Indoor Swimming Pools:

Size: px
Start display at page:

Download "Indoor Swimming Pools:"

Transcription

1 Indoor Swimming Pools: The Technologies 20 th November 2017 Amnon Holland BE Eng, M.AIRAH 1

2 Agenda The driver Code Compliance of Ventilation The Technologies - Heat exchange and heat recovery Smart BMS strategies: Variable speed control of fans and pumps The basics Afterhours pool hall temperature and humidity setback Condensation mitigation when pushing limits with setback Implementation Working with the BMS contractor 2

3 Code Compliance of Ventilation Large volumes of exhaust air are required when the facility is occupied Equals the amount of outdoor air must be introduced Highly energy intensive in cold climate like Canberra This + Filtration pumping is the main reason for high energy intensity in aquatic centres 3

4 Heat Exchange Technologies The opportunity Application 1 Pool Hall Summary of heating inputs: 0 C 28 C 28 C Heating from Boiler or Heatpump + Heat Recovery 27 C Heating from Boiler or Heatpump 4

5 Heat Exchange Technologies Pool Hall In Summer Natural ventilation (i.e. Motorised louvres or doors pool operators), Mechanical Extract or a Combination Heat wheels Switch off when ambient is close to inside Plate HEX/ Run-around coil bypass (or more simply Separate fan) High volumes of air to flush pool hall 35 C 30 C 30 C 27 C 5

6 Heat Exchange Technologies The opportunity Application 2 Entry Foyers & Amenities (Toilets) Must Air to Air plate type. Often can be an in ceiling unit. Select variable speed fans Exhaust Constant Volume Supply Can be ramped back 0 C 6 C 20 C 26 C Foyer Toilets 6

7 Heat Exchange Technologies The Ideal Scenario Full recirc (no outdoor air) No heating OA and minimal fan power High RH (reduce pool water and heat loss) Pool hall T is setback several degrees below water temperature (night) Pool water heating If Heatpumps Run during the day with warmer ambients, float the pool up to 0.5 C higher If Condensing boilers reset the flow temperature below 60 C afterhours (when high temps are likely not required), and float the pool 0.5 C higher Considerations Warm up, dry out period before patrons arrive 7

8 Heat Exchange Technologies 1: Air to Air Plate Heat Exchangers There are 3 main technologies, 2 commonly used Different manufacturers products Crossflow ~70% Peak Eff. Counterflow ~80% Peak Eff. Importance of Filters Cold climate considerations 8

9 Heat Exchange Technologies 1 Ctd. Considerations Size and bulk Co-located supply and exhaust ducts Heating source HW coil or HP Controls Always ensure all 4 airstreams have temp sensors very cheap Check BMS contractor has allowed for variable speed hardware (VFDs, pressure sensors not switches) Sensible vs Latent media 9

10 Heat Exchange Technologies 2: Rotary Heat Wheels Counterflow (80% Eff) in nature and cleanable Speeds, Install & Maintenance 0 C 22 C 6 C 28 C 10

11 Heat Exchange Technologies 3: Run around coils Rarely used Efficiency (between 45-70%) is highly dependant on water flow control More compact, and useful where the intake and exhaust air streams are apart More prone to corrosion/ degradation than HEX units with plastic cores in pool environments 11

12 Heat Exchanger Performance Verification Periodic measuring of performance is essential. 1. Measure airflows Exhaust should be 0-20% greater than Supply 2. Measure temperatures (TRA TOA)/(TRA-TSA) > 65% 12

13 Smart BMS Strategies Variable speed control of fans and pumps The basics first: Unecessary throttling (valves) Controls issues Pressure switches and sensors need to be suitable for new variable flow envelope Otherwise...system reliability Conservation of mass (airflow), cant just apply to one fan in isolation What minimum code ventilation rates need to be maintained during occupied times? In response to what? Zone temp or Humidity, but need checks 13

14 Smart BMS Strategies 14

15 Occupied Unoccupied Occupied Smart BMS Strategies 15

16 Smart BMS Strategies 16

17 Smart BMS Strategies System Lockout Door switches on external doors When opened for >10mins locks out LPHW Heating coil, fans still run Traffic lights on the BMS main screen (monitored by pool attendant) lights up Green = Okay, when ambient conditions are favorable 17

18 Smart BMS Strategies In-slab heating Control Generally controlled by running pump, with inlet temperature via mixing valve Most comfortable and energy form of heating, as heating is localised rather than heating all air. New pools needs insulation under pool apron slab Even though BCA does not cover. Control Weather compensation based Commissioning requires experimenting during start of heating season 18

