INSTALLATION INSTRUCTION BOOKLET FOR SMOKE DAMPERS

Size: px
Start display at page:

Download "INSTALLATION INSTRUCTION BOOKLET FOR SMOKE DAMPERS"

Transcription

1 INSTALLATION INSTRUCTION BOOKLET FOR SMOKE DAMPERS Instructions included in this booklet: IOM # Description Page(s) SMD-XXX, SESMD-XXX, SSSMD-XXX, SMD-XXX Series Smoke Detector (DH100ACDCLP) No Flow Smoke Detector Quick Connect Breakaway Connection Drive Slip Breakaway Connection Flange Mounted SMD Supplement 17-1 KIT # 60 SMOKE DAMPERS SMD & SMDR

2 Part Number SMD-XXX, SESMD-XXX, SSSMD-XXX, SMDRXXX, SESMDR-XXX, and SSSMDR-XXX MODELS Leakage Rated Smoke Dampers Vertical or Horizontal Mount Installation, Operation and Maintenance Instructions These instructions apply to the installation of SMD-XXX, SESMD-XXX SSSMD-XXX, SMDR-XXX, SESMDR-XXX and SSSMDR-XXX series leakage rated smoke dampers supplied with factory installed damper actuators. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL S and UL classification R Typical Actuator SMD-XXX, SESMD-XXX, SSSMD-XXX, SMDR-XXX, SESMDR-XXX, and SSSMDR-XXX Model Dampers are intended for installation in accordance with smoke damper requirements established by: National Fire Protection Association NFPA Standards 90A, 9A, 9B, & 10 IBC International Building Codes New York City (MEA listing #60-91-M) California State Fire Marshal (Listing # :10) OCI Blade Indicator (optional) UL CLASSIFIED (see complete marking on product) UL CLASSIFIED to Canadian safety standards (see complete marking on product) UL Standard S (Classification #R13317) RECEIVING AND HANDLING Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for. Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100 F (3 C). SAFETY WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment. This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete. INSTALLATION SUPPLEMENTS Refer to the appropriate Greenheck installation supplements for special requirements: Smoke Detector Supplement (46313) No Flow Duct Smoke Detector (4691) Drive Slip Breakaway Supplement (46769) Quick Connect Breakaway Supplement (460) Open or Close Indicator Supplement (4966) Double Flange Mounted Supplement (47664) WARRANTY Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization. Due to continuing research, Greenheck reserves the right to change specifications without notice.

3 Table of Contents Pre-Installation Guidelines... Installation...3 Smoke Damper Requirements...3 Location of Damper in Ductwork...3 Attaching Damper to the Duct...3 Installing Multiple Damper Section Assemblies...3 Sealing the Installation...3 Actuator Connections...3 Connection and Operation of Open/Close Indicator...3 SMDR-XXX and SSSMDR Blade Orientation...4 Maintenance...4 Troubleshooting...4 Pre-Installation Guidelines The basic intent of a proper installation is to secure the smoke damper in, not to, the opening or duct in such a manner as to prevent distortion and disruption of damper operation. The following items will aid in completing the damper installation in a timely and effective manner. 1) Lift or handle damper using sleeve or frame. Do not lift damper using blades or actuators. ) Damper (rectangular) has label on outside of sleeve indicating a No Screw area. Do not install screws into this area as screws may interfere with unexposed blade linkage and prevent damper blades from opening and/or closing. 3) Damper must be installed into duct or opening square (round) and free of twist or other misalignment. Damper must not be squeezed or stretched into duct or opening. Out of square, out of round, racked, twisted or misaligned installations can cause excessive leakage and/or torque requirements to exceed damper/actuator design. 4) Damper and actuator must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to: a) Mortar dust b) Drywall dust c) Firesafing materials d) Wall texture e) Paint overspray ) Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within feet of the damper. Excessive dirt or foreign material deposits on damper can cause excessive leakage and/or torque requirements to exceed damper/actuator design. 6) Caulking is not necessary, however, may be supplied to the retaining angles. 7) The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary. 3

4 1. SMOKE DAMPER REQUIREMENTS Smoke dampers are required to close and prevent the passage of air and smoke through ducts or ventilation openings in smoke barriers. Smoke dampers are also applied in engineered smoke control systems to establish air pressure differentials and thereby prevent the spread of smoke.. LOCATION OF DAMPER IN DUCTWORK Place the damper assembly in its proper position relative to the barrier as shown (in figure below right). The plane of the closed damper blades must be within 4 in. (610mm) of the rated smoke barrier and before any duct inlets or outlets. On multiple section damper assemblies, the temperature rating of wiring run in the airstream shall be at least equal to the damper temperature rating plus 0 F (10 C).. SEALING THE INSTALLATION After installing the damper in the ductwork, seal the joint between the damper frame and the duct using Dow Corning RTV 73 sealant, GE100 sereis silicone construction adhesive or Component Hardware SLT-000 silicone sealant. Make sure to press the sealant into the joint to guarantee a proper seal. Use the minimum amount of material required to completely seal the joint. See Figure to the bottom. 3. ATTACHING DAMPER TO THE DUCT Attach the damper to the duct using #10 sheet metal screws, 1 /4 in. (6mm) diameter bolts and nuts, tack or spot welds, or 3 /16 in. (mm) diameter steel pop rivets. Attachments must be made at each flange spaced a maximum of 6 in. (1mm) on centers and a maximum of in. (1mm) from corners on rectangular dampers, and on round dampers as follows: Ducts in. (9mm) in diameter and smaller shall have three attachments. Ducts larger than in. (9mm) in diameter up to and including 36 in., (914mm) have five attachments. 4. INSTALLING MULTIPLE DAMPER SECTION ASSEMBLIES The damper assembly is not restricted to a maximum number of sections, but must not exceed the section sizes and assembly sizes shown below. Damper model SMD-01, 0, 03 SMD-301, 30 SMD-301M, 30M SMD-401 SMDR, SESMDR, SSSMDR SESMD-01, SSSMD-01 SMD-301V SMD-401M Maximum Single Section Size in. (mm) 36 x 4 or 3 x 0 (914 x 119 or 13 x 170) 3 x 0 (13 x 170) 3 x 0 (13 x 170) 4 x 60 (119 x 731) 4 (610) 36 x 4 or 3 x 0 (914 x 119 or 13 x 170) 0 x 3 (170 x 13) 4 x 36 (119 x 914) Maximum Overall Size for Multiple Section Dampers in. (mm) 144 x 100 or x 0 (36 x 40 or 731 x 170) 1 x 100 or 6 x 0 (31 x 40) or (60 x 170) 1 x 100 or 6 x 0 (31 x 40) or (60 x 170) 19 x 7, 4 x, or 34 x 36 (477 x 19, 119 x 731 or 974 x 914) NA 144 x 100 or x 0 (36 x 40 or 731 x 170) 100 x 3 (40 x 13) 144 x 36 (36 x 914) 6. ACTUATOR CONNECTIONS Electrical and/or pneumatic connections to damper actuators should be made in accordance with wiring and piping diagrams developed in compliance with applicable codes, ordinances and regulations. 7. CONNECTION AND OPERATION OF OPEN/CLOSE INDICATOR OCI - The OCI (open or closed indicator) option contains a single pole, double throw switch used to indicate the damper blade position. The switch provides a positive open or closed signal when used in conjunction with remote indicator lights. Refer to Fig. 1 for wiring of the OCI option. Fig. 1 OCI Wiring RATINGS Integral Switch Type: Single Pole, double throw Electrical: 10 Amps, 1 /3 hp, 10 or 40 Vac 1/ Amp, 10 Vdc; 1 /4 Amp 40 Vdc Amps, 10 Vac L (lamp load) 1.0 Amps, 4 Vac 1. Amps, 4 Vdc Ductwork Sealant Damper The damper sections must be attached together with #10 sheet metal screws, 1 /4 in. (6mm) diameter nuts and bolts, 1/ in. (13mm) long welds, or 3 /16 in. (mm) diameter steel pop rivets. 4 Duct Outlet Fig. Sealant 4 in. Max. Smoke Barrier

