Introduction PLAYING NICE: HVAC AND LIGHTING CONTROLS INTEGRATION. Why should I care? Background Integration VAV box Occ sensor

Size: px
Start display at page:

Download "Introduction PLAYING NICE: HVAC AND LIGHTING CONTROLS INTEGRATION. Why should I care? Background Integration VAV box Occ sensor"

Transcription

1 PLAYING NICE: HVAC AND LIGHTING CONTROLS INTEGRATION Lyn Gomes, PE, LEED AP kw Engineering Introduction 2 Why should I care? Background Integration VAV box Occ sensor 4 methods for integration Points of failure Case study Final thoughts kw Engineering

2 Why should I care? 3 Poor implementation of the integration and Cx : MISERY Time consuming callbacks Benefits may never be realized May result in no energy savings Money spent goes down the drain Don t underestimate the effort! You must have a reason 4 Why? Data? Energy efficiency? Additional functionality? Integration for integration s sake is a bad idea kw Engineering

3 System Architecture Layers Remote Access Alarms Browser Based Monitoring and Control Enterprise Applications Building Operations Center Cal/Dispatch Center Reporting/Scheduling $$$ HARD WAN LAN Graphical User Interface Network Tools Diagnostics Web Interface Internet/VPN/Frame Relay Firewall Gateway to proprietary/ legacy systems IP-852 Router or obix XML Server or Web Server MONEY IP/Ethernet COMPLEXITY LON Device Network Standard Network Variables Exchanged Between Devices and to PC, Web, Remote Access $$ NOT AS HARD Source: Ron Bernstein, RBCG Consulting used with permission. One bite at a time 6 Our time is limited HVAC and lighting control system integration for occupancy-based demand controlled ventilation (DCV) Required by code Real-life examples kw Engineering

4 Why consider integration? 7 Code requires occupancy based demand control of lights and HVAC (in certain space types) Title 24 sec c.3 Owners desire energy savings Pushed by manufacturers, ESCOs, utilities But Lightning pace of lighting controls industry Issues with the current design phase approach leads to finger pointing & hiccups Construction phase coordination difficult Lighting controls are uncharted territory for many electrical contractors What is a VAV box? 8 kw Engineering

5 VAV box controller 9 Occupancy sensor load control Line Voltage Low Voltage Images courtesy of WattStopper kw Engineering

6 Occupancy Sensors PIR (Passive InfraRed) Ultrasonic Human hearing: 20Hz 20kHz Ultrasonic: >34kHz Microphonic Dual Technology Four methods Aux Relay within Occupancy Sensor 2. External Aux Relay 3. Separate occupancy sensor 4. BMS/Lighting Control System Integration 5. Others? kw Engineering

7 1. Aux Relay within Occupancy Sensor 13 Low or line voltage sensors only!!!! Responsibilities must be clearly defined Requires coordination in ALL phases How is occupancy status transmitted? How many sensors in the space? How many ways can it fail? 14 Low Voltage Occ Sensor 1 Load Junction Box Aux Relay Connection 2 Points of Failure VAV Controller and misc Controller 4 3 kw Engineering

8 2. External Auxiliary Relay 15 DDC Occupancy sensor plus: Auxiliary isolated relay device, or Auxiliary power pack EE/LC specs components Best value to Owner Status? Multiple sensors? External Aux Relay 16 kw Engineering

9 17 How many ways can it fail? 1 Lighting occupancy sensor 2 Room controller 3 Network Bridge HVAC integration relay Separate occupancy sensor 18 Dedicated occ sensor for VAV box Separate occ sensor for lighting Architect: Two occupancy sensors is ugly Owner: It s more to maintain Mechanical contractor may not understand how to install/adjust Responsibilities clearly defined Must be spec d separately (usu in ) Mechengineer know about Occsensors? It s usually Sparky territory kw Engineering

10 How many ways can it fail? 19 Lighting occupancy sensor Room controller Network Bridge HVAC occupancy sensor BMS/LCS Integration 20 Burden/responsibility shifts to contractor LOTS OF COORDINATION ME and EE GC, & (Mech, Controls, Elect) Subcontractors Specify very carefully! Coordination table Fully networked lighting control system BOTH control specs must include integration ( and ) Include time in your budget for coordination Difficult for maintenance Don t forget about IT/networking! Status? Multiple sensors are easier kw Engineering

11 Case Study: Data Integration 21 Doing Integration Right 22 How to do it wrong: Know whyyou re doing it Investigate capabilities of the system PICS Technical Bulletin IOM (aka O&M Manual) Describe responsibilities Details Specs Describe control sequences * PICS = Protocol Implementation Conformance Statement kw Engineering

