PRO-WATCH NOTIFIER SECONDARY FIRE INTERFACE ARCHITECT AND ENGINEERING SPECIFICATION

Size: px
Start display at page:

Download "PRO-WATCH NOTIFIER SECONDARY FIRE INTERFACE ARCHITECT AND ENGINEERING SPECIFICATION"

Transcription

1 Section SECURITY PRO-WATCH NOTIFIER SECONDARY FIRE INTERFACE ARCHITECT AND ENGINEERING SPECIFICATION PART 1 GENERAL A. The intent of this document is to specify the minimum criteria for the design, supply, installation, and commissioning of a Honeywell Pro-Watch Notifier Secondary Fire Interface 1.01 SUMMARY A. The Pro-Watch Notifier solution shall enable secondary monitoring of Notifier fire events and point status information from a Pro-Watch central command and control location through the Notifier BacNet IP gateway (BacNET-GW-3). The Pro-Watch Secondary Fire Interface is not Underwriters laboratories (UL 864) listed as a fire alarm control unit. It is designed to provide only secondary informative monitoring, and shall under no circumstance be used as a primary fire alarm monitoring solution REFERENCES A. Underwriters Laboratories Inc. (UL 864) B. Notifier BacNet-GW-3 manual and application engineering guide C. Pro-Watch HSDK user s manual 1.03 SYSTEM DESCRIPTION The Pro-Watch Notifier solution shall enable secondary monitoring of Notifier fire events and point status information from a Pro-Watch central command and control location through the Notifier BacNet IP gateway (BACnet-GW-3). The Pro-Watch Notifier solution shall support multi-node BACnet-GW-3 gateway configurations with more than one Notifier panel connected to the same gateway. The Pro-Watch Secondary Fire Interface is not Underwriters laboratories (UL 864) listed as a fire alarm control unit. It is designed to provide only secondary informative monitoring, and shall under no circumstance be used as a primary fire alarm monitoring solution.

2 1.04 SUBMITTALS A. General: Submittals shall be made in accordance with the conditions of the Contract and Submittal Procedures Section. B. Product Data: The following shall be provided: a. Technical datasheets b. A complete set of instruction manuals 1.05 QUALITY ASSURANCE 1.06 DELIVERY, STORAGE, AND HANDLING A. General: Delivery, storage, and handling of Pro-Watch Notifier Secondary Fire interface shall be in accordance with the manufacturer s recommendations. B. Ordering: The manufacturer s ordering instructions and lead-time requirements must be followed in order to avoid installation delays. C. Delivery: Pro-Watch Notifier Secondary Fire interface shall be delivered in the manufacturer s original, unopened, and undamaged electronic delivery package (soft delivery) PROJECT CONDITIONS 1.08 SEQUENCING 1.09 SCHEDULING 1.10 MAINTENANCE A. Preventive Maintenance Agreement during Warranty: As a separate price item, the Contractor shall provide preventive maintenance during the warranty period. Maintenance shall include, but not be limited to: a. Labor and materials, at no additional cost, to repair Pro-Watch Notifier Secondary interface. b. Labor and materials, at no extra cost, to provide test and adjustments to Pro-Watch HSDK Secondary Notifier interface. c. Regular inspections. B. Service Support agreement: The Pro-Watch Notifier Secondary fire interface shall only be available to end-user with a software support agreement. A service support agreement line item shall be included for each Pro-Watch Notifier Secondary fire interface (SSAPWNOTI). The Pro-Watch Notifier Secondary Fire support agreement shall entitle the user to receive Pro-Watch Notifier Secondary Fire interface software updates and fixes for a period of one year.

3 1.11 TRAINING A. System Administrator and Operator training shall be conducted for a minimum of one training session, at the end user s site. B. Training shall include, but not be limited to, Pro-Watch Notifier Secondary Fire administration, provisioning, configuration, operation, and diagnostics. PART 2 PRODUCTS 2.01 SYSTEM COMPONENTS A. HSDK a. Manufacturer: Honeywell Security b. Part #: B. Notifier a. Manufacturer: Honeywell Life Safety b. Part #: BacNet-GW-3 C. Pro-Watch a. Manufacturer: Honeywell Security b. Part #: PWCE D. Pro-Watch Notifer Interface a. Manufacturer: Honeywell Security b. Part #: PWNOTI 2.02 SYSTEM OPERATION A. The Pro-Watch Notifier Secondary fire interface shall include, as a minimum, the following features/functions/specifications: Notifier BacNet/IP gateway (BacNet-GW-3) connectivity 1. Pro-Watch Notifier Secondary fire interface shall support BacNet/IP connectivity to the Notifier BacNet IP gateway (BacNet-GW-3) via standard BacNet/IP. Any and all configurations to the Notifier BacNet/IP gateway (BacNet-GW-3) shall be undertaken by a qualified Notifier dealer under and in compliance with Notifier certifications and best practices.

