SITRANS F. Ultrasonic Flowmeters FST030. Function Manual. Answers for industry. 04/2017. Edition

Size: px
Start display at page:

Download "SITRANS F. Ultrasonic Flowmeters FST030. Function Manual. Answers for industry. 04/2017. Edition"

Transcription

1 SITRANS F Ultrasonic Flowmeters Function Manual Edition 04/2017 Answers for industry.

2

3 Introduction 1 Quick Start 2 SITRANS F Ultrasonic Flowmeters Function Manual Setup 3 Maintenance and diagnostics 4 Communication 5 Security 6 Language 7 Support A This Function Manual applies to Siemens products SITRANS with order codes commencing 7ME372 04/2017 A5E AA

4 Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION indicates that minor personal injury can result if proper precautions are not taken. NOTICE indicates that property damage can result if proper precautions are not taken. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: Trademarks WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed. All names identified by are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Division Process Industries and Drives Postfach NÜRNBERG GERMANY Document order number: A5E P 04/2017 Subject to change Copyright Siemens AG All rights reserved

5 Table of contents 1 Introduction Function Manual scope Purpose of this documentation Quick start wizards Support Product compatability Document history Device documentation package Quick Start Quick commissioning Sensor settings Process values Inputs and outputs Copy configuration Setup Sensor settings Length unit Pipe settings Pipe class Pipe size Outer pipe diameter Wall thickness Pipe material Wall sound velocity Liner settings Inner pipe roughness Inner pipe diameter Active compensations Active compensations - settings Upstream and downstream conditions Disturbed flow profile compensation Disturbed flow profile compensation - settings Type of upstream condition Upstream distance Upstream distance - settings Type of downstream condition Downstream distance Downstream distance - settings Medium characteristics Function Manual, 04/2017, A5E AA 3

6 Table of contents Process medium type Expected sound velocity Process temperature Process pressure Kinematic viscosity Process density Sensor selection Sensor model Clamp-on sensor size Nominal sensor frequency Sensor crystal projection Sensor phase velocity Sensor inactive wedge Sensor fixed time Mounting hole offset Spacing offset Temperature code of the sensor Temperature compensation factor Length of sensor cables settings Installed paths Necessary number of measuring paths Necessary number of measuring paths - settings User calibration Slope offset offset Multipoint calibration Enable multipoint calibration Asymmetric calibration table Calibration point Multipoint calibration table Flow direction Miscellaneous Preamplifier Number of pulses to be transmitted Minimum ringdown delay Electronic time delay Configuration of test blocks About Sensor size Process values Volume flow Units Custom units Custom conversion factor Decimal places Low flow cut-off Alarm and warning limits Mass flow Function Manual, 04/2017, A5E AA

7 Table of contents Units Custom units Custom conversion factor Decimal places Low flow cut-off Alarm and warning limits Standard flow volume Units Custom units Custom conversion factor Decimal places Low flow cut-off Alarms and warning limits Standard temperature Standard pressure Air density at standard conditions Flow velocity Units Custom units Custom conversion factor Decimal places Low flow cut-off Alarm and warning limits Sound velocity Units Custom units Custom conversion factor Decimal places Alarm and warning limits LiquIdent Alarm and warning limits Temperature slope factor Pressure slope factor Density Units Custom units Custom conversion factor Decimal places Alarm and warning limits Kinematic viscosity Units Decimal places Alarm and warning limits Pressure Units Decimal places Alarm and warning limits Medium temperature Units Decimal places Alarm and warning limits Standard density Function Manual, 04/2017, A5E AA 5

8 Table of contents Units Decimal places Alarm and warning limits Standard kinematic viscosity Units Decimal places Alarm and Warning limits API gravity Alarm and warning limits Standard API gravity Alarm and warning limits Specific gravity Alarm and warning limits Standard specific gravity Alarm and warning limits Totalizers Totalizer Process value Units Custom units Custom conversion factor Decimal places Direction Fail-safe behaviour Reset Preset Alarm and warning limits Totalizer Process value Units Custom units Custom conversion factor Decimal places Direction Fail safe behaviour Reset Preset Alarm and warning limits Totalizer Process value Units Custom units Custom conversion factor Decimal places Direction Fail-safe behaviour Reset Preset Alarm and warning limits Reset all totalizers Inputs and outputs Function Manual, 04/2017, A5E AA

9 Table of contents Current input Digital input Channel 1 - output with HART Loop current mode Active operation (read only) PV selection Direction Loop current scale Upper range value Lower range value Fail-safe activation condition Damping value Fail-safe behaviour Fail-safe value Fail-safe minimum time Channel 2 - output Operation mode Active operation (read only) Fail-safe activation condition Current output Frequency output Pulse output Status output Channel 3 - input/output Operation mode Change operation mode Active operation (read only) Fail-safe activation condition Current output Frequency output Pulse output Status output Digital input Current input Channel 3 - relay Operation mode Status mode Sensor alarms (1) Sensor alarms (2) Process alarms (1) Process alarms (2) Process alarms (3) Process alarms (4) Totalizer alarms Device alarms Device alarms - settings Channel 1 alarms Input/output alarms (1) Input/output alarms (2) Input/output alarms (2) - settings Simulation alarms (1) Simulation alarms (2) Function Manual, 04/2017, A5E AA 7

10 Table of contents Alarm class NAMUR status signal Polarity On delay Off delay Channel 4 - input/output Operation mode Change operation mode Active operation (read only) Fail-safe activation condition Current output Frequency output Pulse output Status output Digital input Current input Channel 4 - relay Operation mode Status mode Sensor alarms (1) Sensor alarms (2) Process alarms (1) Process alarms (2) Process alarms (3) Process alarms (4) Totalizer alarms Device alarms Channel 1 alarms Input/output alarms Simulation alarms Alarm class NAMUR status signal Polarity On delay Off delay Channel 5 - input Process value RTD configuration Calibration Channel 6 - input Process value RTD configuration Calibration Date and time Current date and time Set date and time Local display Brightness Backlight Contrast Damping Function Manual, 04/2017, A5E AA

11 Table of contents Damping value Process values (1) Process values (2) View View st value Graph scale mode nd value rd value th process value th process value th process value Trend scale mode Trend log time window Trend scale lower limit Trend scale upper limit View Enable or disable View st value nd process value rd process value th process value th process value th process value Trend scale mode Trend log time window Trend scale lower limit Trend scale upper limit View Enable or disable View st value Graphic scale mode nd process value rd process value th process value th process value th process value Trend scale mode Trend log time window Trend scale lower limit Trend scale upper limit View Enable or disable View st value nd value rd value th value th value th value Function Manual, 04/2017, A5E AA 9

12 Table of contents Trend scale mode Trend log time window Trend scale lower limit Trend scale upper limit View Enable or disable View st value nd value rd value th process value th process value th process value Trend scale mode Trend log time window Trend scale lower limit Trend scale upper limit View Enable or disable View st process value nd process value rd process value th process value th process value th process value Trend scale mode Trend log time window Trend scale lower limit Trend scale upper limit Status icons Maintenance and diagnostics Identification Long tag Tag Descriptor Message Location Installation date Manufacturer Product name Version (read only) Order number (read only) Serial number FW version HW version Final assembly number System type Transmitter electronics HW version FW version Function Manual, 04/2017, A5E AA

13 Table of contents Serial number Order number Comm. interface serial number Local display I/O electronics DSL Sensor Type (read only) Sensor type (read only) Serial number (read only) Serial number (read only) Serial number (read only) Serial number (read only) Serial number (read only) Sensor type (read only) Sensor firmware version (read only) Sensor hardware version (read only) Frontend variant (read only) Serial number (read only) Diagnostic events Active diagnostic events Diagnostic log Clear diagnostic log Acknowledge mode Transmitter detailed events (read only) Suppression time Enable alarms Sensor events (1) Sensor events (2) Process events (1) Process events (2) Process events (3) Process events (4) Totalizer events Device events Simulation events (1) Simulation events (2) Input/output events (1) Input/output events (2) Assign alarm class : No signal : No signal Transm. temp. above alarm limit Transm. temp. below alarm limit Maintenance Copy configuration Spare part replacement Transmitter Sensor Operating time Electronic part identification Function Manual, 04/2017, A5E AA 11

14 Table of contents Transmitter cassette Local display I/O cassette Sensor cassette Diagnostics Sensor Receiver signal Reynolds number (read only) Temperature monitoring Medium temperature Transmitter electronics temperature DSL temperature Inputs and outputs Channel 1 - output with HART Channel 2 - output Channel 3 - input/output Channel 3 - relay Channel 4 - input/output Channel 4 - relay Calibration picture Peak values Process value Process value Maximum Timestamp at maximum value Minimum Timestamp at minimum value Reset peak values Process value Process value Maximum Timestamp at maximum value Minimum Timestamp at minimum value Reset peak values Process value Process value Maximum Timestamp at maximum value Minimum Timestamp at minimum value Reset peak values Process value Process value Maximum Timestamp at maximum value Minimum Timestamp at minimum value Reset peak values Function Manual, 04/2017, A5E AA

15 Table of contents 4.6 Characteristics Transmitter Design (read only) Hazardous area approval (read only) DSL DSL variant (read only) SensorFlash Eject Installed (read only) Capacity total (read only) Capacity available (read only) Data logging Activation Data logging mode Logging interval Process values Advanced logging (expert) Simulation Simulation inputs and outputs Channel 1 - output with HART Channel 2 - output Channel 3 - input/output Relay (3) Channel 4 - Input/output Channel 4 - relay Simulation process values Enable simulation Volume flow Mass flow Standard volume flow Flow velocity Sound velocity LiquIdent Density Kinematic viscosity Pressure Medium temperature Standard density Standard kinematic viscosity API gravity Standard API gravity Specific gravity Standard specific gravity Auxiliary temperature Standardizing factor Liquid identifier Simulate alarms Simulation mode Alarms Alarm class Alarm class Function Manual, 04/2017, A5E AA 13

16 Table of contents 4.9 Audit trail Parameter change log Clear parameter change log (write only) Firmware update change log Clear FW update change log (expert) Self test Display test Resets Restore ordered configuration (write only) Device restart (write only) Firmware update Communication Service channel (USB) USB mode (read only) Auto mode MSD connect (write only) HART (Channel 1) Polling address (SW) Polling address (HW) (read only) TAG HART device type (read only) HART device revision Response preambles Dynamic variable mapping SV process value TV process value QV process value Hart units Volume flow units Mass flow units Standard volume flow unit Flow velocity units Sound velocity units Density units Kinematic viscosity units Pressure units Temperature units Totalizer 1 units Totalizer 2 units Totalizer 3 units Damping Damping value Process values (1) Process values (2) Modbus (Channel 1) Slave address (SW) Slave address (HW) (read only) Baud rate Parity / framing Function Manual, 04/2017, A5E AA

17 Table of contents Floating point byte order Integer byte order Register mapping Enable mapping Source register Target register Modbus units Mass flow unit Volume flow unit Standard volume flow Flow velocity unit Sound velocity unit Density unit Kinematic viscosity unit Pressure unit Temperature units Totalizer 1 unit Totalizer 2 unit Totalizer 3 unit Service Channel (USB) Security Change user PIN Change expert PIN code (expert) Recovery ID PIN recovery Activate user PIN Deactivate user PIN Auto logout Logout Language Language A Support A.1 Technical support Glossary Index Function Manual, 04/2017, A5E AA 15

18 Table of contents 16 Function Manual, 04/2017, A5E AA

19 Introduction Function Manual scope Note This Function Manual applies to the SITRANS only. The transmitter can be connected to sensor types FSS200 and FSS Purpose of this documentation This manual contains a description of all device parameters and is aimed at persons configuring the device. Some parameters are only available for devices using specific communications systems (for example HART or Modbus), and some parameters are not available in the current version. This is mentioned in the relevant chapter/subchapter titles. The default settings and the setting ranges are listed in tables for each parameter. Furthermore, the relation, if any, between parameters is described. As of chapter 3, Setup (Page 23), the chapter and subchapter numbers equal the parameter numbers in the HMI structure. For parameters with access level other than User (for example Read only or Expert), the access level is stated in parenthesis after the parameter name. 1.3 Quick start wizards The device offers a set of wizards which will guide you through configuration of parameters essential for your application. The quick commissioning wizards are described in the Commissioning chapter of the device Operating Instructions. 1.4 Support For product support, or to contact a Siemens representative, see Technical support (Page 337). Function Manual, 04/2017, A5E AA 17

20 Introduction 1.5 Product compatability 1.5 Product compatability The following table shows major changes in the documentation compared to the previous edition. Edition Remarks Product compatibility Compatibility of device integration package 04/2017 First edition HART FW: SIMATIC PDM V8.2 or later EDD: or later EDD: or later HW: 02 AMS Device Manager 12.0 EDD: or later or later Device revision 1 or EDD: or later later SITRANS DTM V4.1 Field communicator V3.8 Edition Remarks Product compatibility 04/2017 First Modbus edition FW: HW: 02 Compatibility of device integration package SIMATIC PDM V8.2 or later AMS Device Manager 12.0 or later SITRANS DTM V4.1 Field communicator V3.8 EDD: or later EDD: or later EDD: or later EDD: or later 1.6 Document history The following table shows major changes in the documentation compared to the previous edition. The most important changes in the documentation when compared with the respective previous edition are given in the following table. Edition Note 04/2017 First edition 18 Function Manual, 04/2017, A5E AA