12 Control System Coordination Table 23 Sequences 24 Standard VAV dual max sequence Explicit time delay Coordinate with lighting, where applicable Additional time delay may be appropriate Which occsensors send the signal? Easy for an office or conference room Harder for a large assembly space Temp setbacks in the Goldilocks Zone Risk losing control 2 deg F is typical Pre-occupancy Purge Mode Minimum airflow when unoccupied Suppress demand? Off-hour trigger exemption kw Engineering

13 How many ways can it fail? 25 Lighting occupancy sensor Room controller 5 Network Bridge VAV Controller and misc Controller BACNet Module 10 VRF Systems 26 Need a BACnet card! Optional equipment for most manufacturers Must be done through the BMS Integration not always necessary Status could be routed to nearby controller BMS then commands VRF unit Beware of input capability Modulate OA kw Engineering

14 27 Case Study Design Design showed no details of integration with vague sequences (Integration not worked out in design) No details = issue gets pushed to construction Integration details still unknown * Cx Role: design review and coordinator kw Engineering

15 Addendum Issues pushed to design integration meeting Issue not resolved in integration meeting because too many other issues to resolve and outsourcing responsibility to controls contractor Issue pushed to submittals Submittals Issue not resolved in submittal too difficult to coordinate different contractors Cx review identified issues Controls see lighting Electrical see controls Contractual issues! kw Engineering

16 Mechanical Controls Submittal 31 Lighting Control System Submittal 32 kw Engineering

17 Height of Construction 33 Contractor, Cx, Owner forced cooperation with Electrical Sub Contractor: We have an issue You need to fix it We will check your work Cx: We will test your work Call in favors to lighting supplier Owner: You work for us Listen to Contractor and kw It got built! Two different kinds of integration: Network Auxiliary relay Results: it works! Adjustments Pre-testing Adjustments Final testing kw Engineering

18 What can go wrong? 35 Applied to inappropriate spaces Or-equal submittal notcoordinated with mechanical (or shared with CxP!!) Crappy sequences Lack of coordination Lack of knowledge Lack of clear responsibility/ies Network latency Expectations not met Or-Equal lighting & HVAC control systems Incomplete integration Incomplete Cx design/build/post-occ What s next? 36 Wireless communication Addressable systems VRFs! kw Engineering

19 Other considerations 37 Owner s maintenance TRUMPs all No energy savings will be realized if it is not programmed or maintained, or if it is disabled Lighting control systems are not or equals Manufacturers report occupancy status differently Sequences must be written differently Thanks for watching! 38 Know what you want Put in the effort Simpler is better Coordinate Maintainability is crucial Test together Lyn Gomes, PE, CCP, LEED AP, CLCATT kw Engineering lgomes@kw-engineering.com kw Engineering

20 Integration and Sequencing Questions 41 How quickly does the HVAC system know when the room is vacant/occupied? How fast does it need to know and respond Is the time it takes for the HVAC system to go vacant the same as the lighting system? Are they on separate timers or subsequent timers What tools are in place to troubleshoot the occupancy state? If the occupancy/hvac system isn t working, who do you call to fix it, the lighting shop, the HVAC shop, or the control engineers? Make Decisions Early and not later 42 Figure out how you will control occupancy based HVAC at the start of the project Don t do it across multiple projects. Define how many lighting controls or metrics you need to manipulate or track centrally Define and assign responsibility for the commissioning and integration of all those systems and solutions. How much will be tested? 10% 100% kw Engineering

21 45 How is your maintenance department set up? (Who will own it?) Maintenance - Physical Stuff Lighting lights, switches HVAC VAV controllers, thermostats, Air Handlers, etc Control System Hardware- controls infrastructure IT Security Network Architecture and infrastructure Security Rules Data shop Data Metering + integration with other energy metering Data Historian Energy Manager What is their role in your org? How to prevent a maintenance nightmare 46 Say something goes wrong: identifying the problem and fixing the issue should NOTrequire teamwork Problems should be solved by one team, one trade No finger pointing! Ensure issues can be resolved by existing staff CxPs: frank discussion of staff s strengths, time commitments Owners: If new expertise is needed, find it. kw Engineering

Energy Savings with Direct Digital Control

Energy Savings with Direct Digital Control Energy Savings with Direct Digital Control Energy Solutions Economizers Demand Controlled Ventilation (DCV) Variable frequency drives Programmable thermostats DDC systems small to large 2 Economizers &

More information

DIVISION 26 ELECTRICAL SECTION LIGHTING CONTROL SYSTEM

DIVISION 26 ELECTRICAL SECTION LIGHTING CONTROL SYSTEM DIVISION 26 ELECTRICAL SECTION 26 09 26 PART 1 GENERAL 1.01 DESCRIPTION A. The intent of this set of specifications is to provide a complete, functional, intelligent, lowvoltage lighting control system

