Electronic control unit for gas leak detection with 4 detection zones
|
|
- Gwendolyn Logan
- 5 years ago
- Views:
Transcription
1 P82 Electronic control unit for gas leak detection with 4 detection zones Electronic control unit for gas leak detection in industrial environment, suitable for controlling and signaling dangerous gas concentration in the air, specifically for detecting methane gas, LPG and carbon monoxide. Dimensions (mm) Power supply Contacts rating Connected sensors Operating ambient temperature Protection degree P82 12Vac/dc ± 10% 8-250V C IP40 ELECTRICL CHRCTERISTICS Power supply: 12Vac/dc ± 10%. bsorption with 1 probe approximately 160m (320m). bsorption with 4 probes approximately 280m (920m). Connection with 2 terminals of 2,5 mm². Input - fuse power supply 1 5x20mm. 4 inputs for sensors S81, S82, S83, or probes TEX S84, S85, S86 (different gas types). Connection to the probe with 3 terminals of 2,5 mm², for each probe: C ( V); S (+4 20m); ( V). Maximum connection length 50 m, for each probe. Section of 3 conductors: 1,5 mm². larm output: n.1 relay with 1 SPDT contact 8 250Vac. Failure output: n.1 relay with 1 SPDT contact 8 250Vac. Outputs connections: n.3 terminals of 2,5 mm² for relay C-NC-NO. 14
2 WIRING DIGRM Vaux 1 2 Probes S Probes S R1 Resistance 18 KOhm ¼W (if probe 4 is missing) 12 Vac/dc S81-S82-S V m V V m V S84-S85-S C S C S + C1 S1 1 C2 S2 2 C3 S3 3 C4 S4 4 R1 C C P82 alarm failure - NO NC NO NC 12 Vac/dc valve ZD... optical signal S80 Vaux STNDRDS ND PPROVLS Complies with the standards EN ; CEI 216-5/1; EMC 89/336/CEE; EN INSTLLTION Rear panel mounting on Omega DIN EN rail. It can be installed on the bottom panel or DIN modular panels. To ensure the proper protection degree of the device is necessary to install the unit in an electric box created according to current regulations for the workplace and within which can also be housed the power supply system. OPERTION P82 control unit allows you to connect up to 4 probes of model S or TEX S84, S85, S86 probes for the construction of gas detection systems in environments such as boiler rooms, garages, warehouses, workshops, etc.. with the possibility to control a solenoid valve or an auxiliary device (siren, flashing light, extractor, etc..) through inside alarm relay. The installation of a gas leak detection system or the presence of carbon monoxide, do not exempt from compliance with all rules for installation and use of gas appliances and from the corresponding safety standards and law in force for this type of systems. The control unit must be powered at 12 Vac/dc. To connect the relay outputs use cables with a minimum section of 1,5 mm². The operation logic, selected by means of jumper E1, can be either positive or negative. The device reports its operation status through the LED. ccording to the selected logic through the jumper E1, in normal situation (no alarm), the led, the failure signaling output and the relay, are: positive logic: led switched on, relays energized; negative logic: led switched off, relays not energized. In case was selected the negative operation logic, the alarm relay can be controlled continuously or pulsed, depending on Jumper E2 position: Position positive logic Position negative logic Position alarm relay continuous control Position alarm relay pulse control E1 E1 E1 E2 E2 E2 15
3 Once it was received the proper power supply, the control unit performs in sequence the following steps: TESTING THE LED ND THE UZZER (PPROXIMTELY 5 SECONDS) Whatever the selected logic, the LEDs are starting to light in sequence and the buzzer emits a short beep. PROES PREHETING (PPROXIMTELY 1 MINUTE) During this phase, which allows the probes to reach the correct operation temperature, the detection system is not functioning. FUNCTIONL TEST (OUT 3 MINUTES) Once the probes preheating phase has finished, the device enters under functional test phase. During this phase all internal timings are resetted in order to facilitate probes operation verification (alarm simulation). INTERFCE POSITIVE LOGIC NEGTIVE LOGIC Power supply led Green Switched ON Switched ON General anomaly led Yellow Switched ON Switched OFF Probe anomaly led Yellow Switched ON Switched OFF larm and faulty line led Red Switched ON Switched OFF larm buzzer No sound No sound larm relay Energized Not energized nomaly relay Energized Not energized During normal operation of the control unit is activated the gas alarm monitoring, as well the self-diagnoses for installation failures (probes) and of the system (control units). In this phase and in the absence of the alarm and the anomaly, the control unit is presented as shown in the table on the right. INTERFCE POSITIVE LOGIC NEGTIVE LOGIC larm led for interested probe Green Switched OFF Switched ON larm buzzer Yellow Continuous sound Continuous sound larm relay Yellow Not energized Energized (continuously or pulsed according to e2) In the presence of dangerous gas concentrations, the unit enters in gas alarm phase and performs the following operations, indicated in the table on the right. INTERFCE POSITIVE LOGIC NEGTIVE LOGIC General anomaly led (for the Yellow Switched OFF Switched ON faulty control unit) Probe anomaly led (for the faulty Yellow Continuous sound Continuous sound probe) larm buzzer Yellow Intermittent Intermittent sound sound nomaly relay Not energized Energized Once