SECTION COMMON MOTOR REQUIREMENTS FOR FIRE SUPPRESSION EQUIPMENT

Size: px
Start display at page:

Download "SECTION COMMON MOTOR REQUIREMENTS FOR FIRE SUPPRESSION EQUIPMENT"

Transcription

1 SECTION COMMON MOTOR REQUIREMENTS FOR FIRE SUPPRESSION EQUIPMENT PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section includes general requirements for single-phase and polyphase, general-purpose, small and medium, squirrel-cage induction motors for use on ac power systems up to 600 V. 1.3 COORDINATION A. Coordinate features of motors, installed units, and accessory devices to be compatible with the following: 1. Motor controllers. 2. Torque, speed, and horsepower requirements of the load. 3. Ratings and characteristics of supply circuit and required control sequence. 4. Ambient and environmental conditions of installation location. PART 2- PRODUCTS 2.1 GENERAL MOTOR REQUIREMENTS A. Comply with NEMA MG 1 unless otherwise indicated. B. Comply with IEEE 841 for severe-duty motors. 2.2 MOTOR CHARACTERISTICS A. Duty: Continuous duty at ambient temperature of 40 deg C and at altitude of up to 3300 feet (1000 m) above sea level. B. Capacity and Torque Characteristics: Sufficient to start, accelerate, and operate connected loads at designated speeds, at installed altitude and environment, with indicated operating sequence, and without exceeding nameplate ratings or considering service factor. COMMON MOTOR REQUIREMENTS FOR FIRE SUPPRESSION PN# Tl

2 2.3 A. B. c. D. E. F. G. H. I. POLYPHASE MOTORS Description: NEMA MG 1, Design B, medium induction motor. Efficiency: Energy efficient, as defined in NEMA MG 1. Service Factor: Multispeed Motors: Separate winding for each speed. Rotor: Random-wound, squirrel cage. Bearings: Regreasable, shielded, antifriction ball bearings suitable for radial and thrust loading. Temperature Rise: Match insulation rating. Insulation: Class F. Code Letter Designation: 1. Motors 15 HP and Larger: NEMA starting Code F or Code G. 2. Motors Smaller than 15 HP: Manufacturer's standard starting characteristic. J. Enclosure Material: Cast iron for motor frame sizes 324T and larger; rolled steel for motor frame sizes smaller than 324T. 2.4 POLYPHASE MOTORS WITH ADDITIONAL REQUIREMENTS A. B. Motors Used with Reduced-Voltage and Multispeed Controllers: Match wiring connection requirements for controller with required motor leads. Provide terminals in motor terminal box, suited to control method. Motors Used with Variable Frequency Controllers: Ratings, characteristics, and features coordinated with and approved by controller manufacturer. 1. Windings: Copper magnet wire with moisture-resistant insulation varnish, designed and tested to resist transient spikes, high frequencies, and short time rise pulses produced by pulse-width modulated inverters. 2. Energy- and Premium-Efficient Motors: Class B temperature rise; Class F insulation. 3. Inverter-Duty Motors: Class F temperature rise; Class H insulation. 4. Thermal Protection: Comply with NEMA MG 1 requirements for thermally protected motors. c. Severe-Duty Motors: Comply with IEEE 841, with 1.15 minimum service factor. 2.5 SINGLE-PHASE MOTORS A. Motors larger than 1/20 hp shall be one of the following, to suit starting torque and requirements of specific motor application: COMMON MOTOR REQUIREMENTS FOR FIRE SUPPRESSION PN# T1227-0l

3 1. Permanent-split capacitor. 2. Split phase. 3. Capacitor start, inductor run. 4. Capacitor start, capacitor run. B. Multispeed Motors: Variable-torque, permanent-split-capacitor type. C. Bearings: Prelubricated, antifriction ball bearings or sleeve bearings suitable for radial and thrust loading. D. Motors 1/20 HP and Smaller: Shaded-pole type. E. Thermal Protection: Internal protection to automatically open power supply circuit to motor when winding temperature exceeds a safe value calibrated to temperature rating of motor insulation. Thermal-protection device shall automatically reset when motor temperature returns to normal range. PART 3- EXECUTION (Not Applicable) END OF SECTION COMMON MOTOR REQUIREMENTS FOR FIRE SUPPRESSION PN# Tl227-0l

