SECTION ROOFTOP REPLACEMENT AIR UNITS
|
|
- Brent Cole
- 6 years ago
- Views:
Transcription
1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Specification Sections, apply to this Section. B. Related Sections include the following: 1. Division 7 Section "Manufactured Roof Specialties" for type and style of roof curbs and equipment supports. 2. Section Motors. 3. Section " Vibration and Seismic Controls for HVAC Piping and Equipment" for manufactured isolation bases. 4. Section Mechanical Identification. 5. Section Metal Ducts. 6. Section Duct Accessories. 7. Section "HVAC Instrumentation and Controls" for temperature-control devices, and control wiring and control devices connected to energy recovery units. 1.2 SUMMARY A. This Section includes rooftop heating and cooling units. 1.3 SUBMITTALS A. Product Data: Include manufacturer's technical data for each model indicated, including rated capacities of selected model clearly indicated; dimensions; required clearances; shipping, installed, and operating weights; furnished specialties; accessories; and installation and startup instructions. B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loadings, required clearances, method of field assembly, components, and location and size of each field connection. Detail mounting, securing, and flashing of roof curb to roof structure. Indicate coordinating requirements with roof membrane system. 1. Wiring Diagrams: Detail wiring for power, signal, and control systems and differentiate between manufacturer-installed and field-installed wiring. C. Commissioning Reports: Indicate results of startup and testing commissioning requirements. Submit copies of checklists. D. Maintenance Data: For equipment to include in the maintenance manuals. E. Warranties: Special warranties specified in this Section. 1.4 QUALITY CONTROL A. Fabricate and label refrigeration system to comply with ASHRAE 15, "Safety Code for Mechanical Refrigeration." Page 1 of 12
2 B. Energy Efficiency Ratio: Equal to or greater than prescribed by ASHRAE 90.1, "Energy Efficient Design of New Buildings except Low-Rise Residential Buildings." C. Coefficient of Performance: Equal to or greater than prescribed by ASHRAE 90.1, "Energy Efficient Design of New Buildings except Low-Rise Residential Buildings." D. Listing and Labeling: Provide electrically operated components specified in this Section that are listed and labeled. 1. The Terms "Listed" and "Labeled": As defined in the National Electrical Code, Article Listing and Labeling Agency Qualifications: A "Nationally Recognized Testing Laboratory" as defined in OSHA Regulation E. Comply with AGA Z223.1 for gas-fired furnace section. F. Comply with NFPA DELIVERY, STORAGE, AND HANDLING A. Deliver rooftop units as factory-assembled units with protective crating and covering. B. Coordinate delivery of units in sufficient time to allow movement into building. C. Handle rooftop units to comply with manufacturer's written rigging and installation instructions for unloading and moving to final location. 1.6 COORDINATION A. Coordinate installation of roof curbs, equipment supports, and roof penetrations with roof construction. Roof specialties are specified in Division 7 Sections. 1.7 WARRANTY A. General Warranty: The special warranty specified in this Article shall not deprive the Owner of other rights the Owner may have under other provisions of the Contract Documents and shall be in addition to, and run concurrent with, other warranties made by the Contractor under requirements of the Contract Documents. B. Special Warranty: A written warranty, executed by the manufacturer and signed by the Contractor, agreeing to replace components that fail in materials or workmanship, within the specified warranty period, provided manufacturer's written instructions for installation, operation, and maintenance have been followed. 1. Warranty Period, Compressors: Manufacturers standard, but not less than 5 years after date of Substantial Completion. 2. Warranty Period, Heat Exchangers: Manufacturers standard, but not less than 10 years after date of Substantial Completion. 1.8 EXTRA MATERIALS A. Furnish extra materials described below that match products installed, are packaged with protective covering for storage, and are identified with labels describing contents. Page 2 of 12
3 PART 2 - PRODUCTS 2.1 MANUFACTURERS 1. Fan Belts: One set for each belt-drive fan. 2. Filters: One set of filters for each unit. A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: B. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Rooftop Units: a. York International Corp. b. Trane Company (The). c. Carrier Corp.; Carrier Air Conditioning Div. 2.2 ROOFTOP UNITS - GENERAL A. Rooftop Unit shall be completely factory assembled, piped, wired, tested and shipped in one piece with a single point power connection. Outside air system, return air system, filters, switches and supply air fan system shall be furnished factory installed. Units shall be specifically designed for outdoor rooftop application and include a weatherproof cabinet. Units shall have direct expansion cooling with natural gas, electric, hot water heat as scheduled and specified. Units shall be shipped fully charged with Refrigerant 22 or as scheduled. B. All units shall have decals and tags to indicate caution areas and aid unit service. Unit nameplates shall be fixed to the deadfront cover in the main control panel. Electrical wiring diagrams shall be attached to control panels. Installation and maintenance bulletins shall be supplied with each unit CABINET, CASING AND FRAME A. The frame and unit base shall be (14-gauge galvanized steel, nominal 18 ton through 30 ton units), (12-gauge galvanized steel, nominal 35 ton through 100 ton units). The unit base shall overhang the roof curb for water run-off and shall have a formed recess that seats on roof curb gasket to provide a positive weathertight seal. Exterior panels shall be constructed of 17-gauge galvanized steel. Access doors downstream of the supply air fan section shall include 20-gauge galvanized steel door liners. All side access doors shall seal to vinyl, dual durometer gasketing which use air pressure differential to guarantee sealing. B. Unit cabinetry shall incorporate a standing top seam and channeled surfaces at all joining sections. Top panels shall be cross-broken for water drainage. Unit cabinet shall be designed to operate at external static pressures up to 5.5 inches W.G. C. Exterior surfaces shall be phosphatized and coated with baked-on, light gray enamel which passes the government, 500 hour salt spray test. Access doors shall be supplied on both sides of every section with stainless steel hinges and a single point latch and service retainer. Access doors requiring mechanical fasteners are not acceptable. Page 3 of 12