5 SMDR-XXX and SSSMDR-XXX Blade Orientation Axle Axle Axle 30 Off Horizontal (Maximum) 30 Off Horizontal (Maximum) Normal Damper Maintenance Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust. Damper actuator(s) must be maintained, cycled, and tested in accordance with: The latest editions of NFPA 90A, 9A, 9B, 10, UL64, AMCA and local codes. Actuator manufacturer recommendations. Damper Troubleshooting The following is a possible cause and correction list for common concerns with the dampers. Sympton Possible Cause Corrective Action Frame is 'racked' causing blades to bind Adjust frame such that it is square and plumb on jamb seals Actuator linkage loose Close damper, disconnect power, adjust and tighten linkage Damper does not fully open and/or close RRL or TOR sensor tripped Damper does not operate Defective motor Screws in damper linkage Contaminants on damper Heat No power supplied to the actuator Replace Damper installed too far into wall. Move out to line as designated on damper label Clean with a non-oil based solvent (see Damper Maintenance) Push reset button located on backside of RRL or TOR Add power supply Copyright 009 Greenheck Fan Corporation SMD-XXX Rev. 9 June 009

6 Refer to: Installation Instructions for SMD, SMDR and SSSMD Series Leakage Rated Smoke Dampers (Part #46133) or Installation Instructions for CFSD Series Corridor Ceiling Dampers (Part #46133) or Installation Instructions for CFSD, FSD, DFD, and SSFSD Series Combination Fire Smoke Dampers (Part #461336) and FSD-3XXV series (Part # ) for additional details. Notes 1. Mininum air velocity for smoke detector operation is 100 fpm (. m/s). Maximum is 4000 fpm (0.3 m/s).. Since the smoke detector is not rated for use at velocities below 00 fpm (. m/s), local code may require an alternate means of damper closure such as zone detection or automated damper closure when the system fan is shut down. The local authority having jurisdiction should be consulted prior to the installation of the damper and smoke detector. 3. Holes on sampling tube must face into airstream. 4. Smoke detector specifications are: Operating temperature range: 3 F to 131 F (- C to C) Operating humidity range: 10% to 93% R.H. Operation voltage: 4 VAC/DC or 10 VAC. Refer to System Sensor, D410 Installation and Maintenance Instructions for further installation details. 6. Refer to System Sensor, D410, Installation and Maintenance Instructions for maintenance and field tests. 7. System Sensor 3 Ohio Avenue St. Charles, Illinois Phone: 1-00-SENSOR Fax: Website: Part Number Installation Instruction Supplement for SMD, SMDR & SSSMD Series Smoke Dampers and FSD, FSD-3XXV & SSFSD Series Combination Fire Smoke Dampers and CFSD Series Corridor Ceiling Dampers with Factory Mounted Duct Smoke Detectors UL CLASSIFIED (see complete marking on product) UL CLASSIFIED to Canadian safety standards (see complete marking on product) Standard (Listing #R13317) Standard S (Listing #R13447) Figure 1: Smoke detector mounting orientation for dampers less than inches (63mm) in height. 6 Figure : Smoke detector mounting orientation for dampers equal to or greater than inches (63mm) in height.

7 A B C 9 10 A B C A B C A B C Wiring Diagrams Duct smoke detector Fusible Link 4 VAC/VDC 11 VAC SECOND THIRD 1. CONDUIT RUNS WHICH EXCEED 7" MUST HAVE GREEN GROUND WIRE.. FLEX CONDUIT MUST BE SECU WITH A CONDUIT CLAMP (496) WITHIN 1" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE SECU ALONG SLEEVE AT A MAXIMUM OF 4" ON CENTER. OCI THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A WIRE MARKER (3169). OCI 4 VAC/VDC 11 VAC SECOND THIRD 1. CONDUIT RUNS WHICH EXCEED 7" MUST HAVE GREEN GROUND WIRE.. FLEX CONDUIT MUST BE SECU WITH A CONDUIT CLAMP (496) WITHIN 1" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE SECU ALONG SLEEVE AT A MAXIMUM OF 4" ON CENTER. 7

8 A B C 9 10 A B C A B C A B C Wiring Diagrams Duct smoke detector RRL RRL 4 VAC/VDC 11 VAC SECOND THIRD 1. CONDUIT RUNS WHICH EXCEED 7" MUST HAVE GREEN GROUND WIRE.. FLEX CONDUIT MUST BE SECU WITH A CONDUIT CLAMP (496) WITHIN 1" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE SECU ALONG SLEEVE AT A MAXIMUM OF 4" ON CENTER. RRL/OCI THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A WIRE MARKER (3169). RRL 4 VAC/VDC 11 VAC SECOND THIRD 1. CONDUIT RUNS WHICH EXCEED 7" MUST HAVE GREEN GROUND WIRE.. FLEX CONDUIT MUST BE SECU WITH A CONDUIT CLAMP (496) WITHIN 1" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE SECU ALONG SLEEVE AT A MAXIMUM OF 4" ON CENTER.

