OPERATION MANUAL Decentral Systems Industry Multi Flair. Technological and Optical Perfection

Size: px
Start display at page:

Download "OPERATION MANUAL Decentral Systems Industry Multi Flair. Technological and Optical Perfection"

Transcription

1 OPERATIO MAUAL Decentral Systems Industry Multi Flair Technological and Optical Perfection

2 Multi Flair DencoHappel product range 2 PR GB Subject to modifications R5-/205

3 Multi Flair Unit Type Code Unit type code Controls package ZM. U 0 W A G. B 0 5 I B A Unit type = Comfort model (with design panel) 2 = Standard model (w/o design panel) Model size = Model size 2 = Model size 2 3 = Model size 3 Capacity stage = Capacity stage 2 = Capacity stage 2 3 = Capacity stage 3 4 = Capacity stage 4 Air flow function U = Recirculating air unit P = Primary air unit Medium specification Only heating 0W = Warm water pump Cooling or Heating WC = Pumped chilled - warm water Heat exchanger design A = Cu/Al Coil connection, filter without filter E = Pipe connections from top F Pipe connections from side with filter (only possible with compact model M) G = Pipe connections from top H = Pipe connections from side Controller type 2 = MATRIX = MATRIX 3000 Controls package r. Control panel IP20 U = MATRIX OP20C A = MATRIX OP2C B = MATRIX OP30C C = MATRIX OP3C D = MATRIX OP44C E = MATRIX OP50C F = MATRIX OP5C IP54 G = MATRIX OP2I H = MATRIX OP30I I = MATRIX OP3I L = MATRIX OP50I M = MATRIX OP5I Z = without control panel Unit type Master unit control panel A = Enclosed C = Without control panel Slave unit D = Without control panel Motor, speeds Wired on terminal strip B = 400 V/3~/50 Hz 2-speed F = 230 V/~/50 Hz -speed With control box and integrated controls L = 400 V/3~/50 Hz 2-speed P = 230 V/~/50 Hz 3-speed Condensate drain / pump 0 = Without (always with heating units) A = With condensate drain (with cooling units) P = With condensate pump (for units with cooling) Colour 4 = Galvanized steel (only for standard model M2) 5 = White RAL = Selectable RAL PR GB Subject to modifications R5-/205 3

4 Table of Contents Multi Flair Table of Contents Safety and User Information Used symbols Safety instructions: warning and danger symbols Safety-conscious working Personnel selection and qualification Proper use Improper use Technical Description Unit components Operating limits Water inlet temperature Unit and heat exchanger Dimensions Basic unit Unit data Unit weight, water charge of heat exchanger and enclosure protection class Electrical data Condensate pump Function of condensate drain Condensate pump Shipping and Storage Transport safety Scope of supply Packaging Shipping Temporary storage Disposal Assembly Installation location Unit installation Removing corner covers Installation on ceiling Installation below suspended ceiling Primary air connection (only for unit with primary air fitting) PR GB Subject to modifications R5-/205

5 Multi Flair Table of Contents Mounting unit cover panel (only M series) Hydraulic Connection General Pipe connections Installation example: pipe connection from top Installation example: pipe connection from side Protection class/water charge/weights/sound pressure level Condensate drain Connection for condensate drain for cooling units with condensate pump Connection for condensate drain for cooling units without condensate pump Electrical Connection Wiring diagrams Connection of field controls for use with control units or MATRIX regulation Overview of unit circuit boards and MATRIX control electronics Unit circuit boards for use on 230 V and 400 V MATRIX 200 and MATRIX 300 controller type Fan with series resistor Installing control panel Electrical connection to control unit by others Connection to 230 V unit circuit board Connection to 400 V unit circuit board Connection of multiple 230 V unit heaters to a control unit Connection of multiple 400 V unit heaters to a control unit Connection of controls for condensate pump unit Electrical connection with MATRIX Connecting mains supply voltage for units with controller Connecting control cables Completing bus connection Connecting external sensor (option) Connecting inlet sensor (option) Connecting room temperature sensor Connecting status and fault messaging Connecting function input Valve connection PR GB Subject to modifications R5-/205 5

6 Table of Contents Multi Flair 6.7 etwork and shielding connection Group structure etwork structure etwork topologies Line structure Line structure with stub line etwork set up Commissioning Safety check Pre-commissioning checklist Checks before commissioning: Setting secondary air louvers After commissioning: Unit air venting Checking condensate pump (applies only to cooling units with condensate pump) Checking condensate pump Terminating resistors Setting address Switch on unit Checking data connection Checking control cables Checking data connection Checking control inputs and outputs Function input Functions Fan mode Valves Condensate pump Standby mode Indoor anti-freeze protection Summer / winter compensation Filter replacement indication Maintenance and Troubleshooting Maintenance Quarterly maintenance Cleaning or replacing filters Annual maintenance Cleaning heat exchanger PR GB Subject to modifications R5-/205

7 Multi Flair Table of Contents Check screw connections of medium lines Checking condensate pump Checking electrical connections and earthing Air venting heat exchanger Cleaning coil drip tray and condensate sump pit Before cooling period Checking condensate pump Retrofitting filter assembly Operating faults EC Declaration of Conformity...87 Copyright note Disclosing, copying, distributing or taking any action in reliance on the contents of this document is strictly prohibited without express prior consent. Violations entail liability for any damages or other liability arising. All rights in relation to patents, utility patents or design patents are reserved. PR GB Subject to modifications R5-/205 7

8 Safety and User Information Multi Flair Safety and User Information This is an original operation manual verified by the manufacturer. The Multi Flair unit heaters are developed and manufactured in accordance with the state-of-the-art technological standards and established technical safety codes, the units meet the requirements of the EC Directive on Machinery. Multi Flair unit heaters ensure maximum operational safety and meet the highest quality standards. This product range combines future-oriented technology with a high level of user friendliness and ease of maintenance. However, Multi Flair unit heaters could pose unavoidable residual risk of injury or risk of equipment or property-damage only accidents. Therefore your personal safety and the proper operation of the unit depend on the strict observance of the safety instructions. Failure to follow the safety precautions could result in death, serious injury or equipment or property-damage-only accidents. Observing the safety instructions in the current operation manual will help avoid the risks, ensure economical operation of the unit and enjoy full benefits of the product. The safety aspects covered by this chapter are valid for the entire operation manual.. Used symbols The following symbols are used to highlight particular text sections in this operation manual: This symbol is used to indicate normal lists. This symbol indicates instructions to follow. The result of an action is indicated with this symbol. USER ISTRUCTIOS User instructions provide optimal, efficient and environmentally friendly methods for using and handling of units. RECYCLIG This symbol is used to highlight information on proper reuse of packaging material and disused components (separated according to recyclable materials, e.g. metal, plastic, etc.). 8 PR GB Subject to modifications R5-/205

9 Multi Flair Safety and User Information.2 Safety instructions: warning and danger symbols All information in this chapter is important and relevant for your safety. That is why not all of the information contained in the present chapter is labelled with special danger pictograms. In subsequent chapters of this manual, warning notes are indicated by pictograms. General safety instructions are listed at the beginning of the respective chapter and special safety instructions on specific jobs are listed along with the respective steps. The following warnings are used: HAZARDOUS VOLTAGE! This symbol indicates a risk of electrical shock that can result in serious injury, death and material damage. DAGER OF SCALDIG! This symbol indicates a risk of scalding through running hot liquids that can result in personal injury including death and material damage. BEWARE OF RISK OF ROTATIG UIT PART! This symbol indicates a hazardous location with a risk of personal injury including death and material damage.this symbol indicates a hazardous location with a risk of personal injury including death and material damage. DAGER OF SUSPEDED HEAVY OBJECTS! This symbol indicates a hazardous location with a risk of personal injury including death and material damage.this symbol indicates a hazardous location with a risk of personal injury including death and material damage. PERSOAL IJURY! This symbol indicates (different from the above-mentioned danger types) a hazardous location with a risk of personal injury including death and material damage. EQUIPMET DAMAGE! This symbol indicates a hazardous location with a risk of material damage that can also lead to personal injury. EVIROMETAL DAMAGE! This symbol warns about damage to the environment. PR GB Subject to modifications R5-/205 9

10 Safety and User Information Multi Flair.3 Safety-conscious working To ensure your own safety consider the following safety instructions: HAZARDOUS VOLTAGE! Before carrying out any jobs on the unit, power the unit down to prevent injury from electrical current. Ensure that the unit is secured against being energised again at an appropriate point of the on-site power supply. DAGER OF SCALDIG! Before performing work on the valves or the inlet or outlet pipes, seal off the heating or cooling medium inlet to prevent scalding. Do not commence work before the heating medium has cooled down. BEWARE OF RISK OF ROTATIG UIT PART! Rotating fan impellers pose a risk and may cause injuries. Before performing any work on the unit, ensure that it is isolated. Ensure that the unit is isolated and secured against being energised at an appropriate point of the on-site power supply. DAGER OF SUSPEDED HEAVY OBJECTS! Wear a helmet and safety boots to prevent injury from falling components, especially when fitting the unit to the ceiling. Ceiling installations should always be performed by two persons. PERSOAL IJURY! Always wear protective gloves when shipping or installing the unit to prevent injury caused by sharp edges. The following accident prevention regulations apply (VBG, BGV A2 (previously: VBG4), VBG7w, VBG9a) and generally recognized codes for machinery and principles of engineering, particularly DI VDE 000, DI VDE Personnel selection and qualification The unit may be installed, operated and maintained only by qualified, specially trained and authorized staff. The following tasks described in the operation manual may only be performed by qualified personnel: Shipping and storage Assembly Hydraulic connection Electrical connection Commissioning Maintenance 0 PR GB Subject to modifications R5-/205

11 Multi Flair Safety and User Information.5 Proper use Multi Flair unit are exclusively designed for heating, filtering and cooling applications. As medium water or water/glycol solution (max. 50 %) may be used as medium. The following limit values apply to medium for operating Cu/Al heat exchangers: Parameter Unit Value ph-value (at 20 C) Conductivity (at 20 C) μs/cm < 700 Oxygen content O 2 mg/l < 0. Total hardness dh - 5 Dissolved sulphur S not detectable Sodium a + mg/l < 00 Iron Fe 2+, Fe 3+ mg/l < 0. Manganese Mn 2+ mg/l < 0.05 Ammonium content H + 4 mg/l < 0. Chloride Cl - mg/l < 00 Sulphate SO 2-4 mg/l < 50 itrite O - 2 mg/l < 50 itrate O - 3 mg/l < 50 Tab. -: Limit values for the medium in closed heating and cooling circuits The following limit values apply to medium in Cu/Al heat exchangers: Parameter Unit Value Max. operating temperature C 90 Min. cooling temperature (in connection with MATRIX controls and control valve) C 6 Max. operating pressure bar 6 Max. air inlet temperature C 40 Tab. -2: Medium limit values for Cu/Al heat exchangers PR GB Subject to modifications R5-/205

12 Safety and User Information Multi Flair EQUIPMET DAMAGE! In open systems (e.g. when using well water, consider limit values specified in Tab. -), used water should additionally be cleansed of suspended matter using a filter to be installed at the inlet. Failure to do so could result in a risk of erosion by suspended matter. It must also be ensured that the unit is protected from dust and other substances that can cause acidic or alkaline reaction with water (aluminium corrosion). The Multi Flair unit may only be used indoors. The Multi Flair unit is designed for ceiling mounting. The unit is considered to be used in an improper manner if it is applied for other purposes or a purpose that is not covered by the scope of the given operation manual. The manufacturer or supplier is not liable for any resulting damage: the user alone bears the full risk. The operator is responsible for proper use. Proper use also stipulates the observance of the operation manual and the inspection and maintenance conditions defined by DencoHappel..6 Improper use It is not allowed to operate the Multi Flair unit: in explosion risk areas; in wet areas or in locations with high dust levels or aggressive air. PERSOAL IJURY AD MATERIAL DAMAGE! Improper use can cause personal injury and material damage. 2 PR GB Subject to modifications R5-/205

13 Multi Flair Technical Description 2 Technical Description 2. Unit components Pos. : Pos. 2: Cover plate Controls 2 Pos. 3: Corner covers, 4-sides 3 Pos. 4: Condensate pump cooling (accessories) 7 4 Pos. 5: Secondary air louver, 4-sides 5 6 Pos. 6: MATRIX printed circuit board Pos. 7: Unit connection circuit board 8 Pos. 8: Circular heat exchanger Pos. 9: Coil drip tray with drain Pos. 0: Base plate Pos. : Pump sump cover Pos. 2: Fan assembly with external rotor motor Pos. 3: Contact protection grille Pos. 4: Filter cassette with 2 guide rails (only with M unit design) Pos. 5: Filter panels (only with M unit design) Pos. 6: Design panel (only with M unit design) 6 Fig. 2-: Unit components (depending on unit model) PR GB Subject to modifications R5-/205 3

14 Technical Description Multi Flair Various unit parts indicated in Fig. 2- are specified in detail as follows. Cover plate (Pos. ) Cover plate with primary air connection and air impact deflector Controls (Pos. 2) With 230 V with series resistor With 400 V with MATRIX circuit board Corner covers, 4-sides (Pos. 3) Corner covers are mounted on the unit Condensate pump cooling (accessories) (Pos. 4) The condensate pump drains condensate of the drip tray into higher placed upstream drainage pipework. MATRIX printed circuit board (Pos. 6) With 230 V unit configuration the controller PCB is fitted here. Unit connection circuit board (Pos. 7) External power supply 230 V / 400 V of the unit is performed here. Circular heat exchanger (Pos. 8) Chilled and warm water heat exchanger is equipped with R 3/4" internal thread connection fittings and air vent valves. Coil drip tray with drain (Pos. 9) Coil drip tray is designed for collecting and routing condensate to the pump sump cover. Base plate (Pos. 0) Base plate with unit identification plate Pump sump cover (Pos. ) Condensate is collected in the pump sump cover (only with cooling units). Fan assembly with external rotor motor (Pos. 2) The fan is performed as an external rotor motor with metal sheet blades. The motor is fitted with motor protection via integrated thermal contacts. Filter cassette with 2 guide rails (Pos. 4) The guide rail is divided within the pump sump. 4 PR GB Subject to modifications R5-/205

15 Multi Flair Technical Description 2.2 Operating limits 2.2. Water inlet temperature To prevent condensate from forming on non-insulated casing parts when the temperature falls below the dew point during cooling operation, specific minimum water supply temperature or evaporating temperature must be maintained. The latter depends on ambient temperature and indoor relative humidity and is specified in the following diagram ϕ = ϕ = 80 ϕ = 75 ϕ = 70 Water inlet temperature in C ϕ = 65 ϕ = 60 ϕ = 55 ϕ = 50 8 ϕ = ϕ = Indoor temperature in C Fig. 2-2: Minimum allowed water inlet temperature as a function of indoor air condition; air pressure = 03 hpa; ϕ = relative humidity PR GB Subject to modifications R5-/205 5

