SECTION (16510) - INTERIOR LIGHTING
|
|
- Joel Miles
- 5 years ago
- Views:
Transcription
1 SECTION (16510) - INTERIOR LIGHTING Note: This Section includes two (2) attachments. The second and third attachments contain the Light Fixture Matrix. PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Interior Lighting Fixtures 2. Lamps 3. Ballasts 4. Exit Signs 5. Emergency Lighting Units 6. Accessories B. Related Sections: 1. Section (09512) - Acoustical Tile Ceilings 2. Section (16050) - Common Work Results For Electrical. 3. Section (16520) - Exterior Lighting 4. Section (16580) - Lighting Accessories: For programmable lighting control systems, time switches, additional photoelectric relays, power relays, and contactors REFERENCES A. American National Standards Institute (ANSI) Publications: 1. C82.4 Ballasts for High Intensity Discharge and Low Pressure Sodium Lamps (Multiple-Supply Type) B. Institute of Electrical and Electronics Engineers, Inc. (IEEE) Publications: 1. C62.41 Surge Voltages in Low-Voltage AC Power Circuits C. Illuminating Engineering Society (IES) Publications: 1. LM-79 Approved Method: Electrical and Photometric Measurements of Solid-State Lighting Products 2. LM-80 Approved Method: Measuring Lumen Maintenance of LED Light Sources D. National Fire Protection Association (NFPA) Publications: 1. NFPA 70 "National Electric Code" 2. NFPA 101 Life Safety Code E. Underwriter's Laboratories, Inc. (UL) Publications: A Standard For Wire Connectors and Soldering Lugs for Use with Copper Conductors B Standard for Wire Connectors for Use with Aluminum Conductors Emergency Lighting and Power Equipment 1.03 SUBMITTALS A. General: Submit the following in accordance with Conditions of Contract and Division 01 Specification Sections. B. Submit Letter of Conformance in accordance with Section (01330) indicating specified items selected for use in project with the following supporting data. PAGE 1 FILE: a-CFRST-Interior Lighting REVISED: 06/06/ , Marriott International, Inc. CFRST SPECMSTR-NEW BUILD
2 REVISED: 06/06/16 1. For each type of lighting fixture indicated, arranged in order of fixture designation. Include data on features, accessories, and the following: a. Dimensions of fixtures. b. Certified results of laboratory tests for fixtures and lamps for photometric performance. c. Emergency lighting unit battery and charger. d. Fluorescent and high-intensity-discharge ballasts. e. Types of lamps. f. Photometric data. 2. Dimming Ballast Compatibility Certificates: Signed by manufacturer of ballast certifying that ballasts are compatible with dimming systems and equipment with which they are used. 3. Field Test Reports: Indicate and interpret test results for compliance with performance requirements. 4. Maintenance Data: For lighting fixtures to include in maintenance manuals specified in Division QUALITY ASSURANCE A. Fixtures, Emergency Lighting Units, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction. B. Comply with NFPA 70. C. NFPA 101 Compliance: Comply with visibility and luminance requirements for exit signs COORDINATION A. Fixtures, Mounting Hardware, and Trim: Coordinate layout and installation of lighting fixtures with ceiling system and other construction EXTRA MATERIALS A. Furnish extra materials described in Section (01790) Spare Parts and Materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. PART 2 PRODUCTS Note: This Section includes two (2) attachments. The second and third attachments contain the Light Fixture Matrix MANUFACTURERS A. Avendra, LLC Preferred Manufacturers: 1. Subject to compliance with requirements, provide the products indicated for each designation in the Light Fixture Matrix attached at the end of this Section. a. None. B. Approved Manufacturers: 1. Subject to compliance with requirements, provide the products indicated for each designation in the Light Fixture Matrix attached at the end of this Section nd Avenue Design ( ) a. Contact: Jan Zanger ( ) 3. 3Form, Inc. ( ) a. Contact: Janice Eldredge ( ) 4. Acclaim Lighting, Los Angeles, CA ( ) 5. Ashley Lighting Inc. ( ) PAGE 2 FILE: a-CFRST-Interior Lighting Deleted: <#>Note: Include paragraphs below for use with CFRST LEED Volume Program. <#>CFRST LEED Volume Program Manufacturers: <#>Philips Lighting Company ( ) <#>Contractor shall furnish items identified as manufactured by Philips Group Brand Companies, as listed in the Light Fixture Matrix, from the Philips Group Brand Companies only. No substitutions will be approved. <#>Contact: Kathleen Kenny ( <#>Products: <#>Light Fixtures <#>Lamps Deleted: CFRST SPECMSTR-NEW BUILD 2016, Marriott International, Inc.