21 Introduction 1.7 Device documentation package 1.7 Device documentation package The user documentation package for this product includes the following documents Document Purpose Intended users Availability Application planning sheets Contains all information needed to plan the mechanical / physical installation and control signals before the product arrives Plant design engineers, control system designers Sent to the customer with Quote Available for download from homepage Operating Instructions Contains all information neeeded to check and identify the delivered package install and electrically connect the product Instrument technicians, plant operators On documentation disk Available for download from homepage commission the product, (setting parameters via HMI menu) Hardcopy can be purchased via PIA Life Cycle Portal operate and maintain the device on a daily basis troubleshoot and remedy minor operation interruptions Sensor Installation Manual Contains all information needed to install Clamp-on sensors. Mechanical and electrical installers; instrument technicians Included in the delivery On documentation disk Available for download from homepage Compact Operating Instructions - Ex Contains all information needed to satisfy the Special conditions for installation of Ex-certified products Instrument technicians, plant operators with special training in systems for hazardous locations. On documentation disk Available for download from homepage Hardcopy can be ordered via PIA Life Cycle Portal Functions Manual Contains descriptions of all functions that can be accessed via the local display (HMI) guide to setting parameters to obtain optimum operation of the device Instrument technicians, plant operators Available for download from homepage Hardcopy can be purchased via PIA Life Cycle Portal Function Manual, 04/2017, A5E AA 19

22 Introduction 1.7 Device documentation package 20 Function Manual, 04/2017, A5E AA

23 Quick Start 2 The quick start wizard topics and introductory explanations are listed below. For detailed quick start wizard procedures refer to the Operating Instructions manual. 2.1 Quick commissioning Quick commissioning - The Quick commissioning wizard will guide you through configuration of parameters essential for your application. You configure parameters essential for your application by selecting the configuration path and sub-wizards appropriate for your application. 2.2 Sensor settings The sensor settings wizard will guide you through configuration of essential parameters. 2.3 Process values The Process values wizard will guide you through setup of process values for your application. The prioritizing of the process values automatically configures the measurement views on the display. The process value configured as 1st process value appears as first value in the views. 2.4 Inputs and outputs The Inputs and outputs wizard will guide you through setup of inputs and outputs on the available channels. The availability of channels 3 and 4 depends on the product configuration. 2.5 Copy configuration This wizard allows you to copy the configuration from the SensorFlash to the device. Function Manual, 04/2017, A5E AA 21

24 Quick Start 2.5 Copy configuration 22 Function Manual, 04/2017, A5E AA

25 3 3.1 Sensor settings Length unit Unit for length values. ft; m; in; cm; mm m Setup Sensor settings Length units Pipe settings Pipe class Pipe class - Read only. Can only be changed via the Sensor Wizard. Indicates the pipe class chosen from the pipe data library included in the sensor setup wizard Pipe size Pipe size - Read only. Can only be changed via the Sensor Wizard. Indicates the pipe class chosen from the pipe data library included in the sensor setup wizard Outer pipe diameter External pipe diameter m to 10.0 m 0.1 m Function Manual, 04/2017, A5E AA 23

26 3.1 Sensor settings Setup Sensor settings Pipe settings Outer pipe diameter Wall thickness Pipe wall thickness m to 0.5 m m Setup Sensor settings Pipe settings Wall thickness Pipe material Pipe material - Read only. Can only be changed via the Sensor Wizard. Read only: Carbon steel; Stainless steel; ABS plastic; Aluminum; Black iron; Brass; Cast iron; Copper nickel 70/30; Copper nickel 90/10; Copper; Ductile iron; FRP plastic; Glass; Hastelloy; Inconel; Kynar plastic; Monel; Nickel; Polyethylene; PVC plastic; Teflon; Titanium Can only be changed via the Sensor wizard Setup Sensor settings Pipe settings Pipe material Wall sound velocity Pipe wall material sound velocity (clamp-on). Use the shear velocity for metallic pipes. Use the longitudinal velocity for plastic pipes m/s to m/s m/s Setup Sensor settings Pipe settings Wall sound velocity 24 Function Manual, 04/2017, A5E AA

27 3.1 Sensor settings Liner settings Liner thickness Pipe liner thickness 0.0 m to 0.5 m 0.0 m Setup Sensor settings Pipe settings Liner settings Liner thickness Liner material Liner material - Read only. Can only be changed via the Sensor Wizard. Read only: Custom; Cement; Coal tar; Enamel; Glass; Plastic; Hi_dens_Poly; PTFE; Rubber Custom Setup Sensor settings Pipe settings Liner settings Liner material Liner sound velocity Liner material sound velocity (clamp-on) m/s to m/s m/s Setup Sensor settings Pipe settings Liner settings Liner sound velocity Inner pipe roughness Roughness of inner pipe/liner material. Function Manual, 04/2017, A5E AA 25

28 3.1 Sensor settings 0.0 m to 0.01 m m Setup Sensor settings Pipe settings Inner pipe roughness Inner pipe diameter Read only. Calculated inner diameter of pipe (clamp-on). 0.0 m Setup Sensor settings Pipe settings Inner pipe diameter Active compensations Active compensations Active compensations - settings Pipe expansion due to temperature, Pipe expansion due to pressure Multiselection Setup Sensor settings Pipe settings Active compensations Upstream and downstream conditions Disturbed flow profile compensation Disturbed flow profile compensation enable/disable 26 Function Manual, 04/2017, A5E AA

29 3.1 Sensor settings Disturbed flow profile compensation - settings Enable; Disabled Disabled Setup Sensor settings Upstream and downstream conditions Disturbed flow profile compensation Type of upstream condition Compensation for upstream pipe geometry. Straight run; Single elbow; Double elbow (in-plane); Double elbow (out-of-plane); Reducer; Expansion Straight run Setup Sensor settings Upstream and downstream conditions Type of upstream condition Upstream distance The distance to the upstream flow disturbance. The distance is given in pipe diameters. Used for clamp-on flow profile compensation Upstream distance - settings 0 to 40 0 Setup Sensor settings Upstream and downstream conditions Upstream distance Type of downstream condition Compensation for downstream pipe geometry. Function Manual, 04/2017, A5E AA 27

30 3.1 Sensor settings Straight run; Single elbow; Double elbow (in-plane); Double elbow (out-of-plane); Reducer; Expansion Straight run Setup Sensor settings Upstream and downstream conditions Type of downstream condition Downstream distance The distance to the downstream flow disturbance. The distance is given in pipe diameters. Used for clamp-on flow profile compensation Downstream distance - settings 0 to 40 0 Setup Sensor settings Upstream and downstream conditions Downstream distance Medium characteristics Process medium type Process medium types - Read only. Can only be changed via the Sensor Wizard. Indicates the fluid medium type chosen from the fluid data library included in the sensor setup wizard Expected sound velocity Expected sound velocity in the medium at process temperature m/s to m/s m/s 28 Function Manual, 04/2017, A5E AA

31 3.1 Sensor settings Setup Sensor settings Fluid settings Expected sound velocity Process temperature Temperature of media used for compensation. Input during setup C to C 20.0 C Setup Sensor settings Medium characteristics Process temperature Process pressure Pressure value used for compensation. Input during setup. 0.0 Pa to Pa Pa Setup Sensor settings Medium characteristics Process pressure Kinematic viscosity Viscosity of media used for compensation. Input during setup m²/s to m²/s m²/s Setup Sensor settings Medium characteristics Kinematic viscosity Function Manual, 04/2017, A5E AA 29

32 3.1 Sensor settings Process density Density of media used for compensation. Input during setup. 0.0 kg/m³ to kg/m³ kg/m³ Setup Sensor settings Medium characteristics Process density Sensor selection Sensor model Installed sensor model (for multi-path all must be the same). Read only. Can only be changed via the Sensor Wizard. Indicates the Sensor model chosen from the sensor setup wizard. Read only: FSS200 high precision; FSS200 / 1011 Universal; FSS200 / 991 high temperature; 1011 high precision liquid FSS200 / 1011 Universal Setup Sensor settings Sensor selection Sensor model Clamp-on sensor size Installed sensor size. Read only. Can only be changed via the Sensor Wizard. Indicates the Sensor model chosen from the sensor setup wizard Nominal sensor frequency Nominal frequencies for the sensors 30 Function Manual, 04/2017, A5E AA

33 3.1 Sensor settings m/s to m/s m/s Setup Sensor settings Sensor selection Nominal sensor frequency Sensor crystal projection Length of the crystal projection onto the emitting surface of the sensor (clamp-on). Access level: Expert user only. 0.0 m to 0.3 m m Setup Sensor settings Sensor settings Sensor crystal projection Sensor phase velocity The velocity at which the wave fronts traverse the interface between the wedge and pipe. Access level: Expert user only m/s to m/s m/s Setup Sensor settings Sensor settings Sensor phase velocity Sensor inactive wedge The part of the wedge that is not part of the sound path. Access level: Expert user only. 0.0 m to 0.05 m m Setup Sensor settings Sensor settings Sensor inactive wedge Function Manual, 04/2017, A5E AA 31

34 3.1 Sensor settings Sensor fixed time Fixed time in sensor wedge. Access level: Expert user only. 2.0 x 10-6 s to x 10-6 s x 10-6 s Setup Sensor settings Sensor settings Sensor fixed time Mounting hole offset Distance between spacer hole and sensor front face. 0.0 m to 0.05 m m Setup Sensor settings Sensor settings Mounting hole offset Spacing offset Sensor spacing offset MIN; NOM; MAX and A,B, C, D for High Temperature sensors MIN Setup Sensor settings Sensor selection Spacing offset Temperature code of the sensor Temperature code selections for sensors. T1 (21 C), T2, T3 T1 (21 C) 32 Function Manual, 04/2017, A5E AA

35 3.1 Sensor settings Setup Sensor settings Sensor selection Temperature code of the sensor Temperature compensation factor Temperature compensation factors for the sensors to Setup Sensor settings Sensor selection Temperature compensation factor Length of sensor cables Length of sensor cable between transmitter/dsl and any sensors. All cables must have the same length. 0.0 m to 20.0 m 0.0 m Setup Sensor settings Sensor selection Length of sensor cables settings Installed paths Bit encoded value containing installed paths for clamp-on systems. Bit 0: 1 installed Bit 1: 2 installed Bit 2: 3 installed Bit 3: 4 installed Bit 4: 5 installed Function Manual, 04/2017, A5E AA 33

36 3.1 Sensor settings 0 to 31 0 Setup Sensor settings settings Installed paths Sensor frequency Desired sensor frequency for path 1. Read only Hz to Hz Setup Sensor settings settings 1 Sensor frequency geometry The number of crossings the signal makes through the pipe (Reflect or Direct geometry for 1). For example: Direct (1 traverse) Reflect (2 traverse) Direct (3 traverse) Reflect (4 traverse) 1 to 10 1 Setup Sensor settings settings 1 geometry 34 Function Manual, 04/2017, A5E AA

37 3.1 Sensor settings Sensor spacing Sensor spacing - Distance between the front faces of the sensors for path m to m 0.0 m Setup Sensor settings settings 1 Sensor spacing Zero point adjustment Zero point adjustment. Can only be changed via the Sensor Wizard. Note Important Please stop all flow in the pipe and perform this function. The flow velocity is measured prior and after the function has been applied. 5 to Setup Sensor settings settings 1 Zero point adjustment Time duration Serial number Serial number of sensor (clamp-on) Setup Sensor settings settings 1 Serial number Function Manual, 04/2017, A5E AA 35

38 3.1 Sensor settings Sensor frequency Desired sensor frequency for path 2. Read only Hz to Hz Setup Sensor settings settings 2 Sensor frequency geometry The number of crossings the signal makes through the pipe (Reflect or direct geometry for path 2). E.g.: Z path = 1 V path = 2 W path = 4 1 to 10 1 Setup Sensor settings settings 2 geometry Sensor spacing Sensor spacing - Distance between the front faces of the sensors for path m to m 0.0 m Setup Sensor settings settings 2 Sensor spacing 36 Function Manual, 04/2017, A5E AA

39 3.1 Sensor settings Zero point adjustment Zero point adjustment. Can only be changed via the Sensor Wizard. Note Important Please stop all flow in the pipe and perform this function. The flow velocity is measured prior and after the function has been applied. 5 to Setup Sensor settings settings 2 Zero point adjustment Time duration Serial number Serial number of sensor (clamp-on) Setup Sensor settings settings 2 Serial number Necessary number of measuring paths List of measuring paths. If less than the specified number of paths are in a measuring state, the meter will report an error Necessary number of measuring paths - settings 1 to 5 5 Setup Sensor settings settings Necessary number of measuring paths Function Manual, 04/2017, A5E AA 37

40 3.1 Sensor settings User calibration Slope A single point flow correction applied to volume flow equally at any flow rate. Q = Q * Slope (e.g. Slope of 0.99 = -1% correction) 0.5 to Setup Sensor settings User calibration Slope offset User calibrated zero offset for path 1. Delta time offset correction value, which can be determined at zero flow ns to 1250ns Setup Sensor settings User calibration 1 offset offset User calibrated zero offset for path 2. Delta time offset correction value, which can be determined at zero flow ns to 1250ns Setup Sensor settings User calibration 2 offset 38 Function Manual, 04/2017, A5E AA

41 3.1 Sensor settings Multipoint calibration Enable multipoint calibration Enable or disable the multipoint calibration. Disabled; Enabled Disabled Setup Sensor settings Multipoint calibration Asymmetric calibration table Note Access level: Expert user only Only available for LUILOCAL_CURRENT_LUI_ACCESS_LEVEL == SUP AND PID_ProtectCalibrationTable == 0 AND PID_EnableUserCalibrationTable == 1 Usage of the calibration table: Unidirectional: All 20 calibration points are used for positive flow calibration and are then mirrored for negative flow. Bidirectional: The first 10 calibration points are used for positive flow calibration and the 10 last calibration points are used for negative flow calibration. Unidirectional; Bidirectional Unidirectional Setup Sensor settings Asymmetric calibration table Calibration point Calibration point that is to be transferred to the multipoint calibration table. 0.0 m 3 /s to m 3 /s 0.0 m 3 /s Function Manual, 04/2017, A5E AA 39