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

PRO-WATCH NOTIFIER SECONDARY FIRE INTERFACE ARCHITECT AND ENGINEERING SPECIFICATION

PRO-WATCH NOTIFIER SECONDARY FIRE INTERFACE ARCHITECT AND ENGINEERING SPECIFICATION Section 00000 SECURITY PRO-WATCH NOTIFIER SECONDARY FIRE INTERFACE ARCHITECT AND ENGINEERING SPECIFICATION PART 1 GENERAL A. The intent of this document is to specify the minimum criteria for the design,

More information

Total Unified Solution for Building Integration: Communications, Access Control, Video Surveillance and Fire

Total Unified Solution for Building Integration: Communications, Access Control, Video Surveillance and Fire ISC West 2013 Product Showcase Total Unified Solution for Building Integration: Communications, Access Control, Video Surveillance and Fire www.mircomgroup.com [TX3] Unified Solution Our unified solution

More information

LG ELECTRONICS Air Conditioning Technologies LG Guide Specifications Controls

LG ELECTRONICS Air Conditioning Technologies LG Guide Specifications Controls LG ELECTRONICS Air Conditioning Technologies LG Guide Specifications Controls 1 Article I. General Section 1.01 Section 1.02 Section 1.03 System Description Quality Assurance Storage and Handling Article

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

LightSweep. Lighting Control System

LightSweep. Lighting Control System LightSweep Lighting Control System Incredible Control GE LightSweep is a comprehensive indoor lighting control system designed to save money while improving the efficiency, comfort, safety and security

More information

LIGHTING CONTROLS

LIGHTING CONTROLS 260923 LIGHTING CONTROLS PART 1: GENERAL 1.01 SUMMARY COMMENTS A. CU has developed this lighting control guideline to direct design professionals toward standard solutions that meet the University s performance

More information

Virginia Tech Standards for Building Automation System

Virginia Tech Standards for Building Automation System March 1, 2016 Virginia Tech Standards for Building Automation System A. Existing Conditions: The Campus Building Automation System is Siemens Apogee and controls all significant campus facilties. Virginia

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES To qualify the upgrade must add or substantially modify 3 or more sequences/system capabilities. Also, all sequences and items listed under the required section are needed in

More information

Document # R01

Document # R01 Viconics VT7600 Series PIR-Ready Rooftop Unit Controllers Part 1 General The VT7600 series is designed for single-stage and multi-stage control of heating/cooling equipment such as rooftop and self-contained

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES HVAC non CENTRAL PLANT 1) Zone Level Scheduling & Override for all air handlers (supply and exhaust) to match occupied hours by zone DDC or occupancy sensors (OS) allowed. (403.2.4.3,

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

ADDENDUM NO.1. March 4, 2013 HEAT PUMP REPLACEMENT FOR: GATE CITY ELEMENTARY SCHOOL

ADDENDUM NO.1. March 4, 2013 HEAT PUMP REPLACEMENT FOR: GATE CITY ELEMENTARY SCHOOL ADDENDUM NO.1 March 4, 2013 HEAT PUMP REPLACEMENT FOR: GATE CITY ELEMENTARY SCHOOL The data included hereinafter is issued by the Engineer (Engineered Systems Associates, 1355 East Center, Pocatello, ID

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

P2000 and Metasys System Integration

P2000 and Metasys System Integration P2000 and Metasys System Integration Product Bulletin Code No. LIT-12012141 Software Release 3.14 SP1 Issued June 23, 2017 The Johnson Controls P2000 Security Management System supports the integration

More information

10+ HVAC Troubleshooting Tips for Healthcare Facilities Jerry Hirsch JCI Facility O&M Performance Development Manager.

10+ HVAC Troubleshooting Tips for Healthcare Facilities Jerry Hirsch JCI Facility O&M Performance Development Manager. 10+ HVAC Troubleshooting Tips for Healthcare Facilities Jerry Hirsch JCI Facility O&M Performance Development Manager 2019 WHEA Webinar Johnson Controls Institute Overview Operation & Maintenance (O&M)

More information

- HSDK. to Integration. Honeywell Integrated Security Consultants Event, July Rev 10/07/11

- HSDK. to Integration. Honeywell Integrated Security Consultants Event, July Rev 10/07/11 Road to Integration - HSDK Road to Integration Honeywell Integrated Security Consultants Event, July 2011 Rev 10/07/11 Agenda The Open Pro-Watch Ecosystem The HSDK Developer Program Building a HSDK solution

More information

PSC-ID-x-CM Series Ceiling Mount Occupancy Sensor

PSC-ID-x-CM Series Ceiling Mount Occupancy Sensor TECHNICAL SPECIFICATIONS PSC-ID-x-CM Series Ceiling Mount Occupancy Sensor Basic Features Line voltage version: 120-277VAC, 60Hz Low voltage version: 24VDC, requires separate class 2 power supply PIR sensor

More information

SECTION INTRUSION DETECTION

SECTION INTRUSION DETECTION (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION

More information

East Central College

East Central College SECTION 260923 LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom Viconics VT7350 Series PIR Ready Fan-coil Controllers General The VT7350 series are PIR Ready low-voltage microprocessor-based fan-coil controllers. Models are available controlling single speed and multi-speed

More information

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process.

