VIADRUS CLAUDIUS K 2 Manual for boiler operation and installation

Size: px
Start display at page:

Download "VIADRUS CLAUDIUS K 2 Manual for boiler operation and installation"

Transcription

1 VIADRUS CLAUDIUS K 2 Manual for boiler operation and installation GB_2016_43 GB_2016_35

2 Content p. 1 Manufactured boiler versions Boiler Uses and Advantages Specifications Boiler description Boiler construction Storage heater VIADRUS OV - H Placement and installation Regulations and guidelines Positioning options Delivery and accessories Boiler Installation Wiring diagram Commissioning Connection to the heating system and filling with water Gas connection Connection to the mains Condensate drain Flue gas exhaust Pressure losses of flue gas exhaust components for the boiler VIADRUS CLAUDIUS K Boiler commissioning Boiler settings Boiler operation by user General description Display description Energy saving Settings overview Error messages Faults Maintenance Checking the device IMPORTANT NOTICE Instructions for product disposal after its service life Warranty and liability for defects

3 Dear customer, Thank you for purchasing VIADRUS CLAUDIUS K 2 and hence your confidence in the company VIADRUS a.s. To get used to a correct way of handling your new product, please read at first this manual for its use, particularly Chapter no. 8 - Boiler operation by users and Chapter no Important information. We ask you to follow further presented information, particularly regarding required annual inspections by a professional company, thus ensuring trouble-free boiler operation to our satisfaction. 1 Manufactured boiler versions In the order, please specify the following order specification code: VIADRUS CLAUDIUS K 2 x 1 x 2 x 3 x 1 Gas valve: L: produced by SIEMENS x 2 Size: 3: 3-section version 5: 5-section version x 3 Equipment: 1: without set three-way valve with pump 3: with three-way valve and pump 5: without set three-way valve with pump 2 Boiler Uses and Advantages Condensing boiler VIADRUS CLAUDUS K 2 is intended for combustion of low pressure natural gas. The size of the condensing boiler is suitable for heating of houses, recreation facilities and also for reconstruction of heat sources in individual flats. Heat output of the condensing boiler is 3.8 to 24 kw (K 2 L3X) and 7.8 to 48.1 kw (K 2 L5X). The boiler body consists of castings made from special aluminium alloy. Individual sections are connected by means of silicon rings and tightened by threaded bars. The maximum working overpressure of the boiler is 250 kpa (2.5 bar). The body is tested by the test overpressure of 600 kpa (6 bar). Combustion mixture is mixed in a mixer in a predetermined ratio of air - gas in its control range. Water volume of the three-section boiler body is 9 l and the water volume of the five-section body is 13 l. The efficiency of the boiler body at a temperature gradient of 50/30 C ranges from 102 to 108% depending on the desired performance. Boiler advantages: Low gas consumption. High combustion efficiency. Continuous output modulation. Easy operation and maintenance. The boiler enables connection to a storage hot service water heater and guarantees its preferential heating. Reliability of regulation and safety elements. Low weight. Automatic detection of faults. Independent time program also for HW. Equithermal boiler regulation. 3

4 3 Specifications Tab.. 1 Sizes, operation temperature and electrical variables K 2 L3X K 2 L5X Fuel type [-] ZP ZP Appliance category [-] I 2H I 2H Weight [kg] Water content [l] 9 13 Boiler dimensions - width (L2) [mm] depth [mm] height [mm] Ø connection of the combustion air [mm] Ø smoke socket [mm] Maximum working water overpressure [kpa]/[bar] 250/ /2.5 Testing water overpressure [kpa]/[bar] 600/6 600/6 Dissipation factor [-] Maximum allowable operating temperature [ C] Connecting fuel overpressure G20 [mbar] Noise level [db] < 55 < 55 Boiler connection - heating water outlet [Js] 3/4 3/4 - heating water outlet to the heater [Js] 3/4 3/4 - return heating water inlet [Js] 3/4 3/4 - return water inlet from the heater [Js] 3/4 3/4 - condensate outlet [mm] Ø 25 Ø 25 - safety valve outlet [Js] 3/4 3/4 - gas inlet [Js] 3/4 3/4 Supply voltage 1/N/PE 230 VAC 50 Hz TN-S Input power including pumps [W] El. protection IP Tab.. 2 Heat-technical parameters Comparative conditions 15 C and 1013,25 mbar, dry gas K 2 L3X K 2 L5X Performance B 23, B 53, C 83 B 23, B 53, C 83 Boiler power range [kw] Rated heat output 80/60 C [kw] Minimum heat output 80/60 C [kw] Rated heat output 50/30 C [kw] Minimum heat output 50/30 C [kw] Rated heat input [kw] Minimum heat input [kw] Efficiency at rated heat output 80/60 C [%] Efficiency at rated heat output 50/30 C [%] Efficiency at minimum heat output 50/30 C [%] Volumetric flow rate of fuel [m 3.h -1 ] Flue gas mass flow [kg.h -1 ] NOx Class [-] 5 5 Flue gas temperature [ C] sect. 5 sect. Fig.. 1 Dependence of the pressure loss on flow 4

5 Information requirements relating to boiler heaters for space heating, boiler combined heaters and cogeneration heaters for space heating Model/Models: Condensing boiler: Low-temperature boiler: Boiler type B1: VIADRUS CLAUDIUS K2 L3X YES NO NO Cogeneration heater for space heating: NO If YES, featured with an auxiliary heater: Combined heater: NO Item Designatio n Value Unit Item Designatio n Value Unit Rated heat output Prated 22.7 kw For the boiler heaters for space heating and boiler combined heaters: useful heat output Seasonal energy efficiency of heating (***) ƞ s 92 % For the boiler heaters for space heating and boiler combined heaters: useful efficiency At rated heat output and high temperature mode (*) P kw At rated heat output and high temperature mode (*) ƞ % At 30% of rated heat output and low temperature regime (**) P kw At 30% of rated heat output and low temperature regime (**) ƞ % Consumption of auxiliary electrical power: Other items: At full load el max kw Heat loss in standby mode P stby kw At partial load el min kw Electricity consumption of the pilot burner P ign - kw In standby mode P SB kw Emissions of nitrogen oxides NO x 12 mg/ kwh Contact information VIADRUS a.s. Bezručova 300 Bohumín (*) High temperature mode for condensing boilers mean return temperature of 60 C at the inlet to the heater and the inlet temperature 80 C at the outlet of the heater. (**) Low temperature for condensing boilers mean return temperature of 30 C, for low temperature boilers it is 37 C, and for other heaters it is 50 C (at the inlet of the heater). (***) For seasonal energy efficiency, the value is based on the gross calorific value according to EU regulation no. 813/2013 5

6 Information requirements relating to boiler heaters for space heating, boiler combined heaters and cogeneration heaters for space heating Model/Models: Condensing boiler: Low-temperature boiler: Boiler type B1: VIADRUS CLAUDIUS K2 L5X YES NO NO Cogeneration heater for space heating: NO If YES, featured with an auxiliary heater: Combined heater: NO Item Designatio n Value Unit Item Designatio n Value Unit Rated heat output Prated 46.1 kw For the boiler heaters for space heating and boiler combined heaters: useful heat output Seasonal energy efficiency of heating (***) ƞ s 93 % For the boiler heaters for space heating and boiler combined heaters: useful efficiency At rated heat output and high temperature mode (*) P kw At rated heat output and high temperature mode (*) ƞ % At 30% of rated heat output and low temperature regime (**) P kw At 30% of rated heat output and low temperature regime (**) ƞ % Consumption of auxiliary electrical power: Other items: At full load el max kw Heat loss in standby mode P stby kw At partial load el min kw Electricity consumption of the pilot burner P ign - kw In standby mode P SB kw Emissions of nitrogen oxides NO x 13 mg/ kwh Contact information VIADRUS a.s. Bezručova 300 Bohumín (*) High temperature mode for condensing boilers mean return temperature of 60 C at the inlet to the heater and the inlet temperature 80 C at the outlet of the heater. (**) Low temperature for condensing boilers mean return temperature of 30 C, for low temperature boilers it is 37 C, and for other heaters it is 50 C (at the inlet of the heater). (***) For seasonal energy efficiency, the value is based on the gross calorific value according to EU regulation no. 813/

7 4 Boiler description 4.1 Boiler construction The heat exchanger of the condensing boiler consists of a front, middle (the number depends on the size of the boiler) and the rear section. These castings are connected by means of silicon rings and tightened by threaded bars. This boiler is equipped with a premixing burner. Combustion mixture is mixed in a mixer in a predetermined ratio of air - gas at the whole performance range. Air is supplied to the mixer using the modulation ventilator. The boiler is constructed for heating with preferred heating of HW. To heat HW, the manufacturer recommends combination with the water heater. Further, the boiler is equipped with LMS automatics and a gas valve. LMS automatic is an electronic control and ignition automatics designed for gas central heating boilers with the modulated ventilator and pre-mixing burner. if the boiler is to be controlled equithermally, it is necessary to connect the outdoor sensor. In this case, we recommend using one of the communication devices, see chap To increase the number of heating circuits, expansion module can be used according to project documentation. Combustion air can be fed and flue gas can be exhausted to the chimney or through the wall. The boiler is an appliance of B or C version. 1 Condensing body 2 Burner plate with burner 3 Ignition electrode (guard electrode) 4 Supply of the mixture to the burner 5 Fan 6 Gas valve 7 Pump with a PWM control 8 Three-way valve 9 Condensate drain 10 Exhaust piping 11 Suction piping 12 Inlet pipe to the boiler 13 Outlet pipe from the boiler 14 Manometer check valve Fig.. 2 Assembly of the boiler 15 SIEMENS display 16 Reset button 17 Manometer 18 Console electro 19 Control panel SIEMENS LMS 20 Housing electro 21 Boiler frame 22 Right side casing part with insulation 23 Left side casing part with insulation 24 Upper casing part with insulation 25 Rear casing part with insulation 26 Front casing part 27 Outlets 28 Blinds 7

