The purpose of this addendum is to further clarify the requirements of the plans and specifications.

Size: px
Start display at page:

Download "The purpose of this addendum is to further clarify the requirements of the plans and specifications."

Transcription

1 ADDENDUM #2 PROJECT: OWNER: ARCHITECT: Door Access Control System for Campus Trigg County Schools Cadiz, KY Trigg County Board of Education 202 Main Street Cadiz, KY JKS Architects & Engineers 402 Liberty Street Hopkinsville, KY ISSUE DATE: July 17, 2012 ISSUED BY: JKS ARCHITECTS & ENGINEERS The purpose of this addendum is to further clarify the requirements of the plans and specifications. The bidders shall be governed by the information in this addendum as if included in the plans and specifications. This addendum does hereby become part of the contract documents. Each bidder shall acknowledge receipt of this addendum in the space provided on the bid form. Item # 1: Item # 2: Item # 3: Item # 4: Refer to Drawing A-0: Revised riser diagrams on attached Sheet A-0a shall replace riser diagrams shown on Drawing A-0. Refer to Drawings A-3.1, A-3.2, A-4.1 and A-4.2: The K symbol at Door 306 means a reader with keypad. Refer to Specification Section The new Prox Readers for the elevator shall be connected to the new access control system. Refer to Drawing A-5: The B symbol at Door 502 means a new push button for the door bell system. Refer to Specification Section Refer to all drawings: Change all DVR references to NVR. Page 1 Addendum # 2 Door Access Control System for Campus Trigg County Schools

2 Item # 5: Refer to Specification Section : All new hollow metal frames shall be grouted solid. Item # 6: Refer to Specification Section : Change 2.2-A-1 to read Hager Roton 780 Series heavy duty, concealed leaf, continuous geared aluminum hinge. 2.2-A-2. Subject to compliance with all requirements of Architect s drawings and specifications, equal products by Select Hinges (Portage, MI), will be acceptable. 2.4-J-2. Subject to compliance with all requirements of Architect s drawings and specifications, equal products by Detex Corp. (New Braunfels, TX), will be acceptable Closers shall be equal to Norton 7500/7700 Series. Item # 7: Refer to Specification Section : Name and contact information for Owner s elevator service company: Thyssen Krupp Josh Heistland josh.heistland@thyssenkrupp.com Item # 8: Refer to Specification Section : Replace entire specification section with attached revised section dated Item # 9: See attached copy of sign-in sheet for pre-bid meeting that was held on END OF ADDENDUM # 2 Page 2 Addendum # 2 Door Access Control System for Campus Trigg County Schools

3

4 SECTION ACCESS CONTROL PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes furnishing and installing a complete access control system as outlined on the Architect's drawings and specified herein. The contractor is responsible for providing a complete access control system that includes all items necessary to make the system fully functional. The contractor is responsible for interface components and assuring the compatibility of the multiple components. Components include (but are not limited to): 1. Proximity card readers. 2. Photo ID proximity cards (compatible with owner's existing card printer). 3. PC, hardware and software for programming the proximity cards. 4. Cameras and power supplies. 5. Intercom Stations. 6. Access Controllers and Cabinets. 7. Access Control Software. 8. Network Video Recorder. 9. Network Switches. 10. U.P.S. / Surge protectors. 11. Door bell and button system (at Gym). 12. Keypad / Reader (at Kitchen). 13. Furnishing and installing all conduit and cabling. 14. All headend equipment for audio and access control. B. This section also includes furnishing and installing proximity card readers for elevators (refer to alternate bid #2). This includes transformers, conduit and cabling to the associated elevator equipment room. Final connections for these proximity card readers shall be made under section C. Related Sections include the following: 1. Division 14 Section "Access Control for Existing Elevators". 1.3 DEFINITIONS A. CCTV: Closed-circuit television. B. LAN: Local area network. C. PC: Personal computer. This acronym applies to the Central Station, workstations, and file servers. ACCESS CONTROLS

5 D. RF: Radio frequency. E. TCP/IP: Transport control protocol/internet protocol incorporated into Microsoft Windows. F. UPS: Uninterruptible power supply. G. WAN: Wide area network. H. Windows: Operating system by Microsoft Corporation. I. Workstation: A PC with software that is configured for specific limited security system functions. J. POE: Power over ethernet. 1.4 PERFORMANCE REQUIREMENTS A. Security access system shall use a single database for access-control and credential-creation functions. System functionality shall include (but not be limited to) the following: 1. Motion detector in camera triggers the NVR to record video with date & time stamp. 2. Motion detection zone is user definable for each camera. 3. Use of proximity card reader opens electric strike and records name, date & time in the event log. 4. If staff remotely opens the electric strike then user name, date & time are recorded in the event log. 5. Strike and bolt position switches are monitored at the command center PC workstations. 6. Access control software can be programmed to automatically open and close any combination of electric strikes in accordance with owner's class changing schedule. 7. Pressing intercom button initiates a two-way conversation with staff at the command center location. 8. Access control software at command centers can "lock down" all controlled doors on a specific building in one step. 9. Access control software at command centers can "lock down" all controlled doors on entire campus in one step. B. Distributed Processing: System shall be a fully distributed processing system so that information, including time, date, valid codes, access levels, and similar data, is downloaded to Controllers so that each Controller makes access-control decisions for that Location. Do not use intermediate Controllers for access control. If communications to Central Station are lost, all Controllers shall automatically buffer event transactions until communications are restored, at which time buffered events shall be uploaded to the Central Station. C. Door Hardware Interface: Coordinate with Division 08 Sections that specify door hardware required to be monitored or controlled by the security access system. The Controllers in this Section shall have electrical characteristics that match the signal and power requirements of door hardware. Integrate door hardware specified in Division 08 Sections to function with the controls and PC-based software and hardware in this Section. ACCESS CONTROLS