42 3.1 Sensor settings Setup Sensor settings Calibration point Multipoint calibration table Calibration point 1-20 Calibration points 1 through 20 for unidirectional flow or calibration points 1 through 20 for bidirectional positive flow. If 0.0 the calibration point is not used. Access level: Expert user only. Note Only available for PID_ProtectCalibrationTable == 1 OR PID_EnableUserCalibrationTable == m 3 /s to m 3 /s 0.0 m 3 /s Setup Sensor settings Multipoint calibration Multipoint calibration table Calibration points Calibration value 1-20 Calibration correction factor that is associated to Calibration points 1 through 20. Access level: Expert user only. 0.5 to Setup Sensor settings Multipoint calibration Multipoint calibration table Calibration value Function Manual, 04/2017, A5E AA

43 3.1 Sensor settings Flow direction The calibrated flow direction is indicated by the arrow on the sensor. If the system requires installation of the sensor with the flow running in the opposite direction, the Flow Direction parameter must be changed from Positive to Negative to totalize correctly. The sensitivity and the accuracy of the sensor do not change with reverse flow. Define positive and negative flow direction. positive flow direction is indicated by the arrow on the sensor. Negative; Positive Positive Setup Sensor settings Flow direction Miscellaneous Preamplifier Preamplifier settings Access level: Expert user only Auto (default): Will automatically turn on the pre-amplifier if the sensor type is clamp-on. Off: Turns off the pre-amplifier regardless of the sensor type (inline or clamp-on). On: Turns on the pre-amplifier regardless of the sensor type (inline or clamp-on). Half transmit amplitude: Reduces the transmit signal from the default ±10 volts to ±5 volts and turns off the pre-amplifier. This may be necessary for the smaller SONO sensors which can saturate the amplifiers even with the pre-amp off. Auto; Off; On; Half transmit amplitude Auto Setup Sensor settings Miscellaneous Preamplifier Number of pulses to be transmitted The number of pulses to configure optimum signal processing. Function Manual, 04/2017, A5E AA 41

44 3.1 Sensor settings Access level: Expert user only. 1 to 10 5 Setup Sensor settings Miscellaneous Number of pulses to be transmitted Minimum ringdown delay The minimum ringdown delay is needed for optimized signal processing. Access level: Expert user only. Read only. The minimum ringdown delay setting for optimized signal processing is: μs Electronic time delay The time delay induced by the DSL electronics. Access level: Expert user only. Read only. The time delay induced by the DSL electronincs is: μs Configuration of test blocks About NOTICE Configuration data overwrite error Running the test block configuration procedure will overwrite any existing sensor configuration. Do not run the test block configuration procedure if configuration data is needed. Back up and record data as necessary. 42 Function Manual, 04/2017, A5E AA

45 3.2 Process values The wizard configures the device for use with the Siemens sensor test blocks including sensor size and sensor path. It also allows for saving the setting Sensor size Sensor size Sensor path A1 1; 2 A2 1; 2 B1 1; 2 B2 1; 2 B3 1; 2 C1 1; 2 C2 1; 2 C3 1; 2 D1 1; 2 D2 1; 2 D3 1; 2 Save settings After settings are complete, press the right arrow to save sensor test block settings. 3.2 Process values Volume flow Units Select units for displayed volume flow rate. Units are not applied at communication interface. Function Manual, 04/2017, A5E AA 43

46 3.2 Process values l/s (liters per second); l/min (liters per minute); l/h (liters per hour); I/d (liters per day); Ml/d (million liters per day); hi/s (hectoliters per second); hi/min (hectoliters per minute); hi/min (hectoliters per hour); hi/min (hectoliters per day); m³/s (cubic meters per second); m³/min (cubic meters per minute); m³/h (cubic meters per hour); m³/d (cubic meters per day); Mm 3 /d (million cubic meters per day); gal/s (US gallons per second); gal/min (US gallons per minute); gal/h (US gallons per hour); gal/d (US gallons per day); Mgal/d (million US gallons per day); i.gal/s (Imperial gallons per second); i.gal/min (Imperial gallons per minute); i.gal/h (Imperial gallons per hour); i.gal/d (Imperial gallons per day); BBL31/s (1 barrel = 31 US gallons); BBL31/min (1 barrel = 31 US gallons); BBL31/h (1 barrel = 31 US gallons); BBL31/d (1 barrel = 31 US gallons); BBL42/s (1 barrel = 42 US gallons); BBL42/min (1 barrel = 42 US gallons); BBL42/h (1 barrel = 42 US gallons); BBL42/d (1 barrel = 42 US gallons); KBBL42/d (Thousand barrels per day); MBBL42/d (million barrels per day); BBL31.5/s (1 barrel=31.5 US gallons); BBL31.5/min (1 barrel=31.5 US gallons); BBL31.5/h (1 barrel=31.5 US gallons); BBL31.5/d (1 barrel=31.5 US gallons); ft³/s (cubic feet per second); ft³/min (cubic feet per minute); ft³/h (cubic feet per hour); ft³/d (cubic feet per day); Mft 3 /d (million cubic feet per day); af/min (acre-feet per minute); af/h (acre-feet per hour); af/d (acre-feet per day); in 3 /sec (cubic inches per second); in 3 /min (cubic inches per minute); in 3 /h (cubic inches per hour); in 3 /d (cubic inches per day); yd 3 /s (cubic yards per second); yd 3 /min (cubic yards per minute); yd 3 /h (cubic yards per hour); yd 3 /d (cubic yards per day); bush/s (bushels per second); bush/min (bushels per minute); bush/h (bushels per hour); bush/d (bushels per day); custom units (see Custom units / Custom conversion factor) m³/h (cubic meters per hour) Setup Process values Volume flow Units Custom units User specific text string for volume flow unit values. The custom units can then be selected in volume flow units. - - Setup Process values Volume flow Custom units Custom conversion factor Conversion factor for user specific standard volume flow values related to SI m³/s Function Manual, 04/2017, A5E AA

47 3.2 Process values Setup Process values Volume flow Custom conversion factor Decimal places Sets the decimal places for the process value displayed in the local display. Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal places; 5 decimal places; 6 decimal places 2 decimal places Setup Process values Standard volume flow Decimal places Low flow cut-off Volume flow limit for low flow cut off. Below limit volume flow output is forced to zero m 3 /h to m 3 /h (depends on sensor) 0.1% of maximum flow (depends on sensor) Setup Process values Volume flow Low flow cut-off Alarm and warning limits Upper alarm limit Set Upper alarm limit. Alarm is triggered if measured value is above the limit m 3 /h to m 3 /h m 3 /h Setup Process values Volume flow Alarm and warning limits Upper alarm limit Function Manual, 04/2017, A5E AA 45

48 3.2 Process values Upper warning limit Exceeding this limit causes a warning m 3 /h to m 3 /h m 3 /h Setup Process values Volume flow Alarm and warning limits Upper warning limit Lower warning limit Falling below this limit causes a warning m 3 /h to m 3 /h m 3 /h Setup Process values Volume flow Alarm and warning limits Lower warning limit Lower alarm limit Set Lower alarm limit. Alarm is triggered if measured value is below the limit m 3 /h to m 3 /h m 3 /h Setup Process values Volume flow Alarm and warning limits Lower alarm limit Hysteresis Sets the hysteresis for alarm and warning limits. The hysteresis is the distance between the limits for activation and deactivation of an alarm/warning m 3 /h to m 3 /h 0.0 m 3 /h 46 Function Manual, 04/2017, A5E AA

49 3.2 Process values Setup Process values Volume flow Alarm and warning limits Hysteresis Mass flow Units Select units for displayed mass flow rate. Units are not applied at communication interface. g/s (grams per second); g/min (grams per min); g/h (grams per hour); kg/s (kilograms per second); kg/min (kilograms per minute); kg/h (kilograms per hour); kg/d (kilograms per day); t/min (1 t = 1000 kg); t/h (1 t = 1000 kg); t/d (1 t = 1000 kg); STon/min (1 STon = 2000 lb); STon/h (1 STon = 2000 lb); STon/d (1 STon = 2000 lb); T/h (1 T = 2240 lb); T/d (1 T = 2240 lb); lb/s (pounds per second); lb/min (pounds per minute); lb/h (pounds per hour); lb/d (pounds per day); custom units (see Custom units / Custom conversion factor) kg/h (kilograms per hour) Setup Process values Mass flow Units Custom units User specific string for mass flow values. - - Setup Process values Mass flow Custom units Custom conversion factor User specific conversion factor based on SI mass flow units kg/s Function Manual, 04/2017, A5E AA 47

50 3.2 Process values Setup Process values Mass flow Custom conversion factor Decimal places Sets the decimal places for the process value displayed in the local display. Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal places; 5 decimal places; 6 decimal places 2 decimal places Setup Process values Mass flow Decimal places Low flow cut-off Mass flow limit for low flow cut off. Below limit mass flow output is forced to zero to kg/h (depends on sensor) 0.1% of maximum mass flow (depends on sensor) Setup Process values Mass flow Low flow cut-off Alarm and warning limits Upper alarm limit If mass flow value exceeds this limit an alarm is triggered kg/h to kg/h kg/h Setup Process values Mass flow Alarm and warning limits Upper alarm limit 48 Function Manual, 04/2017, A5E AA

51 3.2 Process values Upper warning limit If mass flow value exceeds this limit a warning is triggered kg/h to kg/h kg/h Setup Process values Mass flow Alarm and warning limits Upper warning limit Lower warning limit If the mass flow value falls below this limit a warning is triggered kg/h to kg/h kg/h Setup Process values Mass flow Alarm and warning limits Lower warning limit Lower alarm limit If mass flow value falls below this limit an alarm is triggered kg/h to kg/h kg/h Setup Process values Mass flow Alarm and warning limits Lower alarm limit Hysteresis Sets the hysteresis for alarm and warning limits. The hysteresis is the distance between the limits for activation and deactivation of an alarm/warning. 0.0 kg/h to kg/h 0.0 kg/h Function Manual, 04/2017, A5E AA 49

52 3.2 Process values Setup Process values Mass flow Alarm and warning limits Hysteresis Standard flow volume Units Select units for displayed standard volume flow rate. Units are not applied at communication interface. Nm³/h (normal cubic meters per hour); Nm³/d (cubic meters per day); Sl/s (standard liters per sec.); Sl/min (standard liters per minute); Sl/h (standard liters per hour); SI/d (standard liters per day); Sft³/s (standard cubic feet per sec.); Sft³/min (standard cubic feet per min.); Sft³/h (standard cubic feet per hour); Sft³/d (standard cubic feet per day); Sin 3 /sec (cubic inches per second); Sin 3 /min (cubic inches per min.); Sin 3 /h (cubic inches per hour); Sin 3 /d (cubic inches per day); Custom units (see Custom units / Custom conversion factor) Sm³/s Setup Process values Standard volume flow Units Custom units User specific string for standard volume flow values. - - Setup Process values Standard volume flow Custom units Custom conversion factor Conversion factor for user specific standard volume flow values related to Sm³/s. 50 Function Manual, 04/2017, A5E AA

53 3.2 Process values Setup Process values Standard volume flow Custom conversion factor Decimal places Sets the decimal places for the process value displayed in the local display. Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal places; 5 decimal places; 6 decimal places 2 decimal places Setup Process values Standard volume flow Decimal places Low flow cut-off Standard volume flow limit for low flow cut off. Below limit standard volume flow output is forced to zero. Min. 0.0 Sm 3 /s 0.0 Sm 3 /s Setup Process values Standard volume flow Low flow cut-off Alarms and warning limits Upper alarm limit Exceeding this limit causes an alarm Sm 3 /h to Sm 3 /h Sm 3 /h Function Manual, 04/2017, A5E AA 51

54 3.2 Process values Setup Process values Standard volume flow Alarm and warning limits Upper alarm limit Upper warning limit Exceeding this limit causes a warning Sm 3 /h to Sm 3 /h Sm 3 /h Setup Process values Standard volume flow Alarm and warning limits Upper warning limit Lower warning limit Falling below this limit causes a warning Sm 3 /h to Sm 3 /h Sm 3 /h Setup Process values Standard volume flow Alarm and warning limits Lower warning limit Lower alarm limit Falling below this limit causes an alarm Sm 3 /h to Sm 3 /h Sm 3 /h Setup Process values Standard volume flow Alarm and warning limits Lower alarm limit 52 Function Manual, 04/2017, A5E AA

55 3.2 Process values Hysteresis Hysteresis that affects the alarm and warning limits Sm 3 /h to Sm 3 /h 0.00 Sm 3 /h Setup Process values Standard volume flow Alarm and warning limits Hysteresis Standard temperature Standard temperature - This value is used to calculate the standard process values. 0.0 C (32 F) to C (212.0 F) 15.0 C (59.0 F) Setup Process values Standard volume flow Standard temperature Units Standard pressure Standard pressure - This value is used to calculate standard process values Pa to Pa Pa (pascal) Setup Process values Standard volume flow Standard pressure Air density at standard conditions Air density at standard conditions. This value is used to calculate standard process values kg/m³ to 10.0 kg/m³ 1.0 kg/m³ Function Manual, 04/2017, A5E AA 53

56 3.2 Process values Setup Process values Standard volume flow Air density at standard conditions Flow velocity Units Select units for displayed flow velocity. Units are not applied at communication interface. Units for flow velocity values. m/s (meters per second); m/h (meters per hour); in/s (inches per second); in/min (inches per minute); ft/s (feet per second); ft/min (feet per minute); custom units (see Custom units / Custom conversion factor) m/s (meters per second) Setup Process values Flow velocity Units Custom units User specific text string to define custom unit values. The custom unit can then be selected in the flow velocity units. - - Setup Process values Flow velocity Custom units Custom conversion factor Conversion factor for custom unit flow velocity values based on SI velocity units m/s Function Manual, 04/2017, A5E AA