16 Technical Description Multi Flair Unit and heat exchanger Unit and heat exchanger Values Max. operating pressure/temperature,6 MPa (6 bar)/90 C Max. allowed ambient temperature 40 C Min. allowed ambient temperature 2 C Operating voltage 230 V AC, 50 Hz or 400 V AC Power consumption/protection class Refer to identification plate Max. discharge temperature 75 C (fire hazard) Min. temperature primary air 7 C Tab. 2-: Operating limits for unit and heat exchanger 2.3 Dimensions 2.3. Basic unit Fig. 2-3: Dimensions of basic unit Model size Design panel B H H S a b x Ø D F Fig. 2-4: Unit-size-dependent width of basic unit H S : Standard unit, F: Bolt circle for fixation 6 PR GB Subject to modifications R5-/205

17 Multi Flair Technical Description 2.4 Unit data 2.4. Unit weight, water charge of heat exchanger and enclosure protection class Model size 2 3 Protection class IP20 IP20 IP20 Protection class I I I Water volume: CS /2, CS 3/4 (CS - capacity stage) [l].2 / / / 3.2 Weight: unit / cover [kg] 39.5 / / / 5.2 Tab. 2-2: Unit weight and water charge of heat exchanger Electrical data Electrical data for 230 V AC fan motors Model size Current consumption fan motor(s) Power consumption fan motor(s) Motor with a series resistor [A] [W] Tab. 2-3: Electrical data for 230 V AC, 50 Hz fan motors Electrical data for 400 V AC fan motors Model size Current consumption fan motor(s) 2-speed [A] Power consumption fan motor(s) [W] Tab. 2-4: Electrical data for 400 V AC, 50 Hz fan motors PR GB Subject to modifications R5-/205 7

18 Technical Description Multi Flair 2.5 Condensate pump In cooling units condensate may form and is collected in the coil drip tray. If a slope for condensate drainage is not fitted, a condensate pump must to be installed. This pump drains condensate into higher placed upstream drainage pipework Function of condensate drain Additionally to the condensate pump, a float switch is fitted and performs the following functions: Activates the pump when the pre-set water level in the drip tray is exceeded. Switches the pump off if the condensate level falls below the minimum water level. Activates alarm if the maximum allowed water level is exceeded Condensate pump The maximum operating pressure of the pump amounts to 0. MPa ( bar); the maximum flow rate makes up 0 l/h. Fig. 2-6 specifies the pump's capacity in l/h in relation to the delivery head Fig. 2-5: Condensate pump (accessories) with pump sump cover Pos. : Pos. 2: Pos. 3: Pos. 4: Pump control (SKP) Condensate pump Float switch Pump sump cover 8 PR GB Subject to modifications R5-/205

19 Multi Flair Technical Description Technical data of condensate pump Technical Data Values Operating voltage 230 V AC / 50 Hz Current consumption max 0.2 A Power consumption 55 W Max. pump head.3 m Max. water flow rate 60 l/h Sound power level with H = 0 m 45 db(a) with H = 4 m 46 db(a) Tab. 2-5: Technical data condensate pump Condensate pump capacity,40,35 Hose length 2.5 m,30,25,20 Hose length 5.0 m Pressure rise in m H 2 O,5,0,05,00 0,95 0,90 0,85 0,80 0,75 0,70 0,65 0,60 0,55 0,50 0 Valid for: Internal diameter of hose: 6 mm Internal diameter of hose connection: 4.5 mm Resistance of the pressure line considered in the curve: unit internal parts: non-return valve, hose connection 90 bend by others: hose connection for connecting condensate main pipework by others Pressure increase: from pump suction opening Delivery volume Q in l/h Fig. 2-6: Condensate pump capacity PR GB Subject to modifications R5-/205 9

20 Shipping and Storage Multi Flair 3 Shipping and Storage 3. Transport safety DAGER OF SUSPEDED HEAVY OBJECTS! It is extremely dangerous to stand under overhead loads. Make sure there are no persons below an overhead load! EQUIPMET DAMAGE! Improper shipping can cause damage to the Multi Flair unit. If damage has been caused by impacts to the unit or by dropping it, carefully check Multi Flair unit for proper operation. Take care when transporting the Multi Flair unit! 3.2 Scope of supply Remove packing and inspect shipment immediately when received to determine if any damage has occurred to the unit during shipment (if any damage is found, immediately file claim for damage with the transportation company), also check for missing items and verify that the shipment is complete. For this purpose compare the details of the unit type plate with the specifications on the despatch note. The same applies to all accessory items. Missing parts or claims of shipping damage must only be reported to the transport insurance, if the damage has been confirmed by the delivering carrier. 3.3 Packaging The unit is shipped in a sturdy cardboard box. 3.4 Shipping EQUIPMET DAMAGE AD PERSOAL IJURY! Always wear protective gloves to prevent injury caused by sharp edges. To prevent injury it is necessary to use at least two persons to move the Multi Flair unit. In case of delivery on pallets, use only lifting and transport vehicles with sufficient load carrying capacity. Secure the load during transit to prevent it from tipping or falling. 20 PR GB Subject to modifications R5-/205

21 Multi Flair Shipping and Storage 3.5 Temporary storage When storing the unit for a temporary period, the following aspects must be considered: Store and keep the Multi Flair unit in its original packing. The storage location must be protected from the elements, dry and dust-free with relative humidity between 50 and 85 %. The storage temperature must be between -0 to +50 C. EQUIPMET DAMAGE! All residual water must be drained from the heat exchanger! Frost risk! The Multi Flair unit must be protected from impacts and vibration. 3.6 Disposal RECYCLIG! Ensure that operating supplies, packaging and replacement parts are disposed of in a safe and environmentally friendly manner. The local recycling facilities must be used and local regulations and codes must be observed. For disposal components must be separated and sorted by different materials. PR GB Subject to modifications R5-/205 2

22 Assembly Multi Flair 4 Assembly HAZARDOUS VOLTAGE! Before drilling ensure that the drilling area is free from electrical cables or pipes. PERSOAL IJURY! Injury may be caused by falling parts and sharp edges! Put on Personal Protective Equipment (PPE) such as helmet, safety boots and protective gloves when installing the unit. Ceiling installations should always be performed by two persons. OTE! It must be ensured that no mechanical deformations or twisting occurs when installing units in different positions and configurations. Give special attention to the horizontal installation of the unit - level in both directions. All fixation points must be used. 4. Installation location The installation site must fulfil requirements regarding relevant characteristics and ambient temperature for the unit heater (refer to Chapter.5 and Chapter.6). Consider the following points: The ceiling or support surface must be vibration-free and capable of bearing full weight of the unit. Install the unit only in enclosed spaces indoors. For unit fixation use the relevant mounting kit (accessories), especially when mounting the unit below suspended ceilings. Give special attention to the minimum installation height of 2.5 m. The following maximum suspension heights must be observed: Model size 2 3 Suspension height [m] Tab. 4-: Maximum suspension heights 22 PR GB Subject to modifications R5-/205

23 Multi Flair Assembly 4.2 Unit installation Before the unit installation the corner covers must be removed Removing corner covers Before installation the corner covers must be removed. Removing corner covers: Shift the corner covers upward. Pull away the corner covers to the front. Fig. 4-: Removing corner covers OTE! Please consider the direction of arrow when removing the corner covers. PR GB Subject to modifications R5-/205 23

24 Assembly Multi Flair Installation on ceiling OTE! The Multi Flair unit can be mounted directly under the ceiling or can be suspended using appropriate tools. Fig. 4-2: Ceiling mounting of Multi Flair With ceiling installation at least 4 drill holes are necessary (2 on each side). Transfer the drilling measurements on the wall as shown in Fig. 4-3 and Tab. 4-2 on the ceiling. Mount the Multi Flair unit at the marked position. Fixation points Fig. 4-3: Drilling size for ceiling mounting of Multi Flair Model size 2 3 F (mm) Tab. 4-2: Fixation points 24 PR GB Subject to modifications R5-/205

25 Multi Flair Assembly Mounting set 46D The mounting set 46D (refer to Fig. 4-4) consists of: 4 M8 screws with hexagon head 4 spring washers 8 mm 4 flat washers 8 mm 4 elastomer insulated washers 4 dowel plugs 0 mm Set the elastomer insulated washers into fixation openings of the unit base plate. Mount and secure the unit using washers, spring washers and screws. 6 Pos. : Pos. 2: Pos. 3: Pos. 4: Pos. 5: Pos. 6: M8 x 60 mm screw 8 mm spring washer 8 mm flat washer Unit base plate Elastomer insulated washer 0 mm dowel plug Fig. 4-4: Mounting set 46D OTE! Following installation and unit connection the corner covers must be fitted again. For this purpose perform all specified steps in reverse sequence. PR GB Subject to modifications R5-/205 25

26 Assembly Multi Flair Installation below suspended ceiling Dimensions of ceiling plate and pipe connections are specified in Fig Ceiling plate Unit centre line X F ØD Ø Primary air connection 65 2 Unit centre line A View A Unit upper edge Primary air Mounting set 46Z Pipe connections 3/4" internal screw thread65 Fig. 4-5: Sample installation below suspended ceiling Model size 2 3 F (mm) Tab. 4-3: Fixation points 26 PR GB Subject to modifications R5-/205

27 Multi Flair Assembly Mounting set 46Z Mounting set 46Z consists of: 4 mounting brackets (see Fig. 4-6) 4 threaded rods M8 x 500 mm 8 nuts M8 8 hexagon nuts M8 4 dowel plugs 0 mm 4 M8 screws with hexagon head Fig. 4-6: Dimensions of mounting brackets OTE! Following installation and unit connection the corner covers must be fitted again. For this purpose perform all specified steps in reverse sequence. PR GB Subject to modifications R5-/205 27

28 Assembly Multi Flair Primary air connection (only for unit with primary air fitting) Before installing unit on the ceiling or below a suspended ceiling the primary air connection fitting must be secured: Loosen the primary air connection fitting from the cover plate (4 screws) Remove the primary air connection fitting. Rotate the primary air connection fitting by 80. Screw the primary air connection fitting from top together with the cover plate. D Al D Al Fig. 4-7: Primary air connection Mounting clearances and diameter of primary air connection fitting Model size F (mm) F (mm) F 2 (mm) D AI (mm) Tab. 4-4: Mounting clearances and diameter of primary air connection fitting 28 PR GB Subject to modifications R5-/205

29 Multi Flair Assembly Mounting unit cover panel (only M series) EQUIPMET DAMAGE! For units with a side pipe connection the fixation side for the unit cover panel must be the pipe connection side! Angle lugs and mounting brackets should be screwed to the unit bottom side (drill holes are available). Insert the unit cover panel into the angle lugs (see Pos. ). Fold up the unit cover panel (refer to Pos. 2). Screw the unit cover plate at both mounting brackets on the screw side (see Pos. 3). Screw the fixing screws into the angle lugs (insertion side) (see Pos. ) Fig. 4-8: Mounting unit cover plate Pos. : Insertion side Pos. 2: Fold up unit cover plate Pos. 3: Screw side PR GB Subject to modifications R5-/205 29

30 Hydraulic Connection Multi Flair 5 Hydraulic Connection 5. General If Multi Flair units are fitted with field-provided valves, running supply and return lines depends on coil connections performed by others and/or utilised valve. DAGER OF SCALDIG BY ESCAPIG HEATIG MEDIUM! Before the on-site pipework running and setting up hydraulic connections for the Multi Flair unit, the heating/cooling medium must be shut off and secured against inadvertent opening. Unit heaters with cooling function are fitted with a lateral coil drip tray. The tray is used to collect condensate forming in the unit (valves, screw connections and piping). All field cooling medium pipework must be insulated to prevent condensate formation. When all connections are completed, all bolt/screw connections should be tightened and ensured that they are free of mechanical stress. 30 PR GB Subject to modifications R5-/205

31 Multi Flair Hydraulic Connection 5.2 Pipe connections The pipework must be run in such a way as to avoid mechanical stress for the heat exchanger and to ensure accessibility for maintenance and servicing. EQUIPMET DAMAGE! During installation the connecting nut on the heat exchanger must be countered using a suitable tool. Supply and return line: row: connection regardless of direction 2 rows: consider labelling! Pipe connections: internal screw thread 3/4" red brass internal screw thread Air venting of pipework must be provided by others. Unused pipe connections must be properly sealed with enclosed plugs. Pipe connections with cooling units must be insulated Installation example: pipe connection from top 65 3 Ø Fig. 5-: Pipe connection from top Pos. : Supply line Pos. 2: Return line Pos. 3: Suspended ceiling Before unit installation lateral pipe connections must be properly sealed with enclosed threaded plugs. Use the mounting set to secure the unit horizontally in a vibration isolated manner below the suspended ceiling; Air venting of pipework must be ensured by others. Unused pipe connections of cooling units must be insulated. PR GB Subject to modifications R5-/205 3

32 Hydraulic Connection Multi Flair Installation example: pipe connection from side Fig. 5-2: Pipe connection from top Pos. : Supply line Pos. 2: Return line Pos. 3: Air venting Before unit installation top pipe connections must be properly sealed with enclosed threaded plugs. Use the mounting set to secure the unit horizontally in a vibration isolated manner below the ceiling or suspended ceiling; Air venting of pipework must be ensured by others. Unused pipe connections of cooling units must be insulated Protection class/water charge/weights/sound pressure level Model size 2 3 Protection class IP20 IP20 IP20 Protection class I I I Water volume: row/2 rows Liter.2 / / / 3.2 Weight: unit / cover kg 39.5 / / / 5.2 Sound pressure level db(a) (3-speed unit) Sound pressure level db(a) (2-speed unit) Speed I Speed II Speed III Speed I Speed II Tab. 5-: Protection class/water charge/weights/sound pressure level PR GB Subject to modifications R5-/205

33 Multi Flair Hydraulic Connection Sound power of condensate pump with cooling units Sound power sum level of installed condensate pump amounts to: not evaluated: 54 db A-rated: 52 db(a) Sound pressure level amounts to 37 db(a) otice on amplified operating noise of condensate pump in the start-up stage Condensate pump can cause short-term amplified operating noise during start-up stage as a result of air locks in the air intake ductwork and deviations from normal operating temperature. 5.3 Condensate drain 5.3. Connection for condensate drain for cooling units with condensate pump Condensate pump capacity is specified in the pump characteristics curve (see Fig. 2-6 on page 9). A short-period dry run (less than 5 min.) will not cause any operating malfunctions of the condensate pump. When running condensate main by others consider the following: Run the condensate pipework with an accordingly large internal diameter and a slope up to the point of free drainage. If there are no reductions of cross section following the condensate pump, except for non-return valve and 2 hose nozzles, the delivery head amounts to.35 m. (internal diameter of condensate hose: 6 mm, line length: max. 5 m) 5 Pos. : Pos. 2: Pos. 3: Pos. 4: Pos. 5: Pump control (SKP) Condensate pump Float switch Pump sump pit Pressure hose pump Length:.5 m; Internal diameter: 6 mm Fig. 5-3: Condensate pump (accessories) PR GB Subject to modifications R5-/205 33