6 1.5 SUBMITTALS A. Product Data: For each type of product indicated. Include operating characteristics, furnished specialties, and accessories. Reference each product to a location on Drawings. Test and evaluation data presented in Product Data shall comply with SIA BIO-01. B. Shop Drawings: 1. Diagrams for cable management system. 2. System labeling schedules, including electronic copy of labeling schedules that are part of the cable and asset identification system of the software specified in Parts 2 and Wiring Diagrams. Show typical wiring schematics including the following: a. Workstation outlets, jacks, and jack assemblies. b. Patch cords. c. Patch panels. 4. Cable Administration Drawings: As specified in Part 3 "Identification" Article. C. Project planning documents as specified in Part 3. D. Field quality-control test reports. E. Operation and Maintenance Data: For security system to include in emergency, operation, and maintenance manuals. In addition to items specified in Division 01 Section "Operation and Maintenance Data" include the following: 1. Microsoft Windows software documentation. 2. PC installation and operating documentation, manuals, and software for the PC and all installed peripherals. Software shall include system restore, emergency boot diskettes, and drivers for all installed hardware. Provide separately for each PC. 3. Hard copies of manufacturer's specification sheets, operating specifications, design guides, user's guides for software and hardware, and PDF files on CD-ROM of the hardcopy submittal. 4. System installation and setup guides, with data forms to plan and record options and setup decisions. 1.6 QUALITY ASSURANCE A. Installer Qualifications: An employer of workers trained and approved by manufacturer. B. Testing Agency Qualifications: An independent agency, with the experience and capability to conduct the testing indicated, that is a nationally recognized testing laboratory (NRTL) as defined by OSHA in 29 CFR , and that is acceptable to authorities having jurisdiction. C. Source Limitations: Obtain Controllers, readers, and all software through one source from a single manufacturer. ACCESS CONTROLS

7 D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. E. Comply with NFPA 70, "National Electrical Code." 1.7 EXTRA MATERIALS A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Two proximity card readers. 2. Two cameras. 3. Two intercom stations. PART 2 - PRODUCTS 2.1 PROXIMITY CARD READERS A. Basis of design is Honeywell OmniProx series. Equal products by HID, Stanley or GE will be acceptable. B. Bezel color shall be black. 2.2 PHOTO ID PROXIMITY CARDS A. Basis of design is HID ISOProx 2. Equal products by Honeywell, Stanley or GE will be acceptable. Prox cards must be compatibile with owner's existing badge printer. B. Furnish 400 prox cards (slot punched) complete with lanyards. Verify slot punch (horizontal or vertical) with owner prior to ordering. 2.3 PC HARDWARE & SOFTWARE FOR PROGRAMMING PROX CARDS A. Furnish and install a network connected Windows PC workstation for programming prox cards. Verify location with owner. This workstation shall meet (or exceed) system requirements for the programming software. B. Furnish and install prox card programming software on this workstation. C. This PC shall also have Pelco client software installed to review and retrieve video from all Network Video Recorders. 2.4 CAMERAS AND POWER SUPPLIES A. Basis of design is Pelco Sarix IM10-E series. Equal products by Sony or Panasonic will be acceptable. ACCESS CONTROLS

8 B. All mounting accessories and power supplies shall be included. 2.5 INTERCOM STATIONS A. Basis of design is Aiphone LEF system. Equal products by Rauland or Nutone will be acceptable. B. Provide master stations at all command center locations as indicated on drawings. C. Provide sub stations at door locations indicated on drawings. Sub stations shall be weather resistant. 2.6 ACCESS CONTROLLERS AND CABINETS A. Basis of design is Honeywell N-1000 series. Equal products by GE or Stanley will be acceptable. B. Furnish complete with controller modules, battery, communication device(s), relays, enclosure, transformer, etc. 2.7 ACCESS CONTROL SOFTWARE A. Basis of design is Honeywell Win-Pak PE 3.0. Equal products by GE or Stanley will be acceptable. B. Unrestricted number of client workstations. 2.8 NETWORK VIDEO RECORDER A. Basis of design is Pelco Digital Sentry series. Equal products by Honeywell, GE or Stanley will be acceptable. B. H.264 standard definition, supports 128 IP camera streams, 3TB of storage, dvd burner, client and server software, remote control, full function remote client, HDD storage manager, scheduled backup to usb or dvd. 2.9 NETWORK SWITCHES A. Basis of design is Enterasys model B5G124-24P2, 24 port managed switch with POE. Equal products by Cisco or Linksys will be acceptable U.P.S. / SURGE PROTECTORS A. Basis of design is APC back-ups XS series, BX1500G, 1500VA/865 watt. Equal products by Tripp Lite or Belkin will be acceptable. ACCESS CONTROLS