9 A B C 9 10 A B C A B C A B C Wiring Diagrams Duct smoke detector TOR THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A WIRE MARKER (3169). TOR 4 VAC/VDC SWITCHING DEVICE (BY OTHERS) BROWN (OVERRIDE) (PRIMARY) 11 VAC SECOND THIRD 1. CONDUIT RUNS WHICH EXCEED 7" MUST HAVE GREEN GROUND WIRE.. FLEX CONDUIT MUST BE SECU WITH A CONDUIT CLAMP (496) WITHIN 1" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE SECU ALONG SLEEVE AT A MAXIMUM OF 4" ON CENTER. OCI w/ EP switch THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A WIRE MARKER (3169). OCI 4 VAC/VDC 11 VAC SECOND THIRD 1. CONDUIT RUNS WHICH EXCEED 7" MUST HAVE GREEN GROUND WIRE.. FLEX CONDUIT MUST BE SECU WITH A CONDUIT CLAMP (496) WITHIN 1" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE SECU ALONG SLEEVE AT A MAXIMUM OF 4" ON CENTER. 9

10 A B C 9 10 A B C A B C A B C A B C Wiring Diagrams Duct smoke detector RRL/OCI w/ EP switch THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A WIRE MARKER (3169). DH100ACDCLP DUCT DETECTOR RRL 4 VAC/VDC DH100ACDCLP DUCT DETECTOR 11 VAC DH100ACDCLP DUCT DETECTOR SECOND 0/40 VAC THIRD 1. CONDUIT RUNS WHICH EXCEED 7" MUST HAVE GREEN GROUND WIRE.. FLEX CONDUIT MUST BE SECU WITH A CONDUIT CLAMP (496) WITHIN 1" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE SECU ALONG SLEEVE AT A MAXIMUM OF 4" ON CENTER. RRL w/ EP switch RRL 4 VAC/VDC 11 VAC SECOND THIRD 1. CONDUIT RUNS WHICH EXCEED 7" MUST HAVE GREEN GROUND WIRE.. FLEX CONDUIT MUST BE SECU WITH A CONDUIT CLAMP (496) WITHIN 1" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE SECU ALONG SLEEVE AT A MAXIMUM OF 4" ON CENTER. 10

11 A B C A B C Wiring Diagrams Duct smoke detector TOR w/ EP switch THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A WIRE MARKER (3169). TOR 4 VAC/VDC SWITCHING DEVICE (BY OTHERS) BROWN (OVERRIDE) (PRIMARY) 11 VAC SECOND THIRD 1. CONDUIT RUNS WHICH EXCEED 7" MUST HAVE GREEN GROUND WIRE.. FLEX CONDUIT MUST BE SECU WITH A CONDUIT CLAMP (496) WITHIN 1" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE SECU ALONG SLEEVE AT A MAXIMUM OF 4" ON CENTER. Figure 3: Label applied to dampers with factory mounted duct smoke detectors. 11 Copyright 009 Greenheck Fan Corporation Smoke Detector IOM Rev 6 Feb 009

12 Refer to: Installation Instructions for SMD, SESMD, and SSSMD Series Leakage Rated Smoke Dampers (Part #46133) or Installation Instructions for CFSD, FSD, DFD, SEFSD, SSFSD Series Combination Fire Smoke Dampers and (Part#461336) and FSD-3XXV series (Part #461666) for additional details Part number 4691 Installation Instruction Supplement for SMD, SESMD, & SSSMD Series Smoke Dampers and FSD, FSD-3XXV, SEFSD, & SSFSD Series Combination Fire Smoke Dampers with Factory Mounted No Flow Duct Smoke Detectors NOTES 1. Minimum air velocity for smoke detector operation is 0 fpm. Maximum is 3000 fpm.. Model 11 low profile smoke detector is mounted to a standard electrical box within the duct. The twist-in/ twist-out head allows easy removal from the base for quick cleaning and maintenance. 3. Smoke detector specifications are: Operating temperature rating: 3 F to 10 F (0 C to 49 C) Operating humidity range: 10% to 93% RH Operation voltage: 10 VAC 4. Refer to System Sensor, 11, Installation and Maintenance Instructions for further installation details.. Refer to System Sensor, 11, Installation and Maintenance Instructions for maintenance and field tests. 6. System Sensor 3 Ohio Avenue St. Charles, IL Phone: Fax: Website: UL CLASSIFIED (see complete marking on product) UL CLASSIFIED to Canadian safety standards (see complete marking on product) Standard (Listing #R13317) Standard S (Listing # R13447) #10 TEK SCREW 4 X 4 X 1/ HANDI BOX SMOKE DETECTOR ASSEMBLY 1

13 Wiring Diagrams RRL RRL OCI 6 7 TOR SWITCHING DEVICE (BY OTHERS) BROWN (OVERRIDE) (PRIMARY) RRL/OCI OCI RRL/OCI TOR

14 Wiring Diagrams with EP Switch RRL RRL 6 7 OCI 6 7 TOR SWITCHING DEVICE (BY OTHERS) BROWN (OVERRIDE) (PRIMARY) OCI OCI RRL/OCI TOR Copyright 006 Greenheck Fan Corporation 4691 No Flow Smoke Detector IOM Rev. 3 November 006

15 Part number 460 Duct-Sleeve Connection INSTALLATION INSTRUCTION SUPPLEMENT Refer to: Installation Instructions for FD, DFD, SSFD, & KFD Series (Part number 4763) or Installation Instructions for FSD-XXX, DFD-XXX, SSFSD-XXX & CFSD-XXX Series Fire & Combination Fire Smoke Dampers (Part number ) or Installation Instructions for FD & DFD 10X Series Curtain Fire Dampers (Part number 43946) or Installation Instructions for OFSD, ODFD, OFD, AND OSSFD Series Dampers (Part number ) or Installation Instructions for FSD-3XXXV Series Dampers (Part number ) for additional details UL CLASSIFIED (see complete marking on product) UL CLASSIFIED to Canadian safety standards (see complete marking on product) Standards UL & S Classifications Filed at UL under Listing #R13317 These instructions describe an alternate breakaway connection between a fire damper or combination fire smoke damper sleeve and an adjoining piece of ductwork. This alternate connection is covered under the UL certification of the damper. These instructions apply to a connection between a manufactured flange system by Ductmate, Ward, or Nexus and a TDC or TDF flange system. 1. Install the manufactured flange system onto the damper sleeve per the manufacturer s instructions.. To seal the two flange systems together Neoprene or Butyl gasket may be applied to the mating surfaces. 3. Align the two flange systems together. An optional 3/ in. (9mm) bolt may be used in the corners to help with the alignment. These bolts do not have to be removed. 4. Install the metal cleat (see Figure 1) or #10 tek screw (see Figure ), approximately equally spaced, per the schedule described below: Width or height less than 4 in. (610mm); use one cleat or screw per side Width or height 4 in. (610mm) to less than 36 in. (914mm); use cleats or screws per side Width or height 36 in. (914mm) to less than 4 in. (137mm); use 3 cleats or screws per side Width or height 4 in. (137mm) to less than 7 in. (19mm); use 4 cleats or screws per side Width or height 7 in. (19mm) or greater; use cleats or screws per side. Metal cleat #10 x 3/4 TEK Screw TDC or TDF Connection Spot weld or Tek screw per manufacturer instructions TDC or TDF Connection Spot weld or Tek screw per manufacturer instructions Butyl Gasket Damper Sleeve Butyl Gasket Damper Sleeve Figure 1 Figure 1 Copyright 007 Greenheck Fan Corporation 460 Breakaway connection Rev. 3 December 007