19 Smart BMS Strategies Variable speed control of fans and pumps The basics first: Unecessary throttling (valves) Controls issues Pressure switches and sensors need to be suitable for new variable flow envelope Otherwise.. Conservation of mass (airflow), cant always apply to one fan in isolation. In response to what? Zone temp or Humidity, but need checks 19

20 Working with the Team Achieving objectives Include interactive workshops with BMS contractor early in the project before engineering is commenced. Attendees: FM/ Operation staff Mechanical maintenance contractor Clients key staff Technical Consultant Allow for a fixed amount of hours for tuning during DLP Clearly identify the expectations tuning required 20

21 Thank You Amnon Holland BE Eng, M.AIRAH, 21

An HVAC Audit of the Canberra Institute of Technology

An HVAC Audit of the Canberra Institute of Technology An HVAC Audit of the Canberra Institute of Technology 30 th November 2016 Amnon Holland amnon.holland@esbsconsult.com.au www.esbsconsult.com.au Agenda Overview CIT and various other sites The sites Type

More information

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery Steven T. Taylor, PE Principal Taylor Engineering This program is registered with the AIA/CES for continuing professional education.

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

DES CHAMPS PRODUCTS. Specializing in: -- Air-to-Air Energy Recovery -- Conditioning Outdoor Air -- Controlling IAQ -- Indirect Evaporative Cooling

DES CHAMPS PRODUCTS. Specializing in: -- Air-to-Air Energy Recovery -- Conditioning Outdoor Air -- Controlling IAQ -- Indirect Evaporative Cooling DES CHAMPS PRODUCTS Specializing in: -- Air-to-Air Energy Recovery -- Conditioning Outdoor Air -- Controlling IAQ -- Indirect Evaporative Cooling DES CHAMPS PRODUCTS Packaged Heat Recovery Systems Micro-Z

More information

Benefits Offered by Passive Dehumidification Wheel Speed Control

Benefits Offered by Passive Dehumidification Wheel Speed Control Benefits Offered by Passive Dehumidification Wheel Speed Control White paper By John Fischer Benefits Offered by Passive Dehumidification Wheel Speed Control The most significant advantage of the Pinnacle

More information

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc. System Components with ` Emphasis on Packaged Rooftop Application and Installation Jerry Cohen President Jacco & Assoc. Agenda Define and relate in practical terms the following components: System Effect

More information

TDSHS Air Change Requirements and the Basics of Psychrometrics. Presented by: Aric Murray December 06, 2013

TDSHS Air Change Requirements and the Basics of Psychrometrics. Presented by: Aric Murray December 06, 2013 TDSHS Air Change Requirements and the Basics of Psychrometrics Presented by: Aric Murray December 06, 2013 Agenda 1. What are the air change requirements and how do you calculate them? 2. Why are air change

More information

Energy Recovery with Cooling and Heating Model ERCH

Energy Recovery with Cooling and Heating Model ERCH Energy Recovery with Cooling and Heating Model ERCH 100% Outdoor Air System Dedicated Outdoor Air System 1,000-10,000 cfm 1.75 in. wg External Static Pressure Indirect Gas, Hot Water, Electric Heating,

More information

b.) Technical Information:

b.) Technical Information: Section VI- Strategies a.) Summary: It is important for new construction designers to consider the heating, ventilation, and air conditioning needs within a building. There are many different systems,

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma Objectives and Requirements For the Creative and Performing Arts High School (CAPA), the main objective of the mechanical design is to provide an energy efficient system that is easily maintainable and

More information

Standards and Guidelines. Presented by: Aric Murray December 12, 2014

Standards and Guidelines. Presented by: Aric Murray December 12, 2014 TDSHS Ventilation Standards and Guidelines Presented by: Aric Murray December 12, 2014 Agenda 1. What are the TDSHS ventilation 1. What are the TDSHS ventilation requirements? 2. Pressure relationships.

More information

Heat pump and energy recovery systems

Heat pump and energy recovery systems SBS5311 HVACR II http://ibse.hk/sbs5311/ Heat pump and energy recovery systems Ir. Dr. Sam C. M. Hui Faculty of Science and Technology E-mail: cmhui@vtc.edu.hk Oct 2017 Contents Basic concepts Air-to-air

More information

Heat Recovery Units. Heat Recovery 1

Heat Recovery Units. Heat Recovery 1 Heat Recovery Units Heat Recovery 1 Heat Recovery Unit Why? A heat recovery unit (HRU) can help make mechanical ventilation more cost effective by reclaiming energy from exhaust airflows. HRUs use air-to-air