8 gas inlet gas inlet 1. Complete burner 2. Extension tube 3. Gasket Ø mix strainer 5. Screw M5 6. Washer Nut M5 Fig.. 3 Location mix strainer in the gas pipeline of the burner K 2 L5X 5 Storage heater VIADRUS OV - H 100 Water heater VIADRUS OV H 100 is a pressure device adapted to operate at a maximum water pressure of 0.6 MPa (6 bar). Hot service water heater is a device designed for heating and storing hot water. The main part of the heater is a vessel made of steel sheet coated with a layer of enamel. The heater is equipped with a heating coil with large heat exchange surface, which ensures fast heating of large quantities of water. All connections are located in the upper part of the heater and are terminated with an external thread. The heater also offers the possibility of connecting a circulation pump for circulating hot water, and s temperature sensor. There is an outlet at the bottom part of the heater through which the vessel can be drained. The heater is equipped with an additional anticorrosive device in the form of a magnesium anode whose function is based on the utilization of the electrochemical potential difference between the anode and the tank. The magnesium anode is placed in the upper part in the plug 2. Thermal insulation of the heater is made of polyurethane foam free from freon, which minimizes heat loss. An electric heater can be installed in the heater. Tab.. 3 Technical parameters Technical parameters VIADRUS OV H 100 Volume l 100 Maximum allowable temperature C 100 Maximum allowable pressure bar 6 Heat exchanger surface m Heat exchanger volume l 5.6 Consumption of heating water from central heating m 3 /h 2.5 Constant efficiency (70/10/45 o C) l/h 700 Output kw 29 Dimensions A mm 140 B mm 60 C mm 40 D mm 100 E mm 120 Device height L 990 Tank dimensions (without insulation) Ø 400 Tank dimensions (with insulation) mm 455x455 Insulation of soft polyurethane foam mm 30 8

9 Connections Cold water / hot water R 3/4 Circulation R 3/4 Central heating circulation (supply, return pipeline) R 3/4 E-socket (heating coil) R 5/4 Sensor housing R 3/8" Thermometer 1/2 internal thread Water drain 3/4" Magnesium anode An. stopper 2 Weight (empty) kg 57 ANODE PROTECTION DRAIN Fig.. 4 Water heater VIADRUS OV - H 100 9

10 6 Placement and installation 6.1 Regulations and guidelines a) for the heating system CSN Heating systems in buildings Design and installation CSN Heating systems in buildings Safety devices CSN Water and steam for heating equipment with steam working pressure up to 8 MPa EN Gas-fired central heating boilers - Part 1: General requirements and tests EN Gas-fired central heating boilers - Part 2-1: Specific standard for boilers of design C and designs B2, B3 and B5, with a nominal heat input not exceeding 1,000 kw EN 677 Gas-fired central heating boilers Specific requirement for condensing boilers with a nominal heat input not exceeding 70 kw b) for chimneys CSN Chimneys and flues Design, implementation and connection of fuel appliances c) regarding the fire regulations CSN Fire safety of heat installations. EN A1 Fire classification of construction products and building elements Part 1: Classification using test data from reaction to fire tests d) for the system HW heating CSN Thermal systems in buildings Hot water preparation Designing and Installation CSN Heating systems in buildings Safety devices CSN Internal Water Supply e) for the electricity network CSN Electrical regulations. Marking the conductors with colours or digits. Implementing regulations. CSN Electrical regulations. Revision of electrical devices. CSN ed. 2 Low-voltage electrical installations Part 1. Basic terms of determining the fundamental characteristics of the definition. CSN ed. 2 Low-voltage electrical installations Part 4-41, Protective measures to ensure safety Protection against electric shock CSN ed. 3 Low-voltage electrical installations Part Selection and erection of electrical equipment Common rules. CSN ed.2 Electrical installations of buildings Part 7-703: Requirements for special installations or locations Rooms and cabins containing sauna heaters. CSN ed. 2 Low-voltage electrical installations Internal electric distribution lines. CSN CSN electric engineering regulations. Rules for installation of electrical apparatus and appliances. ČSN ed.2 Safety requirements for flexible cords and cables. EN Explosive atmospheres Part 10-1: Classification of areas Explosive gas atmospheres. EN ed.3 Explosive atmospheres Part 14: Electrical installations design, selection and erection. EN ed.3 Household and similar electrical appliances - Safety Part 1: General requirements. EN Household and similar electrical appliances - Safety Part 2 102: Particular requirements for gas, oil and solid-fuel burning appliances having electrical connections. EN ed. 4 Basic and safety principles for man-machine interface, marking of terminals of electrical equipment, ends of cables and wires. f) for the gas distribution EN 1775 Gas supply Gas pipework for buildings Maximum operating pressure <= 5 bar Functional recommendations. EN Gas supply systems Pipelines for maximum operating pressure up to and including 16 bar Part 1: General functional recommendations. EN Gas supply systems Pipelines for maximum operating pressure up to and including 16 bar Part 2: Specific functional requirements for polyethylene (MOP up to and including 10 bar) EN Gas supply systems Pipelines for maximum operating pressure up to and including 16 bar Part 3: Specific functional requirements for steel. EN Gas supply systems Pipelines for maximum operating pressure up to and including 16 bar Part 4: Specific recommendations concerning reconstructions. CSN Boiler rooms with gas fuel-operated equipments CSN Gas equipment, operation principles. 10

11 Act No. 458/2000 Coll. The Act on business conditions and the performance of state administration in the energy sectors and on amendments to certain laws (Energy Act) 6.2 Positioning options When installing and using the boiler, all requirements of CSN must be complied with. Positioning and connection of the boiler must correspond to the project documentation. Flue gas exhaust must comply with the applicable regulations (Technical Regulations TPG ) and the project documentation. The space near and above the boiler must be equal to min. 0.2 m and min. 1 m before the boiler for the assembly and repair. The manufacturer recommends to mount these products into closed heating systems. The boiler may be installed in living rooms. It can be situated in the basic environment according to CSN ed. 2. K 2 L3X K 2 L5X L (mm) Fig.. 5 Main dimensions of the boiler Boiler positioning with regard to fire regulations: Safe distance from flammable materials: When installing and operating the boiler it is necessary to keep the safe distance of 200 mm from flammable materials A1, A2, B and C (D); For easily flammable materials of flammability class E (F), which burn quickly and by themselves also after the ignition source removal (e.g. paper, cardboard, asphalt and tar boards, wood and fibreboards, plastics, flooring materials) the safe distance is doubled, it means that the distance is 400 mm; The safe distance is to be doubled also in case when the fire reaction class is not proven. Tab.. 4 Fire reaction class Fire reaction class Examples of building materials and products classified in reaction to fire class (selection from CSN EN A1) A1 non-combustible material granite, sandstone, concrete, bricks, ceramic tiles, mortars, anti-fire plasters, A2 limited combustibility material akumin, izumin, heraklith, lignos, boards and basalt felt, fibreglass boards, B difficult to ignite Beech, oak, hobrex boards, plywood, werzalit, Formica, sirkolit, C (D) medium inflammable pine, larch, spruce wood, chipboard and cork boards, rubber flooring, E (F) easily flammable Asphalt board, fibreboards, cellulose materials, polyurethane, polystyrene, polyethylene, PVC, Delivery and accessories The boiler VIADRUS CLAUDIUS K 2 is supplied as assembled on a pallet, packed in a carton cover and foil protected. Standard accessories to all boiler variants: Operating instructions and installation manual, which includes a warranty card The list of contractual service organizations For the variant CLAUDIUS K 2 LX3, boiler sensor QAZ 36 Recommended accessories to all boiler variants: One of spatial communication devices Siemens QAA74, QAA75, QAA55, QAA58 (wireless) QAA78 (wireless) 1 pc Outside sensor QAC 34/101 1 pc Recommended accessories are not included in the basic price of the boiler. 11

12 6.4 Boiler Installation According to the marked outlets, the boiler is connected to the heating system including HW (if used) and gas distribution as shown in Fig. No. 6. Condensate drain should be connected in compliance with the applicable standards CSN and EN. Further, the flue gas exhaust is connected according to the project. 1 Heating water outlet from the boiler (if a water heater, it is necessary to make connections via T - piece behind the boiler) 2 Cable bushings 3 Bushings for the sensor 4 Return water from the central heating 5 Output from the safety valve 6 Condensate drain 7 Return water from the water heater 8 Gas inlet 9 Intake flange (diameter 80 mm) 10 Flue gas output (diam. D mm) K 2 L3X K 2 L5X L (mm) L1 (mm) L2 (mm) V1 (mm) diam. D (mm) Fig.. 6 Rear view of the boiler 12

13 6.5 Wiring diagram LEGEND: A1 Control unit A2 Kindling transformer with gas valve A3 Control panel AVS37 B2 Boiler temperature sensor - output B3 HW temperature sensor - output B7 Boiler temperature sensor - input B9 External temperature sensor B38 HW temperature sensor - input BTr Room thermostat E1 Kindling electrode E2 Monitoring electrode MV1 Fan MV1 Fan Q1 Pump X1a Power supply connector 230В X1b Three-way valve and selected output connector X1f Fan and pump power supply connector X2 Protective thermostat connector X4 Temperature sensors and Reset button connector X5a Selected inputs connector X6a Selected inputs connector X7a Connection of room devices (QAA 74, 75 ) X8 PWM fan control connector X10a PWM/1-10В outputs connector X12, 13 Programmable connectors X15 PWM pump control connector X30 Control panel connector Y3 Three-way valve Protective clamps Fig.. 7 Circumferential diagram 13

14 Fig.. 8 Wiring diagram 14 LEGEND: A1 Control unit A2 Kindling transformer with gas valve A3 Control panel AVS37 B2 Boiler temperature sensor - output B3 HW temperature sensor - output B7 Boiler temperature sensor - input B9 External temperature sensor B38 HW temperature sensor - input E1 Kindling electrode E2 Monitoring electrode MV1 Fan Q1 Pump X1a Power supply connector 230В X1b Three-way valve and selected output connector X1f Fan and pump power supply connector X2 Kindling transformer and gas valve connector X4 Temperature sensors and Reset button connector X5a Selected inputs connector X6a Selected inputs connector X7a Connection of room devices (QAA 74, 75 ) X8 PWM fan control connector X10a PWM/1-10В outputs connector X11 Connector for connection of OCI 345 X12, 13 Programmable connectors X15 PWM pump control connector X17 Earth connector X18 Protective thermostat connector X30 Control panel connector X50 RVS regulator connector X54 Water pressure sensor connector Y3 Three-way valve Protective clamps CONDUCTORS COLORS bn (brown) bu (blue) bk (black) gn (green) gnye (green/yellow) rd (red) ye (yellow)

