1 Installation Operation Maintenance Ductable water unit FWD
2 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice in the installation, putting into service, operation and periodic maintenance by the user of FWD units. They do not contain full service procedures necessary for the continued successful operation of this equipment. The services of a qualified service technician should be employed through the medium of a maintenance contract with a reputable service company. Warranty Warranty is based on the general terms and conditions of the constructor. The warranty is void if the equipment is modified or repaired without the written approval of the constructor, if the operating limits are exceeded, or if the control system or the electrical wiring is modified. Damage due to misuse, lack of maintenance, or failure to comply with the manufacturer's instructions, is not covered by the warranty obligation. If the user does not conform to the rules of chapter "Maintenance", it may entail cancellation of warranty and liabilities by the constructor. Reception When the unit arrives on site, check it has not been damaged in any way during transport. If damage is observed, or even merely suspected, notify the carrier within 24 hours by registered letter. Notify the local Trane Sales office at the same time. The unit should be totally inspected within 3 days of delivery. If damage is observed, notify the last carrier by registered letter and notify the local sales office. Warnings and cautions Warnings and Cautions appear at appropriate places in this instruction manual. Your personal safety and the proper operation of this machine require that you follow them carefully. Trane assumes no liability for installations or servicing performed by unqualified personnel. WARNING! : Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION! : Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices or for equipment or property-damageonly accidents Trane 2
3 General Information Safety recommendations To avoid accidents and damage, the following recommendations should be observed during maintenance and service visits: 1. The maximum allowable pressures for system leak testing on low and high pressure side are given in the chapter Installation. Always provide a pressure regulator. 2. Disconnect the main supply before any servicing on the unit. 3. Service work on the refrigeration system and the electrical system should be carried out only by qualified and experienced personnel. Maintenance contract It is strongly recommended that you sign a maintenance contract with your local Service Agency. This contract provides regular maintenance of your installation by a specialist in our equipment. Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur. Finally, regular maintenance ensures the maximum operating life of your equipment. We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty. Training The equipment described in this manual is the result of many years of research and continuous development. To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time, the manufacturer has at your disposal a refrigeration and air conditioning service school. The principal aim of this is to give operators and technicians a better knowledge of the equipment they are using, or that is under their charge. Emphasis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventive maintenance, which reduces the cost of owning the unit by avoiding serious and costly breakdown. 3
4 Contents General Information 2 Foreword 2 Warranty 2 Reception 2 Warnings and cautions 2 Safety recommendations 3 Maintenance contract 3 Training 3 Installation 5 Introduction 5 Technical data 6 Ceiling installation 7 Installation on the ground 7 Condensate drainage 8 Electrical connections 8 Main power supply 9 Duct connections 10 Diagrams 9 Operation / Maintenance 16 Choice of fan speed 16 Initial checks 16 Maintenance recommendations 16 Maintenance 17 Removal of the fan motor 17 Troubleshooting 18 4
5 Installation Introduction Caution. Read this manual carefully before starting to install the system. Components supplied with the unit - 2 corner brackets to suspend the unit from the ceiling Electrical connections - The electrical wiring and connections must comply with local electricity legislation. - Check the electrical characteristics on the name plate correspond to the grid s characteristics. Figure 1 : Description Warning. Never open the electrical panel without first disconnecting the power supply. There is a risk of electrocution! Handling the unit Warning! Wear protection gloves when handling the unit. When removing the unit from its pallet, do not handle it by pipes, spigots, valves, drain pan or control panel. Take precaution to not damage the unit. Description of the unit The FWD unit is a slim discharge cabinet unit for installation in false ceilings, lofts and ventilation spaces. It is designed for horizontal installation with discharge via a duct (see selection catalogue for the available static pressure). The unit s structure consists of unpainted completely insulated galvanised steel panels. ➀ ➁ ➂ ➀ Hot water coil ➁ Fan unit ➂ Control / power cabinet ➃Water inlet and outlet screw-in connections ➃ 5
