1 OPERATION MANUAL Air Curtains MultiMAXX HT Air Curtains for Industrial Application

2 DencoHappel Product Range MultiMAXX HT DencoHappel Product Range 2 PR GB Subject to modifications R2-04/2016

3 MultiMAXX HT Unit Type Code Unit Type Code MultiMAXX HT Accessories H T 8 2. U W A R A T. S S C Z H Model size 8 = Size 8 9 = Size 9 Capacity stage 2 = 2 fans* 3 = 3 fans 4 = 4 fans Aerodynamic function U = Recirculating-air unit Medium specification W = Only heating (PWW and PHW) 1 = Contact protection (only without heat exchanger) Heat exchanger A = Cu/Al, max. 130 C; 1.6 MPa C = Cu/Cu, max. 130 C; 1.6 MPa K = No heat exchanger Coil connection (front view) R = From right L = From left K = No heat exchanger** Model size 8 = Size 8 9 = Size 9 Suspensions 59 = For vertical installation 60 = For horizontal installation Material/Design 0 = Metal sheet Configuration for ZH..59../60.. Installation with wall clearance 0 = vertical installation (ZH.59..) 2 = 2 fans (ZH.60..) 3 = 3 fans (ZH.60..) 4 = 4 fans (ZH.60..) Installation without wall clearance 5 = vertical installation (ZH.59..) 6 = 2 fans (ZH.60..) 7 = 3 fans (ZH.60..) 8 = 4 fans (ZH.60..) Heat exchanger connection A = External screw thread K = Without connection Outlet P = Profile ceiling/wall T = Gate nozzle Ohne Auslass Motor/speeds S = 3 phases 400 V 3-speed - sickle-blade fan Electric equipment S = Fan isolator Design D = Industrial configuration - metal sheet in RAL 7000 * only for model size 8 ** available only on request PR GB Subject to modifications R2-04/2016 3

4 Table of Contents MultiMAXX HT Table of Contents DencoHappel Product Range... 2 Unit Type Code... 3 Table of Contents Safety and User Instructions Scope of the operation manual Used symbols Safety-conscious working Proper use Safety regulations and codes Modifications and changes Spare parts Personnel selection and qualification Technical Description Unit configuration and scope of supply Specification of material Unit variants Unit components Operating conditions Unit dimensions Unit weight and water charge of heat exchanger Operating limits Sound and electric data Shipping and Storage Shipping Shipping and handling of unit Storage Assembly Load-bearing capacity of the installation site Horizontal installation Vertical installation Safety clearance Unit installation Coil Connection Pipe connections Dimensions of heat exchanger connections Electrical Connection Wiring diagrams Fan isolator Motor terminal diagram for 3-speed three-phase external rotor motor 3 x 400 V, 50 Hz (motor type S) Wiring with control units MC 303 or controls by others Wiring room thermostat Commissioning Pre-commissioning checklist Unit air venting Operation Operating instructions Deactivating unit Maintenance and Troubleshooting Maintenance Half-yearly maintenance Annual maintenance Operating faults Disassembly and Disposal Disassembly Recycling PR GB Subject to modifications R2-04/2016

5 MultiMAXX HT Safety and User Instructions 1 Safety and User Instructions This is an original operation manual verified by the manufacturer. The MultiMAXX HT air curtains are developed and manufactured in accordance with the state-of-the-art technological standards and established technical safety codes and meet the requirements of the EC Directive on Machinery. The MultiMAXX HT gate air curtains are reliable in operation and satisfy strict quality standards. This product range combines future-oriented technology with a high level of user friendliness and ease of maintenance. Nevertheless, an air curtain unit could pose unavoidable residual risk of injury or risk of equipment or property-damage only accidents. Therefore your personal safety and the proper operation of the unit depend on the strict observance of the safety instructions. Failure to follow the safety precautions could result in death, serious injury or equipment or property-damage-only accidents. Observing the safety instructions in the current operation manual will help avoid the risks, ensure economical operation of the unit and enjoy full benefits of the product. The safety aspects covered by this chapter are valid for the entire operation manual. 1.1 Scope of the operation manual 1.2 Used symbols This operation manual covers critical points on the following subjects: Shipping Assembly Installation Electrical connection Medium connection Commissioning Operation Maintenance, cleaning and disposal The following symbols are used to highlight specific text sections in this operation manual: Indicates text paragraphs Indicates work steps Indicates work results Refer to this section for additional information on energy-efficient operation of the MultiMAXX HT gate air curtain units. RECYCLING! This symbol is used to highlight instructions on proper reuse of packaging material and disused assembly groups (separated according to recyclable materials). PR GB Subject to modifications R2-04/2016 5

6 Safety and User Instructions MultiMAXX HT The following designations and symbols are used for specifying safety instructions. RISK OF ACCIDENT DUE TO ELECTRICAL CURRENT! This symbol indicates a risk of accident due to electric shock. PERSONAL INJURY! This section specifies procedures and precautions for preventing personal injury. DANGER DUE TO OVERHEAD LOADS! This symbol warns about personal injury and damage caused by overhead loads and suspended heavy objects. DANGER OF HOT SURFACES! This section specifies procedures and precautions for preventing personal injury resulting from contact with hot surfaces. DANGER SHARP CUTTING EDGES! This section specifies procedures and precautions for preventing personal injury resulting from cuts on thin metal fins. HIGH PRESSURE HAZARD! This section specifies procedures and precautions for preventing personal injury resulting from high pressure. WARNING: RISK OF ROTATING COMPONENTS! This section specifies procedures and precautions for preventing personal injury resulting from rotating unit components. RISK OF ACCIDENT DUE TO HOT MEDIUM! This section specifies procedures and precautions for preventing personal injury resulting from contact with hot medium. DANGER OF INFLAMMABLE SUBSTANCES! This section specifies procedures and precautions for preventing personal injury resulting from fire hazard. ENVIRONMENTAL DAMAGE! This symbol warns about damage to the environment and turns attention to all existing national environmental protection regulations. EQUIPMENT DAMAGE! This section specifies procedures and precautions for preventing damage to MultiMAXX HT air curtain unit. 6 PR GB Subject to modifications R2-04/2016

7 MultiMAXX HT Safety and User Instructions 1.3 Safety-conscious working Observe the following instructions during installation, settings, service and maintenance tasks: ELECTRICAL HAZARD! Disconnect all electric power of the unit and ensure the power cannot be inadvertently energised, earth, short-circuit and block off all neighbouring live parts. Noncompliance can lead to death or serious injury. Fluctuations and imbalance in supply voltage must not exceed tolerance limits specified on the unit identification plate; otherwise this could cause severe unit malfunction or failure. 1.4 Proper use The MultiMAXX HT gate air curtains can be installed in industrial facilities, warehouses, sales and exhibition buildings. Mounting brackets, control units and control devices can be supplied as optional accessories. Proper use also stipulates the observance of the current operation manual as well as adherence to all inspection and maintenance intervals specified by DencoHappel. For operating Cu/Al (Cu/Cu) heat exchangers the following limit values must be observed: Parameter Unit Value ph value (at 20 C) Conductivity (at 20 C) ms/cm < 700 Oxygen content O 2 mg/l < 0.1 Total hardness dh 1-15 Dissolved sulphur S not detectable Sodium Na + mg/l < 100 Iron Fe 2+, Fe 3+ mg/l < 0.1 Manganese Mn 2+ mg/l < 0.05 Ammonium content NH + 4 mg/l < 0.1 Chloride Cl - mg/l < 100 Sulphate SO 2-4 mg/l < 50 Nitrite NO - 2 mg/l < 50 Nitrate NO - 3 mg/l < 50 Tab. 1-1: Limit values for different medium types in closed-loop heating circuits EQUIPMENT DAMAGE! In open systems (e.g. when using well water) observe the limit values specified in table Tab If the limit values are exceeded, a filter must be installed to clean the medium. Excess of these values can cause formation of deposits in the medium and creates a risk of erosion. At the same time the unit must be protected against dust and other elements that can result in acidic or alkaline reaction with water (aluminium corrosion). Improper use Any use other than that described above is considered improper. The manufacturer/ supplier is not liable for any damages arising from improper use. The user alone bears the risk. PR GB Subject to modifications R2-04/2016 7

