What can you expect when your state adopts the 2000 International Fire and 2000 International Building Codes?
|
|
- Patricia Poole
- 5 years ago
- Views:
Transcription
1 Issue Number 41 December 1999 Industry Affairs Vigilance pays off What can you expect when your state adopts the 2000 International Fire and 2000 International Building Codes? By Bob Boyer, EST Director of Industry Affairs Good news awaits those communities adopting the new 2000 International Fire and the 2000 International Building Codes. The life safety provisions in the ICC documents provide for greater safety than previously required by (BOCA) Building Official s Code Administrators, (SBCCI) Southern Building Code Congress International, Inc. or (ICBO) International Conference of Building Officials documents separately. As with most well correlated code documents, the ICC requirements for fire alarm systems in the International Building Code (IBC) track closely to the fire alarm requirements set forth in the International Fire Code (IFC) document. Examples of these enhancements contained in the IFC and the IBC follow: 1. All non-required systems are mandated to meet the code. 2. All sprinkler system valves and water-flow switches must be electrically supervised. 3. Emergency Voice Alarm Communication Systems are additionally now required in: a) Mercantile occupancies having an occupant load of 500 or more, or more than 100 persons above or below the level of exit discharge. b) Covered malls exceeding 50,000 square feet. c) Special amusement buildings. d) Buildings with an atrium that connects two or more stories. 4. Emergency Voice Alarm Communication Systems may be used for other announcements. 5. Fire Alarm Systems are required in all factories two stories or more, or with an occupant load of 500 or more above or below the level of exit discharge. 6. Requirements that ALL systems be furnished with: a) Record of completion form. b) An operation, testing and maintenance instruction document, and c) Record drawings. 7. All systems must be inspected, tested and maintained in accordance with NFPA 72. A continuous vigilance of the entire ICC code making process was provided through the combined efforts of the Automatic Fire Alarm Association (AFAA) and the National Electrical Manufacturers Association (NEMA). Without this major undertaking, ground would undoubtedly have been lost rather than gained. Individuals of particular note for their enormous personal dedication and contribution to this successful effort are: Larry Neibauer, AFAA; and, Ron Mengel and Bill Hopple, Codes and Standards Committee of the NEMA 3SB Section. Please, when the opportunity arises, acknowledge your gratitude to these astute individuals for their tremendous contribution to our industry and its future. The author may be reached at: EST, 7852 Browning Road, Pennsauken, NJ Phone: (856) Fax: (856) bob.boyer@gsbsc.gensig.com Technical Fax 3-CPU(1) & 3-ANNCPU(1) RF Reports 2 Product of the Month Pull Out AFT/AFR Audio Fiber Optic Modules 3 7-NFPA Positive Alarm Sequence Programming 5 Calendar of Events 8 1
2 is published every two months by EST's marketing communications department. Its mandate is to pro- mote dialog between EST and those who install and service its products. Editors: Jeff Elie Stella Coultas Advisors: Larry Costa Executive Vice President, EST Steve Hein Vice President, Marketing Mike Browning Director, Business Development Contributing Writers: Dave Miner, Documentation Bob Boyer, Industry Affairs Bob Wanek, EST3 Gary Rehbein, Technical Services 6411 Parkland Drive, FL Phone: EST-2DAY On the Web: Printed in the U.S. on paper containing at least 5% postconsumer waste. Recyclable where facilities exist. 1999, Edwards Systems Technology DL-2 Dialer Setup for the 2-SDU Issue: There is an increased number of calls coming into Technical Services reporting a CPU Fail condition on EST-2(N) systems that have DL-2 Dialers installed. Solution: When installing a DL-2 dialer on an EST-2(N) system you must ENABLE the dialer. This is done by going to Configure, then MCM, then Options. In the Miscellaneous section there is a check box labeled Dialer Enabled. This MUST have an X in it if the dialer is installed. On EST-2 Networked systems each MCMN is capable of having its own dialer. Make sure each MCMN on the network that has a dialer installed also has Dialer Enabled selected. If you have any questions regarding this issue please contact EST Technical Services in, Florida at or
3 PRODUCT OF THE MONTH PULL OUT AFT/AFR AFT/AFR Audio Fiber Optic Modules Ω µ µ µ µ cut on dotted line Ω Ω Ω 3
4 PRODUCT OF THE MONTH PULL OUT AFT/AFR AFT/AFR Audio Fiber Optic Modules cut on dotted line 4
