DOYLE ASSOCIATES, INC. TEST AND BALANCE HVAC Systems
|
|
- Brendan Cox
- 6 years ago
- Views:
Transcription
1
2
3
4 DOYLE ASSOCIATES, INC. TEST AND BALANCE HVAC Systems TO: Corbett Legge and Associates, PLC ATTN: Mr. Andrew Walker FROM: Doyle Associates, Inc. DATE: September 19, 2013 Re: Jackson County School District Vancleave Upper Elementary Administration Bldg Vancleave, Ms. TEST AND BALANCE PROPOSAL Dear Mr. Walker: Thank you for the opportunity to quote the above referenced project. This quote is based on utilizing the N.E.B.B. Procedural Standards and TABB International Certification Board Specifications. We are pleased to submit a firm price of Sixteen Thousand Four Hundred Forty Seven Dollars and Fifty Cents ($16,447.50) to complete the testing and balancing of the above referenced project. The following is based on data derived from the plans and specifications. 1. Eight (8) Split System Air Handling Units 2. Eight (8) Condenser Units 3. Six (6) ERV Units 4. One (1) Ductless Mini Split Unit (Indoor and outdoor unit) 5. One (1) Dehumidification Unit and Condenser Unit 6. One (1) electric Unit Heater 7. Approximately Ninety (90) registers, grilles and diffusers 8. DALT observation included 9. Pitot tube traverses as required 10. Schedules and reports Again, thank you for the opportunity to quote this project. If you have any questions, or require further clarification, please do not hesitate to call. Sincerely, Doyle Associates, Inc. Cc: file 5695 Rabbit Creek Dr, Suite 104 Theodore, AL Phone: Fax:
5 SOUTH COAST TESTING & BALANCING, CO. P.O. BOX 9633 MOBILE, ALABAMA PHONE FAX Test & Balance Price Quote Date: 9/19/2013 PROJECT NAME: VANCLEAVE UPPER ELEMENTARY ADMINISTRATION BUILDING VANCLEAVE, MISSISSIPPI PRICE $7, APPROXIMINATE SCOPE AND NOTES ERV-6 ACU-8 AD-90 DUCT LEAK TESTTING VERIFY CONTROLS REVIEW DESIGN ETC THANK YOU, PATRICK P. CEBALLOS
6 TEST AND BALANCE EF-2 SUBMITTAL DATA Date: PROJECT NAME: VANCLEAVE UPPER ELEMENTARY SCHOOL ADMINISTRATION BUILDING VANCLEAVE, MISSISSIPPI Registration No. #0145 Tested By P. Ceballos Certification: THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF SYSTEM PERFORMANCE AT TIME OF TESTING AND WAS OBTAINED IN ACCORDANCE WITH THE NBC STANDARD PROCEDURES AND THE PROJECT SPECIFICATIONS. ANY VARIANCES FROM DESIGN QUANTITIES WHICH EXCEED REQUIRED TOLERANCES ARE NOTED THROUGHOUT THIS REPORT. TEST AND BALANCE IS WARRANTEED ONE FULL YEAR FROM ABOVE REPORT DATE. TAB Supervisor: Patrick P. Ceballos Approved: David S. Bowen P. E. SOUTH COAST TESTING & BALANCING, CO PH Fax PAGE 1
7 CERTIFICATION CERTIFICATE Registration No. #0145 SOUTH COAST TESTING & BALANCING, CO PH Fax PAGE 2
8 INSTRUMENT CALIBRATION DATA INSTRUMENTS SERIAL NO. APPLICATION CALIBRATION DATE ALNOR EBT BALOMETER OUTLET READINGS Jan-13 ALNOR HUM TEMP PROBE TEMPERATURES Jan-13 DWYER 10" LIQUID MANOMTR 2LFM-1 STATIC PRESSURE N/A FLUKE T5-600 AMP METER VOLT/AMP READING Jan-13 ALNOR EBT MICROMANOMET PRESSURE/TRAVERSE Jan-13 EXTECH ANEMOMETER OUTLET READINGS Jan-13 EXTECH TACH Q TACHOMETER Jan-13 VARIOUS PITOT TUBES N/A AIR FLOW N/A ALNOR HDM HYDRONIC FLOW Jan-13 REMARKS: SOUTH COAST TESTING & BALANCING, CO PH Fax CALIBRATION CERTIFICATES ARE AVAILABLE ON REQUEST VIA OR FAX. PAGE 3