8 Safety and User Instructions MultiMAXX HT PERSONAL INJURY! The MultiMAXX HT gate air curtains must not be operated: in explosion risk areas, in rooms with high dust or moisture content, in rooms with strong electromagnetic fields, in rooms with aggressive environment that may attack plastics. The following accident prevention regulations are valid (VBG1, BGV A2 (previously: VBG4), VBG7w, VBG9a) and generally recognized codes for machinery and principles of engineering, in particular DIN VDE 0100, DIN VDE Safety regulations and codes When carrying out assembly, electric installation, commissioning, maintenance and service of the MultiMAXX HT gate air curtains - relevant national safety regulations and codes as well as generally established technical practices must be considered. 1.6 Modifications and changes It is not allowed to modify, add components, or convert the MultiMAXX HT gate air curtain unit in any way. Changes or modifications of the DencoHappel units will invalidate the CE conformity and render and all warranty claims as null and void. 1.7 Spare parts Only original DencoHappel spare parts are allowed, since DencoHappel is not liable if third-party spare parts are used. 1.8 Personnel selection and qualification Before beginning any work on the MultiMAXX HT gate air curtain the personnel must have read through this operation manual carefully and understood it. Please read this document fully before commencing the task, and not while performing a task. Electrical connection must only be carried out by qualified licensed staff or other individuals with proper professional training and experience in the following areas: Regulations concerning health and safety in the workplace Accident prevention regulations Directives and recognized codes of practice All skilled staff must be able to assess the entrusted work and must be able to recognize and avoid all associated dangers. 8 PR GB Subject to modifications R2-04/2016

9 MultiMAXX HT Technical Description 2 Technical Description 2.1 Unit configuration and scope of supply Fig. 2-1: Unit configuration 1: Sickle-blade fan with contact protection grille 2: Fan module 3: Heat exchanger 4: Heat exchanger casing 5: Profile outlet ceiling 6: Plastic terminal box 7: Fan isolator PR GB Subject to modifications R2-04/2016 9

10 Technical Description MultiMAXX HT 2.2 Specification of material Unit part Material Fan with contact protection grille Various materials Fan module Galvanized sheet steel or galvanized sheet steel with paint finish Heat exchanger Cu/Cu or Cu/Al Heat exchanger casing Galvanized metal sheet Outlet Aluminium fins + painted galvanized metal sheet RAL 7000 Terminal box / switch Various materials Tab. 2-1: Specification of material 2.3 Unit variants Fig. 2-2: Air curtain unit with suspension for horizontal installation Fig. 2-3: Air curtain unit with suspension for vertical installation 2.4 Unit components The MultiMAXX HT air curtain unit is performed with 2 to 4 fans. The heat exchanger casing shall be galvanized and painted metal sheet in RAL The casing is optionally available in other RAL colours selected by the customer. One of two possible outlet variants is installed on the discharge side (refer to unit type code). The rear side of the unit is fitted with axial fans with an integrated contact protection grille that prevents risk posed rotating parts. This requirement meets the EN ISO standard. For securing horizontal and vertical unit suspensions the sides of the fan section are fitted with 2 x 4 rivet nuts. 2.5 Operating conditions The unit is not designed for medium types that can damage or destroy the surface coating due to corrosive, chemical or abrasive effects. Only non-corrosive and non-combustible liquids or steam must be used as a medium (refer to Tab. 1-1). 10 PR GB Subject to modifications R2-04/2016

11 MultiMAXX HT Technical Description 2.6 Unit dimensions Unit dimensions MultiMAXX HT, heat exchanger in Cu/Al, Cu/Cu 2 fans 3 fans 4 fans Fig. 2-4: Unit dimensions MultiMAXX HT PR GB Subject to modifications R2-04/

12 Technical Description MultiMAXX HT Fig. 2-5: Unit dimensions MultiMAXX HT Dimensions [mm] / unit size HT 82 HT 83 HT 84 HT 93 HT 94 A B C D E F G 1 1/4" 1 1/4" 1 1/4" 2" 2" H J L M N P T Dimensions [m] / accessories ZH ZH ZH ZH K Dimensions [m] / accessories ZH (3,4) ZH (7,8) ZH (3,4) ZH (7,8) S Tab. 2-2: Unit dimensions MultiMAXX HT 12 PR GB Subject to modifications R2-04/2016

13 MultiMAXX HT Technical Description 2.7 Unit weight and water charge of heat exchanger Model size Tab. 2-3: Weight including heat exchanger Water charge of heat exchanger Cu/Al [kg] Cu/Cu [kg] Cu/Al a Cu/Cu with T outlet with P outlet with T outlet with P outlet [l] HT HT HT HT HT Unit weight and water charge of heat exchanger 2.8 Operating limits All other important data on unit capacity, weights, connections and sound power is specified in the MultiMAXX HT Air Curtain Units - Data and Facts". Unit Max. ambient temperature -20 C to +40 C Operating voltage 3 x 400 V or 1 x 500 V~ 50 Hz Protection class IP54 Power consumption see unit identification plate Corrosion-resistance class C3 - EN ISO Max. dust concentration in the air 10 mg/m 3 Heat exchanger Cu/Al and Max. operating temperature 130 C Cu/Cu Max. medium pressure 1.6 MPa 2.9 Sound and electric data Model size Speeds Speed RPM Sound power db(a) A-rated sum level Sound pressure* db(a) Max. power consumption kw Max. current A Motor S - 3 x 400 V 3-speed HT HT HT HT HT Tab. 2-4: Sound and electric data * Sound pressure: standard values at 5 m distance to the unit side, at maximum air flow rate and low reflection room. Industrial hall volume 1500 m 3, absorption surface 200 m 2 Sabin, hemispherical radiation = direction coefficient 2. These values can be significantly influenced by the indoor characteristics in a positive or negative way. PR GB Subject to modifications R2-04/

14 Shipping and Storage MultiMAXX HT 3 Shipping and Storage 3.1 Shipping Manufacturer s instructions regarding transporting and storing the unit must be followed (see labels on the packing). When the air curtain is delivered and unpacked, check that the delivery is correct according to the despatch note, and also check for completeness and transit damage. Ship and store air curtains in original packing! EQUIPMENT DAMAGE! After the shipment ensure that the unit is not damaged. Claims for damage or missing parts can only be filed with the insurance company only if shipping damage is confirmed by an authorized worker of the transportation company. 3.2 Shipping and handling of unit Attach lifting gear to the designated points of the assembly unit. Chains/slings should not be knotted and/or be exposed to sharp edges. Special attention must be given to equal weight distribution. Only lifting gear with sufficient load carrying capacity is allowed. DANGER OF OVERHEAD LOADS! Do not raise units overhead with personnel below units. PERSONAL INJURY! Do not use damaged transport devices. Use a fork lift truck only if the unit is placed on a pallet. DANGER SHARP CUTTING EDGES! Use personal protective equipment such as safety gloves, footwear and clothes for unit shipping. 3.3 Storage Protect the MultiMAXX HT unit from humidity and dirt. The unit must be stored in a weather-proof manner indoors in accordance with class IE12 and EN standard. Allowed storing conditions: Air temperature: -25 C to +40 C Air humidity: between 50 and 85 % (relative humidity with no condensation) 14 PR GB Subject to modifications R2-04/2016

15 MultiMAXX HT Assembly 4 Assembly 4.1 Load-bearing capacity of the installation site The assembly site must be vibration-free and suitable for permanently supporting the weight of the gate air curtain unit. If necessary, the approval of a structural engineer or architect has to be received. For mounting the unit, 2 sets with 4 M8 nuts are placed on the fan module refer to Fig. 2.4 and Fig The fixing material is enclosed with suspensions. Unused M8 riv-nuts should be covered by M8 screws that hold the unit to the transport pallet. 4.2 Horizontal installation It is necessary to consider the suspension height and minimum distance to ceiling. Horizontal installation with profile outlet (P) Horizontal installation with gate nozzle (T) Fig. 4-1: Max. suspension height with horizontal installation - P and T outlet. Dimension Model size (m) HT82 HT83 HT84 HT93 HT94 A B C The data in the chart are approximated values and apply to 3rd fan speed and discharge temperature exceeding indoor temperature by Δ15 to 20 K. PR GB Subject to modifications R2-04/

16 Assembly MultiMAXX HT The maximum suspension height for horizontal installation depends on the fan speed - the lower the speed, the smaller the height. Minimum clearance to ceiling (see figures) provides enough space for air intake and service and maintenance. If the minimum clearance to ceiling is not adhered to, unit capacity can change and fan can be damaged. 4.3 Vertical installation Vertical installation with profile outlet (P) Vertical installation with gate nozzle (T) Fig. 4-2: Max. gate width for vertical installation - P and T outlet. Dimension (m) Model size HT82 HT83 HT84 HT93 HT94 A (8.0) 4.5 (8.0) 5.0 (8.5) 5.0 (8.5) B C (10.0) 5.5 (10.0) 6.0 (10.5) 6.0 (10.5) The data in the chart are approximated values and apply to 3rd fan speed and discharge temperature exceeding indoor temperature by Δ15 to 20 K. Values in brackets apply to two units that are installed at two opposing gate sides. 16 PR GB Subject to modifications R2-04/2016