4 THIS PAGE INTENTIONALLY LEFT BLANK

5 SECTION SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Sleeves. 2. Sleeve-seal systems. 3. Sleeve-seal fittings. 4. Grout. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product indicated. PART 2 -PRODUCTS 2.1 SLEEVES A. Cast-Iron Wall Pipes: Cast or fabricated of cast or ductile iron and equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop unless otherwise indicated. B. Galvanized-Steel Wall Pipes: ASTM A 53/A 53M, Schedule 40, with plain ends and welded steel collar; zinc coated. C. Galvanized-Steel-Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, zmc coated, with plain ends. D. PVC-Pipe Sleeves: ASTM D 1785, Schedule 40. E. Galvanized-'Steel-Sheet Sleeves: inch (0.6-mm) minimum thickness; round tube closed with welded longitudinal joint. F. Molded-PE or -PP Sleeves: Removable, tapered-cup shaped, and smooth outer surface with nailing flange for attaching to wooden forms. G. Molded-PVC Sleeves: With nailing flange for attaching to wooden forms. SLEEVES & SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PN# T1227-0l

6 2.2 SLEEVE-SEAL SYSTEMS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Advance Products & Systems, Inc. 2. CALPICO, Inc. 3. Metraflex Company (The). 4. Pipeline Seal and Insulator, Inc. 5. Proco Products, Inc. B. Description: Modular sealing-element unit, designed for field assembly, for filling annular space between piping and sleeve. 1. Sealing Elements: EPDM-rubber interlocking links shaped to fit surface of pipe. Include type and number required for pipe material and size of pipe. 2. Pressure Plates: Carbon steel. 3. Connecting Bolts and Nuts: Carbon steel, with corrosion-resistant coating, of length required to secure pressure plates to sealing elements. 2.3 SLEEVE-SEAL FITTINGS A. Description: Manufactured plastic, sleeve-type, waterstop assembly made for imbedding in concrete slab or wall. Unit has plastic or rubber waterstop collar with center opening to match piping OD. 2.4 GROUT A. Standard: ASTM C 1107 /C 11 07M, Grade B, post-hardening and volume-adjusting, dry, hydraulic-cement grout. B. Characteristics: Nonshrink; recommended for interior and exterior applications. C. Design Mix: 5000-psi (34.5-MPa), 28-day compressive strength. D. Packaging: Premixed and factory packaged. PART 3 - EXECUTION 3.1 SLEEVE INSTALLATION A. Install sleeves for piping passing through penetrations in floors, partitions, roofs, and walls. B. For sleeves that will have sleeve-seal system installed, select sleeves of size large enough to provide l-inch (25-mm) annular clear space between piping and concrete slabs and walls. 1. Sleeves are not required for core-drilled holes. SLEEVES & SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PN# T1227-0l

7 C. Install sleeves in concrete floors, concrete roof slabs, and concrete walls as new slabs and walls are constructed. 1. Permanent sleeves are not required for holes in slabs formed by molded-pe or -PP sleeves. 2. Cut sleeves to length for mounting flush with both surfaces. a. Exception: Extend sleeves installed in floors of mechanical equipment areas or other wet areas 2 inches (50 mm) above finished floor level. 3. Using grout, seal the space outside of sleeves in slabs and walls without sleeve-seal system. D. Install sleeves for pipes passing through interior partitions. 1. Cut sleeves to length for mounting flush with both surfaces. 2. Install sleeves that are large enough to provide 1/4-inch (6.4-mm) annular clear space between sleeve and pipe or pipe insulation. 3. Seal annular space between sleeve and piping or piping insulation; use joint sealants appropriate for size, depth, and location of joint. Comply with requirements for sealants specified. E. Fire-Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at pipe penetrations. Seal pipe penetrations with firestop materials. Comply with requirements for firestopping. 3.2 SLEEVE-SEAL-SYSTEM INSTALLATION A. Install sleeve-seal systems in sleeves in exterior concrete walls and slabs-on-grade at service piping entries into building. B. Select type, size, and number of sealing elements required for piping material and size and for sleeve ID or hole size. Position piping in center of sleeve. Center piping in penetration, assemble sleeve-seal system components, and install in annular space between piping and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make a watertight seal. 3.3 SLEEVE-SEAL-FITTING INSTALLATION A. Install sleeve-seal fittings in new walls and slabs as they are constructed. B. Assemble fitting components of length to be flush with both surfaces of concrete slabs and walls. Position waterstop flange to be centered in concrete slab or wall. C. Secure nailing flanges to concrete forms. D. Using grout, seal the space around outside of sleeve-seal fittings. SLEEVES & SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PN# T

8 3.4 SLEEVE AND SLEEVE-SEAL SCHEDULE A. Use sleeves and sleeve seals for the following piping-penetration applications: 1. Exterior Concrete Walls below Grade: a. Piping Smaller Than NPS 6 (DN 150): Cast-iron wall sleeves with sleeve-seal system. 1) Select sleeve size to allow for l-inch (25-mm) annular clear space between piping and sleeve for installing sleeve-seal system. 2. Concrete Slabs-on-Grade: a. Piping Smaller Than NPS 6 (DN 150): Cast-iron wall sleeves with sleeve-seal system. 3. Interior Partitions: END OF SECTION ) Select sleeve size to allow for l-inch (25-mm) annular clear space between piping and sleeve for installing sleeve-seal system. a. Piping Smaller Than NPS 6 (DN 150): Galvanized-steel-pipe sleeves. SLEEVES & SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PN# T1227-0l