6 Installation TECHNICAL DATA FWD Power supply (V/Ph/Hz) 230/1/50 Capacities Cooling capacity on water (1) (kw) 5,2 8, ,8 30,1 Heating capacity on water (2) (kw) 6,3 11,9 18,9 20,9 38,2 Fan motor (type) 2 x direct drive centrifugal Fan power input (3) (kw) 0,23 0,46 0,65 1,04 1,51 Current amps(3) (A) 1,1 2,2 3,1 4,7 5,5 Start-up amps (A) 3,2 5,5 9,3 14,1 16,5 Rated Input Power (W) Airflow minimum (m3/h) nominal (m3/h) maximum (m3/h) Main coil Water entering/leaving connections (type) ISO R7 rotating female (Dia) 3/4" 3/4" 1"1/2 1"1/2 1"1/2 Hot water coil (accessory for blower only) Heating capacity (4) (kw) 6, ,4 22,4 34,5 G2 filter (filter box accessory) Quantity Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586x421x8 586x621x8 G4 filter (filter box accessory) Quantity Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586x414x48 586x614x48 Condensate pump (accessory) (type) Centrifugal Water flow - lift height (l/h - mm) Not available for FWD30 and FWD45 Sound level (L/M/H speed) Sound pressure level (5) (db(a)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58 Sound power level (5) (db(a)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68 Unit dimensions Width x Depth (mm) 890 x x x x x 1090 Height (mm) Shipped unit dimensions Width x Depth (mm) 933 x x x x x 1133 Height (mm) Weight (kg) Colour galvanised steel Recommended fuse size Unit alone (am/gi) (A) 8/16 8/16 8/16 8/25 8/25 (1) Conditions: Water entering/leaving temperature: 7/12 C, Air inlet temperature 27/19 C DB/WB - Nominal air flow (2) Conditions: Water entering/leaving temperature: 50/45 C,,Air inlet temperature 20 C DB - Nominal air flow (3) At high speed with nominal air flow. (4) Water entering/leaving temperature 90/70 C, air inlet temperature 20 C DB, Nominal air flow. (5) A rectangular glass wool duct 1m50 long is placed on the blower.the measurement is taken in the room containing the blower unit. Heat exchanger operating limits: FWD : - Water temperature: max 100 C - Absolute service pressure: min 1 bar / max 11 bars Accessories - Hot water coil: - Water temperature: min. +2 C / max. 100 C - Absolute service pressure: min 1 bar / max 11 bars 6
7 Installation Ceiling installation Preparation of the ceiling and installation of the unit A template for drilling into the ceiling to fix the threaded rods is printed on the cover of the unit s packaging. The angle brackets can also be used to determine the drilling hole distances. Access must be provided on the water connection end to facilitate installation, maintenance and access to the cabinet. Four 8 mm diam. threaded rods must be securely fixed into the building s slab or structure. Screw a nut A (Figure 2) sufficiently high onto each threaded rod. Put the angle brackets B in place by holding them using a second nut C. Make sure the angle brackets are level in both directions using the bottom nuts C. Once they are perfectly level insert the FWD unit and let the angle brackets support it. Use the top nuts A to tighten the unit against the corner brackets. It is possible to avoid using the 2 angle brackets B supplied with the unit and mount it using just the threaded rods D and the 2 shaped bars E. In both cases isolators can be installed between the nuts C and the angle brackets B or shaped bars E, to reduce transmission of vibrations to the building s structure. Warning. Since the condensate tray is sloped to facilitate flow of condensates, the unit must be positioned absolutely level in both directions. Installation on the ground The unit can be installed on the ground, but make sure the condensate can be drained properly. Ensure it is installed on vibration isolators and that it is level in both directions. Figure 2 : Angle brackets B A Hydraulic connections It is easy to remove the electric cabinet to facilitate access to the hydraulic connections. Operating limits of pressure must not exceed 1.5MPa. Installation procedure - Define the layout of the lines so that they are as short as possible. - Limit pressure losses in the lines caused by pinching, too many bends and bending radii that are too small. - Connection of water inlet and outlet lines: The coil is connected by means of 3/4 female ISO R7 connectors. Warning. Limit the tightening torque applied to the connector nuts to prevent deformation of the piping and seals (risk of leaks). ➀ ➀ Figure 3 : Recommended clearances 7
8 Installation Condensate drainage The unit must be perfectly horizontal in both directions. Connect the condensate tray outlet (outer diam. 20 mm). To ensure satisfactory condensate drainage, the drainage tube must be sloped 10. There must not be a condensate trap anywhere on the line. However a siphon can be provided to prevent outside air being drawn in by the indoor unit. If the pipe passes through a room, insulate it to prevent damage caused by condensation. We recommend polyethylene foam (6 mm thick). Condensate pump (accessory) If it is not possible to drain the condensates by gravity, a condensate pump can be installed as an accessory. Figure 4 : Connection of the condensate drain It can lift the condensates a maximum of 500 mm. For installation and connection of the condensate pump, refer to the submittals supplied with this accessory. Electrical connections If access to the electric cabinet is problematic, it can be moved a maximum distance of 500 mm. All wiring and earthing must comply with local standards. Caution a) Check the electrical characteristics on the unit s name plate. Make sure the wiring corresponds to the manufacturer s electrical diagram and local standards. b) Power up the units using one or more lines protected by a disconnect switch and fuses. c) Earth each unit. d) The wires must not touch the refrigerant lines, the motors or other moving parts. e) The manufacturer does not assume any liability for problems caused by modifications to the unit s internal wiring. f) Tighten the terminals securely. Figure 5 : Moving the electric cabinet 8