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. SECTION 239950 MECHANICAL COMMISSIONING SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. B. Commissioning

More information

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana ADDENDUM NO. 2 RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana TO: All Bidders Gentlemen: This Addendum

More information

ASHRAE Guideline 36 Advanced HVAC Control Sequences

ASHRAE Guideline 36 Advanced HVAC Control Sequences ASHRAE Guideline 36 Advanced HVAC Control Sequences Rick Stehmeyer - Senior Engineer Matt Napolitan, P.E., CCP, CPMP, LEED AP BD+C - Principal Image Source: http://worldatdistance.com/2013/10/07/the-complete-noobs-guide-to-making-a-website//

More information

SECTION ELECTRICAL SYSTEMS COMMISSIONING

SECTION ELECTRICAL SYSTEMS COMMISSIONING SECTION 16990 PART 1 - GENERAL 1.01 SECTION INCLUDES A. Section Includes: 1. General requirements for Commissioning (Cx) of lighting systems components, lighting controls and HVAC systems line voltage

More information

GE LightSweep Lighting Control System Guideform Specification

GE LightSweep Lighting Control System Guideform Specification GE Lighting Control GE LightSweep Lighting Control System Guideform Specification If you have any questions at all regarding this specification, please contact your local GE Lighting Control representative,

More information

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems X X testregistrierung Type Web server, also for mobile devices Zone modules Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems X-AIRCONTROL zone

More information

P2000 and Metasys System Integration

P2000 and Metasys System Integration P2000 and Metasys System Integration Product Bulletin Code No. LIT-12011781 Software Release 3.12 Issued June 20, 2013 Supersedes April 20, 2012 Refer to the QuickLIT Web site for the most up-to-date version

More information

ENTOUCH ONE USER GUIDE

ENTOUCH ONE USER GUIDE ENTOUCH ONE USER GUIDE v4.0 MEASURE. MANAGE. SAVE. Contents Getting Started 3 Installation 7 Using the Setup Wizard 11 Using the Home Screen 12 Using the Main Menu 16 The Setup Menu 19 Using the Web Management

More information

SECTION 26 NX DISTRIBUTED INTELLIGENCE LIGHTING CONTROL SYSTEM HUBBELL CONTROL SOLUTIONS

SECTION 26 NX DISTRIBUTED INTELLIGENCE LIGHTING CONTROL SYSTEM HUBBELL CONTROL SOLUTIONS SECTION 26 NX DISTRIBUTED INTELLIGENCE LIGHTING CONTROL SYSTEM HUBBELL CONTROL SOLUTIONS PART - 1 GENERAL 1 SYSTEM DESCRIPTION A. The distributed lighting control system as specified herein shall be comprised

More information

Subcontract Agreement No.

Subcontract Agreement No. ATTACHMENT G TRADE INTERFACE AGREEMENT Subcontract Agreement No. PROJECT: TEXASTECH UNIVERSITY HEALTH SCIENCES CAMPUS, EL PASO, TEXAS MEDICAL SCIENCE BUILDING II PARTICIPANTS: Sundt Construction, Inc.

More information

v3 360 Dual Technology Low Voltage Occupancy Sensor with Light Level, Isolated Relay and Manual On feature

v3 360 Dual Technology Low Voltage Occupancy Sensor with Light Level, Isolated Relay and Manual On feature DT-300 v3 360 Dual Technology Low Voltage Occupancy Sensor with Light Level, Isolated Relay and Manual On feature Specifications Voltage...18-28VDC/VAC, half wave rectified AC Current Consumption...25

More information

Application of OPC in the Intelligent Building System Integration

Application of OPC in the Intelligent Building System Integration Application of OPC in the Intelligent Building System Integration Jie Chen Dongying Vocational College Dongying 257091, P.R.China Xiuli Sun The control system education of Jinan university Jinan 250022,

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 0800 - COMMISSIONING OF FIRE SUPPRESSION SYSTEMS GENERAL 1.1 SUMMARY General 1. Work under this contract shall meet the requirements of Division 01, General Requirements, Conditions of Contract,

More information

Exhibit J. Subcontract Agreement No.