the gas alarm condition was surmounted is necessary to bring the control unit in normal operation condition. For this purpose must be pressed the RESET/TEST button, situated on the front. In the presence of a failure (probes and/or control units) the control units will be represented like in the table on the right. Once the possible failure was eliminated, is necessary to bring the control unit in normal operation condition. For this purpose must be pressed the RESET/TEST button, situated on the device front. It is recommended to repeat the procedure of operation verification at least once a year, or after a prolonged shutdown period, and anytime when is replaced the probe. The average life time of S81-S82-S83 probes and S84-S85-S86 is 5 years from date of installation. It is mandatory to replace them before the expiry of 5 years of use. The average life time of the probes is calculated taking into consideration a typical use in a normally free of contaminants (gases, thinners, etc.) environment. more frequent presence and in higher concentrations of these substances can accelerate the normal oxidation process of the sensing element, resulting with its life time decrease. 16
4 TECHNICL FETURES Light signals: 1 red LED, power supply on; 1 yellow LED, general failure; 4 yellow LED, failure for each probe series; 4 red LED, gas alarms for each probe series. coustic signals: 1 buzzer with sound intensity > 60db at 1m. 1 button to reset the alarms and for testing the probes. Self-extinguishing plastic housing. Dimensions: 158 x 90 x 58 mm 9 modules complies with DIN standard. Unit weight: 0,25 kg. Rear panel mounting on Omega DIN EN rail. Protection: IP20; IP40 when is properly installed in an electrical box. Environment temperature: 0 50 C. Environment humidity ±90% U.R. without condensation. CCESSORIES S81 Sensor for methane gas detection. S84 Probe for methane gas detection, certified with TEX II 2G Ex d IIC T6. S82 Sensor for LPG gas detection. S85 Probe for LPG gas detection, certified with TEX II 2G Ex d IIC T6. S83 Sensor for carbon monoxide detection. S86 Probe for carbon monoxide detection, certified with TEX II 2G Ex d IIC T6 S80 Emergency signaling device with fixed light and continuous sound. ZD... Normally closed electromagnetic valves, with quick closing and opening, class with approval. 17
5 S81 - S82 - S83 Gas detection sensors for the control units P81 and P82, 4-20m Combustible gas detection sensors to be used with the electronic control units P81 and P82. The sensors are available in 3 versions: S81 for methane gas and city gas, S82 for LPG and S83 for carbon monoxide. Dimensions (mm) Gas type Operating ambient temperature Protection degree S81 Methane gas, or other light gases C IP44 S82 LPG gas (cylinder liquid gas) or other heavy gases C IP44 S83 CO carbon monoxide C IP44 ELECTRICL CHRCTERISTICS Power supply from the control units P81 or P82. bsorption: 40m (200m). 3 terminals of 2,5 mm² for each sensor: C ( V); S (+4 20m); ( V). STNDRDS ND PPROVLS Complies with Directives/Norms EMC 89/336/CEE, Norm EN
6 INSTLLTION Wall mounting by means of screws and plastic anchors. The correct positioning of the probes is essential for the system proper operation. For this purpose the probes must be installed: in areas where always is required a natural circulation of the air; in areas not subjected to dust and dirt that can clog and disable the sensor; never near water jets, aspiration grilles, windows, vents, etc.; at an adequate distance from gas users to avoid system inappropriate interventions due to possible functional losses. In addition, the positioning depends of the gas type that must be detected: S81: up on the wall, about cm from the ceiling; S82: down on the wall, about cm from the floor; S83: about 1,5 m above the floor. In case of new installations, the sensors must be installed the most lately in order that the typical activity of the building yard (especially welding, painting, sealing, etc.) cannot damage the same detectors (especially their sensing element). TECHNICL FETURES Calibration: S81: 10% LEL Methane; S82: 12% LEL Isobutane; S83: 200ppm CO. Self-extinguishing plastic enclosure. Dimensions 66x90x45 mm (according to the model). Unit weight 0,065 kg. Environment temperature: 0 50 C ( C). Environment humidity ±90% U.R. without condensation. 19
GL-CO-RFG Channel Gas Leak Alarm System
Four Elms Road Edenbridge Kent TN8 6AB UK Features & Benefits Remote sensors for natural gas, LPG and CO 1 x SPST relay outputs DIN-rail as standard, panel mounting kit available Adjustable alarm thresholds
More informationGas leak detection system. for heating rooms and similar environments. Description. Sensor for methane gas IP44. Sensor for LPG gas IP44
s 7 603 INTELLIGAS Gas leak detection system for heating rooms and similar environments Electronic control unit for gas leak detection with up to 4 sensors aimed to drive one or two gas flow cut-off 12VD
More informationCOSTER. Code Internal Alarm Pre-alarm Suitable sensor threshold threshold external sensor
G - RGS 8-8 Eng. 5..08 MZ REV. 0 DOMESTIC MICROPROCESSOR- BASED SELECTIVE DETECTORS WITH RELAY OUTPUT G 5..08 MZ REV. 0 RGS 8-8 Eng. Conform to standards: CEI EN 5094 and CEI EN 5044 for combustible gases
More informationA series of technical features make this gas detector extremely versatile, reliable, accurate, and safe.
