1 SECTION PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: I. Backdraft dampers. 2. Manual volume dampers. 3. Fire dampers. 4. Combination fire and smoke dampers. 5. Flange connectors. 6. Turning vanes. 7. Duct-mounted access doors. 8. Flexible connectors. 9. Flexible ducts. 10. Duct accessory hardware. 11. Louvers B Related Sections: 1. Division 23 Section "HVAC Fans" for roof-mounted ventilator caps. 2. Division 26 Section " Fire Alarm System (Addressable, Simplex/Grinnell)" for ductmounted fire and smoke detectors. 1.3 QUALITY ASSURANCE A. Comply with NFPA 90A, "Installation of Air Conditioning and Ventilating Systems," and with NFPA 90B, "Installation of Warm Air Heating and Air Conditioning Systems." B. Comply with AMCA 500-D testing for damper rating. 1.4 EXTRA MATERIALS A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Fusible Links: Furnish quantity equal to 10 percent of amount installed

2 PART 2 - PRODUCTS 2.1 MATERIALS A. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" for acceptable materials, material thicknesses, and duct construction methods unless otherwise indicated. Sheet metal materials shall be free of pitting, seam marks, roller marks, stains, discolorations, and other imperfections. B. Galvanized Sheet Steel: Comply with ASTM A 653/A 653M. 1. Galvanized Coating Designation: [G60 (Z180)] [G90 (Z275)]. 2. Exposed-Surface Finish: Mill phosphatized. C. Stainless-Steel Sheets: Comply with ASTM A 480/A 480M, Type 304, and having a No. 2 finish for concealed ducts and No. 2 finish for exposed ducts. D. Aluminum Sheets: Comply with ASTM B 209 (ASTM B 209M), Alloy 3003, Temper H14; with mill finish for concealed ducts and standard, 1-side bright finish for exposed ducts. E. Extruded Aluminum: Comply with ASTM B 221 (ASTM B 221M), Alloy 6063, Temper T6. F. Reinforcement Shapes and Plates: Galvanized-steel reinforcement where installed on galvanized sheet metal ducts; compatible materials for aluminum and stainless-steel ducts. G. Tie Rods: Galvanized steel, 1/4-inch (6-mm) minimum diameter for lengths 36 inches (900 rm) or less; 3/8-inch (1 0-mm) minimum diameter for lengths longer than 36 inches (900 mm). 2.2 BALANCING DAMPERS A. Balancing dampers for rectangular ductwork shall be opposed blade type, and shall be Ruskin Model MD35 Manual Balancing Damper with Locking Quadrant or equivalent for duct pressure ratings 2 inches w.g. or less, and Ruskin Model CD30AF 1 with Locking Quadrant or equivalent for duct pressure ratings greater than 2 inches w.g. B. Balancing dampers for round ductwork shall be Ruskin Model MDRS25 Round Manual Balancing Damper with Locking Quadrant, or equivalent. 2.3 FIRE DAMPERS A. Fusible link dampers shall be of the folding blade type, shall meet the requirements of NFPA Bulletin 90A, and shall be UL listed and tested in accordance with UL 555 test criteria. Provide fire dampers UL listed for installation in 1-1/2 hour or 2-hour fire separations or divisions. B. Fire dampers for vertical installation shall be gravity operated. Fire dampers for horizontal installation shall have closure springs and latches

3 C. Fire dampers shall have resettable reusable fire link rated at 165 F. November 23,2011 D Fire dampers installed in ductwork shall be Ruskin Model IBD2, Style C, CR, or CO to match duct shape, or equivalent. Maximum pressure drop: 0.05 inches w.g. at 1500 fpm face velocity. E. Equivalent manufacturers: Ruskin, Prefco, National Control Air, Safe-Air, Greenheck, Pottorff. 2.4 DUCT ACCESS DOORS A. In general, access doors shall be at least 18 inches x 18 inches where physically possible; access doors for fire dampers shall be sized in accordance with the fire damper size. B. Access doors shall be of double construction and shall be gasketed around the entire perimeter to minimize air leakage between door and frame. Access doors in insulated ducts or casings, and fire damper access doors, shall be fully insulated with rigid fiberglass insulation between the metal panels. C. In no case shall access to any items of equipment require the removal of nuts, bolts, screws, wedges or any other loose devices. D. Access doors installed in ductwork 2 inches w.g. class and below shall be Ruskin Model ADH22, or equivalent. E. Access doors installed in ductwork above 2 inches w.g. class shall be Ruskin Model ADHP-3 High Pressure Access Doors, or equivalent. 2.5 FLEXIBLE CONNECTIONS A. Flexible connections shall be a minimum of 8 inches long. B. Flexible connection shall be fabricated from approved flameproofed fabric in accordance with the applicable sections of the NFPA overall fire codes. Asbestos cloth is not permitted. 2.6 BACKDRAFT DAMPER A. Damper shall be pressure activated, vertical air flow with face linkage and an adjustable counter weight, with a range of positive pressure from.05 inches to.25 inches w.g. B. Frame shall be constructed of.090 inch thick extruded aluminum. Blades shall be formed from.025 inch aluminum. Blades shall have overlapping edges with extruded vinyl edge seals. C. Damper shall be Ruskin Model CBD2, or equivalent. 2.7 COMBINATION FIRE AND SMOKE DAMPER A. Maximum pressure drop for damper assembly shall be 0.05 inches w.g. at 1500 fpm duct face * velocity