57 3.2 Process values Setup Process values Flow velocity Custom conversion factor Decimal places Sets the decimal places for the process value displayed in the local display. Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal places; 5 decimal places; 6 decimal places 2 decimal places Setup Process values Flow velocity Decimal places Low flow cut-off Flow velocity limit for low flow cut off. Below limit flow velocity output is forced to zero. Min m/s Setup Process values Flow velocity Low flow cut-off Alarm and warning limits Upper alarm limit If process value exceeds this limit an alarm is triggered m/s to m/s m/s Setup Process values Flow velocity Alarm and warning limits Upper alarm limit Function Manual, 04/2017, A5E AA 55

58 3.2 Process values Upper warning limit If process value exceeds this limit a warning is triggered m/s to m/s m/s Setup Process values Flow velocity Alarm and warning limits Upper warning limit Lower warning limit If process value falls below this limit a warning is triggered m/s to m/s m/s Setup Process values Flow velocity Alarm and warning limits Lower warning limit Lower alarm limit If the process value falls below this limit an alarm is triggered m/s to m/s m/s Setup Process values Flow velocity Alarm and warning limits Lower alarm limit Hysteresis Sets the hysteresis for alarm and warning limits. The hysteresis is the distance between the limits for activation and deactivation of an alarm/warning. 0 m/s to m/s 0.00 m/s 56 Function Manual, 04/2017, A5E AA

59 3.2 Process values Setup Process values Flow velocity Alarm and warning limits Hysteresis Sound velocity Units Select units for displayed sound velocity. Units are not applied at communication interface. m/s (meters per second); m/h (meters per hour); in/s (inches per second); in/min (inches per minute); ft/s (feet per second); ft/min (feet per minute); Custom units (see Custom units / Custom conversion factor) m/s (meters per second) Setup Process values Sound velocity Units Custom units User specific text string to define a name for custom unit values. The custom unit can then be selected in the sound velocity units. Setup Process values Sound velocity Custom units Custom conversion factor Conversion factor for custom unit sound velocity values based on SI velocity units m/s. 1.0 Function Manual, 04/2017, A5E AA 57

60 3.2 Process values Setup Process values Sound velocity Custom conversion factor Decimal places Sets the decimal places for the process value displayed in the local display. Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal places; 5 decimal places; 6 decimal places 2 decimal places Setup Process values Sound velocity Decimal places Alarm and warning limits Upper alarm limit If process value exceeds this limit an alarm is triggered m/s to m/s m/s Setup Process values Sound velocity Alarm and warning limits Upper alarm limit Upper warning limit If process value exceeds this limit a warning is triggered m/s to m/s m/s Setup Process values Sound velocity Alarm and warning limits Upper warning limit 58 Function Manual, 04/2017, A5E AA

61 3.2 Process values Lower warning limit if the process value falls below this limit a warning is triggered m/s to m/s m/s Setup Process values Sound velocity Alarm and warning limits Lower warning limit Lower alarm limit If the process value falls below this limit an alarm is triggered m/s to m/s m/s Setup Process values Sound velocity Alarm and warning limits Lower alarm limit Hysteresis Sets the hysteresis for alarm and warning limits. The hysteresis is the distance between the limits for activation and deactivation of an alarm/warning. 0 m/s to m/s 0.00 m/s Setup Process values Sound velocity Alarm and warning limits Hysteresis Function Manual, 04/2017, A5E AA 59

62 3.2 Process values LiquIdent Alarm and warning limits Upper alarm limit Exceeding this limit causes an alarm m/s to m/s m/s Setup Process values LiquIdent Alarm and warning limits Upper alarm limit Upper warning limit Exceeding this limit causes a warning m/s to m/s m/s Setup Process values LiquIdent Alarm and warning limits Upper warning limit Lower warning limit Falling below this limit causes a warning m/s to m/s m/s Setup Process values LiquIdent Alarm and warning limits Lower warning limit 60 Function Manual, 04/2017, A5E AA

63 3.2 Process values Lower alarm limit Falling below this limit causes an alarm m/s to m/s m/s Setup Process values LiquIdent Alarm and warning limits Lower alarm limit Hysteresis Hysteresis that affects the alarm and warning limits. 0 m/s to m/s 0.0 m/s Setup Process values LiquIdent Alarm and warning limits Hysteresis Temperature slope factor Temperature slope factor - This factor is used in connection with the standard condition temperature for calculating LiquIdent. 0.0 m/(s * K) to 8.0 m/(s * K) 4.1 m/(s * K) Setup Process values LiquIdent Temperature slope factor Pressure slope factor Pressure slope factor - This factor is used in connection with the standard condition pressure to calculate LiquIdent m/(s * Pa) to 0.0 m/(s * Pa) m/(s * Pa) Function Manual, 04/2017, A5E AA 61

64 3.2 Process values Setup Process values LiquIdent Pressure slope factor Density Units Displays units for displayed density. Units are not applied at communication interface. Read only. μg/l (micrograms per liter); μg/m³ (micrograms per cubic meter); mg/l (milligrams per liter); g/ml (grams per milliliter); g/cm³ (grams per cubic centimeters); g/l (grams per liter); kg/l (kilograms per liter); kg/m³ (kilograms per cubic meter); lb/in³ (pounds per cubic inch); lb/gal (pounds per US gallon); lb/ft³ (pounds per cubic foot); STon/yd³ (1 STon = 2000 lb); custom units (see Custom units / Custom conversion factor) kg/m³ (kilograms per cubic meter) Setup Process values Density Units Custom units User specific text string to define custom unit values. The custom unit can then be selected in the density units. Setup Process values Density Custom units Custom conversion factor Conversion factor for custom Density values based on SI density units kg/m Function Manual, 04/2017, A5E AA

65 3.2 Process values Setup Process values Density Custom conversion factor Decimal places Sets the decimal places for the process value displayed in the local display. Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal places; 5 decimal places; 6 decimal places 2 decimal places Setup Process values Density Decimal places Alarm and warning limits Upper alarm limit If density value exceeds this limit an alarm is triggered kg/m³ to kg/m³ kg/m³ Setup Process values Density Alarm and warning limits Upper alarm limit Upper warning limit If density value exceeds this limit a warning is triggered kg/m³ to kg/m³ kg/m³ Setup Process values Density Alarm and warning limits Upper warning limit Function Manual, 04/2017, A5E AA 63

66 3.2 Process values Lower warning limit if density value falls below this limit a warning is triggered kg/m³ to kg/m³ 1.00 kg/m³ Setup Process values Density Alarm and warning limits Lower warning limit Lower alarm limit If density value falls below this limit an alarm is triggered kg/m³ to kg/m³ 1.00 kg/m³ Setup Process values Density Alarm and warning limits Lower alarm limit Hysteresis Sets the hysteresis for alarm and warning limits. The hysteresis is the distance between the limits for activation and deactivation of an alarm/warning kg/m³ to kg/m³ 0.00 kg/m³ Setup Process values Density Alarm and warning limits Hysteresis Kinematic viscosity Units Units for kinematic viscosity. 64 Function Manual, 04/2017, A5E AA

67 3.2 Process values Read only. m 2 /s (square meters per second); cst (1 centistoke = 1 mm 2 /s); St (stokes, 1St = 1cm 2 /s) m 2 /s (square meters per second) Setup Process values Kinematic viscosity Units Decimal places Sets the decimal places for the process value displayed in the local display. Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal places; 5 decimal places; 6 decimal places 2 decimal places Setup Process values Kinematic viscosity Decimal places Alarm and warning limits Upper alarm limit If process value exceeds this limit an alarm is triggered m²/s to m²/s m²/s Setup Process values Standard kinematic viscosity Alarm and warning limits Upper alarm limit Upper warning limit If process value exceeds this limit a warning is triggered m²/s to m²/s m²/s Function Manual, 04/2017, A5E AA 65

68 3.2 Process values Setup Process values Kinematic viscosity Alarm and warning limits Upper warning limit Lower warning limit If process value falls below this limit a warning is triggered m²/s to m²/s m²/s Setup Process values Kinematic viscosity Alarm and warning limits Lower warning limit Lower alarm limit If process value falls below this limit an alarm is triggered m²/s to m²/s m²/s Setup Process values Kinematic viscosity Alarm and warning limits Lower alarm limit Hysteresis Sets the hysteresis for alarm and warning limits. The hysteresis is the distance between the limits for activation and deactivation of an alarm/warning m²/s to m²/s 0.00 m²/s Setup Process values Kinematic viscosity Alarm and warning limits Hysteresis 66 Function Manual, 04/2017, A5E AA

69 3.2 Process values Pressure Units Select units for displayed pressure. Units are not applied at communication interface. mbar (millibar); bar; Pa (pascals); kpa (kilopascals); MPa (Megapascals); psi (pounds per square inch); kgf/cm² (kilogram force per square cm); mmh2o (millimeters of water at 68 F); inh2o (inches of water at 68 F); fth2o (feet of water at 68 F); mmh2o (millimeters of water at 4 C); inh2o (inches of water at 4 C); mmhg (millimeters of mercury at 0 C); inhg (inches of mercury at 0 C); hpa (hectopascal); atm (atmosphere); torr; cmh2o (centimeters of water at 4 C); mh2o (meters of water at 4 C); cmhg (centimeters of mercury at 0 C); mhg (meters of mercury at 0 C); gf/cm² (grams force per square cm); kg/m² (kilograms per square meter); lb/ft² (pounds per square foot); fth2o (feet water at 4 C); fth2o (feet water at 60 F) Pa (pascals) Setup Process values Pressure Units Decimal places Sets the decimal places for the process value displayed in the local display. Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal places; 5 decimal places; 6 decimal places 2 decimal places Setup Process values Pressure Decimal places Alarm and warning limits Upper alarm limit If process value exceeds this limit an alarm is triggered Pa to Pa Pa Function Manual, 04/2017, A5E AA 67

70 3.2 Process values Setup Process values Pressure Alarm and warning limits Upper alarm limit Upper warning limit If process value exceeds this limit a warning is triggered Pa to Pa Pa Setup Process values Pressure Alarm and warning limits Upper warning limit Lower warning limit If the process value falls below this limit a warning is triggered Pa to Pa Pa Setup Process values Pressure Alarm and warning limits Lower warning limit Lower alarm limit if process value falls below this limit an alarm is triggered Pa to Pa Pa Setup Process values Pressure Alarm and warning limits Lower alarm limit 68 Function Manual, 04/2017, A5E AA

71 3.2 Process values Hysteresis Sets the hysteresis for alarm and warning limits. The hysteresis is the distance between the limits for activation and deactivation of an alarm/warning. 0 Pa to Pa 0.00 Pa Setup Process values Pressure Alarm and warning limits Hysteresis Medium temperature Units Select units for displayed temperature. Units are not applied at communication interface. C (degrees Celsius); F (degrees Fahrenheit); R (degrees Rankine); K (kelvins) C (degrees Celsius) Setup Process values Medium temperature Units Decimal places Sets the decimal places for the process value displayed in the local display. Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal places; 5 decimal places; 6 decimal places 2 decimal places Setup Process values Medium temperature Decimal places Function Manual, 04/2017, A5E AA 69

72 3.2 Process values Alarm and warning limits Upper alarm limit Exceeding this limit causes an alarm to C C Setup Process values Medium temperature Alarm and warning limits Upper alarm limit Upper warning limit Exceeding this limit causes a warning to C C Setup Process values Medium temperature Alarm and warning limits Upper warning limit Lower warning limit Falling below this limit causes a warning to C C Setup Process values Medium temperature Alarm and warning limits Lower warning limit 70 Function Manual, 04/2017, A5E AA

73 3.2 Process values Lower alarm limit Falling below this limit causes an alarm to C C Setup Process values Medium temperature Alarm and warning limits Lower alarm limit Hysteresis Sets the hysteresis for alarm and warning limits. The hysteresis is the distance between the limits for activation and deactivation of an alarm/warning C to C 0.00 C Setup Process values Medium temperature Alarm and warning limits Hysteresis Standard density Units Select units for displayed standard density. Units are not applied at communication interface. μg/l (micrograms per liter); μg/m³ (micrograms per cubic meter); mg/l (milligrams per liter); g/ml (grams per milliliter); g/cm³ (grams per cubic centimeters); g/l (grams per liter); kg/l (kilograms per liter); kg/m³ (kilograms per cubic meter); lb/in³ (pounds per cubic inch); lb/gal (pounds per US gallon); lb/ft³ (pounds per cubic foot); STon/yd³ (1 STon = 2000 lb); custom unit (see Custom density unit string / factor) kg/m³ (kilograms per cubic meter) Function Manual, 04/2017, A5E AA 71

74 3.2 Process values Setup Process values Standard density Units Decimal places Decimal places Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal places; 5 decimal places; 6 decimal places 2 decimal places Setup Process values Standard density Decimal places Alarm and warning limits Upper alarm limit Exceeding this limit causes an alarm kg/m³ to kg/m³ kg/m³ Setup Process values Standard density Alarm and warning limits Upper alarm limit Upper warning limit Exceeding this limit causes a warning kg/m³ to kg/m³ kg/m³ Setup Process values Standard density Alarm and warning limits Upper warning limit 72 Function Manual, 04/2017, A5E AA

75 3.2 Process values Lower warning limit Falling below this limit causes a warning kg/m³ to kg/m³ 1.00 kg/m³ Setup Process values Standard density Alarm and warning limits Lower warning limit Lower alarm limit Falling below this limit causes an alarm kg/m³ to kg/m³ 1.00 kg/m³ Setup Process values Standard density Alarm and warning limits Lower alarm limit Hysteresis Hysteresis that affects the alarm and warning limits kg/m³ to kg/m³ 0.00 kg/m³ Setup Process values Standard density Alarm and warning limits Hysteresis Function Manual, 04/2017, A5E AA 73