34 Hydraulic Connection Multi Flair Connection for condensate drain for cooling units without condensate pump Pos. : Condensate drain hose length: m Internal diameter: 6 mm Fig. 5-4: Field condensate connection OTE! The connection hose should be run with a slight slope (give special attention to avoid sharp bends and blockage) 34 PR GB Subject to modifications R5-/205

35 Multi Flair Electrical Connection 6 Electrical Connection HAZARDOUS VOLTAGE! The electrical installation of the Multi Flair unit heaters must only be carried out by qualified electricians in observance of this operation manual, valid regulations and codes of practice: VDE regulations, including safety regulations Accident prevention regulations Installation instructions 6. Wiring diagrams The electrical connection of Multi Flair unit heaters must be performed in accordance with the valid wiring diagrams. The wiring diagram is located on the inside cover of the unit connection box or is enclosed separately. HAZARDOUS VOLTAGE! The wiring diagrams do not contain any protective measures. When performing connections currently valid standards and regulations must be observed and checked with the local power company. Control/power electronics MATRIX 200 MATRIX 2002 MATRIX 300 Control units Tab. 6-: Fusing Fusing B 0 A B 0 A B 0 A B 0 A PR GB Subject to modifications R5-/205 35

36 Electrical Connection Multi Flair 6.2 Connection of field controls for use with control units or MATRIX regulation The components are connected via a terminal board. The terminal board is fitted in the metal sheet electric control box (see Fig. 2-). Fig. 6-: Connection diagram attached to inside of cover or enclosed separately Metal sheet electric control box 230 V / 400 V OTE! Refer to the wiring diagram enclosed with the unit for detailed instructions on connection of individual components (fan, valves, etc.). The order code of the unit's electrical equipment and the wiring diagram should be checked before commencing connections. Only one fan speed stage may be activated simultaneously! Connect only in accordance with the unit-specific wiring diagram. 36 PR GB Subject to modifications R5-/205

37 Multi Flair Electrical Connection 6.3 Overview of unit circuit boards and MATRIX control electronics 6.3. Unit circuit boards for use on 230 V and 400 V Unit circuit boards and MATRIX control electronics are built into the electrical control box. The following overview illustrates different unit circuit boards. To perform connections, the following unit circuit boards and their layouts specify the relevant controller type. Controller type (e.g. MATRIX 300) can also be checked in the wiring diagram attached to the inside of the control box cover or as a PCB sticker. For each connectable component an individual table indicates possibilities of connecting electric equipment to the supplied controller hardware. 230 V or 400 V unit circuit boards are used to connect units to 230 V or 400 V mains supply or a control gear. Unit circuit board 230 V Unit circuit board 400 V L L X2 X X7 X6 X5 X4 X TP TP2 TP3 L Fan mode Tk Tk Tk Tk U U2 Z L L L2 L2 L3 L3 X0 X X2 X3 X4 X5 L. L2. L3.. X8 Z2 Motor capacitor Motor capacitor Motor U V W U2 X8 X9 U V W U2 Control V2 V2 W2 W2 Tk X6 X7 Tk Tk Tk Power supply Fan motor connection Thermal contact connection Power supply Fan motor connection Thermal contact connection Connection MATRIX control panel Connection of other units with MATRIX 2002 Fig. 6-2: Unit circuit boards for use on 230 V and 400 V PR GB Subject to modifications R5-/205 37

38 Electrical Connection Multi Flair MATRIX 200 and MATRIX 300 controller type MATRIX MATRIX L L 2 STV STV STV STV STV STV STP STP L L 2 STV STV STV STV STV STV STP STP O STP STP STP 0 2 Fig. 6-3: Power supply Valves Control panel connection Connection of other units with MATRIX 200 Inlet temperature sensor External room sensor MATRIX 200 and MATRIX 300 controller type STP STP STP Power supply Valves Control panel connection Connection of other units with MATRIX 200/300 Inlet temperature sensor External room sensor Status and error messaging External control input 38 PR GB Subject to modifications R5-/205

39 Multi Flair Electrical Connection Fan with series resistor For RPM fan regulation a series resistor is used on 3-speed 230 V motors. This series resistor is used by the factory to set three fixed speed stages Pos. : Pos. 2: Pos. 3: Pos. 4: Pos. 5: Pos. 6: Series resistor is mounted on circuit board Connection box for mains supply voltage by others Connection box for low voltage (sensors, remote control) Condensate pump Circular heat exchanger Primary air connection ote: presented with fan top view 6 4 Fig. 6-4: Fan with series resistor PR GB Subject to modifications R5-/205 39

40 Electrical Connection Multi Flair 6.4 Installing control panel All IP20 control panels have an integrated room temperature sensor. The latter can be used when the control panel is mounted at an optimum indoor location for regulating temperature. All IP54 control panels are supplied with a separate external indoor temperature sensor. OTE! The installation site of the room temperature sensor is crucial for the precise control of indoor temperature. Therefore avoid mounting the sensor in the following locations (refer to Fig. 6-5): next to doors, windows, hatches etc., as intense movement of air can cause incorrect measurements and affect control operation. hot or cold walls (e.g. chimney, outside wall), as wall temperature can cause incorrect measurements and affect control operation. behind curtains and net curtains as the insulating layers of air can cause incorrect measurements. in the direct vicinity to the units' discharge grille as discharge temperature can cause incorrect measurements. If a mounting location for an IP20 control panel is not available, or a IP54 control panel is required, a separate room temperature sensor must be fitted. This automatically disables all temperature sensors fitted in the control panel. * Fig. 6-5: Mounting control panel and room temperature sensor * recommended installation height 40 PR GB Subject to modifications R5-/205

41 Multi Flair Electrical Connection 6.5 Electrical connection to control unit by others 6.5. Connection to 230 V unit circuit board Connection of control unit by others or control unit (5-speed) Tk Tk L PE L L TP TP2 TP3 L Fan Tk Tk Tk Tk U U2 Z Z2 Motor capacitor M ~ Connection can be performed with to 5-speed control unit by others or a control unit Motor monitoring is carried out by thermal contacts built into the motor winding (rated for 230 V AC, 0.5 A). Unit fusing by others must not exceed a maximum of 0 A. (with control units max. 8 A) Connect the unit heater in accordance with the wiring diagram. Fig. 6-6: Connection to 230 V unit circuit board Connection to 400 V unit circuit board L L L2 L2 L3 L3 L. L2. L3.. PE Connection can be performed with a -speed control unit by others. low speed (Y-connection, Pos. 2) high speed (delta connection, Pos. 3) A 2-speed operation can be performed using a control unit (see Pos. ). Motor monitoring is carried out by thermal contacts built into the motor winding (rated for 230 V AC, 0.5 A). Unit fusing by others must not exceed a maximum of 0 A. U U L3 L3 M 3~ V W U2 V2 W2 V W U2 V2 W2 L2 L2 L L 2 3 Connect the unit heater in accordance with the wiring diagram. Tk Tk Tk Tk Thermal contact Fig. 6-7: Connection to 400 V unit circuit board OTE! Cooling unit with a condensate pump must be wired additionally in conformity with a separately enclosed connection diagrams. PR GB Subject to modifications R5-/205 4

42 Electrical Connection Multi Flair Connection of multiple 230 V unit heaters to a control unit Multi Flair Multi Flair 2 Multi Flair 3 L P E T K T K L P E T K T K L P E T K T K Intermediate terminal box U U U U 2 U 2 U Terminal box by others is required for connection of a contact temperature thermostat (for heating or cooling units) Power supply 230V PE L 8A * L 6 7 U U H C ϑ 2 3 ϑ Room thermostat (accessory) Contact temperature thermostat (accessories) Control unit Fig. 6-8: Connection of multiple 230 V unit heaters to a control unit A maximum of 4 unit heaters can be connected to a control unit using an intermediate terminal box (With model size 3 a maximum of 3 units can be connected) Thermal contacts must be connected in series. Without a connected room thermostat bridges must be set for terminals 6-7 in the control unit Max. fusing 8 A. 42 PR GB Subject to modifications R5-/205

43 Multi Flair Electrical Connection Connection of multiple 400 V unit heaters to a control unit Multi Flair Multi Flair 2 Multi Flair 3 U V W U 2 V 2 W 2 P E T K T K U V W U 2 V 2 W 2 P E T K T K U V W U 2 V 2 W 2 P E T K T K Intermediate terminal box U U U V V V W W W U U U V V V W W W Terminal box by others is required for connection of a contact temperature thermostat (for heating or cooling units) Power supply 400 V PE L L2 L3 0A * L L L U V W U 2 V 2 W 2 T K T K 2 3 H C ϑ 2 3 ϑ Control unit Room thermostat (accessory) Contact temperature thermostat (accessories) Fig. 6-9: Connection of multiple 400 V unit heaters to a control unit A maximum of 4 unit heaters can be connected to a control unit using an intermediate terminal box Thermal contacts must be connected in series. Without a connected room thermostat bridges must be set for terminals -2 in the control unit Max. fusing 0 A. PR GB Subject to modifications R5-/205 43

44 Electrical Connection Multi Flair Connection of controls for condensate pump unit F 0,4 AT (L) 2 () max. 6 A PE L Pos. : Power supply 230 V / 50 Hz / / PE max. 6 A Pos. 2: Status output (max. 230 V / 2 A) K is activated if water level is too high K2 is activated if terminal and 2 (L, ) are energised with supply voltage K K2 Status signals max. 2 A Input Ready-to-operate Fault Fig. 6-0: Connection of controls for condensate pump 6.6 Electrical connection with MATRIX 6.6. Connecting mains supply voltage for units with controller MATRIX PE PE L L PE L Pos. : Pos. 2: Pos. 3: Pos. 4: Power supply 230 V AC / 50 Hz, fusing by others max. B 0 A Connection at st unit Connection at 2nd unit To further units PE PE Mains supply voltage is applied on the unit circuit board. 3 L L Apply the mains supply voltage in accordance with the wiring diagram. 4 Fig. 6-: Applying mains supply voltage to unit circuit board 44 PR GB Subject to modifications R5-/205

45 Multi Flair Electrical Connection MATRIX L L2 L3 PE L L L. Pos. : Pos. 2: Power supply 400 V AC / 50 Hz, fusing by others max. B 0 A To further units Mains supply voltage is applied on the unit circuit board. L2 L2 L3 L3 L2. L3.. Apply the mains supply voltage in accordance with the wiring diagram. U U L L2 L3 PE V V 2 W W U2 U2 V2 V2 W2 W2 Tk Tk Tk Tk Fig. 6-2: Applying mains supply voltage to unit circuit board OTE! Additional units can be supplied by the first unit (see Fig. 6-, Pos. 3 and Pos. 4 or Fig. 6-2, Pos. 2). The total power consumption of the units must not exceed 7.5 A. Connection of a second input may be necessary Connecting control cables OTE! Use the following control cables for connection: Short cable lengths and/or location not prone to interference: multi-core control cable, 0.5 mm 2, shielded with aluminium-clad plastic sleeve e.g. J-Y(ST)Y x2x0.8 / 3x2x0.8 / 4x2x0.8 Longer cable lengths and/or location prone to interference: multi-core control cable, 0.5 mm 2 with copper-weave shielding PR GB Subject to modifications R5-/205 45

46 Electrical Connection Multi Flair Control Bediengerät panel MATRIX.OP2 Unit Gerät with mit MATRIX STV STV STV2 STV2 MATRIX Control panel connection air treatment unit without valve control External room sensor (optional) Control panel MATRIX OP2 can only be connected to units equipped with MATRIX Connect control cables in accordance with the wiring diagram. Control panel must be wired with the controller circuit board. Control cable: see bottom note on page 45. Two additional wires must be applied to terminals 2 and 3, if an external room sensor or an external flow sensor is connected to intermediate terminals STV, STV2. Possible eventl. external externer sensor Raumfühler oder Fig. 6-3: Connection control panel air treatment unit without valve control MATRIX Control Bediengert panel MATRIX.OP eventl. externer Raumfhler Possible external sensor Control panel connection air treatment unit without valve control External room sensor (optional) Control panel MATRIX OP2 can only be connected to units equipped with MATRIX Connect control cables in accordance with the wiring diagram. Gert Unit with mit MATRIX Control panel is connected to the unit circuit board. Control cable: see bottom note on page 45. Fig. 6-4: Connection control panel air treatment unit without valve control 46 PR GB Subject to modifications R5-/205

47 Multi Flair Electrical Connection Control Bediengerät panel MATRIX.OP2 Unit Gerät with mit MATRIX STV STV STV2 STV2 MATRIX Connection control panel air treatment unit with controls for external valve External room sensor (optional) Control panel MATRIX OP2 can only be connected to units equipped with MATRIX Connect the control cables in accordance with the wiring diagram. Control panel must be wired with the controller circuit board. Control cable: see bottom note on page 45. Two additional wires must be applied to terminals 2 and 3, if an external room sensor or an external flow sensor is connected to intermediate terminals STV, STV2. Possible eventl. external externer sensor Raumfühler oder Vorlauffühler Fig. 6-5: Connection control panel air treatment unit with controls for external valve PR GB Subject to modifications R5-/205 47

48 Electrical Connection Multi Flair MATRIX Führungsgerät First unit with mit MATRIX.2000 Folgegerät Further units mit with MATRIX Other slave units Connection first unit - further units without valve control All further units must be equipped with MATRIX Connect the control cables in accordance with the wiring diagram. With MATRIX 200 connection is performed on controller circuit boards and with MATRIX on the unit circuit boards. Control cable: see bottom note on page 45. With MATRIX 2002 the connecting wire is not required. Fig. 6-6: Connection first unit - further units without valve control MATRIX Führungsgerät First unit with mit MATRIX.2000 Folgegerät Further units mit with MATRIX Connection first unit - further units with external valve control All further units must be equipped with MATRIX Connect the control cables in accordance with the wiring diagram. Connection is performed on controller circuit boards (only with MATRIX 200). Control cable: see bottom note on page 45. Other slave units Fig. 6-7: Connection first unit - further units with external valve control 48 PR GB Subject to modifications R5-/205