9 Installation Main power supply It is the installer's responsibility to ensure that units are protected by an electrical disconnect device such as a fuse or circuit breaker. Standard units are supplied without any protection. The recommended fuse size is given in the Technical data table. For electrical connections of options or accessories, refer to following diagrams which are supplied with corresponding option/accessory: Motorized water valve for FWD sizes 08-20: Valve (Hot water coil): Automatic change over kit: Lift pump control kit: Motor connections for FWD sizes 8-20: Motor connections for FWD sizes 30-45: Interconnections diagram: Motorized water valve for FWD sizes 30-45: All electrical connections must be made on the terminal blocks of the main electrical control box. WARNING! Disconnect the power supply before making electrical connections. Failure to do so may cause serious injuries as well as irreversible damage to certain electrical components. WARNING! Use copper conductors only. Unit terminals are not designed to accept other types of wiring. Aluminium or other materials could lead to galvanic corrosion or overheating at the contact point thus damaging the unit. The customer's electrical connections must comply with current standards. FWD units manufactured by Trane comply with CEI regulations. All power supply wiring must be sized and selected in accordance with local code and regulation. Fast-acting circuit breaker, which is sensitive to very low levels of current leakage to ground (max 30mA) must be installed as a general line protection. Only copper conductors (Min. 1.5mm 2 - Max 4.0mm 2 ) must be used as unit terminals are not designed to accept other types of wiring. 9
10 Installation Duct connections FWD units can be fitted directly with rectangular discharge and intake ducts. DIMENSIONS OF DUCT CONNECTIONS (INTAKE AND DISCHARGE) Sizes Length Width Warning.The pressure loss caused by the duct network and accessories must not exceed the unit s available static pressure (see selection chart). The air intake can be located at the back of the unit ➀ or underneath it ➁. Filtering: vital to ensure the unit runs smoothly. No filters are supplied with the unit, but they can be ordered as accessories: - Filter box with EU2 filters to fix to the unit s intake. (behind or underneath). Figure 6 : Connection of ducts ➀ ➁ 10
11 11
12 12
13 13
14 Space requirement plans 14
15 15
16 Operation / Maintenance Choice of fan speed The FWD unit is delivered from the factory unwired. Please refer to the selection chart to select the static pressure according to the flowrate. Once the fan rotation speed has been determined, wire up the fan motor to the required speed using the supplied electrical diagrams. For use of temperature control, refer to the guide supplied with the thermostat. Initial checks - Check the electrical connections and water pipes are fixed securely. - Rotate the fan blades by hand to make sure it rotates freely. - Check that all nuts and bolts are tightened correctly. - Make sure the chilled water piping and the condensate drainage tube are properly insulated to avoid problems with condensation water flow. Maintenance recommendations (regular use) Failure to follow these instructions may cause damage to the unit. The frequency of maintenance will depend on the conditions of use of the unit and will be determined by regular inspections. When servicing the units, make sure also that the air passage through the coils (both internal and external) is clean, and free of dirt or debris. a) Clean the air filter by beating it and drawing air through it in the opposite direction to the passage of air. b) Check the condensate tubes are not obstructed. c) Rotate the fan blades and make sure they are not damaged. Clean them if necessary and check they are correctly aligned. d) Motor - check the wiring, and make sure the switches operate correctly. Replace any damaged components. e) Safety disconnection and electrical components - check they operate correctly. f) Water circuit - check there are no leaks. g) Tighten all the nuts and bolts. 16
17 Maintenance Figure 7 : Removal of the fan motor ➂ ➄ ➅ ➇ ➄ ➀ ➂ ➆ ➀ ➁ ➇ ➈ ➉ ➈ ➀ ➁ Unscrew the 4 screws fixing the panel and remove the panel. ➂➃ Unscrew the 4 screws fixing the intake support bracket and remove it. ➄ Unscrew the 4 screws fixing the base of the electrical cabinet by one turn. N.B.. The motor cables must be disconnected in the electrical cabinet. ➅ Push the cabinet upwards and move it enough to access the screws fixing the fan motor. ➆ Loosen the 4 screws fixing the condensate tray by a few turns. ➇ Unscrew the 2 x 2 screws (08) or 2 x 3 screws ( ) fixing the fan motor while holding it up. ➈ ➉ Take out the fan motor assembly, by pushing outwards on the bottom of the 2 side panels, taking care not to damage the insulation material. 17
18 Maintenance Troubleshooting Symptom The unit is not powered up. The unit does not operate The fan motors do not operate. Room temperature too high Room temperature too low No airflow Possible cause A)The electric cabinet is not connected. B) The control circuit is not powered up. A) The thermostat is not controlling the unit. A) The electric motors are not powered up. B)The thermal protection of the motors has been cut. A) The unit is not operating. B) The thermostat settings are incorrect. C) Insufficient air flow D) Insufficient chilled water flow E) Chilled water temperature too high. F) The thermostat is not operating correctly. G) Heat load is greater than expected. A) Clogged filters. B) The fans are rotating the wrong way C) The air flow is obstructed. Solution Check the unit s general disconnect switch is closed. Check the control circuit s fuse. Check the thermostat is plugged in (also refer to the thermostat s instruction manual). Check the fan motors are powered up and the fan circuit-breakers are reset. Check the motor winding resistance after resetting. Check the power supply voltage and the input current. See The unit is not operating. Check the set point. See No air flow Checked the chilled water flow. Check the gate valves and the water circuit. Check the unit s chilled water production. Refer to the thermostat s instruction manual. Check the zone s heat load (too much fresh air). Check the extent of infiltration of outside air. Clean or replace the recycling filters. Check and correct 18
19 Notes 19
20 Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice Trane All rights reserved _1213 Supersedes FWD-SVX01C-E4_0912 We are committed to using environmentally conscious print practices that reduce waste.