9 VARIOUS COMPLETED PROJECTS SINCE 1986 BY P. CEBALLOS BUILDING 90330, HURLBURT FIELD, FLA. MULTIPLE VARIABLE VOLUME SYSTEMS WITH DDC CONTROLS. NSTL PRIMARY COMPUTER CENTER ADD. STENNIS SPACE CENTER, MISSISSIPPI. SET UP CHILLER/CONDENSOR LOOPS FOR CRAY SUPERCOMPUTERS. MICRO-BIOLOGY LAB, UNIVERSITY OF SOUTH ALABAMA, MOBILE, ALABAMA. SET UP BUILDING PRESSURES IN HAZARDOUS TESTING AREAS. UEPH, CB BASE, GULFPORT, MISSISSIPPI. MULTIPLE VARIABLE VOLUME SYSTEMS UTILIZING HOT AND CHILL WATER ALL PNEUMATICALLY CONTROLLED. U.S.D.A. GULFPORT, MISSISSIPPI. SET UP FUME HOODS. WEEKS BAY NATIONAL ESTUARINE RESERVE EDUCATIONAL AND MULTIPURPOSE FACILITY, FAIRHOPE, ALABAMA TYPICAL DIRECT DRIVE SPLIT SYSTEM DESIGN. TRAINING FACIITY AND EMERGENCY BUNKER FOR ALABAMA DEPARTMENT OF TRANSPORTATION 9TH DIVISION MOBILE, ALABAMA. SPLIT SYSTEMS WITH BELT DRIVEN AIR HANDLER UNITS. RENOVATIONS TO LAKEWOOD GOLF CLUBHOUSE POINT CLEAR, ALABAMA. NEW AND OLD SPLIT SYSTEMS IN BUILDING REMODEL. NEW SPIRAL PIPE COATING BUILDING FOR BERG PIPE, MOBILE, ALABAMA. SPLIT SYSTEMS AND EXHAUST SETUP FOR INDUSTRIAL FACILITY. HAMPTON INN, OPELIKA, ALABAMA. SPLIT SYSTEMS AT A FOUR STORY HOTEL. CRANFORD H. BURNS MIDDLE SCHOOL, MOBILE, ALABAMA VARIABLE VOLUME AIR AND HYDRONIC SYSTEMS. OTHER PROJECTS INCLUDE: CHURCHES, CLINICS, BANKS, HOUSING PROJECTS, SCHOOLS, PRISONS, OFFICE COMPLEXES, RETAIL OUTLET STORES, ETC. LISTING AVAILABLE ON REQUEST. SOUTH COAST TESTING & BALANCING, CO PH Fax
10 TEST AND BALANCE PROCEDURES AIR SYSTEMS: 1 DETERMINE ALL AIR EQUIPMENT IS OPERATIONAL AND HAS CLEAN FILTERS. 2 PLACE ALL RELATED SUPPLY, EXHAUST AND RETURN AIR SYSTEMS IN OPERATION, RUNNING AT DESIGN RPM. 3 ESTABLISH SYSTEMS CONDITIONS FOR MAXIMUM DEMAND AIRFLOW; GENERALLY A COOLING APPLICATION. 4 SET UP THE AUTOMATIC CONTROL DEVICES IN THE SYSTEM SO THAT THEY WILL NOT ADVERSELY AFFECT THE BALANCING OPERATIONS. 5 DETERMINE THE VOLUME OF AIR BEING MOVED WITH EACH SYSTEM. 6 MAKE A SURVEY OF EACH ROOM, CHECKING AIR CIRCULATION. 7 THE SYSTEM IS CONSIDERED BALANCED IN ACCORDANCE WITH THESE PROCEDURES WHEN THE VALUE OF THE AIR QUANTITY OF EACH INLET OR OUTLET DEVICE IS MEASURED AND FOUND TO BE WITHIN 10% OF DESIGN QUANTITIES, OR WITHIN PREVAILING SPECIFICATIONS. VARIABLE VOLUME SYSTEMS: 1 TURN ALL THERMOSTATS TO FULL COOL TO SIMULATE FULL LOAD CONDITIONS. 2 MEASURE AIRFLOW MOVING THROUGH THE CONTROLLED AIR TERMINAL. CALIBRATE THE SENSOR IF NECESSARY. 3 OUTLETS ON THE DISTRIBUTION DUCTWORK CAN NOW BE BALANCED IN THE CONVENTIONAL METHOD. SOUTH COAST TESTING & BALANCING, CO PH Fax 4 IF A DIVERSITY FACTOR WAS USED IN THE EQUIPMENT SELECTION, SET THIS FACTOR OF UNITS IN FULL COOLING MODE AND THE REMAINING TERMINALS IN THE FULLY CLOSED POSITON.
11 TEST AND BALANCE PROCEDURES HYDRONIC SYSTEMS: 1 DETERMINE ALL CIRCUITS ARE FUNCTIONAL AND THAT NECESSARY COMPENSATION FOR SEASONAL EFFECTS HAS BEEN MADE. 2 DETERMINE THAT ALL SYSTEMS HAVE BEEN CLEANED AND FILLED. 3 DETERMINE THAT ALL MANUAL VALVES ARE OPEN, OR PRESET AS REQUIRED, AND ALL AUTOMATIC VALVES ARE IN THE CORRECT POSITION AND WILL NOT ADVERSELY AFFECT THE BALANCE OF THE SYSTEM. 4 RECORD THE SYSTEM PRESSURE WITH THE PUMP OFF. 5 PLACE THE SYSTEM IN OPERATION, ELIMINATE ALL AIR FROM THE SYSTEM AND ALLOW FLOW CONDITIONS TO STABILIZE. 6 RECORD THE OIPERATING VOLTAGE, AMPERAGE AND PUMP SPEED. 7 RECORD DISCHARGE PRESSURE, SUCTION PRESSURE AND TOTAL HEAD IN FEET WITH DISCHARGE VALVE CLOSED. 8 RECORD DISCHARGE PRESSURE, SUCTION PRESSURE AND TOTAL HEAD IN FEET WITH DISCHARGE VALVE OPEN. 9 ADJUST THE PUMP FOR 110% OF THE REQUIRED GPM AND VERIFY THE PUMP CALCULATED GPM'S BY CORRELATING WITH THE BOILER/CHILLER DESIGN PRESSURE DROPS. 10 MAKE PRELIMINARY ADJUSTMENTS IN BALANCING DEVICES AND REREAD ENTIRE SYSTEM, REPEAT PROCESS UNTIL ALL ACTUAL WATER FLOW THROUGH EACH PIECE OF EQUIPMENT IS WITHIN 10% OF DESIGN FLOW, OR WITHIN PREVAILING SPECIFICATIONS. SOUTH COAST TESTING & BALANCING, CO PH Fax ALL WORK IS PERFORMED IN COMPLIANCE WITH THE PROJECT SPECIFICATIONS AND PERFORMANCE COMPLIANCE WITH ASHRAE, AABC, NEBB AND SMACNA STANDARDS. ALL PROJECTS(T&B) WARRANTEED ONE FULL YEAR. See to view NBC procedural standards.