More information

MAXIMIZING HYDRONIC SYSTEM DESIGN PART III

MAXIMIZING HYDRONIC SYSTEM DESIGN PART III MAXIMIZING HYDRONIC SYSTEM DESIGN PART III Presented by Cleaver Brooks Steve Connor & DCEs David Grassl June 21, 2017 TODAY S TOPICS Dispelling common myths about condensing boilers Supply water temperature

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

MCH Series Drives. HVAC Application Guide. ag-mch-e2

MCH Series Drives. HVAC Application Guide. ag-mch-e2 Drives HVAC Application Guide ag-mch-e2 % Flow, Torque, HP AFFINITY LAWS Most HVAC systems are designed to perform during peak load conditions that rarely occur during the year. Various flow control methods

More information

Designing Energy Efficient Outdoor Air Systems

Designing Energy Efficient Outdoor Air Systems Designing Energy Efficient Outdoor Air Systems Joseph Thorndal Applied Products Sales Manager Greenheck, Schofield, Wisconsin 1 Joseph Thorndal BS Industrial Engineering North Dakota State University Work

More information

7. MECHANICAL SYSTEM DESIGN

7. MECHANICAL SYSTEM DESIGN 7. MECHANICAL SYSTEM DESIGN The second primary topic of this thesis is to investigate the application of a dedicated outdoor air system (DOAS) to the SLCC. The stated goals for this thesis of improved

More information

Best Practices for Condensing Boilers

Best Practices for Condensing Boilers ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal at www.cleaverbrooks.com. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For

More information

GETTING THE MOST OUT OF HYDRONIC HEATING SYSTEMS

GETTING THE MOST OUT OF HYDRONIC HEATING SYSTEMS GETTING THE MOST OUT OF HYDRONIC HEATING SYSTEMS Copyright 2011. R. Trethewey, All rights reserved. No part of this document or file may be used without permission of the author. All diagrams are conceptual

More information

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,

More information

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings INTRODUCTION TO: ASHRAE STANDARD 90.1, 2013 HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings Rocky Mountain ASHRAE Technical Conference, April 29, 2016 SEAN BEILMAN, P.E.,

More information

DES CHAMPS PRODUCTS 85% 4,400 CFM

DES CHAMPS PRODUCTS 85% 4,400 CFM DES CHAMPS PRODUCTS Saves up to 85% of the heat from exhaust airstream Removes pollutants before they accumulate Transfers heat energy in winter/cool energy in summer Low cost Capacities up to 4,400 CFM

More information

SPACE CONDITIONING IN COMMERCIAL BUILDINGS Overview

SPACE CONDITIONING IN COMMERCIAL BUILDINGS Overview SPACE CONDITIONING IN COMMERCIAL BUILDINGS Overview As in residential buildings the purpose of mechanical conditioning and ventilation is to maintain air quality and thermal comfort in buildings, with

More information

CHAPTER 4. HVAC DELIVERY SYSTEMS

CHAPTER 4. HVAC DELIVERY SYSTEMS CHAPTER 4. HVAC DELIVERY SYSTEMS 4.1 Introduction 4.2 Centralized System versus Individual System 4.3 Heat Transfer Fluids 4.4 CAV versus VAV Systems 4.5 Common Systems for Heating and Cooling 4.6 Economizer

More information

Heat Recovery Ventilator Model PVe Light Industrial Commercial Institutional

Heat Recovery Ventilator Model PVe Light Industrial Commercial Institutional Heat Recovery Ventilator Model PVe Light Industrial Commercial Institutional 1,000-6,000 cfm 2.0 in. wg External Static Pressure Aluminum Plate Heat Exchanger April 2017 Heat Recovery Ventilators Greenheck

More information

GLOBAL FINISHING SOLUTIONS

GLOBAL FINISHING SOLUTIONS GLOBAL FINISHING SOLUTIONS > Eliminate problems with drafts, stale or contaminated air, and temperature stratification > Create balanced building pressure and maintain proper comfort levels > Introduce

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES To qualify the upgrade must add or substantially modify 3 or more sequences/system capabilities. Also, all sequences and items listed under the required section are needed in

More information

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder HVAC DISTRIBUTION and DELIVERY SYSTEMS (Part 2) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Contextual Reminder All-air systems Single zone Terminal reheat Multi-zone Dual-duct VAV Combinations

More information

- Essay Control Functions and Benefits

- Essay Control Functions and Benefits - Essay Control Functions and Benefits E 005 07/01 A hydronic heating control system performs many complex and important functions. Each of these functions provide benefits that make the system comfortable,