9 SECTION ESCUTCHEONS FOR FIRE-SUPPRESSION PIPING PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Escutcheons. 2. Floor plates. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product indicated. PART 2- PRODUCTS 2.1 ESCUTCHEONS A. One-Piece, Cast-Brass Type: With polished, chrome-plated finish and setscrew fastener. B. One-Piece, Deep-Pattern Type: Deep-drawn, box-shaped brass with chrome-plated finish and spring-clip fasteners. C. One-Piece, Stamped-Steel Type: With chrome-plated finish and spring-clip fasteners. D. Split-Casting Brass Type: With polished, chrome-plated finish and with concealed hinge and setscrew. E. Split-Plate, Stamped-Steel Type: With chrome-plated finish, concealed hinge, and spring-clip fasteners. 2.2 FLOORPLATES A. One-Piece Floor Plates: Cast-iron flange with holes for fasteners. B. Split-Casting Floor Plates: Cast brass with concealed hinge. ESCUTCHEONS FOR FIRE-SUPPRESSION PN# Tl227-0l PIPING

10 PART 3- EXECUTION 3.1 INSTALLATION A. Install escutcheons for piping penetrations of walls, ceilings, and finished floors. B. Install escutcheons with ID to closely fit around pipe, tube, and insulation of piping and with OD that completely covers opening. 1. Escutcheons for New Piping: a. Piping with Fitting or Sleeve Protruding from Wall: One-piece, deep-pattern type. b. Chrome-Plated Piping: One-piece, cast-brass or split-casting brass type with polished, chrome-plated fmish. c. Insulated Piping: One-piece, stamped-steel type or split-plate, stamped-steel type with concealed hinge. d. Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-piece, castbrass or split-casting brass type with polished, chrome-plated finish. e. Bare Piping at Ceiling Penetrations in Finished Spaces: One-piece, cast-brass or split-casting brass type with polished, chrome-plated finish. f. Bare Piping in Unfinished Service Spaces: One-piece, cast-brass or split-casting brass type with polished, chrome-plated finish. g. Bare Piping in Equipment Rooms: One-piece, cast-brass or split-casting brass type with polished, chrome-plated finish. 2. Escutcheons for Existing Piping: a. Chrome-Plated Piping: Split-casting brass type with polished, chrome-plated finish. b. Insulated Piping: Split-plate, stamped-steel type with concealed hinge. c. Bare Piping at Wall and Floor Penetrations in Finished Spaces: Split-casting brass type with polished, chrome-plated finish. d. Bare Piping at Ceiling Penetrations in Finished Spaces: Split-casting brass type with polished, chrome-platedfmish. e. Bare Piping in Unfinished Service Spaces: Split-casting brass type with polished, chrome-plated fmish. f. Bare Piping in Equipment Rooms: Split-casting brass type with polished, chromeplated finish. C. Install floor plates for piping penetrations of equipment-room floors. D. Install floor plates with ID to closely fit around pipe, tube, and insulation of piping and with OD that completely covers opening. 1. New Piping: One-piece, floor-plate type. 2. Existing Piping: Split-casting, floor-plate type. ESCUTCHEONS FOR FIRE-SUPPRESSION PN# Tl227-0l PIPING

11 3.2 FIELD QUALITY CONTROL A. Replace broken and damaged escutcheons and floor plates using new materials. END OF SECTION ESCUTCHEONS FOR FIRE-SUPPRESSION PN# T PIPING

12 THIS PAGE INTENTIONALLY LEFT BLANK

13 SECTION VIBRATION CONTROLS FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Elastomeric isolation pads. 2. Elastomeric isolation mounts. 3. Elastomeric hangers. 4. Mechanical anchor bolts. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product. 1. Include rated load, rated deflection, and overload capacity for each vibration isolation device. PART 2- PRODUCTS 2.1 ELASTOMERIC ISOLATION PADS A. Elastomeric Isolation Pads: 1. Manufacturers: Subject to compliance with requirements, provide products by the following: a. Ace Mountings Co., Inc. b. California Dynamics Corporation. c. Isolation Technology, Inc. d. Kinetics Noise Control, Inc. e. Mason Industries, Inc. f. Vibration Eliminator Co., Inc. g. Vibration Isolation. h. Vibration Mountings & Controls, Inc. VIBRATION CONTROLS FOR PN# T1227-0l FIRE-SUPPRESSION PIPING & EQUIPMENT