Installation Operation Maintenance
Installation Operation Maintenance DUCTABLE WATER UNIT FWD 08-12 - 20-30 - 45 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice
More informationInstallation Operation Maintenance
Installation Operation Maintenance Series R Air-Cooled Helical Rotary Liquid Chiller RTAD 085-180 (50Hz) Standard, Free Cooling and Heat Recovery models RTAD-SVX01F-E4 General information Foreword These
More informationInstallation Operation Maintenance
Installation Operation Maintenance Voyager I Rooftop Units Cooling-only TSD/TSH 060 072 102 120 Reversible WSD/WSH 060 072 090 Gas-fired YSD/YSH 060 072 090 102 120 RT-SVX20D-E4 Original instruction Table
More informationAQUASTYLUS Chilled Water Fan Coil Convertible Type CFEA Series 50/60 Hz
Installation Manual AQUASTYLUS Chilled Water Fan Coil Convertible Type CFEA Series 50/60 Hz 50 Hz Models Cooling Only CFEA 04 C0M1 CFEA 06 C0M1 CFEA 08 C0M1 CFEA 10 C0M1 CFEA 12 C0M1 CFEA 14 C0M1 CFEA
More informationInstallation Guide. Wind Baffle for Outdoor Units VRF-SVN079A-EN. VRF Single-Phase and C-Series Systems. October 2015 SAFETY WARNING
Installation Guide Wind Baffle for Outdoor Units VRF Single-Phase and C-Series Systems Model Numbers: CSERWINDBFL1AA CSERWINDBFL24AA CSERWINDBFL36AA SAFETY WARNING Only qualified personnel should install
More information40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT
Carrier International Sdn. Bhd. Malaysia INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT 40LM 120-200 50Hz CONTENTS: Physical Data & Dimension 1-3 Safety Considerations 4 Rigging
More informationINSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP
INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP RV Products A Division of Airxcel, Inc. P.O. Box 4020 Wichita, KS 67204 1976-360 (1-02) PP TABLE OF CONTENTS 1. Warnings......................................................
More informationFUN I / FUN U FUN I MCP / FUN U MCP FUN V / FUN V MCP
OPERATION INSTRUCTIONS MANUAL DUCTED FAN COILS UNIT FUN I / FUN U FUN I MCP / FUN U MCP FUN V / FUN V MCP 1 CONTENTS 1. GENERAL... 3 2. INSTALLATION... 4 3. AIR CONNECTIONS... 5 4. WATER CONNECTIONS...
More informationInstallation Operation Maintenance
Installation Operation Maintenance RTAF SE/HE/XE/HSS/HSE Air-cooled Helical-rotary chillers 300-1600 kw Sintesis chillers are part of the Ingersoll Rand EcoWise portfolio of products that are designed
More informationPanel Fan Series Operators Manual (Galvanized and Polymer)
Panel Fan Series Operators Manual (Galvanized and Polymer) 52" Belt Drive, Galvanized Panel Fan with Three Wing Blade IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before
More informationInstallation Instructions
40MBD Ducted Style Ductless System Sizes 09 to 48 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2
More informationSplit System, 18,000-48,000 Btu/h Underceiling Type MCC Series 50 Hz
Split System, 18,000-48,000 Btu/h Underceiling Type MCC Series 50 Hz Models Cooling Only MCC 518 ZB MCC 524 ZB MCC 530 ZB MCC 536 ZB MCC 048 ZB October 2007 General Information General Information Congratulations
More informationLOW STATIC HYDRONIC DUCTED UNIT
LOW STATIC HYDRONIC DUCTED UNIT PDWA-~AC SERIES PDWA(4R)-~-V-MEDC PDWA(4R)-~-V-MEEU PDWA(R)-~-V PDWA(R+1)-~-P Model cooling capacity( KW) at Medium Speed cooling capacity (KW) at Medium Speed cooling capacity
More informationInstallation Instructions
40MAQ High Wall Ductless Split System Sizes 09 to 36 Installation Instructions NOTE: Read the entire instruction manual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS
More informationPanel Fan Series Operators Manual (Galvanized and Polymer)
Panel Fan Series Operators Manual (Galvanized and Polymer) Galvanized Panel Fan with Three Wing Blade IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble,
More informationPANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer)
PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer) Galvanized Panel Fan IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble, install, operate
More informationSubmittal. 1 1/2 Ton Convertible Air Handler TEM3A0B18S21SA TEM3A0B18-SUB-1C-EN. July 2014 TAG:
Submittal 1 1/2 Ton Convertible Air Handler SAFETY WARNING TAG: Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating,
More informationSubmittal. 2 Ton Convertible Air Handler TEM3A0B24S21SA TEM3A0B24-SUB-1C-EN. July 2014 TAG:
Submittal 2 Ton Convertible Air Handler TEM3A0B24S21SA SAFETY WARNING TAG: Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating,
More informationRV Products Division INSTALLATION INSTRUCTIONS FOR SERIES PACKAGE AIR CONDITIONER
RV Products Division INSTALLATION INSTRUCTIONS FOR 46413 SERIES PACKAGE AIR CONDITIONER 1. WARNINGS IMPORTANT NOTICE These instructions are for the use of qualified individuals specially trained and experienced
More informationINSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC
AQB09JJ6WC_IM_E_2585 2006.4.17 4:26 PM Page 17 INSTALLATION MANUAL Indoor Unit AQB09JJWC AQB12JJWC Outdoor Unit UQB09JJWC UQB12JJWC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)
More informationtechnical data Fan coil unit FWB small duct unit
technical data Fan coil unit FWB small duct unit TABLE OF CONTENTS FWB 1. Nomenclature ---------------------------------------------------------------------- 2 2. Features -----------------------------------------------------------------------------
More informationINSTALLATION, COMMISSIONING AND OPERATING MANUAL
INSTALLATION, COMMISSIONING AND OPERATING MANUAL 1 YTBV-D-CE42_0109 CONTENT Available models and capacities Supplier information Warranty Safety Emergency stops/ shutdowns About this manual Models Physical
More informationHE360 Humidifier Installation Kit
HE360 Humidifier Installation Kit INSTALLATION INSTRUCTIONS WELCOME To the comfortable world of humidified air. When you use your Honeywell humidifier, you notice that your skin is not as dry, and that
More informationTABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13
R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.
