SECTION A. Section Includes: Portable wheelchair lifts, vertical platform lifts, and inclined wheelchair lifts including necessary accessories.
|
|
- Dale Beasley
- 6 years ago
- Views:
Transcription
1 SECTION WHEELCHAIR LIFTS ****** ***** **** *** ** * ** *** **** ***** ****** NOTE TO SPECIFIER: This section contains several types of fixed wheelchair lifts for use at only at renovation or remodeling projects. Program required portable wheelchair lifts will be not in contract (NIC), but are included for reference and coordination only. ****** ***** **** *** ** * ** *** **** ***** ****** PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Portable wheelchair lifts, vertical platform lifts, and inclined wheelchair lifts including necessary accessories. B. Related Section: 1. Division 16 - Electrical SUBMITTALS A. Submit properly identified manufacturer's specifications and installation instructions for review before starting work. B. Submit shop drawings for fabrication, erection, and anchorages. C. Closeout Submittals: 1. Portable Wheelchair Lift: Submit manufacturers service manual and "Set-Up" video QUALITY ASSURANCE A. Furnish components and accessories by one manufacturer. B. Components, accessories, fabricated parts, and structural requirements shall comply, when applicable, with: 1. Florida Department of Education, Office of Educational Facilities - State Requirements for Educational Facilities (SREF). 2. M-DCPS Design Criteria. 3. Americans with Disabilities Act and Accessibility Guidelines (ADA). 4. Florida Department of Community Affairs - Florida Project No. SPECIFICATION GUIDELINES
2 Accessibility Code for Building Construction (DCA). 5. Bureau of Elevators of the Department of Business Regulation as per Chapter 399 of the Florida Statutes. 6. National Electrical Code (NEC). 7. ANSI A Buildings and Facilities-Providing Accessibility and Usability for Physically Handicapped People. 8. ANSI/ASME , Elevators and Escalators WARRANTY a. ANSI/ASME A 17.1, Part XX, Section 2000 (for vertical wheelchair lifts). b. ANSI/ASME A 17.1, Part XX, Section 2001 (for inclined wheel chair lifts). c. ANSI/ASME A 17.1, Part XX, Section 2002 (for inclined stairway lifts). A. Warranty: Provide 1 year limited warranty on the basic unit and electrical systems and 2 year warranty on drive train components. B. Portable Wheelchair Lift: Provide manufacturer's 1 year warranty for parts and 90 day labor limited warranty. PART 2 PRODUCTS 2.01 MANUFACTURER A. Portable Wheelchair Lift: 1. Model SLA-2050 by Ascension, L.C., Tucson, AZ. or accepted equivalent determined by the Board. B. Vertical Platform Lifts: 1. TG Model with toe guard by Access Industries, Grandview, Missouri. 2. VPL Series 2000 "TG" with toe guard, by Cheney, New Berlin, Wisconsin. 3. Model CDE by National Wheel-O-Vator, Roanoke, IL. 4. Model V1504-TL by Savaria, Laval, Quebec. C. Inclined Platform Lift: 1. Stair-Lift by Garaventa, Blaine, WA or accepted equivalent determined by the Board EQUIPMENT Project No. SPECIFICATION GUIDELINES
3 A. Portable Wheelchair Lift Requirements: 1. Lifting Capacity: 650 pounds. 2. Vertical Speed: 5 feet per minute. 3. Self-contained accessible ramp with non-slip surface. 4. Self-contained retractable or locking wheels. 5. Platform: a. 30 by 48 inches clear minimum with non-slip surface. b. 42 inch high, 1-1/2" diameter guardrails at gates and side panels. c. Clear plexiglass panels. 6. Control Switches: b. Key accessed, constant pressure at platform. c. Functions: Call/send, up/down, emergency stop with audible alarm and reset. 7. Tamperproof electro-mechanical door interlocks to: a. Prevent platform movement from landing unless gates are closed and locked. b. Prevent gate opening unless the platform is in the appropriate position. 