3 a. Contact: Laurie Foster ( ) 6. B-K Lighting a. Contact: Kahn Wright ( ) 7. Broan-NuTone LLC ( ) a. Contact: Ron Greene ( ) 8. Challenger Lighting Company ( ) a. Contact: Peggy Hart ( x 13) 9. Continental Group ( ) a. Contact: Sean Snyder ( ) 10. Cree LED Lighting Solutionsm ( ) a. Contact: Mark Wanless ( ) b. To obtain special volume pricing and accuracy for Marriott projects, contact: 1) Wiedenbach-Brown Co., Inc. Attn: Buck Buchanan ( ) or Christine Sturm ( x 353) 11. D Style, Inc. ( ) a. Contact: Jacob Shor ( x 118) 12. Eaton Cooper Lighting Business a. Contact: Kathleen Kenny ( ) 13. Electric Mirror LLC ( ) a. Contact: Doug Finefrock ( ) 14. ExceLine, a Philips Group Brand ( ) 15. Forecast, a Philips Group Brand ( ) 16. Hadco, a Philips Group Brand ( ) 17. InLight, a Unilight International Co, ( ) a. Contact: Patrice Adore ( ) 18. Insight Lighting Inc. ( ) a. Contact: Heather Reed ( ) 19. io LED Cooper Lighting ( ) 20. Kichler Lighting ( ) a. Contact: Peggy Hart ( x 13) 21. LBL Lighting, a Generation Brands Company ( ) a. Contact: Joe Krause ( ) 22. Lightolier, a Philips Group Brand ( ) 23. Lithonia Lighting, Accuity Brands, Inc. ( ) 24. Lumark Lighting, Division of Cooper Industries Company ( ) a. Contact: Mike Larkin ( x 239) 25. Lukas Lighting ( ) a. Contact: Craig Corona ( ) 26. LUMAPRO PAGE 3 FILE: a-CFRST-Interior Lighting REVISED: 06/06/ , Marriott International, Inc. CFRST SPECMSTR-NEW BUILD
4 REVISED: 06/06/ Lumiere, Division of Cooper Industries Company ( ) 28. iworks (LUDO Lamp) ( ) a. Contact: Michele Chan ( ) 29. Ledra, by Bruck Lighting Systems, Inc. ( ) 30. Lyte Poles Incorporated ( ) 31. MaxLite ( ) a. Contact: Bill Masi ( ) 32. National Specialty Lighting, Inc. ( ) 33. Pacific Coast Lighting ( ) a. Contact: Christopher Bryan ( ) 34. Panasonic ( ) a. Contact: Angy Steiner ( ) 35. Lithonia Lighting, Accuity Brands, Inc. ( ) 36. Philips Color Kinetics 37. Philips Lighting Company ( ) 38. Progress Lighting ( ) a. Contact: Rob Anderson ( ) 39. Project Light ( ) a. Contact: Sam Avny ( ) 40. Quoizel Lighting ( ) a. Contact: Hope Steen ( ) 41. Renaissance Lighting, Gotham Lighting, Accuity Brands, Inc. ( ) a. Contact: Troy Cook ( ) 42. Resolute, ( ) a. Contact: Holly Finn ( ) 43. RSA, a Cooper Lighting Brand ( ) 44. Scott Lamp Company ( ) a. Contact: Leanne Weber-Kreis ( ) 45. Stonco Lighting, a Philips Group Brand ( ) 46. TCP, Inc. ( ) a. Contact: Scott Carroll ( ) 47. Tech Lighting, a Generation Brands Company ( ) a. Contact: To obtain special volume pricing and accuracy for Marriott projects, contact: 1) Valley Lighting, Linthicum, MD ( ) 48. Translite Sonoma, a Philips Group Brand ( ) 49. Trend Lighting, a McFadden Lighting Company ( ) a. Contact: Rob Bruck ( ) PAGE 4 FILE: a-CFRST-Interior Lighting CFRST SPECMSTR-NEW BUILD 2016, Marriott International, Inc.
5 50. Trinity Lighting, Inc. ( ) a. Contact: Angie Allison ( ) 51. Van Teal, Inc. ( ) a. Contact: Joey Rogers ( ) 52. Wide-Lite, a Philips Group Brand ( ) 53. Approved Substitution FIXTURES AND FIXTURE COMPONENTS, GENERAL A. Metal Parts: Free from burrs, sharp corners, and edges. B. Sheet Metal Components: Steel, unless otherwise indicated. Form and support to prevent warping and sagging. C. Doors, Frames, and Other Internal Access: Smooth operating, free from light leakage under operating conditions, and arranged to permit re-lamping without use of tools. Arrange doors, frames, lenses, diffusers, and other pieces to prevent accidental falling during re-lamping and when secured in operating position. D. Reflecting Surfaces: Minimum reflectance as follows, unless otherwise indicated: 1. White Surfaces: 85 percent. 2. Specular Surfaces: 83 percent. 3. Diffusing Specular Surfaces: 75 percent. 4. Laminated Silver Metallized Film: 90 percent. E. Lenses, Diffusers, Covers, and Globes: 100 percent virgin acrylic plastic or annealed crystal glass, unless otherwise indicated. 1. Plastic: High resistance to yellowing and other changes due to aging, exposure to heat, and ultraviolet radiation. 2. Lens Thickness: inch minimum, unless greater thickness is indicated FLUORESCENT LAMP BALLASTS A. General Requirements: Unless otherwise indicated, features include the following: 1. Designed for type and quantity of lamps indicated at full light output. 2. Total Harmonic Distortion Rating: Less than 20 percent. 3. Sound Rating: A. B. Electronic Ballasts for Linear Lamps: Unless otherwise indicated, features include the following, besides those in "General Requirements" Paragraph above: 1. Certified Ballast Manufacturer Certification: Indicated by label. 2. Encapsulation: Without voids in potting compound. 3. Parallel Lamp Circuits: Multiple lamp ballasts connected to maintain full light output on surviving lamps if one or more lamps fail. C. Ballasts for Compact Lamps in Recessed Fixtures: Unless otherwise indicated, additional features include the following: 1. Type: Electronic fully encapsulated in potting compound. 2. Power Factor: 90 percent, minimum. 3. Operating Frequency: 20 khz or higher. 4. Flicker: Less than 5 percent. 5. Lamp Current Crest Factor: Less than Transient Protection: Comply with IEEE C62.41 for Category A1 locations. PAGE 5 FILE: a-CFRST-Interior Lighting REVISED: 06/06/ , Marriott International, Inc. CFRST SPECMSTR-NEW BUILD