4 D. Condensing unit section access doors shall have quick turn latches. E. Unit shall be completely insulated with one-inch thick neoprene coated glass fiber secured to side, top and end panels with adhesive and mechanical fasteners. Lifting brackets with lifting holes shall be provided on the unit base to accept cable or chain hooks. 2.4 CONDENSING SECTION A. Compressors shall be heavy-duty, reciprocating, semi-hermetic type with serviceable oil pump, unloaders and cylinder heads along with reversible, positive displacement oil pump, suction and discharge line service valves, crankcase heater and inherent solid state thermal overload protection. Scroll and reciprocating type hermetic compressors may be optioned, when approved by owner. Each compressor shall have its own completely independent refrigeration circuit including sightglass, filter-drier, manual shut-off valve and spring-type high-pressure relief valve. Compressor shall be isolated on spring mounts with vibration line isolators. Compressor capacity reduction shall be accomplished with cylinder unloading and/or hot gas bypass. B. The condensing unit section shall be open on the sides and bottom to assure complete access to and airflow through the coils. Condenser coils shall be multi-row type fabricated from seamless copper tubing mechanically bonded to rippled and corrugated aluminum fins. Condenser coil for each refrigerant circuit shall be provided with an additional circuit for a minimum of 15 degrees of subcooling. Each condenser coil shall be factory leak tested at 315 PSIG under water. Hail guards shall be provided to protect the coil fins from damage by handling and weather. C. Condenser fans shall be direct drive, propeller type designed for low tip speed and vertical air discharge. Fan blades shall be constructed of steel and riveted to an Iridite dipped steel center hub. D. Condenser fan motors shall be heavy-duty, inherently protected, three-phase non-reversing type with permanently lubricated ball bearings and integral rain shield. 2.5 COOLING COIL SECTION A. Evaporator coils shall be multi-row type fabricated from 5/8-inch O.D. seamless copper tubing mechanically bonded to rippled and corrugated aluminum fins. Two-row evaporator coils shall have a maximum of twelve fins per inch and three, four and five-row coils shall have a maximum of eight fins per inch. Coils shall be factory leak tested at 315 PSIG under water. The evaporator coil circuitings shall be fed with an adjustable thermal expansion valve (one per refrigerant circuit) with an external equalizer. The evaporator coil shall be circuited for a combination row/face split on 2 compressor units. B. Chilled water coils shall be multi-row type fabricated from 5/8" O.D. seamless copper tubing mechanically bonded to rippled and corrugated aluminum fins. Chilled water coils shall be available with a variety of coil circuitings, rows, and fins per inch selected from an ARI Certified Computer Program to match the cooling load. (Control of the chilled water coil shall be accomplished by a factory installed control package including a Page 4 of 12
5 three-way modulating control valve, piping and spring return valve operator). Chilled water coils shall be provided with vent and drain connections. C. A mastic coated primary drain pan shall be provided with the cooling coil and extend beyond the leaving side of the coil and underneath the cooling coil connections. The drain pan shall be connected to a threaded drain connection extended through the unit base. Units shall be provided with a secondary mastic coated drain pan connected to the primary drain pan. 2.6 HEAT EXCHANGER SECTION A. Heat exchanger shall be suitable for use with gas burners. The heat exchanger shall have a welded 430 stainless steel cylindrical combustion chamber and a 430 stainless steel header. Secondary heat exchanger surface shall be of corrosion resistant aluminized steel (stainless steel) tubing. A carbon steel heat exchanger surface shall not be acceptable. The heat exchanger design shall permit each section to freely expand and contract at its own rate, including each individual secondary tube. B. There shall be no baffles within the heat exchanger design except secondary surface tubing turbulators. There shall be no gasketed plates, bulkheads, or ports between the inside of the heat exchanger and the supply air stream. Cleanout of the heat exchanger and turbulators shall be accomplished without removing casing panels or passing soot through the supply air passages. A flame observation port shall be provided opposite the burner. The heat exchanger shall have a condensate drain. C. The burner shall be a forced draft type. The burner, controls and valves shall be housed within the integral burner vestibule. The vestibule door shall be hinged at the top and equipped with steel retainer rod to hold the door open for service. The burner shall be fire tested and adjusted at the factory. Final adjustments shall be made in the field at initial start-up by a qualified service organization. D. Modulating gas burner, if applicable, shall be capable of efficient operation from 33% through 100% of rated capacity. (Gas burners shall be forced draft type, complete with flame supervision, integral prepurge timing, combustion air proving switch, intermittent pilot with spark ignition, and a complete gas train. The gas train shall include the main gas valve, main pressure regulator, main shut-off cock, pilot gas valve, pilot pressure regulator, and pilot cock. (Units 400 MBH nominal output and larger shall have electronic flame supervision with 4-second time response.) 2.7 ELECTRIC HEAT A. Electric heating coils shall be constructed with low watt density nickel chromium elements. Safety controls shall include automatic reset high limit control for each heater element, a linear heat limiter in the discharge air stream of each heater bank, and line break protection in each heater circuit. Heating element branch circuits shall be individually fused to a maximum of 48 amps to meet NEC requirements. B. A solid-state control system with full magnetic line break contactors shall provide multiple stages of control. The electric heating section shall contain a single point electrical connection with a factory-mounted non-fused disconnect switch to provide power to the unit as well as the electric heat section. Page 5 of 12