16 Refer to: Installation Instructions for FD, DFD, SSFD, SSDFD, & KFD Series Curtain Fire Dampers (Part #4763) or Installation Instructions for FD and DFD 10X Series Curtain Fire Dampers (Part #43946) or Installation, Operation and Maintenance Instructions for SMD-XXX, SESMD-XXX, SSSMD-XXX Series Smoke Dampers (Part #46133) or Installation, Operation and Maintenance Instructions for FSD-XXX, SSFSD-XXX, DFD-XX, & CFSD-XXX Series Fire & Combination Fire Smoke Dampers (Part #461336) for additional details. Part number Drive Slip Breakaway Connection INSTALLATION INSTRUCTION SUPPLEMENT UL CLASSIFIED (see complete marking on product) UL CLASSIFIED to Canadian safety standards (see complete marking on product) Standards UL & S Classifications Filed at UL under Listing #R13317 S-slip Sleeve Greenheck drive slip connections (S & Drive) are used on the side of the hemmed sleeves and the S-slip joints are used on the top and bottom. Standard drive slips are UL tested breakaway connections on dampers 0 in. (0mm) high and less. Installation Greenheck Dampers may be supplied with factory hemmed 0 ga. (1mm) sleeve for use with drive slip and s-slip joints. Sleeves and duct may be field hemmed by folding back the vertical sides a maximum of 1/ in. (13mm) (as shown in Figure 1) to accommodate the 1 in. (mm) wide drive slip. Join damper sleeve to duct at top and bottom sides using any S-slip (See Figure ). Drive slip connection is used to connect the vertical sides of the damper sleeve to the duct. Cut a length of drive slip connection a maximum of 4 in. (10mm) longer than the vertical duct dimension. Guide the drive slip connection onto the side members securing it over the hemmed edges until the connection extends beyond the top and bottom sides of the damper sleeve/ duct. The extra length should be hammered flat overlapping all four corners. Figure 1 Duct Drive slip S-slip Duct Sleeve Top and Bottom Duct to Sleeve Connection Figure Figure 3 Copyright 007 Greenheck Fan Corporation #46769 Drive Slip Breakaway Connection Rev. December

17 Refer to: Installation Instructions for SMD, SESMD, SSSMD, SMDR, SESMDR, and SSSMDR series Models (Part #) for additional details. UL CLASSIFIED (see complete marking on product) UL CLASSIFIED to Canadian safety standards (see complete marking on product) Standards UL & S Classifications Filed at UL under Listing #R13317 Part number Flange Mounted Installation INSTALLATION INSTRUCTION SUPPLEMENT SMD-xxx, SESMD-xxx, SSSMD-xxx Series Smoke Dampers 1. SMOKE DAMPER REQUIREMENTS AND APPLICATION Smoke dampers are required to close and prevent the passage of air and smoke through ducts or ventilation openings in smoke barriers. Smoke dampers are also applied in engineered smoke control systems to establish air pressure differentials and thereby prevent the spread of smoke. These dampers are designed to operate with blades running horizontally. Dampers can be vertically or horizontally installed at, in accordance with NFPA-90A, or adjacent to the point where the duct passes thru the smoke barrier.. LOCATION OF DAMPER IN DUCTWORK Place the damper assembly in its proper position relative to the barrier. The plane of the closed damper blades must be within 4 in. (610mm) of the rated smoke barrier and before any duct inlets or outlets. 3. ATTACHING DAMPER TO THE DUCT The damper is flange mounted to the duct, sleeve, or wall opening with using #10 sheet metal screws, 1/4 in. (6mm) diameter bolts and nuts, tack or spot welds, or 3/16 in. (mm) diameter steel pop rivets. Attachments must be made at each flange spaced a maximum of 6 in. (1mm) on centers and a maximum of in. (1mm) from corners. 4. SEALING THE INSTALLATION The following duct sealants may be used to seal between the dampers flange and the mating surface: PA04T duct sealant adhesive manufactured by Precision, DP1010 water base duct sealant manufactured by Design Polymetrics, Grey Pookie or Ductmate PROseal in accordance with SMACNA recommendations.. ACTUATOR CONNECTIONS Electrical and/or pneumatic connections to damper actuators should be made in accordance with wiring and piping diagrams developed in compliance with applicable codes, ordinances and regulations. 17 Damper model SMD-301, 30 SMD-301M, 30M SMD-401 SMD-401M Maximum Single Section Size in. (mm) 3 x 0 (13 x 170) 3 x 0 (13 x 170) 4 x 60 (119 x 731) 4 x 36 (119 x 914) Maximum Overall Size for Multiple Section Dampers in. (mm) 1 x 100 or 6 x 0 (31 x 40) or (60 x 170) 1 x 100 or 6 x 0 (31 x 40) or (60 x 170) 19 x 7, 4 x, or 34 x 36 (477 x 19, 119 x 731 or 974 x 914) 144 x 36 (36 x 914)

18 3 4 1 Item Description 1. Damper frame. Duct outlet 3. Fan (not limited to centrifugal) 4. #10 sheet metal screws. Actuator The actuators are to be installed to function per system requirements and to be controlled by smoke detection devices. FAN ISOLATION APPLICATION For air handling equipment isolation, leakage rated dampers are designed to operate with blades running horizontally. Dampers can be installed in a vertical or horizontal position. Sealants and damper seal materials meet the requirements of NFPA90A for smoke developed rating (<0) and flame spread index (<) as tested per UL73/ ASTME4-91A/NFPA. Dampers can be attached to the fan system discharge or inlet without being 4 in. (610mm) of a smoke barrier when used as an air handling equipment isolation damper. 1 Copyright 009 Greenheck Fan Corporation Double Flange SMD Rev. 1 June 009

19 DATE NOTES 19

20 Copyright 010 Greenheck Fan Corporation August 010

DUCT SMOKE DETECTOR D4120

DUCT SMOKE DETECTOR D4120 Purpose/Application National and local safety standards and codes recognize the ability of air duct systems to transfer smoke, toxic gases, and flame from area to area. Sometimes smoke can be of such quantity

More information

Life Safety Dampers Selection and Application Manual

Life Safety Dampers Selection and Application Manual Life Safety Dampers Selection and Application Manual Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers August 2016 1 2 Table of Contents HOW TO USE THIS MANUAL DAMPER

More information

Duct Smoke Detector - D4120

Duct Smoke Detector - D4120 Application The primary purpose of duct smoke detection is to prevent injury, panic, and property damage by reducing the spread (recirculation) of smoke. The detector samples air currents passing through

More information

Fire, Smoke, and Combination Fire Smoke Dampers

Fire, Smoke, and Combination Fire Smoke Dampers Fire, Smoke, and Combination Fire Smoke Dampers Mark Belke Director Damper Products-Greenheck Chairman of Code Action Review Committee (CARC) California Building Code work group NFPA 80A, 90A, 92B, 101,

More information

Tunnel Transit Dampers. Heavy Duty Tunnel Transit Life Safety

Tunnel Transit Dampers. Heavy Duty Tunnel Transit Life Safety Tunnel Transit Dampers Heavy Duty Tunnel Transit Life Safety November 2011 Heavy Duty/Industrial Tunnel Dampers Applications Dampers in subway tunnels and transit systems serve three primary functions,