49 Multi Flair Electrical Connection Führungsgerät First unit with mit MATRIX.3000 Folgegerät Further units mit MATRIX.2000 with MATRIX Other slave units MATRIX Connecting first unit MATRIX further units with MATRIX 2000 Units with MATRIX 300 can be operated with units fitted with MATRIX 200. Connect the control cables in accordance with the wiring diagram. Connection is performed on controller circuit boards. Control cable: see bottom note on page 45. Connections on and are required only for valve regulation. Fig. 6-8: Connecting first unit - further units Completing bus connection Control panel MATRIX OP2 etwork user! '# '$ '% '& ''!!!!"!#!$!%!& '# '$ '% '& '' MATRIX Connecting control panel network participant When connecting control panel MATRIX OP2 to MATRIX.et network, 2-wire bus line should be used. Connect the control cables in accordance with the wiring diagram. The following cable is recommended for the bus line: Manufacturer: HELUKABEL Type: CA-BUS flexible 2 x 2 x... mm 2 Attention: For wiring use data transfer cable certified according to DI 9245 T3 and E 5070 with twisted-pair wire and braided shield. Fig. 6-9: Connecting control panel network participant PR GB Subject to modifications R5-/205 49

50 Electrical Connection Multi Flair Control Bediengerät panel MATRIX MATRIX.OP30 - OP5 bis OP5 Gerät Unit with mit MATRIX3000 MATRIX. 3000/ MATRIX Control panel connection air treatment unit Control panels MATRIX OP30 to MATRIX OP5 can be only operated with units fitted with MATRIX Connect the control cables in accordance with the wiring diagram. Connection is performed on the controller circuit board. The following cable is recommended for the bus line: Manufacturer: HELUKABEL Type: CA-BUS flexible 2 x 2 x... mm 2 Attention: For wiring use data transfer cable certified according to DI 9245 T3 and E 5070 with twisted-pair wire and braided shield. Fig. 6-20: Control panel connection air treatment unit Führungsgerät First unit with mit MATRIX3000 MATRIX. 3000/ Connecting first unit - further units If units are fitted with the same control electronics as MATRIX 3000, a 2-core bus line must be used. Connect the control cables in accordance with the wiring diagram. Folgegerät Further unit with mit MATRIX3000 MATRIX. 3000/ Other slave units Connection is performed on the controller circuit board. The following cable is recommended for the bus line: Manufacturer: HELUKABEL Type: CA-BUS flexible 2 x 2 x... mm 2 Attention: For wiring use data transfer cable certified according to DI 9245 T3 and E 5070 with twisted-pair wire and braided shield. Fig. 6-2: Connecting first unit - further units 50 PR GB Subject to modifications R5-/205

51 Multi Flair Electrical Connection Connecting external sensor (option) MATRIX Pos. : Connection cable (see note on page 45) a summer compensation is required For this purpose an analogue input module MATRIX.AI must be built into the control box by others. For details refer to the operation manual on Global Modules. Fig. 6-22: Connecting external sensor (option) Connecting inlet sensor (option) MATRIX Pos. : Connection cable (see note on page 45) 2 3 Fig. 6-23: Connecting inlet sensor (option) Connect the inlet sensor according to the wiring diagram. With MATRIX 200/2002 the connection can be performed using control panel OP2 (terminals 2, 3) or intermediate terminals of the unit with MATRIX 200 (see page 46 and page 47). Connection of the inlet sensor excludes connection of other sensors (e.g. room temperature sensor). MATRIX Pos. : Connection cable (see note on page 45) " # Connect the inlet sensor according to the wiring diagram. Connection is performed on the controller circuit board MATRIX 300. Fig. 6-24: Connecting inlet sensor (option) PR GB Subject to modifications R5-/205 5

52 Electrical Connection Multi Flair Connecting room temperature sensor MATRIX Pos. : Connection cable (see note on page 45) Connect the room temperature sensor according to the wiring diagram.! With 2-pipe change-over units with MATRIX 2000 connection of an additional room sensor is only possible via the AI module. With MATRIX 200/2002 the connection can be performed using control panel OP2 (terminals 2, 3) or intermediate terminals of the unit with MATRIX 200 (see page 46 and page 47) or directly on the controller with MATRIX 300. Fig. 6-25: Connection of room temperature sensor (option) Connecting status and fault messaging MATRIX The controller PCB enables to tap status and alarm messages using a volt free contact. The contact load at 230 V AC amounts to a maximum of 4 A ohmic / 2 A inductive. Luftbehandlungsgerät Air treatment unit with MATRIX mit 3000 MATRIX.3000/ O C C O C C Fault Operation Connect in accordance with the wiring diagram. Operation: contact closed on terminal 20-2 Fault: contact closed on terminal Fig. 6-26: Connecting status and fault messaging 52 PR GB Subject to modifications R5-/205

53 Multi Flair Electrical Connection Connecting function input Air treatment unit with MATRIX Function input as voltage free contact by others MATRIX Function input can be assigned with different functions depending on the supplied control equipment. To activate the function the contact has to be: closed for economy mode operation open for unit OFF with frost protection Changing this function is possible using the service software MATRIX.PC. Connect in accordance with the wiring diagram. The loop resistance may not exceed 500 Ω. Fig. 6-27: Connecting function input Valve connection Air treatment unit with MATRIX 2000/ Valve opens M ~ Valve closes MATRIX Connection of external valve actuator An actuator with a modulating motor rated at 230 V is required. Depending on unit and controller configuration the valve for 2-pipe systems is used in mode only heating/ only cooling/heating or cooling. Connect the valve actuator in accordance with the wiring diagram. Terminal 02: valve closes Terminal 03: valve opens Fig. 6-28: Valve connection PR GB Subject to modifications R5-/205 53

54 Electrical Connection Multi Flair Control panel MATRIX OP2 Valve module MATRIX.V! '# '$ '% '& ''!!!!"!#!$!%!& '# '$ '% '& '' MATRIX Connection control panel - valve module MATRIX.V Units equipped with MATRIX 2002 and required valve regulation an individual MATRIX.V valve module must be used. When connecting control panel MATRIX OP2 to MATRIX.et network, 2-wire bus line should be used. The valve module MATRIX.V is used to regulate an external valve. For details on the valve connection refer to the operation manual on Global Modules. Connect the control cables in accordance with the wiring diagram. The following cable is recommended for the bus line: Manufacturer: HELUKABEL Type: CA-BUS flexible 2 x 2 x... mm 2 Attention: For wiring use data transfer cable certified according to DI 9245 T3 and E 5070 with twisted-pair wire and braided shield. Fig. 6-29: Connection control panel - valve module MATRIX.V 54 PR GB Subject to modifications R5-/205

55 Multi Flair Electrical Connection 6.7 etwork and shielding connection This section contains specification of the MATRIX.et and correct network setup. The MATRIX.et is a network for connecting various components of the control system (network users) in one data bus. The bus enables to exchange all information required for control and regulation between the users. etwork user may include the following: Controller Control panels Global modules Central clock timer LO interfaces WEB interfaces Service software Group structure A group consists of a minimum of 2 and a maximum of 20 users (control panel, 6 air treatment units, valve module, DV module and LO module). This means, for example, that a control panel and a controller/unit form a group. A group can also be made up of a LO module and a controller/unit. With units fitted with MATRIX 3000 and MATRIX 4000, a group can also be formed by replacing the control panel by a global module, such as MATRIX LO. PR GB Subject to modifications R5-/205 55

56 Electrical Connection Multi Flair Group structure of the MATRIX 2000 system A group can be formed with the MATRIX 2000 system, as shown in Fig etworking Max. control panel Group Unit Unit 2 Unit wires 4-7 wires 4-7 wires Fig. 6-30: Group structure with MATRIX 2000 controller type The group address is assigned via the group address switch on the control panel refer to the Commissioning and Testing chapter in the operation manual for MATRIX control panels. On MATRIX.V the modules (MATRIX.V, MATRIX.LO) are assigned via the group address switch or, on MATRIX.LO, via software refer to the Commissioning and Testing chapter in this operation manual or in the operation manual for MATRIX.LO. Connection of MATRIX.et network is performed on the control panel. 56 PR GB Subject to modifications R5-/205

57 Multi Flair Electrical Connection Group structure of the MATRIX 3000 system in combination with the MATRIX 2000 system A group may be formed using the MATRIX 2000 and MATRIX 3000 systems. The Fig. 6-3 shows an example of a network consisting of a control panel, MATRIX 2000 system, MATRIX 3000 system and various global modules. etworking Group Max. control panel Unit 6 Unit 2 Unit wires 4-7 wires Unit Unit 2 Unit wires 4-7 wires Fig. 6-3: Combined group structure of controller types MATRIX 2000 and MATRIX 3000 The group address is assigned: via the group address switch on the control panel refer to the Commissioning and Testing chapter in the operation manual for MATRIX control panels. on the printed circuit board of the MATRIX 3000 controller refer to the unit s operation manual. On MATRIX.V the modules (MATRIX.V, MATRIX.LO) are assigned via the group address switch or, on MATRIX.LO, via software refer to the Commissioning and Testing chapter in this operation manual or in the operation manual for MATRIX.LO. Any assignment and combination of units 2-6 is possible. The control panel must be connected to a MATRIX 3000 controller type. It is possible to set up a MATRIX 3000 system that also incorporates components of the MATRIX 2000 system. Besides, the control panel is not required if global modules (such as MATRIX.LO, DI, DO and AI) are available and the required operating parameters and setpoints are communicated via these group modules. Group structure of the MATRIX 3000 system and/or MATRIX 4000 A group may be formed using the MATRIX 3000 and MATRIX 4000 systems. The Fig shows an example of a network consisting of a control panel, MATRIX 3000 system, MATRIX 4000 system and various global modules. PR GB Subject to modifications R5-/205 57

58 Electrical Connection Multi Flair Group etworking Unit Unit 2 Unit 6 Fig. 6-32: Combined group structure of controller types MATRIX 3000 and MATRIX 4000 Any assignment and combination of the controllers/units is possible. However, only MATRIX 3000 or only MATRIX 4000 controllers must be used. We recommend to assign the control panel as the first component of a group. The group address is assigned: via the group address switch on the control panel refer to the Commissioning and Testing chapter in the operation manual for MATRIX control panels. on the printed circuit board of the MATRIX 3000/4000 controller refer to the unit s operation manual. On MATRIX.V and MATRIX.LO the modules (MATRIX.V, MATRIX.LO, MATRIX.RF) are assigned via the group address switch or, on MATRIX.LO - via software refer to the Commissioning and Testing chapter in this operation manual or in the operation manual for MATRIX.LO. OTE! The combination of units with MATRIX 3000 and units with MATRIX 2000 systems is permitted in this group set-up Refer to Group structure of the MATRIX 3000 system in combination with the MATRIX 2000 system on page 57. The combination of units with MATRIX 4000 and units with MATRIX 2000 systems is not possible. 58 PR GB Subject to modifications R5-/205

59 Multi Flair Electrical Connection etwork structure A network can consist of one or several groups (up to 6). Global modules can also be integrated into the network. The network structure/network topology of MATRIX.et must be performed linearly Refer to etwork topologies on page 60. The maximum extent of the MATRIX.et network is shown in Fig Group 2 Group 4 Group 6 Group 3 Group Fig. 6-33: Example of maximum extent of the network At its maximum extent, the network can consist of: a maximum of 6 unit groups Refer to etwork topologies on page 60 two digital input modules (MATRIX.DI) two analogue input modules (MATRIX.AI) two digital output modules (MATRIX.DO) a central timer (MATRIX.CLOCK) a return air management (MATRIX.EM) up to 6 LO Modules (MATRIX.LO). Any assignment of the unit groups and the global modules in the network is possible. The following is decisive for the assignment of the units, control panels and global modules to a group as opposed to the physical assignment: the setting of the group address switch (refer to the Chapter Commissioning and Testing in the relevant operation manual) or the assignment of a module input and output to a unit group via the MATRIX.PC service tool (refer to the online help for the service software). and not the physical assignment. PR GB Subject to modifications R5-/205 59

60 Electrical Connection Multi Flair etwork topologies The MATRIX.et can be set in a line structure and a line structure with a stub line. All units fitted with MATRIX system can access this data bus. The data bus must be terminated at both physical ends to avoid reflections which can interfere with data transfer. Configurable bus end resistors are integrated on the respective circuit boards enabling safe termination refer to section Connecting MATRIX.et in the documentation on Global Modules Line structure 2 The illustration shows the setup of the MATRIX.et with line structure. As an example two groups, each consisting of a control panel and a Global Module, are networked. In addition, power supply of the control panel via the controller (terminals 95/99) is shown. Group Group 2 4 wires 2 wires 2 wires 4 wires Fig. 6-34: Set up of MATRIX.et in line structure OTE! The data transfer cable must be run as demonstrated in Fig in such a way that only one side of the respective shielding is applied Refer to Shielding / Earthing on page PR GB Subject to modifications R5-/205

61 Multi Flair Electrical Connection Line structure with stub line 2 3 X The illustration shows the setup of the MATRIX.et as line with stub line structure. A sample connection of a control panel via a stub line in multiple groups is illustrated. The maximum allowed stub line length amounts to 25 m. Group Group 2 Group X 2 wires 4 wires 2 wires Fig. 6-35: Set up of MATRIX.et in a line structure with a stub line* As it is not allowed to connect three wires together, a joining terminal must be provided. To do so, the intermediate terminals (STV) mounted on the board (if not already occupied) or terminals fitted on site by others can be used. OTE! The data transfer cable must be run as demonstrated in Fig. 6-35, in such a way that only one side of the respective shielding is applied Refer to Shielding / Earthing on page 62. PR GB Subject to modifications R5-/205 6

62 Electrical Connection Multi Flair etwork set up Data transfer cable For setting up the MATRIX.et use only data transfer cable certified according to DI 9245 T3 and E 5070 as twisted-pair wire with braided shield. RECOMMEDATIO We recommend the following data transfer cable: Producer: HELUKABEL Type: CA-BUS flexible 2 x 2 x... mm² Line lengths Regardless of the cross section and the number of participants the maximum line length including stub lines to the control panel may amount to a maximum of 600 m. The stub line must not exceed 25 m. The total length of all stub lines may not exceed a maximum 50 m. RECOMMEDATIO Repeaters must be used in the network if there are more than 0 users and the cable length is long. The cross-section of the bus cable must be changed depending on the MATRIX.net cable length! Line length Line type up to 50 m 2 x 2 x 0.22 mm² * x 2 x 0.22 mm² up to 600 m 2 x 2 x 0.5 mm² * x 2 x 0.5 mm² *Contains 2 wires for power supply to control panels or modules Shielding / Earthing Install the data transfer cable (MATRIX.et) on one side in the Multi Flair unit using shielding clips to ensure the best possible electrical contact. Connect the shielding with the shielding clip to a large earth surface area! In systems with a large network extent, or if large scale EMC impairment is likely, the shielding should be applied on both sides. It must be ensured beforehand that no potential differences occur. 62 PR GB Subject to modifications R5-/205