6 2.8 HOT WATER HEAT A. Hot water coils, if applicable, shall be one or two-row type fabricated from l/2-inch O.D. seamless copper tubes mechanically bonded to rippled and corrugated aluminum fins. (Control of the hot water coil shall be accomplished by a factory installed control package including a three-way modulating control valve, piping and a spring return valve operator). 2.9 SUPPLY FAN SECTION A. Supply fans shall be double width, double inlet centrifugal type forward curved or airfoil as specified and scheduled. Nominal 18 ton through 30-ton units shall have two fans and nominal 35 ton through 100-ton units shall have a single fan. All fans shall be statically and dynamically balanced for quiet operation. The forward curved fan wheel and housing shall be fabricated from painted cold rolled steel on nominal 18 ton through 30-ton units and continuous galvanized steel on nominal 35 ton through 100-ton units. The airfoil fan wheel shall be Class II type and fabricated from aluminum with the fan blades continuously welded to the back plate and end rim. Units shall have solid steel fan shafts mounted in heavy-duty, L10 200,000-hour relubricative ball bearings. B. Fan motors shall be heavy-duty, 1800 RPM, open drip-proof type with relubricative ball bearings. The motor shall have a variable pitch sheave and an adjustable base for proper alignment and belt tension adjustment. The entire fan assembly shall be completely isolated from the unit bulkhead with neoprene gasketing and mounted on double deflection spring isolators FILTER SECTION A. The filter section shall be supplied complete with galvanized steel filter racks as an integral part of the unit. Filters shall be accessible from both sides of the unit. The filter section shall be as specified and scheduled RETURN AIR SECTION A. When specified and scheduled, return fans shall be centrifugal type forward curved or airfoil. Nominal 18 ton through 30-ton units shall have two fans and nominal 35 ton through 100 ton units shall have a single fan. All fans shall be statically and dynamically balanced for quiet operation. B. The forward curved fan wheel and housing shall be fabricated from painted cold rolled steel on nominal 18 ton through 30-ton units and continuous galvanized steel on nominal 40 ton through 100 ton units. The airfoil fan wheel shall be Class II type and fabricated from aluminum with the fan blades continuously welded to the back plate and end rim. Units shall have solid steel fan shafts mounted in heavy-duty, L10 200,000-hour relubricative ball bearings. C. Fan motors shall be heavy-duty, 1800 RPM, open drip-proof type with greaseable ball bearings. The motor shall have a variable pitch sheave and an adjustable base for proper alignment and belt tension adjustment. The entire fan assembly shall be completely isolated from the unit bulkhead with neoprene gasketing and mounted on double deflection, spring isolators. Page 6 of 12
7 2.12 OUTSIDE AIR SECTION A. The outside and return air section shall be designed to form a plenum. Outside air arrangement shall be as specified and scheduled for application ELECTRICAL A. Each unit shall be wired and tested at the factory before shipment. Wiring shall comply with NEC requirements and shall conform with all applicable U.L. standards. All wiring shall be number coded per the electrical wiring diagrams. All electrical components shall be labeled according to the electrical diagram and be U.L. recognized where applicable. Each unit (except condensing section only units) shall have a 115-volt control circuit transformer, 115-volt receptacle, system service switch, and control circuit fuse. B. The supply and return air fan, compressor and condenser fan motor branch circuits shall be individually fused. Contactors and inherent thermal overload protection shall be furnished for each compressor and condenser fan motor. The supply and return air fan motors shall have contactors and external overload protection. C. A terminal block shall be provided for the main power connection and a terminal board shall be provided for the low voltage control wiring. Knockouts shall be provided in the bottom of the main control panel for field wiring entrance. A separate keylocked control panel shall house all controls for the condensing section REFRIGERATION CONTROLS A. Each compressor circuit shall include a liquid line solenoid valve, oil pressure switch, high-pressure switch, low-pressure switch, compressor control circuit switch and pumpdown switch. Each refrigeration circuit shall have at least one condenser fan controlled from an ambient thermostat for positive head pressure control. An ambient thermostat shall prevent the refrigeration system from operating below 50 degrees F (adjustable) TEMPERATURE CONTROLS A. Units shall be provided with specified and scheduled control systems. All temperature control system components shall be completely factory wired and tested ELECTROMECHANICAL CONTROLS (if applicable) A. Control of the mechanical cooling and gas heating functions shall be by a 24 volt, mercury bulb type wall thermostat SOLID STATE CONTROLS (if applicable) A. Solid state controls shall be provided for wall thermostat and return air thermostat applications where the unit manufacturer provides all temperature control components including the thermostat, hot water, chilled water and steam valve motors; and/or the economizer damper motor. The solid state control system shall provide two or three-stage cooling; modulating cooling; two or three stage heating; modulating heating; modulating economizer operation; and automatic changeover of the cooling and heating functions. The solid-state control system shall include a solid-state thermostat, discharge Page 7 of 12