9 2.11 DOOR BELL AND BUTTON SYSTEM A. Basis of design for exterior push button is Securitron PB series, no wording on button, commercial grade, weather resistant. Furnish wall mounted acrylic sign that reads "Push Button to Request Entry". Equal products by Rauland or Quam will be acceptable. B. Basis of design for interior bell is Pyramid Technologies model 41392, 24vdc, 8" diameter, wall mount. Furnish with transformer, relay and on/off wall switch. Also furnish and install a wire guard over bell. Equal products by Federal Signal or Wermer will be acceptable KEYPAD / READER A. Basis of design is Honeywell Omniclass series with keypad. Equal products by HID, Stanley or GE will be acceptable. B. Bezel color shall be black CONDUIT AND CABLING A. Shall be as required by component manufacturer and per NFPA 70 National Electric Code and 2007 Kentucky Building Code. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine pathway elements intended for cables. Check raceways, cable trays, and other elements for compliance with space allocations, installation tolerances, hazards to cable installation, and other conditions affecting installation. B. Examine roughing-in for LAN and control cable conduit systems to PCs, Controllers, card readers, and other cable-connected devices to verify actual locations of conduit and back boxes before device installation. C. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 PREPARATION A. Comply with recommendations in SIA CP-01. B. Comply with EIA/TIA-606, "Administration Standard for the Telecommunications Infrastructure of Commercial Buildings." C. Obtain detailed Project planning forms from manufacturer of access-control system; develop custom forms to suit Project. Fill in all data available from Project plans and specifications and publish as Project planning documents for review and approval. 1. Record setup data for control station and workstations. 2. For each Location, record setup of Controller features and access requirements. ACCESS CONTROLS

10 3. Propose start and stop times for time zones and holidays, and match up access levels for doors. 4. Set up groups, facility codes, linking, and list inputs and outputs for each Controller. 5. Assign action message names and compose messages. 6. Set up alarms. Establish interlocks between alarms, intruder detection, and video surveillance features. 7. Prepare and install alarm graphic maps. 8. Develop user-defined fields. 9. Develop screen layout formats. 10. Propose setups for guard tours and key control. 11. Discuss badge layout options; design badges. 12. Complete system diagnostics and operation verification. 13. Prepare a specific plan for system testing, startup, and demonstration. 14. Develop acceptance test concept and, on approval, develop specifics of the test. 15. Develop cable and asset management system details; input data from construction documents. Include system schematics and Visio Technical Drawings. D. In meetings with Architect and Owner, present Project planning documents and review, adjust, and prepare final setup documents. Use final documents to set up system software. 3.3 CABLING A. Comply with NECA 1, "Good Workmanship in Electrical Contracting." B. Install cables and wiring according to requirements in Division 28 Section "Conductors and Cables for Electronic Safety and Security." C. Wiring Method: Install wiring in raceway and cable tray except within consoles, cabinets, desks, and counters. Conceal raceway and wiring except in unfinished spaces. D. Wiring Method: Install wiring in raceway and cable tray except within consoles, cabinets, desks, and counters and except in accessible ceiling spaces and in gypsum board partitions where unenclosed wiring method may be used. Use NRTL-listed plenum cable in environmental air spaces, including plenum ceilings. Conceal raceway and cables except in unfinished spaces. E. Install LAN cables using techniques, practices, and methods that are consistent with Category 6E rating of components and that ensure Category 6E performance of completed and linked signal paths, end to end. F. Install cables without damaging conductors, shield, or jacket. G. Boxes and enclosures containing security system components or cabling, and which are easily accessible to employees or to the public, shall be provided with a lock. Boxes above ceiling level in occupied areas of the building shall not be considered to be accessible. Junction boxes and small device enclosures below ceiling level and easily accessible to employees or the public shall be covered with a suitable cover plate and secured with tamperproof screws. H. Install end-of-line resistors at the field device location and not at the Controller or panel location. ACCESS CONTROLS

11 3.4 CABLE APPLICATION A. Comply with EIA/TIA-569, "Commercial Building Standard for Telecommunications Pathways and Spaces." B. Cable application requirements are minimum requirements and shall be exceeded if recommended or required by manufacturer of system hardware. C. RS-232 Cabling: Install at a maximum distance of 50 feet (15 m). D. RS-485 Cabling: Install at a maximum distance of 4000 feet (1220 m). E. Card Readers and Keypads: 1. Install number of conductor pairs recommended by manufacturer for the functions specified. 2. Unless manufacturer recommends larger conductors, install No. 22 AWG wire if maximum distance from Controller to the reader is 250 feet (75 m), and install No. 20 AWG wire if maximum distance is 500 feet (150 m). 3. For greater distances, install "extender" or "repeater" modules recommended by manufacturer of the Controller. 4. Install minimum No. 18 AWG shielded cable to readers and keypads that draw 50 ma or more. F. Install minimum No. 16 AWG cable from Controller to electrically powered locks. Do not exceed 250 feet (75 m). G. Install minimum No. 18 AWG ac power wire from transformer to Controller, with a maximum distance of 25 feet (8 m). 3.5 GROUNDING A. Comply with Division 26 Section "Grounding and Bonding for Electrical Systems." B. Comply with IEEE 1100, "Power and Grounding Sensitive Electronic Equipment." C. Ground cable shields, drain conductors, and equipment to eliminate shock hazard and to minimize ground loops, common-mode returns, noise pickup, cross talk, and other impairments. D. Bond shields and drain conductors to ground at only one point in each circuit. E. Signal Ground: 1. Terminal: Locate in each equipment room and wiring closet; isolate from power system and equipment grounding. 2. Bus: Mount on wall of main equipment room with standoff insulators. 3. Backbone Cable: Extend from signal ground bus to signal ground terminal in each equipment room and wiring closet. ACCESS CONTROLS