5 7-NFPA Positive Alarm Sequence Programming... Positive Alarm Sequence is a method of fire alarm system operation where evacuation signals can be delayed thereby permitting a brief investigation of an alarm signal. Trained building personnel can prevent unnecessary evacuations where Positive Alarm Sequence operation is implemented. System operation requirements documented below are summarized from NFPA 72 National Fire Alarm Code, 1996 Edition, Section System Operation Requirements: Phase 1: 15 Seconds for Alarm Signal Acknowledgment When an alarm signal is received at the control unit, system operators must acknowledge the alarm within 15 seconds of annunciation to initiate an investigation phase. If the alarm signal is not acknowledged at the control unit in 15 seconds, evacuation signals must activate. Phase 2: 180 Seconds for Alarm Investigation After an operator acknowledges the alarm signal, the system will delay activation of evacuation signals for 180 seconds permitting investigation of the alarm. System reset must cancel signal activation. Second Alarm Signal: If a second alarm signal occurs at any time during Phase 1 or Phase 2, evacuation signals must activate immediately and automatically. Bypass: The system must provide a means to bypass Positive Alarm Sequence operation. Programming: Program a rule that will delay 15 seconds on alarm activation before activating outputs with a LOW priority in the same area where the alarm is reported. In the same rule, delay on activation for 180 more seconds before activating the same outputs again with a LOW priority. Program an Alarm Acknowledge switch for toggle operation that will command all outputs OFF with a LOW priority, regardless of any defined areas. This can be separated into areas if desired. Program alarm initiating devices in an AND group for each area where Positive Alarm Sequence operation is desired. The number of Activations in the AND group must be set for 2. This will cause the outputs to activate immediately in the event of a second alarm. General alarm type operation requires only one group, however several AND groups can be programmed to offer an investigation phase for separate areas. Separate areas will then offer an investigation phase independent of initiated alarms in other areas. Separate areas might be separate buildings, levels or wings. The rules presented use indexing to separate areas. Indexing is not required in a general alarm type application where only one area is defined, and one AND group is programmed. Program a rule that will activate outputs in the same area where the alarm is initiated with a HIGH priority if the AND group becomes active. Program RESET to command all outputs OFF with a HIGH priority. Failure to do this can result in output activation after pressing RESET if the 180-second timer expires prior to the alarm restoring. [ALARM RULE] Alarm L<n:1-3>*ALM* : DelayActivate 15, ON -LOW L<n>*, DelayActivate 180, ON -LOW L<n>* ; [OPERATOR_ACK] Switch C1_SWI1 : OFF -LOW L*, STEADY C1_LED1 ; [AND_GROUP_ACTIVE] ALARM AND AND_L<n:1-3> : ON -HIGH L<n>* ; [RESET COMMAND ALL OFF] RESET:OFF -HIGH L* ; Continued on next page 5
6 Tech Tips an d Stuff NOTES: These rules were tested for proper operation in a single node system with both AUDIBLE and VISIBLE device types. Testing was completed with versions 1.3 SDU and 1.33 Microcode. If amplifiers are used, and output circuits connect directly to notification appliances, versions 1.4 of SDU and Microcode are required. Versions of Microcode prior to 1.4 do not permit a programmer to specify a priority for amplifier outputs. Pressing the user programmed Alarm Acknowledge switch after the 15-second timer expires will turn outputs off, as well as the ALARM SILENCE switch. Expiration of the 180-second timer will reactivate the outputs if either the Alarm Acknowledge or the ALARM SILENCE switch has been pressed. Pressing RESET at any time will force the outputs OFF during the reset period. Output activation timers can still be active after system reset has completed if the point that alarmed does not restore. This can occur only if RESET is pressed early in the investigation phase and the input is not restored after system reset has completed. Site personnel must investigate the initiated alarm and determine whether or not the event is hazardous. If not hazardous, investigation personnel must then notify system operators at the main control and restore the input immediately. Failure to follow this procedure can result in unexpected output activation. The letters ALM were programmed in the labels of all alarm-initiating devices to limit the number of rules needed. A method to bypass Positive Alarm Sequence is not presented. In past programming examples, this offered more confusion than it was worth. Some callers implementing Positive Alarm Sequence examples that were