8 air sensor, central processor, electric heat sequencer, and economizer with enthalpy and low limit control. B. The central processor shall integrate the continuous input signals from the thermostat and discharge air sensor and translate them into the appropriate cooling, heating, or economizer action. The central processor and electric heat sequencer shall include an integral timing network to minimize the cycling of the heating and cooling functions. Night setback operation shall also be an integral part of the control system, automatically closing the outside air dampers and setting the thermostat back 5 F to 15 F from a single time clock without the use of an additional night setback thermostat DISCHARGE AIR CONTROLS (MICROPROCESSOR BASED) (if applicable) A. Discharge air controls shall be provided for use on mechanical or chilled water cooling applications. The discharge air control system shall be completely factory installed to control the discharge air temperature from a single sensor. The sensor shall be located at the discharge air opening. The discharge air controller shall have an adjustable temperature setting (40F to 90F) and an adjustable cycling rate (3 to 6 CPH). B. On mechanical cooling units, the discharge air controller shall operate the economizer and mechanical cooling stages. On multiple compressor units, the discharge air controller shall alternate circuit unloading between compressors. The economizer cycle shall include enthalpy control of the economizer dampers. The mechanical refrigeration system shall be locked out below 50F ambient (adjustable). C. On chilled water cooling units, the discharge air controller shall control the economizer and a three-way modulating chilled water valve. The economizer cycle shall include enthalpy control of the economizer dampers REMOTE MONITORING PANEL A. A remote monitoring panel shall be provided with system operation switches and signal lights for remote control and monitoring of unit functions. The panel shall include "Heat-Auto-Cool" system switch, "On-Off" fan switch, minimum outside air damper potentiometer and four signal lights to indicate supply fan operation, mechanical cooling malfunction, gas heat malfunction, and clogged filters. Two additional lights shall be provided on the remote monitor panel for field hook-up and monitoring of other system functions ROOF CURB A. A prefabricated 12-gauge galvanized steel mounting curb designed and manufactured by the unit manufacturer shall be provided for field assembly on the roof decking prior to unit shipment. The roof curb shall be a perimeter type with complete perimeter support of the air handling section and rail support of the condensing unit section. The curb shall be a minimum of 16 inches high and include a nominal 2 x 4-inch wood nailer strip. Gasketing shall be provided for field mounting between the unit base and roof curb. The roof curb shall be approved by the National Roofing Contractors Association ADDITIONAL EQUIPMENT A. The following additional equipment shall be provided. Page 8 of 12
9 2.24 MOTORS 1. An adjustable 0 to 8 minute timer lockout shall be provided on each compressor to prevent short cycling on safety control or power interruption. 2. Part winding start shall be provided on each compressor and each supply and return fan motor larger than 10 horsepower on 208, 230 or 460 volt units to provide two-step starting. 3. Hot gas bypass control shall be factory installed on each compressor circuit to provide capacity control by artificially loading the evaporator. Hot gas bypass control shall include a solenoid valve, hot gas bypass piping, and a hot gas bypass valve. The hot gas bypass valve shall be sized to modulate the full load. 4. Additional steps of cylinder unloading shall be provided on multiple compressor and single six-cylinder compressor units. Suction pressure switches shall control the cylinder unloaders on units with wall thermostat or return air temperature control. A unit mounted step controller shall control the cylinder unloaders electrically on units with discharge air temperature control. 5. A disconnect switch shall be provided to cut power to the entire unit before the control panel door can be opened. 6. An ionization type smoke detector equal to the Honeywell TC100D shall be factory mounted in the return or supply and return sections as required by code. Sensing tubing shall be strung across outlet openings and connected to the smoke detector sensing ports. Sensing tubing has several openings to get a full sampling and shall shut down the unit and shut outdoor air dampers when sensing smoke. 7. Optional isolation roof curb shall be furnished by the manufacturer of the unit. Isolation curb shall be of the size to match the exact dimensional criteria of the unit casing and factory mounting kits shall be furnished for field installation by the Contractor. A. Refer to Section "Motors" for general requirements for factory-installed motors. B. Motor Construction: NEMA MG 1, general purpose, continuous duty, Design B. C. Enclosure Type: Open, dripproof SOURCE QUALITY CONTROL A. Verification of Performance: Rate capacity according to ARI 210/240, "Unitary Air- Conditioning and Air Source Heat Pump Equipment." B. Verification of Performance: Rate capacity according to ARI 360, "Commercial and Industrial Unitary Air-Conditioning Equipment." 1. Sound Power Level Ratings: Comply with ARI 270, "Standard for Sound Rating of Outdoor Unitary Equipment." PART 3 - EXECUTION 3.1 EXAMINATION A. Examine roof for compliance with requirements for conditions affecting installation and performance of rooftop units. Do not proceed with installation until unsatisfactory conditions have been corrected. Page 9 of 12
10 3.2 INSTALLATION A. Install units according to manufacturer's written instructions. B. Install units level and plumb, maintaining manufacturer's recommended clearances. C. Curb Support: Install roof curb on roof structure, level, according to NRCA's written installation instructions. Install and secure rooftop units on curbs and coordinate roof penetrations and flashing with roof construction. D. Unit Support: Install unit on structural curbs and level. Coordinate wall penetrations and flashing with wall construction. 3.3 CONNECTIONS A. Piping installation requirements are specified in other Division 15 Sections. Drawings indicate the general arrangement of piping, fittings, and specialties. The following are specific connection requirements: 1. Install piping to allow service and maintenance. 2. Gas Piping: Conform to applicable requirements of Section "Facility Natural Gas Piping." Connect gas piping to burner, full size of gas train inlet, and provide union with sufficient clearance for burner removal and service. 3. Hot-Water Heating Piping: Conform to applicable requirements of Section "Hydronic Piping." Connect with shutoff valve and union or flange. B. Duct installation requirements are specified in other Division 15 Sections. Drawings indicate the general arrangement of ducts. The following are specific connection requirements: 1. Install ducts to termination in roof mounting frames. Where indicated, terminate return-air duct through roof structure and insulate space between roof and bottom of unit. C. Electrical: Conform to applicable requirements in Division 16 Sections. D. Ground equipment. 1. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. Where manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B. 3.4 START UP SERVICE A. Verify that installation is as indicated and specified. B. Complete manufacturer's installation and startup checks and perform the following: 1. Level unit on housekeeping base, and flash curbs to unit and to roof. 2. Inspect for visible damage to unit casing. 3. Inspect for visible damage to furnace combustion chamber. 4. Inspect for visible damage to compressor, air-cooled condenser coil, and fans. 5. Verify that clearances have been provided for servicing. 6. Check that labels are clearly visible. 7. Clean furnace flue and condenser and inspect for construction debris. Page 10 of 12