More informationInstallation Instructions
50ES---A, 50EZ---A, 50VL---A, 50VG---A, 50VR---A, 50VT---A, 604D--- ---A, 607C--- ---A, 607E,--- ---A, 704D--- ---A, 707C--- ---A, 707E--- ---A PA3G --- --- A, PH3G --- --- A SMALL PACKAGED PRODUCTS Electric
More informationInstaller manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50
-30 Installer manual Air/air heat pump -40/50 IHB GB 1516-1 331554 Table of Contents 1 Important information 2 5 Installation 7 Safety information 2 Model combinations 7 Read before starting the installation
More informationWINDOW YORK TECHNICAL GUIDE. Single package Cooling only and Heat pump. Models YO-YM R407C YO V6 G YO V7 G
WINDOW TECHNICAL GUIDE Single package Cooling only and Heat pump Models YO-YM 09-24 R407C YM 09 V6 G YM 09 V7 G YO 12-19-24 V6 G YO 12-19-24 V7 G YORK List of Contents Page 1 - Safety...2 2 - Unit packaging...2
More informationHood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL
The Kitchen Cool by Hood Depot is a conditioned make up air unit design with flexibility, form and function kept in mind. Our unit offers a variety of configurations that allow the customer to customize
More informationINSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC
AQB8J6WC_IM_E_25864 2006.4.4 3:29 PM Page 7 INSTALLATION MANUAL Indoor Unit AQB8J6WC AQB24J2WC Outdoor Unit UQB8J6WC UQB24J2WC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)
More informationInstallation Instructions
50ZPB, C, 50ZHB, C, PA3Z ---A, PH3Z ---A, PA4Z, PH4Z, PAJ4,PHJ4,WJA4,WJH4 SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters 5---20 kw For 14 SEER, R---410A Manufactured Home Installation Instructions
More informationINSTALLATION INSTRUCTIONS
C7BA & C7BH Series Split System Indoor Cased Coils INSTALLATION INSTRUCTIONS IMPORTANT It is your responsibility to know this product better than your customer. This includes being able to install the
More informationInstallation Operation Maintenance
Installation Operation Maintenance RAUL Air Cooled Condensing Unit Sizes 190 260 300 350 400 450 500 600 700 800 To be used with the CH530 control module manual General information Foreword These instructions
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS FCP2400D FCP3000D FCP3600D FCP4200D FCP4800D FCP6000D FCP2400C FCX2400C FCP3000C FCP3600C FCX3600C FCP4200C FCP4800C FCX4800C FCP6000C FCX6000C Require AMF001NHA Accessory No
More informationINSTALLATION INSTRUCTIONS FOR 6636 SERIES PACKAGE AIR CONDITIONER
INSTALLATION INSTRUCTIONS FOR 6636 SERIES PACKAGE AIR CONDITIONER TABLE OF CONTENTS 1. Warnings...................................................... 3 2. Component Match-Up...........................................
More informationSPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with
More informationSubmittal. 5 Ton Convertible Air Handler TEM3A0C60S51SA TEM3A0C60-SUB-1C-EN. July 2014 TAG:
Submittal 5 Ton Convertible Air Handler TEM3A0C60S51SA SAFETY WARNING TAG: Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating,
More informationUser Manual Box Exhaust Fan Series (Belt Drive)
User Manual Box Exhaust Fan Series (Belt Drive) 36" Box Exhaust Fan with Three Wing Blade Box with Aluminum Shutter 54" Box with Cone 800-779-3267 sales@schaeferfan.com www.schaeferfan.com 2013 Schaefer
More informationINSTALLATION INSTRUCTIONS FOR 6536 SERIES TWO TON PACKAGED HEAT PUMP
INSTALLATION INSTRUCTIONS FOR 6536 SERIES TWO TON PACKAGED HEAT PUMP TABLE OF CONTENTS 1. Warnings...2 2. Component Match-Up...2 3. Unit Depiction Figures...3 4. Blower Performance Data...5 5. General
More informationInstallation Instructions
50ES--A, 50EZ--A, 50VG--A, B, 50VL--A, B, 50VR--A, 50VT--A, B 604D-- --A, 607C-- --A, B, 607E-- --A, 704D-- --A, 707C-- --A, B, 707E-- --A PA3G -- -- A, PH3G -- -- A, PA4G, PH4G PAD3, PHD3, PAD4, PHD4,
More informationOK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN.