15 7 Commissioning 7.1 Connection to the heating system and filling with water Before filling the heating system with water the system should be duly cleaned, it means that the system should be twice filled with clean water and drained. Water for the boiler and the heating system filling must be clear and colourless, without suspended solids, oil and aggressive chemicals. The heating system must be filled with water that meets the requirements of CSN and especially its hardness must not exceed the required parameters. The parameters of circulating and make-up water must correspond to the following: Tab.. 5 The maximum permissible values of heating water according to CSN Recommended values Hardness mmol/l 1 Ca 2+ mmol/l 0.3 Total Fe + Mn concentration mg/l (0,3)* *recommended value ATTENTION!!! The manufacturer does not recommend the use of antifreeze. If the water hardness is unsuitable it has to be adjusted. Even the multiple heating of water with a higher hardness does not exclude salts on the boiler body walls. Precipitation of 1 mm calcite reduces at a given point the heat transfer from the metal to water by 10%. During the heating season, it is necessary to maintain a constant volume of heating water in the heating system and ensure that the heating system is vented. Water from the boiler and the heating system must never be drained or taken for usage except for the emergency cases like repairs etc. Heating water discharge and filling with new water increases the danger of corrosion and scaling. If it is necessary to refill water in the heating system, refill only the cold boiler in order to avoid disruption. Before filling the system with water, shift a three-way valve control lever into the intermediate position using a screwdriver or manually by pulling it toward yourself slightly down (if the boiler has the option of feeder water preparation) Fig. No. 9. After filling the heating system, dismantle the water valve drive by pushing the metal push button and turning right. After remounting the water valve drive, the lever comes back to the position for heating the heating system. Lever shifted in the intermediate position when filling the heating system and water heater Lever in the position for HW heating Lever in the position for heating the heating system Fig.. 9 Three-way valve VC 4013 When filling the boiler with water the system must be disconnected from the mains. Bleeder valve on the boiler and on the heating system must be open and functional. Adjust the expansion vessel to a pressure of 10 kpa (0.1 bar) higher than the pressure required in the heating system (only for the version CLAUDIUS K 2 L31, CLAUDIUS K 2 L33). The system is pressurized to the desired pressure of about 100 kpa (1 bar) and again vented. For filling water, it is recommended to use a filter on the heating system inlet. The heating system must have a sufficient number of vents. Drain valve must be installed at the lowest point of the heating system. The expansion tank is 8 L volume and its volume is sufficient for 150 l of water in the heating system. The expansion tank is not mounted for the version CLAUDIUS K 2 L5X. The system should be designed to a temperature gradient of 55/45 C with respect to condensation use. Condensing boiler can be used also for old self-load systems which were pre-dimensioned and thus condensation can be efficiently used also for this system, but the system should be supplemented with a corresponding expansion tank. 15

16 Condensing boiler is equipped with low energy pump with a PWM driving Wilo Yonos Para RS 15/7.5. Modulating pump is controlled by the control unit of the boiler according to the chosen strategy. The connection to the heating system, HW and gas is carried out through ball valves. Fig.. 10 Wilo Yonos Para RS 15/7.5 pump characteristics 7.2 Gas connection Before connecting the gas pipeline to the boiler, the gas pipeline should be tested and checked. After the boiler connection to the gas pipeline, all gas connections gas must be re-tested by a gas detector or foam solution. Inlet natural gas pressure is 2 kpa (20 mbar). 7.3 Connection to the mains The boiler is equipped with a movable mains supply and a plug. According to ČSN EN ed. 2 Art , the boiler must be positioned so that the plug is accessible. Near the boiler, a socket 230 V/50 Hz must be placed at the distance of 1.5 meters. The socket must comply with applicable regulations and must be checked. 7.4 Condensate drain To drain condensate, a built-in siphon connected to a sewerage overflow is used. Before the boiler commissioning, check whether the condensate is drained. Size of a waste PVC pipe is of Ø 16 mm. The condensate ph is 4.5 and it can be drained into the sewer system without treatment. The boiler condensate drain must be made so as to not prevent continuous condensate drain. 7.5 Flue gas exhaust The boiler is made in the version B or C according to the way of flue gas exhaust and combustion air inlet. Gas appliances for the version B suck the combustion air from the boiler room. Appliances for the version C suck the combustion air from the outside or from the space outside the boiler room. The boiler is supplied in a standard version. The boiler flue gas exhaust is not part of the boiler supply. It is necessary to use special piping intended for condensing boilers with a wall thickness of 1.5 mm. It is necessary to keep a 3% inclination to the boiler. Pressure loss for the flue gas exhaust must not exceed 150 Pa. Glue gas exhaust and air inlet including their lengths shall be made by a designer in the technical documentation. The boiler must be installed only with a wind protective device which meets the requirements of EN (See Annex N). The boiler must be installed with the necessary accessories (pipeline for the combustion air supply and flue gas exhaust). 16

17 Fig.. 11 Flue gas exhaust and air intake connection options The boiler version B and C is specified by a double digit: - the first digit in the index relates to the possible boiler installation with regard to the way of combustion air inlet and flue gas exhaust, - the second digit in the index relates to the use and positioning of the built-in ventilator in the boiler. The boiler is a boiler with a fan before the combustion chamber/heat exchanger (boiler body) and is marked with a second digit of the index 3. Version B 2 Boiler version B without the flue gas rectifier. Version B 5 Boiler version B without the flue gas rectifier, which is designed for connection via its own flue gas exhaust to the protective orifice. The chimney must be equipped with a special liner intended for the condensation boiler and a condensate drain from the chimney. For the boiler, it is possible to use a plastic liner with the temperature resistance of 120 C. Version C 8 The boiler draws combustion air from the outside and transfers it to the chimney. The combustion chamber and flue gas ways of the appliance are gastight separated from the space in which the appliance is located. If the flange for the air intake is used according to Fig. No. 15, the break-out plate in the rear of the boiler must be removed. Pro the version CLAUDIUS K 2 L5X, the flue gas exhaust has a diameter of 110 mm. The air supply diameter remains 80 mm. The boiler is designed for connection to an individually approved and sold pipeline system for combustion air supply and flue gas exhaust. - The least pressure loss = 17 Pa - The highest pressure loss = 150 Pa - Flue gas temperature for minimum output 30 C - Flue gas temperature for maximum output 85 C 17

18 7.6 Pressure losses of flue gas exhaust components for the boiler VIADRUS CLAUDIUS K2 max. fan pressure 150 Pa Split flue gas exhaust - flue gas K 2 L3X VIADRUS order code code DN Name Loss in Pa PPSB48 80 Bend PPSB98 80 Bend PPRM18 80 Pipe 1m PPSAS8 80 Plastic chimney head starr (set) 2.5 Split flue gas exhaust - flue gas K 2 L5X VIADRUS order code code DN Name Loss in Pa PPSB Bend PPSB Bend PPRM Pipe 1m 3.4 PPSAS1 110 Plastic chimney head starr (set) 2.5 Split flue gas exhaust - intake K2 LXX VIADRUS order code code DN Name Loss in Pa PPSB48 80 Bend PPSB98 80 Bend PPRM18 80 Pipe 1m 2.5 Note: The number of components for each version depends on the location of the boiler. For the boiler, the flue gas exhaust by ALMEVA is approved see accessories in the price list of VIADRUS a. s. In the case of an assembly of two or more boilers in a cascade we recommend contacting the company Almeva for the offer and calculation of the relevant flue gas exhaust. 7.7 Boiler commissioning The entire installation must comply with regulations related to this equipment. The boiler must be compatible with local connecting conditions (check the boiler parameters with those on the nameplate). Putting the boiler in operation may only be performed by organizations authorized and trained by the manufacturer. The minimum pressure in the heating system is 80 kpa (0.8 bar). It is necessary to open all closures and check whether gas leaks. Connect the boiler to the mains. Since the boiler is not equipped with a main switch, the boiler will start. Check the gas distribution behind the gas valve. Check the safety valve functionality. It is also necessary to check the pump operation. Check the functionality of the three-way valve (if used). During the boiler operation it is necessary to check the condensate drain both from the boiler and from the chimney liner. During the first boiler commissioning it is needed to train users in accordance with these instructions and pass this manual to the user with the confirmation of the commissioning. It is also required: - to check revisions prior to commissioning, - to check the water leakage, - to check regulation and safety elements. 18

19 7.8 Boiler settings The product meets the values for Green product. The specific measured values depend on the type of connection of the combustion air supply and flue gas exhaust to a given appliance. Therefore, when the boiler commissioning, CO 2 value should be checked or adjusted. The gas valve is factory set to CO 2 value in the flue gas in the range from 8.4 to 8.8%. Max. CO value must be to 100 mg/m 3 converted to 3% oxygen. 1 Gas supply to the valve 2 Fan 3 Mixer 4 Gas supply to the mixer 5 Gas valve 6 Adjusting screw CO 2 max 7 Adjusting screw CO 2 min 8 Measuring point for the gas output pressure 1 9 Measuring point for the gas input pressure 10 Measuring point for the gas output pressure 11 Measuring point for the flue gas Fig.. 12 CLAUDIUS K 2 L setting 1. Use the control knob to select the symbol and confirm by pressing the control knob. The display shows the line Special Operations (chimney sweep function). 2. Use the control knob scroll to the line Off, confirm by pressing the control knob and then using the control knob select the line ON and confirm again. 3. On the newly displayed line Burner output select Max. heating load using the control knob and confirm. 4. The boiler will heat at the rated output. 5. Unscrew the plug and insert the probe of the flue gas analyser in the flue gas measuring point (see Fig. No Pos. 10). 6. Check the amount of CO 2 in the flue gas which must be in the range of 8.4 to 8.8%. The recommended value is 8.5%. 7. Wait about 120 seconds until the boiler operation gets stabilized and check or adjust the CO 2 max. value using the CO 2 max. regulating screw (Fig. no. 16 pos. 6). 8. On the line Burner output select Partial performance using the control knob and confirm. 9. Wait about 120 seconds until the boiler operation gets stabilized and check or adjust the CO 2 min. value using the CO 2 min. regulating screw (Fig. no. 16 pos. 7). 10. When turning the adjusting screw clockwise, theco 2 volume increases, when turning the adjusting screw counter-clockwise, the CO 2 volume decreases. 11. Screw the cover of the gas valve adjusting screw, remove the flue gas analyser probe and screw the plug into the flue gases measuring point (watch its tightness). 12. After the adjustment, turn off the chimney sweep function. Note: For the boiler version K 2 L3X, the slide ø 7 mm is positioned at the output of the gas valve. 19