More information

Product Line Introduction. Karl Zhang Technical support engineer

Product Line Introduction. Karl Zhang Technical support engineer Product Line Introduction Karl Zhang Technical support engineer Air Conditioning Solutions Heating & Hot Water Solutions Control Solutions Air Conditioning Solutions Residential Application Commercial

More information

MECHANICAL SERVICES 101. Ian White

MECHANICAL SERVICES 101. Ian White MECHANICAL SERVICES 101 Ian White Contents 1. Ventilation 2. Heat Gains & Losses 3. Heating Ventilation Air Conditioning (HVAC) Systems What are Building Services Building Services incorporate all aspects

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012 SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences

More information

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-1142 (510) 749-9135 Fax (510) 749-9136 LLC HVAC DESIGN INTENT PART 1 - GENERAL 1.1 Overview A. The project consists of a 3-story

More information

Appendix 13. Categories of Cooling and Heating systems

Appendix 13. Categories of Cooling and Heating systems EcoShopping - Energy efficient & Cost competitive retrofitting solutions for Shopping buildings Co-funded by the European Commission within the 7 th Framework Programme. Grant Agreement no: 609180. 2013-09-01

More information

recooler HP EQKR HEAT PUMP

recooler HP EQKR HEAT PUMP AIR COMFORT AIR TREATMENT 9566 GB 2016.03.17 recooler HP EQKR HEAT PUMP» TECHNICAL CATALOGUE 2 ReCooler HP EQKR Technical Catalogue Content ReCOOLER HP EQKR HEAT PUMP 3 product presentation. 3 applications.

More information

Single Zone System. One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return

Single Zone System. One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return Single Zone System One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return Multi Zone System Used in small to medium sized buildings

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT

More information

Complete Ventilation, Heat Recovery and Dehumidification Packaged System by. Maintaining Your Climate for Indoor Pools and Waterparks

Complete Ventilation, Heat Recovery and Dehumidification Packaged System by. Maintaining Your Climate for Indoor Pools and Waterparks Ventilation Heat Recovery PoolPak International Maintaining Your Climate for Indoor Pools and Waterparks Complete Ventilation, Heat Recovery and Dehumidification Packaged System by PoolPak International

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES HVAC non CENTRAL PLANT 1) Zone Level Scheduling & Override for all air handlers (supply and exhaust) to match occupied hours by zone DDC or occupancy sensors (OS) allowed. (403.2.4.3,

More information

Munters Heat Exchangers

Munters Heat Exchangers Munters Heat Exchangers Brad Perdew Applications Engineer 8/27/12 DOAS Configurations Cheryl Hughes Regional Sales Manager October 11, 2016 cheryl.hughes@munters.com Munters DOAS Configurations Presentation

More information

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL SECTION 15100 PART 1 GENERAL THIS IS A DESIGN GUIDE NOT A SPECIFICATION Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL HVAC SYSTEMS APPLICATIONS 1.1 SCOPE: The intent of this

More information

Section 4 of 6 DOAS Core Technologies

Section 4 of 6 DOAS Core Technologies Section 4 of 6 DOAS Core Technologies Desiccant dehumidification Air-to-air energy recovery Evaporative cooling 1 Desiccant dehumidification Industrial Desiccant Dehumidifier Hybrid DX + Desiccant Dehumidifier

More information

MODELS VA3B, VB5B VC5B

MODELS VA3B, VB5B VC5B HEAT RECOVERY VENTILATORS MODELS VA3B, VB5B VC5B VA3B VB5B The Heat Recovery Ventilation (HRV) system offered by Bryant is the finest unit on the market today. The VA3B, VB5B, and VC5B provide efficient

More information

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS Presented to: Presented by: Sargon Ishaya, PE www.pragmaticprofessionalengineers.com Introduction Today s Agenda Overview Review

More information

ABOUT US OUR EXPERTISE WHAT IS ENERGY RECOVERY? ERV (Energy Recovery Ventilation) AHU (Air Handling Units) PAC (Package Air Conditioning Equipment)

ABOUT US OUR EXPERTISE WHAT IS ENERGY RECOVERY? ERV (Energy Recovery Ventilation) AHU (Air Handling Units) PAC (Package Air Conditioning Equipment) COMPANY PROFILE ABOUT US THE LEADERS IN AIR TO AIR HEAT RECOVERY. ARMCOR AIR SOLUTIONS IS A DYNAMIC, PROFESSIONAL COMPANY RESPECTED BY THE AIR CONDITIONING INDUSTRY FOR OUR TRACK RECORD IN PROVIDING ADVICE,

More information

APC APPLICATION NOTE #109

APC APPLICATION NOTE #109 #109 Application Guidelines for the InfraStruXure InRow SC Condenser By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring

More information

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

EP SERIES PACKAGED ENERGY RECOVERY SYSTEM ENERGY EFFICIENT AIR COMFORT

EP SERIES PACKAGED ENERGY RECOVERY SYSTEM ENERGY EFFICIENT AIR COMFORT ENERGY EFFICIENT AIR COMFORT EP SERIES PACKAGED ENERGY RECOVERY SYSTEM Certified total energy recovery performance (sensible and latent) up to 90% efficient. Double-wall panel construction eliminates exposed

More information

Product Data HRVCCLHU HRVCCSVC HRVCCLVU. Heat Recovery Ventilators FEATURES

Product Data HRVCCLHU HRVCCSVC HRVCCLVU. Heat Recovery Ventilators FEATURES Product Data HRVCCLHU HRVCCSVC HRVCCLVU Heat Recovery Ventilators HRVCCLHU HRVCCSVC The Heat Recovery Ventilation (HRV) system offered by Carrier is the finest unit on the market today. The HRVC provides

More information

Bill McCullough. Director ERV Products. Dallas, TX

Bill McCullough. Director ERV Products. Dallas, TX Bill McCullough Director ERV Products Dallas, TX TOPICS 1. ERV Definition & Benefit 2. Indoor Air Quality 3. Energy Efficiency 4. ERV Technology & Operation 5. Stand-Alone ERVs 6. Compact ERVs What is

More information

DX Units. Ranging from 15 to 750 tons and 1,000 to 300,000+ CFM

DX Units. Ranging from 15 to 750 tons and 1,000 to 300,000+ CFM D Units Ranging from 15 to 750 tons and 1,000 to 300,000+ CFM INDUSTRY-LEADING HVAC MANUFACTURER Nortek Air Solutions is the largest custom HVAC manufacturer in North America, with a combined total of

More information

Submittal Data Performance Data Electrical Data

Submittal Data Performance Data Electrical Data ERMS Series Submittal Data Submittal Data Unit Designation: Job name: Architect: Engineer: Contractor: Performance Data Revision: 07/01/11 Cooling Capacity: EER: Heating Capacity: COP: Ambient Air Temp:

More information

WORKSHOP VENTILATION- PSYCHROMETRICS-AHU

WORKSHOP VENTILATION- PSYCHROMETRICS-AHU Alkis Triantafyllopoulos Mechanical Engineer Member TEE, MASHRAE a.trianta@gmail.com WORKSHOP VENTILATION- PSYCHROMETRICS-AHU Based on ASHRAE 62 Purpose Set minimum Outdoor Air ventilation Rates Air Quality

More information

Product Data. HRVCCSVU, HRVCCLVU Single---Package Electric Heating Cooling Units Heat Recovery Ventilators

Product Data. HRVCCSVU, HRVCCLVU Single---Package Electric Heating Cooling Units Heat Recovery Ventilators CCSVU, CCLVU Single---Package Electric Heating Cooling Units Heat Recovery Ventilators Product Data CCSVU CCLVU A92268 A92377 The Heat Recovery Ventilation () system offered by Carrier is the finest unit

More information

HRVBBLHU HRVBBSVC HRVBBLVU

HRVBBLHU HRVBBSVC HRVBBLVU SINGLE-PACKAGE ELECTRIC HEATING COOLING UNITS HRVBBLHU HRVBBSVC HRVBBLVU Heat Recovery Ventilators HRVBBLHU HRVBBSVC The Heat Recovery Ventilation (HRV) system offered by Bryant is the finest unit on the

More information

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001 This HAP e-help provides a high-level overview of induction beams, how they work and how to model them in HAP 4.8 (and later versions). The first half of the article explains how induction beams work.

More information

COMcheck Software Version Review Mechanical Compliance Certificate

COMcheck Software Version Review Mechanical Compliance Certificate COMcheck Software Version 4.0.7.2 Review Mechanical Compliance Certificate Section 1: Project Information Energy Code: 2014 Oregon Energy Efficiency Specialty Code Project Title: Benton County Health Project

More information

The PA 600LI Heat Recovery Ventilation unit has been designed to serve the following small scale applications

The PA 600LI Heat Recovery Ventilation unit has been designed to serve the following small scale applications Heat Recovery Ventilation Systems Data Sheet PA600LI The PA 600LI Heat Recovery Ventilation unit has been designed to serve the following small scale applications Houses ranging in size from 100 300 M2

More information

Air System Sizing Summary for AHU/CU-1 Project Name: Wilton Manors Fire Station#16 06/26/2016 Prepared by: L.N.I.