More information

Louvers & Dampers April Product Guide Specification SECTION COMBINATION FIRE SMOKE DAMPERS

Louvers & Dampers April Product Guide Specification SECTION COMBINATION FIRE SMOKE DAMPERS Louvers & Dampers April 2008 P.O. Box 606 7435 Industrial Road Florence, Kentucky, 41042 Phone: (859) 647-2299 Fax: (859) 647-7810 Web Site: www.louvers-dampers.com Product Guide Specification SECTION

More information

Tunnel Transit Dampers Heavy Duty Tunnel Transit Life Safety

Tunnel Transit Dampers Heavy Duty Tunnel Transit Life Safety Tunnel Transit Dampers Heavy Duty Tunnel Transit Life Safety November 2017 Heavy Duty/Industrial Tunnel Dampers Applications Dampers in subway tunnels and transit systems serve three primary functions,

More information

FIRE & SMOKE DAMPERS. Meeting tomorrow's requirements for fire and smoke protection today.

FIRE & SMOKE DAMPERS. Meeting tomorrow's requirements for fire and smoke protection today. FIRE & SMOKE DAMPERS Meeting tomorrow's requirements for fire and smoke protection today. LATEST TECHNOLOGY For more than 40 years Ruskin has led the HVAC industry in the manufacture of dampers and louvers.

More information

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems 233100 AIR DISTRIBUTION PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 230700 HVAC Insulation B. Section 237300 Air Handling C. Section 230900 Building Automation and Control System Guidelines D. Section

More information

SMOKE DAMPERS SMOKE DAMPERS

SMOKE DAMPERS SMOKE DAMPERS MODEL SERIES 1210SS AIROIL BLADE STAINLESS STEEL Model Series 1210SS Stainless Steel Airfoil Blade Smoke Dampers are ideal for high humidity, mildly corrosive or, with optional Type 316 construction, more

More information

SMOKE DAMPERS AIRFOIL STAINLESS STEEL

SMOKE DAMPERS AIRFOIL STAINLESS STEEL MODEL SERIES 1210M AIROIL BLADE MODULATING ACTUATOR Model Series 1210M Modulating Smoke Dampers are classified for use as a volume control damper in applications where building codes require a leakage

More information

SECTION AIR DUCT ACCESSORIES

SECTION AIR DUCT ACCESSORIES SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control

More information

Part # Page Dampers Supported Directly From Structure 5. Dampers Supported From Ductwork Above 4

Part # Page Dampers Supported Directly From Structure 5. Dampers Supported From Ductwork Above 4 Part #453343 INSTALLATION INSTRUCTIONS DAMPERS AND LOUVERS CRD Series s These installation instructions apply to 3 hour rated ceiling radiation dampers mounted in a ceiling with supports from 1) a ceiling

More information

Fire, Smoke and Control Dampers

Fire, Smoke and Control Dampers MANUAL Fire, Smoke and Control Dampers v100 Issue Date: 04/02/15 2015 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Maintenance, Testing and Inspection Recommendations Recommended Maintenance

More information

AIR DUCT ACCESSORIES

AIR DUCT ACCESSORIES SECTION 233300 - PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Modular Supply Make-Up Air Unit

Modular Supply Make-Up Air Unit Modular Supply Make-Up Air Unit Model MSX Flexible Design Factory Assembled Heating Options Hot Water Steam Electric Cooling Options Evaporative Direct Expansion Chilled Water November 2009 Product Features

More information

CLe-series Dishwashers

CLe-series Dishwashers CLe-series Dishwashers Blower-dryer electric (CLe SERIES) ML-138211 ML-138212 ML-138213 ML-138214 electric (CLeR SERIES) ML-138325 ML-138326 ML-138327 ML-138328 STEAM (CLe SERIES) ML-138226 ML-138227 ML-138228

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

COMBINATION FIRE/SMOKE DAMPERS

COMBINATION FIRE/SMOKE DAMPERS MODEL 1221-DOW (1 1/2 HR.) AIRFOIL BLADE OUT OF WALL DUCTED BOTH SIDES The Model 1221-DOW combination fire/smoke damper is specially designed for "out of wall" (vertical mount) or "out of floor" (horizontal

More information

SECTION DUCTWORK. A. Section Painting: Weld priming, weather resistant, paint or coating.

SECTION DUCTWORK. A. Section Painting: Weld priming, weather resistant, paint or coating. SECTION 15890 DUCTWORK PART 1 - GENERAL 1.1 SECTION INCLUDES A. Metal ductwork. B. Duct cleaning. 1.2 RELATED SECTIONS A. Section 09900 - Painting: Weld priming, weather resistant, paint or coating. B.

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Replacement of pneumatic actuators on Ruskin negator spring dampers with Belimo FSxx Series

Replacement of pneumatic actuators on Ruskin negator spring dampers with Belimo FSxx Series WARNING! Before replacing actuator, damper must be inspected and determined to be fully functional. See NFPA checklists below. Contents Replacement of pneumatic actuators on Ruskin negator spring dampers

More information

Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering

Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015 Peter McDonnell, PE, LEED AP BD+C McClure Engineering UL DAMPER TEST STANDARDS UL 555 - FIRE DAMPERS UL555S SMOKE DAMPERS UL555C CEILING

More information

WARNING! Before replacing actuator, damper must be inspected and determined to be fully functional.

WARNING! Before replacing actuator, damper must be inspected and determined to be fully functional. WARNING! Before replacing actuator, damper must be inspected and determined to be fully functional. Greenheck Dampers with MultiProducts, Siebe, Siemens, or Honeywell Motors Replacement with Belimo FSLF,

More information

MPA Modular Plenum Array Installation, Operation, and Maintenance Manual

MPA Modular Plenum Array Installation, Operation, and Maintenance Manual MPA Modular Plenum Array Installation, Operation, and Maintenance Manual This publication contains the installation, operation and maintenance procedures for standard units of the MPA: Modular Plenum Array.

More information

WHEN IT COMES TO FIRE / SMOKE DAMPERS, NAILOR S 1220 SERIES THE WALL PROVIDES THE ULTIMATE CLOSURE!

WHEN IT COMES TO FIRE / SMOKE DAMPERS, NAILOR S 1220 SERIES THE WALL PROVIDES THE ULTIMATE CLOSURE! MODEL SERIES 1220SS (1 1/2 HR.) AND 1220SS-3 (3 HR.) AIRFOIL BLADE STAINLESS STEEL Model Series 1220SS and 1220SS-3 Combination Fire/Smoke Dampers are ideal for high humidity, mildly corrosive environment

More information

COMBINATION FIRE/SMOKE DAMPERS

COMBINATION FIRE/SMOKE DAMPERS MODEL SERIES 1270 (1 1/2 HR.) VEE ROOVE BLADE Model Series 1270 combination fire/smoke dampers, with sturdy veegroove style blades and a rugged mitered corner hat channel frame design that virtually eliminates

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS PART # 538 Model BCF Belt Drive Centrifugal Cabinet Fans Installation, Operation, and Maintenance Manual Please read and save these instructions for future reference. Read

More information

WHEN IT COMES TO FIRE / SMOKE DAMPERS, NAILOR S 1220 SERIES THE WALL PROVIDES THE ULTIMATE CLOSURE!