63 Multi Flair Commissioning 7 Commissioning HAZARDOUS VOLTAGE! Before performing any work on the unit, ensure that it is isolated. Ensure that the unit is secured against being energised at an appropriate point of the on-site power supply. DAGER OF SCALDIG! Before completing any kind of job on fan coil units: Seal off the supply of heating medium before performing work on the valves or the inlet or outlet pipework. Ensure that the shut off pipework can not be opened inadvertently. Do not commence work before the heating medium has cooled down. BEWARE OF RISK OF ROTATIG UIT PART! Rotating fan impellers pose a risk and may cause injuries. Before performing any work on the unit, ensure that it is isolated. Ensure that the unit is isolated and secured against being energised at an appropriate point of the on-site power supply. 7. Safety check 7.. Pre-commissioning checklist Mechanical and electrical installation of the entire system comprising Multi Flair units is complete. The Multi Flair unit is de-energised and isolated. All medium pipes were flushed and are free from residues and foreign matter. The system is properly filled with medium (see Proper use on page ). OTE! Prior to commissioning ensure that the unit discharge (heat exchanger) coil drip tray and filter are clean. If necessary, these components must be cleaned or filter replaced. PR GB Subject to modifications R5-/205 63

64 Commissioning Multi Flair 7..2 Checks before commissioning: Check for proper ceiling mounting and fixation of the Multi Flair unit. Open the valve on the piping. If the medium lines/heat exchanger are empty, competent personnel should refill and air vent them. Make sure the air venting is completed to avoid air bubbles in the heat exchanger. Check that the piping and connections and sealed Setting secondary air louvers Hold the air deflection profiles on the top right and bottom left sides simultaneously. Move the air deflection profiles simultaneously in the required position. Fig. 7-: Setting secondary air louver OTE! The discharge direction must be set in such way as to prevent air draughts in the occupied zone After commissioning: Close the terminal box and mount corner covers. 64 PR GB Subject to modifications R5-/205

65 Multi Flair Commissioning 7.2 Unit air venting To ensure that the exchanger is charged with heating/cooling medium, it must be air vented. OTE! Protect electrical hardware and furniture from escaping water. Open all shut-off and control valves. Use the air vent key to open the first air vent screw (see Fig. 7-2). Close the air vent screw again, only if heating/cooling medium is still pouring out. Proceed in the same way with all remaining air vent screws. 65 Fig. 7-2: Air venting heat exchanger Pos. : Air vent screw PR GB Subject to modifications R5-/205 65

66 Commissioning Multi Flair 7.3 Checking condensate pump (applies only to cooling units with condensate pump) OTE! To prevent transmission of structure-borne noise, suction and pressure lines must be run without contacting the basic unit and pipework. Prior to commissioning ensure that heat exchanger coil drip tray and filter are clean. If necessary, these components must be cleaned or filter replaced Checking condensate pump Condensate forms as a result of unit operation in cooling mode, the same applies to non-insulated pipes. Check that, supply pipes in front of the coil drip tray are sealed to collect entire condensate. coil drip tray is properly secured and stable. Unless already done, apply mains supply voltage. Check operation of condensate pump: Carefully fill the drip tray with some water to activate the pump. After a short period water will be emptied from the sump pit and the pump must be deactivated again. 2 Fig. 7-3: Checking electromagnetic condensate pump Pos. : Pos. 2: Condensate pump Condensate drip tray 66 PR GB Subject to modifications R5-/205

67 O O Multi Flair Commissioning 7.4 Terminating resistors MATRIX Unit printed circuit boards of the MATRIX 2000 control system are not equipped with terminating resistors. The terminating resistors must be activated or deactivated on the control panel (controller), only if a network with other unit groups is established through the CA bus or additional modules, such as a clock module or input and output modules. Activate terminating resistors at the beginning and end of the line (Fig. 7-4): Activate the DIP switch of both users (e.g. control panels, unit circuit boards or modules) by setting position to O. The line beginning and line end correspond to the start and end of the bus cable. The terminating resistors should also be switched on for stand-alone units. Module Module Module Control panel Line start Line end Fig. 7-4: Adjusting terminating resistors DIP switch Function 2 OFF OFF Terminating resistor switched off O O Terminating resistor switched on (default setting) OTE! With default settings the DIP switches are set to O/O and must be deactivated if used for an intermediate unit. PR GB Subject to modifications R5-/205 67

68 O O L L L L STP STP STP STP STP STP STP STP STV STV STV STV STV STV O Commissioning Multi Flair MATRIX Unit printed circuit boards of the MATRIX 3000 control system are equipped with terminating resistors. Activate terminating resistors at the beginning and end of the line (Fig. 7-5): Activate the DIP switch of both users (e.g. control panels, unit circuit boards or modules) by setting position to O. The line beginning and line end correspond to the start and end of the bus cable. The terminating resistors should also be switched on for stand-alone units. Control panel Unit circuit boards Module Module Module Control panel Line beginning Line end Fig. 7-5: Setting terminating resistors DIP switch Function 2 OFF OFF o terminating resistor O O Terminating resistor switched on (default setting) OTE! With default settings the DIP switches are set to O/O and must be deactivated if used for an intermediate unit. 68 PR GB Subject to modifications R5-/205

69 Multi Flair Commissioning 7.5 Setting address MATRIX The unit PCBs of the MATRIX 2000 control system are not fitted with address selection switches. The appropriate group address must be assigned on the control panel. Single group (without networking multiple unit groups) On the control panel, set the address to 0 (factory default setting). etworking multiple groups On the control panel, set the addresses 0-5. Each group is assigned its own address. The labels A to F correspond to the addresses 0 to 5. OTE! Assigning duplicate addresses on the control panels causes malfunctions. The default setting for the group address switch is 0 and must be changed, if necessary. Group addresses: O 0 Group 0 8 Group 8 Group 9 Group 9 2 Group 2 A Group 0 3 Group 3 B Group 4 Group 4 C Group 2 5 Group 5 D Group 3 6 Group 6 E Group 4 7 Group 7 F Group Fig. 7-6: Setting the address on the control panel Pos. : Control panel group 0 (address 0) Pos. 2: Control panel group (address ) Pos. 3: Control panel group 2 (address 2) and so on... PR GB Subject to modifications R5-/205 69

70 Commissioning Multi Flair MATRIX The appropriate group address must be assigned on the control panel and the units of a group. Single group (without networking multiple unit groups) On the control panel, set the address to 0 (factory default setting). Set the address to 0 on the unit circuit board (factory default setting). etworking multiple groups On the control panels and all unit PCBs assigned to the individual groups - set the addresses to 0-5. Each group is assigned its own address. The labels A to F correspond to the addresses 0 to 5. OTE! Assigning duplicate addresses on the control panels causes malfunctions. The default setting for the group address switch is 0 and must be changed, if necessary. Control panel Unit circuit boards Group addresses: O 0 Group 0 8 Group 8 Group 9 Group 9 2 Group 2 A Group 0 3 Group 3 B Group 4 Group 4 C Group 2 5 Group 5 D Group 3 6 Group 6 E Group 4 7 Group 7 F Group Fig. 7-7: Setting address on the control panel Pos. : Control panel, Multi Flair group 0 (address 0) Pos. 2: Control panel, Multi Flair group (address ) Pos. 3: Control panel, Multi Flair group 2 (address 2), etc. 70 PR GB Subject to modifications R5-/205

71 Multi Flair Commissioning 7.6 Switch on unit HAZARDOUS VOLTAGE! The electrical control box is open. Direct interventions in the electrical control box are not permitted! Before completing work on the air treatment unit, ensure that the electrical control box is properly closed (refer to Electrical Connection on page 35). Apply mains supply voltage. The unit is switched on via the MATRIX control panel, control unit of 985 series or a controller by others. For instructions, refer to the operation manual enclosed with the relevant control panel. Switch the unit on using the control panel. Test the fan speeds. 2 Fig. 7-8: Switching the unit on using the control panel Pos. : Pos. 2: Control panel MATRIX OP44C Control panel MATRIX OP50C OTE! The position of the speed selection switch (only OP2XX/OP3XX/OP4XX) can be mechanically limited. The limitation should be set in such a way that the maximum adjustable fan speed corresponds to that of the unit. For details on the limitation, refer to the operation manual for the control panel. PR GB Subject to modifications R5-/205 7

72 Commissioning Multi Flair 7.7 Checking data connection HAZARDOUS VOLTAGE! Before correcting an error in the data connection, de-energise and isolate the entire system down. Ensure that the unit is isolated and secured against being energised at an appropriate point of the on-site power supply Checking control cables MATRIX The data/commands are communicated via control cables. Depending on the unit equipment, the cables must be connected or checked in accordance with the wiring diagram enclosed with the unit connection box (Connecting control cables on page 45). The yellow LED on the unit PCB signals active power supply to the electronics. If the LED is off, check the 230 V power supply on the unit Checking data connection MATRIX Data are communicated via a 2/4-wire data cable. This cable must be connected and/or checked in accordance with the wiring diagram attached to the unit connection box (see Completing bus connection on page 49). 3 LEDs on the unit printed circuit board signal the ready-to-operate status of the unit. LED Gre en Red LED status Operating status ACTIO On Power supply to electronics OK Off Power supply to electronics not OK Check 230 V power supply on unit On Operating system and control software have been started and are working properly Off Software or processor defective Replace PCB Yellow Power PCB down and wait for a short time. Power the PCB on. If the error message is still active, Continuously on Error in electronics replace the PCB. Flashes Data bus interruption Check the connection of the data cables and the setting of the terminating resistors on all units. Tab.: 7-: Operation status and remedy for faults in the data connection (MATRIX 3000) 72 PR GB Subject to modifications R5-/205

73 Multi Flair Commissioning 7.8 Checking control inputs and outputs The MATRIX 3000 control system is fitted with control inputs and outputs. When checking the control inputs and outputs consider that configuration is performed by the manufacturer. Refer to the unit wiring diagram (see inside cover of the unit connection box) for the relevant controller function. Possibly made changes in the configuration by others on site (via MATRIX.PDA service tool or MATRIX.PC service software) can not be considered here Function input MATRIX The input can be assigned with the following functions as required: Window contact Set the jumper on the input terminals. Turn the unit on and change the setpoint as required to activate the fan. Remove the jumper. The fan must switch off, the valves close (unit remains in frost protection monitoring mode). Economy operation Turn the unit on and change the setpoint as required to activate the fan. Couple input terminals. The fan must switch off, the valves close, Requirement: economy mode setpoint set accordingly (unit remains in frost protection mode) PR GB Subject to modifications R5-/205 73

74 Commissioning Multi Flair 7.9 Functions 7.9. Fan mode The behaviour of the fan control depends on the configured control type and operation mode on the selected control panel. The following fan modes can be set: Manual fan control Automatic fan control Automatic fan control in mute mode The fan switches off irrespective of the selected mode if one of the following errors has occurred: Motor thermal monitoring tripped Insufficient operating data due to sensor error Defective hardware Manual The fan is operated at the pre-set fan speed. The fan speed can be pre-set via the control panel, the building management system or via external modules (e.g. digital input module). Fan stages 3 2 Off Switching difference 00[%] Automatic The fan is regulated depending on the difference from the setpoint (temperature). In mute mode the highest fan speed is blocked. The fan speeds are controlled according to the difference between actual and setpoint readings. Both the size and the time of the existing deviation affect the control behaviour. The number of the available fan speeds depends on the unit type. Parameter: Speed number: speed stage fan Speed number: step fan (only MATRIX 2002) Air change function This function enables the fan to operate irrespective of the selected control mode and to remain switched on even if the setpoint temperature has been reached. The fan speed must be selected manually in this case. This should provide an optimal air change in the room. This function can only be selected using the MATRIX OP50 and MATRIX OP5 control panel or the MATRIX.PC service software. 74 PR GB Subject to modifications R5-/205

75 Multi Flair Commissioning Valves Depending on the selected controller equipment, the integrated valve controller supports valves with on/off control or modulating behaviour. The valves can be controlled in the following modes: Heating Cooling Heating or cooling In order to reach a common starting position the factory set synchronisation moves all connected valves (only with modulating control) every 24 hours to OPE or CLOSE position Condensate pump The condensate pump drains the condensate that forms on cooling units. If required, the condensate pump is switched on by a float switch. When a limit value is exceeded, the fan is switched off, and an error message is displayed on the control panel Standby mode Standby temperatures mode is only available with room temperature control option. This does not regulate the temperature to a fixed setpoint, but instead to a pre-set setpoint range. This setpoint range can only be changed using the MATRIX.PC service software. The stand by mode is active if a room temperature sensor is connected but no room temperature setpoint, i.e. no control panel, is available (e.g. during the construction phase to dry out the building). The standby mode function is terminated if specific room temperature setpoint is set Indoor anti-freeze protection This function ensures a frost-free condition when the unit is switched off. At room temperatures < 4 C, the valve is fully opened and the fan is switched at the lowest fan speed, regardless of the inlet temperature. If room temperatures reaches > 6 C, the valve is closed and fan deactivated. ormal regulation mode is activated. PR GB Subject to modifications R5-/205 75

76 Commissioning Multi Flair Summer / winter compensation This function requires to connect an external sensor. End Temperature Temp. Offset Start Temperature End Temperature This function enables a shift in the room temperature setpoint depending on the ambient temperature. Application example: From 26 C outdoor temperature and on, indoor temperature setpoint must be increased by 0.5 C per C rise of outdoor temperature. The setpoint should not be increased any further if outside air temperature reaches 32 C. Thus 26 C as the start temperature and 32 C as the end temperature should be entered. The setpoint offset is calculated as follows: (End temperature - start temperature) * 0.5 C (the increase per C external temperature increase) (32-26) * 0.5 = 6 * 0.5 = 3 The factory set parameters can only be changed via the MATRIX.PC service software Filter replacement indication This function calculates the filter contamination level using the operation times of the respective fan speeds. The necessary filter replacement message is displayed and entered as a warning only on the MATRIX OP50 or MATRIX OP5 control panel. The filter change message is activated after "service period" or "minimum service interval" is exceeded. Confirmation of the warning is followed by the new calculation of the remaining service period. Upon successful filter replacement the internal run timer counter is reset using the menu selection on the control panel. 76 PR GB Subject to modifications R5-/205