INSTALLATION, OPERATION & SERVICE MANUAL FOR COOLER TYPES OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN. 1. Introduction This manual is a guide for the installation, maintenance
More informationINSTALLATION INSTRUCTIONS FOR SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMP
RV Products Division INSTALLATION INSTRUCTIONS FOR 46515 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMP TABLE OF CONTENTS 1. Warnings.................................................. 2 2. Component
More informationInstallation Operation Maintenance
Installation Operation Maintenance / 015-060 Air-cooled scroll chillers and heat pumps 43-164 kw CG-SVX027B-GB Original instructions Table of Contents General Information...4 Model Number Description...6
More informationInstaller manual AG-WL10
LEK LED CLEAN TIMER OPERATION Installer manual Indoor unit air/air heat pump IHB GB 1637-1 331827 Table of Contents 1 Important information Safety information Read before starting the installation Electrical
More informationOperation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.
Spot Cooling Systems, Inc. 120 Century Drive Suite 00 Carrollton, TX 7006 00-6-776 Operation Manual SCT1B and SCT1B Warning! Improper installation, adjustment, alteration, service, or maintenance can cause
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS Models MB08B1500A2 MB12F1900A2 MB16J2200A2 MB20N2600A2 Contents 115 Volt General Information / Installation... 2 Installations... 3 Horizontal Installations... 3 Ductwork Connections...
More informationInstallation Instructions
EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 Installation Instructions NOTE: Read the entire instruction manual before starting
More informationInstallation Instructions
Electric Heaters 5 --- 20 kw SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters For 13 SEER, R---410A Manufactured Home Installation Instructions NOTE: The Dual Point Kit can only be installed on
More informationInstallation Operation Maintenance
Installation Operation Maintenance CGCL Air Cooled Water Chiller With Centrifugal Fans Sizes 200-250 - 300-350 - 400-450 - 500-600 To be used with the manual of SMM Module Reference L80IM022E CGCL-SVX01A-E4
More informationDuct Heaters volts/1 phase volts/3 phase volts/3 phases volts/3 phases. Flange Type Duct Heater.
Duct Heaters Synheat duct heaters come in various sizes and dimensions to fit any compartment. There are three types of duct heaters available: open coil, tubular element or finned tubular heating elements
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS C7BA Series Split System Indoor Cased Coils IMPORTANT ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes being able
More informationINSTALLATION AND USER MANUAL
Swimming Pool Heat Pump Swimming Pool Heat Pump INSTALLATION AND USER MANUAL Thank you for choosing our product and trusting our company. This manual is to provide you with necessary information for optimal
More informationInstallation Instructions
Electric Heaters 5 --- 20 kw SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters For 13 SEER, R---410A, Z Chassis Installation Instructions NOTE: Read the entire instruction manual before starting
More informationInstallation Instructions
Installation Instructions For Cased Coils Upflow-Downflow Heating-Cooling CK5A CK5B SUPPLY RETURN EVAPORATOR COIL DOWNFLOW UPFLOW SUPPLY Fig. 1 Typical Coil Installation NOTE: Read the entire instruction
More informationS Y D. HWP 35, 47, 58 (c/w EC Motor & UC7 Controller) Ducted Water Cooled R410A Packaged Air Conditioner. Installation & Maintenance
HWP 35, 47, 58 (c/w EC Motor & UC7 Controller) Ducted Water Cooled R410A Packaged Air Conditioner Installation & Maintenance Fig. 1 Nomenclature Nomenclature e.g. H W P 3 5 C K Series Size Type S Y D GENERAL
More informationHE220, HE260 Humidifier Installation Kit
HE220, HE260 Humidifier Installation Kit WELCOME To the comfortable world of humidified air. When you use your Honeywell humidifier, you notice that your skin is not as dry, and that your scratchy throat
More informationS D HWP 77, 96. Ducted Water Cooled R410A Packaged Air Conditioner. Installation & Maintenance. Fig. 1 Nomenclature. Fig.
HWP 77, 96 Ducted Water Cooled R410A Packaged Air Conditioner Installation & Maintenance Fig. 1 Nomenclature Nomenclature e.g. H W P 7 7 C K Series Size Type S D GENERAL HWP - A general designation which
More informationVariable Refrigerant Flow (VRF) System Simple Touch Remote Control SAFETY WARNING
User Guide Variable Refrigerant Flow (VRF) System Simple Touch Remote Control Model Numbers: TVCTRLTWR0002T TVCTRLTWR0002A SAFETY WARNING Only qualified personnel should install and service the equipment.