4 B. Dampers shall be UL listed and tested in accordance with UL 555 test criteria and shall be further qualified under UL 555S as a leakage rated damper for use in smoke control systems. The leakage rating shall be no higher than class 1 (4 cfm/sq.ft. at 1 inch w.g.) at 250'F elevated temperature category. UL leakage ratings shall apply to sizes of dampers required herein, and elevated temperature ratings shall apply to operators as well as dampers. C. Each combination fire and smoke damper shall be equipped with a UL classified firestat which shall function to close damper when duct temperature exceeds 165'F. Firestat package shall include two damper position indicator switches, both linked directly to a damper blade, to provide capabilities of remotely indicating damper position. Firestat and damper position indicators shall have capability of interfacing electrically with smoke detectors, building fire alarm systems and remote indicating/control stations. Motor operator shall be 120 volt electric actuated normally closed. D. Motor damper and firestat assembly shall have maximum draw of 4.0 amps. E. Firestat position indicator shall have capabilities of electrically locking damper in a closed position whenever duct temperatures exceed 165 F and the capability of permitting appropriate authority to override the smoke detector and re-open damper as may be required to permit desired smoke control functions only. Damper shall remain closed when firestat temperature is above 165 F. F. Combination motor/fire dampers shall be Ruskin FSD60 or equivalent. G. Firestat shall be Ruskin Model TS 150 or equivalent. H. Equivalent manufacturers: Ruskin, Prefco, National Control Air, Safe-Air, Greenheck. 2.8 DUCT PRESSURE RELIEF DOOR A. Duct pressure relief doors shall be equivalent to Ruskin PRD 18 pressure relief door. Door shall be 12 gauge galvanized steel with polyurethene foam seal, adjustable to relieve pressures from 3 inches to 8 inches positive or negative. 2.9 LOUVERS A. Louvers shall be stationary drainable blade type constructed of extruded aluminum. B. Louver frame shall be 6 inches deep box type. C. Louver frame shall be constructed of inch (minimum) thick aluminum. D. Louver blades shall be inch thick aluminum. E. Louvers shall have an integral color anodized finish. Color shall be selected and approved by Architect. F. Provide aluminum bird screen

5 G. Provide extended sill and clip angles for each louver. November 23,2011 IT Manufacturers: Ruskin, National Control Air, American Warming THERMOMETERS A. Thermometer shall be Ashcroft 5 inch dial thermometer, 20'F to 120'F temperature scale, 9 inch stem length TURNING VANES 1. Ductmate Industries, Inc. 2. Duro Dyne Inc. 3. METALAIRE, Inc. 4. SEMCO Incorporated. 5. Ward Industries, Inc.; a division of Hart & Cooley, Inc. B. Turning Vanes for Metal Ducts shall be curved blades of galvanized sheet steel; support with bars perpendicular to blades set; set into vane runners suitable for duct mounting. 1. Acoustic Turning Vanes: Fabricate airfoil-shaped aluminum extrusions with perforated faces and fibrous-glass fill. C. Manufactured turning vanes for nonmetal ducts shall be fabricated of curved blades of resinbonded fiberglass with acrylic polymer coating; support with bars perpendicular to blades set; set into vane runners suitable for duct mounting. D. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible"; Figures 2-3, "Vanes and Vane Runners," and 2-4, "Vane Support in Elbows." E. Single wall vane construction. F. Vane Construction shall be single wall for ducts up to 48 inches wide and double wall for larger dimensions FLEXIBLE DUCTS A. Noninsulated, flexible duct shall be UL 181, Class 1, multiple layers of aluminum laminate supported by helically wound, spring-steel wire. 1. Pressure Rating: 10-inch wg (2500 Pa) positive and 1.0-inch wg (250 Pa) negative. 2. Maximum Air Velocity: 4000 fpm (20 m/s). 3. Temperature Range: Minus 20 to plus 210 deg F (Minus 29 to plus 99 deg C)