17 MultiMAXX HT Assembly For wide gates two opposite air curtain units can be installed. (see table page 16) Minimum clearance to wall (see figures) provides enough space for air intake and service and maintenance. If the minimum clearance to wall is not adhered to, unit capacity can change and fan can be damaged. 4.4 Safety clearance When installing your air curtain unit, the following safety clearances must maintained: at least 400 mm from unit sides and 1000 mm in air flow direction (as specified by CSN and CSN ). 4.5 Unit installation For horizontal configuration units must be installed level to allow access for air venting and draining of the heat exchanger. Draining the heat exchanger with a vertical installation is carried out using the drain valve which is located at the bottom side of the heat exchanger. An air vent valve must be installed by others on site. The casing of the heat exchanger must be protected during soldering of connection fittings. EQUIPMENT DAMAGE! The unit must be installed in a stain-free, vibration-free and twist-free way. Gate air curtains must be installed in a safe, reliable and visually adequate manner. For these reasons, it is recommended to use manufacturer s suspensions and mounting brackets. PR GB Subject to modifications R2-04/

18 Coil Connection MultiMAXX HT 5 Coil Connection 5.1 Pipe connections The supply and return piping shall be run in such a way as to prevent mechanical stress and without placing a strain on the heat exchanger. Sufficient clearance around the gate air curtain unit must be ensured to allow for maintenance and servicing. Connected piping: pipe and heat exchanger venting must be performed by others on site! Attention! Inlet and outlet heating coil connections: give special attention to fitted labels! EQUIPMENT DAMAGE! Use a pipe wrench when attaching piping to coil fittings to prevent damage (refer to Fig. 5.1). Fig. 5-1: Connecting unit to pipework 5.2 Dimensions of heat exchanger connections For dimensions refer to Fig. 2-4 and Fig. 2-5 as well as heat exchanger connections in Tab PR GB Subject to modifications R2-04/2016

19 MultiMAXX HT Electrical Connection 6 Electrical Connection HAZARDOUS VOLTAGE! The electrical installation of the MultiMAXX HT air curtain unit must only be carried out by qualified electricians in observance of the current operation manual and the following regulations: VDE regulations, including safety regulations Accident prevention regulations Installation instructions 6.1 Wiring diagrams The electrical connection of MultiMAXX HT air curtain units must be performed in accordance with the valid connection diagrams. The connection diagram is attached to the inside cap of the fan isolator (see Fig. 6.1) or is enclosed separately. HAZARDOUS VOLTAGE! The connection diagrams do not specify any protective measures. Currently valid standards and regulations must be observed and checked with the local power company Cable connections The cable connections must be performed in compliance with the local regulations and code of practice. The selection of cable type and cable cross section must be performed by a qualified electrical engineer. Addition of components by others and field line runs must be designed for high temperatures and fitted with spacers. Electrically screened line must be used for the thermal contact and earth screen must be connected on one side to the protective conductor terminal (PE) in the control unit. The decision to apply electrical shielding at both ends can only be made on site (e.g. in case of severe interference) and the relevant applicable local regulations and codes of practice must be observed. After successful cable installation all cable entry points must be sealed in a splashproof manner Motor protection using thermal contact Fan motors of the MultiMAXX HT units are standard fitted with thermal contacts.the fusing and fan motor overtemperature protection is performed by wiring thermal contact to the control cabinet. Thus unit disconnection is ensured in a fault case. If the unit is operated by an external regulation system the thermal contact must be incorporated in the safety circuit. In this case DencoHappel can not assume any warranty obligations for such unit Operation of basic unit Air curtains can be operated with control units designed for recirculating-air units (refer Fig. 6-5). Operation with frequency converters or switch units with voltage reduction (e.g. transformer) is not possible. PR GB Subject to modifications R2-04/

20 Electrical Connection MultiMAXX HT 6.2 Fan isolator The MultiMAXX HT air curtain units are supplied with a fan isolator. 1 2 Fig. 6-1: Position of fan isolator and terminal box Pos. 1 - Fan isolator (unit connection) Pos. 2 - Intermediate terminal box Fan isolator The fan isolator is only used to deactivate the fans for servicing and maintenance. It is not allowed to use this isolator for regular activation and deactivation of the unit. At the same time this isolator is used for incorporating the unit in the electrical circuit. 20 PR GB Subject to modifications R2-04/2016

21 MultiMAXX HT Electrical Connection 6.3 Motor terminal diagram for 3-speed three-phase external rotor motor 3 x 400 V, 50 Hz (motor type S) With thermal contacts With pole-changing capability Winding ΔΔ/YY/Δ Without voltage change-over! For operating voltage refer to the unit identification plate speed operation at operating voltage 3 x 400 V with three-speed control unit (MC 303) (3 x 400 V) Connection cable: 9 + PE = 10 wires Electrically screened cable: 2 TC connecting wires Fig. 6-2: Motor terminal diagram - 3-speed operation speed operation at operating voltage 3 x 400 V Connection cable: 3 + PE = 4 wires Electrically screened cable: 2 TC connecting wires 1-stage mode: stage III (ΔΔ) 1-speed mode: speed II (YY) 1-speed mode at speed I (Δ) Fig. 6-3: Motor terminal diagram - 1-speed operation In order to ensure proper operation of the unit, rotation direction marked with an arrow on the fan impeller must be maintained. To reverse the fan in case of wrong rotation direction, 2 phases must be changed. PR GB Subject to modifications R2-04/

22 Electrical Connection MultiMAXX HT 6.4 Wiring with control units MC 303 or controls by others The components are connected via a terminal strip. ATTENTION! CONTROL UNITS! Wiring diagrams are enclosed with the corresponding MC 303 control units. NOTICE ON CONTROLS BY OTHERS! For details on connecting individual assemblies (e.g. fan, anti-freeze facility, etc.) refer to the unit-specific wiring diagram enclosed with the main unit. Before commencing connections, check that the order code of the unit's electrical equipment matches the wiring diagram. HAZARDOUS VOLTAGE! Before opening the connection box, the air curtain unit must be de-energised and isolated at all poles. Connections must only be performed in accordance with the unit-specific wiring diagram. 6.5 Wiring room thermostat Fig. 6-4: Wiring room thermostat 22 PR GB Subject to modifications R2-04/2016

23 MultiMAXX HT Electrical Connection Room thermostat or gate terminal Intermediate terminal box Type: Power supply Control unit MC 303 Fig. 6-5: Wiring schematic for MultiMAXX HT and MC 303 control unit Required number of wires Control unit MC 303 3x400 V/50 Hz Cable 1 (power supply) 5 Cable 3 (fan motor) 10 Cable 4 (thermostat / gate contact) 4 / 2 Cable 5 (thermal contact) 2 The MC 303 control unit can be simultaneously used for two gate air curtain units (parallel operation). Wiring is performed using an additional intermediate terminal box. PR GB Subject to modifications R2-04/

24 Commissioning MultiMAXX HT 7 Commissioning HAZARDOUS VOLTAGE! Before performing any work on the unit, ensure that the latter is isolated. Ensure that the unit is isolated and secured against being energised at an appropriate point of the on-site power supply. DANGER OF SCALDING! Prior to performing any work on the air curtain unit: Seal off the supply of heating medium before performing work on the valves or the inlet or outlet pipework. Ensure that the shut off pipework can not be opened inadvertently. Do not commence work before the heating medium has cooled down. WARNING: RISK OF ROTATING COMPONENTS! Rotating fan impellers pose a risk and may cause injuries. Before performing any work on the unit, ensure that the latter is isolated. Ensure that the unit is isolated and secured against being energised at an appropriate point of the on-site power supply. Before the commissioning make sure that the unit discharge (heat exchanger) is clean. Protect all electrical equipment and adjacent hardware against leaking water. 7.1 Pre-commissioning checklist Mechanical and electrical installation of the entire system comprising MultiMAXX HT unit is complete. The MultiMAXX HT unit is de-energised and isolated. All medium pipes were flushed and are free from residues and foreign matter. The unit is properly charged with medium (refer to "Proper use" on page 18) Prior to commissioning the following checks must be carried out: Check all screwed pipe connections and fixing points. Check the unit for possible damage. (ensure that the air curtain is error-free). Checking plug fan: minimum clearance between impeller and air suction nozzle must correspond to a minimum 1% of impeller cross section. Open the valves in the pipework. If the pipework / heat exchanger were drained following the assembly, charge the system properly and perform its air venting.(refer to section 7.2). Give special attention to complete air venting of the unit in order to prevent formation of air bubbles in the heat exchanger. Check that the pipework and connections and tight and leak-free. Check electric connections and wiring, as specified in the wiring diagrams of the current operation manual or/and enclosed in the control box of the unit, MC 303 control box. Check correct air flow direction: fan rotating direction is correct, if air is discharged from the discharge louvres into the room. Perform adjustment of secondary-air louvre depending on desired air flow direction. Ensure that air draughts in the occupied zone are eliminated. After checks are carried out, close the plastic electrical control box. Prior to commissioning of the unit fitted with a fan isolator, switch the latter into ON position. 24 PR GB Subject to modifications R2-04/2016