4 2. The BacNET-GW-3 Notifier gateway shall be configured in BacNET multi-state point configuration. If necessary, an additional BacNET-GW- 3 gateway shall be deployed in multi-state point configuration. 3. Configuration of the BacNet IP gateway shall be undertaken by a qualified Notifier dealer for LAN and WAN configurations including BacNet/IP remote gateway support. 4. Configuration of the BacNet IP gateway shall be undertaken by a qualified Notifier dealer to publish BacNet compliant enumerated points containing alarm and status information for each published point. 5. Configuration of the BacNet IP gateway shall be undertaken by a qualified Notifier dealer to publish one or more Notifier panels through the Notifier BacNet IP gateway. Pro-Watch Notifier Secondary fire BacNet/IP configuration tool 6. Pro-Watch Notifier Secondary fire interface shall support a maximum of one Notifier BacNet IP gateway (BacNet-GW-3) and up to 2,000 Notifier points per BacNet-GW-3 Notifier gateway 7. Pro-Watch Notifier Secondary fire interface shall include a configuration tool that enables a user to configure the Pro-Watch Notifier Secondary fire BacNet/IP client interface communications parameters including BacNet/IP Network number. The system administrator shall be responsible for assuring that the appropriate BacNet/IP ports are open and available. 8. Pro-Watch Notifier Secondary fire interface shall include a configuration tool that enables a user to monitor the BacNet/IP network status (up/down). Pro-Watch Notifier Secondary fire interface Notifier BacNet IP gateway (BacNet-GW-3) point discovery 9. Pro-Watch shall implement an authenticated graphical user interface accessible from the Pro-Watch HSDK application module interface or through web browser interface supporting java. Specifically, Internet Explorer or Firefox with Sun Java virtual machine support (including appropriate permissions). 10. Pro-Watch Notifier Secondary fire interface shall implement a BacNet/IP client capable of communicating to the Notifier BacNetIP gateway (BacNet-GW-3). 11. Pro-Watch Notifier Secondary fire interface shall implement a graphical tool to discover and add Notifier BacNet IP gateways in a LAN environment to the Pro-Watch Notifier Secondary fire interface. 12. Pro-Watch Notifier Secondary fire interface shall enable all added Notifier BacNet IP multi-state points to generate Pro-Watch events for normal, offnormal and fault.status transitions.

5 Pro-Watch Notifier Secondary fire interface Pro-Watch point discovery 13. Pro-Watch shall implement a graphical user interface that enables a user to add one or more Pro-Watch Notifier Secondary fire interfaces to a Pro- Watch system as a HSDK application module. 14. Pro-Watch shall implement a Pro-Watch channel for each Pro-Watch Notifier Secondary fire interface mechanism 15. Pro-Watch shall implement a panel for each Pro-Watch Notifier Secondary fire interface 16. Pro-Watch shall implement a Pro-Watch HSDK application module interface for each Pro-Watch Notifier Secondary fire interface. 17. Pro-Watch HSDK application module shall implement a mechanism to graphically import selected Notifier fire points from a Pro-Watch Notifier Secondary fire interface (obix tree) as Pro-Watch obix input points (read only). 18. Pro-Watch obix points shall support Pro-Watch standard store procedures and video integration capabilities including the Pro-Watch video manager integration tab. 19. Pro-Watch HSDK application module shall implement a mechanism to graphically subscribe/unsubscribe to the Pro-Watch Notifier Secondary fire interface (obix tree) to receive Pro-Watch Notifier fire point to normal, off-normal and fault status. 20. Pro-Watch HSDK application module shall implement a mechanism to view the Pro-Watch Notifier Secondary Fire graphical user interface from within Pro-Watch. Pro-Watch Notifier Secondary fire interface Licensing 21. Pro-Watch Notifier Secondary fire interface shall support a maximum of one Notifier BacNet IP gateway (BacNet-GW-3) and up to 2,000 Notifier points per BacNet-GW-3 gateway 22. Pro-Watch Notifier interface shall support 500 points in its base configuration expandable in 250 point increments up to a maximum of 2,000 Notifier points. PART 3 EXECUTION 3.01 PREPARATION A. Prior to installation, the Pro-Watch Notifier Secondary fire interface shall be configured and tested in accordance with the manufacturer s instructions.

