling and technology challenges Bergen West coast of Norway County: 254 road tunnels (222 km) / 111 road tunnels > 500 m (195 km ) 4 road tunnels (15 km) under construction in Bergen West

More information

Modeling a real backdraft incident fire

Modeling a real backdraft incident fire Advanced Computational Methods in Heat Transfer IX 279 Modeling a real backdraft incident fire A. Tinaburri 1 & M. Mazzaro 2 1 Central Direction for Prevention and Technical Safety, Firefighters, Public

More information

Smoke control in car parks

Smoke control in car parks Smoke control in car parks The actual situation in CEN TC 191 SC1 WG9 Imagine the result Jean-Claude DE SMEDT MIFireE,MSFPE,MNFPA Senior Fire Safety Engineering Consultant @ ARCADIS Belgium Convener of

More information

SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE

SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE - 249 - SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE Urs Welte Amstein + Walthert AG, Switzerland ABSTRACT The paper aims at a detailed analysis of the current know-how in the construction of tunnel cabling

More information

Research Needs for the Fire Safety Engineering Profession

Research Needs for the Fire Safety Engineering Profession Research Needs for the Fire Safety Engineering Profession Note: Items highlighted in RED are identified as the highest priority for each thread. Items highlighted in BOLD are identified as the highest

More information

Enclosure 4- RISK ASSESSMENT

Enclosure 4- RISK ASSESSMENT Enclosure 4- RISK ASSESSMENT RISK ASSESSMENT Risk is a potential that a chosen action or activity will lead to a loss of human or property. Risk assessment is a step for Risk Management. Risk assessment

More information

SIGNALISATION AND VISUAL GUIDE INTERACTIVE SYSTEM for EVACUATION ROUTES in TUNNELS and CONFINED AREAS

SIGNALISATION AND VISUAL GUIDE INTERACTIVE SYSTEM for EVACUATION ROUTES in TUNNELS and CONFINED AREAS SIGNALISATION AND VISUAL GUIDE INTERACTIVE SYSTEM for EVACUATION ROUTES in TUNNELS and CONFINED AREAS 19-03-2010 rev.3 P_gal_5a_EN page 1 Description and technical data of the system Innovating system

More information

Tokyo-wan Aqualine - Experience of Traffic and Safety

Tokyo-wan Aqualine - Experience of Traffic and Safety Hisashi Iwata, Chief Engineer, Maintenance and Traffic Operation Department, Japan Highway Public Corporation, Japan Yoshikazu Ota, Chiyoda Engineering Consultants Co., Ltd., Japan 1. General planning

More information

FORMULATION OF FIRE SAFETY REQUIREMENTS FOR NEW RAILWAY INFRASTRUCTURES

FORMULATION OF FIRE SAFETY REQUIREMENTS FOR NEW RAILWAY INFRASTRUCTURES FORMULATION OF FIRE SAFETY REQUIREMENTS FOR NEW RAILWAY INFRASTRUCTURES Ir Law Chi Keung, Peter Hong Kong Fire Services Department, Railway Development Strategy Division, 2/F Tung Lo Wan Fire Station,

More information

1 Development and state of the art in road tunnel ventilation technology

1 Development and state of the art in road tunnel ventilation technology 1 Development and state of the art in road tunnel ventilation technology Dipl.-Ing. Wolfgang Müller, Zweibrücken Dipl.-Phys. Jürgen Steltmann, Zweibrücken Development and state of the art in road tunnel

More information

Third Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG

Third Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG 1 Third Runway Project APM Depot Fire Engineering Design Presented by Ir Wilson Sau-kit TSANG 1 2 Presentation Overview 1. Project Background and Depot Overview 2. Building Information and Challenge for

More information

UL MATERIAL YELLOW CARD GRILON ANNEX Material certificates : Background information and classification information acc. to EN 45545-2 The European standard EN 45545-2 classifies the requirements for fire

More information

Case Study 1 Underground Car Park

Case Study 1 Underground Car Park Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building

More information

This document is a preview generated by EVS

This document is a preview generated by EVS TECHNICAL REPORT ISO/TR 15657 First edition 2013-06-15 Fire resistance tests Guidelines for computational structural fire design Essais de résistance au feu Lignes directrices sur la conception statistique

More information

FROM THE CLASSICAL FIRE-FIGHTING WATER SUPPLY TO STRUCTURE AND SMOKE-GAS COOLING, TAKING THE GLEINALM TUNNEL AS AN EXAMPLE, PART I

FROM THE CLASSICAL FIRE-FIGHTING WATER SUPPLY TO STRUCTURE AND SMOKE-GAS COOLING, TAKING THE GLEINALM TUNNEL AS AN EXAMPLE, PART I - 123 FROM THE CLASSICAL FIRE-FIGHTING WATER SUPPLY TO STRUCTURE AND SMOKE-GAS COOLING, TAKING THE GLEINALM TUNNEL AS AN EXAMPLE, PART I Ch. Kaiser Business manager of Kaiser & Mach ZT-GmbH 1. INTRODUCTION