8. Obstruction sensors at underside of platform. 9. Manual lowering capability, if loss of power. 10. Automatic dock plate to span potential gap between platform and upper landing. 11. Concealed lift mechanism. 12. Finish: Oven baked powder coating. 13. Electrical Requirements: a. 120 VA, 60 hertz, single phase, 10 amp service. b. UL listed. B. Vertical Platform Wheelchair Lift Requirements: 1. Static load rating: 500 percent. 2. Speed: 9.6 to 12.0 feet per minute. 3. Drive: According to manufacturer's design. 4. Stop: Positive and accurate with no coasting once control button is released. 5. Limit switches: a. Up and down switches. Project No. SPECIFICATION GUIDELINES
4 b. Final limit switch to cut power to unit. 6. Platform: a. 30 inches by 48 inches clear minimum. b. 42 inch high guard rails on non-enter/exit sides. c. Platform and ramp shall have non-skid surfaces. 7. Control Switches: b. Key accessed, constant pressure at platform. c. Functions: Call/send, up/down, emergency stop with audible alarm, and reset. 8. Finish: Electrostatic powder coat finish and with weatherproof components. 9. Door Lock: Tamperproof electro-mechanical interlock to: a. Prevent platform movement from landing unless gates or doors are closed and locked. b. Prevent gates or doors from opening unless the platform is in the appropriate position. 10. Provide UL listing. C. Inclined Wheelchair Lift Requirements: 1. Static Load Rating: 500 percent. 2. Power Fold: Folding of the platform when not in use or when traveling to a called station. 3. Platform Size: 30 inches by 48 inches clear minimum. 4. Access Ramps: Automatic operation at appropriate level. 5. Speed: 15 to 20 fpm. 6. Fold down passenger seat. 7. Manual or power assisted safety arms. 8. Obstruction sensors at leading edges and platform underside. 9. Controls: b. Key accessed and wired remote, both with constant pressure at platform. c. Functions: Call/send, up/down, emergency stop, reset, and power fold. 10. Finish: Electrostatic powder coat and with weatherproof components. 11. Provide UL listing. Project No. SPECIFICATION GUIDELINES
5 12. Provide visual and audible signals during operation according to SREF. PART 3 EXECUTION 3.01 INSTALLATION A. Install wheelchair lift according to manufacturer's recommendations, accepted shop drawings and the requirements of this section. B. Provide emergency power and manual operation FIELD QUALITY CONTROL A. Comply with Florida Statutes, Chapter 399, when applicable, before substantial completion DEMONSTRATION A. Train designated the Board's personnel to move inclined lift out of the stair or lower platform lift to lower level if power is interrupted. B. Provide training or video for designated Board's personnel in the normal operation and routine maintainance of the lift. END OF SECTION Project No. SPECIFICATION GUIDELINES
DIVISION 14 - CONVEYING SYSTEMS. 1. Passenger Elevators 2. Vertical Platform and Inclined Wheelchair Lifts.
DIVISION 14 - CONVEYING SYSTEMS I. GENERAL A. This division contains: 1. Passenger Elevators 2. Vertical Platform and Inclined Wheelchair Lifts. B. Elevators in schools are for the disabled, furniture
More informationA. Section Masonry Assemblies: Anchor placement in masonry.
SECTION 14420 WHEEL CHAIR LIFT PART 1 - GENERAL 1.1 RELATED DOCUMENTS PART 1 GENERAL 1.1 SECTION INCLUDES A. Indoor inclined platform wheelchair lifts. 1.2 RELATED SECTIONS A. Section 04800 - Masonry Assemblies:
More informationSECTION XPRESS II INCLINED WHEELCHAIR PLATFORM LIFT. Display hidden notes to specifier by using Tools / Options / View / Hidden Text.