6 3.02 INSTALLATION A. The Pro-Watch Notifier Secondary fire interface must be installed, programmed, and tested in accordance with the manufacturer s instructions. a. In order to ensure a complete, functional Pro-Watch Notifier Secondary fire interface for bidding purposes where information is not available from the Owner upon request, the worst-case condition shall be assumed. b. Interfaces shall be coordinated with the Owner s representative, where appropriate. c. All necessary backboxes, racks, connectors, supports, conduit, cable, and wire must be furnished and installed to provide a complete and reliable Pro-Watch Notifier Secondary fire interface installation. Exact location of all boxes, conduit, and wiring runs shall be presented to the Owner for approval in advance of any installation. B. Any and all configurations to the Notifier BacNet/IP gateway (BacNet-GW-3) shall be undertaken by a qualified Notifier dealer under and in compliance with Notifier certifications and best practices TESTING AND CERTIFICATION A. The Contractor shall demonstrate the functionality of Pro-Watch Notifier Secondary Fire Interface upon completion of installation, documenting the result of all tests and providing these results to the Owner. Pro-Watch Notifier Secondary Fire Interface shall be tested in accordance with the following: a. The Contractor shall conduct a complete inspection and test of all installed Pro-Watch Notifier Secondary Fire Interface equipment. This includes testing and verifying operation with connected equipment. b. The Contractor shall provide staff to test all devices and all operational features of the system for witness by the Owner s representative and the authority having jurisdiction. All testing must be witnessed by the Owner s representative prior to acceptance. c. The testing and certification shall take place as follows: i. Pro-Watch Notifier Secondary Fire Interface shall be tested in conjunction with the manufacturer s representative. ii. All deficiencies noted in the above test shall be corrected. iii. Test results shall be submitted to the consultant or Owner s representative. iv. The test and correction of any deficiencies shall be witnessed by the Owner s representative and noted. v. The Owner s representative shall accept the system. vi. The system shall be witnessed by the authority having jurisdiction. Any deficiencies noted during the testing must be corrected. The Pro-Watch Secondary Fire Interface is not Underwriters laboratories (UL 864) listed as a fire alarm control unit. It is

7 designed to provide only secondary informative monitoring. It shall under no circumstance be used in life safety applications. d. A letter of certification shall be provided to indicate that the tests have been performed, and all equipments are operational. END OF SECTION

B. After installation, the Owner shall be able to perform hardware configuration changes as desired without the services of the Integrator.

B. After installation, the Owner shall be able to perform hardware configuration changes as desired without the services of the Integrator. SECTION 281300 - ACCESS CONTROL SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Minimum standards for Access Control Systems. B. Related Requirements: 1. Section 087100 Door Hardware. 1.2 REFERENCES

More information

DIVISION 26 ELECTRICAL SECTION LIGHTING CONTROL SYSTEM

DIVISION 26 ELECTRICAL SECTION LIGHTING CONTROL SYSTEM DIVISION 26 ELECTRICAL SECTION 26 09 26 PART 1 GENERAL 1.01 DESCRIPTION A. The intent of this set of specifications is to provide a complete, functional, intelligent, lowvoltage lighting control system

More information

ACTIVE INFRARED BARRIER

ACTIVE INFRARED BARRIER Although PROTECH provides high security indoor intrusion sensors for the military and government markets, our specialty is outdoor protection. Since we first introduced our PIRAMID outdoor dual technology

More information

- HSDK. to Integration. Honeywell Integrated Security Consultants Event, July Rev 10/07/11

- HSDK. to Integration. Honeywell Integrated Security Consultants Event, July Rev 10/07/11 Road to Integration - HSDK Road to Integration Honeywell Integrated Security Consultants Event, July 2011 Rev 10/07/11 Agenda The Open Pro-Watch Ecosystem The HSDK Developer Program Building a HSDK solution

More information

SECTION SECURITY TESTING AND COMMISSIONING

SECTION SECURITY TESTING AND COMMISSIONING SECTION 280800 - SECURITY TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 WORK INCLUDES A. General Description: This specification section covers the provision of preliminary testing, acceptance testing,

More information

WebStat Temperature Control System WITH WEB-BASED BUILDING MANAGEMENT

WebStat Temperature Control System WITH WEB-BASED BUILDING MANAGEMENT WebStat Temperature Control System WITH WEB-BASED BUILDING MANAGEMENT ENGINEERING GUIDE SPEC 1. GENERAL 1.1 SUMMARY A. Furnish all labor, materials, equipment, and service necessary for a complete and

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS SECTION 26 92 50 PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

ONYX FirstVision Specification Interactive Firefighters Display

ONYX FirstVision Specification Interactive Firefighters Display ONYX FirstVision Specification Interactive Firefighters Display NOTIFIER is a registered trademark, and ONYX FirstVision, NOTI FIRE NET, and VeriFire are trademarks of Honeywell International Inc. Microsoft

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

opti-visor ultra-efficient chiller plant automation Typical specification

opti-visor ultra-efficient chiller plant automation Typical specification opti-visor ultra-efficient chiller plant automation Typical File No: 90.893 Date: february 9, 2015 Supersedes: 90.893 Date: april 20, 2012 contents 1.0 Chilled water plant 4 1.1 General system requirements

More information

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21 Division 21: FIRE SUPRESSION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM Table of Contents 1 Division 21 SECTION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A.