provided for other systems reported that the bypass feature in the samples did not work. The callers however expected the bypass switch to prevent output activation while in bypass mode. While this may be normal operation for a typical bypass switch, technicians at EST do not believe that this operation is the intention of the NFPA requirement for a bypass switch in this application. The bypass switch in past examples will bypass the investigation phase and the system will activate outputs immediately on the first alarm received while in bypass mode. ATTENTION: Read this information before using 3-SDU version CPU MicroCode Version 1.5 Panel Upgrade Instructions 1.1 CPU Version 1.5 The new application and boot code must both be downloaded to ALL panels in the system. Version 1.5 is not compatible with earlier versions of CPU MicroCode. Do not mix different versions of CPU MicroCode on the same network. By carefully following the steps below, an existing 3-SDU 1.4 system can be upgraded using the network download functionality of CPU version 1.4. Upgrade Instructions: V1.33 or lower (no network download option) to V1.5 Project version numbers are imbedded in each project file. Because the Save As function creates a new version number that is different than the imbedded version, you must use the following procedure to install V1.5. To upgrade the hardware and software in your system, please follow these steps, in order. With 3-SDU version 1.5 installed: 1. Save your project as a new version, using the Save As function in the file menu. 2. Recompile your project, run db-conversion, and then Save the project a second time. 3. Remove nodes from the network. 4. Select SINGLE STEP download, select database, application code, and bootloader code. 5. Connect the laptop to the node CPU, and start the download. 6. Connect the laptop directly to the 3-SSDC and 3- ASU to update application and bootloader code as required. 7. After all nodes are upgraded, reconnect the nodes to the network. 8. Using the Command Menu, restart the system. Upgrade Instructions: V1.4 (network download option available) to V1.5 Project version numbers are imbedded in each project file. Because the Save As function creates a new version number that is different than the imbedded version, you must use the following procedure to install V1.5. To upgrade the hardware and software in your system, please follow these steps, in order. With 3-SDU version 1.5 installed: 1. Save your project as a new version, using the Save As function in the file menu. 2. Recompile your project, run db-conversion, and then Save the project a second time. 3. Select database and application code. DO NOT SELECT BOOTLOADER CODE! 6
7 7-NFPA Positive Alarm Sequence Programming Hardware requirements: 1 (Switch Card) 3-12SG 1 SIGA-CC1 1 SIGA-CC2 1 SIGA-UM Objects: The operator switch must be programmed for toggle type operation. Labels: Operator Acknowledge switch labeled as C1_SW1 Operator Acknowledge LED labeled C1_LED And Group labeled as AND_L1 And Group labeled as AND_L2 And Group labeled as AND_L3 4. Connect the laptop to the first CPU on the network (any node for Class A networks) and NETWORK DOWNLOAD version 1.5 of the database and version 1.5 of the CPU Application code. 5. When complete, select all 3-CPU bootloader code. 6. NETWORK download the bootloader code to all nodes. There are times when you may have to switch a PT-1S printer to work on a different system in the course of one day of testing or troubleshooting. The settings for the IRC-3 and EST-2 are the same. EST-3 systems use a different configuration. SW1 and SW2 are located on the small Serial board under the cover of the PT-1S Serial Printer. The Motherboard switch is located along side the serial board on the main motherboard. SW1 Switch Settings for the IRC-3 and EST-2 OFF OFF ON OFF ON ON ON ON SW2 Switch Settings for the IRC-3 and EST-2 XXX XXX XXX OFF ON ON ON ON Motherboard Switch Settings for the IRC-3 and EST-2 OFF OFF OFF OFF ON OFF ON OFF SW1 Switch Settings for the EST-3 ON ON ON OFF ON ON ON ON SW2 Switch Settings for the EST-3 XXX XXX XXX OFF OFF ON ON ON Motherboard Switch Settings for the EST-3 OFF OFF OFF OFF ON OFF ON OFF In both cases the SW2 switches 1, 2 & 3 are the Baud Rate settings. The following are the different Baud Rate settings that you may encounter. Substitute these settings as needed ON ON OFF Setting for IRC3 and EST2 if using the CDR OFF OFF ON Recommended Setting for IRC3 and EST ON OFF ON Recommended Setting for EST OFF ON ON Optional Setting for EST3 7