12 AIR HANDLER TEST DATA SHEET FAN NAMEPLATE DATA MANUFACTURER MODEL SERIAL # TYPE/SIZE PRESS. CLASS DISCH. ARRANG. FAN DESIGN ACTUAL SUPPLY AIR CFM RETURN AIR CFM OUTSIDE AIR CFM FAN RPM TOTAL S.P." EXTERNAL S.P." DISCHARGE S.P." RETURN S.P." FAN SUCTION S.P." DATE: PROJECT: UNIT No.: MOTOR NAMEPLATE DATA MOTOR MANUFACTURER HORSEPOWER/FR. HORSEPOWER VOLTS/PH/HZ VOLTS FULL LOAD AMPS AMPS SERVICE FACTOR R.P.M. RPM MOTOR B.H.P. LOCATION: SYSTEM: DRIVE PACKAGE TEMPERATURES DEG F FAN PULLEY COOLING EAT DEG F MOTOR SHEAVE COOLING LAT DEG F BELT SIZE HEAT TEMP. EAT/LAT DB SHAFT CNTR DIST. OUTSIDE AIR TEMP #FILTERS/TYPE/SIZE OUT.AIR DAMP POS. RET.AIR DAMP POS. REMARKS: SOUTH COAST TESTING & BALANCING, CO PH Fax
13 DIFFUSER/ GRILLE TEST DATA SHEET AREA Outlet Code Size Required Test % of REMARK Final CFM SERVED No. CFM 1 Design DATE: PROJECT: UNIT: LOCATION: SYSTEM: REMARKS: South Coast Testing & Balancing, Co PH Fax
14 TEMPERATURE BALANCING REPORT CURRENT CONDITIONS TIME OF DAY OUTDOOR TEMPERATURE OUTDOOR HUMIDITY SPACE TEMPERATURES THERMOSTAT CALIBRATED? THERMOSTAT SETPOINT DATE PROJECT SYSTEM Room Name KITCHEN DINING COOK LINE SPACE TEMPERATURE BUILDING PRESSURE MEASUREMENT OUTSIDE AIR CFM TOTAL= MAKE UP AIR FAN CFM TOTAL= EXHAUST CFM TOTAL = CFM DIFFERENCE= MEASURED BUILDING PRESSURE H20"= PREPARATION START UP SYSTEM RUN UNTIL 1ST CYCLE OR 15 MINUTES Comments Comments READINGS BY JOB NUMBER South Coast Testing & Balancing, Co PH Fax Remarks WITNESSED BY:
15 TEST HOLES (") READING NUMBER Remarks Rectangular Duct Traverse Report TEST LOCATIONS (") DUCT TEST PATTERN TEST 1 TEST 2 FINAL TEST DUCT/GRILLE DUCT SIZE FREE AREA HXW/144 VELOCITY CFM/AREA IF GRILLE X AK FACTOR AIR FLOW (CFM) CALCULATIONS TOTAL READINGS (FPM) DIVIDED BY NO. OR READINGS AVERAGE VELOCITY x DUCT AREA DESIGN TEST 1 ACTUAL FINAL = CFM DISTANCE BETWEEN TEST HOLES AND READING LOCATIONS NO. OF TEST SITES AND FACTORS X DUCT TEST HOLE X DUCT READING HEIGHT = LOCATION WIDTH = LOCATION VELOCITY READINGS READING NUMBER TEST 1 TEST 2 FINAL TEST NBC, Inc. DATE PROJECT SYSTEM READINGS BY JOB NUMBER South Coast Testing & Balancing, Co PH Fax
16 EXHAUST FAN TEST DATA SHEET FAN DATA FAN NO. FAN NO. FAN NO. LOCATION SERVICE MANUFACTURER MODEL NO. SERIAL NO. TYPE MTR. MAKE/FR. MTR. H.P./RPM VOLTS/PHASE/HZ F.L. AMPS/S.F. DATE PROJECT SYSTEM FAN PULLEY MOTOR SHEAVE BELTS TEST DATA DESIGN ACTUAL DESIGN ACTUAL DESIGN ACTUAL CFM FAN RPM S.P. IN/OUT TOTAL S.P. MTR. B.H.P. VOLTS AMPS REMARKS South Coast Testing & Balancing, Co PH Fax
17 VAV Terminal Box Report MANUFACTURER DATE MAXIMUM MINIMUM VAV DESIGN COMPUTER ACTUAL DESIGN COMPUTER ACTUAL No. CFM READING CFM CFM READING CFM PROJECT SYSTEM READINGS BY P.CEBALLOS JOB NUMBER South Coast Testing & Balancing, Co PH Fax Remarks: TOTAL
18 NAMEPLATE INFORMATION TEST RESULTS PUMP PUMP Design Actual Manufacturer GPM Model Impeller Size Serial RPM Pump Type Horsepower Discharge PRESSURES Design Actual Rated RPM Off Pressure Impeller Size Required NPSH Valve Closed Head Dischg. Pressure Suction Diffuser Inlet Pressure Dischg. Diffuser Total Pressure Shutoff Valve Total Head (x 2.31) Gauges Inlet Size Plotted Efficiency MOTOR Design Actual Discharge Size Areas Served: Volts T1/T2/T2/T3/T3/T1 Amp T1/T2/T3 Motor RPM MOTOR Manufacturer Frame Horsepower Volts Phase Hertz RPM Full Load Amps Service Factor Motor Frame Seal Type PIPING COMMENTS Pump Test Report Brake Horsepower STRAINER Strainer Size Strainer Cleaned PERFORMANCE COMMENTS DATE PROJECT SYSTEM READINGS BY South Coast testing & Balancing, Co PH Fax
19 Equipment Number Area Served Manufacturer Model Number Serial Number CHILLER TEST REPORT CHILLER INFORMATION DATE PROJECT SYSTEM READINGS BY JOB NUMBER TESTED INFORMATION DESIGN ACTUAL EVAPORATOR DATA ENT./LVG. WATER PRESSURE WATER PRESSURE DROP ENT./LVG. WATER TEMPERATURE GPM XXXX CONDENSOR DATA ENT./LVG. WATER PRESSURE WATER PRESSURE DROP ENT./LVG. WATER TEMPERATURE GPM XXXX South Coast Testing & Balancing, Co PH Fax REMARKS TEMPERATURES GIVEN IN DEGREES FAHRENHEIT.