Belonging to Made in Italy GS911K Gas Detector GS911K Using the catalytic sensor inside it, the GS911K detector detects the presence of explosive gas such as: Methane, LPG, with trip sensitivity calibrated
More informationGAS LEAK DETECTORS FOR METHANE AND LPG P11 - P12
GAS LEAK DETECTORS FOR METHANE AND LPG P11 - P12 1 Sicurgas P11 and P12 it is a device, that through a sensitive sensor, detects methane gas concentration (P11) and LPG concentration (P12) in domestic
More informationUPON COMMENCMENT OF INSTALLATION IT IS OF PARAMOUNT IMPORTANCE THAT THE STEP BY STEP GUIDE (INCLUDED) IS FOLLOWED COMPLETELY
Important UPON COMMENCMENT OF INSTALLATION IT IS OF PARAMOUNT IMPORTANCE THAT THE STEP BY STEP GUIDE (INCLUDED) IS FOLLOWED COMPLETELY UPON COMMENCMENT OF INSTALLATION IT IS OF PARAMOUNT IMPORTANCE THAT
More informationBX444-Mc Gas Detector
Installation and User Guide Rev.01. BX444-Mc Gas Detector Application Duomo is recognised within the gas industry for providing a comprehensive range of low cost, high reliability gas detection for many
More informationGS100M Gas Detector. Technical Specification
GS00M Detector Application Duomo is recognised within the Gas industry for providing a comprehensive range of low cost, high reliability gas detection for many applications. We have installed and commissioned
More informationCarbon Monoxide (CO) Gas Detectors with (0)2-10 Vdc or (0)4-20 ma Output
Features Electrochemical sensor element (0)2-10 Vdc or (0)4-20 ma output, jumper selectable Standard IP65 plastic enclosure Measuring ranges 0-50 ppm 0-100 ppm 0-150 ppm 0-200 ppm 0-250 ppm 0-300 ppm 0-500
More informationTwo-Channel Gas Controller
Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously
More informationBX444-M Gas Detector. Features. Application. Operation
BX-M Gas Detector Application Duomo is recognised within the gas industry for providing a comprehensive range of low cost, high reliability gas detection for many applications. We have installed and commissioned
More informationGAS LEAK DETECTORS FOR METHANE AND LPG P11 - P12
GAS LEAK DETECTORS FOR METHANE AND LPG P11 - P12 1 Sicurgas P11 and P12 it is a device, that through a sensitive sensor, detects methane gas concentration (P11) and LPG concentration (P12) in domestic
More informationGS100M Gas Detection Controller
GS100M Gas Detection Controller GS100M 1 Zone Gas Detection Controller 1 Zone / Sensor Conventional Positive Safety IP44 EN61010-1 EN50270 FEATURES Single Zone Protection Positive Safety Option Detection
More informationControl Unit BX280 CONFORMITY EN EN EMC EN Isntallation and user Guide. Firmware Version 9.0
Belonging to ontrol Unit BX280 Through the connection of 2 remote probe, the BX280 control unit has been designed and built according to European regulations to detect the presence of toxic and/or explosive
More informationPolyGard Single Point Controller SPC-X3-11XX for Toxic Gases and Oxygen
PolyGard Single Point Controller SPC-X3-XX for Toxic Gases and Oxygen DESCRIPTION Gas measuring, monitoring and warning controller based on state-of-the-art micro-technology with integrated sensor and
More informationCTT8 TEMPERATURE MONITOR DEVICE
INSTRUCTION MANUAL IM302-U v2.3 CTT8 TEMPERATURE MONITOR DEVICE GENERALITY The device of control temperatures CTT8 is used in the control of electric machine, transformer, motor, etc. where it s possible
More informationGS100M Gas Detector. Features. Application. Operation
GS00M Gas Detector Microprocessor control Wall or panel mounted zone protection 4-20mA signal input Measuring range 0-20% L.E.L. / 0-300ppm P44 protective rating EN5094 for explosive gases EN5029 for toxic
More informationMO n : 12JMC rév A
CTT8 MO n : rév A Page 2 / 18 MODIFICATIONS Rev. Description Date Checked by Approuved by Z Creation 2012/02/12 JMC LA A First issue 2012/02/14 JMC LA INDEX Page 3 / 18 GENERALITY 4 INTRODUCTION 4 ACCESSORIES
More informationPolyGard Single Point Controller SPC-X3-34XX for Combustible Gases
PolyGard Single Point Controller SPC-X3-34XX for Combustible Gases DESCRIPTION Gas measuring and monitoring controller based on stateof-the-art microtechnology with integrated sensor for continuous monitoring
More informationGasAlertMicroClip X3 Specifications
GasAlertMicroClip X3 Specifications The instrument must satisfy the following: Physical Specifications Size (h x w x d) Physical size shall be no larger than 4.4 x 2.4 x 1.2 in. / 11.3 x 6.0 x 3.2 cm Weight
More informationPolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours
PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours DESCRIPTION Gas measuring, monitoring and warning controller based on state-of-the-art micro-technology with integrated sensor
More informationTEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev.
TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL Microener- Copyright 2010 FW 2.1 Date 01.12.2008 Rev. 0 1. Generality 3 2. Introduction 3 3. Accessories and Options 3 4. Installation 3 5. Connection
More informationDigital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6
Digital Gas Transmitters with Auxiliary s & Control Specifications subject to change without notice. USA 181011 Page 1 of 5 DESCRIPTION Digital RS-485 communicating, addressable toxic and combustible gas
More informationPERSONAL COMBUSTIBLE GAS DETECTOR
PERSONAL COMBUSTIBLE GAS DETECTOR FEATURES Continuous LCD Reading with Back Light Electronic Audio Alarm Visual Alarms include Icons and Red LED Easy Handling Certified Intrinsically Safe Auto Test When
More informationGAS MONITOR Model Model
Sierra Monitor Corporation 1991 Tarob Court, Milpitas, CA 95035 (408) 262-6611 (800) 727-4377 (408) 262-9042 - Fax E-mail: sierra@sierramonitor.com Web Site: www.sierramonitor.com GAS MONITOR Model 2350-00
More informationSPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System
SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM User Instructions For The Model 5200 Gas Monitor System To completely customize the specifications to your exact application, modifications to the following
More informationGas Safety Products. Installation, operating and maintenance 10/12/2017. Merlin Gas Detectors. Merlin Gas Detectors. American Gas Safety LLC 1
Gas Safety Products Merlin Gas Detectors Installation, operating and maintenance 10/12/2017 American Gas Safety LLC 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Mounting the Merlin
More informationCHCO Double Gas Detector
Belonging to Made in Italy HO Double Gas Detector HO The HO Detector has been designed and built according to European regulations to detect the presence of toxic and explosive gas. A microprocessor is
More informationMacurco CM-21A Carbon Monoxide
Macurco CM-21A Carbon Monoxide Detector and Controller User Instructions for 3M Macurco CM-21A - Low voltage, dual relay Carbon Monoxide (CO) detector and controller Important: Keep these User Instructions
More informationFour Channel Gas Detection System AGDS 4. The Home of Control & Automation in Ireland
Four Channel Gas Detection System AGDS 4 The Home of Control & Automation in Ireland Four Channel Gas Detection System The AGDS-4, Gas detection system has been designed for use in boiler houses and plant
More informationBS-316. Gas detection control panel up to 16 inputs. Installation operation manual
BS-316 Gas detection control panel up to 16 inputs Installation operation manual Page 1 from 21 Contents 1 Operation instructions--------------------------------------------------------------------------------------------------------------------3
More informationControl and Annunciator Panels. Compact systems of signalling and control
Control and Annunciator Panels Compact systems of signalling and control 56 Control and Annunciator Panels Technical features Body material: Polycarbonate V0/UL 9 - Colour: Black degree: IP0 Not replaceable
More informationTECHNICAL CATALOGUE GAS LEAK DETECTOR AND SOLENOID SAFETY VALVES
TECHNICAL CATALOGUE GAS LEAK DETECTOR AND SOLENOID SAFETY VALVES TEC ITAP SpA, founded in Lumezzane (Brescia) in 1972, is currently one of the leading production companies in Italy of valves, fittings
More informationGas Safety Products. Installation, operating and maintenance. Merlin Gas Detectors. Merlin Gas Detectors. Rev: 09 Date: Product Data Sheet
Gas Safety Products Merlin Gas Detectors Installation, operating and maintenance Read these instructions carefully before operating or servicing Rev: 09 Date: 19-01-18 1 The unit should be installed by
More informationGas Safety Products. Installation, operating and maintenance 11/26/2015. Merlin Gas Detectors. Merlin Gas Detectors. American Gas Safety LLC 1
Gas Safety Products Merlin Gas Detectors Installation, operating and maintenance 11/26/2015 American Gas Safety LLC 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Mounting the Merlin