Exhibit J. Subcontract Agreement No. Exhibit J SUBCONTRACTOR TRADE INTERFACE AGREEMENT Subcontract Agreement No. PROJECT: NEW EASTSIDE REGIONAL PARK PHASE I PARTICIPANTS (PARTIES): Sundt Construction, Inc. PURPOSE: General Contractor (Sundt)

More information

Tenant Heat Pump Bulletin Temperature Controls Buildings A1, C1, and H1

Tenant Heat Pump Bulletin Temperature Controls Buildings A1, C1, and H1 12/4/2017 Tenant Heat Pump Bulletin Temperature Controls Buildings A1, C1, and H1 This bulletin is to advise you of the fees and responsibilities associated with the tenant s temperature controls. Tenant

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if

More information

Shannon J Markey LC, LEED AP Legrand BCS / Wattstopper Western Regional Manager. Yesterday, Today & Tomorrow

Shannon J Markey LC, LEED AP Legrand BCS / Wattstopper Western Regional Manager. Yesterday, Today & Tomorrow Shannon J Markey LC, LEED AP Legrand BCS / Wattstopper Western Regional Manager Yesterday, Today & Tomorrow The Good Old Days: The.59 Cent Solution Simple, Inexpensive, Easy To Operate, Etc. Everybody

More information

Welcome, and thank you for joining us today!

Welcome, and thank you for joining us today! Welcome, and thank you for joining us today! EnOcean Radio Technology Interoperable Wireless Standard Interoperable technology and products. HVAC&R, monitoring and lighting control systems are readily

More information

Integrated Automation

Integrated Automation Revision 04/27/2017 Purpose: The Architect and/or Engineer shall incorporate the Rice specific requirements indicated in this standard s section into their design. The Architect and/or Engineer shall further

More information

York 25-Ton VAV Rooftop Unit

York 25-Ton VAV Rooftop Unit HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 0996 York 25-Ton VAV Rooftop Unit Introduction Page 3 Overview *3 Configuration 5 Sequence of Operation 7 Modes of Operation

More information

Prescriptions for Critical Healthcare Cx. John D. Villani, P.E. Associate Grumman/Butkus Associates

Prescriptions for Critical Healthcare Cx. John D. Villani, P.E. Associate Grumman/Butkus Associates Prescriptions for Critical Healthcare Cx John D. Villani, P.E. Associate Grumman/Butkus Associates AIA Quality Assurance Learning Objectives 1. Medical Industry Changes and how they impact Design, Construction,

More information

Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc.

Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc. M&V Real Results of High Performance Design Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc. Overview Measurement & Verification (M&V) Plan for New

More information

SENSAPHONE 901 Tryens Road Aston, PA PH:

SENSAPHONE 901 Tryens Road Aston, PA PH: SENSAPHONE 901 Tryens Road Aston, PA 19014 PH: 877-373-2700 www.sensaphone.com Why Choose Sensaphone Sensaphone products are designed to help you watch over a remote facility. Our range of Sensaphone solutions

More information

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include: Model Number: 8680-N2 Product/System Title: Room Pressure AOC Controller with N2 Communications Protocol Contents of this manual supplement include: 1) Sequence of Operation 2) Variable map 3) Description

More information

LonMark. Sheppard Air Force Base Wichita Falls, Texas

LonMark. Sheppard Air Force Base Wichita Falls, Texas LonMark Educational Seminars AHR Expo 2008 Sheppard Air Force Base Wichita Falls, Texas Mark Snyder Contract Officer-Chief 82d Contracting Squadron 136 K Avenue, Suite 1 Sheppard AFB, TC 76311 Earl Gray

More information

The EN54 Part 2 & 4 Fire System

The EN54 Part 2 & 4 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

CAREL heatersteam Electric Element Steam Humidifiers

CAREL heatersteam Electric Element Steam Humidifiers Suggested Engineering Specifications Section 23 84 13 CAREL heatersteam Electric Element Steam Humidifiers 1. GENERAL SCOPE 1. Furnish and install as indicated on the drawings and plans, in-duct [space]

More information

ADDENDUM NO. 2 COOK LIBRARY BATHROOM RENOVATIONS PROJECT NUMBER TU-1874-SBR

ADDENDUM NO. 2 COOK LIBRARY BATHROOM RENOVATIONS PROJECT NUMBER TU-1874-SBR ADDENDUM NO. 2 COOK LIBRARY BATHROOM RENOVATIONS PROJECT NUMBER TU-1874-SBR 5/9/18 Procurement Towson University 8000 York Road Towson, MD 21252-0001 t. 410 704-2171 f. 410 704-8233 Ladies and Gentlemen:

More information

HOME MANAGEMENT GATEWAY

HOME MANAGEMENT GATEWAY LS-20 The Universal Box HOME MANAGEMENT GATEWAY OPERATION MANUAL V1.00 INTRODUCTION Thank you for purchasing the LS-20 the Universal Home Management Gateway. By adopting modern embedded system and Cloud

More information

Dual Relay Multi-Technology Wall Switch Occupancy Sensors

Dual Relay Multi-Technology Wall Switch Occupancy Sensors Dual Relay Multi-Technology Wall Switch Occupancy Sensors The OSSMD line of dual relay multi-technology Decora style wall switch occupancy sensors features several models to provide automatic lighting

More information

Wireless Indoor Lighting Control System

Wireless Indoor Lighting Control System enabled by Lutron Wireless Indoor Lighting Control System Lutron the image company TM enabled by Lutron simple to specify simple to install simple to use 2 AirLink Simple to specify The flexibility you

More information

CONTENTS. Installation Guide. VT7200 Series

CONTENTS. Installation Guide. VT7200 Series VT7200 Series Installation Guide For mercial HVAC Applications November 2015 CONTENTS Installation 2 Location 2 Installation 2 Configurable BI/UI inputs overview 4 Network ready 6 Terminal, Identification

More information

C. The system shall be capable of turning luminaires on/off (where supported by the luminaire) as well as full range dimming.

C. The system shall be capable of turning luminaires on/off (where supported by the luminaire) as well as full range dimming. SECTION 260943 SPECIFICATIONS - Wireless Network Lighting Controls. PART 1 - GENERAL 1.1 RELATED DOCUMENTS 1.2 SUMMARY AND KEY SYSTEM DIFFERENTIATORS A. The lighting control system specified herein shall

More information

BULLETIN. Temperature Controls (Chilled Water) Phase III only (3/11/2010)

BULLETIN. Temperature Controls (Chilled Water) Phase III only (3/11/2010) BULLETIN Temperature Controls (Chilled Water) Phase III only (3/11/2010) This bulletin is to advise you of the fees and responsibilities associated with the tenant s temperature controls. Tenant Responsibility:

More information

Product Manual SZ1022/SZ1031/SZ1035/

Product Manual SZ1022/SZ1031/SZ1035/ Product Manual SZ1022/SZ1031/SZ1035/ Conventional Heating & Cooling Thermostats Communicating Thermostats Description The SZ1022, SZ1031, and SZ1035, are microprocessorbased mable thermostats designed

More information

Metasys Integrator TITUS Application

Metasys Integrator TITUS Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date October 12, 2005 APPLICATION NOTE Metasys Integrator TITUS Application lntroduction Page 3 Application

More information

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide SE8600 Series Room Controllers 2 TABLE OF CONTENTS Overview 2 SE8600 Rooftop Unit and Indoor Air Quality Controllers 3 SE8600UxBxx 2 Heating

More information

BULLETIN. Temperature Controls (10/2013)

BULLETIN. Temperature Controls (10/2013) BULLETIN Temperature Controls (10/2013) This bulletin is to advise you of the fees and responsibilities associated with the tenant s temperature controls. This applies to Phase I & II only. Tenant Responsibility:

More information

1.0 Digital Controller

1.0 Digital Controller Form CP-AHU D19_D21_D22 (11-17) D303072-A Obsoletes Forms CP-Preeva-D21 (1-16) Doc No 303072, CP-Preeva-D19 (1-16) Doc No 303071 Applies to: Preeva, MAPS, MAPS II, RPB, RPBL & SSCBL Series For Air Handler

More information

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT SEQUENCE OF OPERATION GUIDELINE AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT Document: VAV-HTG rev1 Revision: 1.0 Rev. Date: July 22, 2011 NOTES: 1. THIS SEQUENCE

More information

Alarm module for leak detection with webserver

Alarm module for leak detection with webserver This instruction document consists of 2 parts : one part about the assembly of the components and one part about configuration and starting-up of the system. The assembly is done by the qualified installer

More information

SECTION LIGHTING CONTROLS

SECTION LIGHTING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 09 23 LIGHTING CONTROLS SPEC WRITER NOTE: 1. Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

Vykon. Security. Integrated Access Control. Web enabled security management built on the Niagara Framework

Vykon. Security. Integrated Access Control. Web enabled security management built on the Niagara Framework Vykon Security Integrated Access Control Web enabled security management built on the Niagara Framework Niagara for Security Applications Integrating security within building automation systems brings

More information

Version 1.03 January-2002 USER S MANUAL

Version 1.03 January-2002 USER S MANUAL Version 1.03 January-2002 1 USER S MANUAL 2 Version 1.03 January-2002 System Details CUSTOMER:...... PHONE:... FAX:... INSTALLED BY:...... PHONE:... FAX:... MAINTENANCE & SERVICE:...... PHONE:... FAX:...