20 8 Boiler operation by user 8.1 General description The boiler is equipped with a control unit LMS14. To set the parameters, use the display AVS37. For the proper operation of the boiler, it is important to observe the hydraulic connection. For these purpose, design documentation is prepared. The boiler is factory set so that it heats to the set temperature of the boiler (parameter 742). Switching is via a jumper at the input H5. When connecting the switching room unit to the input H5, the jumper should be removed. It is also recommended to use an outdoor sensor, due to weather-compensated heating and time programs use. Further, we recommend using a communication room device according to the menu, see chap Using the expansion modules, the control unit can manage up to 3 mixed heating circuits, hot water, cascade, solar, pool, wood-fired boiler etc. (see VIADRUS design documents). Another possible method of the boiler switching boiler is using 0-10 V via the input H1. The boiler is then only a heat source. 8.2 Display description Press the button OK (E) to enter the setup mode, where you can move through the menu or adjust the value of the parameter using the control knob (D). Press the OK button to enter the desired menu or parameter, and confirm the selected parameter value. A B C D E F G H I J A B C D E F G H I J Feed water operating mode switch RESET button ESC button Room temperature adjustment knob Confirmation button OK Manual operation button Chimney sweep function button Operation mode switch for the heating circuits Display Info button Fig.. 13 A Operation mode switch FV - OFF/ON for the HW heating B RESET button - burner fault unblocking (press for about 3 s) C ESC button - returning one step back in the menu (the selected value is not stored) D Room temperature adjustment knob - room temperature option or selection in the menu E Confirmation button - shifting one step forward in the menu and confirmation of the selected value F Manual operation button - the boiler running at a preset temperature of 60 C, all the pumps are running, the G H I J mixer is not controlled - the display shows the symbol. Chimney sweep function button - after short pressing, the boiler enters the emission measurement mode. This button is intended for an authorized service technician. Operation mode switch for the heating circuits: - operation according to preset time mode (transition to summer mode depending on the outdoor temperature is active) - continuous operation at nominal set room temperature - continuous operation at setback set room temperature - maintaining the anti-frost desired room temperature Display Info button - information about the current state of the boiler, heating circuits, HW and error messages. 20

21 8.2.1 Energy saving Use automatic operation. Set the desired comfortable temperature. Use your time program. The main rule is that the Automatic mode must be set as operating mode: In this mode, the controller monitors the heating for optimal heat consumption (e.g.: summer/winter switching). Or you can individually adjust the operating mode for anti-frost, permanent setback, comfort, according to your needs. Set comfort temperature which has to be maintained during the use of the room, that means during the time set in the time program. Use the time program for setting the time during which the comfortable temperature must be maintained, and outside the comfortable temperature the controller will heat up to the setback temperature. Setting the time program should correspond to room occupancy or night setback. The time program is only used in the Automatic mode of operation. Hot water heating... Settings for the operating mode, temperature and time program for HW heating are identical with settings for heating. 8.3 Settings overview The table shows all available user settings. Time and date Parameter Function Factory settings Min. Max. Units 1 Time :00 23:59 hh:mm 1 Date dd:mm 5 Summer time start dd:mm 6 Summer time end dd:mm Current date and time must be set due to the correct function of the time programs for heating circuits and hot water. Time program HC1 Parameter Function Factory settings Min. Max. Units 500 Preset Mo-Su 00:00 24:00 hh:mm 501 Mo-Su : 1. Phase ON 6:00 00:00 24:00 hh:mm 502 Mo-Su : 1. Phase OFF 22:00 00:00 24:00 hh:mm 503 Mo-Su : 2. Phase ON 24:00 00:00 24:00 hh:mm 504 Mo-Su : 2. Phase OFF 24:00 00:00 24:00 hh:mm 505 Mo-Su : 3. Phase ON 24:00 00:00 24:00 hh:mm 506 Mo-Su : 3. Phase OFF 24:00 00:00 24:00 hh:mm 516 Standard values NO 1. (2, 3) Phase On start of the heating phase at the selected comfortable temperature. 1. (2, 3) Phase Off end of the heating phase at the selected comfortable temperature and switching to the setback temperature. Default values reset of the time program to factory settings Time program HC2 (only if activated) Parameter Function Factory settings Min. Max. Units 520 Preset Mo-Su 00:00 24:00 hh:mm 521 Mo-Su : 1. Phase ON 6:00 00:00 24:00 hh:mm 522 Mo-Su : 1. Phase OFF 22:00 00:00 24:00 hh:mm 523 Mo-Su : 2. Phase ON 24:00 00:00 24:00 hh:mm 524 Mo-Su : 2. Phase OFF 24:00 00:00 24:00 hh:mm 525 Mo-Su : 3. Phase ON 24:00 00:00 24:00 hh:mm 526 Mo-Su : 3. Phase OFF 24:00 00:00 24:00 hh:mm 536 Standard values NO 21

22 Time program 3/HC3 Parameter Function Factory settings Min. Max. Units 540 Preset Mo-Su 00:00 24:00 hh:mm 541 Mo-Su : 1. Phase ON 6:00 00:00 24:00 hh:mm 542 Mo-Su : 1. Phase OFF 22:00 00:00 24:00 hh:mm 543 Mo-Su : 2. Phase ON 24:00 00:00 24:00 hh:mm 544 Mo-Su : 2. Phase OFF 24:00 00:00 24:00 hh:mm 545 Mo-Su : 3. Phase ON 24:00 00:00 24:00 hh:mm 546 Mo-Su : 3. Phase OFF 24:00 00:00 24:00 hh:mm 556 Standard values NO Time program 4/HW Parameter Function Factory settings Min. Max. Units 560 Preset Mo-Su 00:00 24:00 hh:mm 561 Mo-Su : 1. Phase ON 6:00 00:00 24:00 hh:mm 562 Mo-Su : 1. Phase OFF 22:00 00:00 24:00 hh:mm 563 Mo-Su : 2. Phase ON 24:00 00:00 24:00 hh:mm 564 Mo-Su : 2. Phase OFF 24:00 00:00 24:00 hh:mm 565 Mo-Su : 3. Phase ON 24:00 00:00 24:00 hh:mm 566 Mo-Su : 3. Phase OFF 24:00 00:00 24:00 hh:mm 576 Standard values NO Time program 5 Parameter Function Factory settings Min. Max. Units 600 Preset Mo-Su 00:00 24:00 hh:mm 601 Mo-Su : 1. Phase ON 6:00 00:00 24:00 hh:mm 602 Mo-Su : 1. Phase OFF 22:00 00:00 24:00 hh:mm 603 Mo-Su : 2. Phase ON 24:00 00:00 24:00 hh:mm 604 Mo-Su : 2. Phase OFF 24:00 00:00 24:00 hh:mm 605 Mo-Su : 3. Phase ON 24:00 00:00 24:00 hh:mm 606 Mo-Su : 3. Phase OFF 24:00 00:00 24:00 hh:mm 616 Standard values NO Holidays HC1 Parameter Function Factory settings Min. Max. Units 641 Preset Start dd.mm 643 End dd.mm 648 Type of operation Anti-frost protection Anti-frost protection, hh:mm Setback Holidays the selected operating mode for heating for a long period. The function is activated by the date set in parameter 642 and ends at 00:00 of the date set in the parameter 643. Holidays HC2 (only if activated) Parameter Function Factory settings Min. Max. Units 651 Preset Start dd.mm 653 End dd.mm 658 Type of operation Anti-frost protection Anti-frost protection, hh:mm Setback Holidays HC3 (only if activated) Parameter Function Factory settings Min. Max. Units 661 Preset Start dd.mm 663 End dd.mm 668 Type of operation Anti-frost protection Anti-frost protection, hh:mm Setback 22

23 Heating circuit 1 Parameter Function Factory settings Min. Max. Units 710 Comfort temperature 20 Line 712 Line 716 C 712 Setback temperature 16 Line 714 Line 710 C 714 Anti-frost temperature 10 4 Line 712 C 720 Heating curve slope Summer / winter automatic /8 30 C 742 Req. T Run-up Room Thermostat 65 Line 740 Line 741 C 855 Cur. req. drying temp C 856 Current drying day Comfortable temperature required room temperature that will be maintained at the heating phase. Setback temperature required room temperature that will be maintained at the setback phase. Anti-frost temperature setting of the required anti-frost room temperature. Heating curve slope the value shows the heat curve setting, see Fig. No. 18 Summer/winter automatic temperature limit for switching between summer and winter mode. Req. T Run-up Room Thermostat the temperature to which the boiler will heat when the outside sensor is not used. Current req. drying temp setting of the temperature for drying of the floor heating. Current drying day setting of the drying day for the floor heating. Hot water Parameter Function Factory settings Min. Max. Units 1610 Rated temperature C Nominal temperature setting the required comfortable hot water temperature. Set heating curve uses the required room temperature of 20 C. If the required/room temperature changes, the heating curve changes as well. The heating curve shows the required temperature to the heating circuit depending on the corrected outside temperature. When using the room unit QAA74, QAA75 etc, in addition, the heating curve is corrected by the parameters Set room temperature and Room influence. 23