6 B. Insulated, flexible duct shall be UL 181, Class 1, multiple layers of aluminum laminate supported by helically wound, spring-steel wire; R-6 fibrous-glass insulation; polyethylene aluminized vapor-barrier film. 1. Pressure Rating: 10-inch wg (2500 Pa) positive and 1.0-inch wg (250 Pa) negative. 2. Maximum Air Velocity: 4000 fpm (20 m/s). 3. Temperature Range: Minus 20 to plus 210 deg F (Minus 29 to plus 99 deg C). C. Flexible Duct Connectors: 1. Clamps: Stainless-steel band with cadmium-plated hex screw to tighten band with a worm-gear action in sizes 3 through 18 inches (75 through 460 mm), to suit duct size and adhesive mastic. D. Equivalent manufacturers: Flexmaster U.S.A., McGill AirFlow LLC 2.13 DUCT ACCESSORY HARDWARE A. Instrument Test Holes: Cast iron or cast aluminum to suit duct material, including screw cap and gasket. Size to allow insertion of pitot tube and other testing instruments and of length to suit duct-insulation thickness. B. Adhesives: High strength, quick setting, neoprene based, waterproof, and resistant to gasoline and grease. PART 3 - EXECUTION 3.1 INSTALLATION A. Install duct accessories according to applicable details in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" for metal ducts and in NAIMA AH 116, "Fibrous Glass Duct Construction Standards," for fibrous-glass ducts. B. Install duct accessories of materials suited to duct materials; use galvanized-steel accessories in galvanized-steel and fibrous-glass ducts, stainless-steel accessories in stainless-steel ducts, and aluminum accessories in aluminum ducts. C. Install backdraft dampers at inlet of exhaust fans or exhaust ducts as close as possible to exhaust fan unless otherwise indicated. D. Install volume dampers at points on supply, return, and exhaust systems where branches extend from larger ducts. Where dampers are installed in ducts having duct liner, install dampers with hat channels of same depth as liner, and terminate liner with nosing at hat channel. 1. Coordinate subparagraphs below with Division 23 Section "Metal Ducts." Install steel volume dampers in steel ducts. 2. Install aluminum volume dampers in aluminum ducts

7 E. Set dampers to fully open position before testing, adjusting, and balancing. November 23,2011 F. Install test holes at fan inlets and outlets and elsewhere as indicated. G. Install fire and smoke dampers according to UL listing. H. Install duct access doors on sides of ducts to allow for inspecting, adjusting, and maintaining accessories and equipment at the following locations: 1. On both sides of duct coils. 2. Downstream from manual volume dampers, control dampers, turning vanes, and equipment. 3. Adjacent to and close enough to fire or smoke dampers, to reset or reinstall fusible links. Access doors for access to fire or smoke dampers having fusible links shall be pressure relief access doors and shall be outward operation for access doors installed upstream from dampers and inward operation for access doors installed downstream from dampers. 4. At each change in direction and at maximum 50-foot spacing. 5. Upstream of turning vanes. 6. Elsewhere as indicated. I. Install access doors with swing against duct static pressure. J. Access Door Sizes: 1. One-Hand or Inspection Access: 8 by 5 inches. 2. Two-Hand Access: 12 by 6 inches. 3. Head and Hand Access: 18 by 10 inches. 4. Head and Shoulders Access: 21 by 14 inches. 5. Body Access: 25 by 14 inches. 6. Body plus Ladder Access: 25 by 17 inches. K. Label access doors according to Division 23 Section "Identification for HVAC Piping and Equipment" to indicate the purpose of access door. L. Install flexible connectors to connect ducts to equipment. M. For fans developing static pressures of 5-inch wg (1250 Pa) and more, cover flexible connectors with loaded vinyl sheet held in place with metal straps. N. Connect terminal units to supply ducts directly or with maximum 12-inch (300-mm) lengths of flexible duct. Do not use flexible ducts to change directions. 0. Connect diffusers or light troffer boots to low-pressure ducts directly or with maximum 60-inch (1500-mn) lengths of flexible duct clamped or strapped in place. P. Connect flexible ducts to metal ducts with liquid adhesive plus tape. Q. Install duct test holes where required for testing and balancing purposes. is

8 R. Install thrust limits at centerline of thrust, symmetrical on both sides of equipment. Attach thrust limits at centerline of thrust and adjust to a maximum of 1/4-inch (6-mm) movement during start and stop of fans. 3.2 FIELD QUALITY CONTROL A. Tests and Inspections: 1. Operate dampers to verify full range of movement. 2. Inspect locations of access doors and verify that purpose of access door can be performed. 3. Operate fire, smoke, and combination fire and smoke dampers to verify full range of movement and verify that proper heat-response device is installed. 4. Inspect turning vanes for proper and secure installation. 5. Operate remote damper operators to verify full range of movement of operator and damper. END OF SECTION

SECTION DUCTWORK. A. Section Painting: Weld priming, weather resistant, paint or coating.