More information

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA 250BP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA 250BP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM SECURITY ACCESS AND SURVEILLANCE SECTION 13850 VISTA 250BP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM ADEMCO Group 165 Eileen Way Syosset, New York 11791 1-800-645-7568 SECTION 13850 DETECTION

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ). SECTION 28 13 00 - ACCESS CONTROL PART I - GENERAL 1.1 SUMMARY A. This specification section describes the furnishing, installation, commissioning, and programming of a complete, turnkey, hardwired Andover

More information

Northwestern University Scope of BAS Contractor

Northwestern University Scope of BAS Contractor The purpose of this document is to describe the Enterprise Level Server at Northwestern University, and the separation of roles between the System Integrator and the Building Automation System Contractor.

More information

C. The system shall be capable of turning luminaires on/off (where supported by the luminaire) as well as full range dimming.

C. The system shall be capable of turning luminaires on/off (where supported by the luminaire) as well as full range dimming. SECTION 260943 SPECIFICATIONS - Wireless Network Lighting Controls. PART 1 - GENERAL 1.1 RELATED DOCUMENTS 1.2 SUMMARY AND KEY SYSTEM DIFFERENTIATORS A. The lighting control system specified herein shall

More information

MultiSite Manager. Setup Guide

MultiSite Manager. Setup Guide MultiSite Manager Setup Guide Contents 1. Introduction... 2 How MultiSite Manager works... 2 How MultiSite Manager is implemented... 2 2. MultiSite Manager requirements... 3 Operating System requirements...

More information

Installation, Configuration and User Manual

Installation, Configuration and User Manual Model 8826 System Controller Model 8826 System Controller Installation, Configuration and User Manual READ AND SAVE THESE INSTRUCTIONS WELCOME Thank you for choosing the Aprilaire HVAC Automation System.

More information

DIVISION LOW VOLTAGE DE-ICING / SNOW MELTING SYSTEM IN EXISTING ASPHALT/CONCRETE

DIVISION LOW VOLTAGE DE-ICING / SNOW MELTING SYSTEM IN EXISTING ASPHALT/CONCRETE DIVISION 23 8313 LOW VOLTAGE DE-ICING / SNOW MELTING SYSTEM IN EXISTING ASPHALT/CONCRETE PART 1 GENERAL 1.1 SUMMARY A. Includes But Not Limited To: 1. Furnish and install low voltage de-icing / snow melting

More information

SECTION NURSE CALL SYSTEM

SECTION NURSE CALL SYSTEM NURSE CALL SMARTCARE NURSE CALL SOLUTION Architectural Specifications Part 1 General SECTION 275223 - NURSE CALL SYSTEM 1.0 Summary 1.1 This section includes nurse call system and requirements for system

More information

Linear Heat Detection Engineering Specifications

Linear Heat Detection Engineering Specifications Linear Heat Detection Engineering Specifications July, 2007 SAFE Fire Detection Inc. 5915 Stockbridge Dr. Monroe, NC 28110 Phone: (704) 821-7920 Fax: (704) 821-4327 Website: www.safefiredetection.com E-mail:

More information

DONALD H. BERG, ARCHITECT

DONALD H. BERG, ARCHITECT DONALD H. BERG, ARCHITECT DVA PROJECT 632-CSI-402 PET/CT ROOM #A0-10 RENOVATION BASEMENT LEVEL, BUILDING 200 ARCHITECT S PROJECT No. 0917-02 ADDENDUM NO. 1 JUNE 25, 2018 Page 1 of 1 ARCHITECTURAL 1. Specifications:

More information

SPECIFICATIONS FOR TENDER # SUPPLY OF A FIRE ALARM SYSTEMS SERVICE AGREEMENT FOR WESTERN HEALTH

SPECIFICATIONS FOR TENDER # SUPPLY OF A FIRE ALARM SYSTEMS SERVICE AGREEMENT FOR WESTERN HEALTH SPECIFICATIONS FOR TENDER #0371-0739 SUPPLY OF A FIRE ALARM SYSTEMS SERVICE AGREEMENT FOR WESTERN HEALTH CLOSING DATE: 8 June 2007 CLOSING TIME: 11:00 AM (Newfoundland Time) Invitation to Tender for a

More information

Michigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE

Michigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE PAGE 280800-1 SECTION 280800 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

CRESTRON MEDIAMANAGER INTELLICLASS

CRESTRON MEDIAMANAGER INTELLICLASS CRESTRON MEDIAMANAGER INTELLICLASS Crestron IntelliClass systems provide educators with a simplified yet comprehensive classroom presentation solution that saves time and money. Designed to deliver the

More information

HikCentral Web Client. User Manual

HikCentral Web Client. User Manual HikCentral Web Client User Manual Legal Information User Manual 2018 Hangzhou Hikvision Digital Technology Co., Ltd. About this Manual This Manual is subject to domestic and international copyright protection.