76 3.2 Process values Standard kinematic viscosity Units Select unit for displayed standard kinematic viscosity. Unit is not applied at communication interface. Read only. m 2 /s (square meters per second); cst (1 centistoke = 1 mm 2 /s); St (stokes, 1 St = 1cm 2 /s) m 2 /s (square meters per second) Setup Process values Standard kinematic viscosity Units Decimal places Sets the decimal places for the process value displayed in the local display. Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal places; 5 decimal places; 6 decimal places 2 decimal places Setup Process values Standard kinematic viscosity Decimal places Alarm and Warning limits Upper alarm limit Exceeding this limit causes an alarm m²/s to m²/s m²/s Setup Process values Standard kinematic viscosity Alarm and warning limits Upper alarm limit 74 Function Manual, 04/2017, A5E AA

77 3.2 Process values Upper warning limit Exceeding this limit causes a warning m²/s to m²/s m²/s Setup Process values Standard kinematic viscosity Alarm and warning limits Upper warning limit Lower warning limit Falling below this limit causes a warning m²/s to m²/s m²/s Setup Process values Standard kinematic viscosity Alarm and warning limits Lower warning limit Lower alarm limit Falling below this limit causes an alarm m²/s to m²/s m²/s Setup Process values Standard kinematic viscosity Alarm and warning limits Lower alarm limit Hysteresis Sets the hysteresis for alarm and warning limits. The hysteresis is the distance between the limits for activation and deactivation of an alarm/warning. Function Manual, 04/2017, A5E AA 75

78 3.2 Process values 0.00 m²/s to m²/s 0.00 m²/s Setup Process values Standard kinematic viscosity Alarm and warning limits Hysteresis API gravity Alarm and warning limits Upper alarm limit Exceeding this limit causes an alarm API to API API Setup Process values API gravity Alarm and warning limits Upper alarm limit Upper warning limit Exceeding this limit causes a warning API to API API Setup Process values API gravity Alarm and warning limits Upper warning limit Lower warning limit Falling below this limit causes a warning. 76 Function Manual, 04/2017, A5E AA

79 3.2 Process values API to API API Setup Process values API gravity Alarm and warning limits Lower warning limit Lower alarm limit Falling below this limit causes an alarm API to API API Setup Process values API gravity Alarm and warning limits Lower alarm limit Hysteresis Hysteresis that affects the alarm and warning limits API to API 0.00 API Setup Process values API gravity Alarm and warning limits Hysteresis Standard API gravity Alarm and warning limits Upper alarm limit Exceeding this limit causes an alarm. Function Manual, 04/2017, A5E AA 77

80 3.2 Process values API to API API Setup Process values Standard API gravity Alarm and warning limits Upper alarm limit Upper warning limit Exceeding this limit causes a warning API to API API Setup Process values Standard API gravity Alarm and warning limits Upper warning limit Lower warning limit Falling below this limit causes a warning API to API API Setup Process values Standard API gravity Alarm and warning limits Lower warning limit Lower alarm limit Falling below this limit causes an alarm API to API API 78 Function Manual, 04/2017, A5E AA

81 3.2 Process values Setup Process values Standard API gravity Alarm and warning limits Lower alarm limit Hysteresis Hysteresis that affects the alarm and warning limits API to API 0.00 API Setup Process values Standard API gravity Alarm and warning limits Hysteresis Specific gravity Alarm and warning limits Upper alarm limit Exceeding this limit causes an alarm SGU to SGU SGU Setup Process values Specific gravity Alarm and warning limits Upper alarm limit Upper warning limit Exceeding this limit causes a warning SGU to SGU SGU Function Manual, 04/2017, A5E AA 79

82 3.2 Process values Setup Process values Specific gravity Alarm and warning limits Upper warning limit Lower warning limit Falling below this limit causes a warning SGU to SGU SGU Setup Process values Specific gravity Alarm and warning limits Lower warning limit Lower alarm limit Falling below this limit causes an alarm SGU to SGU SGU Setup Process values Specific gravity Alarm and warning limits Lower alarm limit Hysteresis Hysteresis that affects the alarm and warning limits SGU to SGU 0.00 SGU Setup Process values Specific gravity Alarm and warning limits Hysteresis 80 Function Manual, 04/2017, A5E AA

83 3.2 Process values Standard specific gravity Alarm and warning limits Upper alarm limit Exceeding this limit causes an alarm SGU to SGU SGU Setup Process values Standard specific gravity Alarm and warning limits Upper alarm limit Upper warning limit Exceeding this limit causes a warning SGU to SGU SGU Setup Process values Standard specific gravity Alarm and warning limits Upper warning limit Lower warning limit Falling below this limit causes a warning SGU to SGU SGU Setup Process values Standard specific gravity Alarm and warning limits Lower warning limit Function Manual, 04/2017, A5E AA 81

84 3.3 Totalizers Lower alarm limit Falling below this limit causes an alarm SGU to SGU SGU Setup Process values Standard specific gravity Alarm and warning limits Lower alarm limit Hysteresis Hysteresis that affects the alarm and warning limits SGU to SGU 0.00 SGU Setup Process values Standard specific gravity Alarm and warning limits Hysteresis 3.3 Totalizers Totalizer Process value Select the process value to be totalized. Mass flow; Volume flow; Standard volume flow (only Hydrocarbon and gas applications) Mass flow Setup Totalizers Totalizer 1 Process value 82 Function Manual, 04/2017, A5E AA

85 3.3 Totalizers Units Select units for displayed Totalizer 1. The set of units depends on the selected process value. Units are not applied at communication interface. Process value = Mass flow: g (grams); kg (kilograms); t (1 t = 1000 kg); STon (1 STon = 2000 lb); T (1 T = 2240 lb); oz (ounces); lb (pounds); Process value = Volume flow: l (liters); hl (hectoliters); m³ (cubic meters); gal (US gallons); i.gal (Imperial gallons); BBL31.5 (1 barrel = 31.5 US gallons); BBL31 (1 barrel = 31 US gallons); BBL42 (1 barrel = 42 US gallons); in³ (cubic inches); ft³ (cubic feet); yd³ (cubic yards);bush (bushels); Process value = Standard volume flow: Nl (normal liters); Nm³ (normal cubic meters); Sl (standard liters); Sft³ (standard cubic feet); Sm³ (standard cubic meters); custom units (see Custom units / Custom conversion factor) kg (kilograms) Setup Totalizers Totalizer 1 Units Custom units User specific string to define custom unit Totalizer 1 values. - - Setup Totalizers Toalizer 1 Custom units Custom conversion factor Conversion factor for user specific standard mass flow values related to SI kg Setup Totalizers Totalizer 1 Custom conversion factor Function Manual, 04/2017, A5E AA 83

86 3.3 Totalizers Decimal places Sets the decimal places for the process value displayed in the local display. Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal places; 5 decimal places; 6 decimal places 2 decimal places Setup Totalizers Totalizer 1 Decimal places Direction Totalizer 1 direction. Forward and backward; Forward; Backward; Hold Forward Setup Totalizers Totalizer 1 Direction Fail-safe behaviour Behaviour of the totalizer during the occurrence of bad input value. RUN; totalization is continued using the bad input value; HOLD; totalization is stopped; MEMORY; totalization is continued based on the last incoming good value RUN; totalization is continued using the bad input value Setup Totalizers Totalizer 1 Fail safe mode Reset Reset totalizer to zero. Cancel; OK Cancel 84 Function Manual, 04/2017, A5E AA

87 3.3 Totalizers Setup Totalizers Totalizer 1 Reset Preset Reset Totalizer 1 to selected preset value. After selecting OK the user is asked for the PRESET value. The PRESET value units depend on the selected Process value. Therefore the range of the Preset value is for: Mass flow: kg to kg Volume flow: m³ to m³ Standard volume flow: Sm³ to Sm³ Cancel; OK Cancel Setup Totalizers Totalizer 1 Preset Alarm and warning limits Upper alarm limit Alarm is triggered if Totalizer 1 value is above the limit. Process value = Mass flow: kg to kg Process value = Volume flow: m³ to m³ Process value = Standard volume flow: Sm³ to Sm³ Process value = Mass flow: kg Process value = Volume flow: m³ Process value = Standard volume flow: Sm³ Setup Totalizers Totalizer 1 Alarm and warning limits Upper alarm limit Function Manual, 04/2017, A5E AA 85

88 3.3 Totalizers Upper warning limit Warning is triggered if Totalizer 1 value is above the limit. Process value = Mass flow: kg to kg Process value = Volume flow: m³ to m³ Process value = Standard volume flow: Sm³ to Sm³ Process value = Mass flow: kg Process value = Volume flow: m³ Process value = Standard volume flow: Sm³ Setup Totalizers Totalizer 1 Alarm and warning limits Upper warning limit Lower warning limit Warning is triggered if Totalizer 1 value is below the limit. Process value = Mass flow: kg to kg Process value = Volume flow: m³ to m³ Process value = Standard volume flow: Sm³ to Sm³ Process value = Mass flow: kg Process value = Volume flow: m³ Process value = Standard volume flow: Sm³ Setup Totalizers Totalizer 1 Alarm and warning limits Lower warning limit Lower alarm limit Alarm is triggered if Totalizer 1 value is below the limit. Process value = Mass flow: kg to kg Process value = Volume flow: m³ to m³ Process value = Standard volume flow: Sm³ to Sm³ Process value = Mass flow: kg Process value = Volume flow: m³ Process value = Standard volume flow: Sm³ Setup Totalizers Totalizer 1 Alarm and warning limits Lower alarm limit 86 Function Manual, 04/2017, A5E AA

89 3.3 Totalizers Hysteresis Hysteresis sets the alarm and warning limits. The hysterious is the distance between the limits for activation and deactivation of an alarm/warning. Process value = Mass flow: 0.00 kg to kg Process value = Volume flow: 0.00 m³ to m³ Process value = Standard volume flow: 0.00 Sm³ to Sm³ Process value = Mass flow: 0.00 kg Process value = Volume flow: 0.00 m³ Process value = Standard volume flow: 0.00 Sm³ Setup Totalizers Totalizer 1 Alarm and warning limits Hysteresis Totalizer Process value Select the process value to be totalized. Mass flow; Volume flow; Standard volume flow (only Hydrocarbon and gas applications) Mass flow Setup Totalizers Totalizer 2 Process value Units Select units for displayed Totalizer 2. The set of units depends on the selected process value. Units are not applied at communication interface. Function Manual, 04/2017, A5E AA 87

90 3.3 Totalizers Process value = Mass flow: g (grams); kg (kilograms); t (1 t = 1000 kg); STon (1 STon = 2000 lb); T (1 T = 2240 lb); oz (ounces); lb (pounds); Process value = Volume flow: l (liters); hl (hectoliters); m³ (cubic meters); gal (US gallons); i.gal (Imperial gallons); BBL31.5 (1 barrel = 31.5 US gallons); BBL31 (1 barrel = 31 US gallons); BBL42 (1 barrel = 42 US gallons); in³ (cubic inches); ft³ (cubic feet); yd³ (cubic yards);bush (bushels); Process value = Standard volume flow: Nl (normal liters); Nm³ (normal cubic meters); Sl (standard liters); Sft³ (standard cubic feet); Sm³ (standard cubic meters); custom units (see Custom units / Custom conversion factor) kg (kilograms) Setup Totalizers Totalizer 2 Units Custom units User specific string to define custom unit Totalizer 2 values. - - Setup Totalizers Totalizer 2 Custom units Custom conversion factor Conversion factor for user specific standard mass flow values related to SI mass units kg Setup Totalizers Totalizer 2 Custom conversion factor Decimal places Sets the decimal places for the process value displayed in the local display. 88 Function Manual, 04/2017, A5E AA

91 3.3 Totalizers Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal places; 5 decimal places; 6 decimal places 2 decimal places Setup Totalizers Totalizer 2 Decimal places Direction Totalizer 2 direction. Forward and backward; Forward; Backward; Hold Forward Setup Totalizers Totalizer 2 Direction Fail safe behaviour Behavior of the totalizer during the occurrence of bad input value. RUN; totalization is continued using the bad input value; HOLD; totalization is stopped; MEMORY; totalization is continued based on the last incoming good value RUN; totalization is continued using the bad input value Setup Totalizers Totalizer 2 Fail safe behaviour Reset Reset totalizer to zero. Cancel; OK Cancel Setup Totalizers Totalizer 2 Reset Function Manual, 04/2017, A5E AA 89

92 3.3 Totalizers Preset Reset Totalizer 2 to selected preset value. After selecting OK the user is asked for the PRESET value. The PRESET value units depend on the selected Process value. Therefore the range of the Preset value is for: Mass flow: kg to kg Volume flow: m³ to m³ Standard volume flow: Sm³ to Sm³ Cancel; OK Cancel Setup Totalizers Totalizer 2 Preset Alarm and warning limits Upper alarm limit Alarm is triggered if Totalizer 2 value is above the limit. Process value = Mass flow: kg to kg Process value = Volume flow: m³ to m³ Process value = Standard volume flow: Sm³ to Sm³ Process value = Mass flow: kg Process value = Volume flow: m³ Process value = Standard volume flow: Sm³ Setup Totalizers Totalizer 2 Alarm and warning limits Upper alarm limit Upper warning limit Warning is triggered if Totalizer 2 value is above the limit. 90 Function Manual, 04/2017, A5E AA