25 MultiMAXX HT Commissioning 7.2 Unit air venting Open all shut-off and control valves. Use an air venting key to open an air vent screw by others. Close the air-vent screw again, only if heating medium is still pouring out. 7.3 Operation Fan Activation and deactivation is performed via a speed selection switch (mounted on MC 303 control box), or using a field-provided control contact. 7.4 Operating instructions Ensure free cross section and unobstructed air discharge at the outlet. Adjust the air flow to provide stable separation of air in the climate-controlled room from outside air. The fan isolator fitted on the unit is used for deactivation of the fan only. This switch is not used as the main isolator or emergency switch. 7.5 Deactivating unit Set the speed selection switch on the MC 303 control box to 0 position. PR GB Subject to modifications R2-04/

26 Maintenance and Troubleshooting MultiMAXX HT 8 Maintenance and Troubleshooting 8.1 Maintenance We recommend to conclude a maintenance contract with a service company. The service firm staff should be trained by the unit manufacturer. HAZARDOUS VOLTAGE! Isolate all power supply connections to the air curtain unit and ensure the power cannot be inadvertently energised. WARNING: RISK OF ROTATING COMPONENTS! Wait to allow the fan rotational momentum to cease! RISK OF ACCIDENT DUE TO HOT MEDIUM! Wait until the heat exchanger of the air curtain unit has cooled down! For unit (air curtain) maintenance - inspections at regular intervals must be observed and possible malfunctions repaired (see Tab. 8.1). Maintenance must only be performed if the unit is fully isolated by authorized and qualified staff. Function test of the unit fan and heat exchanger must be included in the inspection. If necessary, possible dirt and solid deposits must be removed from the heat exchanger. Ensure that the impeller is not obstructed and rotate the fan impeller to ensure free movement. The impeller surface must maintain the same distance to the inlet nozzle. List of regular maintenance procedures The following maintenance tasks must be performed at the indicated time intervals. Maintenance interval Components Half-yearly Annually Before cooling season Checking air intake grille * x Checking air discharge grille * x Checking fan or fan section * x Checking screw connections of pipes** x Checking electrical connections x Checking earthing x Air venting heat exchanger ** x Checking antifreeze agent (if used) in medium * If necessary, clean and remove foreign objects Tab. 8-1: Regular maintenance 26 PR GB Subject to modifications R2-04/2016

27 MultiMAXX HT Maintenance and Troubleshooting 8.2 Half-yearly maintenance Checking fan Check: fan impeller to confirm it turns freely in the proper direction power supply cable of the fan motor for damage power supply cable of the fan motor on the terminal strip mounted on the fan module 8.3 Annual maintenance Cleaning heat exchanger Compressed air can be used to clean a dirty heat exchanger. Remove the outlet louvre before cleaning the heat exchanger. Adhere to the specified sequence (1-3) when removing heat exchanger (see Fig. 8-1). Use a compressed-air jet (2) to clean the heat exchanger fins. Mount the louvre on the unit. For unit commissioning follow the relevant instructions specified in chapter 7 Commissioning. Fig. 8-1: Cleaning heat exchanger EQUIPMENT DAMAGE! Beware not to damage fins or louvres during cleaning of heat exchanger. Non compliance will result in the reduction of heating output. Drain water from the heat exchanger, if the air curtain is deactivated for the winter period. Otherwise this may cause water in the heat exchanger to freeze. PR GB Subject to modifications R2-04/

28 Maintenance and Troubleshooting MultiMAXX HT 8.4 Operating faults Symptom Possible cause Action/remedy Fan fails to start Unit not switched on Switch on unit Fan isolator (optional) is activated Warning lamp "Operation" on the MC Missing supply voltage Check fuse/circuit breaker/power supply (technical personnel only) 3xx control panel is inactive Electric lines not connected Connect electrical cables (technical personnel only) Failure in unit fusing Replace fuses (technical personnel only) Controller switched off fan on reaching room temperature Refer to the operation manual for control panels, increase the setpoint on the control panel. Fan fails to start Fan isolator (optional) is activated Warning lamp "STOP" (fault) on the MC 3xx control panel is active Unit too noisy Unit fails to heat/heats insufficiently (pumped warm water) Water leakage around unit Motor protection was activated Unit running at too high RPM Air intake or discharge areas blocked Noisy fan bearings Fan not switched on Air flow rate of unit too low Air intake or discharge areas blocked Fan blocked/faulty Heating medium is not hot Water flow rate too low Leaking heat exchanger or hydraulic connections * Reactivation after cause is eliminated (troubleshooting): Use control panel to set speed selection switch to 0, switch to the required speed again Tab. 8-2: Causes of malfunctions and remedies Check temperature of the fan motor, allow time to cool down, if required, and activate again (in case of a repeated fault always make sure that the cause of the fault is identified). Set a lower RPM Clear discharge/air intake of obstructions or bends Replace faulty fan (technical personnel only) Switch on fan Select higher speed Clear or clean ducts Check fan, replace if necessary (technical personnel only); also refer to Fan fails to start Switch on the heating system (boiler) Switch on the circulating pump Unit air venting Check pump capacity (technical personnel only) Check pipe run balance and adjust using calculated pressure drop (technical personnel only) Check heat exchanger, vent and valve connections for leak-free state On valves, check screw connections for ease of movement, clean sealing surfaces and replace seals, if necessary (technical personnel only) Check soldered joints between collector and heat exchanger tubes and on heat exchanger deflection bends for leaks; in this case, replace heat exchanger (technical personnel only) If the malfunction cannot be eliminated by the maintenance personnel, please consult our authorized service department. 28 PR GB Subject to modifications R2-04/2016

29 MultiMAXX HT Disassembly and Disposal 9 Disassembly and Disposal ENVIRONMENTAL DAMAGE! Dismantling and disposal of the MultiMAXX HT air curtain unit must only be performed by qualified and licensed staff. 9.1 Disassembly For dismantling the MultiMAXX HT unit consider the following instructions: HAZARDOUS VOLTAGE! When carrying out decommissioning and dismantling work on the air curtain, disconnect all power supply connections, ensure the power cannot be inadvertently energised and verify that electrical lines have been disconnected. When carrying out decommissioning and dismantling jobs on the unit, isolate all power supply connections and ensure that power cannot be inadvertently energised. Earth and isolate all adjacent live parts. Non-compliance can lead to death or serious injury. HIGH PRESSURE HAZARD! When carrying out decommissioning and dismantling jobs on the air curtain, shut off and evacuate/empty all connected piping until system pressure has equalized with ambient air pressure. Failure to follow safety precautions can result in serious injury. Isolate all connections and ensure there are no leaking materials such as oil, refrigerant and water-glycol mix. Loosen the connections. PERSONAL INJURY Secure the air curtain against slipping. Relevant shipping instructions for units must be followed. 9.2 Recycling RECYCLING! Ensure safe and environmentally friendly disposal of operating, auxiliary and packing materials as well as spare parts. Consider and follow local regulations and codes of practice regarding recycling procedures. For disposal - unit components must be separated and grouped according to their features and material type in the best possible manner (refer to unit specification on page 11). ENVIRONMENTAL DAMAGE! Dispose of all operating materials (e.g. oil, refrigerant and water-glycol mix) and components in an environmentally-friendly manner and in compliance with local laws and regulations. PR GB Subject to modifications R2-04/

30 MultiMAXX HT PR GB Subject to modifications R2-04/

31 MultiMAXX HT EC Declaration of Conformity pursuant to Directive 2006/42/EC of the European Parliament and of the Council (original EC Declaration of Conformity) 2016/092/5AA68788 Manufacturer: DencoHappel CZ a.s., Slovanská 781, Liberec XXV - Vesec, Czech Republic, ID No.: Entity authorized to compile technical documentation: DencoHappel CZ a.s., Slovanská 781, Liberec XXV - Vesec, Czech Republic, ID No.: Description and identification of machinery: Air curtains SAHARA MAXX / MultiMAXX type HTXX.XXXXXX.XXX including accessories and MC 303 control cabinet Air curtains SAHARA MAXX HT/MultiMAXX HT, including accessories and MC 303 control cabinet, are installed in industrial, warehouse, sale and exposition buildings, i.e. standard environment pursuant to EN It is used to prevent the passage of untreated outside air into the interior of the building and the leakage of conditioned air from within. It is possible to order accessories, such as brackets and control cabinets (controls) with corresponding sensors. Declaration: The machinery complies with all relevant provisions of Directives 2006/42/EC, 2014/30/EC and 2014/35/EC. List of harmonized standards applied in the conformity assessment: EN 953+A1:2009, EN 1037+A1:2009, EN ISO 12100:2011, EN ISO :2009, EN ISO 13857:2008, EN ISO 3746:2011, EN ISO 11202:2011, EN ed.2:2003, EN ed.2:2004, EN :1998, EN 62233:2008 List of other technical standards and regulations: EN 307:1999 This declaration relates exclusively to the machinery in the state in which it was placed on the market, and excludes components which are added and/or operations carried out subsequently by the final user. Issued at Liberec: Name, title: Ing. Jiří Doubrava, chairman of the board Signed PR GB Subject to modifications R2-04/