11 8. Verify that controls are connected and operable. 9. Remove shipping bolts, blocks, and tie-down straps. 10. Verify that filters are installed. 11. Adjust vibration isolators. 12. Connect and purge gas line. 13. Check that burner and controls are suitable to operate at temperatures as low as minus 40 deg F. 14. Check acoustic insulation. 15. Check operation of barometric dampers. C. Lubricate bearings on fan. D. Check fan-wheel rotation for correct direction without vibration and binding. E. Adjust fan belts to proper alignment and tension. F. Start unit according to manufacturer's written instructions. 1. Perform starting of refrigeration in summer only. 2. Complete startup sheets and attach copy with Contractor's startup report. G. Check and record performance of interlocks and protection devices; verify sequences. H. Operate unit for an initial period as recommended or required by manufacturer. I. Perform the following operations for both minimum and maximum firing, and adjust burner for peak efficiency. Adjust pilot to stable flame. 1. Measure gas pressure on manifold. 2. Measure combustion-air temperature at inlet to combustion chamber. 3. Measure flue-gas temperature at furnace discharge. 4. Perform flue-gas analysis. Measure and record flue-gas carbon dioxide and oxygen concentration. 5. Measure supply-air temperature and volume when burner is at maximum firing rate and when burner is off. Calculate useful heat to supply air. 6. Check for backdraft under full operation. J. Calibrate thermostats. K. Adjust and check high-temperature limits. L. Check internal isolators. M. Check outside-air damper for proper stroke and interlock with return-air dampers. N. Check controls for correct sequencing of heating, mixing dampers, refrigeration, and normal and emergency shutdown. O. Start refrigeration and measure and record the following: 1. Coil leaving-air, dry- and wet-bulb temperatures. 2. Coil entering-air, dry- and wet-bulb temperatures. 3. Outside-air, dry-bulb temperature. 4. Air-cooled-condenser, discharge-air, dry-bulb temperature. Page 11 of 12
12 P. Measure and record the following minimum and maximum airflows. Plot fan volumes on fan curve. 1. Supply-air volume. 2. Return-air volume. 3. Relief-air volume. 4. Outside-air intake volume. Q. Simulate maximum cooling demand and check the following: 1. Compressor refrigerant suction and hot-gas pressures. 2. Short circuiting air through condenser or from condenser to outside-air intake. R. Verify operation of remote panel, including pilot-light operation and failure modes. Check the following: 1. High-limit heat exchanger. 2. Warm-up for morning cycle. 3. Freezestat operation. 4. Free-cooling mode, outside-air changeover. 5. Alarms. S. After starting and performance testing, change filters, vacuum heat exchanger and cooling and condenser coils, lubricate bearings, adjust belt tension, and check operation of power vents. 3.5 DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel as specified below: 1. Train Owner's maintenance personnel on procedures and schedules related to startup and shutdown, troubleshooting, servicing, and preventive maintenance. 2. Review data in the maintenance manuals. Refer to Section "Contract Closeout." 3. Review data in the maintenance manuals. Refer to Section "Operation and Maintenance Data." 4. Schedule training with Owner with at least 7 days' advance notice. END OF SECTION Page 12 of 12
KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION
SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to
More informationSECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof
More informationSECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS
SECTION 237413 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the
More informationSECTION FAN COIL UNITS
PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:
More informationConstruction Standards Page
Construction Standards Page 236313-1 SECTION 236313 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationC. Samples for Initial Selection: For units with factory-applied color finishes.
SECTION 238126- SPLIT-SYSTEM AIR-CONDITIONERS PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION PACKAGED COMPRESSOR AND CONDENSER UNITS
SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply
More informationSECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS
SECTION 237339 - DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary
More informationSECTION SPLIT-SYSTEM AIR-CONDITIONERS
SECTION 238126 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to
More informationC. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.
SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers
More informationSECTION AIR COILS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:
More informationSECTION AIR HANDLING UNIT
SECTION 15800 - AIR HANDLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR
More informationA. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.
SECTION 238113 - PACKAGED TERMINAL AIR CONDITIONERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSECTION WATER-SOURCE UNITARY HEAT PUMPS
SECTION 23 81 46 WATER-SOURCE UNITARY HEAT PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION COMPUTER ROOM AIR CONDITIONING SYSTEMS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Specification Sections, apply to this Section. B. Related
More informationBrown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS
SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett
More informationSECTION SPLIT-SYSTEM AIR-CONDITIONERS
SECTION 23 81 26 SPLIT-SYSTEM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.
More informationSPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS
SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification
More informationA. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.