More information

Knorr-Bremse Group. Presentation of EDT101. Working Group on Derailment Detection Rome, October 13 th 15 th, Knorr-Bremse Group

Knorr-Bremse Group. Presentation of EDT101. Working Group on Derailment Detection Rome, October 13 th 15 th, Knorr-Bremse Group Knorr-Bremse Group Presentation of EDT101 Working Group on Derailment Detection Rome, October 13 th 15 th, 2014 Knorr-Bremse Group Motivation for the Development of Derailment Detectors In the 1990s there

More information

The Physical Environment Portal: Module 5, LS Leadership

The Physical Environment Portal: Module 5, LS Leadership The Physical Environment Portal: Module 5, LS.02.01.10 - Leadership Fire Safety: Background Fire safety impacts both the lives of the occupants and the physical structures. In the early 1900 s many buildings

More information

( )

( ) Course Title: Fire Dynamics (3087) Course Number: FST - 3087 Course Credit Hours: (3) Three Semester Hours Instructor Information: Bernard W. Becker, III, MS (937-751-7371) ccfdchiefbecker@yahoo.com Textbook:

More information

5. Land use database applications

5. Land use database applications 48 Towards an urban atlas 5. Land use database applications The Murbandy/Moland project is a continuously evolving activity. To date, the territorial data sets have been completed and validated for 25

More information

Smoke Control Requirements for New Railway Infrastructure. Ir Peter Law

Smoke Control Requirements for New Railway Infrastructure. Ir Peter Law Smoke Control Requirements for New Railway Infrastructure Ir Peter Law Overview Railway Development in Hong Kong Regulatory Regime for Railway Fire Safety Formulation of Fire Safety Requirements Smoke

More information

REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS

REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS Nikola TANASIĆ, Tomislav SIMONOVIĆ, Miloš IVOŠEVIĆ, Branislav

More information

2 nd European Forum of Road Tunnel Safety Officers

2 nd European Forum of Road Tunnel Safety Officers 2 nd European Forum of Road Tunnel Safety Officers Brussels, 18 January 2012 How to define a continuous process to improve safety? Bernt Freiholtz How to define a continuous process to improve safety?

More information

BUSINESS PLAN CEN/TC 305 POTENTIALLY EXPLOSIVE ATMOSPHERES EXPLOSION PREVENTION AND PROTECTION EXECUTIVE SUMMARY

BUSINESS PLAN CEN/TC 305 POTENTIALLY EXPLOSIVE ATMOSPHERES EXPLOSION PREVENTION AND PROTECTION EXECUTIVE SUMMARY BUSINESS PLAN CEN/TC 305 POTENTIALLY EXPLOSIVE ATMOSPHERES EXPLOSION PREVENTION AND PROTECTION CEN/TC 305 Business Plan Page: 1 Business environment, benefits and priorities EXECUTIVE SUMMARY CEN/TC 305

More information

CFD Analysis of Fire Characteristics on Subway Junction Station

CFD Analysis of Fire Characteristics on Subway Junction Station ISGSR27 First International Symposium on Geotechnical Safety & Risk Oct. 18~19, 27 Shanghai Tongji University, China CFD Analysis of Fire Characteristics on Subway Junction Station G. H. Wu, X. Han, Q.Q.

More information

Petralba tunnel: A case of success

Petralba tunnel: A case of success Thermal cameras Petralba tunnel: A case of success 7 th September 2016 Rafael López Guarga President - ATC (PIARC) Spanish Technical Committee of Road Tunnels Chief Engineer of Aragon s Public Roads Administration

More information

Fire and Smoke Management in a Uni-Directional Road Tunnel for a Congested Traffic Condition

Fire and Smoke Management in a Uni-Directional Road Tunnel for a Congested Traffic Condition International Journal of Ventilation ISSN 1473-3315 Volume 8 No 4 Fire and Smoke Management in a Uni-Directional Road Tunnel for a Congested Traffic Condition Y. Liu 1, J. Munro 1 and B. Dandie 2 1 Parsons

More information

DCN: ENGINE COMPANY OPERATIONS CHAPTER 4 March 15, 1997 FIRE SCENE OPERATIONS

DCN: ENGINE COMPANY OPERATIONS CHAPTER 4 March 15, 1997 FIRE SCENE OPERATIONS DCN: 4.05.01 ENGINE COMPANY OPERATIONS CHAPTER 4 March 15, 1997 FIRE SCENE OPERATIONS 4. FIRE SCENE OPERATIONS 4.1 FIREFIGHTING OBJECTIVES 4.1.1 The objectives of firefighting are to protect life and property

More information

Design of Fire safety in Multi Occupancy Residential Accommodation

Design of Fire safety in Multi Occupancy Residential Accommodation Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability

More information

CASE STUDY. Safety and system uptime in the St. Gotthard Base Tunnel

CASE STUDY. Safety and system uptime in the St. Gotthard Base Tunnel CASE STUDY Safety and system uptime in the St. Gotthard Base Tunnel Two competent partners one solution: electrical enclosure manufacturer and thermal management specialist develop a concept that withstands

More information