93 3.3 Totalizers Process value = Mass flow: kg to kg Process value = Volume flow: m³ to m³ Process value = Standard volume flow: Sm³ to Sm³ Process value = Mass flow: kg Process value = Volume flow: m³ Process value = Standard volume flow: Sm³ Setup Totalizers Totalizer 2 Alarm and warning limits Upper warning limit Lower warning limit Warning is triggered if Totalizer 2 value is below the limit. Process value = Mass flow: kg to kg Process value = Volume flow: m³ to m³ Process value = Standard volume flow: Sm³ to Sm³ Process value = Mass flow: kg Process value = Volume flow: m³ Process value = Standard volume flow: Sm³ Setup Totalizers Totalizer 2 Alarm and warning limits Lower warning limit Lower alarm limit Alarm is triggered if Totalizer 2 value is below the limit. Process value = Mass flow: kg to kg Process value = Volume flow: m³ to m³ Process value = Standard volume flow: Sm³ to Sm³ Process value = Mass flow: kg Process value = Volume flow: m³ Process value = Standard volume flow: Sm³ Setup Totalizers Totalizer 2 Alarm and warning limits Lower alarm limit Function Manual, 04/2017, A5E AA 91

94 3.3 Totalizers Hysteresis Hysteresis sets the alarm and warning limits. The hysterious is the distance between the limits for activation and deactivation of an alarm/warning. Process value = Mass flow: 0.00 kg to kg Process value = Volume flow: 0.00 m³ to m³ Process value = Standard volume flow: 0.00 Sm³ to Sm³ Process value = Mass flow: 0.00 kg Process value = Volume flow: 0.00 m³ Process value = Standard volume flow: 0.00 Sm³ Setup Totalizers Totalizer 2 Alarm and warning limits Hysteresis Totalizer Process value Select the cut-off filtered process value to be totalized. Mass flow; Volume flow; Standard volume flow (only Hydrocarbon and gas applications) Mass flow Setup Totalizers Totalizer 3 Process value Units Select units for displayed Totalizer 3. The set of units depends on the selected process value. Units are not applied at communication interface. 92 Function Manual, 04/2017, A5E AA

95 3.3 Totalizers Process value = Mass flow: g (grams); kg (kilograms); t (1 t = 1000 kg); STon (1 STon = 2000 lb); T (1 T = 2240 lb); oz (ounces); lb (pounds); Process value = Volume flow: l (liters); hl (hectoliters); m³ (cubic meters); gal (US gallons); i.gal (Imperial gallons); BBL31.5 (1 barrel = 31.5 US gallons); BBL31 (1 barrel = 31 US gallons); BBL42 (1 barrel = 42 US gallons); in³ (cubic inches); ft³ (cubic feet); yd³ (cubic yards);bush (bushels); Process value = Standard volume flow: Nl (normal liters); Nm³ (normal cubic meters); Sl (standard liters); Sft³ (standard cubic feet); Sm³ (standard cubic meters); custom units (see Custom units / Custom conversion factor) kg (kilograms) Setup Totalizers Totalizer 3 Units Custom units User specific string to define custom unit Totalizer 3 values. - - Setup Totalizers Totalizer 3 Custom units Custom conversion factor Conversion factor for user specific standard mass flow values related to SI mass units kg Setup Totalizers Totalizer 3 Custom conversion factor Decimal places Sets the decimal places for the process value displayed in the local display. Function Manual, 04/2017, A5E AA 93

96 3.3 Totalizers Auto; No decimal place; 1 decimal place; 2 decimal places; 3 decimal places; 4 decimal places; 5 decimal places; 6 decimal places 2 decimal places Setup Totalizers Totalizer 3 Decimal places Direction Totalizer 3 direction. Forward and backward; Forward; Backward; Hold Forward Setup Totalizers Totalizer 3 Direction Fail-safe behaviour Behavior of the totalizer during the occurrence of bad input value. RUN; totalization is continued using the bad input value; HOLD; totalization is stopped; MEMORY; totalization is continued based on the last incoming good value RUN; totalization is continued using the bad input value Setup Totalizers Totalizer 3 Fail safe mode Reset Reset totalizer to zero. Cancel; OK Cancel Setup Totalizers Totalizer 3 Reset 94 Function Manual, 04/2017, A5E AA

97 3.3 Totalizers Preset Reset Totalizer 3 to selected preset value. After selecting OK the user is asked for the PRESET value. The PRESET value units depend on the selected Process value. Therefore the range of the Preset value is for: Mass flow: kg to kg Volume flow: m³ to m³ Standard volume flow: Sm³ to Sm³ Cancel; OK Cancel Setup Totalizers Totalizer 3 Preset Alarm and warning limits Upper alarm limit Alarm is triggered if Totalizer 3 value is above the limit. Process value = Mass flow: kg to kg Process value = Volume flow: m³ to m³ Process value = Standard volume flow: Sm³ to Sm³ Process value = Mass flow: kg Process value = Volume flow: m³ Process value = Standard volume flow: Sm³ Setup Totalizers Totalizer 3 Alarm and warning limits Upper alarm limit Upper warning limit Warning is triggered if Totalizer 3 value is above the limit. Function Manual, 04/2017, A5E AA 95

98 3.3 Totalizers Process value = Mass flow: kg to kg Process value = Volume flow: m³ to m³ Process value = Standard volume flow: Sm³ to Sm³ Process value = Mass flow: kg Process value = Volume flow: m³ Process value = Standard volume flow: Sm³ Setup Totalizers Totalizer 3 Alarm and warning limits Upper warning limit Lower warning limit Warning is triggered if Totalizer 3 value is below the limit. Process value = Mass flow: kg to kg Process value = Volume flow: m³ to m³ Process value = Standard volume flow: Sm³ to Sm³ Process value = Mass flow: kg Process value = Volume flow: m³ Process value = Standard volume flow: Sm³ Setup Totalizers Totalizer 3 Alarm and warning limits Lower warning limit Lower alarm limit Alarm is triggered if Totalizer 3 value is below the limit. Process value = Mass flow: kg to kg Process value = Volume flow: m³ to m³ Process value = Standard volume flow: Sm³ to Sm³ Process value = Mass flow: kg Process value = Volume flow: m³ Process value = Standard volume flow: Sm³ Setup Totalizers Totalizer 3 Alarm and warning limits Lower alarm limit 96 Function Manual, 04/2017, A5E AA

99 3.4 Inputs and outputs Hysteresis Hysteresis sets the alarm and warning limits. The hysterious is the distance between the limits for activation and deactivation of an alarm/warning. Process value = Mass flow: 0.00 kg to kg Process value = Volume flow: 0.00 m³ to m³ Process value = Standard volume flow: 0.00 Sm³ to Sm³ Process value = Mass flow: 0.00 kg Process value = Volume flow: 0.00 m³ Process value = Standard volume flow: 0.00 Sm³ Setup Totalizers Totalizer 3 Alarm and warning limits Hysteresis Reset all totalizers Reset command to reset totalizers 1 to 3 to zero. Cancel; OK Cancel Setup Totalizers Reset all totalizers 3.4 Inputs and outputs The available configuration of the hardware functionality of input and output is described in the following table. Table 3-1 Hardware and software configuration of the input/output channels Channel HW configuration (fixed when ordering) SW configuration available to the user 1 Current output Current (4-20 ma) HART 1 Modbus Modbus Function Manual, 04/2017, A5E AA 97

100 3.4 Inputs and outputs Channel HW configuration (fixed when ordering) 2 Signal output Outputs: 3 Signal input/output Inputs: SW configuration available to the user Current output (0/4-20 ma) Frequency ouput Pulse output Status output Alarm class Alarm item NAMUR status signals Current input (0/4-20 ma) Digital input: Totalizer reset Remote zero adjust Force outputs Freeze process values Outputs: Current output (0/4-20 ma) Frequency ouput Pulse output Status output Alarm class Alarm item NAMUR status signals Relay output Status Output: Alarm class Alarm item NAMUR status signals 98 Function Manual, 04/2017, A5E AA

101 3.4 Inputs and outputs Channel HW configuration (fixed when ordering) 4 Signal input/output Inputs: SW configuration available to the user Current input (0/4-20 ma) Digital input: Totalizer reset Remote zero adjust Force outputs Freeze process values Outputs: Current output (0/4-20 ma) Frequency ouput Pulse output Status output Alarm class Alarm item NAMUR status signals Relay output Status Output: Alarm class Alarm item NAMUR status signals Current output All four channels can be configured as current output. Current output configuration The following process values can be assigned to the current output: Volume flow Mass flow Sound velocity Flow velocity Density Medium temperature Pressure Kinematic viscosity The following process values are additionally available in devices for oil applications: Standard volume flow Standard kinematic viscosity Standard density Function Manual, 04/2017, A5E AA 99

102 3.4 Inputs and outputs LiquIdent - Available with Oil software option only. API gravity Standard API gravity Specific gravity Standard specific gravity All process variables are available through Channels 1 to 4. The accuracy specified for the analog output signal applies only within the range 4 to 20 ma. Lower limit (4 ma) and upper limit (20 ma) can be assigned to any specific flow values Linear control range Lower saturation limit Upper saturation limit Lower fault current value Recommended setting range for lower fault current Recommended setting range for upper fault current Measuring range Figure 3-1 Current limits for NAMUR configuration The fail safe current output signal can be selected to: Lower fault current (defined in the Loop current scale selection) Upper fault current (defined in the Loop current scale selection) Last valid value (the last process value before the failure occurred) Current value (actual measured value) Fail-safe value (within the range of 0 ma to 25 ma 1) ) 100 Function Manual, 04/2017, A5E AA

Installing the assembly SIMATIC. Installing the assembly. Overview 1. Installing the assembly. Getting Started A5E

Installing the assembly SIMATIC. Installing the assembly. Overview 1. Installing the assembly. Getting Started A5E Overview 1 2 SIMATIC Getting Started 03/2013 A5E03973659-01 Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as

More information

SITRANS F. Ultrasonic Flowmeters FST030 (HART) Operating Instructions. Answers for industry. 07/2017. Edition

SITRANS F. Ultrasonic Flowmeters FST030 (HART) Operating Instructions. Answers for industry. 07/2017. Edition SITRANS F Ultrasonic Flowmeters Operating Instructions Edition 07/2017 Answers for industry. Introduction 1 Safety notes 2 SITRANS F Ultrasonic flowmeters Operating Instructions Description 3 Installing/Mounting

More information

SITRANS F. Ultrasonic Flowmeters FST030 (HART) Operating Instructions. Answers for industry. 02/2017. Edition

SITRANS F. Ultrasonic Flowmeters FST030 (HART) Operating Instructions. Answers for industry. 02/2017. Edition SITRANS F Ultrasonic Flowmeters Operating Instructions Edition 02/2017 Answers for industry. Introduction 1 Safety notes 2 SITRANS F Ultrasonic flowmeters Operating Instructions Description 3 Installing/Mounting

More information

SITRANS. Temperature transmitter Functional safety for SITRANS TW. Introduction. General safety instructions 2. Device-specific safety instructions

SITRANS. Temperature transmitter Functional safety for SITRANS TW. Introduction. General safety instructions 2. Device-specific safety instructions Introduction 1 General safety instructions 2 SITRANS Temperature transmitter Device-specific safety instructions 3 Appendix List of Abbreviations/Acronyms A B Product Information Supplement to Operating

More information

FloCat MFE Electromagnetic Flow Meter PRODUCT MANUAL

FloCat MFE Electromagnetic Flow Meter PRODUCT MANUAL FloCat MFE Electromagnetic Flow Meter PRODUCT MANUAL Flocat Electromagnetic Flowmeter Operation Manual Table of Contents Part 1. 3-line Display on Transmitter 2 Main Interface. 2 Part 2. Programming Guide...

More information

User Guide OI/FEX100HART EN Rev. A. WaterMaster FEX100 HART Field Device Specification

User Guide OI/FEX100HART EN Rev. A. WaterMaster FEX100 HART Field Device Specification User Guide OI/FEX100HART EN Rev. A WaterMaster FEX100 The Company We are an established world force in the design and manufacture of measurement products for industrial process control, flow measurement,

More information

Operating Instructions Edition 11/2005. Process monitoring Ex-barrier for Diagnostics Unit SITRANS DA400 7MJ2010-1AA. sitrans

Operating Instructions Edition 11/2005. Process monitoring Ex-barrier for Diagnostics Unit SITRANS DA400 7MJ2010-1AA. sitrans Operating Instructions Edition 11/2005 Process monitoring Ex-barrier for Diagnostics Unit SITRANS DA400 7MJ2010-1AA sitrans Introduction 1 General safety instructions 2 SITRANS Process monitoring Ex-barrier

More information

Functional Safety Manual June pointek CLS500/LC500

Functional Safety Manual June pointek CLS500/LC500 Functional Safety Manual June 2009 pointek CLS500/LC500 Introduction 1 Level Switch Pointek CLS500 SITRANS LC500 SIL Safety Manual Supplement to device manual General safety instructions 2 Device-specific

More information

FLOW CONTROLLER TYPE S/601

FLOW CONTROLLER TYPE S/601 Checked Version Release date QA V4.2.6 F1 F2 EN 26.01.2012 Manual FLOW CONTROL FLOW CONTROLLER TYPE S/601 MODELS F1 AND F2 INTRODUCTION Thank you for using the S/601 flow and batch control series. This

More information

SIMATIC IPC DiagBase SIMATIC. Industrial PC SIMATIC IPC DiagBase. Introduction. DIAG software components. Quick-Start Guide

SIMATIC IPC DiagBase SIMATIC. Industrial PC SIMATIC IPC DiagBase. Introduction. DIAG software components. Quick-Start Guide Introduction 1 DIAG software components 2 SIMATIC Industrial PC Operating Manual Quick-Start Guide 3 Hardware and software requirements 4 Installing and removing the software 5 Description of the Management

More information

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations.