More informationOPTIONAL SPRING MTG HANGING CENTRES WATER CONN'S: TWO BSP MALE. 19 mm (3/4") ELECTRICAL CONDUIT HOLES ACCESS PANEL OUT (WATER) IN 485 MOUNTING
HWP 117 225 Ducted Water Cooled R410A Packaged Air Conditioner Dimensions (mm) Fig. 1 HWP 117 60 1210 SPRING MOUNTING CENTRES 690 (HEIGHT = 370) FILTER BOX PROJECTION Net Weight 105 kg Installation & Maintenance
More informationInstallation Instructions
40MBFQ Floor Console Ductless System Sizes 09 to 12 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 DIMENSIONS... 5 CLEARANCES... 5
More informationOwner s Information Manual
50EZ---A and 50VT ---A Comfort and Performance 13 and 14 SEER Single Packaged Heat Pump System With PuronR (R ---410A) Refrigerant Single and Three Phase 2---5 Nominal Tons (Sizes 24---60) Owner s Information
More informationINSTALLATION, OPERATION, AND MAINTENANCE MANUAL
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended
More informationAHU INSTALLATION & OPERATION MANUAL
AHU INSTALLATION & OPERATION MANUAL VERSION 2 AIR HANDLING UNIT MODELS: AHU 500, AHU 900, AHU 1200, AHU 1700, AHU 2000, AHU 2500, AHU3500, AHU 4500, AHU 5000, AHU 6000, AHU 7000, AHU 8000, AHU 10000, AHU
More informationHKF 8180 Operating instructions
Operating instructions EN Version 1.0en /Edition 05/2013 Contents 1 Important basic information... 3 1.1 Limitation of liability... 3 1.2 Operator's responsibilities... 3 1.3 Documentation... 3 1.3.1 Content
More information2
Installation Operation Commissioning Maintenance N 11.47A 2 3 1 g c e f b j d h a i 4 2 1 2 3 4 9 5 8 10 6 7 3 5 4 6 5 6 7 8 7 9 a b 10 8 11 12 9 13 14 15 2 16 1 17 a 10 18 rep.2 rep.1 rep.3 rep.4 19 11
More informationStandard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual
Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check
More informationInstallation Electric Dryers Instructions 01
Installation Electric Dryers Instructions 01 Questions? Call 800.GE.CARES (800.432.2737) or visit our Web site at: GEAppliances.com This is the safety alert symbol. This symbol alerts you to potential
More informationInstallation Instructions
40MBFQ Floor Console Ductless System Sizes 09 to 58 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING... 4 DIMENSIONS... 5 CLEARANCES...
More informationInstallation Instructions
40MAQ High Wall Ductless System Sizes 09 to 36 Installation Instructions NOTES: Read the entire instruction manual before starting the installation. Images are for illustration purposes only. Actual models
More informationCELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler
CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check for any interior and exterior damage, and
More informationPackaged Heat Pumps. Owner s Guide to Operating and Maintaining Your Heat Pump
Packaged Heat Pumps Owner s Guide to Operating and Maintaining Your Heat Pump NOTE TO EQUIPMENT OWNER: For your convenience, please record the model and serial numbers of your new equipment in the spaces
More informationInstallation Instructions
8GXM / 0GXM Multi---Split High---Wall Duct Free Split System 8GXM --- Size 18k, k, and 0k 0GXM --- Size 9k, 1k, and 18k Installation Instructions NOTE: Read the entire instruction manual before starting
More informationINSTALLATION, USE AND MAINTENANCE MANUAL HIGH PRESSURE FAN COIL FOR PROFESSIONAL APPLICATIONS, BUILT-IN VERSION
INSTALLATION, USE AND MAINTENANCE MANUAL HIGH PRESSURE FAN COIL FOR PROFESSIONAL APPLICATIONS, BUILT-IN VERSION a-life2 HP 302 1202 a-life2 HP 304 1204 EN OBSERVATIONS In order to use the unit correctly
More informationIMPORTANT SAFETY INFORMATION:
Owner s Manual Model CUH05B31T IMPORTANT SAFETY INFORMATION: Always read this manual first before attempting to install or use this heater. For your safety, always comply with all warnings and safety instructions
More informationOPERATION MANUAL U L US LISTED CM12 READ THIS MANUAL CAREFULLY FOR INSTRUCTIONS ON CORRECT INSTALLATION AND USAGE, AND READ ALL SAFEGUARDS.
OPERATION MANUAL CM12 READ THIS MANUAL CAREFULLY FOR INSTRUCTIONS ON CORRECT INSTALLATION AND USAGE, AND READ ALL SAFEGUARDS C U L US LISTED 2006 DENSO SALES CALIFORNIA, INC All rights reserved This book
More informationARMITAGE CEILING FAN ITEM # MODEL #CC52WW5L. Español p. 17 ATTACH YOUR RECEIPT HERE. Purchase Date
ITEM #0807426 ARMITAGE CEILING FAN MODEL #CC52WW5L Harbor Breeze is a registered trademark of LF, LLC. All Rights Reserved. Español p. 17 ATTACH YOUR RECEIPT HERE Purchase Date 4009654 Questions, problems,
More informationInstallation Instructions Part No , Part No Part No
Torsion-Flex Motor mount for PSC motors and Rigid-Mount for ECM motors Replacement Kit Cancels: New Installation Instructions Part No. 327752-401, Part No. 327753-401 Part No. 327754-401 IIK-310A-45-11
More informationInstallation Instructions
Split System Indoor Coils Installation Instructions! CAUTION: Read the Installation Instructions supplied with furnace/air handler and observe all safety requirements outlined in instructions and/or furnace/air
More informationBosch 80% AFUE Gas Furnace BGS80 Model
Bosch 80% AFUE Gas Furnace BGS80 Model 4-Way Multipoise Category I Fan-Assisted Furnace User's Information Manual 3124627 2 Bosch 80% AFUE Gas Furnace User's Information Manual Data subject to change 06.2018
More information238 Series. Industrial/Commercial Electric Unit Heater. Owner s Manual