More informationPolyGard 2-channel Gas Controller MGC-03
PolyGard 2-channel Gas Controller MGC-03 DESCRIPTION Gas measuring and monitoring controller based on state-ofthe-art micro-technology with integrated buzzer for continuous monitoring of the ambient air
More informationPioneer-R16 Gas Monitor Operator s Manual
Pioneer-R16 Gas Monitor Operator s Manual Edition 7/2/97 RKI INSTRUMENTS, INC RKI Instruments, Inc. 33248 Central Ave, Union City, CA 94587 (510) 441-5656 Chapter 1: Description About the Pioneer-R16 Gas
More informationPremier Hazard STC Instructions
PREMIER HAZARD Ltd Bessingby Industrial Estate Bridlington YO16 4SJ Tel: +44 (0) 113 239 1111 Fax: +44 (0) 113 239 1131 www.premierhazard.co.uk info@premierhazard.co.uk Premier Hazard STC Instructions
More informationDräger Polytron Fixed Gas Detector. Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors
Dräger Polytron 5700 Fixed Gas Detector Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors Dräger Polytron 5700 Including e-box for increased safety wiring The Dräger
More informationWD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.
Data Sheet Ref: 90501085 WD-CS Water leak detection cable Technical Overview The WD-CS range of cable sensors are typically used to detect water leaks usually under floors, and are used in conjunction
More informationGS300M Gas Detector. Features. Application. Operation
GS300M Gas Detector Microprocessor control Wall or panel mounted 3 zone protection 4-0mA signal input Measuring range 0-0% LEL / 0-300ppm P44 protective rating EN5094 for explosive gases EN509 for toxic
More informationGas Central with built-in Gas Detector for Nitrogen Dioxide (NO 2
Features Integrated (built-in NO2 sensor / detector (Electro chemical sensor type Measuring ranges 0-10 ppm, 0-20 ppm or 0-30 ppm LCD display to show actual in ppm Status LED indication Normal operation
More informationtesto 316-EX gas leak detector Instruction manual
testo 316-EX gas leak detector Instruction manual 2 1 Safety and the environment 1 Safety and the environment 1.1. About this document Use > Please read this documentation through carefully and familiarize
More informationZareba Metro Gas Detector
Zareba Metro Gas Detector The Metro addressable gas detector enables remote monitoring of flammable and toxic gas hazards Metro Gas Detector One-Stop Shop Flammable and toxic gas monitors available Methane,
More informationCH 4 C 2 H 2 C 3 H 8 CO 2 H 2 H 2 S HFC NH 3 NO 2 O 2 O 3 SO 2
PluraSens CH 4 C 2 H 2 C 3 H 8 CO CO 2 H 2 H 2 S HFC NH 3 NO 2 O 2 O 3 SO 2 VOC E2600 Family Gas Detectors E2610 Series Compact wall-mount housing providing optimal airflow Integrated sensor with long
More informationAquiTron. AT-LDM Liquid Detection Module INSTALLATION INSTRUCTIONS
AquiTron Liquid Detection Module INSTALLATION INSTRUCTIONS Please read these instructions carefully and keep them in a safe place (preferably close to the module) for future reference. These instructions
More informationSYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System
SYSTEM MANUAL FT1-SB Single Zone Fire Alarm System DOCUMENT HISTORY Issue Date Description Written By Checked By Draft 0 2/9/2008 Original Document. A. Shenouda C. Orr Issue 1 4/11/2011 Update drawing
More informationGas Detection System SGAES-TG Operating Manual R01
Gas Detection System SGAES-TG Operating Manual 80018-001 R01 Gas Detection Systems SGAES-TG Operating Manual 80018-001 R01 ESP Safety Inc 555 N. First Street San Jose, CA 95112 408-886-9746 April 2011
More informationIR FLAME DETECTOR RIV-601/F
IR FLAME DETECTOR EN 54-10 class 2 VdS approval G 205044 application manual CONTROL LOGIC rev. 4 DEC07 MAFE DEC07 IR FLAME DETECTORS SUMMARY Page general notions...3 description...4. Electrical and general
More informationWaterLeakStop Manual. Detection and Management of Water Leaks WLS-1
WaterLeakStop Manual Detection and Management of Water Leaks WLS-1 Contents: Brief description...3 Specifications:...3 Functions:...3 Pictures - Tables:...4 Terminals...5 Description indicators and buttons...6
More informationGas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. American Gas Safety LLC 1 05/10/2016
Gas Safety Products Installation, operating and maintenance 05/10/2016 American Gas Safety LLC 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting.... 3 2.2 Mains Supply...