SECTION 14 42 13 XPRESS II INCLINED WHEELCHAIR PLATFORM LIFT Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Indoor inclined platform
More informationSECTION INCLINE WHEELCHAIR LIFTS. Display hidden notes to specifier by using Tools / Options / View / Hidden Text.
SECTION 14 42 13 INCLINE WHEELCHAIR LIFTS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Indoor inclined platform wheelchair lifts.
More informationGSL Artira Inclined Lift Specifications L DS Section
SECTION 14 42 13 INCLINE WHEELCHAIR LIFTS Display hidden notes to specifier. (Don't know how? Click Here ) PART 1 GENERAL 1.1 SECTION INCLUDES A. Indoor inclined platform wheelchair lifts. B. Outdoor inclined
More informationSECTION HYDRAULIC PASSENGER ELEVATOR
SECTION 14200 HYDRAULIC PASSENGER ELEVATOR PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 05500 - Metal Fabrications. 2. Division 15 - Mechanical. 3. 16721 - Fire Alarm Detection System 4. Division
More informationGaraventa GSL Artira Inclined Platform Lift
Garaventa GSL Artira Inclined Platform Lift Dolphin Stairlifts Gurlyn Farm Relubbus Penzance Cornwall TR20 9DA Phone: 01736 763580 E-mail: info@dolphinstairlifts.co.uk Web: www.dolphinstairlifts.co.uk
More informationNational Reach. Local Service.
National Reach. Local Service. Section 142600 LIMITED USE/LIMITED APPLICATION ELEVATOR PART 1 GENERAL 1.1 SECTION INCLUDES A. Limited Use/Limited Application (LU/LA) Hydraulic Passenger Elevator. B. The
More informationDESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES
SECTION 10 00 00 - SPECIALTIES 10 28 12 - TOILET PARTITIONS: Owner Preferences: Solid core phenolic, polymer based solid surfacing, and solid plastic toilet compartment and screen systems. No Stainless
More informationARCHITECTURAL SPECIFICATIONS
1 B9.1 In Ground Page 1 of 6, Aug 12 DIVISION 08 - OPENINGS SECTION 08 71 13 POWER DOOR OPERATORS Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements. Add section
More informationA. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.
B B11.0 DIVISION 08 - OPENINGS SECTION 08 17 00 INTEGRATED DOOR OPENING ASSEMBLIES Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements. Add section numbers and
More informationDETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR
DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR SECTION 08 71 13 LOW ENERGY AUTOMATIC OPERATORS Specifier Note: Coordinate and edit articles
More informationMultilift Vertical Platform Lift OWNER S MANUAL
Multilift Vertical Platform Lift OWNER S MANUAL (To Be Retained by Owner After Installation by Authorized Savaria Dealer) Part No. 000609 02-m06-2016 2 IMPORTANT Ensure that only an authorized Savaria
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL
SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationMULTI-LEVEL & COVERED BOOTH CONDITIONS
MULTI-LEVEL & COVERED BOOTH CONDITIONS Covered Booth Definition To place something over or upon an exhibit or portion of an exhibit (e.g., roof, ceiling, tenting, lattice, fabric, plastic) to cover the
More informationLife Safety - Means of Egress/Exits NFPA 101
Life Safety - Means of Egress/Exits NFPA 101 Properly designed exits provide a safe path of escape from a fire or other emergency environment. The means of egress (exits) should be arranged to permit all
More informationA. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.
15855 AIR HANDLING UNITS SPECIFIER: CSI MasterFormat 2004 number: 237313 PART 1 GENERAL 1.1 SUMMARY A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution
More informationElevators Revision 01/04/2019
Revision 01/04/2019 SUMMARY Work of this section includes providing equipment, incidental material and labor required for a new elevator. Where singular reference is made to elevator or elevator components,
More informationArchitectural Specification Sheet
Architectural Specification Sheet 1. General 1.01 Summary A. commercial low energy automatic swing door operator that consists of: -Aluminum housing -Electro-mechanical motor -Operator control assembly
More informationSECTION ELECTRIC WATER HEATERS
SECTION 22 36 01 ELECTRIC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationC. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.
SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers
More informationSECTION SPLIT-SYSTEM AIR-CONDITIONERS
SECTION 238126 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationThe Owner will provide the QEI inspection and certification services.
General The Owner will provide the QEI inspection and certification services. Elevators Electric operated traction elevators are preferred; holeless hydraulic oil operation may be considered where use
More informationRecommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.
SMOKE GUARD SYSTEM MODEL 400 SPECIFICATION Smoke Guard, Inc. 287 N. Maple Grove Boise, ID 83704 Toll Free: 800.574.0330 Fax: 208.376.1600 e-mail: info@smokeguard.com website: http://www.smokeguard.com/
More informationB. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).
SECTION 28 13 00 - ACCESS CONTROL PART I - GENERAL 1.1 SUMMARY A. This specification section describes the furnishing, installation, commissioning, and programming of a complete, turnkey, hardwired Andover
More informationNET BARRIER REDUCED RISK FINAL DENIAL VEHICLE BARRIER Model Va-Net-300
NET BARRIER REDUCED RISK FINAL DENIAL VEHICLE BARRIER Model Va-Net-300 PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent applicable. The publications
More informationPALM SPRINGS FIRE DEPARTMENT REGULATIONS FOR TRADE SHOW EXHIBITORS, CONVENTIONS AND SPECIAL EVENT GATHERINGS BASED ON THE 2010 CALIFORNIA FIRE CODE
PALM SPRINGS FIRE DEPARTMENT REGULATIONS FOR TRADE SHOW EXHIBITORS, CONVENTIONS AND SPECIAL EVENT GATHERINGS BASED ON THE 2010 CALIFORNIA FIRE CODE FIRE DEPARTMENT REGULATIONS For Additional Information
More informationFlorida Senate SB 982 By Senator Bennett
By Senator Bennett 1 A bill to be entitled 2 An act relating to electrical and alarm system 3 contracting; amending s. 489.503, F.S.; 4 requiring certain contractors to be certified 5 pursuant to part
More informationSECTION AIR DUCT ACCESSORIES
SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control
More informationA. Product Data: Include rated capacities, furnished specialties and accessories.
BASE BID: SECTION 15542 FUEL-FIRED RADIANT HEATERS PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install a Co-Ray-Vac Low Intensity Vented Infrared Radiant Vacuum Gas Heating System. System must be certified
More informationMAINE. Downloaded g. Maintain an effective pest control program so that the facility is free of pests and rodents;
Housekeeping/Laundry/Maintenance Each licensed facility shall: MAINE Downloaded 01.15.11 g. Maintain an effective pest control program so that the facility is free of pests and rodents; 20.J.2. Soiled
More informationSECTION PLUMBING/HVAC FINAL TESTING, ADJUSTING AND BALANCING
SECTION 15990 PLUMBING/HVAC FINAL TESTING, ADJUSTING AND BALANCING PROJECT NO. ####### PART I - GENERAL 1.01 WORK INCLUDED A. Final test and balance of air distribution systems. B. Final test and balance
More informationSECTION INTRUSION DETECTION SYSTEM
SECTION 13845 INTRUSION DETECTION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested intrusion detection system, bearing Underwriters Laboratories (UL) mercantile listing
More informationUNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:
SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating
More information1 P a g e w w w. s m o k e c o n t r o l. c o m. a u
PROPRIETARY ITEM: SMOKESHIELD S AUTOMATIC OVERHEAD PERIMETER TYPE FABRIC SMOKE CURTAIN PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire alarm or smoke detector-activated, overhead coiling fabric
More informationSECTION WET-PIPE SPRINKLER SYSTEMS
SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The demolition
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 12/12/2018
SECTION 10 2800 - TOILET, BATH, AND LAUNDRY ACCESSORIES GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More information1. Items known commercially as finish hardware or builders hardware, required for swing, sliding, or folding doors.