14 2. Fabrication: Single or multiple layers of sufficient durometer stiffness for uniform loading over pad area. 3. Size: Factory or field cut to match requirements of supported equipment. 4. Pad Material: Oil and water resistant with elastomeric properties. 5. Surface Pattern: Smooth, Ribbed or Waffle pattern. 6. Infused nonwoven cotton or synthetic fibers. 7. Load-bearing metal plates adhered to pads. 8. Sandwich-Core Material: Resilient and elastomeric. a. Surface Pattern: Smooth, Ribbed or Waffle pattern. b. Infused nonwoven cotton or synthetic fibers. 2.2 A. ELASTOMERlC ISOLATION MOUNTS Double-Deflection, Elastomeric Isolation Mounts: 1. Manufacturers: Subject to compliance with requirements, provide products by the following: a. Ace Mountings Co., Inc. b. California Dynamics Corporation. c. Isolation Technology, Inc. d. Kinetics Noise Control, Inc. e. Mason Industries, Inc. f. Vibration Eliminator Co., Inc. g. Vibration Isolation. h. Vibration Mountings & Controls, Inc. 2. Mounting Plates: a. Top Plate: Encapsulated steel load transfer top plates, factory drilled and threaded with threaded studs or bolts. b. Baseplate: Encapsulated steel bottom plates with holes provided for anchoring to support structure. 3. Elastomeric Material: Molded, oil-resistant rubber, neoprene, or other elastomeric material. 2.3 ELASTOMERlC HANGERS A. Elastomeric Mount in a Steel Frame with Upper and Lower Steel Hanger Rods: 1. Manufacturers: Subject to compliance with requirements, provide products by the following: a. Ace Mountings Co., Inc. b. California Dynamics Corporation. c. Isolation Technology, Inc. d. Kinetics Noise Control, Inc. VIBRATION CONTROLS FOR PN# T FIRE-SUPPRESSION PIPING & EQUIPMENT

15 e. Mason Industries, Inc. f. Vibration Eliminator Co., Inc. g. Vibration Mountings & Controls, Inc. 2. Frame: Steel, fabricated with a connection for an upper threaded hanger rod and an opening on the underside to allow for a maximum of 30 degrees of angular lower hangerrod misalignment without binding or reducing isolation efficiency. 3. Dampening Element: Molded, oil-resistant rubber, neoprene, or other elastomeric material with a projecting bushing for the underside opening preventing steel to steel contact. 2.4 A. MECHANICAL ANCHOR BOLTS Manufacturers: Subject to compliance with requirements, provide products by the following: 1. Cooper B-Line, Inc. 2. Hilti, Inc. 3. Kinetics Noise Control, Inc. 4. Mason Industries, Inc. B. Mechanical Anchor Bolts: Drilled-in and stud-wedge or female-wedge type in zinc-coated steel for interior applications and stainless steel for exterior applications. Select anchor bolts with strength required for anchor and as tested according to ASTM E 488. PART 3- EXECUTION 3.1 EXAMINATION A. Examine areas and equipment to receive vibration isolation and seismic-control devices for compliance with requirements for installation tolerances and other conditions affecting performance of the Work. B. Examine roughing-in of reinforcement and cast-in-place anchors to verify actual locations before installation. C. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 APPLICATIONS A. Multiple Pipe Supports: Secure pipes to trapeze member with clamps approved for application. B. Hanger-Rod Stiffeners: Install hanger-rod stiffeners where indicated or scheduled on Drawings to receive them and where required to prevent buckling of hanger rods due to seismic forces. C. Strength of Support and Restraint Assemblies: Where not indicated, select sizes of components so strength is adequate to carry present and future static loads within specified loading limits. VIBRATION CONTROLS FOR PN# Tl227-0l FIRE-SUPPRESSION PIPING & EQUIPMENT