Air System Sizing Summary for AHU/CU-1 Project Name: Wilton Manors Fire Station#16 06/26/2016 Prepared by: L.N.I. Air System Sizing Summary for AHU/CU-1 AHU/CU-1 Floor Area 1678.0 ft² Central Cooling Coil Total coil load 4.8 Tons Total coil load 57.8 MBH Sensible coil load 41.8 MBH Coil CFM at Jul 1500 1909 CFM Max

More information

SESSION Michigan Energy Code (MEC) Update (3 Technical) Per SMACNA Standard (TAB, Duct Design) and ASHRAE ( ) ASHRAE Detroit Members:

SESSION Michigan Energy Code (MEC) Update (3 Technical) Per SMACNA Standard (TAB, Duct Design) and ASHRAE ( ) ASHRAE Detroit Members: SESSION 1-2015 Michigan Energy Code (MEC) Update (3 Technical) Per SMACNA Standard (TAB, Duct Design) and ASHRAE (90.1.2013) ASHRAE Detroit Members: AM Session is eligible for (X) Professional Development

More information

DEMAND CONTROLLED VENTILATION WITHOUT WIRES

DEMAND CONTROLLED VENTILATION WITHOUT WIRES DEMAND CONTROLLED VENTILATION WITHOUT WIRES With increased demand for intelligent climate control systems, more and more HVAC installations deploy VAV/VAQ terminals that allow temperature control in such

More information

COMcheck Software Version Mechanical Compliance Certificate

COMcheck Software Version Mechanical Compliance Certificate COMcheck Software Version 4.0.8.1 Mechanical Compliance Certificate Project Information Energy Code: Location: Climate Zone: Project Type: 90.1 (2013) Standard Buda, Texas 2a New Construction Construction

More information

VH Series B ENVIRO-STAC Vertical Hi-Rise Fan Coil Unit with Enhanced Humidity Control

VH Series B ENVIRO-STAC Vertical Hi-Rise Fan Coil Unit with Enhanced Humidity Control VH Series B ENVIRO-STAC Vertical Hi-Rise Fan Unit with Enhanced Humidity Control Motorized Bypass Damper Temperature and Humidity Controller Reheat Control Elastomeric Foam Insulation High Efficiency,

More information

TEVHR. Heat Recovery Ventilator

TEVHR. Heat Recovery Ventilator TEVHR Heat Recovery Ventilator Contents Teknogen Who we are, what we do? TEVHR... 1 Unit Specifications... 2 Performance Data... 3 Technical Specification... 5 Components... 6 Dimensions... 7 Duct Connection

More information

Dehumidifying with Dedicated Outdoor Air

Dehumidifying with Dedicated Outdoor Air Dehumidifying with Dedicated Outdoor Air System Configurations Figure 71. Configurations for dedicated outdoor-air systems A dedicated outdoor-air handler separately filters, cools, dehumidifies, heats,

More information

HEX390. Balanced Pressure Ventilation with Heat Recovery. for healthy indoor air

HEX390. Balanced Pressure Ventilation with Heat Recovery. for healthy indoor air HEX390 Balanced Pressure Ventilation with Heat Recovery for healthy indoor air MADE IN NZ HEX390 Made in New Zealand for New Zealand conditions. BALANCED PRESSURE The HEX390 is a balanced pressure system.

More information

Next Generation Passivhaus Archives

Next Generation Passivhaus Archives Next Generation Passivhaus Archives Alan Clarke, Gloucestershire, UK, alan@arclarke.co.uk Nick Grant, Herefordshire, UK, nick@elementalsolutions.co.uk Andy Jarvis E3, Bath, UK, andy.jarvis@e3ce.com 1 Introduction

More information

Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 Prepared by: psuae

Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 Prepared by: psuae APPENDIX C Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 12:56PM Air System Information Air System Name Equipment Class Air System Type Lobby System CW AHU SZCAV Number

More information

Applications and Piping Strategies for Condensing Boilers - Introduction

Applications and Piping Strategies for Condensing Boilers - Introduction Applications and Piping Strategies for Condensing Boilers - Introduction Foil 2, 10/2015 Viessmann Manufacturing Applications and Piping Strategies for Condensing Boilers Webinar Objectives: 1. Control

More information

Strategies for Building Energy Efficiency

Strategies for Building Energy Efficiency Strategies for Building Energy Efficiency Ben Sliwinski Technical Director SEDAC University of Illinois at Urbana-Champaign How Buildings Use Energy Building Envelope (Walls, Roof, Windows, Floors) Lighting

More information

Ventilation in Humid Climates: Data from Field Experiments

Ventilation in Humid Climates: Data from Field Experiments Gaylord Texan Resort & Convention Center October 20-23, 2004 - Dallas, Texas Ventilation in Humid Climates: Data from Field Experiments Neil Moyer FSEC Yearly Housing Starts Past 3 Years Source: NAHB x

More information

Ohio Energy. Workshop HH. Strategies & Technologies to Improve the Boiler Room Efficiency. Wednesday, February 21, p.m. to 3:15 p.m.