6 D. Ballasts for Dimmer-Controlled Fixtures: Comply with general and fixture-related requirements above for electronic ballasts. 1. Compatibility: Certified by manufacturer for use with specific dimming system indicated for use with each dimming ballast. E. Ballasts for Low-Temperature Environments: As follows: 1. Temperatures 0 Deg F Above: Electronic or electromagnetic type rated for 0 deg F starting temperature. 2. Temperatures Minus 20 Deg F and Above: Electromagnetic type designed for use with high-output lamps HIGH-INTENSITY-DISCHARGE LAMP BALLASTS A. General: Comply with ANSI C82.4. Unless otherwise indicated, features include the following: 1. Type: Constant wattage autotransformer or regulating high-power-factor type, unless otherwise indicated. 2. Operating Voltage: Match system voltage. 3. Minimum Starting Temperature: Minus 22 deg F for single lamp ballasts. 4. Normal Ambient Operating Temperature: 104 deg F 5. Open-circuit operation that will not reduce average life. 6. Auxiliary, Instant-on, Quartz System: Automatically switches quartz lamp on when fixture is initially energized and when momentary power outages occur. Automatically turns quartz lamp off when high-intensity-discharge lamp reaches approximately 60 percent light output EXIT SIGNS A. General Requirements: Comply with UL 924 and the following: 1. Sign Colors and Lettering Size: Comply with authorities having jurisdiction. B. Internally Lighted Signs: As follows: 1. Lamps for AC Operation: Light-emitting diodes, 70,000 hours minimum rated lamp life. C. Self-Powered Exit Signs (Battery Type): Integral automatic charger in a self-contained power pack. 1. Battery: Sealed, maintenance-free, nickel-cadmium type with special warranty. 2. Charger: Fully automatic, solid-state type with sealed transfer relay. 3. Operation: Relay automatically energizes lamp from unit when circuit voltage drops to 80 percent of nominal or below. When normal voltage is restored, relay disconnects lamps, and battery is automatically recharged and floated on charger EMERGENCY LIGHTING UNITS A. General Requirements: Self-contained units. Comply with UL 924. Units include the following features: 1. Battery: Sealed, maintenance-free, lead-acid type with minimum 10-year nominal life and special warranty. 2. Charger: Fully automatic, solid-state type with sealed transfer relay. 3. Operation: Relay automatically turns lamp on when supply circuit voltage drops to 80 percent of nominal voltage or below. Lamp automatically disconnects from battery when voltage approaches deep-discharge level. When normal voltage is restored, relay disconnects lamps, and battery is automatically recharged and floated on charger. REVISED: 06/06/16 PAGE 6 FILE: a-CFRST-Interior Lighting CFRST SPECMSTR-NEW BUILD 2016, Marriott International, Inc.
7 4. Integral Time-Delay Relay: Arranged to hold unit on for fixed interval after restoring power after an outage. Provides adequate time delay to permit high-intensity-discharge lamps to restrike and develop adequate output LED FIXTURES A. Fixtures shall be UL or Intertek (ETL) Listed. B. Drivers shall be capable of accepting the voltage indicated on the [schedule] [drawings] and capable of dimming if required. The driver shall meet the following requirements: 1. Class A Sound Rating 2. Total Harmonic Distortion of less than 20 percent. 3. Operating temperature between -40 degree Celsius and 40 degrees Celsius. 4. Driver shall not contain any Polychlorinated Biphenyl (PCB). C. All LED fixtures shall be tested to IES LM-79 and IES LM-80 and meet the following: 1. Fixture Efficacy (Lumens per watt): 60 or greater. 2. Color Accuracy: Color Rendering Index (CRI): 70 or greater. 3. Light Color: As indicated on lighting fixture schedule. 4. Outdoor fixtures shall be IP65 Rated. 5. LEDs, driver and all components shall have a system lifetime of 50,000 hours or more at 25 degrees Celsius. 6. Fixture shall have a minimum of a five year warranty on all components and finishes LAMPS A. Fluorescent Color Temperature and Minimum Color-Rendering Index: 3500 K and 85 CRI, unless otherwise indicated. B. Non-compact Fluorescent Lamp Life: Rated average is 20,000 hours at 3 hours per start when used on rapid-start circuits. C. Metal-Halide Color Temperature and Minimum Color-Rendering Index: 3600 K and 70 CRI, unless otherwise indicated FIXTURE SUPPORT COMPONENTS A. Comply with Section 26/ (16050) "Basic Electrical Materials and Methods," for channel- and angle-iron supports and nonmetallic channel and angle supports. B. Single-Stem Hangers: 1/2-inch steel tubing with swivel ball fitting and ceiling canopy. Finish same as fixture. C. Twin-Stem Hangers: Two, 1/2-inch steel tubes with single canopy arranged to mount a single fixture. Finish same as fixture. D. Rod Hangers: 3/16-inch- minimum diameter, cadmium-plated, threaded steel rod. E. Hook Hangers: Integrated assembly matched to fixture and line voltage and equipped with threaded attachment, cord, and locking-type plug. F. Aircraft Cable Support: Use cable, anchorages, and intermediate supports recommended by fixture manufacturer FINISHES A. Fixtures: Manufacturer's standard, unless otherwise indicated. 1. Paint Finish: Applied over corrosion-resistant treatment or primer, free of defects. 2. Metallic Finish: Corrosion resistant. 3. Colors as indicated in Light Fixture Matrix. PAGE 7 FILE: a-CFRST-Interior Lighting REVISED: 06/06/ , Marriott International, Inc. CFRST SPECMSTR-NEW BUILD