PART 1 - GENERAL 1.1 SUMMARY: A. Section Includes: SECTION 08710 FINISH HARDWARE 1. Items known commercially as finish hardware or builders hardware, required for swing, sliding, or folding doors. 2. Types
More informationSECTION WATER HEATERS
SECTION 15457 WATER HEATERS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete hot water generating system with necessary accessories as indicated on Construction Documents, as specified, and
More informationDIVISION FINNED WATER-TUBE BOILERS
MVB, TYPE H - MODELS 504A-2004A SUGGESTED SPECIFICATIONS Catalog No.: 2000.933C Effective: 06-25-15 Replaces: 12-21-09 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section
More informationDONALD H. BERG, ARCHITECT
DONALD H. BERG, ARCHITECT DVA PROJECT 632-CSI-402 PET/CT ROOM #A0-10 RENOVATION BASEMENT LEVEL, BUILDING 200 ARCHITECT S PROJECT No. 0917-02 ADDENDUM NO. 1 JUNE 25, 2018 Page 1 of 1 ARCHITECTURAL 1. Specifications:
More informationALABAMA. Downloaded
Housekeeping/Laundry/Maintenance ALABAMA Downloaded 01.15.11 (e) Maintain an effective pest control program so that the facility is free of pests and rodents. In the laundry, provision shall be made to
More informationEG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G
E SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF DATE: 11/13/06 2/1/07 1 Copyright, E, Inc. E 1. ENERAL...4 1.1 Scope Of Work... 4 1.2 Codes and Standards... 4 2. PRODUCTS...5
More informationSECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 15990 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the Specifier in correctly specifying Mechanical System Testing Adjusting
More informationRecommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.
SMOKE GUARD SYSTEM MODEL 200 SPECIFICATION Smoke Guard inc. 287 N. Maple Grove Boise, ID 83704 Toll Free: 800.574.0330 Fax: 208.639.7851 e-mail: info@smokeguard.com website: http://www.smokeguard.com/
More information1 P a g e w w w. s m o k e c o n t r o l. c o m. a u
PROPRIETARY ITEM: FIBERHSIELD S AUTOMATIC OVERHEAD PERIMETER TYPE FABRIC FIRE CURTAIN This master specification should be read in conjunction with How to specify fire curtains technical guide to be published
More informationDIVISION FINNED WATER-TUBE BOILERS
MVB, TYPE H - MODELS 503A-2003A SUGGESTED SPECIFICATIONS Catalog No.: 2000.932C Effective: 04-01-14 Replaces: 07-15-13 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section
More informationSECTION PACKAGED COMPRESSOR AND CONDENSER UNITS
SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply
More informationTelecab17 Residential Elevator OWNER S MANUAL
Telecab17 Residential Elevator OWNER S MANUAL (To Be Retained by Owner After Installation by Authorized Savaria Dealer) Part No. 001081 30-m06-2017 2 IMPORTANT Ensure that only an authorized Savaria Dealer
More informationDESIGN & CONSTRUCTION GUIDELINES
ADMINISTRATIVE SERVICES 4202 E. FOWLER AVENUE, FPC110 PHONE: (813) 974-2625 FACILITIES PLANNING & CONSTRUCTION TAMPA, FLORIDA 33620-7550 WEBSITE: USF.EDU/FPC DESIGN & CONSTRUCTION GUIDELINES DIVISION 21
More informationRecommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.