Ohio Energy. Workshop HH. Strategies & Technologies to Improve the Boiler Room Efficiency. Wednesday, February 21, p.m. to 3:15 p.m. Ohio Energy Workshop HH Strategies & Technologies to Improve the Boiler Room Efficiency Wednesday, February 21, 2018 2 p.m. to 3:15 p.m. Biographical Information Jon Green, Mechanical Equip. Consultant

More information

Indoor Pool Design Considerations Colorado Springs, Colorado

Indoor Pool Design Considerations Colorado Springs, Colorado Indoor Pool Design Considerations Colorado Springs, Colorado September 20, 2018 Presentation by Eric S. Johnson, P.E. LifeMember, ASHRAE, Austin Chapter DESIGN CONSIDERATIONS HUMIDITY CONTROL FOR INDOOR

More information

ELECTRICAL QUANTITY WEIGHT (LB)

ELECTRICAL QUANTITY WEIGHT (LB) VRF SYSTEM INDOOR UNIT ENTERING AIR TEMPERATURES ( F) CAPACITIES (kbtuh) Max SOUND ELECTRICAL WEIGHT TOSHIBA-CARRIER COOLING HEATING Airflow PRESSURE, MARK NO. TYPE ROOM TOTAL SENSIBLE HEATING V / Ø /

More information

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney FAST AND ROBUST BUILDING SIMULATION SOFTWARE Chilled Beam Performance: 1 Shelly Street, Sydney 3D Model Creation 1 Shelley Street, Sydney 3D Model Creation 1 Shelley Street, Sydney Daylight Analysis 1

More information

Economical, Flexible, Advanced Performance. Ventilation and Dehumidification for Healthy IAQ

Economical, Flexible, Advanced Performance. Ventilation and Dehumidification for Healthy IAQ Economical, Flexible, Advanced Performance Ventilation and Dehumidification for Healthy IAQ CompleVent the Energy Conserving, Cost-Efficient Way to Meet ASHRAE Standards Today s focus on indoor air quality

More information

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge ESL-TR-99/12-04 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University-Corpus Christi (TAMU-CC) Corpus Christi, Texas Submitted to Texas

More information

ENGINEERING. Edition No. 13 October 2002

ENGINEERING. Edition No. 13 October 2002 Edition No. 13 October 2002 ENGINEERING S Y S T E M S O L U T I O N S W e at McQuay are very proud of our tradition of producing industry leading water source heat pumps. Our heritage stretches back more

More information

AIR COOLED ROOFTOP UNITS, COOLING CAPACITY FROM 50 TO 240 kw, AIRFLOW FROM TO m3/h

AIR COOLED ROOFTOP UNITS, COOLING CAPACITY FROM 50 TO 240 kw, AIRFLOW FROM TO m3/h COMFORT ROOFTOP UNITS AIR COOLED ROOFTOP UNITS, COOLING CAPACITY FROM 50 TO 240 kw, AIRFLOW FROM 10000 TO 45000 m3/h climaveneta.com COMFORT ROOFTOP UNITS ENGINEERED FOR MAXIMUM EFFICIENCY AND VERSATILITY

More information

COMMERCIAL HVAC PACKAGED EQUIPMENT. Rooftop Units Level 1: Constant Volume

COMMERCIAL HVAC PACKAGED EQUIPMENT. Rooftop Units Level 1: Constant Volume COMMERCIAL HVAC PACKAGED EQUIPMENT Rooftop Units Level 1: Constant Volume Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application

More information

EarthWise System Seminar

EarthWise System Seminar EarthWise System Seminar Tim Gasper, P.E. Solutions Engineer Brady-Trane Services, Inc. EarthWise Systems? Energy Efficiency Emissions Buildings use 39% of the Primary Energy Consumed in the United States

More information

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate

More information

AHRI Guideline W (I-P) 2014 Guideline for Selecting, Sizing, & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment

AHRI Guideline W (I-P) 2014 Guideline for Selecting, Sizing, & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment AHRI Guideline W (I-P) 2014 Guideline for Selecting, Sizing, & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does