20 Cooling Tower Test Report COOLING TOWER INFORMATION Equipment Number Area Served Manufacturer Model Number Serial Number DATE PROJECT SYSTEM READINGS BY JOB NUMBER TESTED INFORMATION DESIGN ACTUAL ENT./LVG. WATER PRESSURE WATER PRESSURE DROP GPM XXXX South Coast Testing & Balancing, Co PH Fax REMARKS TEMPERATURES GIVEN IN DEGREES FAHRENHEIT. REFRIGERATION/COMPRESSOR/CONDENSOR DATA TO BE FURNISHED BY THE INSTALLER OF THE EQUIPMENT.
21 Duct Leakage Test Report PROJECT NAME DATE DATE SYSTEM TEST TEST LEAKAGE % OF WITNESSED LOCATION PRESSURE CFM LEAKAGE BY PROJECT SYSTEM READINGS BY P.CEBALLOS JOB NUMBER South Coast Testing & Balancing, Co PH Fax REMARKS: MEASUREMENTS TAKEN UTILIZED A 4.9" ORIFACE PLATE PER SMACNA. TEST PRESSURE IS 1.5 X OPERATING PRESSURE OF THE DUCT UNLESS OTHERWISE SPECIFIED.
22 Project Symbols CFM Cubic Feet per Minute Return Duct Diameter Supply Duct DATE Supply OSA Outside Air PROJECT Return Equipment Designation Exhaust SP Static Pressure Direction of Airflow SWS T Thermostat/control SWR Sidewall Supply Sidewall Return D Damper CS DD DIRECT DRIVE OP OPEN Ceiling Supply Volume Damper HP Horsepower OBD Opposed Blade Damper BD Backdraft Damper FLA Unit Location V SF F Furnace BHP CU Condensing Unit DNA CC Cooling Coil DNL AH Air Handler NA L Louver NT Volts Full Load Amps Service Factor Brake Horsepower Data Not Available Data Not Listed Not Accessible Not Taken - no valid South Coast Testing & Balancing, Co. P.O. Box 9633 Mobile, Alabama ph fax TABHVAC@gmail.com
SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 15990 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the Specifier in correctly specifying Mechanical System Testing Adjusting
More informationTESTING, ADJUSTING AND BALANCING
PART 1 GENERAL 1.01 DESCRIPTION A. Work Included: After completion of the work of installation, owner is responsible for procuring an air balancing and testing agency to test and regulate all components
More informationSECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationCity of Duluth Festival Center 04/25
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationSECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC
PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 23 0593 TESTING, ADJUSTING, AND A. Testing, adjustment, and balancing of air systems. B. Testing, adjustment, and balancing of hydronic, steam, and refrigerating
More informationSECTION PLUMBING/HVAC FINAL TESTING, ADJUSTING AND BALANCING
SECTION 15990 PLUMBING/HVAC FINAL TESTING, ADJUSTING AND BALANCING PROJECT NO. ####### PART I - GENERAL 1.01 WORK INCLUDED A. Final test and balance of air distribution systems. B. Final test and balance
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Balancing Air Systems: a. Constant-volume air systems. b. Variable-air-volume systems. 2.