8 PART 3 EXECUTION 3.01 INSTALLATION A. Fixtures: Set level, plumb, and square with ceiling and walls, and secure according to manufacturer's written instructions and approved submittal materials. Install lamps in each fixture. B. Support for Fixtures in or on Grid-Type Suspended Ceilings: 1. Recessed lighting fixtures shall be supported independently from the suspended ceiling system. Number 8 gauge galvanized steel wire or approved type hangers from the overhead building structures shall be provided for fixture support. C. Suspended Fixture Support: As follows: 1. Pendants and Rods: Where longer than 48 inches brace to limit swinging. 2. Stem-Mounted, Single-Unit Fixtures: Suspend with twin-stem hangers. 3. Continuous Rows: Suspend from cable installed according to fixture manufacturer's written instructions and details on Drawings CONNECTIONS A. Ground Equipment. 1. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B FIELD QUALITY CONTROL A. Inspect each installed fixture for damage. Replace damaged fixtures and components. B. Advance Notice: Give dates and times for field tests. C. Provide instruments to make and record test results. D. Tests: As follows: 1. Verify normal operation of each fixture after installation. 2. Emergency Lighting: Interrupt electrical supply to demonstrate proper operation. REVISED: 06/06/16 3. Verify normal transfer to battery source and retransfer to normal. 4. Report results in writing. E. Malfunctioning Fixtures and Components: Replace or repair, then retest. Repeat procedure until units operate properly. F. Corrosive Fixtures: Replace during warranty period CLEANING AND ADJUSTING A. Clean fixtures internally and externally after installation. Use methods and materials recommended by manufacturer. B. Adjust aimable fixtures to provide required light intensities. Revision Log END OF SECTION PAGE 8 FILE: a-CFRST-Interior Lighting Comment [Comment1]: REVISION LOG: 08/17/01: Add Revision Log. 09/05/01: 2.01-Change Marketplace to Avendra, LLC. 09/20/01: 1.02-Revise/Clarify Text, Revise Paragraph Numbering. 12/30/05: Revised to 2006 Format 01/05/07: Updated to 2007 format 06/19/07: Added list of manufacturers and contacts. 09/28/07: Updated to 2007 Section Format. 04/01/09: Added Tech Lighting and updated Genlyte companies to Philips. 01/01/10: Updated contact person for all Philips Companies and Tech Lighting. 01/01/10: Moved GE, Philips and TCP from Avendra Approved to Approved Manufacturers. 01/01/10: Updated References. 06/01/10: Added Section for CFRST LEED Volume Program specifications. 01/01/11: Updated contact information. Added MaxLite, Neptun, and Cree LED Lighting Solutions as approved manufacturers. 09/03/12: Updated entire Section 09/03/12: Added Lukas Lighting as approved Manufacturer. 01/01/13: Updated manufacturer contact information. 01/06/14: Added LED Fixture specifications. 05/05/14: Updated manufacturer contact information. 12/01/15: Update manufacturer contact information 06/06/16: Updated Acclaim Lighting contact information. CFRST SPECMSTR-NEW BUILD 2016, Marriott International, Inc.
MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 26 ELECTRICAL
SECTION 265100 - INTERIOR LIGHTING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Interior lighting fixtures, lamps, and ballasts. 2. Emergency lighting units. 3. Exit signs. 4.
More informationSECTION INTERIOR LIGHTING
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the
More informationSECTION INTERIOR LIGHTING
SECTION 26 51 00 INTERIOR LIGHTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION INTERIOR LIGHTING
SECTION 26 51 00 INTERIOR LIGHTING PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationE. Luminaire: Complete lighting fixture, including ballast housing if provided.
SECTION 16511 - INTERIOR LIGHTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 16 Specification
More information2. Lighting fixtures mounted on exterior building surfaces.
PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 DEFINITIONS... 2 1.4 SUBMITTALS... 2 1.5 QUALITY ASSURANCE... 3 1.6 COORDINATION... 3 1.7 WARRANTY... 4 1.8 EXTRA MATERIALS... 4 PART
More informationSECTION INTERIOR AND EXTERIOR LIGHTING FIXTURES
SECTION 26 50 00 INTERIOR AND EXTERIOR LIGHTING FIXTURES PART 1: GENERAL 1.1 WORK INCLUDED: A. Interior lighting fixtures and accessories B. Exterior lighting fixtures and accessories C. Emergency battery
More informationA. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings.