32 DencoHappel is a global company with expertise in air treatment, air conditioning and air filtration. Our nearest sales and service teams will be glad to discuss ideas and develop creative and effective solutions with you. DencoHappel CZ a.s. Subject to modifications R2-04/2016 PR GB

MultiMAXX HN OPERATION MANUAL

MultiMAXX HN OPERATION MANUAL MultiMAXX HN OPERATION MANUAL FläktGroup product range MultiMAXX HN FläktGroup product range 2 FläktGroup DC-2011-0143-GB 2018-05/R4 Subject to modifications MultiMAXX HN Unit Type Code Unit Type Code

More information

OPERATION MANUAL Decentral Systems Industry Multi Flair. Technological and Optical Perfection

OPERATION MANUAL Decentral Systems Industry Multi Flair. Technological and Optical Perfection OPERATIO MAUAL Decentral Systems Industry Multi Flair Technological and Optical Perfection Multi Flair DencoHappel product range 2 PR-2008-0402-GB Subject to modifications R5-/205 Multi Flair Unit Type

More information

We have some on stock... GEA MultiMAXX Prompt. Unit Heaters Data & Facts. GEA Heat Exchangers / HVAC Systems

We have some on stock... GEA MultiMAXX Prompt. Unit Heaters Data & Facts. GEA Heat Exchangers / HVAC Systems We have some on stock... GEA MultiMAXX Prompt Unit Heaters Data & Facts GEA Heat Exchangers / HVAC Systems Short Description/Overview of Capacity Quick solution for heating of industrial halls For more

More information

Installation and operating instructions. DK energy storage and DK energy buffer

Installation and operating instructions. DK energy storage and DK energy buffer Installation and operating instructions DK energy storage and DK energy buffer Edition: 08-2015 1 Preliminary note With this DK energy storage / DK energy buffer you purchased a DK quality product. The

More information

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59 SOUND-INSULATED FAN OPERATION MANUAL _v.1(2)-en.indd 1 10.08.2015 15:20:59 CONTENT Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 3 Fan design 4 Delivery

More information

Operating instructions

Operating instructions ebm-papst Mulfingen GmbH & Co. KG Bachmühle D-74673 Mulfingen Phone +49 (0) 793-0 Fax +49 (0) 793-0 info@de.ebmpapst.com www.ebmpapst.com CONTENTS. SAFETY REGULATIONS AND NOTES. Levels of hazard warnings.

More information

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

INSTALLATION, COMMISSIONING AND OPERATING MANUAL INSTALLATION, COMMISSIONING AND OPERATING MANUAL 1 YTBV-D-CE42_0109 CONTENT Available models and capacities Supplier information Warranty Safety Emergency stops/ shutdowns About this manual Models Physical

More information

INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL

INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL CONTENT 3 Introduction 3 General 3 Safety rules 3 Storage and transportation rules 3 Manufacturer s warranty 4 Fan design 4 Delivery set 5 Technical data

More information

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4 Installation Operation Maintenance Ductable water unit FWD 08-12 - 20-30 - 45 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice

More information

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING USER S MANUAL VCU/ Series CENTRIFUGAL FAN IN SCROLL CASING 2 CONTENTS Introduction Use Delivery set Designation key Technical data Safety requirements Design and operating logic Mounting and set-up Connection

More information

Installation manual surface mounting plugs and socket outlets, panel mounting plugs and socket outlets with screw connection (16/32 A)

Installation manual surface mounting plugs and socket outlets, panel mounting plugs and socket outlets with screw connection (16/32 A) EN Installation manual surface mounting plugs and socket outlets, panel 60003214 Issue 04.2016 2016-04-01 Table of contents 1 About this manual 3 1.1 Structure of the warnings 3 1.2 Symbols used 4 1.3

More information

USER S MANUAL. Heat Recovery Ventilator. Vents Brig HRV 200 Vents Brig HRV 300

USER S MANUAL. Heat Recovery Ventilator. Vents Brig HRV 200 Vents Brig HRV 300 USER S MANUAL Heat Recovery Ventilator Vents Brig HRV 200 Vents Brig HRV 300 2 Brig HRV 200 (300) CONTENT Introduction... 3 Application... 3 Delivery set... 3 Unit designation key... 4 Basic unit dimensions...

More information

HEAT RECOVERY AIR HANDLING UNIT

HEAT RECOVERY AIR HANDLING UNIT HEAT RECOVERY AIR HANDLING UNIT OPERATION MANUAL KOMFORT_L v2(2)_en.indd 1 07.08.2015 15:0:44 CONTENTS Introduction General Safety regulations Transportation and storage regulations Manufacturer's warranty

More information

OPERATION AND MONTAGE MANUAL ROOF FANS

OPERATION AND MONTAGE MANUAL ROOF FANS NO RFEC/U/2017-1 (EN) (valid since 18.08.2017) ROOF FANS RF/EC...-... / RFV/EC...-... Venture Industries Sp. z o.o. is not responsible for any damage caused by improper use of the fan and reserves the

More information

CENTRIFUGAL FAN IN SCROLL CASING. Helix S-Vent OPERATION MANUAL

CENTRIFUGAL FAN IN SCROLL CASING. Helix S-Vent OPERATION MANUAL CENTRIFUGAL FAN IN SCROLL CASING Helix S-Vent EN OPERATION MANUAL Helix / S-Vent www.blaubergventilatoren.de CONTENTS CONTENTS 3 Introduction 3 Use 3 Delivery set 4 Technical data 10 Safety requirements

More information

Installation manual surface mounting plugs and socket outlets, panel mounting plugs and socket outlets QUICK-CONNECT (63 A)

Installation manual surface mounting plugs and socket outlets, panel mounting plugs and socket outlets QUICK-CONNECT (63 A) EN Installation manual surface mounting plugs and socket outlets, panel 60003506 Issue 04.2016 2016-04-01 Table of contents 1 About this manual 3 1.1 Structure of the warnings 3 1.2 Symbols used 4 1.3

More information

OPERATION AND MONTAGE MANUAL ROOF FANS

OPERATION AND MONTAGE MANUAL ROOF FANS NO RF/U/2017 (ENGLISH) (valid since 13.10.2017) ROOF FANS RF / RFV Venture Industries Sp. z o.o. is not responsible for any damage caused by improper use of the fan and reserves the right to modify this

More information

Installation manual plugs and connectors QUICK-CONNECT (63 A)

Installation manual plugs and connectors QUICK-CONNECT (63 A) EN Installation manual plugs and connectors QUICK-CONNECT (63 A) 60003217 Issue 04.2016 2016-04-01 Table of contents 1 About this manual 3 1.1 Structure of the warnings 3 1.2 Symbols used 4 1.3 Signal

More information

Installation manual extra-low-voltage socket outlets for panel- and surface-mounting

Installation manual extra-low-voltage socket outlets for panel- and surface-mounting EN Installation manual extra-low-voltage socket outlets for panel- and 60003221 Issue 04.2016 2016-04-01 Table of contents 1 About this manual 3 1.1 Structure of the warnings 3 1.2 Symbols used 4 1.3 Signal

More information

TTV 4500 / TTV 4500 HP / TTV 7000

TTV 4500 / TTV 4500 HP / TTV 7000 TTV 4500 / TTV 4500 HP / TTV 7000 EN OPERATING MANUAL AXIAL FAN TRT-BA-TTV4500-4500HP-7000-TC-003-EN Table of contents The current version of the operating manual can be found at: Notes regarding the operating

More information

LS Condensate Removal Pump INSTRUCTION MANUAL REVISION A

LS Condensate Removal Pump INSTRUCTION MANUAL REVISION A LS Condensate Removal Pump INSTRUCTION MANUAL 6-71-075-115 REVISION A CAUTION: Combustible liquids may not be pumped! The condensate pump may not be run dry, as this can destroy the bearings in a very

More information

User Manual GV25 GV35 GV702. Company information: Original instructions GV12066 (1)

User Manual GV25 GV35 GV702. Company information:   Original instructions GV12066 (1) User Manual Original instructions GV25 GV35 GV702 Company information: www.vipercleaning.eu info-eu@vipercleaning.com GV12066 (1) 2012-04-10 USER MANUAL ENGLISH TABLE OF CONTENTS Introduction... 4 Manual