12 3.6 INSTALLATION A. Push Buttons: Where multiple push buttons are housed within a single switch enclosure, they shall be stacked vertically with each push-button switch labeled with 1/4-inch- (6.4-mm-) high text and symbols as required. Push-button switches shall be connected to the Controller associated with the portal to which they are applied, and shall operate the appropriate electric strike, electric bolt, or other facility release device. B. Install card, fob, and biometric readers. 3.7 IDENTIFICATION A. In addition to requirements in this Article, comply with applicable requirements in Division 26 Section "Identification for Electrical Systems" and with TIA/EIA-606. B. Using cable and asset management software specified in Part 2, develop Cable Administration Drawings for system identification, testing, and management. Use unique, alphanumeric designation for each cable, and label cable and jacks, connectors, and terminals to which it connects with same designation. Use logical and systematic designations for facility's architectural arrangement. C. Label each terminal strip and screw terminal in each cabinet, rack, or panel. 1. All wiring conductors connected to terminal strips shall be individually numbered, and each cable or wiring group being extended from a panel or cabinet to a building-mounted device shall be identified with the name and number of the particular device as shown. 2. Each wire connected to building-mounted devices is not required to be numbered at the device if the color of the wire is consistent with the associated wire connected and numbered within the panel or cabinet. D. At completion, cable and asset management software shall reflect as-built conditions. 3.8 SYSTEM SOFTWARE A. Develop, install, and test software and databases for the complete and proper operation of systems involved. Assign software license to Owner. 3.9 FIELD QUALITY CONTROL A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust field-assembled components and equipment installation, including connections, and to assist in field testing. Report results in writing. B. Testing Agency: Engage a qualified testing and inspecting agency to perform field tests and inspections and prepare test reports: C. Perform the following field tests and inspections and prepare test reports: ACCESS CONTROLS

13 1. LAN Cable Procedures: Inspect for physical damage and test each conductor signal path for continuity and shorts. Use Class 2, bidirectional, Category 6 tester. Test for faulty connectors, splices, and terminations. Test according to TIA/EIA-568-1, "Commercial Building Telecommunications Cabling Standards - Part 1 General Requirements." Link performance for UTP cables must comply with minimum criteria in TIA/EIA-568-B. 2. Test each circuit and component of each system. Tests shall include, but are not limited to, measurements of power supply output under maximum load, signal loop resistance, and leakage to ground where applicable. System components with battery backup shall be operated on battery power for a period of not less than 10 percent of the calculated battery operating time. Provide special equipment and software if testing requires special or dedicated equipment. 3. Operational Test: After installation of cables and connectors, demonstrate product capability and compliance with requirements. Test each signal path for end-to-end performance from each end of all pairs installed. Remove temporary connections when tests have been satisfactorily completed. D. Remove and replace malfunctioning devices and circuits and retest as specified above STARTUP SERVICE A. Engage a factory-authorized service representative to supervise and assist with startup service. Complete installation and startup checks according to approved procedures that were developed in " Preparation" Article and with manufacturer's written instructions. 1. Enroll and prepare badges and access cards for Owner's operators, management, and security personnel PROTECTION A. Maintain strict security during the installation of equipment and software. Rooms housing the control station, and workstations that have been powered up shall be locked and secured, with an activated burglar alarm and access-control system reporting to a Central Station complying with UL 1610, "Central-Station Burglar-Alarm Units," during periods when a qualified operator in the employ of Contractor is not present TRAINING A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain security access system. Record video of training session(s) and provide a dvd copy with close out documentation. END OF SECTION ACCESS CONTROLS

14

B. After installation, the Owner shall be able to perform hardware configuration changes as desired without the services of the Integrator.

B. After installation, the Owner shall be able to perform hardware configuration changes as desired without the services of the Integrator. SECTION 281300 - ACCESS CONTROL SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Minimum standards for Access Control Systems. B. Related Requirements: 1. Section 087100 Door Hardware. 1.2 REFERENCES

More information

CARD ACCESS CONTROL SYSTEM

CARD ACCESS CONTROL SYSTEM SECTION 13851 CARD ACCESS CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested, integrated proximity access control system, to operate on a proximity principle where

More information

SECTION INTRUSION DETECTION

SECTION INTRUSION DETECTION (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ). SECTION 28 13 00 - ACCESS CONTROL PART I - GENERAL 1.1 SUMMARY A. This specification section describes the furnishing, installation, commissioning, and programming of a complete, turnkey, hardwired Andover

More information

SECTION SECURITY TESTING AND COMMISSIONING

SECTION SECURITY TESTING AND COMMISSIONING SECTION 280800 - SECURITY TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 WORK INCLUDES A. General Description: This specification section covers the provision of preliminary testing, acceptance testing,

More information

RFP Addendum 2 March 31, 2016

RFP Addendum 2 March 31, 2016 RFP Addendum 2 March 31, 2016 For Best Value Procurement Option Three Security Upgrades Ph 1 UT Health Science Center SBC No. 540/013-04-2015 This Addendum forms a part of the Request for Proposals (RFP)

More information

Section PERIMETER SECURITY SYSTEMS

Section PERIMETER SECURITY SYSTEMS Section 28 16 43 PERIMETER SECURITY SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Provide and install a perimeter security system as herein specified for the purpose of detecting entry into a designated security

More information

Access CONTROL. MANAGEMENT Software

Access CONTROL. MANAGEMENT Software Software Guide Access CONTROL MANAGEMENT Software Engineered to meet today s demands and tomorrow s challenges, Keyscan s System VII software delivers unique features to provide an access control solution

More information

The system should also be capable of recording events automatically on any compatible DVR and should be able to retrieve recordings based on events.