16 3.3 A. B. c. D. E. F. VIBRATION CONTROL AND RESTRAINT DEVICE INSTALLATION Coordinate the location of embedded connection hardware with supported equipment attachment and mounting points and with requirements for concrete reinforcement. Installation of vibration isolators must not cause any change of position of equipment, piping, or ductwork resulting in stresses or misalignment. Install bushing assemblies for anchor bolts for floor-mounted equipment, arranged to provide resilient media between anchor bolt and mounting hole in concrete base. Install bushing assemblies for mounting bolts for wall-mounted equipment, arranged to provide resilient media where equipment or equipment-mounting channels are attached to wall. Attachment to Structure: If specific attachment is not indicated, anchor bracing to structure at flanges of beams, at upper truss chords of bar joists, or at concrete members. Drilled-in Anchors: 1. Identify position of reinforcing steel and other embedded items prior to drilling holes for anchors. Do not damage existing reinforcing or embedded items during coring or drilling. Notify the structural engineer if reinforcing steel or other embedded items are encountered during drilling. Locate and avoid prestressed tendons, electrical and telecommunications conduit, and gas lines. 2. Do not drill holes in concrete or masonry until concrete, mortar, or grout has achieved full design strength. 3. Wedge Anchors: Protect threads from damage during anchor installation. Heavy-duty sleeve anchors shall be installed with sleeve fully engaged in the structural element to which anchor is to be fastened. 4. Adhesive Anchors: Clean holes to remove loose material and drilling dust prior to installation of adhesive. Place adhesive in holes proceeding from the bottom of the hole and progressing toward the surface in such a manner as to avoid introduction of air pockets in the adhesive. 5. Set anchors to manufacturer's recommended torque, using a torque wrench. 6. Install zinc-coated steel anchors for interior and stainless-steel anchors for exterior applications. 3.4 ACCOMMODATION OF DIFFERENTIAL MOTION A. Install flexible connections in piping where they cross joints, where adjacent sections or branches are supported by different structural elements, and where the connections terminate with connection to equipment that is anchored to a different structural element from the one supporting the connections as they approach equipment. 3.5 FIELD QUALITY CONTROL A. Perform tests and inspections. B. Tests and Inspections: VIBRATION CONTROLS FOR PN# Tl227-0l FIRE-SUPPRESSION PIPING & EQUIPMENT

17 1. Provide evidence of recent calibration of test equipment by a testing agency acceptable to authorities having jurisdiction. 2. Schedule test with Owner, through Architect, before connecting anchorage device to restrained component (unless postconnection testing has been approved), and with at least seven days' advance notice. 3. Obtain Architect's approval before transmitting test loads to structure. Provide temporary load-spreading members. 4. Test at least four of each type and size of installed anchors and fasteners selected by Architect. 5. Test to 90 percent of rated proof load of device. 6. Measure isolator restraint clearance. 7. Measure isolator deflection. 8. Verify snubber minimum clearances. C. Remove and replace malfunctioning units and retest as specified above. D. Prepare test and inspection reports. END OF SECTION VIBRATION CONTROLS FOR PN# T FIRE-SUPPRESSION PIPING & EQUIPMENT

18 THIS PAGE INTENTIONALLY LEFT BLANK VIBRATION CONTROLS FOR PN# Tl227-0l FIRE-SUPPRESSION PIPING & EQUIPMENT

19 SECTION IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Equipment labels. 2. Warning signs and labels. 3. Pipe labels. 4. Valve tags. 5. Warning tags. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product. B. Samples: For color, letter style, and graphic representation required for each identification material and device. C. Equipment-Label Schedule: Include a listing of all equipment to be labeled and the proposed content for each label. D. Valve Schedules: Valve numbering scheme. 1.4 CLOSEOUT SUBMITTALS A. Maintenance Data: For each piping system to include in maintenance manuals. PART 2- PRODUCTS 2.1 EQUIPMENT LABELS A. Metal Labels for Equipment: 1. Material and Thickness: Brass, inch (0.8 mm), thick, with predrilled holes for attachment hardware. 2. Letter Color: Black. IDENTIFICATION FOR FIRE- PN# T SUPPRESSION PIPING & EQUIPMENT

20 3. Background Color: White. 4. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by 3/4 inch (64 by 19 mm). 5. Minimum Letter Size: 1/4 inch (6.4 mm) for name of units if viewing distance is less than 24 inches (600 mm), 1/2 inch (13 mm) for viewing distances up to 72 inches (1830 mm), and proportionately larger lettering for greater viewing distances. Include secondary lettering two-thirds to three-fourths the size of principal lettering.. 6. Fasteners: Stainless-steel rivets or self-tapping screws. 7. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate. B. Plastic Labels for Equipment: 1. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving, 1/16 inch (1.6 mm) thick, with predrilled holes for attachment hardware. 2. Letter Color: Black. 3. Background Color: White. 4. Maximum Temperature: Able to withstand temperatures up to 160 deg F (71 deg C). 5. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by 3/4 inch (64 by 19 mm). 6. Minimum Letter Size: 1/4 inch (6.4 mm) for name of units if viewing distance is less than 24 inches (600 mm), 1/2 inch (13 mm) for viewing distances up to 72 inches (1830 mm), and proportionately larger lettering for greater viewing distances. Include secondary lettering two-thirds to three-fourths the size of principal lettering. 7. Fasteners: Stainless-steel rivets or self-tapping screws. 8. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate. C. Label Content: Include equipment's Drawing designation or unique equipment number, Drawing numbers where equipment is indicated (plans, details, and schedules), and the Specification Section number and title where equipment is specified. D. Equipment-Label Schedule: For each item of equipment to be labeled, on 8-1/2-by-11-inch (A4) bond paper. Tabulate equipment identification number and identify Drawing numbers where equipment is indicated (plans, details, and schedules) and the Specification Section number and title where equipment is specified. Equipment schedule shall be included in operation and maintenance data. 2.2 WARNING SIGNS AND LABELS A. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving, 1/16 inch (1.6 mm) thick, with predrilled holes for attachment hardware. B. Letter Color: Black. C. Background Color: White. D. Maximum Temperature: Able to withstand temperatures up to 160 deg F (71 deg C). E. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by 3/4 inch (64 by 19 mm). IDENTIFICATION FOR FIRE- PN# Tl227-0l SUPPRESSION PIPING & EQUIPMENT