More information

SECTION DIGITAL-NETWORKING LIGHTING CONTROLS ENLIGHTED LIGHT MANAGEMENT SYSTEM

SECTION DIGITAL-NETWORKING LIGHTING CONTROLS ENLIGHTED LIGHT MANAGEMENT SYSTEM SECTION 260943.13 DIGITAL-NETWORKING LIGHTING CONTROLS ENLIGHTED LIGHT MANAGEMENT SYSTEM PART 1 - GENERAL 1.1 SUMMARY LED Lighting Upgrade 26 00 00 1 Digital Network Lighting Controls A. The following

More information

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS HVAC Upgrades Phase 2 Page 1 of 5 Part 1 General 1.1 SUMMARY.1 Section Includes:.1 Materials and installation for fire alarm systems upgrades..2 Audible signal devices..3 End-of-line devices..4 Sustainable

More information

SECTION AUTOMATIC VERTICAL CONVEYOR SYSTEM CLOSURE FIRE BARRIER

SECTION AUTOMATIC VERTICAL CONVEYOR SYSTEM CLOSURE FIRE BARRIER SECTION 08 3493 AUTOMATIC VERTICAL CONVEYOR SYSTEM CLOSURE FIRE BARRIER PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Smoke detector-activated, vertical closing fire barrier conveyor system closure.

More information

IntesisBox BACnet/IP Server - Notifier ID3000 series

IntesisBox BACnet/IP Server - Notifier ID3000 series IntesisBox Server - Notifier ID3000 series Gateway for integration of Notifier ID3000, ID3002, ID50 and ID60 fire panels into enabled control systems. Integrate your Notifier fire panels into your BACnet

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-21 21 03.00 10 February 2009) ---------------------------------- Preparing Activity: USACE Superseding UFGS-21 21 03.00 10 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

DTW Master Specification Section EMCS: Start Up, Verification and Commissioning

DTW Master Specification Section EMCS: Start Up, Verification and Commissioning Page 1 of 6 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Related Sections..1 The contractor is to ensure that all related work is co ordinated among all specification sections, as well as between Division 11,

More information

CSI Master Format 2004 Guide Specification for: Freezer Frost Heave Prevention (Mineral Insulated)

CSI Master Format 2004 Guide Specification for: Freezer Frost Heave Prevention (Mineral Insulated) CSI Master Format 2004 Guide Specification for: Freezer Frost Heave Prevention (Mineral Insulated) System for preventing frost heave in freezers, cold rooms and ice arenas with temperature control, monitoring,

More information

East Central College

East Central College SECTION 260923 LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials. B B11.0 DIVISION 08 - OPENINGS SECTION 08 17 00 INTEGRATED DOOR OPENING ASSEMBLIES Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements. Add section numbers and

More information

Western Michigan University Facilities Management Engineering Division

Western Michigan University Facilities Management Engineering Division Western Michigan University Facilities Management Engineering Division Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG21-1 Fire Suppression Systems & Equipment I. GENERAL... 1 A. General

More information

Advanced Power Monitor (APM)

Advanced Power Monitor (APM) Advanced Power Monitor (APM) What is the APM? The Advanced Power Monitor (APM) is used to monitor and measure the RF coverage performance determining characteristics of a communications site, on an individual

More information

ADDENDUM NO. 1 FDVA-ITB B ITB TITLE: Bennett SVNH Nurse Call System ISSUE DATE: March 27, 2014

ADDENDUM NO. 1 FDVA-ITB B ITB TITLE: Bennett SVNH Nurse Call System ISSUE DATE: March 27, 2014 Mike Prendergast Executive Director State of Florida DEPARTMENT OF VETERANS AFFAIRS Division of Administration and Public Information 11351 Ulmerton Road, #311-K Largo, FL 33778-1630 Phone: (727) 518-3202

More information

SECTION REGULATORY REQUIREMENTS. A. Relationship between Code, Ordinances, Standards and Contract Documents

SECTION REGULATORY REQUIREMENTS. A. Relationship between Code, Ordinances, Standards and Contract Documents SECTION 01410 PART I - GENERAL 1.01 SECTION INCLUDES A. Relationship between Code, Ordinances, Standards and Contract Documents B. Applicable Codes, Laws and Ordinances C. Project Inspections D. Office

More information

SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC

SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC SECTION 08 35 13.23 ACCORDION FOLDING FIRE DOORS PART 1 GENERAL 1.01 SUMMARY OF WORK A. Division 0 and 1, as indexed, apply to this section. B. Furnish and install