More information

InfinityPro. Control System for Rapid Engineering, LLC Air Handlers. User, Operation & Troubleshooting Manual

InfinityPro. Control System for Rapid Engineering, LLC Air Handlers. User, Operation & Troubleshooting Manual InfinityPro Control System for Rapid Engineering, LLC Air Handlers User, Operation & Troubleshooting Manual Depending upon the date of shipment of your air handler(s), you will have received one of the

More information

Advanced Installation and Configuration Instructions

Advanced Installation and Configuration Instructions TP-WEM01-A Performance Series AC/HP Wi- Fi Thermostat Carrier Côr Thermostat Advanced Installation and Configuration Instructions Table of contents How to Use This Document... 3 Wiring Diagrams... 4 Installations

More information

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS 1 AIR HANDLING UNIT TRENDS 2 1. The trending charts provided on the following pages prepared as part of a retro-commissioning investigation. The

More information

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx Case Study: Furman University Charles H. Townes Center for Science Michael K. Mantai, PE, CCP President System WorCx AIA Quality Assurance Learning Objectives 1. Case study example of Chilled Beam technology

More information

WIRELESS CONTROLLABLE DEUS LLC

WIRELESS CONTROLLABLE DEUS LLC WIRELESS CONTROLLABLE L I G H T I N G S Y S T E M DEUS LLC TECHNOLOGY AND INTELLECTUAL PROPERTY POWER SUPPLY MANUFACTURER FIXTURE MANUFACTURER LIGHTING SYSTEM DISTRIBUTOR LIGHTING SYSTEM PROJECT ORGANIZATION

More information

User & Installer Manual SMT-400 "Enterprise" Wi-Fi Thermostat

User & Installer Manual SMT-400 Enterprise Wi-Fi Thermostat User & Installer Manual SMT-400 "Enterprise" Wi-Fi Thermostat Ver 1.01 May 2018 Great care has been taken in the preparation of this manual. Smart Temp Australia P/L takes no responsibility for errors

More information

PIR Application Guide for the for VT76xxX5x00(X) Series thermostats (Issue Date: November, 2015)

PIR Application Guide for the for VT76xxX5x00(X) Series thermostats (Issue Date: November, 2015) PIR Application Guide for the for VT76xxX5x00(X) Series thermostats (Issue Date: November, 2015) 1 Product Overview The VI-PIR Accessory covers with embedded Passive Infra-Red motion detector have been

More information

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers TABLE OF CONTENTS Overview 2 VT86X0U5X00B 2 heating / 2 Cooling for Rooftop unit and Indoor air quality 3

More information

Ceiling-Mounted Motion Detector. 752/CD, 752/CP, 752/CU and 752/Cx180. Installation Instructions

Ceiling-Mounted Motion Detector. 752/CD, 752/CP, 752/CU and 752/Cx180. Installation Instructions Ceiling-Mounted Motion Detector 752/CD, 752/CP, 752/CU and 752/Cx180 Installation Instructions Contents 1.0 Description...3 1.1 Contents of the Box...3 2.0 Safety...4 3.0 Coverage Patterns...4 3.1 PIR

More information

Sensors and Detectors

Sensors and Detectors 12/12/2017 Sensors and Detectors - Clipsal by Schneider Electric Sensors and Detectors Add sensors and detectors to make an environment smarter and more efficient. C-Bus sensors and detectors allow environmental

More information

Terminal Commissioning Case Study- Terminal A Logan International Airport

Terminal Commissioning Case Study- Terminal A Logan International Airport Terminal Commissioning Case Study- Terminal A Logan International Airport ACI-NA Environmental and Operations & Technical Conference May 4, 2008 Brad Jones, PE, AP Sebesta Blomberg Sam Sleiman, PE, CCM

More information

EC-BOS-602/616 AX Security

EC-BOS-602/616 AX Security D a t a s h e e t EC-BOS-602/616 AX Security Comprehensive, easy-to-use Access Control management solution Overview The heart of EC-Net AX Security is the EC- BOS-602/616 AX Security, an advanced IP-based

More information

Introduction. What is the RTU Open controller?