SECTION DUCTWORK. A. Section Painting: Weld priming, weather resistant, paint or coating. SECTION 15890 DUCTWORK PART 1 - GENERAL 1.1 SECTION INCLUDES A. Metal ductwork. B. Duct cleaning. 1.2 RELATED SECTIONS A. Section 09900 - Painting: Weld priming, weather resistant, paint or coating. B.

More information

SECTION (15820) - AIR DUCT ACCESSORIES

SECTION (15820) - AIR DUCT ACCESSORIES PART 1 GENERAL 1.01 SUMMARY A. Section includes: SECTION 23 33 00 (15820) - AIR DUCT ACCESSORIES 1. Manual-Volume Dampers 2. Fire Dampers 3. Turning Vanes 4. Duct-Mounted Access Doors 5. Flexible Connectors

More information

SECTION AIR DUCT ACCESSORIES

SECTION AIR DUCT ACCESSORIES SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control

More information

SECTION DUCTWORK

SECTION DUCTWORK PART 1 GENERAL 1.1 REFERENCES SECTION 23 31 00 DUCTWORK A. ASHRAE - Handbook, Duct Design B. ASHRAE - Handbook, Duct Construction C. ASTM A90/A90M - Standard Test Method for Weight (Mass) of Coating on

More information

SECTION DUCTWORK

SECTION DUCTWORK SECTION 15890 DUCTWORK PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 07270 - Firestopping and Fire and Smoke Barrier Caulking. 2. 15260 - Vibration Isolation. 3. 15280 - Thermal Insulation (HVAC).

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

A. Section Common Motor Requirements for HVAC Equipment: Fan motors. SECTION 233516 - ENGINE EXHAUST SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Exhaust fans. B. Ductwork and duct fittings. C. Inlet fittings. D. Accessories. E. Carbon monoxide detectors. 1.2 RELATED

More information

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Construction Standards Page 233423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified

More information

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

A. General: Refer to paragraph entitled SUBMITTAL in Section Include the following data: SECTION 15860 - FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR MECHANICAL

More information

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems 233100 AIR DISTRIBUTION PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 230700 HVAC Insulation B. Section 237300 Air Handling C. Section 230900 Building Automation and Control System Guidelines D. Section

More information

FIRE & SMOKE DAMPERS. Meeting tomorrow's requirements for fire and smoke protection today.

FIRE & SMOKE DAMPERS. Meeting tomorrow's requirements for fire and smoke protection today. FIRE & SMOKE DAMPERS Meeting tomorrow's requirements for fire and smoke protection today. LATEST TECHNOLOGY For more than 40 years Ruskin has led the HVAC industry in the manufacture of dampers and louvers.

More information

SECTION AIR OUTLETS AND INLETS

SECTION AIR OUTLETS AND INLETS SECTION 23 37 00 AIR OUTLETS AND INLETS PART 1 - GENERAL 1.1 SUMMARY A. Section includes diffusers, light troffer diffusers, registers/grilles, door grilles, louvers, louvered penthouses, roof hoods, goosenecks.

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

SECTION (15833) - HVAC POWER VENTILATORS

SECTION (15833) - HVAC POWER VENTILATORS PART 1 GENERAL 1.01 SUMMARY SECTION 23 34 23 (15833) - HVAC POWER VENTILATORS A. Section Includes: 1. Centrifugal Roof Ventilators. 2. Up-blast Roof Exhaust Fans (Kitchen Hood Exhaust). 3. Ceiling-Mounted

More information

D. Fabrication: Steel or Aluminum with baked enamel off-white finish. B. Type: Square and rectangular, adjustable pattern, multi-louvered diffuser.

D. Fabrication: Steel or Aluminum with baked enamel off-white finish. B. Type: Square and rectangular, adjustable pattern, multi-louvered diffuser. SECTION 23 37 00 - AIR OUTLETS AND INLETS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Diffusers. 2. Registers 3. Grilles. PART 2 - PRODUCTS 2.1 ROUND CEILING DIFFUSERS B. Product Description:

More information

Square Ceiling Diffusers : All extruded aluminum constructions. Opposed blade damper is adjustable from face of diffuser. Available in square and

Square Ceiling Diffusers : All extruded aluminum constructions. Opposed blade damper is adjustable from face of diffuser. Available in square and Square Ceiling Diffusers : All extruded aluminum constructions. Opposed blade damper is adjustable from face of diffuser. Available in square and rectangular type with one, two, three or four way patterns.