WHEN IT COMES TO FIRE / SMOKE DAMPERS, NAILOR S 1220 SERIES THE WALL PROVIDES THE ULTIMATE CLOSURE! ENERAL PRODUCT OVERVIEW As today s modern commercial and industrial building construction becomes increasingly life safety oriented, fire containment and active smoke management systems are being utilized

More information

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP)

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) Our Expertise, Your Air-Moving Solution ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) PART# 0601710001_rev_A INSTALLATION, OPERATION & MAINTENANCE MANUAL Please read and save these instructions for future reference.

More information

FAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design

FAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design FAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design Fan motor (PSC or ECM). UL Listed 1 insulation conforms to UL Test 181 and NFPA 90A. Plenum air filter rack. (Filter Optional) Casing has

More information

I-VICFLEX.AB4. Victaulic VicFlex Style AB4 Sprinkler Fitting for Hat Furring Channel Ceiling Systems WARNING INSTALLATION INSTRUCTIONS

I-VICFLEX.AB4. Victaulic VicFlex Style AB4 Sprinkler Fitting for Hat Furring Channel Ceiling Systems WARNING INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS I-VICFLEX.AB Victaulic VicFlex Style AB Sprinkler Fitting for Hat Furring Channel Ceiling Systems Read and understand all instructions before attempting to install any Victaulic

More information

VSR-M REPLACEMENT Waterflow Switch for Globe Sprinkler Model UMC Manifold

VSR-M REPLACEMENT Waterflow Switch for Globe Sprinkler Model UMC Manifold Features NEMA 4 solid metal enclosure Factory installed neoprene gasket 0-90 second field replaceable pneumatic retard 350 PSI system pressure rated Synchronized switch action Waterflow switches that are

More information

ELECTRIC COOKTOP INSTALLATION INSTRUCTIONS

ELECTRIC COOKTOP INSTALLATION INSTRUCTIONS INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER. IMPORTANT: SAVE FOR LOCAL ELECTRICAL INSPECTOR'S USE. READ AND SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE. U.S.A. WARNING FOR YOUR

More information

COMBINATION FIRE/SMOKE DAMPERS

COMBINATION FIRE/SMOKE DAMPERS MODEL SERIES 1270 (1 1/2 HR.) VEE ROOVE BLADE Model Series 1270 combination fire/smoke dampers, with sturdy veegroove style blades and a rugged mitered corner hat channel frame design that virtually eliminates

More information

SECTION Overhead Coiling Doors

SECTION Overhead Coiling Doors SECTION 08 33 00 Overhead Coiling Doors To display hidden notes to specifier, select tools/ options/ view/ hidden text. GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,

More information

WARNING! Before replacing actuator, damper must be inspected and determined to be fully functional. See NFPA 80 & NFPA 105 below for recommendations.

WARNING! Before replacing actuator, damper must be inspected and determined to be fully functional. See NFPA 80 & NFPA 105 below for recommendations. WARNING! Before replacing actuator, damper must be inspected and determined to be fully functional. See NFPA 80 & NFPA 105 below for recommendations. Replacement of Honeywell ML & MS motors to Belimo FS

More information

COMBINATION FIRE/SMOKE DAMPERS

COMBINATION FIRE/SMOKE DAMPERS MODEL SERIES 1270 (1 1/2 HR.) VEE ROOVE BLADE Model Series 1270 combination fire/smoke dampers, with sturdy veegroove style blades and a rugged mitered corner hat channel frame design that virtually eliminates

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended

More information

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Construction Standards Page 233423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified

More information

ACT Cartridge Dust Collector

ACT Cartridge Dust Collector IOM-101-1 ACT Cartridge Dust Collector Installation and Operation Manual ACT Dust Collectors CAUTION! Accidents happen, be careful and always follow all local and federal regulations! Fires and explosions

More information

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

A. Section Common Motor Requirements for HVAC Equipment: Fan motors. SECTION 233516 - ENGINE EXHAUST SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Exhaust fans. B. Ductwork and duct fittings. C. Inlet fittings. D. Accessories. E. Carbon monoxide detectors. 1.2 RELATED

More information

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART # INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #238-39387-00 THIS INSTRUCTION SUPPLEMENT IS ONLY INTENDED TO GIVE INSTALLATION INSTRUCTIONS AND INFORMATION RELATED TO THE INDUCED

More information

MNEFDD54 & MNBCDD54 GALVANIZED WALL FANS Installation, Operation, and Maintenance Instructions

MNEFDD54 & MNBCDD54 GALVANIZED WALL FANS Installation, Operation, and Maintenance Instructions FARM PRODUCTS DIVISION MEMBER OF AMCA AMERICAN COOLAIR CORPORATION P.O. BOX 2300 JACKSONVILLE, FLORIDA 32203 PHONE (904) 389-3646 FAX (904) 387-3449 E-MAIL - fans@coolair.com MNEFDD54 & MNBCDD54 GALVANIZED

More information

INSTRUCTION SHEET - Replacement of Ruskin Phillips P150 to Belimo FSNF or FSAF Actuator

INSTRUCTION SHEET - Replacement of Ruskin Phillips P150 to Belimo FSNF or FSAF Actuator WARNING! Before replacing actuator, damper must be inspected and determined to be fully functional. INSTRUCTION SHEET - Replacement of Ruskin Phillips P150 to Belimo FSNF or FSAF Actuator Contents UL...

More information

OCH-SS series Direct Wired Units Indoor * and Outdoor Comfort Heaters

OCH-SS series Direct Wired Units Indoor * and Outdoor Comfort Heaters 1200 North Main Street Fostoria, OH 44830 Phone: 800-495-4525 Fax: 419-435-0842 A DIVISION OF www.fostoriaindustries.com OCH-SS series Direct Wired Units Indoor * and Outdoor Comfort Heaters *EXCLUDING

More information

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2 I&M NUMBER: 316-42-15-1 Page: 1 _ Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL SWP (Models SWP08 through SWP20) OPERATION & MAINTENANCE MANUAL IMPORTANT! Read before proceeding! Read carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT

More information

SECTION DUCTWORK

SECTION DUCTWORK SECTION 15890 DUCTWORK PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 07270 - Firestopping and Fire and Smoke Barrier Caulking. 2. 15260 - Vibration Isolation. 3. 15280 - Thermal Insulation (HVAC).