8 -Calendar- Class Schedule: Contact EST Institute at (941) for enrollment information. (New) Basic Access Control (2 days) March Basic Fire Alarm Course (2 days) February 7 8 February March Fire Alarm Technician s Course (3 days; Basic Fire prerequisite, this is also a Certification course sponsored by the IMSA) February March FCC Course (5 days; IRC3 prerequisite) February IRC3 Operations and Maintenance Course February 9 11 EST3 Operations and Maintenance Course (2 days) February 9 10 Fireworks Course w/est3 or IRC3 (5 days, EST3 or IRC3 prerequisite) February EST3 Hardware & Installation and EST3 Program & Network Combo (8 days please sign up for both parts) January February 9 18 March EST3 Program & Network Course (5 days with EST3 Self-Study prerequisite. Must complete the self-study before enrolling) January February March Fire Alarm Systems Programming Course (2 days, Basic Fire or equivalent prerequisite) February Fire Alarm Systems Troubleshooting (3 days, Basic Fire or equivalent prerequisite) March 1 3 IRC3/Signature Course (10 days) January 24 February 4 March IRC3 Certification Course (5 days Must complete IRC3 Self-Study before enrolling) March 6 10 EST2 Hardware & Installation and EST2 Program & Network Combo (8 days. Please sign up for both parts on the enrollment form) January February 9 18 March EST2 Program & Network Course (5 days with EST2 H&I Self-Study prerequisite. Must complete self-study before enrolling) January February March Fire Alarm Systems Project Management Course (5 days) January 31 February 4 SALES TRAINING Strategic Partner Product Sales Course (4 days Quick start program for the new salesperson) January 31 February 4 Strategic Partner Competitive Strategies (3 days PSS is a recommended prerequisite) January Chicago February 29 March 2 8 EDWARDS SYSTEMS TECHNOLOGY 6411 Parkland Drive, FL Return Postage Guaranteed
Simplex Panel Interface Guide
Simplex Panel Interface Guide February 2016 SATEON Software Integrations Simplex Panel Interface Guide Issue 1.0, released February 2016 Disclaimer Copyright 2016, Grosvenor Technology. All rights reserved.
More information2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is
More informationTable of Contents. Appendix A Special Characters 31
Table of Contents Introduction 2 Section 1: General System Operation 3 1.1 Getting to Know Your System... 3 1.2 How to Arm... 4 1.3 Alternate Arming Methods... 5 1.4 Disarming... 6 1.5 Alarm Memory...
More information4/9/2015. Introductions. Introductions Scott Lord Executive Officer, All Systems. Mass Notification And Emergency Communications (MNEC)
Mass Notification And Emergency Communications (MNEC) Scott Lord, All Systems Chuck Wilson, National Systems Contractors Association 1 Chuck Wilson Executive Director, NSCA Introductions The National Systems
More informationZX1e ZX2e ZX5e. Document No Issue 01 user manual
ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL
More informationMaintaining Building and Fire Safety During Active Assailant Events and Other Terrorist Events
Position Statement Maintaining Building and Fire Safety During Active Assailant Events and Other Terrorist Events Maintaining school safety in light of recent terrorist events is challenging for everyone,
More informationEST3X User Guide P/N EN REV 1.0 ISS 10MAY11
EST3X User Guide P/N 3101799-EN REV 1.0 ISS 10MAY11 Copyright Trademarks and patents Manufacturer Version FCC compliance Contact information 2011 UTC Fire & Security. All rights reserved. The EST3X name
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL
PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if
More informationAddressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards
Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards Wayne D. Moore, P.E., CFPS, SET Vice President JENSEN HUGHES 117 Metro Center Boulevard, Suite 1002
More informationEST2 System Operations Manual. P/N Rev AUG00
EST2 System Operations Manual P/N 270188 Rev 5.0 16AUG00 DEVELOPED BY COPYRIGHT NOTICE TRADEMARKS CREDITS Edwards Systems Technology 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 2000
More informationNetwork Display Unit Installation Instructions
Network Display Unit Installation Instructions Introduction This publication describes the installation procedures for the optional Network Display Units (NDUs). This product is compatible with both the
More informationFire Operator Workstation (Fire OWS) User s Guide
Fire Operator Workstation (Fire OWS) User s Guide 1-1 Fire Operator Workstation (Fire OWS) User s Guide Introduction This user s guide details the components, capabilities, and operation procedures of
More informationNFPA 72 Code Changes vs 2013
NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996
More informationVersion 1.03 January-2002 USER S MANUAL
Version 1.03 January-2002 1 USER S MANUAL 2 Version 1.03 January-2002 System Details CUSTOMER:...... PHONE:... FAX:... INSTALLED BY:...... PHONE:... FAX:... MAINTENANCE & SERVICE:...... PHONE:... FAX:...