Page 238126-1 SECTION 238126 - This Section includes requirements for the LEED Rating System. However, equipment specified in this Section may not qualify for LEED Rating System prerequisites and credits.
More informationStanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT
SECTION 23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes packaged roof top unit, unit controls, remote panel, roof mounting curb and base, maintenance service,
More information1.1 This section applies to air handling units for HVAC Systems.
AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling
More informationSECTION AIR COOLED WATER CHILLERS
PART 1 GENERAL 1.1 SECTION INCLUDES A. Chiller package B. Charge of refrigerant and oil C. Controls and control connections D. Chilled water connections E. Starters F. Electrical power connections 1.2
More informationUNIVERSITY OF MISSOURI Central Station Air-Handling Units March
GENERAL: 1. This section provides criteria for the design and installation of air handling units. DESIGN GUIDELINES: Design General 1. Location 1.1. For new construction, and existing buildings where possible,
More informationExclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA
Page 236423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical Plant
More informationSECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS
SECTION 23 62 13 - AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",
More informationSECTION ROTARY-SCREW WATER CHILLERS
PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.
More informationUNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:
SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating
More informationTECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703
TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.
More informationSECTION (15733) - DEDICATED OUTDOOR AIR UNITS
PART 1 GENERAL 1.01 SUMMARY SECTION 23 74 33 (15733) - DEDICATED OUTDOOR AIR UNITS A. Section Includes: 1. Dedicated Outdoor-Air Units with Energy Recovery B. Related Sections: 1.02 REFERENCES 1. Section
More informationSECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM
SECTION 23 81 06 - PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. This Section includes equipment types that contain all the components of the refrigeration process within
More information1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.
SECTION 15855 GAS FURNACE/DX COOLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of contract including General and Supplementary Conditions of Division 1 of Specification
More informationSECTION (15833) - HVAC POWER VENTILATORS
PART 1 GENERAL 1.01 SUMMARY SECTION 23 34 23 (15833) - HVAC POWER VENTILATORS A. Section Includes: 1. Centrifugal Roof Ventilators. 2. Up-blast Roof Exhaust Fans (Kitchen Hood Exhaust). 3. Ceiling-Mounted
More informationSubmittal Data Performance Data Electrical Data
ERMS Series Submittal Data Submittal Data Unit Designation: Job name: Architect: Engineer: Contractor: Performance Data Revision: 07/01/11 Cooling Capacity: EER: Heating Capacity: COP: Ambient Air Temp:
More informationA. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.
Page 238219-1 SECTION 238219 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationConstruction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA
Construction Standards Page 233423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified
More informationSECTION WATER-SOURCE UNITARY HEAT PUMPS
SECTION 23 81 46 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph
More informationHVAC REPAIR/REPLACEMENT 07/18/12 SECTION HVAC - MAJOR EQUIPMENT
SECTION 15300 - HVAC - MAJOR EQUIPMENT PART 1 - GENERAL 1.1 MECHANICAL GENERAL A. Section 15010 is applicable. PART 2 - PRODUCTS 2.1 FANS A. General: 1. All fans shall bear the AMCA Certified Performance
More informationA. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.
15855 AIR HANDLING UNITS SPECIFIER: CSI MasterFormat 2004 number: 237313 PART 1 GENERAL 1.1 SUMMARY A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution
More information.2 Section Waste Management and Disposal.
Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3
More informationA. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.
SECTION 15622 DIRECT GAS-FIRED BURNER & MANIFOLD SYSTEM PART 1: GENERAL 1.1 Section includes: A. Direct gas-fired heater modules B. Controls C. Equipment schedule 1.2 Related Sections A. Section 01655:
More informationA. This Section includes air-handling units with coils for indoor installations.
SECTION 237313 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes air-handling units with coils for indoor installations. 1.2 SUBMITTALS A. Product Data: For each type of indoor air-handling unit
More informationSECTION AIR-SOURCE UNITARY HEAT PUMPS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 81 43 AIR-SOURCE UNITARY HEAT PUMPS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable
More informationAIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.
SECTION 15855 AIR HANDLING UNITS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15885 - Air Filtration Equipment. 3. 15890 - Ductwork. 1.02 REFERENCES A. Air Moving
More informationA. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.
Section 15 _ Energy Recovery Air Handling System Part 1: GENERAL 1.1 Section Includes: A. Energy Recovery Air Handler B. Controls (most by Others) C. Equipment Schedule 1.2 Related Sections: A. Section
More informationCatalog Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers
Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers Models RCS 025C through 135C 25 to 135 Tons R-22/R407C Refrigerant Catalog 221-1 Table of Contents Introduction.... 3 The Condensing
More informationSECTION (15733) - DEDICATED OUTDOOR AIR UNITS
PART 1 GENERAL 1.01 SUMMARY SECTION 23 74 33 (15733) - DEDICATED OUTDOOR AIR UNITS A. Section Includes: 1. Dedicated Outdoor-Air Units with Energy Recovery B. Related Sections: 1.02 REFERENCES 1. Section
More informationAir-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers
Catalog 221-1 Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers Model RCS 025C to 135C R-22/R-407C Refrigerant Contents Introduction............................... 3 The Condensing
More informationSAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER
SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section
More informationDirect Fired Heater Model AD Specification
Direct Fired Heater Model AD Specification Description A Direct-fired gas heating and ventilating unit(s), as indicated on the drawings shall be furnished. Unit(s) shall be tested in accordance with ANSI
More informationModular Heating & Ventilating Unit Model IGX-HV
Modular Heating & Ventilating Unit Model IGX-HV Indirect Gas-Fired Heating Evaporative Chilled Water DX Cooling October 2008 Product Features Model IGX-HV Indirect Gas-Fired Heating and Ventilating Unit
More informationSECTION WATER-TUBE BOILERS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections
More informationSECTION AIR COILS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 82 16 AIR COILS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in the section
More informationInternal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.