24 8.4 Error messages Table 6 shows a list of the most common fault conditions of the boiler. In case of displaying a different error message, please contact service. Error messages If you see this symbol, it is the fault. Press the info button and read further information. Maintenance or special operation If you see this symbol, it presents a service message or a special operation. Press the info button and read further information. Tab.. 6 Error code Description of error Reason/Solution 10 Short-circuit/interruption of the outside Check the outside temperature sensor temperature sensor Contact service 50 Short-circuit/interruption of the HW Check the HW sensor sensor Contact service 110 The boiler is overheated, electronic Let the device cool down and restart it by pressing the Reset safety thermostat is off. button 111 The pump is defective or thermostatic valves are closed, there was the initiation of the temperature sensor. 119 There is and initiation of the water pressure switch. In case of recurrence of the error contact service Open the thermostatic valves In case of recurrence of the error contact service Check the water pressure, refill water is the pressure is low 128 Loss of flame during operation Rerun the boiler by pressing the Reset button In case of recurrence of the error contact service 133 Controlling and regulating control panel Rerun the boiler by pressing the Reset button is locked. Possible causes: lack of gas, In case of recurrence of the error contact service no ignition. 8.5 Faults Fault Reason Solution The boiler No voltage at the boiler Check whether the power cord is plugged in and whether there does not is voltage in the socket. ignite Insufficient or stopped gas supply Check opening of the gas main supply and shut-off valve of the boiler. There is no requirement for heating and Check the settings of the operating mode HW Room temperature of the room does not match No HW heating Shutdown at the fault Incorrect Date and Time settings Set Date and Time The boiler is in summer mode (switched off from the outside temperature) Low water pressure Refill water to the system Time program of the heating does not match the required one Set room temperature does not match the required one The boiler can be put into operation by switching the operating mode for permanent comfort Check and, if necessary, adjust setting of the day of the week, time and date Change of the time program of the heating Check and, if necessary, adjust the room temperature, adjust the parameter 720 Heating curve slope and Room influence (parameter of the Service settings) HW heating is off Check and, if necessary, turn on the hot water heating (see Fig. no Pos. A) Comfort required temperature is too Check and, if necessary, adjust the comfort required low temperature Incorrect Date and Time settings Check and, if necessary, adjust setting of the day of the week, time and date HW sensor has poor contact with the Check HW sensor tightening heater housing Three-way valve does not switch Check the connection and switching of the three-way valve. See Table. no. 6 See Table. no. 6 Contact service 24

25 ATTENTION! Boiler sensors do not work as the signalling equipment. When the floor heating is used, it must be provided by an external thermostat. Otherwise, in the case of manual opening of the three-way valve, the floor heating may be damaged. 9 Maintenance The boiler housing can be washed using lukewarm detergent solution. All other maintenance can be performed only by a contractual service organization trained by the manufacturer! 9.1 Checking the device 1. Unplug the boiler by unplugging the cord from the mains. Close the gas supply, remove the front cover of the boiler. 2. Disconnect the fan connectors. 3. Disconnect the gas supply to the mixer. 4. Disconnect the silicone hose from the mixer. 5. Disconnect the grounding conductor of the electrode. 6. Remove the burner plate and the fan (unscrew 4 nuts M6). 7. Clean the burner using a steel brush and purge with air. Remove possible impurities on the ignition electrode using emery paper. 8. Check mixer visually. 9. The body should be cleaned using one of the following ways: a) Spray Metanotherm through the burner chamber on the body convection surface. b) Pour diluted soap solution through the burner chamber - leave for 10 min. and rinse with clean water. Any impurities will be discharged through a siphon. 10. Install the burner plate by means of 4 nuts and washers M6, connect the fan connectors according to the wiring. Then connect: - silicone hose to the mixer, - gas inlet to the mixer, - grounding wire to the ignition electrode. When assembling various parts, it is necessary to take care they are assembled in the correct order and direction. All seals that were removed during assembly, must be checked and replaced, if necessary. 11. Open gas supply uwing the ball valve. 12. Check all el. parts which had to be disconnected, whether they are connected to the respective locations according to the wiring diagram, and plug the cord to the mains. 13. Check for gas leaks using a gas detector or foaming solution. 14. It is necessary to check whether the burner plate is well-sealed and tightened using the gas detector. 15. Check the pressure in the heating system using a pressure gauge on the boiler and check the safety valve functionality. If there is the pressure drop in the system, refill the central heating system with water to the required value. 80 kpa (0.8 bar). 16. Mount the front cover 17. Check the boiler setting according to chap. no. 7.7 and check the performance according to the consumption readings at the gas meter. 25

26 10 IMPORTANT NOTICE For the installation and adjustment of the boiler it is necessary to call a service organization trained by the manufacturer. The boiler may only be used for the intended purposes. The boiler may be operated only by adult persons in accordance with these instructions. The boiler is not intended for use by persons (including children) whose physical, sensory or mental disability or lack of experience and knowledge prevents them from safe use of the appliance, unless they are supervised or instructed on the use by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance. The boiler is fully automatic, it is not recommended to disconnect it from the mains. The boiler is equipped with automatic anti-freeze protection (if it is plugged to the mains). it is forbidden to interfere with the secured parts. No flammable objects must be placed, installed or hung near the boiler and the flue gas exhaust (safety distance of an appliance from flammable materials in the direction of the main radiation is 50 mm, in other directions it is 10 mm). The safe distance of boiler and flue gas exhaust from flammable materials must be observed. If there are any construction works performed near the boiler, switch the boiler off and protected against pollution. If there are any adjustment works performed near the boiler (works with paints, glues, etc.), switch the boiler off and protected against pollution. Do not clean the boiler by flammable or explosive means. In winter (e.g. when going on holiday), checking of the boiler functions and the whole heating system must be ensured to the necessary extent, to avoid water freezing and the damage to the device due to the external causes (electricity failure, fuel gas supply failure etc.). Due to a long-term electricity failure in the heating period, it is necessary to add to the system a manufacturer-approved antifreeze for this type of boiler or drain the system to avoid freezing of the heating system and the boiler. For the boilers with flue gas exhaust into the surroundings through an external wall of the building, it is necessary to check at a frosty weather that the condensed water from flue gas in the exhaust basket does not freeze. The boiler is supplied with electric power of 230 V. In case of fire, extinguish the boilers as an el. device. Beware of gas leaks (if you have suspicion of gas escaping, shut off the gas intake, ventilate - contact service organization). The gas valve under the boiler must always be accessible. It is necessary to avoid combustion air pollution with halogen hydrocarbons (contained in sprays, solvents, paints, glues etc.) and dust. When assembling, installing and operating the appliance, it is necessary to comply with the rules that apply in the country of destination. In case of failure to comply with these conditions, it is not possible to claim warranty repairs. 11 Instructions for product disposal after its service life VIADRUS a.s. is a contract partner of EKO KOM a.s. with the client number F Packages comply with CSN EN Packaging should be disposed of as follows: - plastic foil, cardboard - waste disposal organization - metal strapping tape - waste disposal organization - wooden packing is designed for a single use and cannot be used further as a product. Its disposal is subject to the Act 477/2001 Coll. and 185/2001 Coll. as amended. Individual parts of the boiler should be disposed of as follows: - exchanger (aluminum alloy) - waste disposal organization - pipe distributions, housing - waste disposal organization - other metal parts - waste disposal organization - insulating material - waste disposal organization With the loss of useful properties of the product, it is possible to return the product back (if applicable), if the originator has declared that it is waste, the waste should be disposed according to the valid legislation of the relevant country. 26

VIADRUS K 5 Manual for boiler operation and installation

VIADRUS K 5 Manual for boiler operation and installation VIADRUS K 5 Manual for boiler operation and installation GB_2017_41 GB_2016_42 1 Content: page 1 Produced versions of boilers... 3 2 Usage and advantages of the boiler... 3 3 Technical data... 4 4 Boiler

More information

VIADRUS P7C Manual for boiler operation and installation

VIADRUS P7C Manual for boiler operation and installation VIADRUS P7C Manual for boiler operation and installation GB_2016_50 GB_2015_47 Content: p. 1 Boiler Use and Advantages... 3 2 Technical parameters of the boiler... 3 3 Description... 7 3.1 Boiler Construction...

More information

VIADRUS K4 Manual for boiler operation and installation

VIADRUS K4 Manual for boiler operation and installation VIADRUS K4 Manual for boiler operation and installation GB_2017_24 GB_ 2015_31 Table of Contents page General Information 1 Produced Versions of the Boilers... 3 2 Boiler Application and Benefits... 3

More information

HERCULES U 32 Manual for boiler operation and installation

HERCULES U 32 Manual for boiler operation and installation HERCULES U 32 Manual for boiler operation and installation GB_2017_20 GB_2015_46 Content p. 1 Boiler Use and Advantages... 3 2 Technical parameters of the boiler... 3 3 Description... 5 3.1 Boiler Construction...

More information

WALL HUNG GAS BOILER FOR C.H. AND PREDISPOSTION FOR INSTANTANEOUS D.H.W. PRODUCTION (with optional kit) MODELS 34,8 kw (depotenziata) 50 C

WALL HUNG GAS BOILER FOR C.H. AND PREDISPOSTION FOR INSTANTANEOUS D.H.W. PRODUCTION (with optional kit) MODELS 34,8 kw (depotenziata) 50 C ALKON 50 C ALKON 70 C WALL HUNG GAS BOILER FOR C.H. AND PREDISPOSTION FOR INSTANTANEOUS D.H.W. PRODUCTION (with optional kit) OUTPUT RANGE from 50 to 560 kw (in battery) WORKING TEMPERATURE no limit on

More information

1. Order and Auxiliaries

1. Order and Auxiliaries VIADRUS Hercules G U26 90 MANUAL FOR ASSEMBLY Návod OF BOILER k obsluze Contents: page 1. Order and Auxiliaries...3 1.1 Order...3 1.2 Delivery a accessories...3 2. Boiler Uses and Advantages...4 3. VIADRUS

More information

VIADRUS A0C Manual for boiler operation and installation

VIADRUS A0C Manual for boiler operation and installation VIADRUS A0C Manual for boiler operation and installation GB_2016_31 GB_2016_28 Content: page 1 Usage and advantages of the boiler... 3 2 Technical data of the boiler... 4 3 Description... 11 3.1 Boiler

More information

/2010 US/CA

/2010 US/CA 6 720 646 148-11/2010 US/CA (en) For the user User s Instructions Condensing gas boiler Logamax plus GB162-L.B. 80 kw/100 kw Please read thoroughly before operating This manual is available in the English

More information

HERCULES Gre H e e n rc E u c l o e s T e 2 r 6

HERCULES Gre H e e n rc E u c l o e s T e 2 r 6 HERCULES Green Hercules Eco Therm U26 MANUAL FOR BOILER Návod OPERATION k obsluze AND INSTALATION Contents: page 1. Produced variants of boiler... 3 2. Technical data of the boiler... 4 3. Boiler description...