More information

Life Safety Dampers Selection and Application Manual

Life Safety Dampers Selection and Application Manual Life Safety Dampers Selection and Application Manual Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers August 2016 1 2 Table of Contents HOW TO USE THIS MANUAL DAMPER

More information

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

Modular Supply Make-Up Air Unit

Modular Supply Make-Up Air Unit Modular Supply Make-Up Air Unit Model MSX Flexible Design Factory Assembled Heating Options Hot Water Steam Electric Cooling Options Evaporative Direct Expansion Chilled Water November 2009 Product Features

More information

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup. SECTION 23 70 00- CENTRAL HVAC EQUIPMENT PART 1: GENERAL 1.1 PURPOSE: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.

More information

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems. 15855 AIR HANDLING UNITS SPECIFIER: CSI MasterFormat 2004 number: 237313 PART 1 GENERAL 1.1 SUMMARY A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution

More information

Bulletin C6200 MAY Buffalo. Big Buffalo. Air Handling. Custom Applications

Bulletin C6200 MAY Buffalo. Big Buffalo. Air Handling. Custom Applications Bulletin C6200 MAY 20 3 Buffalo Air Handling Big Buffalo Custom Applications Buffalo Air Handling Big Buffalo The historic strength of Buffalo Air Handling is the custom designed air handling equipment

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 237413 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the

More information

SECTION AIR HANDLING UNIT

SECTION AIR HANDLING UNIT SECTION 15800 - AIR HANDLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork. SECTION 15855 AIR HANDLING UNITS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15885 - Air Filtration Equipment. 3. 15890 - Ductwork. 1.02 REFERENCES A. Air Moving

More information

Louvers & Dampers April Product Guide Specification SECTION COMBINATION FIRE SMOKE DAMPERS

Louvers & Dampers April Product Guide Specification SECTION COMBINATION FIRE SMOKE DAMPERS Louvers & Dampers April 2008 P.O. Box 606 7435 Industrial Road Florence, Kentucky, 41042 Phone: (859) 647-2299 Fax: (859) 647-7810 Web Site: www.louvers-dampers.com Product Guide Specification SECTION

More information

Modular Heating & Ventilating Unit Model IGX-HV

Modular Heating & Ventilating Unit Model IGX-HV Modular Heating & Ventilating Unit Model IGX-HV Indirect Gas-Fired Heating Evaporative Chilled Water DX Cooling October 2008 Product Features Model IGX-HV Indirect Gas-Fired Heating and Ventilating Unit

More information

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March GENERAL: 1. This section provides criteria for the design and installation of air handling units. DESIGN GUIDELINES: Design General 1. Location 1.1. For new construction, and existing buildings where possible,

More information

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS SECTION 237339 - DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

SECTION CUSTOM INDOOR CENTRAL-STATION AIR-HANDLING UNITS For large systems, 50,000 cfm or more.

SECTION CUSTOM INDOOR CENTRAL-STATION AIR-HANDLING UNITS For large systems, 50,000 cfm or more. Page 237323-1 SECTION 237323 - For large systems, 50,000 cfm or more. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

DIVISION 23 - HVAC HVAC Air Distribution

DIVISION 23 - HVAC HVAC Air Distribution PART 1 - GENERAL 1.01 GENERAL CRITERIA A. General Design Criteria 1. System standards require that buildings be fully ducted (supply, exhaust and return air). 2. Provide positive exhaust ventilation for

More information

15900 HVAC INSTRUMENTATION AND CONTROLS

15900 HVAC INSTRUMENTATION AND CONTROLS 15900 HVAC INSTRUMENTATION AND CONTROLS PART 1 GENERAL - Andover Controls BAS system is the standard for the University, and may be specified as a proprietary item. 1.0 RELATED DOCUMENTS A. Drawings and

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 08:50:16 AM Job Name: EarthWise Modular Climate Changer Full Spec Location: Any Town, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SUBMITTALS Submittals

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT

More information

SECTION AIR DOORS

SECTION AIR DOORS SECTION 23 34 33 AIR DOORS Berner Series VSA air doors are designed for openings up to 12 ft for environmental separation and up to 10 ft for insect control. Berner Series VSB air doors are designed for

More information

INSTRUMENTATION AND CONTROL DEVICES FOR HVAC

INSTRUMENTATION AND CONTROL DEVICES FOR HVAC PART 1 GENERAL 1.01 RELATED REQUIREMENTS SECTION 23 0913 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC A. Section 26 2717 - Equipment Wiring: Electrical characteristics and wiring connections. 1.02 ADMINISTRATIVE

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Placement within a mechanical room is required for all major mechanical equipment. Only small units may be roof-mounted, and shall be made as inconspicuous