77 Multi Flair Maintenance and Troubleshooting 8 Maintenance and Troubleshooting OTE! Maintenance must only be performed by qualified licensed staff in observance of the given operation manual and current regulations. BEWARE OF RISK OF ROTATIG UIT PART! The rotating fan wheel poses a risk of injury! Before performing any work on the unit, ensure that it is isolated. Ensure that the unit is secured against being energised at an appropriate point of the onsite power supply. DAGER OF SCALDIG! Prior to all jobs on the Multi Flair: Seal off the heating medium inlet before performing work on the valves or the inlet or outlet pipes and secure this sealing from being opened unintentionally. Do not commence work before the heating medium has cooled down. HAZARDOUS VOLTAGE! Power the unit down before carrying out any kind of work that involves removing of covers. Ensure that the unit is isolated and secured against being energised at an appropriate point of the on-site power supply. 8. Maintenance Multi Flair is a high-quality and reliable unit heater. To guarantee the durability and trouble-free performance of the unit, regular maintenance and inspection by qualified staff is required. OTE! The manufacturer s warranty will be invalidated if unit damage is attributed to the failure in completing regular maintenance and inspections. PR GB Subject to modifications R5-/205 77

78 Maintenance and Troubleshooting Multi Flair List of regular maintenance procedures The following maintenance tasks must be performed at the indicated time intervals. Maintenance interval Components Quarterly Half-yearly Annually Before cooling period Checking filter Cleaning heat exchanger* Checking screw connections of medium lines ** Checking electrical connections Checking earthing Air venting heat exchanger ** Checking condensate drain and cleaning condensate sump pit ** Checking condensate pump ** x x * Clean and remove objects, if required ** Depends on the model Tab. 8-: Regular maintenance x x x x x x x 78 PR GB Subject to modifications R5-/205

79 Multi Flair Maintenance and Troubleshooting 8.2 Quarterly maintenance 8.2. Cleaning or replacing filters To clean or replace filters as depicted in Fig. 8- proceed as follows: Open the rotary locks and remove the filter cover panel. Pull out the filter cassette. Replace or clean the filter mat. Clean filter material in lukewarm water using mild detergents. OTE! Do not use solvents/thinners when cleaning filter. The best results can only be achieved by inserting a new filter element. Using order numbers to 30 to order a replacement filter set (2 pieces). Insert the filter cassette so that its transversal wire brackets face upwards. Lock the filter cover panel. Pos. : Pos. 2: Open the filter cover panel Transversal wire brackets of the filter cassette must face upwards. 2 Fig. 8-: Removing filter, cleaning and replacing filter PR GB Subject to modifications R5-/205 79

80 Maintenance and Troubleshooting Multi Flair 8.3 Annual maintenance 8.3. Cleaning heat exchanger Loosen screws of the motor. Hang the motor on the metal sheet lug placed on the side. Hang the outer wire ring of the protective cage into the slot of the guide rail in the depicted location (Pos. ) (applies to units with filter only). The motor cable must not disconnected for this task. Fig. 8-2: Dismounting fan Check the heat exchanger for dirt and contamination. If required, ensure that the heat exchanger is properly cleaned from the inside (e.g. through vacuum cleaning). ATTETIO! Do not bend or damage heat exchanger fins when cleaning Check screw connections of medium lines Check all screwed pipework and coil connections for tight seat. Manually check the mounting of valve actuators Checking condensate pump Check condensate pump as specified in Chapter 7.3 page Checking electrical connections and earthing HAZARDOUS VOLTAGE! Before completing the following tasks, ensure that the unit is isolated and secured against being energised at an appropriate point of the on-site power supply. Before completing work on the air treatment unit, ensure that the electrical control box is properly closed (refer to Chapter 6.2). 80 PR GB Subject to modifications R5-/205

81 Multi Flair Maintenance and Troubleshooting Open the terminal box or the electrical control box. Check that all electrical connections are securely seated in the terminal strips. Check for correct earthing of the unit with an appropriate measuring device. Close the terminal box or the electrical control box Air venting heat exchanger Air vent the heat exchanger as specified in Chapter 7.2 page Cleaning coil drip tray and condensate sump pit Clean the coil drip tray. Check and clean the drain fitting of the main drip tray, if required. For this purpose the drainage pipework, sump pit cover and non-return valve must be cleaned. Loosen the screw (Pos. 2). Fold the condensate sump pit cover to the bottom (Pos. 3). Clean the condensate sump pit cover. Properly close the condensate sump pit cover. For unit without a condensate pump loosen the condensate main pipework (Pos. ). Pos. : Pos. 2: Pos. 3: Condensate main pipework Screw Condensate sump pit cover Fig. 8-3: Cleaning condensate sump pit 2 3 PR GB Subject to modifications R5-/205 8

82 Maintenance and Troubleshooting Multi Flair 8.4 Before cooling period 8.4. Checking condensate pump Check condensate pump as specified in Chapter 7.3 page Retrofitting filter assembly 2 3 Pos. : Pos. 2: Pos. 3: Pos. 4: Pos. 5: Pos. 6: Filter cassette with filter mat Transversal wire bracket (wire bracket faces unit side) 2 guide rails 4 wing screws Rivet nut 2 filter cover panels Fig. 8-4: Filter assembly The filter assembly is mounted on the unit bottom side: Screw on the guide rails to the unit bottom side (holes are pre-fabricated, sheet-metal screws 4.8 x 9.5 mm are supplied). Insert the filter mat and wire bracket facing the unit internal side. Insert the wing screws through the filter cover panel. Secure the filter cover panel by turning the wing nuts into rivet nuts. Fig. 8-5: Mounting guide rail 82 PR GB Subject to modifications R5-/205

83 Multi Flair Maintenance and Troubleshooting 8.6 Operating faults Deviations from normal operating conditions of fan coil units are evidence of malfunctions that must be investigated by maintenance personnel. The following table should serve as a starting point for maintenance personnel regarding possible causes of malfunctions and their remedy. Symptom Possible causes Remedy Fan fails to start Unit not switched on Switch on unit o electrical voltage Check fuse/circuit breaker/ power supply (technical personnel only) Electrical cables not connected Connect electrical cables (technical personnel only) Faulty unit fuses Replace fuses (technical personnel only) Controller switched off fan on reaching room temperature Refer to operation manual MATRIX control panels or control panel or control unit of 985 series Unit too noisy Unit running at too high RPM Set a lower RPM Air intake or discharge areas blocked Clear discharge/air intake of obstructions or bends oisy fan bearings Replace faulty fan (technical personnel only) Filter is dirty Clean/replace filter Unit does not heat/heats Fan not switched on Switch on fan insufficiently Air flow rate of unit too low Select higher speed Air intake or discharge areas blocked Clear or clean ducts Fan blocked/faulty Check fan, replace is necessary (technical personnel only) Filter is dirty Clean/replace filter Heating medium is not hot Switch on the heating system (boiler) Switch on the circulating pump Unit air venting Water flow rate too low Check pump performance (technical personnel only) Check pipe run balance and adjust using calculated pressure drop (technical personnel only) Selected temperature setpoint of control panel/thermostat too low Use control panel to increase temperature setpoint PR GB Subject to modifications R5-/205 83

84 Maintenance and Troubleshooting Multi Flair Symptom Possible causes Remedy Unit does not heat/heats insufficiently Unit does not cool/cools insufficiently Water leakage around unit Control panel/thermostat or sensor is located above a heat source or exposed to direct sun rays Control valve fails to open Fan not switched on Air flow rate of unit too low Air intake or discharge areas blocked Fan blocked/faulty Filter is dirty Cooling medium is not cold Water flow rate too low Selected temperature setpoint of control panel/thermostat too high Control panel/thermostat or sensor is fitted in cold air flow, e.g. adjacent to door Control valve fails to open Drain/outlet of main condensate tray is clogged Drain pipework of condensate sump is clogged Chilled water lines not (correctly) insulated Unit not positioned horizontally Fit control panel/thermostat or sensor in proper location (technical personnel only) Replace faulty control valve (technical personnel only) Switch on fan Select higher speed Clear or clean ducts Check fan, replace if necessary (technical personnel only) also refer to Fan does not work page 83 Clean or replace filter Switch on chiller unit Switch on the circulating pump Unit air venting Check pump performance (technical personnel only) Check pipe run balance and adjust using calculated pressure drop (technical personnel only) Use control panel to decrease temperature setpoint Fit control panel/thermostat or sensor in proper location (technical personnel only) Replace faulty control valve (technical personnel only) Clean main condensate tray and condensate drain Clean condensate sump (technical personnel, if required) Insulate chilled water lines (technical personal, if required) Align the unit and position it horizontally (technical personnel only) If necessary, re-tighten connections, clean screw insert or reseal connections 84 PR GB Subject to modifications R5-/205

85 Multi Flair Maintenance and Troubleshooting Symptom Possible causes Remedy Water leakage around unit Controller switches on continuously Condensate pump Fan fails to run Red LED of the control panel is flashing: Flash codes: = TC fault = Condensate pump fault Leaking heat exchanger or hydraulic connections Control panel/thermostat or sensor fitted in the improper location (e.g. adjacent to open door, window or discharge grille) Heating medium temperature too high/ low Cooling medium temperature too high/ too low Other heating elements with individual control are in the same pipe run (e.g. radiators with thermostat valves) Thermal contact (TC) of fan motor and/ or alarm contact of humidity sensor of condensate pump activated Fan was switched off Power electronics/controller and/or fan faulty T630 ma fuse is faulty Condensate pump coil faulty Check heat exchanger, vent and valve connections for leak-free state On valves, check screw connections for ease of movement, clean sealing surfaces and replace seal if necessary (technical personnel only) Check soldered joints between collector and heat exchanger tubes and on heat exchanger deflection bends for leaks; if this case, replace heat exchanger (technical personnel only) Fit control panel/thermostat or sensor in proper location where room temperature can be measured representatively (only technical personnel only) Correct the external temperature curve on the controller of the boiler system. Check the control mode and adjust accordingly (technical personnel only) Correct the inlet temperature on the controller of the refrigeration system. Check the control mode and adjust accordingly (technical personnel only) Separate medium supply if necessary. Check the control mode and adjust accordingly (technical personnel only) Check thermal contact of fan motor (through connection). Replace power electronics/controller and/or fan motor (technical personnel only) Replace fuse (technical personnel only) Replace condensate pump (technical personnel only) Water leakage near unit; no fault reported. Water leakage around unit, pump is activated almost permanently T630 ma fuse is faulty Delivery head of pump is too high Pressure-side pump hose clogged Replace fuse (technical personnel only) Reduce delivery head Clean or replace hose PR GB Subject to modifications R5-/205 85

86 Maintenance and Troubleshooting Multi Flair Symptom Possible causes Remedy Condensate pump does not run Pump thermal contact is faulty Pump coil is faulty Wiring became loose Tab. 8-2: Causes of malfunctions and remedies Replace pump (technical personnel only) Replace pump (technical personnel only) Reconnect the wiring (technical personnel only) Excessive pump noise Pump not sucking in any condensate Replace pump (technical personnel only) Pump run time too short; too little condensate sucked in Excessive noise (vibration) of unit and pump assembly Pressure hose not properly attached (possible structure-borne noise) Pump mounting loose Thermal contact switches off pump due to overheating Pump mounting loose Pump sucks in air Unit mounting position not level Connect mountings and hoses properly; prevent structure-borne noise Re-tighten pump mounting Replace pump (technical personnel only) Re-tighten pump mounting Position pump suction hose properly; clean if necessary Align unit level If the malfunction cannot be eliminated by the maintenance personnel, please consult our authorized service department. 86 PR GB Subject to modifications R5-/205

87 Multi Flair EC Declaration of Conformity pursuant to Directive 2006/42/EC of the European Parliament and of the Council (original EC Declaration of Conformity) Manufacturer: DencoHappel CZ a.s., Slovanská 78, Liberec XXV - Vesec, Czech Republic, ID o.: Entity authorized to compile technical documentation: DencoHappel CZ a.s., Slovanská 78, Liberec XXV - Vesec, Czech Republic, ID o.: Description and identification of machinery: Unit heater Multi Flair type designation Mxxx.xxxxx.xxx Multi Flair air-conditioning units including accessories serve for the heating, ventilation, cooling and filtering of indoor air. They are installed in industrial, warehouse, retail and exhibition premises. Declaration: The machinery complies with all relevant provisions of Directives 2006/42/EC, 2006/95/EC and 2004/08/EC. List of harmonized standards applied in the conformity assessment: E ISO 200:20, E 953+A:2009, E ISO 3857:2008, E ISO 202:200, E ISO 3746:20 This declaration relates exclusively to the machinery in the state in which it was placed on the market, and excludes components which are added and/or operations carried out subsequently by the final user. Issued in: Liberec On: ame: Title: Ing. Jiří Doubrava Director of joint-stock company Signed: Year of manufacture: PR GB Subject to modifications R5-/205 87

88 DencoHappel is a global company with expertise in air treatment, air conditioning and air filtration. Our nearest sales and service teams will be glad to discuss ideas and develop creative and effective solutions with you. R5-/205 PR GB

OPERATION MANUAL Air Curtains MultiMAXX HT. Air Curtains for Industrial Application

OPERATION MANUAL Air Curtains MultiMAXX HT. Air Curtains for Industrial Application OPERATION MANUAL Air Curtains MultiMAXX HT Air Curtains for Industrial Application DencoHappel Product Range MultiMAXX HT DencoHappel Product Range 2 PR-2011-0144-GB Subject to modifications R2-04/2016

More information

MultiMAXX HN OPERATION MANUAL

MultiMAXX HN OPERATION MANUAL MultiMAXX HN OPERATION MANUAL FläktGroup product range MultiMAXX HN FläktGroup product range 2 FläktGroup DC-2011-0143-GB 2018-05/R4 Subject to modifications MultiMAXX HN Unit Type Code Unit Type Code

More information

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4 Installation Operation Maintenance Ductable water unit FWD 08-12 - 20-30 - 45 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice

More information

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59 SOUND-INSULATED FAN OPERATION MANUAL _v.1(2)-en.indd 1 10.08.2015 15:20:59 CONTENT Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 3 Fan design 4 Delivery

More information

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING USER S MANUAL VCU/ Series CENTRIFUGAL FAN IN SCROLL CASING 2 CONTENTS Introduction Use Delivery set Designation key Technical data Safety requirements Design and operating logic Mounting and set-up Connection

More information

CENTRIFUGAL FAN IN SCROLL CASING. Helix S-Vent OPERATION MANUAL

CENTRIFUGAL FAN IN SCROLL CASING. Helix S-Vent OPERATION MANUAL CENTRIFUGAL FAN IN SCROLL CASING Helix S-Vent EN OPERATION MANUAL Helix / S-Vent www.blaubergventilatoren.de CONTENTS CONTENTS 3 Introduction 3 Use 3 Delivery set 4 Technical data 10 Safety requirements

More information

HEAT RECOVERY AIR HANDLING UNIT

HEAT RECOVERY AIR HANDLING UNIT HEAT RECOVERY AIR HANDLING UNIT OPERATION MANUAL KOMFORT_L v2(2)_en.indd 1 07.08.2015 15:0:44 CONTENTS Introduction General Safety regulations Transportation and storage regulations Manufacturer's warranty

More information

USER S MANUAL. Heat Recovery Ventilator. Vents Brig HRV 200 Vents Brig HRV 300

USER S MANUAL. Heat Recovery Ventilator. Vents Brig HRV 200 Vents Brig HRV 300 USER S MANUAL Heat Recovery Ventilator Vents Brig HRV 200 Vents Brig HRV 300 2 Brig HRV 200 (300) CONTENT Introduction... 3 Application... 3 Delivery set... 3 Unit designation key... 4 Basic unit dimensions...