DIVISION 26 ELECTRICAL SECTION 26 51 13 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings. B. Luminaire
More informationSECTION INTERIOR LIGHTING
PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 26 51 00 SPEC WRITER NOTES: Use this section only for NCA projects. Delete between //----// if not applicable to project. Also, delete any other item or paragraph
More informationSECTION (16140) - WIRING DEVICES
SECTION 26 27 26 (16140) - WIRING DEVICES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Receptacles, Connectors, Switches, and Finish Plates. B. Related Sections: 1. Section 00 31 13.43 (00370) -
More informationWINDSOR FOREST HIGH SCHOOL HVAC REPLACEMENT ADDENDUM #2 SAVANNAH CHATHAM COUNTY PUBLIC SCHOOL SYSTEM FEBRUARY 18, 2016
SECTION 26 2030 - LIGHTING FIXTURES PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including General and Special Conditions and Division 1 Specification Sections,
More informationSECTION (16460) - LOW-VOLTAGE TRANSFORMERS
PART 1 GENERAL 1.01 SUMMARY SECTION 26 22 00 (16460) - LOW-VOLTAGE TRANSFORMERS A. Section Includes: 1. Dry-Type Distribution And Specialty Transformers Rated 1000 V And Less. a. General-Purpose Distribution
More informationSECTION LIGHTING CONTROL DEVICES
SECTION 16145 LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More information1. Division 26 Section Electrical General Requirements. 2. Division 26 Section "Wiring Devices" for wall-box dimmers and manual light switches.
PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 REFERENCES... 2 1.4 DEFINITIONS... 2 1.5 SUBMITTALS... 2 1.6 QUALITY ASSURANCE... 3 1.7 COORDINATION... 3 1.8 DELIVERY, STORAGE, AND
More informationA. This Section includes the following lighting control devices:
Attachment G LIGHTING CONTROL SPECIFICATIONS (Download Document separately) LIGHTING CONTROL SPECIFICATIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including
More informationEmery County Senior Center Green River 06/07
SECTION 260923 - LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION LIGHTING
SECTION 26 50 00 LIGHTING PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and required to furnish and install
More informationCatalog Number. Notes
Catalog Number FEATURES & SPECIFICATIONS INTENDED USE Built on the compact, low-profile Z strip channel, this LED strip offers long maintenance-free life, several color s, lumen outputs and lengths. Ideal
More informationSECTION (13730) - INTRUSION DETECTION
PART 1 GENERAL 1.01 SUMMARY A. Section Includes: SECTION 28 16 00 (13730) - INTRUSION DETECTION 1. Intrusion Detection Sensors 2. Signal Equipment 3. System Controls 4. Alarm Displays 5. Alarm Indicating
More informationSECTION (15833) - HVAC POWER VENTILATORS
PART 1 GENERAL 1.01 SUMMARY SECTION 23 34 23 (15833) - HVAC POWER VENTILATORS A. Section Includes: 1. Centrifugal Roof Ventilators. 2. Up-blast Roof Exhaust Fans (Kitchen Hood Exhaust). 3. Ceiling-Mounted
More informationA. This Section includes the following lighting control devices:
SECTION 26 09 23 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationB. It is recognized that these standards are updated irregularly and lighting technology is changing rapidly.
PART 1 GENERAL 1.01 Lighting design: A. Reference UAF Facilities Services Guidelines for Average Illumination Levels. B. It is recognized that these standards are updated irregularly and lighting technology
More informationSECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL
SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply
More informationSECTION EXTERIOR LIGHTING
SECTION 26 56 00 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of exterior luminaries, controls, poles and supports. 1.2 RELATED WORK A. Section 26
More informationCatalog Number. Notes. Type. FST Snap on frosted, diffuse L/LENS No diffuser
Catalog Number FEATURES & SPECIFICATIONS INTENDED USE Built on the compact, low-profile Z strip channel, this LED strip offers long maintenance-free life, several color s, lumen outputs and lengths. Ideal
More informationSECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS
SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from
More informationSETION EMERGENCY LIGHTING NATIONAL FIRE PROTECTION ASSOCIATION (NEPA) (2006) Life Safety Code, 2006 Edition
SETION 16420 PART 1 - GENERAL 1.01 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation
More informationSECTION PARKING STRUCTURE LIGHTING
SECTION 26 56 16 PARKING STRUCTURE LIGHTING PART 1 - GENERAL 1.1 SYSTEMS DESCRIPTION A. Illumination Levels 1. The parking structure illumination level is intended to balance concerns for personal safety
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph
More informationCL001 >400 Watt lamp basecase, up to 600 Watt replacement fixture $95.00 Fixture
Lighting Specifications Business Please read the details below to ensure you are installing a qualifying product(s). An MID inspection of the pre-existing lighting scheme is required prior to the installation
More informationLIGHTING CONTROL DEVICES
SECTION - PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this
More informationSECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features:
PART 1 - GENERAL 1.1 SUMMARY A. This Section includes fast-transfer central battery inverters with the following features: 1. Emergency-only circuits. 1.2 DEFINITIONS A. LCD: Liquid-crystal display. B.
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-26 52 00.00 40 (November 2017) ----------------------------------- Preparing Activity: NASA Superseding UFGS-26 52 00.00 40 (August 2014) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More information1. Building wires and cables rated 600 V and less. 2. Connectors, splices, and terminations rated 600 V and less.
Copyright 2010 AlA MasterSpec Full Length 09/10 SECTION 260519- LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART I-GENERAL 1.1 SUMMARY A. Section Includes: 1. Building wires and cables rated 600
More informationUltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW
12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes
More informationMN/DOT Specification Sign Lighting Luminaire With 150 or 250 Watt Metal Halide Lamps 11/05/09
1. LISTING REQUIREMENTS MN/DOT Specification Sign Lighting Luminaire With 150 or 250 Watt Metal Halide Lamps 11/05/09 1.1. The Luminaire shall be listed by a National Recognized Testing Laboratory (NRTL)
More informationFPLHB - Fidelux Premier Linear Highbay
FPLHB - Fidelux Premier Linear Highbay Product Description Fidelux LED Linear High Bays meet the challenging maintenance, safety, and performance requirements of industrial environments through an unbeatable
More informationA. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.