21 F. Minimum Letter Size: 114 inch (6.4 mm) for name of units if viewing distance is less than 24 inches (600 mm), 1/2 inch (13 mm) for viewing distances up to 72 inches (1830 mm), and proportionately larger lettering for greater viewing distances. Include secondary lettering twothirds to three-fourths the size of principal lettering. G. Fasteners: Stainless-steel rivets or self-tapping screws. H. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate. I. Label Content: Include caution and warning information, plus emergency notification instructions. 2.3 A. B. c. PIPE LABELS General Requirements for Manufactured Pipe Labels: Preprinted, color-coded, with lettering indicating service and showing flow direction. Self-Adhesive Pipe Labels: Printed plastic with contact-type, permanent-adhesive backing. Pipe-Label Contents: Include identification of piping service using same designations or abbreviations as used on Drawings; pipe size; and an arrow indicating flow direction. 1. Flow-Direction Arrows: Integral with piping-system service lettering to accommodate both directions, or as separate unit on each pipe label to indicate flow direction. 2. Lettering Size: At least 1-1/2 inches (38 mm) high. D. Pipe-Label Colors: 1. Background Color: Red. 2. Letter Color: White. 2.4 VALVE TAGS A. Valve Tags: Stamped or engraved with 1/4-inch (6.4-mm) letters for piping-system abbreviation and 1/2-inch (13-mm) numbers. 1. Tag Material: Brass, inch (0.8 mm) thick, with predrilled holes for attachment hardware. 2. Fasteners: Brass wire-link chain or S-hook. 3. Valve-Tag Color: Red. 4. Letter Color: White. B. Valve Schedules: For each piping system, on 8-1/2-by-11-inch (A4) bond paper. Tabulate valve number, piping system, system abbreviation (as shown on valve tag), location of valve (room or space), normal-operating position (open, closed, or modulating), and variations for identification. Mark valves for emergency shutoff and similar special uses. 1. Valve-tag schedule shall be included in operation and maintenance data. IDENTIFICATION FOR FIRE- PN# Tl227-0l SUPPRESSION PIPING & EQUIPMENT

22 2.5 A. WARNING TAGS Warning Tags: Preprinted or partially preprinted, accident-prevention tags, of plasticized card stock with matte finish suitable for writing. 1. Size: 3 by 5-1/4 inches (75 by 133 mm) minimum. 2. Fasteners: Brass grommet and wire. 3. Nomenclature: Large-size primary caption such as "DANGER," "CAUTION," or "DO NOT OPERATE." 4. Color: Yell ow background with black lettering. PART 3- EXECUTION 3.1 PREPARATION A. Clean piping and equipment surfaces of substances that could impair bond of identification devices, including dirt, oil, grease, release agents, and incompatible primers, paints, and encapsulants. 3.2 LABEL INSTALLATION A. B. c. D. E. Coordinate installation of identifying devices with completion of covering and painting of surfaces where devices are to be applied. Coordinate installation of identifying devices with locations of access panels and doors. Install or permanently fasten labels on each major item of mechanical equipment. Locate equipment labels where accessible and visible. Pipe-Label Locations: Locate pipe labels where piping is exposed or above accessible ceilings in finished spaces; machine rooms; accessible maintenance spaces such as shafts, tunnels, and plenums; and exterior exposed locations as follows: 1. Near each valve and control device. 2. Near each branch connection excluding short takeoffs. Where flow pattern is not obvious, mark each pipe at branch. 3. Near penetrations through walls, floors, ceilings, and inaccessible enclosures. 4. At access doors, manholes, and similar access points that permit view of concealed piping. 5. Near major equipment items and other points of origination and termination. 6. Spaced at maximum intervals of 50 feet (15m) along each run. Reduce intervals to 25 feet (7.6 m) in areas of congested piping and equipment. 7. On piping above removable acoustical ceilings. Omit intermediately spaced labels. IDENTIFICATION FOR FIRE- PN# T1227-0l SUPPRESSION PIPING & EQUIPMENT