The system should also be capable of recording events automatically on any compatible DVR and should be able to retrieve recordings based on events. 0BThe System The Security Management System should be capable of Controlling and Monitoring Access through the doors, Monitor and control Inputs and Outputs, include an Integrated Video Badging, Integrate

More information

USD 380 Centralia, Frankfort & Vermillion

USD 380 Centralia, Frankfort & Vermillion PROJECT MANUAL District Wide Security Upgrade Project Software and Hardware Specifications Covering Locking Hardware Access Control Software & Hardware Video Software & Hardware January 30, 2018 USD 380

More information

SECTION ENCLOSED CONTROLLERS

SECTION ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes ac,

More information

SECTION INTRUSION DETECTION SYSTEM

SECTION INTRUSION DETECTION SYSTEM SECTION 13845 INTRUSION DETECTION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested intrusion detection system, bearing Underwriters Laboratories (UL) mercantile listing

More information

BSD Technical Standard. Division 28: Electronic Safety & Security

BSD Technical Standard. Division 28: Electronic Safety & Security Division 28: Electronic Safety & Security I. PURPOSE This Technical Standard is a narrative describing Beaverton School District s (BSD s) basis of design for electronic safety and security in BSD facilities.

More information

ONYX FirstVision Specification Interactive Firefighters Display

ONYX FirstVision Specification Interactive Firefighters Display ONYX FirstVision Specification Interactive Firefighters Display NOTIFIER is a registered trademark, and ONYX FirstVision, NOTI FIRE NET, and VeriFire are trademarks of Honeywell International Inc. Microsoft

More information

SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY

SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY SECTION 28 0513 -CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

CRESTRON MEDIAMANAGER INTELLICLASS

CRESTRON MEDIAMANAGER INTELLICLASS CRESTRON MEDIAMANAGER INTELLICLASS Crestron IntelliClass systems provide educators with a simplified yet comprehensive classroom presentation solution that saves time and money. Designed to deliver the

More information

SECTION (13730) - INTRUSION DETECTION

SECTION (13730) - INTRUSION DETECTION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: SECTION 28 16 00 (13730) - INTRUSION DETECTION 1. Intrusion Detection Sensors 2. Signal Equipment 3. System Controls 4. Alarm Displays 5. Alarm Indicating

More information

Nash Rocky Mount Schools. Specifications for; Upgrades and Additions to Existing Door Access Control System Phase 3

Nash Rocky Mount Schools. Specifications for; Upgrades and Additions to Existing Door Access Control System Phase 3 Nash Rocky Mount Schools Specifications for; Upgrades and Additions to Existing Door Access Control System Phase 3 Access Control System Section 281300 Page 1 Nash Rocky Mount Schools is seeking bids to

More information

Access Control for. Part 3 of 4. Brought to You by. Presented by Video Security Consultants

Access Control for. Part 3 of 4. Brought to You by. Presented by Video Security Consultants 2008 Video Security Consultants Brought to You by Presented by Part 3 of 4 A1 Part 3 of 4 Taking a Hard Look at Software The essential function of an electronic access control system (EACS) is to control

More information

A. This Section includes the following lighting control devices:

A. This Section includes the following lighting control devices: SECTION 26 09 23 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

GMS GRAPHICAL MANAGEMENT SYSTEM

GMS GRAPHICAL MANAGEMENT SYSTEM GMS GRAPHICAL MANAGEMENT SYSTEM 1 GMS Security management system for multi-site organizations. PACOM Graphical Management System (GMS) is the modular client-server application that integrates all of PACOM

More information

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS SECTION 26 92 50 PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

DOOR MONITORING/DURESS SYSTEM

DOOR MONITORING/DURESS SYSTEM SECTION PART 1 - GENERAL 1.1 RELATED SECTIONS A. Comply with the requirements of Section 27 05 00 Common Work Results for Communications. 1.2 DEFINITIONS A. Not used. 1.3 DESCRIPTION OF SYSTEM: A. Provide

More information

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE The University of Arizona has implemented a Keyless Access and Security System program to provide a cost effective, efficient, and maintainable means

More information

A. The requirements of this Section and the other Division 26, 27 & 28 Sections apply to all the video surveillance system work.

A. The requirements of this Section and the other Division 26, 27 & 28 Sections apply to all the video surveillance system work. PART 1 GNRAL 1.1. APPLICABL PROVISIONS A. The General, Supplementary and other Conditions of the Contract, modifications to the General Conditions, the Drawings, and the applicable provisions of the other

More information

SECTION LIGHTING CONTROL DEVICES

SECTION LIGHTING CONTROL DEVICES SECTION 16145 LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Control Panels. Control Panels for Commercial Applications. Control panels provide the central processing

Control Panels. Control Panels for Commercial Applications. Control panels provide the central processing Control Panels Control Panels for Commercial Applications Control panels provide the central processing and logic for an integrated system. In a typical system, there are four major functions: inputs,

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES ACCESS CONTROL SYSTEM

CONSULTANT PROCEDURES & DESIGN GUIDELINES ACCESS CONTROL SYSTEM GENERAL: To provide minimum standards for Access Control Systems. PART 1 Common Work Results for Access Control System 1.1 Owner will provide server and software for connecting control panels through the

More information

CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 1

CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 1 GREEN LIGHT ARCHITECTURAL DIMMING CONTROLS (GLPD) Crestron Green Light and Green Light Express Network Dimming Control Systems are web accessible, network connected dimming control systems that receive

More information

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Emery County Senior Center Green River 06/07

Emery County Senior Center Green River 06/07 SECTION 260923 - LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Architectural and Engineering Specification for a Real-Time Locating System Flare

Architectural and Engineering Specification for a Real-Time Locating System Flare Architectural and Engineering Specification for a Flare AE-T1-IN-R3-E-0617 Page 1 of 14 This document is intended to provide performance specifications and operational requirements for the Flare. It is