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 23 0594 - TESTING, ADJUSTING, AND BALANCING (TAB) PART 1 - GENERAL 1.1 SUMMARY A. This Section includes testing, adjusting and balancing HVAC systems to provide design conditions as indicated by
More informationSECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC
SECTION 23 05 93 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph
More informationSECTION TESTING, ADJUSTING AND BALANCING
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections
More informationTest, Adjust, and Balance Services Submittal
TAB Submittal Alley 111 Test, Adjust, and Balance Services Submittal Page 2 Professional Qualifications Page 4 Applicable Certifications Page 7 MMFS TAB Agenda Page 13 Sample report Page 1 of 44 25 05
More informationRAMAPO COLLEGE OF NEW JERSEY CCA0803 PHASE II HOUSING REHABILITATION 2012
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More information2009 IECC Commercial Mechanical Requirements
BUILDING ENERGY CODES UNIVERSITY 2009 IECC Commercial Mechanical Requirements Ken Baker PNNL-SA-66171 Learning(Objec-ves(( ( 1. Find(minimum(equipment(efficiency(requirements( and(recite(at(least(3(common(terms(for(measuring(
More informationGuide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:
Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT
More informationComputing Services Center
Continuous Commissioning Report for the Computing Services Center Building #516 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory
More informationHVAC Mandatory Provisions Part II, Page 1
HVAC Mandatory Provisions Part II, Page 1 Mandatory Equipment Efficiency Worksheet (6.4.1.1) System Equipment Type Size Category (Tables 6.8.1A through K) Sub-Category or Rating Condition Units of Efficiency
More informationCOMcheck Software Version Review Mechanical Compliance Certificate
COMcheck Software Version 4.0.7.2 Review Mechanical Compliance Certificate Section 1: Project Information Energy Code: 2014 Oregon Energy Efficiency Specialty Code Project Title: Benton County Health Project
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section
More informationNovember 11, City of Sparks 215 S. 21 st St. Sparks, NV
November 11, 2014 City of Sparks 215 S. 21 st St. Sparks, NV 89432-0857 Attn: Brian Cason Re: Sparks City Hall HVAC Upgrade Project-Alerton Direct Digital HVAC Control System to Match Existing City of
More informationSHOE PALACE HUNTINGTON PARK M.200
M.200 SPLIT SYSTEM CONDENSING UNIT SCHEDULE MARK SERVICE MODEL NO. COOLING DIMENSIONS ELECTRICAL REMARKS CAPACITY AMBIENT DB REFRIGERANT LENGTH WIDTH HEIGHT WEIGHT VOLT/PHASE MCA MOP (MBH) (DEG F) (IN)
More informationAABC National Standards for Total System Balance, 7th Edition: A Guided Tour Course Number: CXENERGY1624
AABC Commissioning Group AIA Provider Number 50111116 AABC National Standards for Total System Balance, 7th Edition: A Guided Tour Course Number: CXENERGY1624 Gaylon Richardson, TBE, CxA Engineered Air
More information1 - This title will copy onto other forms Date
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 Mechanical Summary MECH-SUM Project Title: 1 - This title will copy onto other forms Date 1/1/2015
More informationCivil Engineering Building
Continuous Commissioning Report For the Civil Engineering Building Building 492 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory
More informationSubmitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge
ESL-TR-99/12-04 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University-Corpus Christi (TAMU-CC) Corpus Christi, Texas Submitted to Texas
More informationCOMcheck Software Version Mechanical Compliance Certificate
COMcheck Software Version 4.0.4. Mechanical Compliance Certificate Project Information Energy Code: Location: Climate Zone: Project Type: 205 IECC Dallas, Texas 3a New Construction Construction Site: 56
More informationCOMcheck Software Version Mechanical Compliance Certificate
COMcheck Software Version 4.0.8.1 Mechanical Compliance Certificate Project Information Energy Code: Location: Climate Zone: Project Type: 90.1 (2013) Standard Buda, Texas 2a New Construction Construction
More informationDACC Health Sciences Building Air Handler Assessment/Study
DACC Health Sciences Building Air Handler Assessment/Study NMSU Facilities and Services Department P.O. Box 30001 Las Cruces, NM 88003-8001 June 14, 2016 Final Submittal 1065 S. Main St., Bldg. D, Ste.
More informationDucted Propeller. Airflow Volume
Total Pressure Radial-Blade Centrifugal Tubeaxial Backward-inclined Airfoil Centrifugal Forward-curved Centrifugal Ducted Propeller Airflow Volume Figure 2: Forward-Curved Centrifugal Fan
More informationCOMcheck Software Version Mechanical Compliance Certificate
COMcheck Software Version 4.0.6.2 Mechanical Compliance Certificate Project Information Energy Code: Location: Climate Zone: Project Type: 90.1 (2007) Standard HALCYON Bldg. 400 Alpharetta, Georgia 3a
More informationCOMcheck Software Version Mechanical Compliance Certificate
COMcheck Software Version 4.0.3.0 Mechanical Compliance Certificate Section 1: Project Information Energy Code: 2014 Oregon Energy Efficiency Specialty Code Project Title: AHSC (Asian Heal Service Center
More informationHigh Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)
High Plume Blowers Suggested Specification Section 15500 (Master Format 1996) Suggested Specification Section 23 38 16 (Master Format 2004) PART 1 GENERAL 1.01 WORK INCLUDED High Plume Laboratory Exhaust
More informationMechanical Compliance Certificate
COMcheck Software Version 4.0.7.0 Mechanical Compliance Certificate Project Information Energy Code: Location: Climate Zone: Project Type: 90.1 (2013) Standard Austin, Texas 2a (weather data: TBD) New
More information1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT
Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-1142 (510) 749-9135 Fax (510) 749-9136 LLC HVAC DESIGN INTENT PART 1 - GENERAL 1.1 Overview A. The project consists of a 3-story
More informationTechnical Assignment 3 11/15/04. Executive Summary
Executive Summary This report is an analysis of the existing systems within the Outreach Innovation Building in University Park, PA. One significant design criteria was a lower than average noise criteria
More informationNEW CHILLER SCHEDULE
TITLE: REPLACE CHILLER MACC MAXIMO # 4542690 PROJECT # 14M108CN MACC # 14-0459 ATTACHMENTS: 1. MAXIMO Equipment update form SCOPE OF WORK: The contractor shall provide all material, labor, equipment, and
More informationFan Selection. and Energy Savings
Fan Selection and Energy Savings Reducing power consumption by minimizing system pressure loss and choosing the right equipment HBy BRIAN MLEZIVA Greenheck Fan Corp. Schofield, Wis. Power Consumption HVAC
More information1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process.