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations. 1 P age Ezeio v9-120317 Eze Cloud Based Monitoring Systems. Created by Intech Instruments Ltd December 2014 Important Supplementary Manual to the main Ezeio manual. Ezeio Controller and the 2400-A16 input

More information

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA HART Field Device Specification Meridian wiredhart 4320 Goldmine Rd. Monroe, NC 28110 USA HART is a registered trademark of the HART Communication Foundation TABLE OF CONTENTS 1. Introduction...5 1.1 Scope...5

More information

Installer Manual KNX Touchscreen Thermostat

Installer Manual KNX Touchscreen Thermostat Installer Manual 02952 KNX Touchscreen Thermostat Index GENERAL FEATURES AND FUNCTIONALITY from page 5 ETS PARAMETERS AND COMMUNICATION OBJECTS from page 7 COMMUNICATION OBJECTS GENERAL FEATURES AND FUNCTIONALITY

More information

SIMATIC IPC DiagBase SIMATIC. Industrial PC. Introduction. DIAG software components. Quick-Start Guide. Hardware and software requirements

SIMATIC IPC DiagBase SIMATIC. Industrial PC. Introduction. DIAG software components. Quick-Start Guide. Hardware and software requirements Introduction 1 DIAG software components 2 SIMATIC Industrial PC Operating Manual Quick-Start Guide 3 Hardware and software requirements 4 Installing and removing the software 5 Description of the Management

More information

FlameGard 5 UV/IR HART

FlameGard 5 UV/IR HART FlameGard 5 UV/IR HART HART Communication Manual The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized

More information

Wiser Air User Interface Guide. Thermostat

Wiser Air User Interface Guide. Thermostat Wiser Air User Interface Guide Thermostat 2 User Guide Wiser Air Scope This document outlines the user interface features of the Wiser Air smart thermostat. It is intended to support individual users and

More information

Operating Instructions Edition 02/2007

Operating Instructions Edition 02/2007 Operating Instructions Edition 02/2007 Temperature Transmitter 7NG3214 with PROFIBUS PA 7NG3215 with FOUNDATION Fieldbus sitrans Introduction 1 General safety notes 2 SITRANS T Temperature transmitter

More information

SITRANS F. Coriolis Flowmeters. SITRANS FC430 with HART. Operating Instructions. Answers for industry.

SITRANS F. Coriolis Flowmeters. SITRANS FC430 with HART. Operating Instructions. Answers for industry. SITRANS F Coriolis Flowmeters Operating Instructions Edition 06/2012 Answers for industry. Introduction 1 Safety notes 2 Description 3 SITRANS F Coriolis Flowmeters Operating Instructions Installing/mounting

More information

FL500 Modbus Communication Operating Manual. Order No.: /00. MSAsafety.com

FL500 Modbus Communication Operating Manual. Order No.: /00. MSAsafety.com FL500 Modbus Communication Operating Manual Order No.: 10193214/00 MSAsafety.com 1000 Cranberry Woods Drive Cranberry Township, PA 16066 A Phone 1-800-MSA-2222 Fax 1-800-967-0398 For your local MSA contacts

More information

Netbiter Tank Sensor

Netbiter Tank Sensor For Netbiter Tank Sensor HMS Industrial Networks AB Post address: Box 4126 300 04 Halmstad SWEDEN Visitor s address: Stationsgatan 37 302 45 Halmstad SWEDEN Telephone: + 46 35 17 29 00 Fax: + 46 35 17

More information

SPECIFICATIONS - DETAILED PROVISIONS Section Magnetic Flowmeters C O N T E N T S

SPECIFICATIONS - DETAILED PROVISIONS Section Magnetic Flowmeters C O N T E N T S Revised 04/13/16 SPECIFICATIONS - DETAILED PROVISIONS Section 17210 - Magnetic Flowmeters C O N T E N T S PART 1 - GENERAL... 1 1.01 GENERAL REQUIREMENTS... 1 1.02 PROJECT SPECIFIC REQUIREMENTS... 1 1.03

More information

SITRANS F. SITRANS FUG1010 Clamp-on Gas Flowmeters. Answers for industry.

SITRANS F. SITRANS FUG1010 Clamp-on Gas Flowmeters. Answers for industry. SITRANS FUG1010 Clamp-on Gas Flowmeters The WideBeam ultrasonic transit time measurement principle, patented by Siemens, ensures flow measurement tolerance of most wet gas conditions allowing for continuous

More information

DOCUMENTATION IPS640

DOCUMENTATION IPS640 DOCUMENTATION IPS640 TECHNICAL AND APPLICATION DESCRIPTION Authors: Nebojša Božič, Peter Hauner Last modification: 2017-01-25 2001-2017 Apricum d.o.o. Mažuranićeva 4, 21312 Podstrana, Hrvatska Details,

More information

DOCUMENTATION IPS640

DOCUMENTATION IPS640 DOCUMENTATION IPS640 TECHNICAL AND APPLICATION DESCRIPTION Authors: Nebojša Božič, Peter Hauner Last modification: 2018-07-06 2001-2018 Apricum d.o.o. Mažuranićeva 4, 21312 Podstrana, Hrvatska Details,

More information

FlameGard 5 MSIR HART

FlameGard 5 MSIR HART FlameGard 5 MSIR HART Multi-Spectral Infrared Flame Detector HART Communication with the FlameGard 5 Multi-spectral Infrared Detector The information and technical data disclosed in this document may be

More information

Mounting and Operating Instructions EB 5610 EN. TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller

Mounting and Operating Instructions EB 5610 EN. TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller Mounting and Operating Instructions Electronics from SAMSON EB 5610 EN Firmware version 1.40 Edition December 2014 Controller

More information

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV CyCLO User Guide Version 2.00 19 th December 2017 REV 2.00 1 Contents 1. Hardware... 3 1.1. Introduction... 3 1.2. Electrical Specification... 3 1.3. Board Overview... 4 1.4. Electrical Installation...

More information

Installation Guide. ECL Comfort 210, application A Table of Contents

Installation Guide. ECL Comfort 210, application A Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 4 2.1 Before you start.....................................................

More information

SECTION ULTRASONIC TRANSIT TIME CLAMP-ON FLOW MEASURING SYSTEM

SECTION ULTRASONIC TRANSIT TIME CLAMP-ON FLOW MEASURING SYSTEM SECTION 40 71 66 ULTRASONIC TRANSIT TIME CLAMP-ON FLOW MEASURING SYSTEM PART 1-GENERAL 1.01 SUMMARY A. Ultrasonic clamp-on flow measurement system designed for non-intrusive external to pipe measurement

More information

AS950 ALL-WEATHER REFRIGERATED SAMPLERS

AS950 ALL-WEATHER REFRIGERATED SAMPLERS AS950 ALL-WEATHER REFRIGERATED SAMPLERS Applications Wastewater Collections Industrial Pretreatment Environmental Monitoring Stormwater Sampling has never been this easy. The AS950 All-Weather Refrigerated

More information

SCAN200E USER S MANUAL

SCAN200E USER S MANUAL SCAN200E USER S MANUAL Code No. 2071 1052 rev. 1.4 Code No. 2071 1052 Rev. 1.4 Page 2/16 SCAN200E User s Manual Foreword This manual is for SCAN200E Controller running software version 2.03 or later. We

More information

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS Firmware versions up to V2.0.X INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGCUIT2Protocol-IM-H57880 06/15 1/32 Contents Section I Introduction

More information

LineGuard 2300 Program User Manual (FloBoss 107)

LineGuard 2300 Program User Manual (FloBoss 107) Form A6251 Part Number D301346X012 November 2012 LineGuard 2300 Program User Manual (FloBoss 107) Remote Automation Solutions Revision Tracking Sheet November 2012 This manual may be revised periodically

More information

EXPERT TRI-STAR. Temperature controller. User s Manual

EXPERT TRI-STAR. Temperature controller. User s Manual Temperature controller r s Manual WARNINGS The warranty can be void if this product is used in a manner not specified by the manufacturer. Every effort has been made to ensure that this manual is complete,

More information

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL Operation Manual Celltrol II Bioreactor Control System Page 1 of 33 Table of Contents 1) Introduction... 3 1.1) Scope of Document... 3 1.2) Control System Overview... 3 1.3) Introduction to Celltrol II...

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information

Substation Monitoring System

Substation Monitoring System Substation Monitoring System UHF Partial Discharge Monitoring System Description Introduction The UHF PDM System is the third generation, spanning 20 years, of monitoring systems developed for GIS partial

More information

Document TM777030, rev. B. Initial release: 22 January 2008 Current release: 16 February 2010

Document TM777030, rev. B. Initial release: 22 January 2008 Current release: 16 February 2010 Peckman Industrial Park, 218 Little Falls Road, Cedar Grove, NJ 07009 Tel. 973-239-8398 Fax 973-239-7614 Email: spectrex@spectrex-inc.com HART Communication With the SharpEye Flame Detector Document TM777030,

More information

User manual. KNXgal. version

User manual. KNXgal. version User manual version 1.3 gal Management alarm control panels Galaxy from bus powered from bus Communication indication on and with Galaxy control panel DIN rail mount (1 modul) Adjustable address on with

More information

Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/

Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/ Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/09 Table Of Contents Interconnecting the HART Communicator with the Detector.... 1 HART Device Description Language.... 3 Detector Wiring.......................................

More information

4/8/12/16 Channel Temperature Scanner with FREE Data Logging PC Software RS485

4/8/12/16 Channel Temperature Scanner with FREE Data Logging PC Software RS485 Select Option Device Wise Device/Group HumiLog Y-Axis Text Show/Hide Ledgends MIN MAX Scale Y Max 08-05-2015 15:17:59 PV_C PV_RH Color default default Graph Refresh Interval 2 Set Interval PV Low Alarm

More information

Dryer Controller M720

Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 2.00 Software version 2.00 Manual M720 Dryer controller Page 1 of 60 Document history Preliminary version: - Created in April, 2009 Hardware Version 2.00,

More information

i.c³ User Guide For Helmer i.series Ultra-Low Freezers A/A

i.c³ User Guide For Helmer i.series Ultra-Low Freezers A/A i.c³ User Guide For Helmer i.series Ultra-Low Freezers 360175-A/A Document History Revision Date CO Supersession Revision Description A 18 APR 2014* 9275 n/a Initial release. * Date submitted or change

More information

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel Manual# 1006494 User s Manual 200E Series DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel User's Manual Rev. 1.0 Marine Pro 200E Series ~~~ DCU 210E Diesel Engine Control Unit DCU 208E Diesel

More information

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option SM3000 Videographic Recorder User Guide (RTU) Communications Option ABB The Company We are an established world force in the design and manufacture of instrumentation for industrial process control, flow

More information

SIMATIC. Industrial PC SIMATIC IPC DiagBase V Introduction. SIMATIC IPC DiagBase software components. Quick-Start Guide

SIMATIC. Industrial PC SIMATIC IPC DiagBase V Introduction. SIMATIC IPC DiagBase software components. Quick-Start Guide Introduction 1 SIMATIC IPC DiagBase software components 2 SIMATIC Industrial PC Operating Manual Quick-Start Guide 3 Hardware and software requirements 4 Installing and removing the software 5 Displaying

More information

DFM. flow pressure temperature MULTI PARAMETER DIGITAL MASS FLOW METERS. Totalizer. Interface

DFM. flow pressure temperature MULTI PARAMETER DIGITAL MASS FLOW METERS. Totalizer. Interface Multi Parameter flow meters provide accurate data on three different fluid parameters: flow pressure temperature The flow rate can be displayed in volumetric flow or mass flow engineering units for standard

More information

Analog Room Pressure Monitor RPC Series

Analog Room Pressure Monitor RPC Series Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the

More information

Database for CTS6000 MODBUS

Database for CTS6000 MODBUS Database for CTS6000 MODBUS Valid for: LONcard SW1.7.4B, Variable List V2.02 Version 1.08-4, 01-05-2016 Contents Contents... 2 1. Installation... 3 1.1. Installation and operating instructions... 3 2.

More information

Module Features are-configurable, no module jumpers to set

Module Features are-configurable, no module jumpers to set December 2011 PACSystems* RX3i Isolated Thermocouple Input Module, 6 Channels, IC695ALG306 Isolated Thermocouple Input Module, 12 Channels, IC695ALG312 Isolated Thermocouple Input module IC695ALG306 provides

More information

Simplex Panel Interface Guide

Simplex Panel Interface Guide Simplex Panel Interface Guide February 2016 SATEON Software Integrations Simplex Panel Interface Guide Issue 1.0, released February 2016 Disclaimer Copyright 2016, Grosvenor Technology. All rights reserved.