SMOKE GUARD SYSTEM MODEL 600 REV. 3 SPECIFICATION Smoke Guard, Inc 287 Maple Grove Boise, ID 83704 Toll Free: 800.574.0330 Fax: 208.639.7851 e-mail: info@smokeguard.com website: http://www.smokeguard.com/
More informationUNIVERSITY OF MISSOURI Central Station Air-Handling Units March
GENERAL: 1. This section provides criteria for the design and installation of air handling units. DESIGN GUIDELINES: Design General 1. Location 1.1. For new construction, and existing buildings where possible,
More informationA. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:
SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationHCD DSA OSHPD 1 2 1/AC AC SS SS/CC
CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 30 ELEVATORS AND CONVEYING SYSTEMS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency
More informationB. Product Schedule: For appliances. Use same designations indicated on Drawings.
SECTION 113100 - RESIDENTIAL APPLIANCES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017
SECTION 10 2800 - TOILET, BATH, AND LAUNDRY ACCESSORIES GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationDIVISION FINNED WATER-TUBE BOILERS
MVB, TYPE H - MODELS 2503-4003 SUGGESTED SPECIFICATIONS Catalog No.: 2000.934A Effective: 04-01-14 Replaces: 06-01-13 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section
More informationSECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR
SECTION 08734 COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Overhead
More information1.3 REFERENCE STANDARDS
SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises
More informationDIVISION FINNED WATER-TUBE WATER HEATERS
DELTA LIMITED, TYPE WH - MODELS 399B-899B SUGGESTED SPECIFICATIONS Catalog No.: 3500.97B Effective: 04-01-17 Replaces: 11-15-08 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY
More informationPlanning Guide. for Residential Elevators ASME A17.1, Part V, Section 5.3. April 18, ThyssenKrupp Access
Planning Guide for Residential Elevators ASME A17.1, Part V, Section 5.3 April 18, 2011 ThyssenKrupp Access Introduction This Planning Guide is designed to assist architects, contractors, home owners and
More informationUBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6
Page 1 of 6 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 20 00 05 Mechanical - General Requirements.2 Section 22 05 00 Plumbing - General Requirements.3 UBC Standard Fire Hydrant Drawings.4 Section
More informationSPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS
SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification
More informationSECTION AUTOMATIC VERTICAL CONVEYOR SYSTEM CLOSURE FIRE BARRIER
SECTION 08 3493 AUTOMATIC VERTICAL CONVEYOR SYSTEM CLOSURE FIRE BARRIER PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Smoke detector-activated, vertical closing fire barrier conveyor system closure.
More informationA. Standards: Except where modified or exceeded by the requirements of this Specification, conform to the following standards:
SECTION 11 53 53 BIOLOGICAL SAFETY CABINETS PART 1 - GENERAL 1.1 QUALITY ASSURANCE A. Standards: Except where modified or exceeded by the requirements of this Specification, conform to the following standards:
More informationDIVISION COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS
MVB, TYPE WH - MODELS 503A-2003A SUGGESTED SPECIFICATIONS Catalog No.: 3500.952C Effective: 06-25-15 Replaces: 12-22-09 DIVISION 23 34 36.29 COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 22 3300 - ELECTRIC, DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features:
PART 1 - GENERAL 1.1 SUMMARY A. This Section includes fast-transfer central battery inverters with the following features: 1. Emergency-only circuits. 1.2 DEFINITIONS A. LCD: Liquid-crystal display. B.
More informationSAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER
SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018
SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationDIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS
XPAK FT TYPE H - MODELS 088AR-398A SUGGESTED SPECIFICATIONS Catalog No.: 2100.91 Effective: 05/01/15 Replaces: new DIVISION 23 52 33.13 WALL-HUNG STAINLESS STEEL HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY
More informationSECTION LOW VOLTAGE POWER PANELBOARDS - SPECTRA
PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Low voltage power panelboards 1.02 RELATED SECTIONS 1.03 REFERENCES
More informationSECTION FIRE PUMP AND CONTROLS
SECTION 15320 FIRE PUMP AND CONTROLS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Fire pump, jockey pump, and controls including necessary accessories as shown in Construction Documents, specified
More informationSECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower
SECTION 15682 CENTRIFUGAL WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B. Removal
More informationB. Section Transfer Switches: Automatic transfer switch.