SECTION 239950 MECHANICAL COMMISSIONING SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. B. Commissioning
More informationAugust 15, 2013 Page 1 of 19
Section C401 Application Compliance with C402, C403, C404 and C405 AND (either C406.2, C406.3 or C406.4) Compliance with C402, C403, C404 or C405 Section C402 Building Envelope (Climate Zone 5A) Space-Conditioning
More informationMID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN
MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN September 30, 2015 PBA Project No. 2015.0140.00 PETER BASSO ASSOCIATES INC. CONSULTING ENGINEERS 5145 LIVERNOIS ROAD,
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 23 05 93 - TESTING, ADJUSTMENT AND BALANCING PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More information2011 Manitoba Energy Code for Buildings (MECB) PART 5, Heating, Ventilating and Air-conditioning Systems
2011 Manitoba Energy Code for Buildings (MECB) PART 5, Heating, Ventilating and Air-conditioning Systems Dieter Bartel, Manitoba Hydro September 17 th, 2014 Outline Scope and compliance Prescriptive path
More informationArchitectural Alliance Incorporated MDP CONSULTING ENGINEERS, INC N 11th Street Beaumont, TX 77702
04/08/2013 last saved: TRENT plotted: DRAWN BY: TLH CHECKED BY: DWD 04/08/2013 last saved: DMCPHERSON plotted: DRAWN BY: TLH CHECKED BY: DWD 04/08/2013 last saved: DMCPHERSON plotted: DRAWN BY: TLH CHECKED
More informationCOMcheck Software Version Mechanical Compliance Certificate
COMcheck Software Version 3.9.4 Mechanical Compliance Certificate 01 IECC Section 1: Information Type: Addition Title : Construction Site: Owner/Agent: Designer/Contractor: 3030 North Industrial Way Castle
More informationUNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationFan Power in 90.1 & IECC
AMCA International Fan Power in 90.1 & IECC Jeff Boldt, Principal IMEG Corp Jeff.G.Boldt@IMEGcorp.com Air System Engineering & Technology (ASET) Conference US San Antonio, TX Hyatt Regency San Antonio
More informationCOMMERCIAL PACKAGED HEAT PUMP AIR HANDLER UNITS, 6 20 TONS
Product Specifications COMMERCIAL PACKAGED HEAT PUMP AIR HANDLER S, 6 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE Multi position design for horizontal or vertical installation without modification.
More informationPackaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE
Service Facts Customer Property: Contains wiring and service information. Please retain. WC*240-SF-1H Library Service Literature Product Section Unitary Product Package Air Conditioner Model WC* Literature
More informationKINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION
SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to
More informationA. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.
SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate
More informationSECTION AIR DUCT ACCESSORIES
SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control
More informationIndiana WX Oil Furnace Inspection Guide
Indiana WX Oil Furnace Inspection Guide Client: Job # : Address: Phone: Client Interview: Oil Dealer: Date of last service: Comments/Billing information: Standard Inspection / Clean and Tune Follow-up:
More informationTrue performance and rugged durability. TU, LF and LD Models
Unit heaters/ Duct furnaces True performance and rugged durability TU, LF and LD Models Separated Combustion Unit Heaters at a glance: Ideal for hard-to-heat applications requiring fresh air for combustion
More information2009 Washington State Non-Residential Energy Code Scott Rushing, PE, LEED AP - Rushing Company Lisa Rosenow, CSBA, LEED AP NEEC
2009 Washington State Non-Residential Energy Code Scott Rushing, PE, LEED AP - Rushing Company Lisa Rosenow, CSBA, LEED AP NEEC Mechanical Systems Agenda Changes in NREC Chapter 11 Changes in NREC Chapter
More informationEXHAUST FAN SCHEDULE
DUCTWORK SCHEDULE CONCEALED SUPPLY AIR RECTANGULAR, RTU CONCEALED SUPPLY AIR RECTANGULAR, ERV CONCEALED SUPPLY AIR ROUND, RTU CONCEALED SUPPLY AIR ROUND, ERV EXPOSED SUPPLY AIR ROUND RUNOUTS RETURN AIR
More informationSECTION DUCTWORK
SECTION 15890 DUCTWORK PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 07270 - Firestopping and Fire and Smoke Barrier Caulking. 2. 15260 - Vibration Isolation. 3. 15280 - Thermal Insulation (HVAC).