Introduction. What is the RTU Open controller? TU Open v3 CAIE COPOATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-521-01 8/22/2017 Verify that you have the most current version of this document

More information

The integral solution for. Air Handling Units. Technology & Evolution

The integral solution for. Air Handling Units. Technology & Evolution The integral solution for Air Handling Units Technology & Evolution For over 25 years Carel has been dealing with the design and production of electronic controllers and supervision systems for Air-Conditioning

More information

SMART Buildings: How sensor and information technologies are transforming the built environment

SMART Buildings: How sensor and information technologies are transforming the built environment SMART Buildings: How sensor and information technologies are transforming the built environment G. Sandy Diehl November 13, 2013 NFPA Research Foundation Annual Conference Current Reality Now that smart

More information

Daikin ENVi Thermostat installation overview

Daikin ENVi Thermostat installation overview Daikin ENVi Thermostat installation overview RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL Presenter s Name Presenter s Title Daikin ENVi system overview (web based thermostat) Slide 2 Daikin ENVi System Overview

More information

NH Series. Electric Steam Humidifiers. Designed for installation flexibility while maintaining precise humidification control

NH Series. Electric Steam Humidifiers. Designed for installation flexibility while maintaining precise humidification control NH Series Electric Steam Humidifiers Designed for installation flexibility while maintaining precise humidification control NORTEC NH Series humidifiers resolve demanding application needs. commercial

More information

lighting management standalone sensors

lighting management standalone sensors lighting management standalone sensors installation details Ceiling mounting All sensors have built-in bracket systems that enable ceiling mounting. Most sensors are suitable for standard EU boxes (Ø65).

More information

COMcheck Software Version Mechanical Compliance Certificate

COMcheck Software Version Mechanical Compliance Certificate COMcheck Software Version 4.0.3.0 Mechanical Compliance Certificate Section 1: Project Information Energy Code: 2014 Oregon Energy Efficiency Specialty Code Project Title: AHSC (Asian Heal Service Center

More information

Welcome to a world where technology flows through the heart of your business environment. Welcome to CDC

Welcome to a world where technology flows through the heart of your business environment. Welcome to CDC Welcome to a world where technology flows through the heart of your business environment Welcome to CDC Introduction to Integra 4 Integra configuration 4 Graphical Supervisor 6 Integra difference 8 Integra

More information

LENNOX MINI-VRF SYSTEMS. CONNECTING TECHNOLOGY WITH EXPERTISE.

LENNOX MINI-VRF SYSTEMS. CONNECTING TECHNOLOGY WITH EXPERTISE. LENNOX MINI-VRF SYSTEMS. CONNECTING TECHNOLOGY WITH EXPERTISE. LENNOX MINI-VRF MAKES MULTI-ZONE COMFORT EASY AND EFFICIENT. Available in 3- to 5-ton configurations, with options to control up to 9 zones,

More information

Tailored air movement control solutions

Tailored air movement control solutions Tailored air movement control solutions Fantech is committed to the ongoing development of innovative technologies that are designed to optimise the indoor environment and lower energy consumption. In

More information

ACTIVE INFRARED BARRIER

ACTIVE INFRARED BARRIER Although PROTECH provides high security indoor intrusion sensors for the military and government markets, our specialty is outdoor protection. Since we first introduced our PIRAMID outdoor dual technology

More information

Smart Vent System + ecobee3 Setup Guide

Smart Vent System + ecobee3 Setup Guide Smart Vent System + ecobee3 Setup Guide Table of Contents How to Connect... 3 How to Use... 8 Frequently Asked Questions Integration Basics... 12 Integration Support... 14 2 How to Connect How to Connect

More information

Integrated Security Solutions

Integrated Security Solutions Integrated Security Solutions Table of Contents Control Panels 4 Keypads 8 Communication Modules 16 I/O Expanders 20 Door Control 24 Home Automation 25 RF Receivers 26 3 Our integrated security solutions

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings INTRODUCTION TO: ASHRAE STANDARD 90.1, 2013 HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings Rocky Mountain ASHRAE Technical Conference, April 29, 2016 SEAN BEILMAN, P.E.,

More information

Integrated Automation Instrumentation & Terminal Devices

Integrated Automation Instrumentation & Terminal Devices Sections Included In This Standard: 1.1 Building Systems Control 1.2 Building Aumotation Systems (BAS) 1.1 BUILDING SYSTEMS CONTROL A. HVAC CONTROLS: 1. General: Temperature control zones shall not combine

More information

Yoosee fast operating guide V1.6

Yoosee fast operating guide V1.6 Yoosee fast operating guide V1.6 (Suitable for device of 8188WiFi modules) Version explanation: 20171207:V1.6 Simplify & normalize operating process. I. Learn about your camera 1. Ethernet port 2.TF card

More information

RFP Addendum 2 March 31, 2016

RFP Addendum 2 March 31, 2016 RFP Addendum 2 March 31, 2016 For Best Value Procurement Option Three Security Upgrades Ph 1 UT Health Science Center SBC No. 540/013-04-2015 This Addendum forms a part of the Request for Proposals (RFP)

More information

Product Manual SZ1009

Product Manual SZ1009 Product Manual SZ1009 Conventional Heating & Cooling Thermostats with Heat Pump Mode Communicating Thermostats Description The SZ1009 is a microprocessor-based mable thermostats designed for conventional

More information