More information

User Manual. Dryer Controller M720

User Manual. Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 1.00 Software version 1.00 Preliminary version Manual M720 Dryer controller Page 1 of 42 Document history Preliminary version: - Created in April, 2009

More information

Substation Monitoring System

Substation Monitoring System Substation Monitoring System SF6 Gas Density Monitoring System Description Introduction As a result of recent European legislation on the control of greenhouse gasses, utilities and manufacturers alike

More information

2012 Toolbar & NH3 Operators Manual

2012 Toolbar & NH3 Operators Manual 2012 Toolbar & NH3 Operators Manual P/N 320379 Amity Technology, LLC 2800 7th Avenue North Fargo, ND 58102 (701) 232-4199 www.amitytech.com This Page Left Intentionally Blank Page 2 2012 Toolbar/NH3 Manual

More information

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer Installation and interface must be performed by a qualified controls technician. IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, INTERFACE AND CONFIGURATION OF THIS EQUIPMENT. READ

More information

Ethernet General Purpose

Ethernet General Purpose Ethernet General Purpose Technical Manual Revision 1.03 8 November 2013 Pakton Technologies IO PAE224 Ethernet GPIO Manual.docx Page 1 of 22 Revision 1.03 Last updated 8/11/2013 Table of Contents INTRODUCTION...3

More information

PowerRouter application guideline

PowerRouter application guideline PowerRouter application guideline Software installation tool - version 3.4 Before operating the PowerRouter, you may initialize the PowerRouter by using the PowerRouter software installation tool. The

More information

AS950 PORTABLE SAMPLERS

AS950 PORTABLE SAMPLERS AS950 PORTABLE SAMPLERS Applications Wastewater Collections Industrial Pretreatment Environmental Monitoring Stormwater Sampling has never been this easy. The AS950 Portable Sampler makes programming,

More information

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual Revision 1.03 8 November 2013 JVA Technologies Ethernet General Purpose IO Technical Manual www.jva-fence.com.au Table of Contents INTRODUCTION...3 Scope and Purpose...3 Glossary...3 SPECIFICATIONS...4

More information

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS.  A4741 / Rev.1 DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS User Manual and Menu Map A4741 / Rev.1 www.entes.com.tr ATTENTION -Disconnect all power before connecting the device. -Don t remove

More information

CONTROL UNIT: REFERENCE MANUAL

CONTROL UNIT: REFERENCE MANUAL CONTROL UNIT: REFERENCE MANUAL 1 THE DISPLAY AND REVIEW SCREENS...3 1.1 The Single Bar-graph Display...4 1.2 The View Multiple Devices Display...5 1.2.1 Multiple Bar-graph Display...5 1.2.2 Multiple Device

More information

User Guide

User Guide ABS control panel CP 112 212 ON ON ON ON ON ON User Guide www.absgroup.com ii ABS CONTROL PANEL CP 112 212, USER GUIDE Copyright 2008 ABS Group. All rights reserved. This manual, as well as the software

More information

OT-FX2 OLED TOUCH for the FX II Touch control panel OPERATOR S MANUAL. Technicold Marine Systems

OT-FX2 OLED TOUCH for the FX II Touch control panel OPERATOR S MANUAL. Technicold Marine Systems OT-FX2 OLED TOUCH for the FX II Touch control panel OPERATOR S MANUAL Technicold Marine Systems www.technicold.com Technicold by Northern Lights 1419 W. Newport Center Drive Deerfield Beach, FL 33442 Tel:

More information

DMFPM-2R MULTIFUNCTIONAL

DMFPM-2R MULTIFUNCTIONAL Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND

More information

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12 AUTOMATION P R O D U C T S GROUP, INC. Operator s Manual RST-5000 Series Web Enabled Input Module Rev. A2, 1/12 Tel: 1/888/525-7300 Fax: 1/435/753-7490 www.apgsensors.com E-mail: sales@apgsensors.com RST-5000

More information

Engineering Guideline. pac-carriers Type for Yokogawa ProSafe-RS

Engineering Guideline. pac-carriers Type for Yokogawa ProSafe-RS Engineering Guideline pac-carriers Type 9195 for Yokogawa ProSafe-RS 2 Engineering Guideline / Yokogawa ProSafe-RS 06.06.2017 Integrated solutions for Yokogawa R. STAHL offers a wide range of customized

More information

NexSysLink. 2 CAN Display Operation Manual. CAN Instruments Product Family

NexSysLink. 2 CAN Display Operation Manual. CAN Instruments Product Family NexSysLink CAN Instruments Product Family 2 CAN Display Operation Manual Contact Beede Beede Electrical Instrument Company, Inc. 88 Village Street Penacook, NH 03303 (603) 753-6362 Toll-free 800-451-8255

More information

SITRANS T temperature transmitters A broad product family for every application. sitrans

SITRANS T temperature transmitters A broad product family for every application. sitrans SITRANS T temperature transmitters A broad product family for every application sitrans The SITRANS T family High-precision, intrinsically safe, and available for a wide variety of sensors Whether you

More information

AS950 REFRIGERATED SAMPLERS

AS950 REFRIGERATED SAMPLERS AS950 REFRIGERATED SAMPLERS Applications Wastewater Collections Industrial Pretreatment Environmental Monitoring Stormwater Sampling has never been this easy. The AS950 Refrigerated Sampler makes programming,

More information

Siemens Drives & PLCs

Siemens Drives & PLCs Introduction 1 DIAG software components 2 SIMATIC Industrial PC Operating Manual Quick-Start Guide 3 Hardware and software requirements 4 Installing and removing the software 5 Description of the Management

More information

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1 NGC-40 Bridge Overview Raychem-AR-H58862-NGC40BridgeOV-EN-1805 nvent.com 1 Table of Contents 1. NGC-40 Overview... 9 1.1 Example NGC-40 System... 10 2. Legal stuff... 11 3. Protocols... 12 3.1 Data es...

More information

ECO N DATE DESCRIPTION OF CHANGE CHG

ECO N DATE DESCRIPTION OF CHANGE CHG Model Number: M21E-24-DIN Description: The product is a loop powered device which controls an unsupervised dual pole output channel suitable to manage 24VAC loads. The M21E-24-DIN is micro-controller operated,

More information

No part of this publication may be reproduced, stored in an automated data file or made public in any form or by any means, whether electronic,

No part of this publication may be reproduced, stored in an automated data file or made public in any form or by any means, whether electronic, No part of this publication may be reproduced, stored in an automated data file or made public in any form or by any means, whether electronic, mechanical, by photocopying, recording or in any other manner

More information

Addendum. HART Communication with the FlexSonic Acoustic Detector. 1.1 Rev: 1/

Addendum. HART Communication with the FlexSonic Acoustic Detector. 1.1 Rev: 1/ Addendum HART Communication with the FlexSonic Acoustic Detector 1.1 Rev: 1/15 Table Of Contents Interconnecting the HART Communicator with the Acoustic Detector... 1 HART Device Description Language...

More information

S/601 Controller Installation Manual

S/601 Controller Installation Manual Checked Version Release date QA V4.6.5 PC1 EN 02.07.2012 2011 S/601 Controller Installation Manual FLOW CONTROL PC1 - Pump controller Introduction Thank you for using the S/601 flow, batch and pump control

More information

WeatherLink for Alarm Output Addendum

WeatherLink for Alarm Output Addendum WeatherLink for Alarm Output Addendum Introduction This Streaming Data Logger is designed to provide an electrical interface between a Vantage Pro or Vantage Pro2 weather station console or Weather Envoy

More information

Ultrasonic Flowmeters SITRANS F US SONO Operating instructions 01/2010 SITRANS F

Ultrasonic Flowmeters SITRANS F US SONO Operating instructions 01/2010 SITRANS F Ultrasonic Flowmeters Operating instructions 01/2010 SITRANS F SITRANS F Flowmeters Operating Instructions Introduction Safety notes Description Installing/Mounting Electrical connection Maintenance and

More information

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications Instruction Manual Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications Manual PCT-3000 Revision 9/2014 The PCT-3000 series control console incorporates

More information

Manual# User s Manual. 200 Series. DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel

Manual# User s Manual. 200 Series. DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel Manual# 1100334 User s Manual 200 Series DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel Rev. March 2012 User's Manual for the Marine Pro 200 Series ~~~ DCU 210 Diesel Engine Control Unit DCU

More information

SCHMIDT LED Measured Value Display MD Instructions for Use

SCHMIDT LED Measured Value Display MD Instructions for Use SCHMIDT LED Measured Value Display MD 10.010 Instructions for Use Table of Contents 1 Important Information... 3 2 Application range... 4 3 Mounting instructions... 4 4 Electrical connection... 6 5 Signalizations...

More information

Operating instructions

Operating instructions MA00929301 09/2015 Operating instructions ED10429002 ESYLUX GmbH An der Strusbek 40 22926 Ahrensburg Germany info@esylux.com www.esylux.com 1 Table of contents 1 Using the manual 8 2 Safety instructions

More information

Spa Touch Control Panel with BP2100, BP6013 spa controllers. (Spa Owner s Manual insert)

Spa Touch Control Panel with BP2100, BP6013 spa controllers. (Spa Owner s Manual insert) Spa Touch Control Panel with BP2100, BP6013 spa controllers. (Spa Owner s Manual insert) P.N. 7876C (export) February 12, 2015 For Spas equipped with BP2100, BP6013 controllers and Spa Touch panel. Spa

More information

PACSystems* RX3i. Thermocouple Input Module, 12 Channels, IC695ALG412. GFK-2578B October 2011

PACSystems* RX3i. Thermocouple Input Module, 12 Channels, IC695ALG412. GFK-2578B October 2011 October 2011 PACSystems* RX3i Thermocouple Input Module, 12 Channels, IC695ALG412 The PACSystems * Thermocouple Input module IC695ALG412 provides twelve isolated differential thermocouple input channels.

More information

General Purpose IO Technical Manual

General Purpose IO Technical Manual General Purpose IO Technical Manual Revision 1.06 8 November 2013 Pakton Technologies PAE222 GPIO Manual.docx Page 1 of 21 Revision 1.06 Last updated 8/11/2013 Table of Contents INTRODUCTION...3 Scope

More information

AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System

AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin AD-1272 Code No. LIT-12012477 Issued December 2017 Refer to the QuickLIT website for the most up-to-date version of

More information

Flow Measurement SITRANS F C

Flow Measurement SITRANS F C Overview The flow measuring principle is based on the Coriolis Effect. The FCS sensor s measuring tubes are energized by an electromechanical driver circuit which oscillates them at their resonance frequency.

More information

VISY-X. Technical Documentation. VISY-SoftView V 1.7 User Guide for VISY-Command GUI and VISY-View Touch. Edition: Version: 6 Art.

VISY-X. Technical Documentation. VISY-SoftView V 1.7 User Guide for VISY-Command GUI and VISY-View Touch. Edition: Version: 6 Art. Technical Documentation VISY-X VISY-SoftView V 1.7 User Guide for VISY-Command GUI and VISY-View Touch Edition: 2015-04 Version: 6 Art. No: 350026 FAFNIR GmbH Bahrenfelder Str. 19 22765 Hamburg, Germany

More information

M3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO

M3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO User s Manual Copyright 2017 SELCO SELCO Betonvej 11 - DK-4000 Roskilde Denmark Phone: 45 7026 1122 - Fax: 45 7026 2522 e-mail: selco@selco.com www.selco.com Table of contents 1 INTRODUCTION...4 2 SOFTWARE

More information

Halton SAFE / 7.14 user guide and installation instructions

Halton SAFE / 7.14 user guide and installation instructions Halton SAFE / 7.14 user guide and installation instructions VERIFIED SOLUTIONS BY H A LTO N Enabling Wellbeing Table of contents 1 System description 3 2 User Accounts 4 3 Main menu 7 3.1 Main menu - Change

More information

Application description

Application description Application description Application description Hersteller KNX Touch Control Hager Displays Touch Displays ETS Touch Control Order number Product designation Application programme TP product SWDT03 WDT030

More information

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS NOVA PD56 Series Thermocouple, RTD, & Process Inputs Universal Power Supply 1-24 VAC Up to 3 Alarm Relays Retransmitting 4-2 ma Output Input Max/Min

More information

PowerLogic ION Setup Meter Configuration Software Configuration Guide

PowerLogic ION Setup Meter Configuration Software Configuration Guide PowerLogic ION Setup Meter Configuration Software Configuration Guide 70002-0293-03 12/2010 Conventions Used in this Manual This section describes the symbols and terminology used in this guide. Symbols

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE Release January 2001 CONTENTS 1.0 GENERAL CHARACTERISTICS... 4 1.1 MAIN CHARACTERIS TICS... 4 2.0 USER INTERFACE (CODE C5121230)... 5 2.1 DISPLAY... 5 2.2 MEANING OF THE LEDS...

More information

QuadraTouch Pro Software Manual Dryer Control System

QuadraTouch Pro Software Manual Dryer Control System QuadraTouch Pro Software Manual Dryer Control System Software is constantly changing. Make sure you are up to date with Sukup s newest software. New software and manuals are available for download at:

More information

Modbus TCP/IP Option Instruction Manual

Modbus TCP/IP Option Instruction Manual W A L C H E M An Iwaki America Company WebMaster Modbus TCP/IP Option Web Master WIND Modbus TCP/IP Option Instruction Manual s825v008 and higher Five Boynton Road Hopping Brook Park Holliston, MA 01746

More information

Connections, displays and operating elements C D E G H. Installing the control unit

Connections, displays and operating elements C D E G H. Installing the control unit 1 2 3 GB Control unit 0-10 V REG-K/3-gang with manual mode Operating instructions Art. no. MTN646991 ¼ DANGER Risk of fatal injury from electrical current. All work on the device should only be carried

More information

DEEP SEA ELECTRONICS PLC DSE94xx Battery Charger Series Configuration Suite PC Software Manual

DEEP SEA ELECTRONICS PLC DSE94xx Battery Charger Series Configuration Suite PC Software Manual DEEP SEA ELECTRONICS PLC DSE94xx Battery Charger Series Configuration Suite PC Software Manual Document Number: 057-159 Author: Fady Atallah DSE94xx Configuration Suite PC Software Manual ISSUE 15 DSE94xx

More information

Dryer Moisture Systems Inc. Dryer Master M 2. Product Manual

Dryer Moisture Systems Inc. Dryer Master M 2. Product Manual Dryer Moisture Systems Inc. Dryer Master M 2 Revision 1. January, 27 Revision 1.1 March, 27 Revision 1.2 June, 27 Revision 1.22 July, 27 Revision 1.22.1 January, 28 Revision 1.22.2 April, 28 Revision 1.23

More information

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL MYRIAD TPC VISIT OUR WEBSITE SIGMACONTROLS.COM MYRIADI&O062705 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING 7,8

More information