More information

SECTION (15900) - INSTRUMENTATION AND CONTROL FOR HVAC

SECTION (15900) - INSTRUMENTATION AND CONTROL FOR HVAC SECTION 23 09 00 (15900) - INSTRUMENTATION AND CONTROL FOR HVAC PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Control Panels 2. Thermostats 3. Actuators 4. Dampers 5. Wiring B. Related Sections:

More information

SINGLE DUCT TERMINAL UNITS

SINGLE DUCT TERMINAL UNITS Performance Data AHRI Certification and Performance Notes Model Series 3000 asic Unit AHRI Certification Rating Points VAV: Fiberglass Inlet Size Airflow cfm l/s Min. Inlet Ps w.g. Pa Discharge Sound Power

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter

More information

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

DIVISION 15 MECHANICAL

DIVISION 15 MECHANICAL DIVISION 15 MECHANICAL A. GENERAL DESIGN CONDITIONS 1. Design occupied spaces to maintain 72 F and a space dew point temperature not to exceed 55 F. 2. Design classroom and office space buildings with

More information

City of Duluth Festival Center 04/25

City of Duluth Festival Center 04/25 SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete wet chemical automatic fire suppression system for the exhaust hood, including necessary

More information

SECTION METERS AND GAGES FOR HVAC PIPING

SECTION METERS AND GAGES FOR HVAC PIPING SECTION 23 0519 METERS AND GAGES FOR HVAC PIPING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Thermometers. 2. Gages. 3. Test plugs. 4. Thermowells. 1.2 SUBMITTALS A. Product Data: For each type

More information

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services Page 238216-1 Copyright 2003 and 2005 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical

More information

Chilled Water DOAS Fan Powered Terminal Units

Chilled Water DOAS Fan Powered Terminal Units Chilled Water DOAS Fan Powered Terminal Units CHILLED WATER DOAS FAN POWERED TERMINAL UNITS DOAS TERMINAL UNITS FEATURES AND BENEFITS MINIMUM VENTILATION CONTROL The DOAS unit provides the Designer, Owner

More information

DIVISION 23 - HVAC HVAC Air Distribution

DIVISION 23 - HVAC HVAC Air Distribution PART 1 - GENERAL 1.01 GENERAL CRITERIA A. General Design Criteria 1. System standards require that buildings be fully ducted (supply, exhaust and return air). 2. Provide positive exhaust ventilation for

More information

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete automatic fire suppression system for the exhaust hood, including necessary accessories.

More information

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - Systems and Equipment. Page 238239-1 SECTION 238239 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Direct Gas-Fired Make-Up Air

Direct Gas-Fired Make-Up Air Direct Gas-Fired Make-Up Air Model TSU Heavy Duty, High Airflow Applications Manufacturing and Industrial Facilities Up to 64,000 cfm August 2012 Products Model TSU Direct Gas-Fired Make-Up Air Unit The

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM SECTION 23 81 06 - PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. This Section includes equipment types that contain all the components of the refrigeration process within

More information

A. This Section includes air-handling units with coils for indoor installations.

A. This Section includes air-handling units with coils for indoor installations. SECTION 237313 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes air-handling units with coils for indoor installations. 1.2 SUBMITTALS A. Product Data: For each type of indoor air-handling unit

More information

EXHAUST FAN SCHEDULE

EXHAUST FAN SCHEDULE DUCTWORK SCHEDULE CONCEALED SUPPLY AIR RECTANGULAR, RTU CONCEALED SUPPLY AIR RECTANGULAR, ERV CONCEALED SUPPLY AIR ROUND, RTU CONCEALED SUPPLY AIR ROUND, ERV EXPOSED SUPPLY AIR ROUND RUNOUTS RETURN AIR

More information

SECTION AXIAL FANS

SECTION AXIAL FANS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES SECTION 15856 MODULAR AIR HANDLING UNITS PART 1 DESIGN DIRECTIVES 1.1 QUALITY ASSURANCE A. NFPA Compliance: Modular air handling units and components shall be designed, fabricated, and installed in compliance

More information

INSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

SECTION AIR COILS

SECTION AIR COILS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter except as otherwise

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 23 0594 - TESTING, ADJUSTING, AND BALANCING (TAB) PART 1 - GENERAL 1.1 SUMMARY A. This Section includes testing, adjusting and balancing HVAC systems to provide design conditions as indicated by

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCESA / NASA UFGS-23 00 00 (October 2006) ---------------------------- Preparing Activity: USACE Superseding UFGS-23 00 00 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters. SECTION 15622 DIRECT GAS-FIRED BURNER & MANIFOLD SYSTEM PART 1: GENERAL 1.1 Section includes: A. Direct gas-fired heater modules B. Controls C. Equipment schedule 1.2 Related Sections A. Section 01655:

More information

SAFETY AND INSTALLATION MANUAL MODEL 8100

SAFETY AND INSTALLATION MANUAL MODEL 8100 SAFETY AND INSTALLATION MANUAL ENERGY RECOVERY VENTILATORS MODEL 8100 Provides year-round fresh air Recovers 77% of the apparent heating or cooling energy from the exhausted air See Warnings Page 3 Table

More information

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A Publication No. WT-CSX-0616A Central Station Air Handling Units Complete HVAC Capability Horizontal Draw-Thru to Size 65 Vertical Draw-Thru to Size 50 1000 to 60,000 CFM Forward Curved or Airfoil Wheels

More information

SMOKE DAMPERS SMOKE DAMPERS

SMOKE DAMPERS SMOKE DAMPERS MODEL SERIES 1210SS AIROIL BLADE STAINLESS STEEL Model Series 1210SS Stainless Steel Airfoil Blade Smoke Dampers are ideal for high humidity, mildly corrosive or, with optional Type 316 construction, more

More information

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements. SECTION 15855 AIR HANDLING UNITS WITH COILS PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Central Station Air Handling Units. B. Related Sections: 1.02 REFERENCES 1. Section 15010 - Basic Mechanical

More information

Contents INDEX. TDM Series Indirect Fired Heaters

Contents INDEX. TDM Series Indirect Fired Heaters Contents Typical Indoor Installations................... 000 Indoor Unit Dimensions (Vertical).............. 000 Indoor Unit Dimensions (Horizontal)............ 000 Outdoor Unit Dimensions.....................

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Balancing Air Systems: a. Constant-volume air systems. b. Variable-air-volume systems. 2.

More information

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials. B B11.0 DIVISION 08 - OPENINGS SECTION 08 17 00 INTEGRATED DOOR OPENING ASSEMBLIES Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements. Add section numbers and

More information

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section. SECTION 15855 GAS FURNACE/DX COOLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of contract including General and Supplementary Conditions of Division 1 of Specification

More information

SECTION AIR COILS

SECTION AIR COILS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 82 16 AIR COILS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in the section

More information

. ECTION METERS AND GAGES

. ECTION METERS AND GAGES . ECTION 230519 - METERS AND GAGES PART I - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 00 thru 01 Specification

More information

SMOKE DAMPERS AIRFOIL STAINLESS STEEL

SMOKE DAMPERS AIRFOIL STAINLESS STEEL MODEL SERIES 1210M AIROIL BLADE MODULATING ACTUATOR Model Series 1210M Modulating Smoke Dampers are classified for use as a volume control damper in applications where building codes require a leakage

More information

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004) High Plume Blowers Suggested Specification Section 15500 (Master Format 1996) Suggested Specification Section 23 38 16 (Master Format 2004) PART 1 GENERAL 1.01 WORK INCLUDED High Plume Laboratory Exhaust

More information

Instructions. Duct Mount Accessory Q Rev: 11/

Instructions. Duct Mount Accessory Q Rev: 11/ Instructions Duct Mount Accessory Q5016 Rev: 11/16 95-8752 Table of Contents DESCRIPTION...1 FEATURES...1 OPERATION...1 SPECIFICATIONS.... 2 INSTALLATION... 2 Detector Location...2 Tools for Assembly...4

More information

C. Manufactured double wall chimneys for fuel fired equipment. D. NFPA 54 - National Fuel Gas Code; National Fire Protection Association; 2009.

C. Manufactured double wall chimneys for fuel fired equipment. D. NFPA 54 - National Fuel Gas Code; National Fire Protection Association; 2009. SECTION 235100 - BREECHINGS, CHIMNEYS, AND STACKS PART 1 GENERAL 1.1 SECTION INCLUDES A. Fabricated breechings. B. Manufactured chimneys for gas fired equipment. C. Manufactured double wall chimneys for

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. Page 238219-1 SECTION 238219 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

INSTALLATION INSTRUCTION BOOKLET FOR SMOKE DAMPERS

INSTALLATION INSTRUCTION BOOKLET FOR SMOKE DAMPERS INSTALLATION INSTRUCTION BOOKLET FOR SMOKE DAMPERS Instructions included in this booklet: IOM # Description Page(s) 46133 SMD-XXX, SESMD-XXX, SSSMD-XXX, SMD-XXX Series - 46313 Smoke Detector (DH100ACDCLP)

More information

Tunnel Transit Dampers. Heavy Duty Tunnel Transit Life Safety

Tunnel Transit Dampers. Heavy Duty Tunnel Transit Life Safety Tunnel Transit Dampers Heavy Duty Tunnel Transit Life Safety November 2011 Heavy Duty/Industrial Tunnel Dampers Applications Dampers in subway tunnels and transit systems serve three primary functions,

More information

COHASSET, MA March 6, The following is the HVAC outline specifications, which defines the scope of work of the HVAC system.