A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall
More informationAdvance Release September 2009
Vertical Air Cooled DSV Series R 410A Model DSV096 DSV120 DSV144 DSV180 Nominal Cooling (Tons) 8 10 12 15 Refrigerant R 410A R 410A R 410A R 410A Cooling Performance Gross Cooling Capacity(Btu/h) 95,000*
More informationA. Section includes factory-packaged units capable of supplying up to 100 percent outdoor air and providing cooling and heating.
SECTION 15850 PACKAGED DEDICATED OUTDOOR-AIR UNITS SPECIFIER: CSI MasterFormat 2004 number: 23 74 33. PART 1 GENERAL 1.1 RELATED SECTIONS A. 15960 Variable Frequency Drives. 1.2 SUMMARY A. Section includes
More informationCity of Duluth Festival Center 04/25
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationSECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS
SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from
More informationDTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5
Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3
More informationSubmittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS
AutoZone R Model Single Package Rooftop Gas Heating/Electric Cooling Unit Size 07 with Puronr (R---410A) Refrigerant Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION
More informationDARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES
SECTION 15856 MODULAR AIR HANDLING UNITS PART 1 DESIGN DIRECTIVES 1.1 QUALITY ASSURANCE A. NFPA Compliance: Modular air handling units and components shall be designed, fabricated, and installed in compliance
More informationSKYPAK II, 3 Ton Series, gives you a
SKYPAK II 3 ton Heating And Cooling self-contained Package SKYPAK II, 3 Ton Series, gives you a complete air-conditioning and heating system as an all in one package unit. Designed for convenient through-the-wall
More informationModular Supply Make-Up Air Unit
Modular Supply Make-Up Air Unit Model MSX Flexible Design Factory Assembled Heating Options Hot Water Steam Electric Cooling Options Evaporative Direct Expansion Chilled Water November 2009 Product Features
More informationCopyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services
Page 238216-1 Copyright 2003 and 2005 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical
More informationGAS FURNACES G20RE/ G20RXE EXISTING NEG ENGINEERING DATA EXISTING NEG. Typical Applications
ENGINEERING DATA Typical Applications G20RE and G20RXE WhisperHeat DOWN-FLO GAS FURNACES *78.0% A.F.U.E. 50,000 to 150,000 Btuh Input Add-On Cooling 2 thru 5 Nominal Tons *Isolated Combustion System rating
More information1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.
Page 238239-1 SECTION 238239 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationGuide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:
Date: 05/21/2001 Time: 08:50:16 AM Job Name: EarthWise Modular Climate Changer Full Spec Location: Any Town, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SUBMITTALS Submittals
More informationMIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/
1 of 3 Cooling Capacity [Btuh] 24,800 * Condensing Unit SEER: 13.0 ** Condensing Unit CFM: 1,600 Condenser Fan No./Type: 1/CENTRIFUGAL Diameter x Width [in]: 10x10 Drive: Adjustable Belt Motor HP: 0.5
More informationSKYPAK II, 3 Ton Series, gives you a
SKYPAK II 3 ton Heating And Cooling self-contained Package SKYPAK II, 3 Ton Series, gives you a complete air-conditioning and heating system as an all in one package unit. Designed for convenient through-the-wall
More informationSECTION (15767) - UNIT HEATERS
SECTION 23 82 39 (15767) - UNIT HEATERS PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Unit Heaters. 2. Cabinet Unit Heaters. 3. Duct Heaters. 4. Baseboard Heaters. B. Related Sections: 1. Section
More informationRGE 13 A T - 1 A
PRODUCT SPECIFICATIONS PACKAGED GAS / ELECTRIC 3GEP / RGE3 Rooftop Units 60HZ Bulletin No. 2063 December 202 Supersedes October 202 MODEL NUMBER IDENTIFICATION -PHASE MODELS SEER - 3.00 (3GEP Shown) AFUE
More informationA. Product Data: Include rated capacities, furnished specialties and accessories.
BASE BID: SECTION 15542 FUEL-FIRED RADIANT HEATERS PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install a Co-Ray-Vac Low Intensity Vented Infrared Radiant Vacuum Gas Heating System. System must be certified
More informationIndirect Gas-Fired Make-Up Air
Indirect Gas-Fired Make-Up Air Model IG 800 to 7,000 cfm Up to 400,000 Btu/hr Multiple Furnace Control Options Optional Evaporative Cooling May 20041 Product Features Model IG Indirect Gas-Fired Make-Up
More informationHEATING & COOLING SUBMITTAL The DuraPac Series Unit 559F/579F180, 216, 240, , 18, 20, and 25 NOMINAL TONS
HEATING & COOLING SUBMITTAL The DuraPac Series Unit 559F/579F180, 216, 240, 300 15, 18, 20, and 25 NOMINAL TONS COMMERCIAL ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS ELECTRIC HEATING/ELECTRIC COOLING UNITS
More informationDSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data
DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data July 28, 2008 Page 1 1 of 3 PROJECT: TAG: Gross Cooling Capacity [Btuh]: 37,800* Design CFM: 1,200 Seasonal
More informationSECTION AIR DOORS
SECTION 23 34 33 AIR DOORS Berner Series VSA air doors are designed for openings up to 12 ft for environmental separation and up to 10 ft for insect control. Berner Series VSB air doors are designed for
More informationA. Section Common Motor Requirements for HVAC Equipment: Fan motors.