More information

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description Technical Services 800-381-9312 +1-401-781-8220 www.tyco-fire.com Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description The TYCO Model ESFR-17 Dry

More information

Replacement of Safe-Air Honeywell ML & MS Motors with Belimo FSNF120 Series

Replacement of Safe-Air Honeywell ML & MS Motors with Belimo FSNF120 Series WARNING! Before replacing actuator, damper must be inspected and determined to be fully functional. See NFPA 80 & NFPA 105 below for checklist. Replacement of Safe-Air Honeywell ML & MS Motors with Belimo

More information

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete wet chemical automatic fire suppression system for the exhaust hood, including necessary

More information

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete automatic fire suppression system for the exhaust hood, including necessary accessories.

More information

CAR-MON DUST COLLECTORS SERIES 207, 2410, 3015

CAR-MON DUST COLLECTORS SERIES 207, 2410, 3015 INSTALLATION-OPERATION-MAINTENANCE CAR-MON DUST COLLECTORS SERIES 207, 2410, 3015 TEFC 3 phase motor Outlet duct Fan wheel housing Inlet duct connection After filter transition Optional after filter unit

More information

TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range

TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range 825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 60-77-6495

More information

MODEL CDB8 INSTALLATION INSTRUCTIONS

MODEL CDB8 INSTALLATION INSTRUCTIONS REV 0417 TJERNLUND PRODUCTS, INC. 1601 Ninth Street White Bear Lake, MN 55110-6794 PHONE (800) 255-4208 (651) 426-2993 FAX (651) 426-9547 Visit our web site www.tjernlund.com SUITABLE FOR SIDE WALL OR

More information

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

"S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16

S SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16 Webster Pumps "S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16 PLEASE READ THE FOLLOWING INFORMATION PRIOR TO INSTALLING AND USING Webster PUMPS or HAYWARD VALVES,

More information

FAN POWERED VAV TERMINALS

FAN POWERED VAV TERMINALS FAN POWERED VAV TERMINALS Models VFR, CFR and CFRQ INSTALLATION, OPERATION AND MAINTENANCE MANUAL All data herein is subject to change without notice. Refer to www.enviro-tec.com for current catalog data

More information

DBF 4XL Dryer Booster Fans

DBF 4XL Dryer Booster Fans Installation and Operation Manual Item #: 401315 Rev Date: 050814 DBF 4XL Dryer Booster Fans DBF4XL Kit Includes: Dryer Booster Fan, 1 pc Fan Mounting Bracket and Hardware, 1 pc Wall Label (Mount on wasll

More information

SeasonMaker Hi-Line Fan-coil Unit Model HSS S30 through S80

SeasonMaker Hi-Line Fan-coil Unit Model HSS S30 through S80 Installation & Maintenance Data IM 255-6 SeasonMaker Hi-Line Fan-coil Unit Model HSS S30 through S80 Group: Fan coil Part Number: # 106332400 Date: August 2000 Table of Contents Inspection............................................................................

More information

OWNER S MANUAL MODEL BW4B SLICER WARMER

OWNER S MANUAL MODEL BW4B SLICER WARMER Model BW4B PRODUCT DESCRIPTION The Model BW4B slicer/warmer holds meat on the slicer at or above the minimum required temperature as mandated by food safety codes. The Slicer Warmer is designed to be bolted

More information

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 800-736/7672, FAX: 630-377-6495 Before

More information

WATLOW IND. WATROD Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2.00

WATLOW IND. WATROD Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2.00 I&M NUMBER: 316-42-8-1 Page: 1 _ Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

Modular Heating & Ventilating Unit Model IGX-HV

Modular Heating & Ventilating Unit Model IGX-HV Modular Heating & Ventilating Unit Model IGX-HV Indirect Gas-Fired Heating Evaporative Chilled Water DX Cooling October 2008 Product Features Model IGX-HV Indirect Gas-Fired Heating and Ventilating Unit

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Ventilating Fan Representative models: Model No. FV-0511VQ1 FV-0511VQC1 FV-0511VQ1 Contents GENERAL SAFETY INFORMATION --------------2~3 DESCRIPTION ----------------------------------------4

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 464664 Model AX Axial Fan Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate

More information

WATLOW IND. FIREBAR Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

WATLOW IND. FIREBAR Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00 I&M NUMBER: 316-42-2-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to elements

More information

DIRECT DRAW BEER COOLERS Installation, Operation and Maintenance Instructions

DIRECT DRAW BEER COOLERS Installation, Operation and Maintenance Instructions DIRECT DRAW BEER COOLERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the Bill of Lading to ensure all crates

More information

M Series Fan Filter Units

M Series Fan Filter Units M Series Fan Filter Units Product Specifications... 2 Safety Instructions... 3 Receiving and Unpacking... 3 Pre-Installation Instructions... 3-4 Installation Instructions... 4 Electrical Installation Instructions...

More information

DH100LP Air Duct Smoke Detector with Extended Air Speed Range

DH100LP Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS DH100LP Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 The Innovair DH100LP

More information

1-300 Fire and/or Smoke Dampers to Inspect $ Fire and/or Smoke Dampers to Inspect $34.30

1-300 Fire and/or Smoke Dampers to Inspect $ Fire and/or Smoke Dampers to Inspect $34.30 Life Safety Services, LLC TXMAS Schedule Contract Number: TXMAS-12-03FAC030 Passive Fire Protection Services Authorized Federal Supply Schedule Price List Quantity of Dampers to Inspect Per Damper to Survey

More information

Field Start-Up Sheet Direct Fired Gas Equipment

Field Start-Up Sheet Direct Fired Gas Equipment Customer: Sales Representative: Model Number: Serial Number: Field Start-Up Sheet Direct Fired Gas Equipment ***Please Print*** INITIAL INSPECTION I. Installer Responsibilities 1. Remote Panel: All interconnecting

More information

Installation & Maintenance Instructions

Installation & Maintenance Instructions Installation & Maintenance Instructions Listed & Tested to UL641, ULC-S609, ULC/ORD C441 AMERIVENT Model PVP Pellet Pipe Plus Vent Connector for Pellet-Fuel Appliances and Other Low-Temperature Applications

More information

DH400 Air Duct Smoke Detector

DH400 Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS DH400 Air Duct Smoke Detector Before Installing Please thoroughly read System Sensor s Guide for Proper Use of Smoke Detectors in Duct Applications (I56-473-XX),

More information

Installation, Operation & Service Manual

Installation, Operation & Service Manual Installation, Operation & Service Manual WARNING Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and

More information

HUMIDITY SENSING BATH FAN

HUMIDITY SENSING BATH FAN HUMIDITY SENSING BATH FAN MODEL VFB070B3H / SLM70H TABLE OF CONTENTS Package Contents General Safety Information 3 Preparation and Wiring Diagrams 4 Assembly Instructions - New Construction 5 Assembly

More information

WARNING. Flexible Hose AH2 With AB6 With AB6. AH2-CC With AB6 With AB6

WARNING. Flexible Hose AH2 With AB6 With AB6. AH2-CC With AB6 With AB6 INSTALLATION INSTRUCTIONS I-VICFLEX. Victaulic VicFlex Sprinkler Fittings: Style Bracket Assembly with Models V33,, or V40 Dry Sprinklers Read and understand all instructions before attempting to install