More informationWhite Papers: Delayed Egress Hardware
www.sdcsecurity.com service@sdcsecurity.com [t] 800.413.8783 805.494.0622 [f] 805.494.8681 801 Avenida Acaso, C ox 3670, Camarillo CA 93011-3670 www.sdcsecurity.com White Papers: Delayed Egress Hardware
More informationEST3 Installation and Service Manual
EST3 Installation and Service Manual P/N 270380 Rev 3.0 21OCT99 DEVELOPED BY COPYRIGHT NOTICE TRADEMARKS CREDITS Edwards Systems Technology 6411 Parkland Drive Sarasota, FL 34243 (941) 739 4300 Copyright
More informationPanel Remote Annunciators Installation Instructions
Panel Remote Annunciators Installation Instructions Introduction This publication describes the installation procedures for the following PIDs: 4100-9607 Remote Annunciator w/ Flexible User Interface Domestic
More information1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.
PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This
More informationOperator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B
Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES 579-685 Rev. B ii iii Cautions and Warnings Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation
More informationONYX FirstVision Specification Interactive Firefighters Display
ONYX FirstVision Specification Interactive Firefighters Display NOTIFIER is a registered trademark, and ONYX FirstVision, NOTI FIRE NET, and VeriFire are trademarks of Honeywell International Inc. Microsoft
More informationONYXWORKS AND FIRSTVISION. Version 4
ONYXWORKS AND FIRSTVISION Version 4 Version 4: Next Generation CONNECTED SOLUTIONS ONYXWorks FirstVision 2 ONYXWORKS Version 4 New to ONYXWorks v4.30 Look Ahead Test Monitoring Configuration Tool Display
More informationInnovative protection that combines power and flexibility
Innovative protection that combines power and flexibility Desigo Fire Safety Modular outpaces industry standards and includes cutting-edge detection and communication capabilities usa.siemens.com/desigo-fs-modular
More informationTrueAlarm Fire Alarm Systems
OPERATOR OPERATOR OR TROUBLE CONDITION: TO : FIRE PRIORITY 2SYSTEM SYSTEM SIGNALS POWER INDICATOR. SUPERVISORYTROUBLE SILENCED ON D. TO SILENCE SIGNALS: - PRESS " SILENCE". SUPV TBL SYSTEM ACK ACK ACK
More informationFI6000 INSTRUCTION MANUAL. Thank you for choosing another quality product from Amperes Electronics. Fire Alarm Interface
INSTRUCTION MANUAL FI6000 Fire Alarm Interface Thank you for choosing another quality product from Amperes Electronics. FI6000 is a phase evacuation controller which can be integrated with various Amperes
More informationFunctional Performance Test
Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control
More informationHinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 28 3111 DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Heat detectors.
More informationSecond Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement
of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections
More informationD8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide
System Reset Trou ble Silence Ala rm Silence Manual Ala rm ENTER NO YES Letters Numb ers Keyword Radionics System Reset Trouble Silence Alarm Silence Manual Alarm ENTER NO YES Le ters Numbers Keyw ord
More informationFIRE FIRE. 4100U Fire Alarm. Operator's Manual. Technical Manuals Online! -
FIRE FIRE 4100U Fire Alarm Operator's Manual 579-197 574-xxx Rev. Rev. B 4 Blank Page- Back of Front Cover Copyrights and Trademarks Copyright Simplex Time Recorder Co., 2001. All rights reserved. Printed
More informationMichigan State University Construction Standards FIRE DETECTION AND ALARM PAGE
PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationALARM SYSTEMS AND EVACUATION PLANS SELF INSPECTION CHECKLIST
OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ALARM SYSTEMS AND EVACUATION PLANS Guidelines: This checklist covers regulations issued
More informationBold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards
More informationNetwork Hardware and wiring (quiz)...
4120 Network/TSW (FA049) Course Agenda Day 1 Course Introduction (Presentation)... 8:00 am to 8:30 am Break Module 1 Installing and Configuring Network Software Applications 4120 New Network Programmer
More informationFire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016
Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the
More informationTHIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS.
THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS. IF YOU RECEIVED A NOTICE BY MAIL AND YOU DO NOT CURRENTLY HAVE A FIRE ALARM INSTALLED IN YOUR BUILDING, YOU MAY DISREGARD THE NOTICE. Dear Building
More informationFunctional Challenges of Integrating Mass Notification and Fire Alarm Systems
Functional Challenges of Integrating Mass Notification and Fire Alarm Systems By Scott Lacey FPE, CSP, SFPE President Lacey Fire Protection Engineering February 12, 2007 Abstract: By Scott Lacey, FPE,
More informationTABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover
TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2 INSTALLATION 3 Mounting the Panel... 3 Mounting the Keypad... 3 Auxiliary Power Connection... 3 PGM Terminal Connections... 3 Bell/Siren Connection... 3 Keypad
More informationWeekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT
Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT-1201739 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................
More informationNetSOLO Broadband. Voice Evacuation. Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System
Voice Evacuation NetSOLO Broadband Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System General The NetSOLO Broadband is a revolutionary advance in fire detection
More informationThe Residences at Christina Landing Wilmington, DE
5.0 FIRE PROTECTION EXISTING CONDITIONS 5.1 Project Specific Fire Protection Data Codes, Regulations, and Standards Building Officials and Code administrators (BOCA) National Building Code [1996] with
More informationRancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency
More informationMetasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway
Metasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway Code No. LIT-1201993 Software Release 2.1 Issued April 12, 2006 Supersedes July 20, 2005 Document Introduction.................................................
More informationZP2 Series Operation Manual
ZP2 Series Operation Manual P/N 501-405203-2-31 REV 03.10 ISS 07NOV13 Copyright Trademarks and patents Manufacturer Version Certification European Union directives Contact information 2013 UTC Fire & Security.
More informationPC4020 v3.2 Instruction Manual
PC4020 v3.2 Instruction Manual WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire
More informationLaptop / PC Programming Manual
Laptop / PC Programming Manual Doc. # Fire PC Program rev B 01.07 This Document is property of Evax Systems, Inc. The Evax Fire Solutions Programmer Components 2 1.0 System Setup 4 1.1 Interface Setup
More informationControl Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2
Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...
More informationFlorida Building Code 2010
Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with
More informationHikvision Certification Tracks
www.hikvisionlearning.com PAGE 2 Hikvision Certification Tracks You asked for it... and we delivered! Hikvision is proud to announce the Hikvision Certification Program! We ve partnered with SecurityCEU.
More information1.3 REFERENCE STANDARDS
SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises
More informationFlorida Building Code Chapter 9 Fire Protection Systems Advanced Course
Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors
More informationOPERATOR S MANUAL MR-2100/2200. Fire Alarm Control Unit. Revision 0 Document #: LT-2002
MR-2100/2200 Fire Alarm Control Unit OPERATOR S MANUAL Revision 0 Document #: LT-2002 WARNING: This manual contains information on limitations regarding product use and function and information on the
More informationNarrative Reports As Regulated by 780 CMR, Section 903.0
EXHIBIT 20 Narrative Reports As Regulated by 780 CMR, Section 903.0 903.1.1 - FIRE PROTECTION CONSTRUCTION DOCUMENTS a. Basis (methodology) of design for the protection of the occupancy and hazard for
More informationMoreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline
Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to
More informationSyncro AS. Analogue Addressable Fire Control Panel. User Manual
Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level
More informationSECTION 907 FIRE ALARM AND DETECTION SYSTEMS
SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing
More informationTABLE OF CONTENTS TABLE OF CONTENTS 1
TABLE OF CONTENTS TABLE OF CONTENTS 1 FEATURES 2 Keypad Programmable... 2 EEPROM Memory... 2 Static/Lightning Protection... 2 Supervision... 2 Operation... 2 SPECIFICATIONS 2 PC1550 Control Panel... 2
More informationSECURITY SYSTEM NOTES
SECURITY SYSTEM NOTES Installing/Service Company For Service Call Central Station Duress Code FUNCTION CODES Function Code Controls Function EMERGENCY ACTIVATION KEYS (check if enabled) Fire Auxiliary
More informationPART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:
PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,
More informationGE Security EST Fire & Life Safety. Sensible. EST2 Networkable Fire Alarm Control Panels with Voice Audio
GE Security EST Fire & Life Safety Sensible EST2 Networkable Fire Alarm Control Panels with Voice Audio We re not very good Before the remarkable EST2 life safety system, only large facilities could justify
More informationSTATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT
STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT The interaction of fire protection systems can be extremely complex. The detection of a fire in a building by an automatic device
More informationLYNX Touch L5210 Series Security System
LYNX Touch L5210 Series Security System User Guide 800-19975 12/14 Rev. B LYNX Touch L5210 Series Your Honeywell security system is designed for use with devices manufactured or approved by Honeywell for
More informationDATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D
DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION Fike s CyberCat 254 (P/N 10-066) is a state-of-the-art true intelligent digital peer-to-peer modular fire alarm control system.