More information

Read this manual through carefully before installing/using the cleaner, paying special attention to the SAFETY INSTRUCTIONS

Read this manual through carefully before installing/using the cleaner, paying special attention to the SAFETY INSTRUCTIONS PW1370TD 2 EN Read this manual through carefully before installing/using the cleaner, paying special attention to the SAFETY INSTRUCTIONS 3 E3 E1 C3 A1-A2-A3-A4 B4 B1 B5 B2 C1 B3 D 1 4 1 2 3 4 5 6 7 Ø13

More information

AXIS-QA G TUBO-M/MZ AXIAL FANS. Axis / Tubo OPERATION MANUAL

AXIS-QA G TUBO-M/MZ AXIAL FANS. Axis / Tubo OPERATION MANUAL TUBO-M/MZ AXIS-QA AXIS-Q TUBO-F AXIS-QR AXIS-F AXIS-QRA AXIS-QA G AXIAL FANS EN OPERATION MANUAL www.blaubergventilatoren.de CONTENT 3 Introduction 3 General 3 Safety rules 3 Transport and storage requirements

More information

DATA & FACTS Clean Rooms DencoHappel Air Shower. Active Air Shower for Personnel in Clean Rooms

DATA & FACTS Clean Rooms DencoHappel Air Shower. Active Air Shower for Personnel in Clean Rooms DATA & FACTS Clean Rooms DencoHappel Air Shower Active Air Shower for Personnel in Clean Rooms Clean Rooms DencoHappel Air Shower Table of Contents Introduction... 3 Unit setup and components... 3 Cleaning

More information

General safety precautions English

General safety precautions English English 1 1 1.1 About the documentation The original documentation is written in English. All other languages are translations. The precautions described in this document cover very important topics, follow

More information

Installation and assembly instructions. for standard configuration radial blowers

Installation and assembly instructions. for standard configuration radial blowers Installation and assembly instructions for standard configuration radial blowers 001_KL01_01 Printed in Germany We reserve the right to change the information and illustrations shown in this operating

More information

INLINE CENTRIFUGAL FAN. Centro-M OPERATION MANUAL

INLINE CENTRIFUGAL FAN. Centro-M OPERATION MANUAL INLINE CENTRIFUGAL FAN OPERATION MANUAL www.blaubergventilatoren.de CONTENT 3 Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 4 Fan design 4 Delivery

More information

Decentralised ventilation units

Decentralised ventilation units Notes on installation Decentralised ventilation units FSL / SCHOOLAIR GB/en TROX GmbH Heinrich-Trox-Platz 47504 Neukirchen-Vluyn Germany Phone: +49 (0) 2845 2020 Fax: +49 (0) 2845 202265 E-mail: trox@trox.de

More information

K Operating Instructions. Before first use of the unit read these operating instructions and act in accordance with them.

K Operating Instructions. Before first use of the unit read these operating instructions and act in accordance with them. K 1.100 Operating Instructions Before first use of the unit read these operating instructions and act in accordance with them. www.kaercher.com/register-and-win 59651430 (10/13) Contents General information..............

More information

Steam Trap BK 45 BK 45-U BK 45-LT BK 46

Steam Trap BK 45 BK 45-U BK 45-LT BK 46 Steam Trap BK 45 BK 45-U BK 45-LT BK 46 Original Installation Instructions 810437-08 Contents Foreword... 3 Availability... 3 Formatting features in the document... 3 Safety... 3 Use for the intended purpose...

More information

VADA - V80-H PRODUCT OVERVIEW CONSTRUCTION USAGE LIMITATIONS MOTOR WARRANTY

VADA - V80-H PRODUCT OVERVIEW CONSTRUCTION USAGE LIMITATIONS MOTOR WARRANTY PRODUCT OVERVIEW The VADA horizontal multistage centrifugal pumps combine the functional benefits of centrifugal pumps and the practical benefits of self priming pumps. They warrant high hydraulic and

More information

p Permanent magnet water cooled motors Additional manual

p Permanent magnet water cooled motors Additional manual p Permanent magnet water cooled motors Additional manual Safety Instructions 1 General General safety regulations, safety precautions and specific agreements made for each work site shown in this document

More information

USER S MANUAL. VKP Series INLINE FAN

USER S MANUAL. VKP Series INLINE FAN USER S MANUAL Series INLINE FAN 2 CONTENTS Safety requirements 3 Introduction 5 Use 5 Delivery set 5 Designation key 5 Technical data 5 Design and operating logic 8 Mounting and set-up 8 Connection to

More information

USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES

USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES Bucket Fan 420 Bucket Fan 1055 Bucket Fan 1460 420 1055 1460 2 Bucket Fan CONTENT INTRODUCTION 3 USE 3 WHAT S INCLUDED IN THE BOX 3 DESIGNATION

More information

Contents. Safety instructions. Device elements. Colour coding. Hazard levels

Contents. Safety instructions. Device elements. Colour coding. Hazard levels Please read and comply with these original instructions prior to the initial operation of your appliance and store them for later use or subsequent owners. Contents Device elements........... EN 1 Safety

More information

Katherm NE - Natural convection with electric heating element 2.45

Katherm NE - Natural convection with electric heating element 2.45 1.26 1.45 Katherm NE - Natural convection with electric heating element 2.45 Please retain this manual carefully for future use! Read carefully prior to commissioning! I 60/0/09/01 GB 2.45 Katherm NE -

More information

USER S MANUAL. Heat (Energy) Recovery Ventilator. Vents Frigate HRV 120 S Vents Frigate ERV 120 S

USER S MANUAL. Heat (Energy) Recovery Ventilator. Vents Frigate HRV 120 S Vents Frigate ERV 120 S USER S MANUAL Heat (Energy) Recovery Ventilator Vents Frigate HRV 120 S Vents Frigate ERV 120 S 2 Frigate HRV(ERV) 120 S CONTENT Introduction... 3 Application... 3 Delivery set... 3 Unit designation key...

More information

CRU-S Series Stainless Steel Condensate Recovery Unit

CRU-S Series Stainless Steel Condensate Recovery Unit IM-UK-CRU-S UK Issue 1 CRU-S Series Stainless Steel Condensate Recovery Unit 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Storage, shutdown and equipment protection

More information

Original operating instructions Safety switch with guard locking AC901S AC902S

Original operating instructions Safety switch with guard locking AC901S AC902S Original operating instructions Safety switch with guard locking AC901S AC902S 7390914/03 01/2017 Contents 1 Preliminary note...4 1.1 Explanation of symbols...4 2 Safety instructions...4 3 Items supplied...5

More information

V80-H Multistage Pump Instruction Manual

V80-H Multistage Pump Instruction Manual V80-H Multistage Pump Instruction Manual PRODUCT OVERVIEW The VADA horizontal multistage centrifugal pumps combine the functional benefits of centrifugal pumps and the practical benefits of self priming

More information

TopVent Design Handbook

TopVent Design Handbook TopVent Design Handbook Recirculation Units and Supply Air Units for Heating and Cooling High Spaces TopVent Content TopVent DHV Recirculation unit for heating high spaces TopVent NHV Recirculation unit

More information

GLEB Kitchen exhaust fan

GLEB Kitchen exhaust fan GLEB Kitchen exhaust fan Installation and Maintenance??.1.2013 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN.

OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN. INSTALLATION, OPERATION & SERVICE MANUAL FOR COOLER TYPES OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN. 1. Introduction This manual is a guide for the installation, maintenance

More information

FSA-Series Heavy-Duty Flat panel Emitter Architectural Electric Overhead Infrared Heaters

FSA-Series Heavy-Duty Flat panel Emitter Architectural Electric Overhead Infrared Heaters TPI Corporation P.O. Box 4973 Johnson City, TN 37602 www.tpicorp.com FSA-Series Heavy-Duty Flat panel Emitter Architectural Electric Overhead Infrared Heaters FSA-14 FSA-43 FSA-31 FSA-95 IMPORTANT SAFETY

More information

SMHA Hatch High temperature fan HT-fan Installation and Maintenance

SMHA Hatch High temperature fan HT-fan Installation and Maintenance High temperature fan HT-fan Installation and Maintenance 22.8.2012 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

SINGLE-ROOM REVERSIBLE UNIT WITH HEAT AND HUMIDITY RECOVERY VENTO V50-1 OPERATION MANUAL

SINGLE-ROOM REVERSIBLE UNIT WITH HEAT AND HUMIDITY RECOVERY VENTO V50-1 OPERATION MANUAL SINGLE-ROOM REVERSIBLE UNIT WITH HEAT AND HUMIDITY RECOVERY VENTO V50-1 EN OPERATION MANUAL CONTENTS Introduction 3 General 3 Safety rules 3 Transportation and storage rules 3 Manufacturer's warranty 3

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance DUCTABLE WATER UNIT FWD 08-12 - 20-30 - 45 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice

More information

52 CEILING FAN. Owner s Manual Models #50336, 50337

52 CEILING FAN. Owner s Manual Models #50336, 50337 52 CEILING FAN Owner s Manual Models #50336, 50337 If a problem cannot be remedied or you are experiencing difficulty in installation, please contact the Service Department: 1-877-706-3267, 9 a.m.- 5 p.m.