More information

IN2 Lighting Control Devices

IN2 Lighting Control Devices Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Lighting Control Devices Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

Electronic Safety and Security

Electronic Safety and Security 28 Electronic Safety and Security NOTE: This is a new section, which includes content from previous sections of the KU Design Standards, along with appropriate revisions and updates. Significant revisions

More information

SECTION NURSE CALL SYSTEM

SECTION NURSE CALL SYSTEM NURSE CALL SMARTCARE NURSE CALL SOLUTION Architectural Specifications Part 1 General SECTION 275223 - NURSE CALL SYSTEM 1.0 Summary 1.1 This section includes nurse call system and requirements for system

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

A. This Section includes the following lighting control devices:

A. This Section includes the following lighting control devices: Attachment G LIGHTING CONTROL SPECIFICATIONS (Download Document separately) LIGHTING CONTROL SPECIFICATIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including

More information

5. Identification products.

5. Identification products. Essex County College - West Essex Campus Addition And Renovations dib # 54292 / 11-14 [SECTION 260523- CONTROL-VOLTAGE ELECTRICAL POWER CABLES PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general

More information

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 28 3111 DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Heat detectors.

More information

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 1.0 General 1.1 Manufacturer Manufacturer of the Fire Alarm Control Panel (FACP) equipment shall be: Digital Monitoring Products, Incorporated 2500 N.

More information

Addendum # 2 Wicomico County Circuit Court Second Floor Renovations Date of Addendum: 2/6/2017

Addendum # 2 Wicomico County Circuit Court Second Floor Renovations Date of Addendum: 2/6/2017 Wicomico County Purchasing 125 N. Division St. Room B-3 Salisbury, MD 21801 Ph. 410-548-4805 Fax 410-334-3130 Email: purchasing@wicomicocounty.org Addendum # 2 Wicomico County Circuit Court Second Floor

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

GARCIA GALUSKA DESOUSA Consulting Engineers

GARCIA GALUSKA DESOUSA Consulting Engineers L#57297 /Page 1/July 21, 2017 ELECTRICAL SYSTEMS NARRATIVE REPORT The following is the Electrical Systems narrative, which defines the scope of work and capacities of the Power and Lighting systems, as

More information

SECTION POWER SUPPLIES AND DISTRIBUTION

SECTION POWER SUPPLIES AND DISTRIBUTION SECTION 17460 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for Power Supplies and Power Distribution for Station communications. 1.02 REFERENCE STANDARDS A. American National Standards

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if

More information

Architectural and Engineering Specification for a. Flash / Flare

Architectural and Engineering Specification for a. Flash / Flare Architectural and Engineering Specification for a Flash / Flare June 27, 2014 Page 1 of 12 T1DA0115-001 Rev D This document is intended to provide performance specifications and operational requirements

More information

UBC Technical Guidelines Section Edition Access Control Page 1 of 5

UBC Technical Guidelines Section Edition Access Control Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 28 05 00 Access Services: General Standards.2 Section 08 71 00 Door Hardware 1.2 Coordination Requirements.1 UBC Access Services 1.3 Description.1

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA 250BP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA 250BP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM SECURITY ACCESS AND SURVEILLANCE SECTION 13850 VISTA 250BP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM ADEMCO Group 165 Eileen Way Syosset, New York 11791 1-800-645-7568 SECTION 13850 DETECTION

More information

SECTION (13740) - VIDEO SURVEILLANCE

SECTION (13740) - VIDEO SURVEILLANCE PART 1 GENERAL 1.01 SUMMARY A. Section Includes: SECTION 28 23 00 (13740) - VIDEO SURVEILLANCE 1. CCTV Closed Circuit Television System. B. Related Sections:. 1.02 REFERENCES 1. Section 26 05 00 (16050)

More information

DIVISION 28 ELECTRONIC SAFETY AND SECURITY

DIVISION 28 ELECTRONIC SAFETY AND SECURITY 281300 - ACCESS CONTROL A. General DIVISION 28 ELECTRONIC SAFETY AND SECURITY At the beginning of the project, schedule a meeting with the Facilities Access/Maintenance Coordinator with questions and concerns.

More information

SECTION LOW VOLTAGE LIGHTING CONTROLS

SECTION LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. SECTION 238113 - PACKAGED TERMINAL AIR CONDITIONERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION (16460) - LOW-VOLTAGE TRANSFORMERS

SECTION (16460) - LOW-VOLTAGE TRANSFORMERS PART 1 GENERAL 1.01 SUMMARY SECTION 26 22 00 (16460) - LOW-VOLTAGE TRANSFORMERS A. Section Includes: 1. Dry-Type Distribution And Specialty Transformers Rated 1000 V And Less. a. General-Purpose Distribution

More information

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5 Construction Standards Page 1 of 5.1 General Description.1 The University requires that all new fire alarm system control panel, components, and devices, as required for the project, be Secutron 2900 Series

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY SECTION 280513 - CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Coaxial cabling. 2. RS-232 cabling. 3. RS-485 cabling. 4. Low-voltage control

More information

LIGHTING CONTROL DEVICES

LIGHTING CONTROL DEVICES SECTION - PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this

More information

ACTIVE INFRARED BARRIER

ACTIVE INFRARED BARRIER Although PROTECH provides high security indoor intrusion sensors for the military and government markets, our specialty is outdoor protection. Since we first introduced our PIRAMID outdoor dual technology

More information

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers.