More informationJH Series Installation
JH Series Installation Space Heating / Fresh Air Make-Up From the Manufacturers of Hi-Velocity Systems TM Includes: JH-15 JH-30 Module-JH-Series-Installation-Manual-010118 Installation JH fan coils by
More informationAdvance Release September 2009
Vertical Air Cooled DSV Series R 410A Model DSV096 DSV120 DSV144 DSV180 Nominal Cooling (Tons) 8 10 12 15 Refrigerant R 410A R 410A R 410A R 410A Cooling Performance Gross Cooling Capacity(Btu/h) 95,000*
More informationField Start-Up Sheet Direct Fired Gas Equipment
Customer: Sales Representative: Model Number: Serial Number: Field Start-Up Sheet Direct Fired Gas Equipment ***Please Print*** INITIAL INSPECTION I. Installer Responsibilities 1. Remote Panel: All interconnecting
More informationSchust Engineering, Inc. 701 North Street P.O. Box 128 Auburn, IN (260) Fax: (260)
Schust Engineering, Inc. 701 North Street P.O. Box 128 Auburn, IN 46706 (260) 925-6550 Fax: (260) 925-6093 Industrial Facility Midwest Re: Facility Ventilation Audit Schust Engineering, Inc. is pleased
More informationSubmitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge
ESL-TR-99/12-05 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Galveston (TAMU-G) Galveston, Texas Submitted to Texas A&M University
More informationModular Supply Make-Up Air Unit
Modular Supply Make-Up Air Unit Model MSX Flexible Design Factory Assembled Heating Options Hot Water Steam Electric Cooling Options Evaporative Direct Expansion Chilled Water November 2009 Product Features
More informationPresents PANTONE COOL GRAY 10 C PANTONE 3155 C
Presents Chilled/Hydronic Ductless Air Handlers PANTONE COOL GRAY 10 C PANTONE 3155 C Chilled/Hydronic Ductless Air Handlers Co mfor t w h e re i t co u n t s EMI ComfortWave Ductless Series Fan Coil Air
More informationBrown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS
SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett
More informationHVAC Controls Upgrades: Requirement Details ( )
REQUIRED CONTROLS/FEATURES HVAC non CENTRAL PLANT 1) Zone Level Scheduling & Override for all air handlers (supply and exhaust) to match occupied hours by zone DDC or occupancy sensors (OS) allowed. (403.2.4.3,
More informationFAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design
FAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design Fan motor (PSC or ECM). UL Listed 1 insulation conforms to UL Test 181 and NFPA 90A. Plenum air filter rack. (Filter Optional) Casing has
More informationDIVISION 15 MECHANICAL
DIVISION 15 MECHANICAL A. GENERAL DESIGN CONDITIONS 1. Design occupied spaces to maintain 72 F and a space dew point temperature not to exceed 55 F. 2. Design classroom and office space buildings with
More information4. OVERVIEW OF MECHANICAL SYSTEM
4. OVERVIEW OF MECHANICAL SYSTEM The 87,000 SF SLCC is served by six (6) Trane M-Series Climate Changer Air Handing Units (AHUs). Each unit serves a distinct zone within the facility that is unique in
More informationModular Heating & Ventilating Unit Model IGX-HV
Modular Heating & Ventilating Unit Model IGX-HV Indirect Gas-Fired Heating Evaporative Chilled Water DX Cooling October 2008 Product Features Model IGX-HV Indirect Gas-Fired Heating and Ventilating Unit
More informationCONTENTS. B. System Design and Performance Requirements
15815 Metal Ducts This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes
More informationInspection Phase Three. Mechanical, Electrical & Plumbing Section 503
Inspection Phase Three Mechanical, Electrical & Plumbing Section 503 COMCheck Mechanical Field Inspection Checklist Mechanical Mechanical, Electrical & Plumbing Equipment Efficiencies But a lot ore too
More informationMODEL TRC TOTAL RECOVERY FOR ALL CLIMATES - COMMERCIAL APPLICATIONS
TOTAL RECOVERY FOR ALL CLIMATES - COMMERCIAL APPLICATIONS MODEL FTURES MERV-8 filters Transformer/relay package allowing simple on/off control Access doors for easy access to blowers, core and filters
More informationB. System Design and Performance Requirements
15815 Metal Ducts This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes
More informationSECTION SPECIFICATION FOR HI-VELOCITY FAN COIL SYSTEMS
1.0 GENERAL SECTION 15740 SPECIFICATION FOR HI-VELOCITY FAN COIL SYSTEMS 1.01 DESCRIPTION Item A. Scope This section specifies four sizes of fan coil units designed for hydronic heating and air conditioning.