More information

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 800/736-7672, FAX: 630-377-6495 www.systemsensor.com

More information

BESF Box Ventilator. Installation & Operating Manual USA CAN READ AND SAVE THESE INSTRUCTIONS

BESF Box Ventilator. Installation & Operating Manual USA CAN READ AND SAVE THESE INSTRUCTIONS Installation & Operating Manual 3001806 03.02 USA CAN BESF Box Ventilator READ AND SAVE THESE INSTRUCTIONS 1200 Northmeadow Parkway, STE 180 Roswell, GA 30076 (770) 587-3238 (800) 255-2923 Fax (770) 587-4731

More information

Series SFN Unbraided Flexible Hose Assemblies Series SFB Braided Flexible Hose Assemblies

Series SFN Unbraided Flexible Hose Assemblies Series SFB Braided Flexible Hose Assemblies Series SFN Unbraided Flexible Hose Assemblies Series SFB Braided Flexible Hose Assemblies SprinkFLEX Stainless Steel Sprinkler Fittings connect the branch line to the sprinkler using a flexible stainless

More information

AeroVent 3X Product Manual

AeroVent 3X Product Manual Product Manual AeroVent 3X TABLE OF CONTENTS Precautionary Warning... Page 1 Assembly... Page 2 Assembly Drawing... Page 3 Parts List... Page 3 Operation... Page 4 Maintenance... Page 5 Cobalt Point Replacement...

More information

SECTION (15820) - AIR DUCT ACCESSORIES

SECTION (15820) - AIR DUCT ACCESSORIES PART 1 GENERAL 1.01 SUMMARY A. Section includes: SECTION 23 33 00 (15820) - AIR DUCT ACCESSORIES 1. Manual-Volume Dampers 2. Fire Dampers 3. Turning Vanes 4. Duct-Mounted Access Doors 5. Flexible Connectors

More information

DH100ACDCI Ionization Air Duct Smoke Detector

DH100ACDCI Ionization Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS Ionization Air Duct Smoke Detector Before Installing Please thoroughly read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Applications (A05-1004),

More information

INSTRUCTION MANUAL. AlarmGard Chain Operator (Model FCA) AlarmGard Crank Operator (Model FKA)

INSTRUCTION MANUAL. AlarmGard Chain Operator (Model FCA) AlarmGard Crank Operator (Model FKA) INSTRUCTION MANUAL AlarmGard Chain Operator (Model FCA) & AlarmGard Crank Operator (Model FKA) WARNING 1. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within

More information

WATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

WATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00 I&M NUMBER: 316-42-5-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Watlow heaters are built to comply with UL and CSA dielectric requirements, it may be

More information

Installation Instructions

Installation Instructions 48/50A2,A3,A4,A5020-060, 48/50P2,P3,P4,P5030-100, 48/50N 75 to 105 Ton Return Smoke Detector Accessory Installation Instructions Part No. CRSMKDET002C00 CONTENTS GENERAL........................................

More information

Ruskin Honeywell ML & MS to Belimo Replacement Instructions

Ruskin Honeywell ML & MS to Belimo Replacement Instructions WARNING! Before replacing actuator, damper must be inspected and determined to be fully functional. Ruskin Honeywell ML & MS to Belimo Replacement Instructions Contents UL... 2 Code and Standard Issues...

More information

DH100ACDCI Ionization Air Duct Smoke Detector

DH100ACDCI Ionization Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS Ionization Air Duct Smoke Detector Before Installing Please thoroughly read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Applications (A05-1004),

More information

DH500 Intelligent Air Duct Smoke Detector Housing

DH500 Intelligent Air Duct Smoke Detector Housing INSTALLATION AND MAINTENANCE INSTRUCTIONS DH500 Intelligent Air Duct Smoke Detector Housing 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 www.systemsensor.com Specifications

More information

Direct Fired Heater Model AD Specification

Direct Fired Heater Model AD Specification Direct Fired Heater Model AD Specification Description A Direct-fired gas heating and ventilating unit(s), as indicated on the drawings shall be furnished. Unit(s) shall be tested in accordance with ANSI

More information

Corr/Guard PRESSURE RATED VENTING SYSTEM IMPORTANT: DO NOT INSTALL WITHOUT FIRST READING THESE INSTRUCTIONS VERY CAREFULLY.

Corr/Guard PRESSURE RATED VENTING SYSTEM IMPORTANT: DO NOT INSTALL WITHOUT FIRST READING THESE INSTRUCTIONS VERY CAREFULLY. CORR/GUARD INSTALLATION INSTRUCTIONS This symbol on the nameplate means this product is listed by Underwriters Laboratories Inc. Tested to UL1738 / CAN / ULCS636-1995 Listing No. MH26687 Testing No. 11EN

More information

568X, 587X, 588X Series

568X, 587X, 588X Series Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

Indirect Gas-Fired Make-Up Air

Indirect Gas-Fired Make-Up Air Indirect Gas-Fired Make-Up Air Model IG 800 to 7,000 cfm Up to 400,000 Btu/hr Multiple Furnace Control Options Optional Evaporative Cooling May 20041 Product Features Model IG Indirect Gas-Fired Make-Up

More information

VENTILATION FAN READ AND SAVE THESE INSTRUCTIONS MODEL 50F / 70F / 70HS TABLE OF CONTENTS. Package Contents 2. General Safety Information 3

VENTILATION FAN READ AND SAVE THESE INSTRUCTIONS MODEL 50F / 70F / 70HS TABLE OF CONTENTS. Package Contents 2. General Safety Information 3 VENTILATION FAN MODEL 50F / 70F / 70HS TABLE OF CONTENTS Package Contents General Safety Information 3 Preparation and Wiring Diagrams 4 Assembly Instructions - New Construction 5 Assembly Instructions

More information

VENTILATION FAN. MFG Model : VFB80HLED2/VFB080C4L2 /VFB080C4LED2/ VFB100HLED2/VFB100C4LED1 READ AND SAVE THESE INSTRUCTIONS

VENTILATION FAN. MFG Model : VFB80HLED2/VFB080C4L2 /VFB080C4LED2/ VFB100HLED2/VFB100C4LED1 READ AND SAVE THESE INSTRUCTIONS VENTILATION FAN MODEL 80HLED/80L/80LED/00HLED/00LED TABLE OF CONTENTS Package Contents General Safety Information 3 Preparation Assembly Instructions 5 New Construction 5 Existing Construction 6 Connect

More information

Manual No: Revision: E. Groundwater Sensor. Installation Guide

Manual No: Revision: E. Groundwater Sensor. Installation Guide Manual No: 576013-763 Revision: E Groundwater Sensor Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties

More information

Operating Instructions & Parts Manual Models 99533, 99532

Operating Instructions & Parts Manual Models 99533, 99532 Operating Instructions & Parts Manual Models 99533, 99532 2 Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Internal ridged board 1 x 1.5 foil face installation shall be installed on roof, walls and base of casing. A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall

More information