More information

AIR TREATMENT. ReCOOLER HP» INTEGRATED COOLING/HEATING FUNCTION WITH REVERSIBLE HEAT PUMP IN THE eq AIR HANDLING UNIT

AIR TREATMENT. ReCOOLER HP» INTEGRATED COOLING/HEATING FUNCTION WITH REVERSIBLE HEAT PUMP IN THE eq AIR HANDLING UNIT AIR TREATMENT ReCOOLER HP ReCOOLER HP» INTEGRATED COOLING/HEATING FUNCTION WITH REVERSIBLE HEAT PUMP IN THE eq AIR HANDLING UNIT Energy efficiency the essence of our solutions All our research, development

More information

AHU Air Handling Unit Fundamentals. j.ilangumaran

AHU Air Handling Unit Fundamentals. j.ilangumaran AHU Air Handling Unit Fundamentals j.ilangumaran Objectives Review primary components of an AHU Understand the basic progression and advantages of advanced AHU control Understand the basic control sequences

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483586 Microprocessor Controller for Dedicated Outdoor Air System Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before

More information

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating Rooftop Ventilator with Packaged Cooling & Heating Models RV and RVE Institutional Commercial Industrial 800-1,500 cfm.0 in. wg External Static Pressure Indirect Gas, Hot Water, Electric Heating Packaged

More information

Technical Information HXV - HRV Ventilation

Technical Information HXV - HRV Ventilation Technical Information HXV - HRV Ventilation General description Technical data Accessories VENTILATION HXV 5 1 General description 1.01-1.02 2 Technical data 2.01-2.02 3 Accessories 3.01-3.03 HRV 5 4 General

More information

Best Practices for Applied Rooftop ` Systems - Application and. Jerry Cohen President Jacco & Assoc. Installation

Best Practices for Applied Rooftop ` Systems - Application and. Jerry Cohen President Jacco & Assoc. Installation Best Practices for Applied Rooftop ` Systems - Application and Jerry Cohen President Jacco & Assoc. Installation Who is Jacco Established 1968 Hudson, Ohio Columbus, Ohio Toledo, Ohio Systems Knowledgeable

More information

nzeb office building

nzeb office building nzeb office building Ympäristötalo in Helsinki, Finland City of Helsinki has taken the exemplary role of the public sector seriously. The latest proof is the Environment Centre building Ympäristötalo completed

More information

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA CITY OF DANA POINT COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 33282 Golden Lantern, Suite 209 Dana Point, CA 92629 949 248 3594 www.danapoint.org INDOOR AIR QUALITY B011 AIR 2013 CALIFORNIA CODES CODE

More information

RN/RQ. Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS.

RN/RQ. Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS. RN/RQ Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS RQ Series Features: Air-cooled or water-cooled condenser, with unit capacities

More information

The PA 600LI Heat Recovery Ventilation unit has been designed to serve the following small scale applications

The PA 600LI Heat Recovery Ventilation unit has been designed to serve the following small scale applications Heat Recovery Ventilation Systems Data Sheet PA600LI The PA 600LI Heat Recovery Ventilation unit has been designed to serve the following small scale applications Houses ranging in size from 100 300 M2

More information

Application Data. Fig. 1 39M Unit with Energy Recovery Section

Application Data. Fig. 1 39M Unit with Energy Recovery Section Aero 39MN03-30 Air Handlers Energy Recovery Section Application Data CONTENTS Page INTRODUCTION.................................1,2 Why Energy Recovery Ventilation?............... 2 AERO 39MN ENERGY RECOVERY

More information

Horizontal rotor heat recovery ventilation unit RH 5. Vertical rotor heat recovery ventilation unit RV 9

Horizontal rotor heat recovery ventilation unit RH 5. Vertical rotor heat recovery ventilation unit RV 9 ERV/ HRV CONTENTS Horizontal rotor heat recovery ventilation unit RH 5 Vertical rotor heat recovery ventilation unit RV 9 Suspended plate heat recovery ventilation unit CFP Horizontal plate heat recovery

More information

PRODUCT RANGE: ROOFTOP PACKAGE

PRODUCT RANGE: ROOFTOP PACKAGE Packaged Air Cooled Reverse Cycle Type Air Conditioner Range 11-125kWr With Energy / Heat Recovery The Roof Top Packaged unit range is designed to be used when high fresh air quantities are required. They

More information

DADANCO Technical Paper

DADANCO Technical Paper DADANCO Technical Paper 260 North Elm Street Westfield, MA 01085 Phone: (413) 564-5657 Fax: (413) 568-2969 March 2013 CLASSROOM SOLUTION USING ACTIVE CHILLED BEAMS (Note: This technical paper assumes the

More information