More information

SECTION ( ) FIRE DETECTION AND ALARM SYSTEM. ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM February 2017

SECTION ( ) FIRE DETECTION AND ALARM SYSTEM. ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM February 2017 SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM February 2017 PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes

More information

15900 HVAC INSTRUMENTATION AND CONTROLS

15900 HVAC INSTRUMENTATION AND CONTROLS 15900 HVAC INSTRUMENTATION AND CONTROLS PART 1 GENERAL - Andover Controls BAS system is the standard for the University, and may be specified as a proprietary item. 1.0 RELATED DOCUMENTS A. Drawings and

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

Installation Manual. ATS Remote Annunciator Catalog 5350 DANGER WARNING D

Installation Manual. ATS Remote Annunciator Catalog 5350 DANGER WARNING D ASCO 5350 The ASCO 5350 ATS Remote Annunciator is listed under the Underwriter s Laboratories Standard UL-1008 for Automatic Transfer Switch accessories. This stand-alone device provides individual status

More information

i.net Engineered system solutions for

i.net Engineered system solutions for i.net Engineered system solutions for Sound Masking, PAGING & AUDIO i.net The Intelligent Network Lencore is committed to providing solutions, products and services that transform environments and change

More information

Avigilon Control Center 5 System Integration Guide

Avigilon Control Center 5 System Integration Guide Avigilon Control Center 5 System Integration Guide for Paxton Net2 Access Control Systems 2014 Avigilon Corporation. All rights reserved. Unless expressly granted in writing, no license is granted with

More information

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications: PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,

More information

Fire Smoke Damper Actuator Replacements SECTION COMMISSIONING OF HVAC

Fire Smoke Damper Actuator Replacements SECTION COMMISSIONING OF HVAC PART 1 GENERAL 1.01 SUMMARY SECTION 23 08 00 COMMISSIONING OF HVAC A. This section covers the Contractor's and Commissioning Authority (CA) responsibilities for commissioning; each subcontractor or installer

More information

Thermo Scientific Revco UxF -80C Series Upright ULT Freezers

Thermo Scientific Revco UxF -80C Series Upright ULT Freezers Thermo Scientific Revco UxF -80C Series Upright ULT Freezers PART 1 GENERAL 1.1 DESIGN AND PERFORMANCE CRITERIA A. Ultra Low Temperature Freezer manufactured to operate in a temperature range of -50C to

More information

GARCIA GALUSKA DESOUSA Consulting Engineers

GARCIA GALUSKA DESOUSA Consulting Engineers L#57297 /Page 1/July 21, 2017 ELECTRICAL SYSTEMS NARRATIVE REPORT The following is the Electrical Systems narrative, which defines the scope of work and capacities of the Power and Lighting systems, as

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

OJD ITB No Attachment E Duress Alarm Equipment Specifications

OJD ITB No Attachment E Duress Alarm Equipment Specifications Duress Alarm Equipment Specifications PART 1 GENERAL 1.1 SECTION INCLUDES A. Duress devices. B. Alarm control panel. C. Signaling devices. 1.2 REFERENCE STANDARDS A. NFPA 70 - National Electrical Code;

More information

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA 250FBP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA 250FBP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM SECURITY ACCESS AND SURVEILLANCE SECTION 13850 VISTA 250FBP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM ADEMCO Group 165 Eileen Way Syosset, New York 11791 1-800-645-7568 SECTION 13850 DETECTION

More information

Perimeter Product Overview. Effective protection for your business

Perimeter Product Overview. Effective protection for your business Perimeter Product Overview Effective protection for your business The Gallagher difference Our innovation is driven by the desire to solve problems, meet your needs and provide real business value. We

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

SECTION Mass Notification Systems

SECTION Mass Notification Systems Specifier Notes: This product guide specification is written according to the Construction Specifications Institute (CSI) 3-Part Format, including MasterFormat, SectionFormat, and PageFormat, as described

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR SYSTEM INTEGRATION AND TESTING. ITS:CLC 1 of 13 APPR:LWB:DBP: FHWA:APPR:

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR SYSTEM INTEGRATION AND TESTING. ITS:CLC 1 of 13 APPR:LWB:DBP: FHWA:APPR: MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR SYSTEM INTEGRATION AND TESTING ITS:CLC 1 of 13 APPR:LWB:DBP:08-01-13 FHWA:APPR:09-23-13 a. Description. This work consists of conducting system

More information

LightSweep. Lighting Control System

LightSweep. Lighting Control System LightSweep Lighting Control System Incredible Control GE LightSweep is a comprehensive indoor lighting control system designed to save money while improving the efficiency, comfort, safety and security

More information

DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC

DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC PART 1 GENERAL SECTION 23 0923 DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC 1.01 RELATED WORK UNDER OTHER SECTIONS: A. In addition to the general building construction, work directly related to the automatic

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-28 20 02 (November 2008) ----------------------------- Preparing Activity: USACE Superseding UFGS-13729 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

A. The requirements of this Section and the other Division 26, 27 & 28 Sections apply to all the video surveillance system work.