23 3.3 VALVE-TAG INSTALLATION A. Install tags on valves and control devices in piping systems. List tagged valves in a valve-tag schedule. B. Valve-Tag Application Schedule: Tag valves according to size, shape, and with captions similar to those indicated in "Valve-Tag Size and Shape" Subparagraph below: 1. Valve-Tag Size and Shape: a. Wet-Pipe Sprinkler System: 1-1/2 inches (38 mm), round. b. Dry-Pipe Sprinkler System: 1-1/2 inches (38 mm) round. 3.4 WARNING-TAG INSTALLATION A. Write required message on, and attach warning tags to, equipment and other items where required. END OF SECTION IDENTIFICATION FOR FIRE- PN# T SUPPRESSION PIPING & EQUIPMENT

24 THIS PAGE INTENTIONALLY LEFT BLANK

25 SECTION FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section includes fire-suppression water-service piping and related components outside the building and service entrance piping through floor into the building. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product indicated. 1.4 INFORMATIONAL SUBMITTALS A. Coordination Drawings: For piping and specialties including relation to other services in same area, drawn to scale. Show piping and specialty sizes and valves, meter and specialty locations, and elevations. B. Field quality-control reports. 1.5 QUALITY ASSURANCE A. Regulatory Requirements: 1. Comply with standards of authorities having jurisdiction for fire-suppression waterservice piping, including materials, hose threads, installation, and testing. B. Piping materials shall bear label, stamp, or other markings of specified testing agency. C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. D. Comply with the "Approval Guide," published by UL's "Fire Protection Equipment Directory" for fire-service-main products. E. NFP A Compliance: Comply with NFP A 24 for materials, installations, tests, flushing, and valve and hydrant supervision for fire-suppression water-service piping. FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING PN# T1227-0l

26 1.6 DELIVERY, STORAGE, AND HANDLING A. Preparation for Transport: Prepare valves, including fire hydrants, according to the following: 1. Ensure that valves are dry and internally protected against rust and corrosion. 2. Protect valves against damage to threaded ends and flange faces. 3. Set valves in best position for handling. Set valves closed to prevent rattling. B. During Storage: Use precautions for valves, including fire hydrants, according to the following: 1. Do not remove end protectors unless necessary for inspection; then reinstall for storage. 2. Protect from weather. Store indoors and maintain temperature higher than ambient dew point temperature. Support off the ground or pavement in watertight enclosures when outdoor storage is necessary. C. Handling: Use sling to handle valves and fire hydrants if size requires handling by crane or lift. Rig valves to avoid damage to exposed parts. Do not use handwheels or stems as lifting or rigging points. D. Deliver piping with factory-applied end caps. Maintain end caps through shipping, storage, and handling to prevent pipe-end damage and to prevent entrance of dirt, debris, and moisture. E. Protect stored piping from moisture and dirt. Elevate above grade. Do not exceed structural capacity of floor when storing inside. F. Protect flanges, fittings, and specialties from moisture and dirt. G. Store plastic piping protected from direct sunlight. Suppmi to prevent sagging and bending. H. Coordinate connection to water main with utility company. PART 2- PRODUCTS 2.1 DUCTILE-IRON PIPE AND FITTINGS A. B. c. Grooved-Joint, Ductile-Iron Pipe: A WW A Cl51, with cut, rounded-grooved ends. Mechanical-Joint, Ductile-Iron Pipe: A WW A Cl51, with mechanical-joint bell and plain spigot end. Push-on-Joint, Ductile-Iron Pipe: A WW A C 151, with push-on-joint bell and plain spigot end. 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. Anvil International, Inc. b. Shurjoint Piping Products. c. Star Pipe Products. d. Victaulic Company. FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING PN# T

27 D. Mechanical-Joint, Ductile-Iron Fittings: A WW A CllO, ductile- or gray-iron standard pattern or A WW A Cl53, ductile-iron compact pattern. 1. Glands, Gaskets, and Bolts: A WW A Cl11, ductile- or gray-iron glands, rubber gaskets, and steel bolts. E. Push-on-Joint, Ductile-Iron Fittings: A WW A Cl53, ductile-iron compact pattern. 1. Gaskets: AWWA Clll, rubber. F. Flanges: ASME Bl6.1, Class 125, cast iron. 2.2 SPECIAL PIPE FITTINGS A. Ductile-Iron Flexible Expansion Joints: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. EBAA Iron, Inc. b. ROMAC Industries Inc. c. Star Pipe Products. 2. Description: Compound, ductile-iron fitting with combination of flanged and mechanical-joint ends complying with AWWACllO or AWWAC153. Include two gasketed ball-joint sections and one or more gasketed sleeve sections. Assemble components for offset and expansion indicated. Include A WW A C 111, ductile-iron glands, rubber gaskets, and steel bolts. 3. Pressure Rating: 250 psig (1725 kpa) minimum. B. Ductile-Iron Deflection Fittings: 1. Description: Compound, ductile-iron coupling fitting with sleeve and one or two flexing sections for up to 15-degree deflection, gaskets, and restrained-joint ends complying with AWWACllO or AWWAC153. Include AWWAC111, ductile-iron glands, rubber gaskets, and steel bolts. 2. Pressure Rating: 250 psig (1725 kpa) minimum. 2.3 JOINING MATERIALS A. Gaskets for Ferrous Piping and Copper-Alloy Tubing: ASME B16.21, asbestos free. B. Brazing Filler Metals: A WS A5.8/A5.8M, BCuP Series. 2.4 PIPING SPECIAL TIES A. Transition Fittings: Manufactured fitting or coupling same size as, with pressure rating at least equal to and ends compatible with, piping to be joined. FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING PN# T