More information

PANTHER P Automatic Boiler Operator's Manual

PANTHER P Automatic Boiler Operator's Manual KOVARSON s.r.o. Lhota u Vsetína 4 755 01, Vsetín tel. CZ: +420 571 420 926 tel. SK: +421 949 176 717 email: info@kovarson.cz PANTHER P Automatic Boiler Operator's Manual - 1 - Dear Customer, Thank you

More information

VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power

VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power VICTRIX 90 is the new wall-hung condensing boiler for room heating only, set-up for independent functioning and for that in cascade mode

More information

VI He ADrcules U26 RUS G 350 CALOR SRL -

VI He ADrcules U26 RUS G 350 CALOR SRL   - VIADRUS Hercules G U26 350 MANUAL FOR BOILER Návod OPERATION k obsluze AND INSTALLATION Table of contents: page 1. Boiler use and advantages... 3 2. Boiler VIADRUS G 350 technical data... 4 3. Description...

More information

VIADRUS A2C Manual for boiler operation and installation

VIADRUS A2C Manual for boiler operation and installation VIADRUS A2C Manual for boiler operation and installation GB_2016_31 GB_2016_28 Content: page 1 Usage and advantages of the boiler... 3 2 Technical data of the boiler... 4 3 Description... 8 3.1 Boiler

More information

VIADRUS U 22 Manual for boiler operation and installation

VIADRUS U 22 Manual for boiler operation and installation VIADRUS U 22 Manual for boiler operation and installation GB_2017_14 LP GB_2015_24 Contents page 1 Usage and advantages of the boiler... 3 2 Technical data of the boiler... 3 3 Description... 4 3.1 Construction

More information

VIADRUS A0C Manual for boiler operation and installation

VIADRUS A0C Manual for boiler operation and installation VIADRUS A0C Manual for boiler operation and installation GB_2017_30 GB_2016_28 Content page 1 Usage and advantages of the boiler... 3 2 Technical data of the boiler... 3 3 Description... 6 3.1 Boiler structure...

More information

1 VICTRIX ZEUS Superior kw I features

1 VICTRIX ZEUS Superior kw I features Wall-hung condensing VICTRIX ZEUS Superior kw I is the new range of wall-hung condensing boilers with 54 litre stainless steel storage tank available in two versions with nominal heat output of 26 kw and

More information

AVIO kw Export 1 FEATURES. Wall-mounted with storage tank

AVIO kw Export 1 FEATURES. Wall-mounted with storage tank 1 FEATURES Wall-mounted with storage tank Compact wall-mounted open chamber boiler with conventional flue and 45 litre stainless steel storage tank and nominal heat output of 23.7 kw (20,382 kcal/h). AVIO

More information

USER GUIDE. IMAX XTRA EL kW. For Installation Guide see reverse of book

USER GUIDE. IMAX XTRA EL kW. For Installation Guide see reverse of book USER GUIDE IMAX XTRA EL 320-620kW For Installation Guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

WHE 2.24 / WHE 2.24 FF

WHE 2.24 / WHE 2.24 FF EN Wall-hung gas boilers WHE 2.24 WHE 2.24 FF User Guide 300011777-001-C . Contents 1 Introduction.............................................................................3 1.1 Symbols used...........................................................................................3

More information

PELLETS BURNER 15-60kW MOC

PELLETS BURNER 15-60kW MOC PELLETS BURNER 15-60kW MOC. Please read those documentation before first start up the unit. Improper burner start may lead to its damage and may create a danger for end user! Table of Contents: 1. Admission

More information

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Hybrid 20

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Hybrid 20 INSTALLATION, OPERATION AND MAINTENANCE Ariterm Hybrid 20 TABLE OF CONTENTS General...3 Installation... 4-5 Dimensions - with flue gas exhauster...6 Dimensions - without flue gas exhauster...7 Pipe installations...8

More information

Operating instructions

Operating instructions Operating instructions Capriz 2 24c 28c GB, IE Contents Contents 1 Safety... 3 1.1 Action-related warnings... 3 1.2 Intended use... 3 1.3 General safety information... 4 2 Notes on the documentation...

More information

VIADRUS A0C Manual for boiler operation and installation

VIADRUS A0C Manual for boiler operation and installation VIADRUS A0C Manual for boiler operation and installation GB_2017_45 LP GB_2016_28 Content page 1 Usage and advantages of the boiler... 3 2 Technical data of the boiler... 3 3 Description... 5 3.1 Boiler

More information

USERS MANUAL FOR GAS BOILERS

USERS MANUAL FOR GAS BOILERS USERS MANUAL FOR GAS BOILERS PLEASE READ THE MANUAL CAREFULLY: IT CONTAINS IMPORTANT INFORMATION REGARDING SAFETY, INSTALLATION, USE AND MAINTENANCE OF THE APPLIANCE MODELS: NOVADENS 24 NOVADENS 24C NOVADENS

More information

Operating instructions

Operating instructions The energy you need Operating instructions Betacom 3 24c -A (H-GB) 30c -A (H-GB) GB, IE Contents Contents 1 Safety... 3 1.1 Action-related warnings... 3 1.2 Intended use... 3 1.3 General safety information...

More information

Great Britain en. Installation, user and service manual. Control panel HMI Gas 310/610 ECO PRO

Great Britain en. Installation, user and service manual. Control panel HMI Gas 310/610 ECO PRO Great Britain en Installation, user and service manual Control panel HMI Gas 310/610 ECO PRO Dear Customer, Thank you very much for buying this appliance. Please read through the manual carefully before

More information

The competent brand for energy saving systems NEW. Gas-combi boiler CGG-1K-24/28

The competent brand for energy saving systems NEW. Gas-combi boiler CGG-1K-24/28 The competent brand for energy saving systems NEW Gas-combi boiler CGG-1K-24/28 Gas-combi boiler CGG-1K Technical data room sealed fannned flue model gas combi boiler for low temperature heating and d.h.w.

More information

INSTRUCTION FOR THE USER THC V E OIL BLU

INSTRUCTION FOR THE USER THC V E OIL BLU INSTRUCTION FOR THE THC V E OIL BLU CONTENTS General safety information 4 Precautions 4 Control panel 5 Mode selection 8 User levels 10 Start-up 12 Temporary shutdown 15 Preparing for extended periods

More information

INSTRUCTION MANUAL & SERVICE MANUAL ORLIGNO 400

INSTRUCTION MANUAL & SERVICE MANUAL ORLIGNO 400 INSTRUCTION MANUAL & SERVICE MANUAL ORLIGNO 400 Content 1. Delivery......................................................................... 3 2. Installation and assembly.........................................................

More information

Hercules U2 LIGNAT 6

Hercules U2 LIGNAT 6 Hercules LIGNATOR U26 MANUAL FOR BOILER Návod OPERATION k obsluze AND INSTALLATION Table of contents: page 1. Boiler use and advantages... 3 2. LIGNATOR boiler technical data... 4 3. Description... 7 3.1

More information

UNI. Cast-iron solid fuel boiler. Installation and operating instructions

UNI. Cast-iron solid fuel boiler. Installation and operating instructions UNI Cast-iron solid fuel boiler Installation and operating instructions Rev. June 2010 Content: 1. Introduction 2. Characteristics of boilers 3. Technical parameters 4. Delivery and accessories 5. Location

More information

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-i.

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-i. Additional Operating Instructions SITRANS F Vortex flowmeters Ex-i Edition 09/2018 CONTENTS 1 Safety instructions 3 1.1 General notes... 3 1.2 EU conformity... 3 1.3 Approval according to the IECEx scheme...

More information

VIADRUS HERCULES U 24 Manual for boiler operation and installation

VIADRUS HERCULES U 24 Manual for boiler operation and installation VIADRUS HERCULES U 24 Manual for boiler operation and installation GB_2014_21 Table of contents page 1. Technical information... 3 1.1 Usage... 3 1.2 Boiler advantages... 3 1.3 Boiler technical data...

More information

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A... 70 80 99-00-O Residential Gas Condensing Boiler ZBR//8/35/4-3A... ZWB8/35/4-3A... 70 80 993 (03/03) CA/US Operating Instructions Contents Contents Key to symbols and safety instructions............................

More information

Heat 45 & 55. User Instructions FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER

Heat 45 & 55. User Instructions FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER Heat 45 & 55 User Instructions FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER CE/PI No. 86-CN-69 Heat 45 - GC No. 41-930-40 Heat 55 - GC No. 41-930-41 These instructions

More information

Operating instructions

Operating instructions Operating instructions For the operator Operating instructions ecotec plus Gas-fired wall-hung high-efficiency boiler GB, IE Publisher/manufacturer Vaillant GmbH Berghauser Str. 40 D-42859 Remscheid Telefon

More information

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data. ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data. The RVA63 controller can be utilized to control the following system configurations via LPB communication. Equipment Required

More information

TECHNICAL MANUAL ASGX

TECHNICAL MANUAL ASGX TECHNICAL MANUAL ASGX MEDIUM/HIGH PRESSURE HOT WATER BOILER INDEX 1 TECHNICAL CHARACTERISTICS... 2 1.1 GENERAL... 2 1.2 TECHNICAL DATA... 2 2 ACCESSORIES... 3 2.1 PRESSURE... 3 Pressure gauge... 3 Operation

More information

TECHNICAL PROPERTIES OF THE APPLIANCE

TECHNICAL PROPERTIES OF THE APPLIANCE TGR 30-120 SM EN Dear buyer, thank you for purchasing our product. Prior to the installation and first use of the electric water heater, please read these instructions carefully. THIS APPLIANCE IS NOT

More information

24/31-28/35-33/40 kw Premix System Condensing - ErP Combi Gas Boilers. Enerwa / EnerwaPlus.