A. The requirements of this Section and the other Division 26, 27 & 28 Sections apply to all the video surveillance system work. PART 1 GNRAL 1.1. APPLICABL PROVISIONS A. The General, Supplementary and other Conditions of the Contract, modifications to the General Conditions, the Drawings, and the applicable provisions of the other

More information

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications: PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,

More information

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s) Furnish and install as shown on AERCO International plans and operation and maintenance manuals, with all applicable codes and authorities having local, state and federal jurisdiction, Benchmark Series

More information

See Part II for additional information regarding Indoor Pollutant Reduction and Control, Energy Efficiency, etc.

See Part II for additional information regarding Indoor Pollutant Reduction and Control, Energy Efficiency, etc. UC Santa Cruz Campus Design Guide DIVISION 25 BUILDING AUTOMATION SYSTEMS (BAS) Includes the following sections: 25 00 00 (BAS) See Part II for additional information regarding Indoor Pollutant Reduction

More information

Home center Interface Server. Technical sheet

Home center Interface Server. Technical sheet Home center Interface Server Technical sheet September 2014 About Home center Interface Server is a product by Stijnen Solutions to operate your home automation system. Connect to this device with Home

More information

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO Prepared For: Public Schools Facilities Authority State of New Mexico 2019 Galisteo, Suite

More information

LG ELECTRONICS Air Conditioning Technologies LG Guide Specifications Controls

LG ELECTRONICS Air Conditioning Technologies LG Guide Specifications Controls LG ELECTRONICS Air Conditioning Technologies LG Guide Specifications Controls 1 Article I. General Section 1.01 Section 1.02 Section 1.03 System Description Quality Assurance Storage and Handling Article

More information

Bosch TCU Integration Module Administrator's Guide

Bosch TCU Integration Module Administrator's Guide Bosch TCU Integration Module 1.0 - Administrator's Guide 10 Dec 2008 Rev 1.2 Table of Contents 1 Overview... 3 1.1 Compatibility...3 1.2 References...3 2 Installation... 4 3 Configuration... 5 3.1 System

More information

RFP Addendum 2 March 31, 2016

RFP Addendum 2 March 31, 2016 RFP Addendum 2 March 31, 2016 For Best Value Procurement Option Three Security Upgrades Ph 1 UT Health Science Center SBC No. 540/013-04-2015 This Addendum forms a part of the Request for Proposals (RFP)

More information

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process.

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. SECTION 239950 MECHANICAL COMMISSIONING SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. B. Commissioning

More information

CONSTRUCTION SYSTEMS AND ASSEMBLIES

CONSTRUCTION SYSTEMS AND ASSEMBLIES Insert project name SECTION 25 00 00 BUILDING AUTOMATION SYSTEMS (BAS) GENERAL PART 1 - GENERAL CONSTRUCTION SYSTEMS AND ASSEMBLIES STANDARDS AND GUIDELINES Note: Reference the University of Houston Design

More information

Electronic Safety and Security

Electronic Safety and Security 28 Electronic Safety and Security NOTE: This is a new section, which includes content from previous sections of the KU Design Standards, along with appropriate revisions and updates. Significant revisions

More information

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA-128FB ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA-128FB ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM SECURITY ACCESS AND SURVEILLANCE SECTION 13850 VISTA-128FB ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM ADEMCO Group 165 Eileen Way Syosset, New York 11791 1-800-645-7568 SECTION 13850 DETECTION

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR SECTION 08734 COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Overhead

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

HikCentral Web Client. User Manual

HikCentral Web Client. User Manual HikCentral Web Client User Manual Legal Information User Manual 2018 Hangzhou Hikvision Digital Technology Co., Ltd. About this Manual This Manual is subject to domestic and international copyright protection.

More information

Advanced FireAlarm Panel 1-4Loop

Advanced FireAlarm Panel 1-4Loop Advanced FireAlarm Panel 1-4Loop Advanced Technologies Advanced Electronics Ltd IP Gateway Monitoring and interrogation via the internet Password protected multiple user permissions Event notification

More information

SENTRY PRODUCTS, INC. 01/98 SCAN - STAND-ALONE - Sample Specification

SENTRY PRODUCTS, INC. 01/98 SCAN - STAND-ALONE - Sample Specification This sample specification is for a duress only stand-alone SCAN system using SR series receivers with zone-within-a-zone and graphic display. SECTION 17 DURESS SYSTEM PART 1.00 - GENERAL 1.01 DESCRIPTION