COHASSET, MA March 6, The following is the HVAC outline specifications, which defines the scope of work of the HVAC system. 23 00 00 HEATING, VENTILATING & AIR-CONDITIONING The following is the HVAC outline specifications, which defines the scope of work of the HVAC system. PART 1 GENERAL 1.1 CODES A. All work installed under

More information

Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering

Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015 Peter McDonnell, PE, LEED AP BD+C McClure Engineering UL DAMPER TEST STANDARDS UL 555 - FIRE DAMPERS UL555S SMOKE DAMPERS UL555C CEILING

More information

Tunnel Transit Dampers Heavy Duty Tunnel Transit Life Safety

Tunnel Transit Dampers Heavy Duty Tunnel Transit Life Safety Tunnel Transit Dampers Heavy Duty Tunnel Transit Life Safety November 2017 Heavy Duty/Industrial Tunnel Dampers Applications Dampers in subway tunnels and transit systems serve three primary functions,

More information

Indirect Gas-Fired Make-Up Air

Indirect Gas-Fired Make-Up Air Indirect Gas-Fired Make-Up Air Model IG 800 to 7,000 cfm Up to 400,000 Btu/hr Multiple Furnace Control Options Optional Evaporative Cooling May 20041 Product Features Model IG Indirect Gas-Fired Make-Up

More information

UFGS (August 2008) UFGS (January 2007) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS (August 2008) UFGS (January 2007) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCESA / NASA UFGS-23 82 46.00 40 (February 2011) ----------------------------------- Preparing Activity: NASA Superseding UFGS-23 82 46 (August 2008) UFGS-40 41 13.13 40 (January 2007)

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 82 46.00 40 (May 2017) --------------------------------- Preparing Activity: NASA Superseding UFGS-23 82 46.00 40 (August 2014) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

A. Codes and Standards that are Standard at the University:

A. Codes and Standards that are Standard at the University: PART 1: GENERAL 1.01 Purpose: 1.02 References: 1.03 Requirements: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The

More information

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components. Page 238126-1 SECTION 238126 - This Section includes requirements for the LEED Rating System. However, equipment specified in this Section may not qualify for LEED Rating System prerequisites and credits.

More information

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No. SECTION 22 63 13 GAS PIPING FOR LABORATORY AND HEALTHCARE FACILITIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

FAN ENGINEERING. Sealing of Fan Housings

FAN ENGINEERING. Sealing of Fan Housings FAN ENGINEERING Information and Recommendations for the Engineer FE-700 Sealing of Fan Housings Introduction A variety of options are offered by fan manufacturers to seal fan housings. Sealing the housing

More information

AIR HANDLING. B. Section Building Automation and Control System Guidelines. C. Section Air Cleaning Devices and Filters

AIR HANDLING. B. Section Building Automation and Control System Guidelines. C. Section Air Cleaning Devices and Filters 237300 AIR HANDLING PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 230530 Clean Steam Generation B. Section 230900 Building Automation and Control System Guidelines C. Section 234100 Air Cleaning Devices

More information

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters. Section 15 _ Energy Recovery Air Handling System Part 1: GENERAL 1.1 Section Includes: A. Energy Recovery Air Handler B. Controls (most by Others) C. Equipment Schedule 1.2 Related Sections: A. Section

More information

B. System Design and Performance Requirements

B. System Design and Performance Requirements 15815 Metal Ducts This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 15815 Metal Ducts This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

Linear Floor Heaters

Linear Floor Heaters Linear Floor Heaters The Price Linear Floor Heater family provides ultimate flexibility in terms of style, performance, and ease of installation. Using room-side heat virtually eliminates the requirement

More information

Fire, Smoke, and Combination Fire Smoke Dampers

Fire, Smoke, and Combination Fire Smoke Dampers Fire, Smoke, and Combination Fire Smoke Dampers Mark Belke Director Damper Products-Greenheck Chairman of Code Action Review Committee (CARC) California Building Code work group NFPA 80A, 90A, 92B, 101,

More information

SPECIFICATIONS - DETAILED PROVISIONS Section Heating, Ventilation, and Air Conditioning Equipment C O N T E N T S

SPECIFICATIONS - DETAILED PROVISIONS Section Heating, Ventilation, and Air Conditioning Equipment C O N T E N T S Revised 04/14/16 SPECIFICATIONS - DETAILED PROVISIONS Section 15700 - Heating, Ventilation, and C O N T E N T S PART 1 - GENERAL... 1 1.01 DESCRIPTION... 1 1.02 SPECIFIC PROJECT VENTILATION AND AIR CONDITIONING

More information