238 Series Industrial/Commercial Electric Unit Heater Owner s Manual This manual covers installation, operation and maintenance. Read carefully before attempting to install, operate or service the 238
More informationOwner s Information Manual
48ES---A and 48VL---A Comfort and Performance 13 and 14 SEER Single Packaged Air Conditioner and Gas Furnace System With Puron (R---410A) Refrigerant Single and Three Phase 2---5 Nominal Tons (Sizes 24---60)
More informationApplication guide FLATAIR - FLCK/FLHK. Providing indoor climate comfort
Application guide FLATAIR - FLCK/FLHK Providing indoor climate comfort MSL60E-0701 12-2006 Congratulations you have made a wise choice and we feel sure that it will meet your expectation INDEX CONTENTS
More informationUSER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES
USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES Bucket Fan 420 Bucket Fan 1055 Bucket Fan 1460 420 1055 1460 2 Bucket Fan CONTENT INTRODUCTION 3 USE 3 WHAT S INCLUDED IN THE BOX 3 DESIGNATION
More informationInstallation Instructions
40MHH High Wall Ductless System Sizes 09 to 24 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. NOTE: Images are for illustration purposes only. Actual
More informationTECHNICAL MANUAL YEFB HIGH PRESSURE DUCTED UNIT
1. GENERAL INFORMATION 1.1 Applications page 2 1.2 Operation» 2 1.3 Performances» 2 1.4 Product range» 2 1.5 Selection software» 2 2. DIMENSIONS AND WEIGHTS» 3 3. COMPONENTS 3.1 Structure» 4 3.2 Coils»
More informationInstallation Instructions Remote Blowers
Installation Instructions Remote Blowers Models: REMP3, REMP16 Suitable for use in a household cooking area. Suitable for use with solid state controls. To complete this blower, a Dacor hood assembly or
More informationST. KITTS CEILING FAN
ITEM #0845047 ST. KITTS CEILING FAN MODEL #40829 Questions, problems or missing parts? Before returning this item to your retailer, call our customer service department at 1-800-643-0067, Monday - Thursday,
More informationBHW INSTALLATION, OPERATION AND MAINTENANCE MANUAL MEDIUM STATIC PRESSURE DUCTABLE TYPE. Models:
INSTALLATION, OPERATION AND MAINTENANCE MANUAL BHW MEDIUM STATIC PRESSURE DUCTABLE TYPE Models: 174 205 358 410 515 720 724 Cooling capacities from 3,1 to 25 KW Heating capacities from 4,5 to 55,5 KW Thank
More informationMAYFIELD CEILING FAN LISTED E ITEM # MODEL #BTH44ABZC5C BTH44BNK5C Español p. 20 ATTACH YOUR RECEIPT HERE.
Harbor Breeze is a registered trademark of LF, LLC. All Rights Reserved. ITEM #0331094 0331096 MAYFIELD CEILING FAN MODEL #BTH44ABZC5C BTH44BNK5C Español p. 20 ATTACH YOUR RECEIPT HERE Serial Number Purchase
More informationInstallation Instructions
Installation Instructions EHMA SERIES ELECTRIC HEATERS FOR PAM3 SERIES PACKAGE AIR CONDITIONERS PHM3 SERIES PACKAGE HEAT PUMPS TABLE OF CONTENTS SAFE INSTALLATION REQUIREMENTS... 2 GENERAL INFORMATION...
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS C8DA Series Split System Uncased Indoor Coils - Downturn IMPORTANT ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes
More informationInstallation Instructions
Installation Instructions For Free Standing NoFrost Combined Refrigerator-Freezers CS 1660 7084 203-00 Important Please Read and Follow these Instructions These instructions contain Danger, Warning and
More informationInstallation, Operating & Maintenance Instructions. Air Handler Models: AH & AV
Installation, Operating & Maintenance Instructions Air Handler Models: AH & AV Table of Contents Table of Contents... 2 Product Safety... 2 Important Information About Safety Instructions... 2 Receiving...
More informationUNIVERSITY OF MISSOURI Central Station Air-Handling Units March
GENERAL: 1. This section provides criteria for the design and installation of air handling units. DESIGN GUIDELINES: Design General 1. Location 1.1. For new construction, and existing buildings where possible,
More informationSECTION FAN COIL UNITS
PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:
More informationVariable Speed Convertible Air Handler 4 Ton
Submittal Variable Speed Convertible Air Handler 4 Ton TEM6A0D48H41S Note: The TEM6 series air handler is designed for installation in a closet, utility room, alcove, basement, crawlspace or attic. These
More informationSWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL
SWP (Models SWP08 through SWP20) OPERATION & MAINTENANCE MANUAL IMPORTANT! Read before proceeding! Read carefully before attempting to assemble, install, operate or maintain the product described. Protect
More informationHE120, HE160 Humidifier Installation Kit
HE120, HE160 Humidifier Installation Kit INSTALLATION INSTRUCTIONS WELCOME To the comfortable world of humidified air. When you use your Honeywell humidifier, you notice that your skin is not as dry, and
More informationCentral Air Conditioning System
Owner s Information Manual Central Air Conditioning System NOTE TO EQUIPMENT OWNER: For your convenience, please record the model and serial numbers of your new equipment in the spaces provided. This information,
More informationINSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X
INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...
More informationInstallation Instructions. For the 18 Built-In Dishwasher and Front Color Panels
Installation Instructions For the 18 Built-In Dishwasher and Front Color Panels Printed in USA 154232102 Before You Begin DO NOT INSTALL DISHWASHER UNTIL YOU HAVE READ ALL INSTRUCTIONS. FOR YOUR SAFETY,
More information