More information

SECTION SAMPLE SPECIFICATION FOR BOILER CONTROLLER CONVERSION KIT

SECTION SAMPLE SPECIFICATION FOR BOILER CONTROLLER CONVERSION KIT SECTION 23 09 33 SAMPLE SPECIFICATION FOR BOILER CONTROLLER CONVERSION KIT HARSCO INDUSTRIAL, PATTERSON-KELLEY NURO CONTROL CONVERSION KIT Part 1 - GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 / CSA 4.9

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR

DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR SECTION 08 71 13 LOW ENERGY AUTOMATIC OPERATORS Specifier Note: Coordinate and edit articles

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

CAREL heatersteam Electric Element Steam Humidifiers

CAREL heatersteam Electric Element Steam Humidifiers Suggested Engineering Specifications Section 23 84 13 CAREL heatersteam Electric Element Steam Humidifiers 1. GENERAL SCOPE 1. Furnish and install as indicated on the drawings and plans, in-duct [space]

More information

September 30, Dear Fire Suppression System Contractor/Designer:

September 30, Dear Fire Suppression System Contractor/Designer: CITY OF BOZEMAN FIRE DEPARTMENT P.O. Box 1230 Bozeman, Montana 59771-1230 Phone (406) 582-2350 CITY OF BOZEMAN BUILDING DEPARTMENT 20 E Olive St, STE 208 Bozeman, Montana 59715-4790 Phone (406) 582-2375

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

SECTION ELECTRICAL SYSTEMS COMMISSIONING

SECTION ELECTRICAL SYSTEMS COMMISSIONING SECTION 16990 PART 1 - GENERAL 1.01 SECTION INCLUDES A. Section Includes: 1. General requirements for Commissioning (Cx) of lighting systems components, lighting controls and HVAC systems line voltage

More information

Architectural and Engineering Specification for a Real-Time Locating System Flare

Architectural and Engineering Specification for a Real-Time Locating System Flare Architectural and Engineering Specification for a Flare AE-T1-IN-R3-E-0617 Page 1 of 14 This document is intended to provide performance specifications and operational requirements for the Flare. It is

More information

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website.

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website. 4.e STATE OF MISSOURI County of Franklin ss. COMMISSION ORDER Commission Order No. 2016-316 Third Quarter Term 2016 Tuesday,August,09,2016 Bid Notice IN THE MATTER OF ADVERTISING FOR SEALED BIDS FOR SMOKE

More information

Introduction PLAYING NICE: HVAC AND LIGHTING CONTROLS INTEGRATION. Why should I care? Background Integration VAV box Occ sensor

Introduction PLAYING NICE: HVAC AND LIGHTING CONTROLS INTEGRATION. Why should I care? Background Integration VAV box Occ sensor PLAYING NICE: HVAC AND LIGHTING CONTROLS INTEGRATION www.kw-engineering.com Lyn Gomes, PE, LEED AP kw Engineering Introduction 2 Why should I care? Background Integration VAV box Occ sensor 4 methods for

More information

CARD ACCESS CONTROL SYSTEM

CARD ACCESS CONTROL SYSTEM SECTION 13851 CARD ACCESS CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested, integrated proximity access control system, to operate on a proximity principle where

More information

PRIVATE FIRE SERVICE INSTALLATION PACKET

PRIVATE FIRE SERVICE INSTALLATION PACKET PRIVATE FIRE SERVICE INSTALLATION PACKET The 2017 Edition supersedes all previous versions for Private Fire Service Installation To Whom It May Concern: SUBJECT: PRIVATE FIRE SERVICE INSTALLATION Illinois

More information

Proliphix. Remote Management. User Guide

Proliphix. Remote Management. User Guide Proliphix Remote Management User Guide Rev 2.5 Page 2 of 12 Table of Contents Intended Audience...3 Remote Management...4 Remote Management Interface (RMI)...5 Accessing My Account... 5 Device List Page...

More information

SECTION GENERATOR PARALLELING CONTROLS

SECTION GENERATOR PARALLELING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 13 GENERATOR PARALLELING CONTROLS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

ADDENDUM NO.1. March 4, 2013 HEAT PUMP REPLACEMENT FOR: GATE CITY ELEMENTARY SCHOOL

ADDENDUM NO.1. March 4, 2013 HEAT PUMP REPLACEMENT FOR: GATE CITY ELEMENTARY SCHOOL ADDENDUM NO.1 March 4, 2013 HEAT PUMP REPLACEMENT FOR: GATE CITY ELEMENTARY SCHOOL The data included hereinafter is issued by the Engineer (Engineered Systems Associates, 1355 East Center, Pocatello, ID

More information

CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 1

CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 1 GREEN LIGHT ARCHITECTURAL DIMMING CONTROLS (GLPD) Crestron Green Light and Green Light Express Network Dimming Control Systems are web accessible, network connected dimming control systems that receive

More information