24/31-28/35-33/40 kw Premix System Condensing - ErP Combi Gas Boilers. Enerwa / EnerwaPlus. 24/31-28/35-33/40 kw Premix System Condensing - ErP Combi Gas Boilers Enerwa / EnerwaPlus www.warmhaus.com Condensing-ErP Premix System Boilers 24/31-28/35-33/40 kw Warmhaus wall-hung gas combi boilers

More information

Installer manual ELK 213 Immersion heater

Installer manual ELK 213 Immersion heater Installer manual ELK 213 LEK IHB GB 1535-3 031403 Table of Contents 1 English, IHB - ELK 213 General Component positions Pipe connections 2 2 3 5 Disturbances in comfort Accessories Technical data Electrical

More information

Remeha. Fuel oil/gas boilers P 520. Installation and Service Manual A

Remeha. Fuel oil/gas boilers P 520. Installation and Service Manual A Remeha Fuel oil/gas boilers EN Installation and Service Manual 300016859-001-A 63115 Declaration of conformity The appliance complies with the standard model described in declaration of compliance. It

More information

Operating instructions

Operating instructions Operating instructions For the operator Operating instructions HOME SYSTEM GB, IE Publisher/manufacturer Vaillant GmbH Berghauser Str. 40 D-42859 Remscheid Tel. +49 21 91 18 0 Fax +49 21 91 18 28 10 info@vaillant.de

More information

R40 (Evolution Range) Gas-Fired, Wall Hung Condensing Boiler Boiler Options & Systems Planner Manual

R40 (Evolution Range) Gas-Fired, Wall Hung Condensing Boiler Boiler Options & Systems Planner Manual R40 (Evolution Range) Gas-Fired, Wall Hung Condensing Boiler Boiler Options & Systems Planner Manual STOKVIS ENERGY SYSTEMS Unit 34 Central Park Estate 34 Central Avenue West Molesey Surrey KT8 2QZ Tel:

More information

Hercu Wle o s o U dp2

Hercu Wle o s o U dp2 Hercules Woodpell U26 MANUAL FOR BOILER Návod OPERATION k obsluze AND INSTALLATION Table of contents: page 1. Produced variants of boiler...3 1.1 Order...3 2. Use and advantages of boiler...3 3. Boiler

More information

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND Aqua Balance AquaBalance TM CONTROL MODULE QUICK START GUIDE 10 1 Domestic Hot Water temperature setpoint decreasing button 2 Domestic Hot Water temperature setpoint increasing button 3 Central Heating

More information

Operating manual. Pellet boiler. Orlan Pellet ISO 9001

Operating manual. Pellet boiler. Orlan Pellet ISO 9001 Operating manual Pellet boiler Orlan Pellet ISO 9001 Contens 1. Boiler s use...................................................................... 3 2. Boiler s way of working...........................................................

More information

HIGH POWER. VICTRIX PRO 2 ErP. High power, wall-hung condensation boiler

HIGH POWER. VICTRIX PRO 2 ErP. High power, wall-hung condensation boiler HIGH POWER VICTRIX PRO 2 ErP High power, wall-hung condensation boiler MAIN INDEX INDEX 1 VICTRIX PRO 35-55 2 ErP SPECIFICATIONS...5 2 VICTRIX PRO 80-100-120 2 ErP SPECIFICATIONS...6 3 VICTRIX PRO 35-55

More information

STORAGE WATER HEATERS

STORAGE WATER HEATERS Owners Manual STORAG WATR HATRS RBC 200, RBC 300, RBC 400, RBC 500, RBC 500HP, RBC 750, RBC 1000, RBC 1000HP, RBC 1500, RBC 2000, RBC 3000 N v. 1.4 CONTNTS 1 Description... 3 1.1 Models... 3 1.2 Tank protection...

More information

USER'S INFORMATION MANUAL

USER'S INFORMATION MANUAL USER'S INFORMATION MANUAL : If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use gasoline

More information

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data.

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data. ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data. The RVA 46 Zone Controller can only be used in conjunction with a RVA47 controlled boiler installation. The RVA46 controller

More information

ASSEMBLY INSTRUCTIONS FOR THE PUMP AND CONTROL UNIT ZPS 18a-01

ASSEMBLY INSTRUCTIONS FOR THE PUMP AND CONTROL UNIT ZPS 18a-01 ASSEMBLY INSTRUCTIONS FOR THE PUMP AND CONTROL UNIT ZPS 18a-01 1. Use and construction of the pump and control unit The pump and control unit is designed to work with solar collectors in systems with required

More information

VIADRUS HERCULES Hercules U U26 AND INSTALLATION

VIADRUS HERCULES Hercules U U26 AND INSTALLATION VIADRUS HERCULES Hercules U U26 MANUAL FOR BOILER Návod OPERATION k obsluze AND INSTALLATION Table of contents: page 1. Boiler use and advantages... 3 2. Boiler technical data... 3 3. Description... 8

More information

VIADRUS HERCULES U26 ECO Manual for boiler operation and installation

VIADRUS HERCULES U26 ECO Manual for boiler operation and installation VIADRUS HERCULES U26 ECO Manual for boiler operation and installation GB_2015_21 GB_2016_48 Table of contents: page 1 Boiler use and advantages... 3 2 Boiler technical data... 3 3 Description... 6 3.1

More information

WOLF GAS CONDENSING BOILERS COMFORTLINE

WOLF GAS CONDENSING BOILERS COMFORTLINE WOLF GAS CONDENSING BOILERS COMFORTLINE CGB-35/50 / CGB-75/100 30m 3 /h THE EXTENSIVE EQUIPMENT RANGE from system supplier WOLF offers the ideal solution for commercial and industrial buildings, new build

More information

Glass and Dishwashers AMX / AUX Series

Glass and Dishwashers AMX / AUX Series Glass and Dishwashers AMX / AUX Series INSTALLATION OPERATION REV. 8.xx 04.07.2005 Installation and Operation Instructions for Models of AMX / AUX Series Content Page 1 Installation... 3 2 Connections...

More information

SOLID FUEL HEATING UNIT TYPES NPS 35 AND NPS 70 ORIGINAL INSTRUCTION MANUAL

SOLID FUEL HEATING UNIT TYPES NPS 35 AND NPS 70 ORIGINAL INSTRUCTION MANUAL SOLID FUEL HEATING UNIT TYPES NPS 35 AND NPS 70 ORIGINAL INSTRUCTION MANUAL 1. General information The Original Instruction Manual constitutes an integral and material part of the product, and is to be

More information

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Vedo

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Vedo INSTALLATION, OPERATION AND MAINTENANCE Ariterm Vedo CONTENTS General...3 Installation...4-5 Laddomat 21 Connection diagram...6 Temperature control valve...7 About burning wood...8 Operation...9-11 Service

More information

VIADRUS HERCULES U 26 Manual for boiler operation and installation

VIADRUS HERCULES U 26 Manual for boiler operation and installation VIADRUS HERCULES U 26 Manual for boiler operation and installation GB_2016_48 2010 GB_ 2015_20_model 2010 Table of contents: page 1 Boiler use and advantages... 3 2 Boiler technical data... 3 3 Description...

More information

VICTRIX Superior kw Export VICTRIX Superior kw X Export

VICTRIX Superior kw Export VICTRIX Superior kw X Export Wall-hung condensing VICTRIX Superior kw is the instantaneous sealed chamber wallhung boiler with power of 32 kw which, thanks to condensation technology, is characterised for its high efficiency and guarantees

More information

Protection and Control of Solid Fuel Boilers

Protection and Control of Solid Fuel Boilers Protection and Control of Solid Fuel Boilers thermal relief valves thermostatic valves and pump stations draft regulators www.regulus.eu BOILER PROTECTION AGAINST OVERHEATING Solid fuel boilers may get

More information

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use GB122 7210 1300-12/2002 GB(EN) For trade use Servicing manual Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C Please read thoroughly before attempting to diagnose fault List of contents

More information

MANUAL FOR ASSEMBLY OF BOILER VIADRUS G 300

MANUAL FOR ASSEMBLY OF BOILER VIADRUS G 300 MANUAL FOR ASSEMBLY OF BOILER VIADRUS G 300 Date of revision 8/2007 Contents: 1. Boiler use and advantages...3 2. VIADRUS GLADIATOR G 300 Boiler Technical Data...4 3. Generally...6 4. Boiler Installation...6

More information

HEAT RECOVERY AIR HANDLING UNIT

HEAT RECOVERY AIR HANDLING UNIT HEAT RECOVERY AIR HANDLING UNIT OPERATION MANUAL KOMFORT_L v2(2)_en.indd 1 07.08.2015 15:0:44 CONTENTS Introduction General Safety regulations Transportation and storage regulations Manufacturer's warranty

More information

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use GB122 Servicing manual Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C For trade use Please read thoroughly before attemting to diagnose fault 7217 4900 (03/2010) GB/IE List of contents

More information

T UNI 7000 F. Operating instructions For the user (2006/05) AU/GB

T UNI 7000 F. Operating instructions For the user (2006/05) AU/GB 6 720 648 662-00.1T UNI 7000 F Operating instructions For the user AU/G 2 Contents Contents Contents 2 1 Safety information and explanation of symbols 3 1.1 For your safety 3 1.2 Explanation of symbols

More information

Main Features. Functions. with automatic ignition and control functions for the heating and domestic hot water circuit

Main Features. Functions. with automatic ignition and control functions for the heating and domestic hot water circuit 7 618 Gas Burner Controls with automatic ignition and control functions for the heating and domestic hot water circuit ISO 9001 Microprocessor-based gas burner controls providing all control functions

More information

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A cod. 6272262A GENERAL DATA Heating Data Heat Output Input (Adjustable) (Adjustable) Format 34i 11.2 34KW 45 145MJ/hr Format 34e 11.2 34KW 45 145MJ/hr General Specifications FORMAT 34i 34e Main burner injectors

More information

ir-range 8G /03.15 Changes reserved.

ir-range 8G /03.15 Changes reserved. U s e r m a n u a l ic-range is-range ir-range 8G.52.80.00/03.15 Changes reserved. Contents 1. Introduction...3 2. Safety...5 3. Boiler description...6 4. Display and functions...7 4.1 DHW and Heating

More information

ENERGY TOP. Condensing boiler solutions

ENERGY TOP. Condensing boiler solutions ENERGY TOP Condensing boiler solutions 1 ENERGY TOP > ENERGY TOP RANGE A wide array of flexible solutions both for centralised residential application and big commercial plants The increasing need for

More information

Residential Gas Condensing Boiler Greenstar combi 100 p / 151 p ZWB28-3A... ZWB42-3A...