SECTION 263213 - ENGINE GENERATORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Packaged engine generator set. B. Exhaust silencer and fittings. C. Remote control panel. D. Battery and charger. E. Weatherproof
More informationA. This Section includes the following emergency plumbing fixtures:
Page 224500-1 SECTION 224500 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationDivision 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21
Division 21: FIRE SUPRESSION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM Table of Contents 1 Division 21 SECTION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A.
More informationSECTION INTRUSION DETECTION
(NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION
More information2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010)
CHAPTER 1 SCOPE AND ADMINISTRATION 102.7 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 45 47 and such codes and standards shall
More informationSECTION AIR COILS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 82 16 AIR COILS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in the section
More informationSPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC
SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC SECTION 08 35 13.23 ACCORDION FOLDING FIRE DOORS PART 1 GENERAL 1.01 SUMMARY OF WORK A. Division 0 and 1, as indexed, apply to this section. B. Furnish and install
More information1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for detention furniture.
SECTION 125500-WALL BED SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More information1 P a g e w w w. s m o k e c o n t r o l. c o. nz
PROPRIETARY ITEM: FIBERHSIELD EI60 AUTOMATIC OVERHEAD COILING TYPE FABRIC FIRE CURTAIN PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire alarm or smoke detector-activated, overhead coiling fabric
More informationMichigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE
PAGE 280800-1 SECTION 280800 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More informationResidential Based Care Facility Guidelines
Moreno Valley Fire Department Fire Prevention Bureau Residential Based Care Facility Guidelines Approved and Authorized By: Randall Metz, Fire Marshal Issued: January 1, 2011 Residential Based Care Facilities
More informationSECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL
SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply
More informationSECTION FIRE EXTINGUISHER CABINETS
SECTION 104413 FIRE EXTINGUISHER CABINETS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationUNIVERSITY OF ROCHESTER DESIGN STANDARDS FEBRUARY 2005MARCH 2007
SECTION 08710 - DOOR HARDWARE 1.1 SUMMARY A. Door hardware required for swinging doors. No pocket or folding doors permitted at U of R. 1.2 SUBMITTALS A. Hardware Schedule: To be coordinated with doors,
More informationLIGHTING CONTROL DEVICES
SECTION - PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this
More informationrpsa FIRE PROTECTION ENGINEERS
FIRE PROTECTION ENGINEERS R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator
More informationXRRS Specification Fire Ready Hood
XRRS Specification Fire Ready Hood ************************************************************************************************************************ Note to User: This document is subject to copyright
More informationResidential-based Care Facility R-4 Guideline
Moreno Valley Fire Department Fire Prevention Bureau Residential-based Care Facility R-4 Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 7, 2017 Residential-based Care
More informationRecommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region
Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2015 International Existing
More informationE. Luminaire: Complete lighting fixture, including ballast housing if provided.
SECTION 16511 - INTERIOR LIGHTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 16 Specification
More informationGuide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:
Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT
More informationSECTION DOMESTIC WATER HEATERS
SECTION 223500 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to
More informationS000 SITE REVIEW APPR NO. FIRE CODE COMPLIANCE ITEM
APPR NO. FIRE CODE COMPLIANCE ITEM S000 S001 S005 (Automobile Access Aisle) shall be a minimum of 5 ft wide, a common access aisle may be shared by 2 vehicles. Surface slopes shall not exceed 1:50(2%)
More informationARCHITECTURAL SPECIFICATIONS
1 G4.1 Entrance System Page 1 of 6, August 2017 DIVISION 10 - SPECIALTIES SECTION 10450 PEDESTRIAN CONTROL DEVICES Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements.
More informationSECTION SECURITY TESTING AND COMMISSIONING
SECTION 280800 - SECURITY TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 WORK INCLUDES A. General Description: This specification section covers the provision of preliminary testing, acceptance testing,
More information