More informationFlorida Department of Transportation
Page 1 of 7 RICK SCOTT GOVERNOR Florida Department of Transportation 1109 S. Marion Avenue Lake City, Florida 32025 ANANTH PRASAD SECRETARY September 27, 2011 To: Proposal Holders Addendum No: 1, E2Q23,
More informationCOMcheck Software Version Interior Lighting Compliance Certificate
Section 1: Project Information Energy Code: 2009 IECC Project Title: Berry Farms Animal Hospital Project Type: New Construction COMcheck Software Version 4.0.3.0 Interior Lighting Compliance Certificate
More informationUFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas
UFAD and Displacement Ventilation Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas UFAD and DV Systems, Objectives: Understand Differences between: Well Mixed, Partially Stratified and Fully
More informationHVAC Controls Upgrades: Requirement Details ( )
REQUIRED CONTROLS/FEATURES To qualify the upgrade must add or substantially modify 3 or more sequences/system capabilities. Also, all sequences and items listed under the required section are needed in
More informationAdding More Fan Power Can Be a Good Thing
This article was published in ASHE Journal, May 14. Copyright 14 ASHE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission of
More informationA. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:
SECTION 15860 - FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR MECHANICAL
More informationAdvance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units
Advance Product Data 42WKN Hydronic Fan Coil Units 3 4 to 2 1 2 Tons UNIT SIZES 004-010 UNIT SIZES 016,020 The new Carrier Hydronic Cassette offers a modern solution for a wide variety of small and medium
More informationINTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings
INTRODUCTION TO: ASHRAE STANDARD 90.1, 2013 HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings Rocky Mountain ASHRAE Technical Conference, April 29, 2016 SEAN BEILMAN, P.E.,
More informationINSTRUMENTATION AND CONTROL DEVICES FOR HVAC
PART 1 GENERAL 1.01 RELATED REQUIREMENTS SECTION 23 0913 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC A. Section 26 2717 - Equipment Wiring: Electrical characteristics and wiring connections. 1.02 ADMINISTRATIVE
More informationFans: Features and Analysis
Technical Development Program COMMERCIAL HVAC EQUIPMENT Fans: Features and Analysis PRESENTED BY: Michael Ho Version 1.2 Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Section
More informationENVIRO UNIT ENGINEERING MANUAL KES SERIES
ENVIRO UNIT ENGINEERING MANUAL KES SERIES The Cadexair INC. Enviro System (KES) and Recirculation System (KRS) have been designed and constructed specifically for a commercial kitchen exhaust. The units
More information2006 Washington State Nonresidential Energy Code Compliance Form Washington State Nonresidential Energy Code Compliance Forms Revised July 2007
Mechanical Summary 2006 Washington State nresidential Energy Code Compliance Form MECH-SUM 2006 Washington State nresidential Energy Code Compliance Forms Revised July 2007 Project Info Project Address
More informationThe Current (2017) State of the Art for Air Leakage in Ductwork
The Current (2017) State of the Art for Air Leakage in Ductwork Over the last ten years there has been a major shift in the way ASHRAE has approached air leakage in ductwork. This is reflected in the latest
More informationEVALUATION OF SWINE FACILITIES VENTILATION
EVALUATION OF SWINE FACILITIES VENTILATION Dr. Steven Matthis Sampson Community College Animal Science Technology Department Clinton, NC 28329-0318 Email: smatthis@sampsoncc.edu Introduction Ventilation
More informationTHIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL
SECTION 15100 PART 1 GENERAL THIS IS A DESIGN GUIDE NOT A SPECIFICATION Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL HVAC SYSTEMS APPLICATIONS 1.1 SCOPE: The intent of this
More informationSystem and equipment drains shall be piped to a floor drain. Gauges shall be provided on the suction and discharge side of all pumps installed.
230000 Heating Ventilation and Air Conditioning 230500 Common Work for HVAC Provide access panels where maintenance will be required for items behind an enclosed wall or ceiling. All piping shall be installed
More informationProduct Data FEATURES/BENEFITS 524J***H 6 TO 20 TON DIRECT EXPANSION PACKAGED HEAT PUMP AIR -HANDLING UNIT. Indoor air quality features 524J-H 07-12
524J***H 6 TO 20 TON DIRECT EXPANSION PACKAGED HEAT PUMP AIR -HANDLING Product Data the environmentally sound refrigerant Certified to ISO 9001 524J-H 07-12 524J-H 16-25 C10899 Bryant s versatile packaged
More informationIndustrial Space Heating Direct Gas-Fired Heating. Greenheat 50/50 Recirculation
Industrial Space Heating Direct Gas-Fired Heating Greenheat 00% Outdoor Air Greenheat 50/50 Recirculation 80/0 Recirculation March 008 Product Overview Industrial Space Heating Greenheck s space heating
More informationC13-Series Engineering Guide
Engineering Guide Effective January 2018 Horizontal Air-Cooled, Water-Cooled, Chilled Water and Heat Pump Contents Product Features............................... 3 Product Options................................
More informationSPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS
036-21096-001 (0101) SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240 20 NOMINAL TONS DESCRIPTION This 20 ton evaporator blower is designed with two distinct modules to provide maximum application flexibility. The
More informationTechnical Report #3 Mechanical Systems Existing Conditions Evaluation
Mechanical Option Technical Report #3 Technical Report #3 Mechanical Systems Existing Conditions Evaluation Instructor: Dr. Bahnfleth 11.15.04 Building Sponsor: CCG Facilities Integration Table of Contents
More informationSESSION Michigan Energy Code (MEC) Update (3 Technical) Per SMACNA Standard (TAB, Duct Design) and ASHRAE ( ) ASHRAE Detroit Members:
SESSION 1-2015 Michigan Energy Code (MEC) Update (3 Technical) Per SMACNA Standard (TAB, Duct Design) and ASHRAE (90.1.2013) ASHRAE Detroit Members: AM Session is eligible for (X) Professional Development
More informationContinuous Commissioning SM Report. For. Wing 86, Chemistry Complex (Building # 376) Hui Chen Song Deng Homer L. Bruner, Jr., CEM.
Continuous Commissioning SM Report For Wing 86, Chemistry Complex (Building # 376) By Hui Chen Song Deng Homer L. Bruner, Jr., CEM Contact: Song Deng (979-862-1234) Homer L. Bruner, Jr. (979-862-7185)
More informationProduct Specifications. Vertical Floor Consoles By First Co.
NOW WITH 18 GAUGE CABINET AND FACTORY INSTALLED SERVICE SWITCH Product Specifications VFB Series VSB Series VCB Series Vertical Console Fan Coils 300-00 CFM Vertical Floor Consoles By First Co. VFB Series
More informationEMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons
560.20-TG1Y (388) EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons Each circuit includes a fully hermetic compressor with a crankcase
More informationInternal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.
A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall
More informationENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory
Overview of Chilled Beam Technology Purpose Chilled beam technology is new to the United States but has been used in Europe since the 1950 s. Chilled beams can reduce energy costs, improve indoor air quality,
More information