More information

USER S MANUAL. VKP Series INLINE FAN

USER S MANUAL. VKP Series INLINE FAN USER S MANUAL Series INLINE FAN 2 CONTENTS Safety requirements 3 Introduction 5 Use 5 Delivery set 5 Designation key 5 Technical data 5 Design and operating logic 8 Mounting and set-up 8 Connection to

More information

CASSETTE UNIT. Comfort Circle

CASSETTE UNIT. Comfort Circle CASSETTE UNIT Comfort Circle Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient climate system to heat or cool

More information

FSW300 Series Flow Switch

FSW300 Series Flow Switch . FSW300 Series Flow Switch - 2 - Series FSW300 Series FSW300 Table of contents page 0 About this operating manual... 4 1 Device description... 5 1.1 Intended use... 5 1.1.1 Reed contact - Switching of

More information

USER S MANUAL. Heat (Energy) Recovery Ventilator. Vents Frigate HRV 120 S Vents Frigate ERV 120 S

USER S MANUAL. Heat (Energy) Recovery Ventilator. Vents Frigate HRV 120 S Vents Frigate ERV 120 S USER S MANUAL Heat (Energy) Recovery Ventilator Vents Frigate HRV 120 S Vents Frigate ERV 120 S 2 Frigate HRV(ERV) 120 S CONTENT Introduction... 3 Application... 3 Delivery set... 3 Unit designation key...

More information

Decentralised ventilation units

Decentralised ventilation units Notes on installation Decentralised ventilation units FSL / SCHOOLAIR GB/en TROX GmbH Heinrich-Trox-Platz 47504 Neukirchen-Vluyn Germany Phone: +49 (0) 2845 2020 Fax: +49 (0) 2845 202265 E-mail: trox@trox.de

More information

Operating instructions

Operating instructions ebm-papst Mulfingen GmbH & Co. KG Bachmühle D-74673 Mulfingen Phone +49 (0) 793-0 Fax +49 (0) 793-0 info@de.ebmpapst.com www.ebmpapst.com CONTENTS. SAFETY REGULATIONS AND NOTES. Levels of hazard warnings.

More information

We have some on stock... GEA MultiMAXX Prompt. Unit Heaters Data & Facts. GEA Heat Exchangers / HVAC Systems

We have some on stock... GEA MultiMAXX Prompt. Unit Heaters Data & Facts. GEA Heat Exchangers / HVAC Systems We have some on stock... GEA MultiMAXX Prompt Unit Heaters Data & Facts GEA Heat Exchangers / HVAC Systems Short Description/Overview of Capacity Quick solution for heating of industrial halls For more

More information

Installation Instructions

Installation Instructions 40MBFQ Floor Console Ductless System Sizes 09 to 12 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 DIMENSIONS... 5 CLEARANCES... 5

More information

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use!

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use! Mess-, Regel- und Überwachungsgeräte für Haustechnik, Industrie und Umweltschutz Lindenstraße 20 74363 Güglingen Telefon +49 7135-102-0 Service +49 7135-102-211 Telefax +49 7135-102-147 info@afriso.de

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance DUCTABLE WATER UNIT FWD 08-12 - 20-30 - 45 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice

More information

INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL

INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL CONTENT 3 Introduction 3 General 3 Safety rules 3 Storage and transportation rules 3 Manufacturer s warranty 4 Fan design 4 Delivery set 5 Technical data

More information

LS Condensate Removal Pump INSTRUCTION MANUAL REVISION A

LS Condensate Removal Pump INSTRUCTION MANUAL REVISION A LS Condensate Removal Pump INSTRUCTION MANUAL 6-71-075-115 REVISION A CAUTION: Combustible liquids may not be pumped! The condensate pump may not be run dry, as this can destroy the bearings in a very

More information

Installation Instructions

Installation Instructions 40MAQ High Wall Ductless Split System Sizes 09 to 36 Installation Instructions NOTE: Read the entire instruction manual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS

More information

Installation Instructions

Installation Instructions 40MBFQ Floor Console Ductless System Sizes 09 to 58 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING... 4 DIMENSIONS... 5 CLEARANCES...

More information

3-way switching valve

3-way switching valve Operating Manual UK 3-way switching valve for domestic hot water charging USV 1" AG USV 5/4" AG USV 6/4" IG UK805189 / 201109 Translation of the original instruction manual Please read first This operating

More information

User Manual GV25 GV35 GV702. Company information: Original instructions GV12066 (1)

User Manual GV25 GV35 GV702. Company information:   Original instructions GV12066 (1) User Manual Original instructions GV25 GV35 GV702 Company information: www.vipercleaning.eu info-eu@vipercleaning.com GV12066 (1) 2012-04-10 USER MANUAL ENGLISH TABLE OF CONTENTS Introduction... 4 Manual

More information

F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS

F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS Contents Page User instructions 3-5 General 3 Fan installation 3-4 Maintenance 3 Electrical installation 5 Troubleshooting 5 Technical description 6-8 General

More information

Installer manual AG-WL10

Installer manual AG-WL10 LEK LED CLEAN TIMER OPERATION Installer manual Indoor unit air/air heat pump IHB GB 1637-1 331827 Table of Contents 1 Important information Safety information Read before starting the installation Electrical

More information

Technology for life. Unit heater LH

Technology for life. Unit heater LH Technology for life. Unit heater 1 2 Contents Contents... Page Basic unit: casing, fan, motors... 4 Basic unit: heat exchanger... 5 Performance tables 25...6-7 Performance tables 40...8-9 Performance tables

More information

CRU-S Series Stainless Steel Condensate Recovery Unit

CRU-S Series Stainless Steel Condensate Recovery Unit IM-UK-CRU-S UK Issue 1 CRU-S Series Stainless Steel Condensate Recovery Unit 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Storage, shutdown and equipment protection

More information

Installation Instructions

Installation Instructions 53DS --- 900 --- --- --- 092 Duct---Free Systems Accessory Power Ventilation Kit for In --- Ceiling Cassette Fan Coil Units Size 018 --- 036 Installation Instructions NOTE: Read and become familiar with

More information

HEAT RECOVERY VENTILATOR

HEAT RECOVERY VENTILATOR HEAT RECOVERY VENTILATOR HRV H 00 ERV H 00 HRV H 300 ERV H 300 EN OPERATION MANUAL HRV /ERV H 00(300) www.blaubergventilatoren.de CONTENTS Application... Delivery set...3 Unit designation key...3 Basic

More information

SUPPLEMENT TO OPERATION MANUAL Modular Air Handling Units CAIRplus ECOTWINcool

SUPPLEMENT TO OPERATION MANUAL Modular Air Handling Units CAIRplus ECOTWINcool SUPPLEMENT TO OPERATION MANUAL Modular Air Handling Units CAIRplus ECOTWINcool Table of Contents Overview of units and packaged content... 3 Adiabatic cooling... 3 Design features... 4 Fan arrangement...

More information

TopVent Design Handbook

TopVent Design Handbook TopVent Design Handbook Recirculation Units and Supply Air Units for Heating and Cooling High Spaces TopVent Content TopVent DHV Recirculation unit for heating high spaces TopVent NHV Recirculation unit

More information

BHW INSTALLATION, OPERATION AND MAINTENANCE MANUAL MEDIUM STATIC PRESSURE DUCTABLE TYPE. Models:

BHW INSTALLATION, OPERATION AND MAINTENANCE MANUAL MEDIUM STATIC PRESSURE DUCTABLE TYPE. Models: INSTALLATION, OPERATION AND MAINTENANCE MANUAL BHW MEDIUM STATIC PRESSURE DUCTABLE TYPE Models: 174 205 358 410 515 720 724 Cooling capacities from 3,1 to 25 KW Heating capacities from 4,5 to 55,5 KW Thank

More information

Installation instructions and operating manual. Sauna control system FCU1000 / FCU1200

Installation instructions and operating manual. Sauna control system FCU1000 / FCU1200 Series FCU1x00 Installation instructions and operating manual Sauna control system FCU1000 / FCU1200 only sauna FCU1000 additional humidity FCU1200 Doc-ID: B_M_FCU1xxx-A5_EN Version: V 1.06 certificated

More information

LS Condensate Removal Pump Installation, Operation and Service Instructions

LS Condensate Removal Pump Installation, Operation and Service Instructions Bell & Gossett Instruction Manual 6-71-075-115 LS Condensate Removal Pump Installation, Operation and Service Instructions INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. WARNING: This safety

More information

Operating instructions Electric agitator RE80Ex. T-Dok-520-GB-Rev.5 Article no Translation of the original operating instructions

Operating instructions Electric agitator RE80Ex. T-Dok-520-GB-Rev.5 Article no Translation of the original operating instructions GB Operating instructions Electric agitator RE80Ex T-Dok-520-GB-Rev.5 Article no. 200-0332 Translation of the original operating instructions Thank you for selecting a Krautzberger product. This product

More information

Instruction manual. Submersible sump pump. Safety instructions Application Electrical connection Installation Maintenance Technical data

Instruction manual. Submersible sump pump. Safety instructions Application Electrical connection Installation Maintenance Technical data Instruction manual Submersible sump pump Safety instructions Application Electrical connection Installation Maintenance Technical data U 3 K /2 U 3 KS /2 U 3 K spezial /2 U 3 KS spezial /2 U 5 K /0 U 5

More information

TIH 300 S / TIH 400 S / TIH 500 S / TIH 700 S / TIH 900 S / TIH 1100 S

TIH 300 S / TIH 400 S / TIH 500 S / TIH 700 S / TIH 900 S / TIH 1100 S TIH 300 S / TIH 400 S / TIH 500 S / TIH 700 S / TIH 900 S / TIH 1100 S EN OPERATING MANUAL INFRARED HEATING PANEL TRT-BA-TIH300S-TIH400S-TIH500S-TIH700S-TIH900S-TIH1100S-TC-002-EN Table of contents Notes

More information

HT V2 HT Split

HT V2 HT Split Scroll compressor Refrigerant R07C Aqu@Scop HT V Aqu@Scop HT Split High Temperature Air-to-Water Heat Pumps Models -, -7 and 8-9.0 to 7.9kW Aqu@Scop HT V / Aqu@Scop HT Split Installation examples - Single

More information

Comfort Ceiling Fan Coil System INDULVENT ec. Draught-free ambient air distribution with cooling capacity up to 2600 W

Comfort Ceiling Fan Coil System INDULVENT ec. Draught-free ambient air distribution with cooling capacity up to 2600 W Comfort Ceiling Fan Coil System INDULVENT ec NEW Draught-free ambient air distribution with cooling capacity up to 2600 W Low sound power levels Only electrical, cooling water and condensate connections

More information

HEATING AND COOLING DEVICE AGC

HEATING AND COOLING DEVICE AGC GDYNIA HEATING AND COOLING DEVICE - AGC 2013 1/8 HEATING AND COOLING DEVICE AGC SERVICE phone.: (+48 58) 783 99 50/51 Fax: (+48 58) 783 98 88 mobile: (+48) 510 098 081 E-mail: serwis@klimor.pl GDYNIA,

More information

1-WAY CEILING CASSETTE FAN COIL UNIT

1-WAY CEILING CASSETTE FAN COIL UNIT 1-WAY CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MH1WC4W One way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and service must

More information

Topvex SR 09, 11, Topvex TR Compact Air Handling Units

Topvex SR 09, 11, Topvex TR Compact Air Handling Units Topvex SR 09, 11, Topvex TR 09-15 Compact Air Handling Units Installation instructions Document in original language 125593 A003 GB Copyright Systemair AB All rights reserved E&OE Systemair AB reserves

More information

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT Carrier International Sdn. Bhd. Malaysia INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT 40LM 120-200 50Hz CONTENTS: Physical Data & Dimension 1-3 Safety Considerations 4 Rigging

More information

CWX 3 - CWX 5 CASSETTE TYPE TERMINAL UNIT. Cooling

CWX 3 - CWX 5 CASSETTE TYPE TERMINAL UNIT. Cooling TECHNICAL INSTRUCTIONS CWX 3 - CWX 5 CASSETTE TYPE TERMINAL UNIT Cooling Heating CWX 3 pipes.60 3.9 pipes + electric heating.08.96 +.5 pipes.08.5 CWX 5 pipes.70 5.70 pipes + electric heating.3 5.3 +.50

More information

INSTRUCTION MANUAL HETO CBN 8 / 18 / C Cooling Baths ID: IM.doc Revision 1

INSTRUCTION MANUAL HETO CBN 8 / 18 / C Cooling Baths ID: IM.doc Revision 1 Revision 1 INSTRUCTION MANUAL HETO CBN 8 / 18 / 28-30 - 30 C Cooling Baths ID: 88872215 Page 2 / 9 INSTRUCTION MANUAL CBN 8 / 18 / 28-30 Important user information Please read this entire manual to fully

More information

Original operating instructions Safety switch with guard locking AC901S AC902S

Original operating instructions Safety switch with guard locking AC901S AC902S Original operating instructions Safety switch with guard locking AC901S AC902S 7390914/03 01/2017 Contents 1 Preliminary note...4 1.1 Explanation of symbols...4 2 Safety instructions...4 3 Items supplied...5

More information

Installation Instructions

Installation Instructions 40MBD Ducted Style Ductless System Sizes 09 to 48 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2

More information

READ AND SAVE THESE INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS 2591830 EN 1710 READ AND SAVE THESE INSTRUCTIONS This manual must be read in conjunction with Nortec ME Control installation manual and operation manual! ADDENDUM MANUAL Adiabatic air humidification/air

More information

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50 -30 Installer manual Air/air heat pump -40/50 IHB GB 1516-1 331554 Table of Contents 1 Important information 2 5 Installation 7 Safety information 2 Model combinations 7 Read before starting the installation

More information

OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN.

OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN. INSTALLATION, OPERATION & SERVICE MANUAL FOR COOLER TYPES OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN. 1. Introduction This manual is a guide for the installation, maintenance

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

technical data Fan coil unit FWB small duct unit

technical data Fan coil unit FWB small duct unit technical data Fan coil unit FWB small duct unit TABLE OF CONTENTS FWB 1. Nomenclature ---------------------------------------------------------------------- 2 2. Features -----------------------------------------------------------------------------

More information

Installation instructions. For the heating engineer. Installation instructions. timeswitch VTS 160 GB, IE

Installation instructions. For the heating engineer. Installation instructions. timeswitch VTS 160 GB, IE Installation instructions For the heating engineer Installation instructions timeswitch VTS 160 GB, IE Table of contents Table of contents 1 Notes on the installation instructions...4 1.1 Observing other

More information

Branching and Connection Box AAB. Operating manual AAB EN11. GTE Industrieelektronik GmbH

Branching and Connection Box AAB. Operating manual AAB EN11. GTE Industrieelektronik GmbH AAB 430-2410-001 EN11 EN Operating manual Branching and Connection Box AAB GTE Industrieelektronik GmbH Helmholtzstr. 21, 38-40 D-41747 Viersen, GERMANY info@gte.de +49(0)2162 / 3703-0 www.gte.de Branching

More information

AIRGOCLEAN 10 E OPERATING MANUAL AIR CLEANER TRT-BA-AIRGOCLEAN10E-TC-001-EN

AIRGOCLEAN 10 E OPERATING MANUAL AIR CLEANER TRT-BA-AIRGOCLEAN10E-TC-001-EN AIRGOCLEAN 10 E EN OPERATING MANUAL AIR CLEANER TRT-BA-AIRGOCLEAN10E-TC-001-EN Table of contents Notes regarding the operating manual... 1 You can download the current version of the operating manual and

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

INLINE CENTRIFUGAL FAN. Centro-M OPERATION MANUAL

INLINE CENTRIFUGAL FAN. Centro-M OPERATION MANUAL INLINE CENTRIFUGAL FAN OPERATION MANUAL www.blaubergventilatoren.de CONTENT 3 Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 4 Fan design 4 Delivery

More information

Cassette units Model Comfort Circle. - heating - cooling - ventilation

Cassette units Model Comfort Circle. - heating - cooling - ventilation Cassette units Model Comfort Circle - heating - cooling - ventilation Cassette unit: Comfort Circle A comfortable room and climate are pleasant to work in and may also entice visitors to lengthen their

More information

This label warns for risk of electrical shock when failing to observe.

This label warns for risk of electrical shock when failing to observe. MANUAL horizontal centrifugal pumps MB series ic drive SB series mechanical seal 1. Introduction 2. Safety precautions 3. Receipt 4. Installation / Operation and Maintenance 4.1 Installation 4.2 Operation

More information

ST. KITTS CEILING FAN

ST. KITTS CEILING FAN ITEM #0845047 ST. KITTS CEILING FAN MODEL #40829 Questions, problems or missing parts? Before returning this item to your retailer, call our customer service department at 1-800-643-0067, Monday - Thursday,

More information

HKF 8180 Operating instructions

HKF 8180 Operating instructions Operating instructions EN Version 1.0en /Edition 05/2013 Contents 1 Important basic information... 3 1.1 Limitation of liability... 3 1.2 Operator's responsibilities... 3 1.3 Documentation... 3 1.3.1 Content

More information

OPERATING MANUAL. BAK Thermoplastic Welding Technology AG 1

OPERATING MANUAL. BAK Thermoplastic Welding Technology AG 1 OPERATING MANUAL BAK Thermoplastic Welding Technology AG 1 SAFETY Danger to life Unplug the tool before opening it as live components and connections are exposed. Danger of fire and explosion in case of

More information

Instruction Manual. Automatic fuel oil de-aerator SMART-FLO 3/K B100 COMPATIBLE

Instruction Manual. Automatic fuel oil de-aerator SMART-FLO 3/K B100 COMPATIBLE Sid Harvey s 605 Locust Street Garden City, NY 11530 Instruction Manual Automatic fuel oil de-aerator SMART-FLO 3/K Read manual before use! Observe all safety information! Keep manual for future use! 05.2015

More information

Supplement to operating and installation manual no for the VR 81 remote control unit

Supplement to operating and installation manual no for the VR 81 remote control unit Supplement to operating and installation manual no. 0020044392 for the VR 81 remote control unit The VR 81/2 remote control unit can be used together with the VRC 430/VRC 430f and VRC 470 compensator types.

More information

Installation and operating instructions. DK energy storage and DK energy buffer

Installation and operating instructions. DK energy storage and DK energy buffer Installation and operating instructions DK energy storage and DK energy buffer Edition: 08-2015 1 Preliminary note With this DK energy storage / DK energy buffer you purchased a DK quality product. The

More information

51AKS I S O OWNER S MANUAL

51AKS I S O OWNER S MANUAL LLOYD'S REGISTER QUALITY ASSURANCE 51AKS I S O 9 00 1 OWNER S MANUAL This manual applies to the following models Stand-alone Split 51AKS 085--- 51AKS 010--- 51AKS 185--- 51AKS 013--- 51AKS 113--- 51AKS

More information

Topvex SF02-SF12 Air Handling Unit

Topvex SF02-SF12 Air Handling Unit Topvex SF02-SF12 Air Handling Unit Installation instructions Document in original language 130324 A004 GB Copyright Systemair AB All rights reserved E&OE Systemair AB reserves the rights to alter their

More information

USER S MANUAL NKP. Duct heater for supply air pre-heating with external control

USER S MANUAL NKP. Duct heater for supply air pre-heating with external control USER S MANUAL Duct heater for supply air pre-heating with external control CONTENTS Contents... 2 Safety requirements... 2 Purpose... 4 Delivery set... 4 Designation key... 4 Technical data... 5 Design

More information

ELECTRIC BOILERS FOR CENTRAL HEATING

ELECTRIC BOILERS FOR CENTRAL HEATING ELECTRIC BOILERS FOR CENTRAL HEATING TermoMax INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS FOR INSTALLATION We reserve the right of alternations WE ARE NOT LIABLE FOR DAMAGES RESULTING FROM NON- OBSERVING

More information

USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES

USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES Bucket Fan 420 Bucket Fan 1055 Bucket Fan 1460 420 1055 1460 2 Bucket Fan CONTENT INTRODUCTION 3 USE 3 WHAT S INCLUDED IN THE BOX 3 DESIGNATION

More information

USER GUIDE. DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER -

USER GUIDE. DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER - USER GUIDE DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER - II CONTENTS 1. SYMBOLS AND WARNINGS... 5 2. GENERAL INFORMATION... 6 3. WARNINGS... 7 4. GENERAL DESCRIPTION... 8 5. INSTALLATION...

More information

Acquaer Ltd. H-4900, Fehérgyarmat, Szatmári út 11. CENTRIFUGAL PUMP Instruction Manual ACm60 / ACm75 / ACm150 / ACm150B2

Acquaer Ltd. H-4900, Fehérgyarmat, Szatmári út 11. CENTRIFUGAL PUMP Instruction Manual ACm60 / ACm75 / ACm150 / ACm150B2 CENTRIFUGAL PUMP Instruction Manual ACm60 / ACm75 / ACm150 / ACm150B2 Congratulations on your purchase of a LEO Centrifugal Pump It is important that you read, fully understand and observe the following

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP RV Products A Division of Airxcel, Inc. P.O. Box 4020 Wichita, KS 67204 1976-360 (1-02) PP TABLE OF CONTENTS 1. Warnings......................................................

More information

Read this manual through carefully before installing/using the cleaner, paying special attention to the SAFETY INSTRUCTIONS

Read this manual through carefully before installing/using the cleaner, paying special attention to the SAFETY INSTRUCTIONS PW1370TD 2 EN Read this manual through carefully before installing/using the cleaner, paying special attention to the SAFETY INSTRUCTIONS 3 E3 E1 C3 A1-A2-A3-A4 B4 B1 B5 B2 C1 B3 D 1 4 1 2 3 4 5 6 7 Ø13

More information

THE QUALITY BRAND IN FANS

THE QUALITY BRAND IN FANS THE QUALITY BRAND IN FANS CAUTION! DO NOT THROW AWAY THIS BOOK! READ ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLATION AND FAN OPERATION. Minor design changes or otherwise may result in slight variations

More information

52 BAYTOWNE CEILING FAN

52 BAYTOWNE CEILING FAN 52 BAYTOWNE CEILING FAN Owner s Manual Models #20501 If a problem cannot be remedied or you are experiencing difficulty in installation, please contact the Service Department: 1-877-459-3267, 9 a.m.- 5

More information

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

INSTALLATION, COMMISSIONING AND OPERATING MANUAL INSTALLATION, COMMISSIONING AND OPERATING MANUAL 1 YTBV-D-CE42_0109 CONTENT Available models and capacities Supplier information Warranty Safety Emergency stops/ shutdowns About this manual Models Physical

More information

FSA-Series Heavy-Duty Flat panel Emitter Architectural Electric Overhead Infrared Heaters

FSA-Series Heavy-Duty Flat panel Emitter Architectural Electric Overhead Infrared Heaters TPI Corporation P.O. Box 4973 Johnson City, TN 37602 www.tpicorp.com FSA-Series Heavy-Duty Flat panel Emitter Architectural Electric Overhead Infrared Heaters FSA-14 FSA-43 FSA-31 FSA-95 IMPORTANT SAFETY

More information

SELF-PRIMING JET PUMPS

SELF-PRIMING JET PUMPS SS Anti-Rust SS Shaft Copper & Cold-rolled SELF-PRIMING JET PUMPS CONTENTS 1. Applications.... Model Description.... Technical Data... 4. Implementation Standards... 5. Safety Precautions... 6. Product

More information

238 Series. Industrial/Commercial Electric Unit Heater. Owner s Manual

238 Series. Industrial/Commercial Electric Unit Heater. Owner s Manual 238 Series Industrial/Commercial Electric Unit Heater Owner s Manual This manual covers installation, operation and maintenance. Read carefully before attempting to install, operate or service the 238

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB -

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw CHGV 22 CHGV 2 CHGV 32 CHGV 40 PHRV heat pump model also available September 2007 10 12 11 - GB - 02

More information

EC Box Fan www.flaktwoods.com/oandm Safety, Installation, Operation and Maintenance Instructions CONTENTS Paragraphs Safety 1 Handling/Storage 2 Installation (Mechanical) 3 Fig. 1: Fig. 2: Tilt Mechanism

More information

Instruction Manual. Electronic gas and smoke detector GRM

Instruction Manual. Electronic gas and smoke detector GRM Mess-, Regel- und Überwachungsgeräte für Haustechnik, Industrie und Umweltschutz Lindenstraße 20 DE-74363 Güglingen Telefon +49(0)7135-102-0 Service +49(0)7135-102-211 Telefax +49(0)7135-102-147 E-Mail

More information

Katherm NE - Natural convection with electric heating element 2.45

Katherm NE - Natural convection with electric heating element 2.45 1.26 1.45 Katherm NE - Natural convection with electric heating element 2.45 Please retain this manual carefully for future use! Read carefully prior to commissioning! I 60/0/09/01 GB 2.45 Katherm NE -

More information

Air curtain.

Air curtain. Air curtain www.wingbyvts.com 01 VTS GROUP 1.1 VTS: Manufacturer No. 1 in the world 1.2 3 constituents of success 02 2.1 air curtains 2.2 Silence and power 2.3 Design and performance 2.4 Quality and design

More information

Minimalist Bottom Outlet Thermostatic Bar Shower. Telephone Product Specification

Minimalist Bottom Outlet Thermostatic Bar Shower. Telephone Product Specification Product Specification ~ Minimum Working Pressure 0.5 bar ~ Maximum Working Pressure 4.0 bar ~ Cold Water Supply Temp 4-20 c ~ Hot Water Supply Temp 55-85 c ~ Fixing Centres 150mm +/- 20mm ~ Outlet size

More information

SMHA Hatch High temperature fan HT-fan Installation and Maintenance

SMHA Hatch High temperature fan HT-fan Installation and Maintenance High temperature fan HT-fan Installation and Maintenance 22.8.2012 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

Optimal work climate with open doors. Industrial air curtains Model IndAC

Optimal work climate with open doors. Industrial air curtains Model IndAC Optimal work climate with open doors Industrial air curtains Model IndAC Industrial air curtain Optimal work climate During loading and unloading the door remains open, without the indoor climate being

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service,

More information

EKA EKA NI EKA NIS EKA NV EKA NV PH EKA NV PTC/PS

EKA EKA NI EKA NIS EKA NV EKA NV PH EKA NV PTC/PS ELECTRIC DUCT HEATERS EKA EKA NI EKA NIS EKA NV EKA NV PH EKA NV PTC/PS USER MANUAL Subject to technical modification EKA_P0093_AZ_0001 SAFETY INSTRUCTIONS AND PRECAUTIONS 3 WARNING! SAFETY REQUIREMENTS

More information

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to

More information

p Permanent magnet water cooled motors Additional manual

p Permanent magnet water cooled motors Additional manual p Permanent magnet water cooled motors Additional manual Safety Instructions 1 General General safety regulations, safety precautions and specific agreements made for each work site shown in this document

More information

KPSW CONSOLE TERMINAL UNIT

KPSW CONSOLE TERMINAL UNIT TECHNICAL INSTRUCTIONS KPSW CONSOLE TERMINAL UNIT Cooling Heating KPSW.40 kw.75 kw KPSW.9 kw 4.07 kw KPSW 4.60 kw 5.0 kw November 008 0 7 - GB - 0 MARKING This product marked conforms to the essential

More information

Operating Instructions. Accessory Units Melitta Cafina XT Series. Melitta Professional Coffee Solutions

Operating Instructions. Accessory Units Melitta Cafina XT Series. Melitta Professional Coffee Solutions Operating Instructions Accessory Units Melitta Cafina XT Series Melitta Professional Coffee Solutions Contents General... 4. Manufacturer information... 4.2 About these instructions... 4.3 Explanation

More information

DRYTEK 1 - User Manual ELECTRICAL PANEL FOR 1 MOTOR WITH POWER FACTOR CONTROL

DRYTEK 1 - User Manual ELECTRICAL PANEL FOR 1 MOTOR WITH POWER FACTOR CONTROL DRYTEK 1 - User Manual ELECTRICAL PANEL FOR 1 MOTOR WITH POWER FACTOR CONTROL CONTENTS 1. INTRODUCTION... 5 2. WARNINGS... 6 3. GENERAL DESCRIPTION... 7 4. INSTALLATION... 8 5. CONTROL PANEL... 9 5.1

More information

Pump WaterVISE, FloVISE

Pump WaterVISE, FloVISE General information It is important that this manual is read carefully by the user and the installer in order to ensure proper functioning and lifespan of the pump. Pahlen pumps are manufactured in accordance

More information

SUTTON 52 CEILING FAN

SUTTON 52 CEILING FAN SUTTON 52 CEILING FAN MODELS #50188, 50189, 50190 Español p. 19 Questions, problems, missing parts? Before returning to your retailer, call our customer service department at 1-877-361-3883, Monday - Thursday,

More information