More information

FSS-Series Heavy-Duty Flat panel Emitter Electric Overhead Infrared Heaters

FSS-Series Heavy-Duty Flat panel Emitter Electric Overhead Infrared Heaters TPI Corporation P.O. Box 4973 Johnson City, TN 37602 www.tpicorp.com FSS-Series Heavy-Duty Flat panel Emitter Electric Overhead Infrared Heaters FSS-14 FSS-43 FSS-31 FSS-95 IMPORTANT SAFETY INFORMATION

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Installation, Operation and Maintenance Manual Packaged Chiller Models CC 6601, 6501, 6401, 6301, 6201, 6101 For Service, please contact Pfannenberg Service Company: U.S.A. Pfannenberg Inc. 68 Ward Road.

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

BMA 0010 Instruction and Installation Manual Oil-Air Cooler ACN

BMA 0010 Instruction and Installation Manual Oil-Air Cooler ACN BMA 0010 Instruction and Installation Manual Oil-Air Cooler ACN Compact oil-air cooler High cooling capacity High operating pressure Low pressure loss Low noise emission Contents 1. Basic information 3

More information

Test Unit GTL 100 for Fire Detectors

Test Unit GTL 100 for Fire Detectors Test Unit GTL 100 for Fire Detectors Description and Operation Manual Zertifiziertes QM System Nach DIN EN ISO 9001 Description and Operation Manual Table of Contents 1. Instructions 1.1 General 1.2 Standards

More information

TTK 75 ECO OPERATING MANUAL DEHUMIDIFIER TRT-BA-TTK75ECO-TC-002-EN

TTK 75 ECO OPERATING MANUAL DEHUMIDIFIER TRT-BA-TTK75ECO-TC-002-EN TTK 75 ECO EN OPERATING MANUAL DEHUMIDIFIER TRT-BA-TTK75ECO-TC-002-EN Table of contents Notes regarding the operating manual... 01 Information about the device... 02 Safety... 04 Transport...05 Start-up...05

More information

Instructions for installation

Instructions for installation Instructions for installation Read this notice carefully before installing, maintaining or repairing this appliance! The symbol indicates important information that you must take into account to avoid

More information

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP WWPPCHLFT260 Instructions WWPPCHLFT260_Horizontal Multistage Centrifugal Pump_IB.indd 1 READ THIS MANUAL CAREFULL BEFORE INSTALL, START THE PUMP 1. Suction 2. Plug

More information

Acquaer Ltd. H-4900, Fehérgyarmat, Szatmári út 11. CENTRIFUGAL PUMP Instruction Manual ACm60 / ACm75 / ACm150 / ACm150B2

Acquaer Ltd. H-4900, Fehérgyarmat, Szatmári út 11. CENTRIFUGAL PUMP Instruction Manual ACm60 / ACm75 / ACm150 / ACm150B2 CENTRIFUGAL PUMP Instruction Manual ACm60 / ACm75 / ACm150 / ACm150B2 Congratulations on your purchase of a LEO Centrifugal Pump It is important that you read, fully understand and observe the following

More information

52 BERKSHIRE CEILING FAN

52 BERKSHIRE CEILING FAN 52 BERKSHIRE CEILING FAN Owner s Manual Models #20223, 20224 If a problem cannot be remedied or you are experiencing difficulty in installation, please contact the Service Department: 1-877-459-3267, 9

More information

STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE

STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE ISO 9001 : 2000 STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE CUSTOMER : 1 CONTENTS 1 SAFETY... 5 1.1 General... 6 1.2 Description of symbols and pictograms... 6

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB -

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw CHGV 22 CHGV 2 CHGV 32 CHGV 40 PHRV heat pump model also available September 2007 10 12 11 - GB - 02

More information

EHA Hoffmann International GmbH

EHA Hoffmann International GmbH EHA Hoffmann International GmbH Operating Instructions EHA - Embossing Press 50-75 Professional Machine number: Model year: The side shelfs are optional and are not included in the Standard scope of delivery.

More information

Installation instructions and operating manual. Sauna control system FCU1000 / FCU1200

Installation instructions and operating manual. Sauna control system FCU1000 / FCU1200 Series FCU1x00 Installation instructions and operating manual Sauna control system FCU1000 / FCU1200 only sauna FCU1000 additional humidity FCU1200 Doc-ID: B_M_FCU1xxx-A5_EN Version: V 1.06 certificated

More information

Operating instructions

Operating instructions Operating instructions (Translation of the original operating instructions) Type TEKA FILTERCUBE-MV TEKA Absaug- und Entsorgungstechnologie GmbH Industriestraße 13 D-46342 Velen Postfach 1137 D-46334 Velen

More information

TTV 1500 / TTV 3000 OPERATING MANUAL CONVEYING FAN TRT-BA-TTV TC EN

TTV 1500 / TTV 3000 OPERATING MANUAL CONVEYING FAN TRT-BA-TTV TC EN TTV 1500 / TTV 3000 EN OPERATING MANUAL CONVEYING FAN TRT-BA-TTV1500-3000-TC2016-26-004-EN Table of contents Notes regarding the operating manual... 2 You can download the current version of the operating

More information

LONGONI ENGINEERING SRL

LONGONI ENGINEERING SRL INDEX 1.1 Classification of heat exchanger and components 1.1.2 Type of heat exchanger and components 1.2 Purpose and scope of the manual 1.3 General instruction 1.4 Warning installation 1.5 Notes for

More information

Operating Instructions. Accessory Units Melitta Cafina XT Series. Melitta Professional Coffee Solutions

Operating Instructions. Accessory Units Melitta Cafina XT Series. Melitta Professional Coffee Solutions Operating Instructions Accessory Units Melitta Cafina XT Series Melitta Professional Coffee Solutions Contents General... 4. Manufacturer information... 4.2 About these instructions... 4.3 Explanation

More information

General safety precautions English

General safety precautions English English 1 1 1.1 About the documentation The original documentation is written in English. All other languages are translations. The precautions described in this document cover very important topics, follow

More information

USER S MANUAL NKP. Duct heater for supply air pre-heating with external control

USER S MANUAL NKP. Duct heater for supply air pre-heating with external control USER S MANUAL Duct heater for supply air pre-heating with external control CONTENTS Contents... 2 Safety requirements... 2 Purpose... 4 Delivery set... 4 Designation key... 4 Technical data... 5 Design

More information

PURESTREAM. ACW Air Cooled Fluid Cooler User and Maintenance Manual AMBIENT FLUID COOLER BY FRIULAIR

PURESTREAM. ACW Air Cooled Fluid Cooler User and Maintenance Manual AMBIENT FLUID COOLER BY FRIULAIR PURESTREAM AMBIENT FLUID COOLER BY FRIULAIR ACW Air Cooled Fluid Cooler User and Maintenance Manual Dear Customer, Please read this manual carefully in order to obtain the best performance from our products.in

More information

INSTRUCTIONS FOR USE

INSTRUCTIONS FOR USE -1- INSTRUCTIONS FOR USE INDUCTION COOKERS Base-Line Fajita Heater SH/BA 3500 FH -2- CONTENT 1 General remarks...3 1.1 Description of danger signs...3 1.2 Purpose of induction cookers...4 2 Description

More information

TIH 300 S / TIH 400 S / TIH 500 S / TIH 700 S / TIH 900 S / TIH 1100 S

TIH 300 S / TIH 400 S / TIH 500 S / TIH 700 S / TIH 900 S / TIH 1100 S TIH 300 S / TIH 400 S / TIH 500 S / TIH 700 S / TIH 900 S / TIH 1100 S EN OPERATING MANUAL INFRARED HEATING PANEL TRT-BA-TIH300S-TIH400S-TIH500S-TIH700S-TIH900S-TIH1100S-TC-002-EN Table of contents Notes

More information

Operating Instructions

Operating Instructions Operating Instructions Varioset Standard After-sales service For after-sales service please contact the Veit representative in your country. GmbH & Co. Justus - von - Liebig - Str. 15 D - 86899 Landsberg

More information

FES - Series Portable Electric Heaters. YES - Series Suspended Electric Heaters CONTENTS

FES - Series Portable Electric Heaters. YES - Series Suspended Electric Heaters CONTENTS FOSTORIA INDUSTRIES, INC. A DIVISION OF FES - Series Portable Electric Heaters YES - Series Suspended Electric Heaters (FES-1524-3E shown) IMPORTANT SAFETY INFORMATION INSIDE Serious injury or death possible.