More informationSignature Series Auto-Sync Output Module (CC1S)
Signature Series Auto-Sync Output Module (CC1S) Product description Mounting The Signature Series can be mounted in a North American 2-1/2 in (64 mm) deep 2-gang box or a standard 4 in square box 1-1/2
More informationSECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD
PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard
More informationENGROSSED SUBSTITUTE HOUSE BILL State of Washington 60th Legislature 2007 Regular Session
ENGROSSED SUBSTITUTE HOUSE BILL 1968 State of Washington 60th Legislature 2007 Regular Session By House Committee on Commerce & Labor (originally sponsored by Representatives Simpson, Conway and Ormsby)
More informationrpsa FIRE PROTECTION ENGINEERS
FIRE PROTECTION ENGINEERS R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator
More informationParadox Integration Module Settings Guide
Paradox Integration Module Settings Guide List of Terms used in Paradox Integration Module Settings Guide............. 3 Introduction into Paradox Integration Module Settings Guide............... 4 Configuration
More informationLYNX Touch Security System
LYNX Touch Security System User Guide 1:35 2 PM October 26, 2011 72 Mostly Sunny 68 F F Feels Like 71 Security Messages Automation 5-Day Forecast News Traffic 800-10615 1/12 Rev. A LYNX Touch L5100 Series
More informationGE Healthcare Healthcare Systems 9900 Innovation Drive Wauwatosa, WI USA
URGENT Field Safety Notice GE Healthcare Healthcare Systems 9900 Innovation Drive Wauwatosa, WI 53226 USA 22 nd January 2014 GEHC Ref 36092 To: Healthcare Administrator / Risk Manager Chief of Nursing
More informationSTRUCTURAL BUILDING COMPONENTS MAGAZINE September/October 2003
STRUCTURAL BUILDING COMPONENTS MAGAZINE September/October 2003 The Other Building Code: NFPA 5000 by Kelly Gutting, TPI TPI Technical Director Could NFPA 5000 be coming soon to a jurisdiction near you?
More informationQS1 Technical Reference Manual P/N REV 05 REB 14FEB13
QS1 Technical Reference Manual P/N 3100184 REV 05 REB 14FEB13 DEVELOPED BY COPYRIGHT NOTICE DISCLAIMER TRADEMARKS UTC Fire & Security 8985 Town Center Parkway Bradenton, FL 34202 (941) 739-4200 2013 UTC
More informationReport on First Revisions with Statement June 2014 NFPA 101
101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,
More informationSECTION INTRUSION DETECTION
(NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION
More informationControl Relay Modules
TM INTERNATIONAL ANALOG ADDRESSABLE INPUT/OUTPUT DEVICES Control Relay Modules Model SIGA-CR, SIGA-MCR, SIGA-CRR, Features! Provides one no/nc contact (SIGA-CR/MCR) Form C dry relay contact can be used
More informationAmerican Fire Sprinkler Association. An Introduction to the IBC and IFC
American Fire Sprinkler Association Presents An Introduction to the IBC and IFC October 13, 2005 Speaker Roland Huggins, P.E. Vice President of Engineering and Technical Services American Fire Sprinkler
More informationArea Systems While the alarm bell or siren is sounding, enter your user code. The system silences the alarm bell or siren.
XR20 User s Guide Silencing an Alarm All/Perimeter and Home/Away Systems While the alarm bell or siren is sounding, enter your user code. The keypad displays DISARM SILENCE. Press the Select key under
More informationControl/Communicator
Architectural & Engineering Specifications Control/Communicator 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 13852- PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this
More informationMECKLENBURG COUNTY FIRE MARSHAL S OFFICE
Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and
More informationFirst Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM
2 of 326 11/21/2013 1:03 PM First Revision No. 82-NFPA 72-2013 [ Section No. 2.3.4 ] 2.3.4 ISO Publications. International Organization for Standardization, 1, ch. de la Voie-Creuse, Case postale 56, CH-1211
More informationThe blank report forms are enclosed. If additional blank forms are needed you may contact my office at (210) and ask for Maria Castoreno.