More informationCommercial and Light Industrial Fire Alarm Control Panel
FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel Features Easily expandable. All new plug-in board design Two supervised audible circuits Lamp and system trouble circuit test Ground
More informationGas Safety Products. Installation, operating and maintenance 11/18/2015. Merlin 1000S+ Gas Utility & Electrical Isolation Controller
Gas Safety Products Installation, operating and maintenance 11/18/2015 American Gas Safety LLC 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting.... 3 2.2 Power Supply....
More informationSafe Operation Manual. Honeywell IQ Force Gas Detector
Safe Operation Manual Honeywell IQ Force Gas Detector Honeywell Analytics 800-663-4164 403-248-9226 Fax 403-575-3708 03JUN2012 P/N 50105843-047 Version 01 http://www.honeywell.com HONEYWELL IQ Force PERSONAL
More informationSigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009
Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009 CONTENTS Contents... Page Safety & Installation...2 Installation - continued...3
More informationOperating Instructions. For. Alarm Control Module. Model SSR 500
SSR 500 LEVEL CONTROL RELAY MODULE Operating Instructions For Alarm Control Module Model SSR 500 SSR Operation Instructions Rev. 1 Jan 01 Page 1/7 1. Note Please read and take note of these operating instructions
More informationS5000 Gas Monitor. GMS5000.com
S5000 Gas Monitor GMS5000.com A DETECTOR AS TOUGH AS YOU ARE... LOWER TEMPERATURE SPEC?... ARCTIC WINTERS IT HAS TO BE THE MOST RELIABLE PIECE OF EQUIPMENT OUT HERE IF THE DETECTOR DOESN T WORK, WE DON
More informationGas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. Rev: 03 Date:
Gas Safety Products Merlin 1500S Gas Interlock System Installation, operating and maintenance Rev: 03 Date: 08-01-18 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting....
More informationKAB Gas Alarm Operation Manual
KAB Gas Alarm Operation Manual Henan Hanwei Electronics Co.,Ltd ISO9001-2008 Precautions: To avoid personal safety injury, Instrument damage and potential dangerous accident; do not use gas detector before
More informationGas Safety Products. Installation, operating and maintenance. Merlin 1000S+i Gas & Electric Utility Controller. Rev: 03 Date:
Gas Safety Products Merlin 1000S+i Gas & Electric Utility Controller Installation, operating and maintenance Rev: 03 Date: 14-08-18 1 Table of contents 1 General information... 3 2 Installation... 3 2.1
More informationWarranty Registration
WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free from defects in workmanship and materials for a period
More informationALTAIR 5X Multigas Detector Product Specification
ALTAIR 5X Multigas Detector Product Specification PHYSICAL CHARACTERISTICS Gas delivery Size, pumped unit without IR Size, pumped unit with IR Weight Handling Case material Environmental protection Display
More informationCopying contents of this booklet or handing over to third party is strictly forbidden without written permission from Detector Oy.
Installation manual detector and controller Code no. 20711062 Page 1/30 CONTENTS Controller... 2 Function of the Relays... 2 Gas Detectors... 2 Cabling... 4 Mechanical Installation of the gas detectors...
More informationSelf-contained and intrinsically safe wireless stand-alone multi-point gas detector.
Introduction United Safety applies the detection system as a multi-point monitoring for toxic gases, combustibles and oxygen hazards. Self-powered and solar-capable, the features unequaled versatility,
More informationProduct Data Sheet. Merlin GDP2. Gas Safety Products. Merlin GDP2. Installation, operating and maintenance 23/08/2016. S&S Northern Ltd 1
Gas Safety Products Merlin GDP2 Installation, operating and maintenance 23/08/2016 S&S Northern Ltd 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting..... 3 2.2 Mains
More informationEXTINGUISHING CONTROL PANEL PX2 SERIES
EXTINGUISHING CONTROL PANEL PX2 SERIES AE/PX2 AE/SA-PX2 AE/94-PX2 USER MANUAL VERSION 1.0 APR/2007 CONTENT PAGE 1 INTRODUCTION...3 1.1 PURPOSE OF THE MANUAL... 3 1.2 REMARKS... 3 1.3 WARNINGS AND PRECAUTIONS....