SECTION 235533 - FUEL-FIRED UNIT HEATERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Gas fired unit heaters. B. Oil fired unit heaters. C. Tubular infrared heaters. 1.2 RELATED REQUIREMENTS A. Section 230513
More informationSTR-Series Indirect-Fired Air Turnover Units
STR-Series Indirect-Fired Air Turnover Units Equipment Specifi cations 1.800.589.3691 www.weather-rite.com GAS/OIL HEATING ONLY INDIRECT-FIRED AIR TURNOVER UNIT GUIDE SPECIFICATIONS PART 1 GENERAL [Gas][Oil][Gas/Oil
More informationSECTION PLUMBING EQUIPMENT
PART 1 GENERAL 1.1 SECTION INCLUDES A. Water heaters B. Packaged water heating systems C. Water storage tanks D. Water softeners E. Pumps F. Circulators 1.2 REFERENCES SECTION 22 30 00 PLUMBING EQUIPMENT
More informationSECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.
SECTION 15855 AIR HANDLING UNITS WITH COILS PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Central Station Air Handling Units. B. Related Sections: 1.02 REFERENCES 1. Section 15010 - Basic Mechanical
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS
PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Placement within a mechanical room is required for all major mechanical equipment. Only small units may be roof-mounted, and shall be made as inconspicuous
More informationDirect Gas-Fired Make-Up Air
Direct Gas-Fired Make-Up Air Model TSU Heavy Duty, High Airflow Applications Manufacturing and Industrial Facilities Up to 64,000 cfm August 2012 Products Model TSU Direct Gas-Fired Make-Up Air Unit The
More informationSubmittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS
Single Package Rooftop Gas Heating/Electric Cooling Unit Two Stage Cooling Capacity Control with NOVATIONt Coil Sizes 08, 12, 14 with Puronr (R---410A) Refrigerant Submittal Data PERFORMANCE DATA CERTIFIED
More informationPGF SERIES 7-1/2 Ton. Belt Drive CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT
PGF SERIES 7-1/2 Ton C Belt Drive CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT SINGLE PACKAGE Combination gas heating and electric cooling, self contained for year-round comfort. Systems can be installed
More informationA. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:
SECTION 15860 - FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR MECHANICAL
More informationDesign and Construction Standards SECTION PLUMBING EQUIPMENT
SECTION 15450 PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES: A. Water heaters. B. Packaged water heating systems. C. Water storage tanks. D. Water softeners. E. Pumps. F. Circulators. 1.2 REFERENCES
More informationB. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).
Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage
More informationFLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13
Tag Data - Split System Air Conditioning Units (Large) (Qty: 6) Item Tag(s) Qty Description Model Number A1 20 ton vfd 6 6-25 Ton Unitary Split Systems ( SSC2 TTA24004H00-TWE240E404A TTA Air Condensing
More informationLiebert CSU3000 Chiller
CSI 15620 - Packaged Water Chillers Liebert CSU3000 Chiller Guide Specifications for 7.5-37 Ton CS/CD/CT Models 1.0 GENERAL 1.1 CS/CD MODELS The main-frame coolant supply unit shall be a Liebert Model,
More informationUNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013
SECTION 15800 - AIR HANDLING EQUIPMENT 1.1 GENERAL A. All air handlers installed shall conform to the University of Rochester specification Guideline for Semi-Custom and Pre-Engineered Air Handling Units.
More information30GT FLOTRONIC AIR-COOLED CHILLERS
30GT-41SB 30GT040-110 FLOTRONIC AIR-COOLED CHILLERS PERFORMANCE DATA FIELD WIRING DIAGRAM 1998 Carrier Corporation Syracuse, New York 13221 Form 30GT-41SB Supersedes 30GT-21SB, 30GT-22SB, 30GT-23SB, Printed
More informationSECTION CONVECTION HEATING AND COOLING UNITS
PART 1 GENERAL 1.01 SECTION INCLUDES A. Baseboard radiation. B. Finned tube radiation. C. Convectors. D. Unit heaters. E. Cabinet unit heaters. F. Fan-coil units. G. Unit ventilators. H. Blower-coil units.
More informationPGB SERIES 3thru5Ton 10 SEER CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT
PGB SERIES 3thru5Ton 10 SEER C CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT SINGLE PACKAGE Combination gas heating and electric cooling, self contained for year-round comfort. Systems can be installed
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Balancing Air Systems: a. Constant-volume air systems. b. Variable-air-volume systems. 2.
More informationGuide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:
Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT
More informationSECTION AIR DUCT ACCESSORIES
SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control
More informationSECTION ELECTRIC WATER HEATERS
PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:
More informationSECTION GAS-FIRED RADIANT HEATERS
SECTION 23 55 23 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph
More informationC. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.
Buchtel/Perkins Community Learning Center GPD -2007271.15 OSFC Project # 55-7110-9029425 Phase 3 CLC Package Bidding Documents July 1, 2010 SECTION 15513 CONDENSING BOILERS PART I- GENERAL 1.1 RELATED
More informationSECTION HEATING BOILERS
SECTION 23 52 00 HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes boilers, controls and boiler trim, steam and condensate connections, hot water connections, fuel burning system and connections,
More informationSECTION AXIAL FANS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:
More information