More information

General safety precautions English

General safety precautions English English A min (m 2 ) 550 530 540 510 520 490 500 470 480 450 460 430 440 410 420 390 400 370 380 350 360 330 340 310 320 290 300 270 280 250 260 230 240 210 220 190 200 170 180 150 160 130 140 110 120

More information

Translation of the original instructions. Type: MKR 600

Translation of the original instructions. Type: MKR 600 Lebensmitteltechnik Translation of the original instructions - Tumbler Type: MKR 600 Rühle GmbH, Beim Signauer Schachen 10, D-79865 Grafenhausen Tel.: +49 7748 523-11, Fax: +49 7748 523-8511 www.original-ruehle.de

More information

General safety precautions English

General safety precautions English English A min (m 2 ) 550 530 540 510 520 490 500 470 480 450 460 430 440 410 420 390 400 370 380 350 360 330 340 310 320 290 300 270 280 250 260 230 240 210 220 190 200 170 180 150 160 130 140 110 120

More information

Pond Pump 280 / 420 / 575. Operating instructions Notice d emploi Instrucciones de uso

Pond Pump 280 / 420 / 575. Operating instructions Notice d emploi Instrucciones de uso Pond Pump 280 / 420 / 575 Operating instructions Notice d emploi Instrucciones de uso REMINDER CALL 1-866-627-3435 BEFORE RETURNING TO STORE. Part Description QTY A Pump 1 B 3/4 in. ID tubing adapter with

More information

LS Condensate Removal Pump Installation, Operation and Service Instructions

LS Condensate Removal Pump Installation, Operation and Service Instructions Bell & Gossett Instruction Manual 6-71-075-115 LS Condensate Removal Pump Installation, Operation and Service Instructions INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. WARNING: This safety

More information

TermEfekt USER S MANUAL AIR HEATER. Model PGA 14

TermEfekt USER S MANUAL AIR HEATER. Model PGA 14 Przedsiębiorstwo Produkcyjno-Wdrożeniowe ARAJ sp. z o.o. 55-080 Kąty Wrocławskie, ul. Mireckiego 30 POLAND USER S MANUAL AIR HEATER TermEfekt Model PGA 14 Kąty Wrocławskie, 2004 Product identification

More information

SuperStor Ultra Stainless Steel Storage Tank

SuperStor Ultra Stainless Steel Storage Tank SuperStor Ultra Stainless Steel Storage Tank INSTALLATION START-UP MAINTENANCE PARTS Storage Tank Models SSU-30CB / SSU-45CB SSU-60CB / SSU-80CB / SSU-119CB For Residential and Commercial Use This manual

More information

Operating Manual. VIENNA Hot Display

Operating Manual. VIENNA Hot Display Operating Manual VIENNA Hot Display Operating and Maintenance instructions Please read this manual carefully before you start to operate your heated display case. Following these instructions helps you

More information

THERMAL SYSTEMS, INC. Installation and Operation Manual

THERMAL SYSTEMS, INC. Installation and Operation Manual THERMAL SYSTEMS, INC. Installation and Operation Manual Revised September 2016 1. GENERAL SAFETY INFORMATION 1.1 Specification Never exceed the maximum allowable temperature or pressure ratings. Never

More information

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw Air-Cooled Liquid Chillers Nominal cooling capacity 21-94 kw Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. The

More information

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT Carrier International Sdn. Bhd. Malaysia INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT 40LM 120-200 50Hz CONTENTS: Physical Data & Dimension 1-3 Safety Considerations 4 Rigging

More information

Installation & Maintenance Instructions

Installation & Maintenance Instructions Portable High Temperature Blower Attention: Do not operate this heater in explosive areas. Installation & Maintenance Instructions Dear Owner, Congratulations! Thank you for purchasing this new heater

More information

K 5.80 M ( ) Caution! Do not use the unit without first having read the operating instructions.

K 5.80 M ( ) Caution! Do not use the unit without first having read the operating instructions. K 5.80 M 5.960-830 (2004330-04-03) Caution! Do not use the unit without first having read the operating instructions. Contents Short instructions... 2 Assembly... 3 Safety Notes... 4 Before first use...

More information

Pump WaterVISE, FloVISE

Pump WaterVISE, FloVISE General information It is important that this manual is read carefully by the user and the installer in order to ensure proper functioning and lifespan of the pump. Pahlen pumps are manufactured in accordance

More information

Operating instructions Electric agitator RE80Ex. T-Dok-520-GB-Rev.5 Article no Translation of the original operating instructions

Operating instructions Electric agitator RE80Ex. T-Dok-520-GB-Rev.5 Article no Translation of the original operating instructions GB Operating instructions Electric agitator RE80Ex T-Dok-520-GB-Rev.5 Article no. 200-0332 Translation of the original operating instructions Thank you for selecting a Krautzberger product. This product

More information

52 SAN LUCAS CEILING FAN

52 SAN LUCAS CEILING FAN 52 SAN LUCAS CEILING FAN Owner s Manual Models #20551 If a problem cannot be remedied or you are experiencing difficulty in installation, please contact the Service Department: 1-877-459-3267, 9 a.m.-

More information

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION ECO-FRIENDLY REFRIGERANT GAS INSTALLATION AND OPERATION MANUAL Dear Customer, Thank you for having purchased a FERROLI product. It is the result of many years

More information

INSTRUCTION MANUAL (English version) Water still

INSTRUCTION MANUAL (English version) Water still INSTRUCTION MANUAL (English version) Water still Model : Brand : W4000 Merit Merit Water Still W4000 & W4000/EURO Cooling water inlet Condenser Constant level control Boiler Thermostat reset buttons To

More information

Ceiling Mount Air Purification System

Ceiling Mount Air Purification System Ceiling Mount Air Purification System HA-CMP-G2-R/HA-CMP-G2-OV Owner s Manual Table of Contents HealthyAir Series 1219 Filters 1 Important Safety Instructions 2 Technical Specifications 3 Packaging Reference

More information

AUTOMATIC ICE-CUBE MAKER - INSTRUCTIONS AND WARNINGS

AUTOMATIC ICE-CUBE MAKER - INSTRUCTIONS AND WARNINGS AUTOMATIC ICE-CUBE MAKER - INSTRUCTIONS AND WARNINGS Dear Customer, Congratulations on having chosen a quality product which will certainly fully meet your expectations. Thank you for having purchased

More information

Illustration shows item no Z Original operating manual. Operating manual. BlueMobil 60. Item no: Z-3285

Illustration shows item no Z Original operating manual. Operating manual. BlueMobil 60. Item no: Z-3285 Operating manual BlueMobil 60 Item no: Z-3285 Original operating manual Illustration shows item no Z-3285 Important Copyright It is essential that you read this manual thoroughly before the initial operation

More information

AIRGOCLEAN 10 E OPERATING MANUAL AIR CLEANER TRT-BA-AIRGOCLEAN10E-TC-001-EN

AIRGOCLEAN 10 E OPERATING MANUAL AIR CLEANER TRT-BA-AIRGOCLEAN10E-TC-001-EN AIRGOCLEAN 10 E EN OPERATING MANUAL AIR CLEANER TRT-BA-AIRGOCLEAN10E-TC-001-EN Table of contents Notes regarding the operating manual... 1 You can download the current version of the operating manual and

More information

Operating manual 1 SAFETY REGULATIONS AND INFORMATION. Original operating manual INDEX 2218 F/2TDH4P

Operating manual 1 SAFETY REGULATIONS AND INFORMATION. Original operating manual INDEX 2218 F/2TDH4P Operating manual 2218 F/2TDH4P 1 SAFETY REGULATIONS AND INFORMATION Read the operating manual carefully before commencing work at the product. Pay attention to the following warnings to avoid risk to persons

More information

BESF Box Ventilator. Installation & Operating Manual USA CAN READ AND SAVE THESE INSTRUCTIONS

BESF Box Ventilator. Installation & Operating Manual USA CAN READ AND SAVE THESE INSTRUCTIONS Installation & Operating Manual 3001806 03.02 USA CAN BESF Box Ventilator READ AND SAVE THESE INSTRUCTIONS 1200 Northmeadow Parkway, STE 180 Roswell, GA 30076 (770) 587-3238 (800) 255-2923 Fax (770) 587-4731

More information

Operating manual 1 SAFETY REGULATIONS AND INFORMATION. Original operating manual INDEX. RG CPAP 24 V mit Powermodul 24V sensorless

Operating manual 1 SAFETY REGULATIONS AND INFORMATION. Original operating manual INDEX. RG CPAP 24 V mit Powermodul 24V sensorless Operating manual RG CPAP 24 V mit Powermodul 24V sensorless 1 SAFETY REGULATIONS AND INFORMATION Read the operating manual carefully before commencing work at the product. Pay attention to the following

More information