More informationMulti Channel Gas Detection System AGDS MC. The Home of Control & Automation in Ireland
Multi Channel Gas Detection System AGDS MC The Home of Control & Automation in Ireland Multi-channel Gas Detection System The AGDS-MC, Gas detection system has been designed for use in boiler houses and
More informationDräger X-am 7000 Multi-Gas Detection
Dräger X-am 7000 Multi-Gas Detection Dräger X-am 7000 is the solution for the simultaneous and continuous measurement of up to five gases. It is the ideal companion in a variety of applications where the
More informationWater Detection Controllers
Page 1 of 5 Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation or erosion
More informationCarbon Monoxide (CO) detection system
1973 Carbon Monoxide (CO) detection system CARB MOXIDE Presentation DESIGN GUIDE AND SELECTI OF CO SYSTEMS The basic purpose of a CO detection system, resides in ensuring a minimum conditions of sanitation
More informationQAS SERIES PLUG-IN CONTROLLERS c/w SOLID STATE SENSOR
QAS-10000 SERIES PLUG-IN CONTROLLERS c/w SOLID STATE SENSOR INSTALLATION, OPERATION AND MAINTENANCE MANUAL QUATROSENSE ENVIRONMENTAL LTD. 5935 OTTAWA STREET, PO BOX 749, RICHMOND, ONTARIO, CANADA. K0A
More informationGasSens. Self Checking Gas Sensors. Modular Gas Detector... Gas & Range Availability
GasSens Modular Gas Detector... Self Checking Gas Sensors GasSens is a flexible component system providing a variety of options to meet individual gas detection and alarm requirements. From chemical and
More informationPAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00
PAT E N T System 88 COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 Pg 1 of 12 CONTENTS 1. GENERAL 1.1 Introduction 2 1.2 System Description
More informationGas Detection System TOX ALARM DG2000-Garage
Gas Detection System TOX ALARM DG2000-Garage Gas Detection System 32 independent programmable channels 2 programmable alarm levels for each gas = up to 6 for each channel LCD alphanumeric display of gas
More informationGas Safety Products. Installation, operating and maintenance. Merlin Gas Detectors. Read these instructions carefully before operating or servicing.
Gas Safety Products Merlin Gas Detectors Read these instructions carefully before operating or servicing. Installation, operating and maintenance S&S Northern Ltd 1 The unit should be installed by a competent
More informationDräger Polytron 5700 IR Detection of flammable gases and vapours
Dräger Polytron 5700 IR Detection of flammable gases and vapours The Dräger Polytron 5700 IR is a cost effective explosion-proof transmitter for the detection of flammable gases in the lower explosive
More informationTECHNICAL INSTRUCTIONS
Carbon Monoxide Detector Installation Instructions TECHNICAL INSTRUCTIONS Carbon Monoxide Detector Installation Instructions This document provides instructions for installing the Carbon Monoxide Detector
More informationRAM3 Remote Alarm Module
RAM3 Remote Alarm Module INSTRUCTIONS Installation and Operation of the AMC-RAM3 with AMC Monitors IMPORTANT: Please read this installation and operating instructions completely and carefully before starting.