SECTION 238113 - PACKAGED TERMINAL AIR CONDITIONERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSECTION (15767) - UNIT HEATERS
SECTION 23 82 39 (15767) - UNIT HEATERS PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Unit Heaters. 2. Cabinet Unit Heaters. 3. Duct Heaters. 4. Baseboard Heaters. B. Related Sections: 1. Section
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018
SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationProduct Specifications MaxLumen MRI LED Diffused Lighting
NOVA Energy & Automation Product Specifications MaxLumen MRI LED Diffused Lighting Model MXLumen22-X 03 January 2012 Product Description 1. Standard Applications The Nova Max Lumen LED 2x2 light fixture
More informationBdl60u Fluorescent Emergency Ballast
A Division Of Philips Electronics North America Corporation One- or two-lamp emergency; Universal input voltage: 120 through 277 V, 50 or 60 Hz; Replaces B60U Bdl60u Fluorescent Emergency Ballast Product
More informationExplosion Proof C1D2 0-10V Dimmable LED Fixture - 4ft 2 Lamp - Emergency Ballast - Terminal Strips
Explosion Proof C1D2 0-10V Dimmable LED Fixture - 4ft 2 Lamp - Emergency Ballast - Terminal Strips Part #: HAL-EMG-48-2L-LED-D-V2 Page: 1 Made in the USA The Larson Electronics HAL-EMG-48-2L-LED-D-V2 Hazardous
More informationProduct Specifications MaxLumen MRI LED Diffused Lighting
NOVA Energy & Automation Product Specifications MaxLumen MRI LED Diffused Lighting Model NEA-MXLumen14-X 03 January 2012 Product Description 1. Standard Applications The Nova Max Lumen LED 1x4 light fixture
More informationExplosion Proof LED Light - Equivalent to Watt HID C1D2, UL Listed
Explosion Proof LED Light - Equivalent to 150-175 Watt HID C1D2, UL Listed Part #: EPLC2-LED-175W Page: 1 Made in the USA The Larson Electronics explosion proof LED is designed for use in hazardous work
More informationCONTENTS AUTOMATIC TRANSFER SWITCHES
CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training
More informationLighting. Showroom Lighting Requirements. Introduction. Technology. Fixture and Performance
Showroom Lighting Requirements Introduction The Chevrolet Showroom Lighting Strategy is designed to assist the Dealer in reducing energy consumption through the use of high performance tested and approved
More informationSECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the
More informationSECTION BIOLOGICAL SAFETY CABINETS AND LAMINAR AIRFLOW WORK STATIONS
SECTION 11 53 53 BIOLOGICAL SAFETY CABINETS AND LAMINAR AIRFLOW WORK STATIONS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Delete other items or paragraphs in the section
More informationHazardous Location LED Pivoting Light - C1D2 - Dimmable - Modbus TCP/IP Network - Meets USCG Specs
Hazardous Location LED Pivoting Light - C1D2 - Dimmable - Modbus TCP/IP Network - Meets USCG Specs Part #: HALP-ANC-48-2L-LED-D-V2 Page: 1 Made in the USA The Larson Electronics HALP-ANC-48-2L-LED-D-V2
More informationLUCE 1 TL. specifications: internal. specifications: external. ordering logic. builder. Job/Location:
LUCE 1 TL indoor / damp Job/Location: Contractor: Prepared By: Job Type: Date: The LUCE-1TL thinline emergency ballast is designed to provide emergency illumination to existing or new fluorescent luminaires.
More informationProduct Specifications MaxLumen MRI LED Diffused Lighting
NOVA Energy & Automation Product Specifications MaxLumen MRI LED Diffused Lighting Model MXLumen22-X 03 January 2012 Product Description 1. Standard Applications The Nova Max Lumen LED 2x2 light fixture
More informationB. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.
DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS
More informationUBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 27 05 05 Communication Rooms Design Guidelines 2.13 1.2 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations Electrical
More informationCRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 1
GREEN LIGHT ARCHITECTURAL DIMMING CONTROLS (GLPD) Crestron Green Light and Green Light Express Network Dimming Control Systems are web accessible, network connected dimming control systems that receive
More informationSECTION FAN COIL UNITS
PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:
More informationSECTION GAS-FIRED RADIANT HEATERS
SECTION 23 55 23 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph
More informationLow Profile Clean Room 150W LED Light - 2x2 Lay-In Troffer C1D1 - C2D2 - ISO 14644/FS-209E
Low Profile Clean Room 150W LED Light - 2x2 Lay-In Troffer - 140 - C1D1 - C2D2 - ISO 14644/FS-209E Part #: HALD-24-1X150LED-V2-140DB Page: 1 Made in the USA The HALD-24-1X150LED-V2-140DB from Larson Electronics
More informationelite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems
5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification
More informationFast. Precise. Versatile. UL Lighting Sciences
Fast. Precise. Versatile. UL Lighting Sciences As the world turns to LED and SSL technology as a primary source of electric light, UL Lighting Sciences continues to build upon our industry-leading technical
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-26 51 00.00 40 (February 2013) Change 1-11/14 ----------------------------------- Preparing Activity: NASA Superseding UFGS-26 51 00.00 40 (February 2011) UNIFIED FACILITIES
More informationTABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5
DOC Cremer Heating and Hot Water Plant Project Number: M 1411-04 TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION 21 30 00- WATER BASED FIRE PROTECTION SYSTEMS... 5 SECTION 22 40 00 -PLUMBING
More informationSECTION (15900) - INSTRUMENTATION AND CONTROL FOR HVAC
SECTION 23 09 00 (15900) - INSTRUMENTATION AND CONTROL FOR HVAC PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Control Panels 2. Thermostats 3. Actuators 4. Dampers 5. Wiring B. Related Sections:
More information208W Explosion Proof Low Profile LED - Emergency Backup - 27,040 Lumens - C1&2 D1&2 - ATEX /IEC
208W Explosion Proof Low Profile LED - Emergency Backup - 27,040 Lumens - C1&2 D1&2 - ATEX /IEC Part #: EPL-EMGX-LP-2X48-LED Page: 1 The Larson Electronics EPL-EMGX-LP-2X48-LED Low Profile Explosion Proof
More informationSECTION (15820) - AIR DUCT ACCESSORIES
PART 1 GENERAL 1.01 SUMMARY A. Section includes: SECTION 23 33 00 (15820) - AIR DUCT ACCESSORIES 1. Manual-Volume Dampers 2. Fire Dampers 3. Turning Vanes 4. Duct-Mounted Access Doors 5. Flexible Connectors
More informationA. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.
SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:
More informationA. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings.
DIVISION 26 ELECTRICAL SECTION 26 27 26 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings. B. Specialty switches and outlets
More informationSECTION AUTOMATIC TRANSFER SWITCHES
SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationExplosion Proof 70 Watt Low Profile LED Light Fixture Lumens - C1D1 Group B - Hydrogen Rated
Explosion Proof 70 Watt Low Profile LED Light Fixture - 6000 Lumens - C1D1 Group B - Hydrogen Rated Part #: EPL-LP-70W-LED-B The Larson Electronics EPL-LP-70W-LED-B Low Profile LED light fixture provides
More informationC2D1/C1D2 Explosion Proof 50 Watt LED Light Fixture - Paint Spray Booth Approved - 6,250 Lumens
C2D1/C1D2 Explosion Proof 50 Watt LED Light Fixture - Paint Spray Booth Approved - 6,250 Lumens Part #: EPLC2-HB-50LED-RT Page: 1 The Larson Electronics EPLC2-HB-50LED-RT Explosion Proof High Bay light
More informationAltman Lighting Spectra Cyc UV 50 Specification
1.01 UV CYCLORAMA LIGHTING A. General 1. The fixture shall be a compact, lightweight color-mixing LED asymmetrical wash fixture with 8 or 16 bit DMX control of intensity and color. The fixture shall be
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-23 83 00.00 20 (April 2006) -------------------------------- Preparing Activity: NAVFAC Replacing without change UFGS-15768N (September 1999) UNIFIED FACILITIES GUIDE
More information*REPRESENTS 3500K/80CRI 2 FT 4 FT 6 FT 8 FT 2 FT 4 FT 6 FT 8 FT *REPRESENTS 3500K/80CRI LINEAR
SUSPENDED SYSTEM The ELEMENT Merge Suspended LED linear system represents the marriage of indirect downlight, independent up light, and a track system; all in one system with independent control and outputs
More informationSECTION (15530) - REFRIGERANT PIPING
PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Tubes. 2. Fittings. SECTION 23 23 00 (15530) - REFRIGERANT PIPING 3. Joining Materials. 4. Specialties. B. Related Sections: 1.02 REFERENCES 1. Section
More information150W Explosion Proof High Bay LED Light Fixture - C1D1&2 - C2D1&2-17,500 Lumens - 60 Beam
150W Explosion Proof High Bay LED Light Fixture - C1D1&2 - C2D1&2-17,500 Lumens - 60 Beam Part #: EPLC2-HB-155W-LED-PND Page: 1 The Larson Electronics EPLC2-HB-155W-LED-PND Explosion Proof High Bay light
More informationSECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS
SECTION 26 05 53 (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Electrical identification materials and devices required to comply with ANSI C2, NFPA
More informationEvolution EXWW RECESSED LINEAR WALL WASH LUMINAIRE
Evolution EXWW Project Name Date Type RECESSED LINEAR WALL WASH LUMINAIRE 3-13/16 (96.8mm) 5-1/8 (130.2mm) Extruded aluminum trim with formed cold rolled 20 gauge steel back box housing Highly reflective,
More informationSECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES
PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Lighting and appliance panelboards 1.02 RELATED SECTIONS A. 16475,
More informationADDENDUM #2. Bid #18-12, Proposition 39 Interior LED Lighting Retrofit at Designated Sites
ADDENDUM #2 Bid #18-12, Proposition 39 Interior LED Lighting Retrofit at Designated Sites This addendum is to provide the lighting specifications for this project. Baldwin Park Unified School District
More informationSPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS
SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification
More informationSECTION (13900) - FIRE SUPPRESSION SYSTEMS
PART 1 GENERAL 1.01 SUMMARY SECTION 21 10 00 (13900) - FIRE SUPPRESSION SYSTEMS A. Section Includes: 1. Pipe and Fittings. 2. Sprinklers. B. Related Documents: 1. Marriott s Fire Protection and Life Safety
More information25W Hazardous Location Integrated LED Light Fixture Lumens - Low Profile - ATEX IEC CSA UL
25W Hazardous Location Integrated LED Light Fixture - 3294 Lumens - Low Profile - ATEX IEC CSA UL Part #: HAL-19-25W-ITG-LED Page: 1 The Larson Electronics HAL-19-25W-ITG-LED 25 Watt Explosion Proof Low
More informationStudent Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.
SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:
More informationADDENDUM NO. 3 Bessemer City Schools Bus Maintenance Shop Building
PROJECT NO. 14BIR08 DATE August 3, 2015 BIDS RECEIVED: DATE: August 13, 2015 TIME 5:00 p.m. ADDENDUM NO. 3 Bessemer City Schools Bus Maintenance Shop Building PLACE: Board Room Bessemer City Board of Education
More information300W Low Profile Clean Room LED Light - LED Signal Light - C1D1 - C2D2 - ISO 14644/FS-209E Rated
300W Low Profile Clean Room LED Light - LED Signal Light - C1D1 - C2D2 - ISO 14644/FS-209E Rated Part #: HALD-48-2X150LED-V2-C-OXM Page: 1 Made in Texas The HALD-48-2X150LED-V2-C-OXM from Larson Electronics
More information1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.
Page 238239-1 SECTION 238239 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationFahrenheit Recessed LED Downlight Fire and Sound-Rated New Construction 4, 5, 6 Aperture
PRODUCT SPECIFICATIONS Frame-in Kit HOUSING: Fire and sound-rated housing. Up to 20 minute fire rated L500 (floor-ceiling) & P500 (roof-ceiling) design. Die formed #24 gauge galvanized steel construction.
More informationSECTION (13740) - VIDEO SURVEILLANCE
PART 1 GENERAL 1.01 SUMMARY A. Section Includes: SECTION 28 23 00 (13740) - VIDEO SURVEILLANCE 1. CCTV Closed Circuit Television System. B. Related Sections:. 1.02 REFERENCES 1. Section 26 05 00 (16050)
More information100W Explosion Proof Ultraviolet Portable LED Fixture - 365NM - EXP Cord Caps - 150ft Cord
100W Explosion Proof Ultraviolet Portable LED Fixture - 365NM - EXP Cord Caps - 150ft Cord Part #: EPL-PM-100LED-UVA-150-EPP Page: 1 The EPL-PM-100LED-UVA-150-EPP from Larson Electronics is an Explosion
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-26 51 00 (May 2016) Change 1-11/16 -------------------------- Preparing Activity: NAVFAC Superseding UFGS-26 51 00 (July 2007) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationPacific Gas and Electric Company Energy Efficiency Rebates for Your Business. Lighting Rebate Catalog Saving energy for a brighter future
Pacific Gas and Electric Company Energy Efficiency Rebates for Your Business Lighting Rebate Catalog Saving energy for a brighter future Customers may be eligible to participate in Pacific Gas and Electric
More informationSPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC
SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC SECTION 08 35 13.23 ACCORDION FOLDING FIRE DOORS PART 1 GENERAL 1.01 SUMMARY OF WORK A. Division 0 and 1, as indexed, apply to this section. B. Furnish and install
More informationZipTwo LED 707. Micro-profile interior direct lighting for open office, wall wash and wall graze applications. Spec Guide
Adaptive architectural lighting systems Type Project Spec Guide ZipTwo LED 707 Micro-profile interior direct lighting for open office, wall wash and wall graze applications. Benefits & Features Ultra low
More informationPowerWave 2 Busway System
PowerWave 2 Busway System Guide Specifications (Revision 004, 11/17/2017) 1 GENERAL 1.1 Summary This specification covers the electrical characteristics and general requirements for a continuous opening,
More informationTHE HIGH STRIP FIXTURE SERIES PERFORMANCE KEY FEATURES INCLUDE: LED Fixture Series for General, Direct and Indirect Illumination
THE HIGH PERFORMANCE LED Fixture Series for General, Direct and Indirect Illumination KEY FEATURES INCLUDE: Advanced Thermal Management Industry Leading Deep Fin Heat Sinks with Aircraft Grade Aluminum
More informationREPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045
REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045 FOR THE SCOPE OF ACCREDITATION UNDER NVLAP LAB CODE 100402-0. Project No. G101030158 Date: February 26, 2013 REPORT NO. 101030158CRT-001 TEST OF ONE LED
More informationT8 Self Ballasted UL & CSA LED TUBE RETROFITS
T8 Self Ballasted UL & CSA LED TUBE RETROFITS Sept. 2011 Part Numbers T8 LED TUBE TECHNICAL SPECIFICATIONS Part Numbers LR-T8-17W-3.2-1200 LR-T8-17W-4.5-1200 LR-T8-17W-6.5-1200 LRT8-23WW-FS2 LRT8-23CW-FS2
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Lighting. Basis of Design
Basis of Design This section applies to the design and installation of lighting systems. Design Criteria Select interior lighting to achieve initial system efficiencies greater than 64 lumens per watt.
More informationA. This Section includes transfer switches rated 600 V and less, including the following:
SECTION 16415 - TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION (15530) - REFRIGERANT PIPING
SECTION 23 23 00 (15530) - REFRIGERANT PIPING PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Tubes. 2. Fittings. 3. Joining Materials. 4. Specialties. B. Related Sections: 1. Section 07 92 00 (07920)
More information