Residential Gas Condensing Boiler Greenstar combi 100 p / 151 p ZWB28-3A... ZWB42-3A... Residential Gas Condensing Boiler Greenstar combi 00 p / 5 p ZWB8-3A... ZWB4-3A... Operating Instructions 708733 (07/04) US/CA Contents Contents Explanation of symbols and safety instructions.......................

More information

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER Heating Circuit ZONE Controller RVA 46.531/109 Zonal temperature controller for control of a lowtemperature heating system, for use with condensing gas boilers Instructions for the INSTALLER INDEX Page

More information

Air Comfort. Installation instructions (English) A

Air Comfort. Installation instructions (English) A Air Comfort Installation instructions (English) WWW.BRINKAIRFORLIFE.NL 614788-A This appliance may be used by children as of 8 years of age, persons of reduced mental or physical capacities and those of

More information

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler Gas boiler UPON COMPLETION OF THE INSTALLATION THE INSTALLER MUST INSTRUCT THE OWNER AND OPERATOR ON THE FUNCTIONALITY AND THE PROPER OPERATION OF THE BOILER AND THE HEATING SYSTEM. INSTALLER MUST REVIEW

More information

Planner Documentation R600 EVO

Planner Documentation R600 EVO Planner Documentation R600 03/2017 Contents Gas condensing boiler R600 Models and output... 4 Application possibilities... 4 Value propositions... 4 Technical description Description... 4 Technical data...

More information

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en 8 716 473 216-00.3O Gas boiler WBN 6000-30-H-E-N/L-S2400 Operating instructions for the end customer en 2 Contents Contents 1 Key to symbols and safety instructions................... 2 1.1 Key to symbols..................................

More information

ecotec pro Operating instructions Operating instructions For the operator GB, IE Gas-fired wall-hung high-efficiency boiler

ecotec pro Operating instructions Operating instructions For the operator GB, IE Gas-fired wall-hung high-efficiency boiler Operating instructions For the operator Operating instructions ecotec pro Gas-fired wall-hung high-efficiency boiler GB, IE Publisher/manufacturer Vaillant GmbH Berghauser Str. 40 D-42859 Remscheid Tel.

More information

GB24 & GB30. User Manual

GB24 & GB30. User Manual GB24 & GB30 User Manual BOILER OUTPUT To Domestic Hot Water:To Central Heating: GB24/30 Minimum 8.0 kw (27,296 Btu/h) GB24 Maximum 24.2 kw (82,570 Btu/h) GB30 Maximum 30.3 kw (103,384 Btu/h) GB24/30 Minimum

More information

INSTALLATION AND OPERATING INSTRUCTIONS EVOLUTION EV HFM

INSTALLATION AND OPERATING INSTRUCTIONS EVOLUTION EV HFM INSTALLATION AND OPERATING INSTRUCTIONS EVOLUTION EV HFM Thank you for choosing a DOMUSA TEKNIK heating boiler. From the range of DOMUSA TEKNIK products you have chosen the Evolution EV HFM model. This

More information

VIADRUS HERCULES ECO Manual for boiler operation and installation

VIADRUS HERCULES ECO Manual for boiler operation and installation VIADRUS HERCULES ECO Manual for boiler operation and installation GB_2015_11 SD Table of contents: page 1. Produced boiler variants...3 1.1 Purchase order...3 2. Boiler usage and advantages...3 3. Boiler

More information

MONOBLOCK NG SERIES GAS BURNERS INSTALLATION, OPERATING AND MAINTENANCE MANUAL

MONOBLOCK NG SERIES GAS BURNERS INSTALLATION, OPERATING AND MAINTENANCE MANUAL MONOBLOCK NG SERIES GAS BURNERS INSTALLATION, OPERATING AND MAINTENANCE MANUAL MODULATING OPERATION ECO 50 NG ECO 55 NG ECO 60 NG ECO 65 NG ECO 70 NG www.ecostar.com.tr DEAR USER, ECOSTAR ECO 50 NG, ECO

More information

SPECIFICATIONS - NIKE

SPECIFICATIONS - NIKE Wall-mounted instant boilers NIKE Mini kw Special is the ideal Immergas solution for modern building and wherever space is limited and has to be made the most of. Simple to use and easy to install, thanks

More information

INSTALLATION AND MANINTENANCE INSTRUCTIONS

INSTALLATION AND MANINTENANCE INSTRUCTIONS INSTALLATION AND MANINTENANCE INSTRUCTIONS Appr. Nr. A 9503 T - 0085 AQ 0765 PEGASUS F2 T HIGH EFFICIENCY GAS-FIRED CAST-IRON BOILERS Models 51-68 - 85-102 2 Contents 1. General technical data 2. Dimensional

More information

IST 03 C ELBA DUAL INSTALLATION, USE AND MAINTENANCE

IST 03 C ELBA DUAL INSTALLATION, USE AND MAINTENANCE IST 03 C 202-01 ELBA DUAL INSTALLATION, USE AND MAINTENANCE GB Thank you for choosing our boilers. Please read these installation and maintenance instructions with care. Please note that the boiler must

More information

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL STREBEL GENEVA CE ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL INDEX TABLE 1 TECHNICAL DATA SECTION 1 SECTION 2 SECTION 3 SECTION 4 SECTION 5 SECTION 6 SECTION 7 SECTION 8 SECTION

More information

Heating, Air Conditioning, Ventilation. Отопление-Кондиционеры-Вентиляция. MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL

Heating, Air Conditioning, Ventilation. Отопление-Кондиционеры-Вентиляция. MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL Heating, Air Conditioning, Ventilation Отопление-Кондиционеры-Вентиляция MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL 1. Usage MTM 8-30 universal oil heater is designed for heating commercial rooms

More information

User Manual FLOWMAX-90. for model. Condensing water heater 85,000 BTU. Installation, operating, commissioning and maintenance instructions.

User Manual FLOWMAX-90. for model. Condensing water heater 85,000 BTU. Installation, operating, commissioning and maintenance instructions. User Manual for model FLOWMAX-90 Condensing water heater 85,000 BTU WARNING If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal

More information

RS /E-EV C01 SERIES

RS /E-EV C01 SERIES The well-known RS 300-800/E-EV BLU Burner Series, till now available up to 8 MW, has been upgraded with two new powerful burner models, the RS 1000-1200/E-EV C01 models that extend his max output up to

More information

SOLID FUEL RANGE COOKER

SOLID FUEL RANGE COOKER SOLID FUEL RANGE COOKER TYPE 9101 OPERATION & MAINTENANCE MANUAL INSTALLATION MANUAL TYPE 9101 07/2014 1 TYPE 9101 07/2014 2 OPERATION AND MAINTENACE MANUAL Dear customer, Thank you for purchasing of the

More information

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit Operating instructions for the system user VIESMANN With constant temperature or weather-compensated control unit VITODENS 050-W 9/2014 Please keep safe. Safety instructions For your safety Please follow

More information

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59 SOUND-INSULATED FAN OPERATION MANUAL _v.1(2)-en.indd 1 10.08.2015 15:20:59 CONTENT Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 3 Fan design 4 Delivery

More information

PELLET BURNER PV 350

PELLET BURNER PV 350 PELLET BURNER PV 350 INSTRUCTION MANUAL v1.1 1 PRODUCT DESCRIPTION...3 2 SAFETY RULES...3 3 WARNINGS...4 4 INSTALLATION INSTRUCTIONS...5 4.1 BOILER REQUIREMENTS...5 4.2 PELLET CONTAINER...6 4.3 INSTALLATION

More information

HE H R e C rc U u L le E s S U D 2 U 6

HE H R e C rc U u L le E s S U D 2 U 6 HERCULES Hercules DUO U26 MANUAL FOR BOILER Návod OPERATION k obsluze AND INSTALLATION Table of contents: page. 1. Use of boiler and its advantages...3 2. Boiler technical data...3 3. Description...7 3.1

More information

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc Mikrofill Ethos Condensing combination boiler Maintenance Instructions 24cc IMPORTANT Benchmark Installation, Commissioning and Service Record Log Book is enclosed in your customer information pack. This

More information

Open Vented Condensing Boilers

Open Vented Condensing Boilers Dimplex 18 OV Dimplex 32 OV Open Vented Condensing Boilers User s Operating Instructions These instructions should be left with the user Dimplex Boilers 2008 CONTENTS SECTION DESCRIPTION PAGE 1.0 Using

More information

INSTRUCTIONS FOR INSTALLATION AND MANUAL Solid fuel stove for central heating THERMO IN

INSTRUCTIONS FOR INSTALLATION AND MANUAL Solid fuel stove for central heating THERMO IN INSTRUCTIONS FOR INSTALLATION AND MANUAL Solid fuel stove for central heating THERMO IN To respected customer, We are very pleased for your trust and your decision to buy our product. You made a good choice,

More information

DIGITAL MODULATING BOILERS

DIGITAL MODULATING BOILERS DIGITAL MODULATING BOILERS FOR HEATING AND SANITARY HOT WATER CMX15 CMX18 CM15 CM18 INSTALLATI INSTRUCTIS AND USER GUIDE Please read these instructions before installing or using this appliance for the

More information

INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS BG 2000-S (V13) RU PL DE IT ES NL EN 1 662Y0600 A

INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS BG 2000-S (V13) RU PL DE IT ES NL EN 1 662Y0600 A INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS G 2000-S 25-35 - 45-55 60-70 - 100 (V13) 1 Index WARNINGS GAS FLOW RATE DIMSIONS SETTINGS PARAMETERS SERVICING THE URNER 3 8 13 OPERATING DESCRIPTION

More information

Gas Instantaneous Water Heater

Gas Instantaneous Water Heater 6 720 607 823 GB (06.06) SM Installation and Operating Instructions Gas Instantaneous Water Heater WR10..B... WR11..B... With electronic ignition and triple safety system consisting of ionisation detector,

More information

Installation & Manual. Model T-25

Installation & Manual. Model T-25 Installation & Manual TR Central Heating Stove With Solid Fuel Model T-25 Tested according to DIN EN 13240 For product efficiency and emission values, see the declaration of conformity! TABLE OF CONTENTS

More information