More informationGas Safety Products. Installation, operating and maintenance. Merlin 1000VW+ Gas Interlock, Gas Proving, Electric & Water Isolation System
Gas Safety Products Merlin 1000VW+ Gas Interlock, Gas Proving, Electric & Water Isolation System Installation, operating and maintenance Read these instructions carefully before operating or servicing
More informationWARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro
A d e v i h c r D c o n e m u WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free from defects in workmanship
More informationPR5. INSTRUCTION MANUAL IM846-U v0.4
INTRUCTION MANUAL IM846-U v0.4 REMOTE IGNALLING AND CONTROL PANEL to join to the following devices for the permanent insulation control: HRI-R40 HRI-R22t HRI-R22 HRI-R24 HRI-R24N GENERAL The remote signalling
More informationNitrogen Dioxide (NO2) Single-Point Gas Detection System
Nitrogen Dioxide (NO) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in nitrogen dioxide (NO)/diesel fume gas sensor, accepts one analog remote device such as a secondary
More informationWater Leak Detector - Four Zone with open/short-circuit detection. Product overview
Water Leak Detector - Four Zone with open/short-circuit detection Product overview The AX-WLDF is a four zone water leak detection module with open or short circuit sensor cable detection. The module must
More informationGas Safety Products. Installation, operating and maintenance. Merlin 1000BH Gas Proving/Gas Detection System
Gas Safety Products Merlin 1000BH Gas Proving/Gas Detection System Installation, operating and maintenance Read these instructions carefully before operating or servicing Rev: 05 Date: 08-01-18 1 Table
More informationMODEL B2 INSTALLATION MANUAL
RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and
More informationGas Safety Products. Installation, operating and maintenance 23/08/2016. Merlin 1000BH Gas Proving/Gas Detection System
Gas Safety Products Merlin 1000BH Gas Proving/Gas Detection System Installation, operating and maintenance 23/08/2016 S&S Northern Ltd 1 Table of contents 1 General information... 3 2 Installation... 3
More informationINSTRUCTION MANUAL. Software Revision Card 3.2 DOCUMENT SES-KS E REV. 3
2402 COMBUSTIBLE GAS CARD 2 CHANNELS 2404 TOXIC GAS CARD 2 CHANNELS 2407 OXYGEN GAS CARD 2 CHANNELS INSTRUCTION MANUAL Software Revision Card 3.2 DOCUMENT SES-KS-2402-04-07-E REV. 3 2402 2404 2407-2 CHANNELS
More informationDIGITAL ALARM UNIT Model ALU-AP
DIGITAL ALARM UNIT Model ALU-AP Description Digital alarm unit ALU-AP has the following characteristics: 1. Operates in MASTER or SLAVE mode. 2. It can connect with other devices through a RS485 network
More informationULTIMA X5000. MSAX5000.com
ULTIMA X5000 MSAX5000.com WE KNOW YOU RE TIRED OF... NEEDING TO DISCONNECT POWER BEFORE CHANGING A SENSOR REMEMBERING HOW TO CALIBRATE THIS THING HAVING TO PULL SO MUCH WIRE AT EVERY GAS DETECTOR INSTALLATION...
More informationFireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel
PROTECTOWIRE FireSystems Features Easily expandable Two supervised audible circuits Lamp and system trouble circuit test Ground fault detection Initiating device circuit (IDC) alarm test Monitors up to
More informationWarranty Registration
WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free from defects in workmanship and materials for a period
More informationLodam Compressor Protection Module. Technical manual. Version 3.0 SE-G1
Lodam Compressor Protection Module Technical manual Version 3.0 SE-G1 Contents 1. Read this first... 4 1.1. Reading instructions... 4 1.2. User manual... 4 1.3. Safety... 4 2. General... 5 3. Definitions...
More informationTechnical Manual. Level Alarm Unit CARLA & WIDS
CARLA & WIDS Technical Manual SAS au Capital de 2 158 244-444 871 933 R.C.S. Bourges - APE : 2651B Headquarter : 9, rue Isaac Newton - 18000 Bourges - France Technical Manual CARLA for Tankers Cargo Tanks
More informationMTRA-FSP Level Control Relay. Installation & Operation Manual
MTRA-FSP Level Control Relay Installation & Operation Manual This Manual is the support documentation for the installation, commissioning and operation of the MTRA-FSP Level Control Relay. Document Revision
More informationMacurco CM-E1 Carbon Monoxide Detector
Macurco CM-E1 Carbon Monoxide Detector User Instructions Important: These User Instructions are to be provided to the homeowner/end user upon product installation. Each person installing or using this
More informationGS920 Gas Detector with Earthquake-proof Device
Belonging to Made in Italy GS920 Gas Detector with Earthquake-proof Device The GS920 is a high-technology device, thanks to its innovative Seismic Detection feature and the possibility of selecting the
More informationGS920 Gas Detector with Earthquake-proof Device
Belonging to Made in Italy GS920 Gas Detector with Earthquake-proof Device The GS920, thanks to its innovative Seismic Detection feature and the possibility of selecting the Intrinsic Safety Control, is
More informationFlame Safeguards LFE10. Building Technologies HVAC Products
7 71 Flame Safeguards LAE LFE Flame safeguards for burners with intermittent operation The LAE is used for the supervision and indication of oil flames The LFE is used for the supervision and indication
More informationFEC403EN Installation Manual
FEC403EN Installation Manual P/N 10-4101-501-2FC1-01 ISS 22JAN15 Copyright Trademarks and patents Manufacturer 2015 UTC Fire & Security. All rights reserved. The FEC403EN name and logo are trademarks of
More informationLC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV
LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998
More information