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers. September 2012, rev. 00 26 2416 Panelboards PART 1. GENERAL 1.01 Summary A. Section includes: 1.02 Definitions 1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load

More information

Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System. FlexZone

Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System. FlexZone Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System FlexZone April 15, 2014 Page 1 of 14 G6DA0115-001 This document is intended to provide performance specifications

More information

Changes to this Division since the last issuance are indicated with yellow highlighted text.

Changes to this Division since the last issuance are indicated with yellow highlighted text. Table of Contents 28 10 00 ELECTRONIC ACCESS CONTROL AND INTRUSION DETECTION... 2 A. GENERAL... 2 B. DESIGN REQUIREMENTS... 2 C. CONSTRUCTION REQUIREMENTS... 3 28 20 00 ELECTRONIC SURVEILLANCE... 4 A.

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work. Buchtel/Perkins Community Learning Center GPD -2007271.15 OSFC Project # 55-7110-9029425 Phase 3 CLC Package Bidding Documents July 1, 2010 SECTION 15513 CONDENSING BOILERS PART I- GENERAL 1.1 RELATED

More information

SECTION FAN COIL UNITS

SECTION FAN COIL UNITS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

PRO-WATCH NOTIFIER SECONDARY FIRE INTERFACE ARCHITECT AND ENGINEERING SPECIFICATION

PRO-WATCH NOTIFIER SECONDARY FIRE INTERFACE ARCHITECT AND ENGINEERING SPECIFICATION Section 00000 SECURITY PRO-WATCH NOTIFIER SECONDARY FIRE INTERFACE ARCHITECT AND ENGINEERING SPECIFICATION PART 1 GENERAL A. The intent of this document is to specify the minimum criteria for the design,

More information

Why Should You Invest In An Access Management System?

Why Should You Invest In An Access Management System? Why Should You Invest In An Access Management System? The key word in this question is Invest. Buying and installing an access system by itself is an investment that will increase security, enhance overall

More information

A. Drawings and general provisions of Contract, including General and Supplementary Conditions apply to work of this section.

A. Drawings and general provisions of Contract, including General and Supplementary Conditions apply to work of this section. SECTION 16770 PAGE 1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions apply to work of this section. B. Division 16

More information

SECTION ( ) FIRE DETECTION AND ALARM SYSTEM. ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM February 2017

SECTION ( ) FIRE DETECTION AND ALARM SYSTEM. ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM February 2017 SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM February 2017 PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes

More information

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase General Specification 550 VA/Watts 1300 VA/Watts 1.0 GENERAL This specification defines the electrical and mechanical characteristics

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Access Control System - CAAMS. Basis of Design

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Access Control System - CAAMS. Basis of Design Basis of Design The section applies to the design, rough-in, and installation of automated access control systems for University facilities. These systems control access at building entrances and at the

More information

SECTION HEALTHCARE COMMUNICATION AND MONITORING SYSTEM (NURSE CALL)

SECTION HEALTHCARE COMMUNICATION AND MONITORING SYSTEM (NURSE CALL) SECTION 27 52 23 HEALTHCARE COMMUNICATION AND MONITORING SYSTEM (NURSE CALL) PART 1 - GENERAL 1.1 SECTION INCLUDES A. Basic System Requirements B. Stations C. Master Stations/Consoles D. Annunciators,

More information

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III SECTION 28 3111 - DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Tech Data Sheet D01662GB0_Esgraf 4.1 and Configuration Server 30/2011 2/(5)

Tech Data Sheet D01662GB0_Esgraf 4.1 and Configuration Server 30/2011 2/(5) Tech Data Sheet D01662GB1_Esgraf 4.1 and Configuration Server 30/2011 1/(5) Esgraf 4.1 graphical user interface, configuration server and fire detectors contamination monitoring Esgraf 4.1 ESGRAF is a

More information

Security Considerations for Secure Workplaces

Security Considerations for Secure Workplaces Security Considerations for Secure Workplaces Mitchell Factor HMA Consulting, Inc. USA Canada UK UAE Overview Security Risk Assessment The Process Security Design Process Technology Updates & Design Considerations

More information

Avigilon Control Center System Integration Guide

Avigilon Control Center System Integration Guide Avigilon Control Center System Integration Guide with Gallagher Command Centre INT-CARDAX-C-Rev3 Copyright 2013 Avigilon. All rights reserved. No copying, distribution, publication, modification, or incorporation

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 27 COMMUNICATIONS SECTION PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 27 COMMUNICATIONS SECTION PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS SECTION 275116 - PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Preamplifiers. 2. Power amplifiers. 3. Microphones. 4. Control console. 5. Loudspeakers.

More information

Full Service Central Station Fire Alarm Listing Evaluation

Full Service Central Station Fire Alarm Listing Evaluation Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm

More information

Alarm Lock A Division of the Napco Security Group 333 Bayview Avenue Amityville, New York Phone (631) Fax (631)

Alarm Lock A Division of the Napco Security Group 333 Bayview Avenue Amityville, New York Phone (631) Fax (631) Alarm Lock ArchiTech Series Lockset Specification Alarm Lock A Division of the Napco Security Group 333 Bayview Avenue Amityville, New York 11701 Phone (631) 842-9400 Fax (631) 789-3383 http://www.alarmlock.com

More information

OJD ITB No Attachment E Duress Alarm Equipment Specifications

OJD ITB No Attachment E Duress Alarm Equipment Specifications Duress Alarm Equipment Specifications PART 1 GENERAL 1.1 SECTION INCLUDES A. Duress devices. B. Alarm control panel. C. Signaling devices. 1.2 REFERENCE STANDARDS A. NFPA 70 - National Electrical Code;