San Antonio Independent School District 1702 N. Alamo Street, Suite 307 San Antonio, Texas 78215-1213 Telephone (210) 554-2420 Fax (210) 271-3330 Office of Construction Services TO: FROM: All Principals
More informationChanges in NFPA
Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration
More information&RPPHUFLDO)LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ
9,67$)% &RPPHUFLDO)LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ 8VHU*XLGH FIRE FIRE * PULL K3522 3/99 TABLE OF CONTENTS SYSTEM OVERVIEW...4 General...4 A Partitioned System...4 Zones...5 Fire
More informationThe EN54 Part 2, 4 and 13 Fire System
Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54
More informationMMX TM. Intelligent Fire Alarm Network. User Guide
MMX TM Intelligent Fire Alarm Network User Guide LT-893SEC Rev 1 May 2017 MMX TM User Guide Table of Contents Introduction... 1 About this Manual... 1 Front Panel Indicators, Controls, and Operation...
More informationGV2 Series Control Panels
GV2 Series Control Panels EN Owner's Manual Supplement System Requirements Minimum system requirements for Classification in accordance with ANSI/SIA CP-01-2000: UL Listed and Classified control unit Model
More informationNETWORX TM. User manual NX-4
NETWORX TM User manual NX-4 POWER Light is on when AC power is present; flashes to indicate a low battery condition. ARMED Light is on when armed; off when disarmed; flashes to indicate a previous alarm.
More informationCORNELL Emergency Response Systems
CORNELL Emergency Response Systems Door Monitor Systems Series 1000 CORNELL Communications, Inc. Milwaukee, WI USA 800-558-8957 - www.cornell.com rev 6/04 A-1000 SERIES DOOR MONITOR OPERATION AND WIRING
More informationNetworX Series NX-1500E LED Keypad
NetworX Series NX-1500E LED Keypad User Manual SECURITY SYSTEM NOTES Installing/Service Company For Service Call Central Station Duress Code FUNCTION CODES Function Code Controls Function This system
More informationM3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO
User s Manual Copyright 2017 SELCO SELCO Betonvej 11 - DK-4000 Roskilde Denmark Phone: 45 7026 1122 - Fax: 45 7026 2522 e-mail: selco@selco.com www.selco.com Table of contents 1 INTRODUCTION...4 2 SOFTWARE
More informationBuilding Code Basics: Fire. Based on the 2012 International Fire Code
Building Code Basics: Fire Based on the 2012 International Fire Code Building Code Basics: Fire, Based on the 2012 International Fire Code Kevin H. Scott International Code Council Executive Vice President
More informationIllinois Office: Michigan Office:
Despite the actions, or inactions, of the government as it relates to the budget or anything else it is responsible for, the third quarter of 2013 continued to display the increased, albeit slow, commercial
More informationMODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description
MODUL-R FIRE ALARM CONTROL PANELS MR-2900/MR-2920 Addressable Fire Alarm Control Panels Description MR-2900 Fire Alarm Control Panel The MR-2900 fire alarm system control unit is the heart of a sophisticated
More information4010 Fire Alarm PC Programmer Installation and Programming Instructions
4010 Fire Alarm PC Programmer Installation and Programming Instructions 574-187 Rev. C Copyright and Trademarks Copyright Simplex Time Recorder Co., 2000. All rights reserved. Printed in the United States
More informationCONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3
CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 2.1 Electrical Specifications... 3 2.2 Communication Loop Parameters... 3 2.3 Dimensions...
More informationTrueCom. Building Communications Systems 5115-Series , Area of Rescue Communications System. Description
TrueCom Building Communications Systems 5115-Series 5115-9001, -9002 Area of Rescue Communications System Description The Simplex 5115-9001 and -9002 Area of Rescue Communications System provides buildings
More informationFA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel
LAMP TEST REMOTE CPU FAULT GROUND FAULT SIGNAL SILENECE FIRE DRILL BUZZER SILENCE INFO AC ON ALARM SUPERVISORY BATTERY SYSTEM RESET AUXILIARY DISCONNECT LAMP TEST MENU LAMP TEST REMOTE CPU FAULT GROUND
More informationAustin Independent School District Police Department Policy and Procedure Manual
Policy 8.07 Austin Independent School District Police Department Policy and Procedure Manual Life Safety Systems I. POLICY The proper operations of the AISD Life Safety Systems (LSS) are essential for
More informationInstallation, Operating and Maintenance Manual
STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS
More informationData Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906
s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones
More information