More information

Appendix 1 LACCD Districtwide Security Performance Requirements

Appendix 1 LACCD Districtwide Security Performance Requirements Appendix 1 LACCD Districtwide Security Performance Requirements SECTION LISTING 28 01 10 Overview 28 13 00 Access Control System 28 13 01 Access Control System Installation 28 13 26 Access Control Remote

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

SECTION FIRE ALARM

SECTION FIRE ALARM SECTION 16740 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

DONALD H. BERG, ARCHITECT

DONALD H. BERG, ARCHITECT DONALD H. BERG, ARCHITECT DVA PROJECT 632-CSI-402 PET/CT ROOM #A0-10 RENOVATION BASEMENT LEVEL, BUILDING 200 ARCHITECT S PROJECT No. 0917-02 ADDENDUM NO. 1 JUNE 25, 2018 Page 1 of 1 ARCHITECTURAL 1. Specifications:

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

DESIGN GUIDELINES AND TECHNICAL STANDARDS

DESIGN GUIDELINES AND TECHNICAL STANDARDS DESIGN GUIDELINES AND TECHNICAL STANDARDS Date of Issuance: January 1, 2014 DIVISION 28 SECURITY SECTION 28 0000 SECURITY DESIGN CRITERIA 1. General: This section outlines general requirements for security

More information

SECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

SECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING SECTION 27 13 23 COMMUNICATIONS OPTICAL FIBER PART 1 - GENERAL 1.1 SUMMARY A. Section Includes the following: 1. 50/125-micrometer, optical fiber cabling. 2. Cable connecting hardware, termination panels,

More information

SECTION DIGITAL-NETWORKING LIGHTING CONTROLS ENLIGHTED LIGHT MANAGEMENT SYSTEM

SECTION DIGITAL-NETWORKING LIGHTING CONTROLS ENLIGHTED LIGHT MANAGEMENT SYSTEM SECTION 260943.13 DIGITAL-NETWORKING LIGHTING CONTROLS ENLIGHTED LIGHT MANAGEMENT SYSTEM PART 1 - GENERAL 1.1 SUMMARY LED Lighting Upgrade 26 00 00 1 Digital Network Lighting Controls A. The following

More information

East Central College

East Central College SECTION 260923 LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

ARCHITECTURAL AND ENGINEERING SPECIFICATION

ARCHITECTURAL AND ENGINEERING SPECIFICATION ARCHITECTURAL AND ENGINEERING SPECIFICATION Access Control System ACTpro Vanderbilt Industries, Clonshaugh Business and Technology Park, Dublin, D17 KV84, Ireland TABLE OF CONTENTS PART 1 GENERAL 1.1 System

More information

Architect and Engineering Specification

Architect and Engineering Specification Architect and Engineering Specification TD0045a rev0400 5007 South Howell Ave. Milwaukee WI 53207 (414) 769-5980 (800) 323-4576 Fax (414) 769-5989 www.engsysgroup.com SECTION 13800 BUILDING AUTOMATION

More information

CSI Master Format 2004 Guide Specification for: Freezer Frost Heave Prevention (Mineral Insulated)

CSI Master Format 2004 Guide Specification for: Freezer Frost Heave Prevention (Mineral Insulated) CSI Master Format 2004 Guide Specification for: Freezer Frost Heave Prevention (Mineral Insulated) System for preventing frost heave in freezers, cold rooms and ice arenas with temperature control, monitoring,

More information

Pro-Watch Software Suite. Architect and Engineering Specifications. January 9, 2002 Revision 3.4

Pro-Watch Software Suite. Architect and Engineering Specifications. January 9, 2002 Revision 3.4 Architect and Engineering Specifications Revision 3.4 SECTION 13800 BUILDING AUTOMATION AND CONTROL Part 1 GENERAL 1.0.1. GENERAL 1.0.2. REFERENCES 1.0.3. DEFINITIONS 1.0.4. SYSTEM DESCRIPTIONS 1.0.5.

More information

Addendum 002. Acknowledge receipt of this Addendum in the space provided in the Bid Form. Failure to do so may disqualify the Bidder.

Addendum 002. Acknowledge receipt of this Addendum in the space provided in the Bid Form. Failure to do so may disqualify the Bidder. BSA-Architects, Inc. 12946 Dairy Ashford, Suite 360 Sugar Land, Texas 77478 Main: (713) 529-5071 www.bsa-architects.com Addendum 002 Date: September 20, 2018 Project: Texana Administrative Office Building

More information

Avigilon Control Center System Integration Guide

Avigilon Control Center System Integration Guide Avigilon Control Center System Integration Guide with Gallagher Command Centre INT-CARDAX-C-Rev2 Copyright 2011 Avigilon. All rights reserved. No copying, distribution, publication, modification, or incorporation

More information

C. The system shall be capable of turning luminaires on/off (where supported by the luminaire) as well as full range dimming.

C. The system shall be capable of turning luminaires on/off (where supported by the luminaire) as well as full range dimming. SECTION 260943 SPECIFICATIONS - Wireless Network Lighting Controls. PART 1 - GENERAL 1.1 RELATED DOCUMENTS 1.2 SUMMARY AND KEY SYSTEM DIFFERENTIATORS A. The lighting control system specified herein shall

More information

Gallagher System Integrations

Gallagher System Integrations Gallagher System Integrations Gallagher Command Centre supports integrations with a range of third party security products, using Gallagher developed interface software and industry standard protocols.

More information

UNC100 Integra Manual

UNC100 Integra Manual UNC100 Integra Manual New Generation Building Security July 30, 2014 V1.2 Copyright Notice Copyright 1995-2014 by All rights reserved Worldwide. Printed in Canada. This publication has been provided pursuant

More information