28 B. Tubular-Sleeve Pipe Couplings: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. Cascade Waterworks Manufacturing. b. Dresser, Inc.; Dresser Piping Specialties. c. Ford Meter Box Company, Inc. (The); Pipe Products Division. d. JCM Industries. e. ROMAC Industries Inc. f. Smith-Blair, Inc.; a Sensus company. g. Viking Johnson. 2. Description: Metal, bolted, sleeve-type, reducing or transition coupling, with center sleeve, gaskets, end rings, and bolt fasteners, and with ends of same sizes as piping to be joined. 3. Standard: A WWA C Center-Sleeve Material: Manufacturer's standard. 5. Gasket Material: Natural or synthetic rubber. 6. Pressure Rating: 150 psig (1035 kpa) minimum. 7. Metal Component Finish: Corrosion-resistant coating or material. PART 3 - EXECUTION 3.1 EARTHWORK A. Comply with excavating, trenching, and backfilling requirements m Section "Earth Moving." 3.2 PIPING INSTALLATION A. Comply with NFP A 24 for fire-service-main piping materials and installation. B. Install ductile-iron, water-service piping according to AWWA C600 and A WW A M41. C. Bury piping with depth of cover over top at least 30 inches (750 mm), with top at least 12 inches (300 mm) below level of maximum frost penetration, and according to the following: I. Under Driveways: With at least 36 inches (91 0 mm) of cover over top. D. Install pipi11g by tunneling or jacking, or combination of both, under streets and other obstructions that cannot be disturbed. E. Extend fire-suppression water-service piping and connect to water-supply source and building fire-suppression water-service piping systems at locations and pipe sizes indicated. 1. Tenninate fire-suppression water-service piping at building floor slab until buildingwater-piping systems are installed. Terminate piping with caps, plugs, or flanges as FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING PN# T1227-0l

29 required for piping material. Make connections to building's fire-suppression waterservice piping systems when those systems are installed. F. Install underground piping with restrained joints at horizontal and vertical changes in direction. Use restrained-joint piping, thrust blocks, anchors, tie-rods and clamps, and other supports. G. Comply with requirements in Section "Wet-Pipe Sprinkler Systems," and Section "Dry-Pipe Sprinkler Systems" for fire-suppression-water piping inside the building. H. Install sleeves for piping penetrations of walls, ceilings, and floors. I. Install sleeve seals for piping penetrations of concrete walls and slabs. 3.3 JOINT CONSTRUCTION A. Install couplings, flanges, flanged fittings, unions, nipples, and transition and special fittings that have finish and pressure rating same as or higher than systems pressure rating for aboveground applications unless otherwise indicated. B. Install unions adjacent to each valve in tubing NPS 2 (DN 50) and smaller. C. Install flanges, flange adaptors, or couplings for grooved-end piping on valves, apparatus, and equipment having NPS 2-1/2 (DN 65) and larger end connections. D. Ream ends of tubes and remove burrs. E. Remove scale, slag, dirt, and debris from outside and inside of pipes, tubes, and fittings before assembly. F. Copper-Tubing, Brazed Joints: Join copper tube and fittings according to CDA's "Copper Tube Handbook," "Brazed Joi1,1ts" Chapter. G. Ductile-Iron Piping, Gasketed Joints for Fire-Service-Main Piping: UL 194. H. Ductile-Iron Piping, Grooved Joints: Cut-groove pipe. Assemble joints with grooved-end, ductile-iron-piping couplings, gaskets, lubricant, and bolts. I. Flanged Joints: Select appropriate gasket material in size, type, and thickness suitable for water service. Join flanges with bolts according to ASME B31.9. J. Dissimilar Materials Piping Joints: Use adapters compatible with both piping materials, with OD, and with system working pressure. K. Do not use flanges or unions for underground piping. 3.4 ANCHORAGE INSTALLATION A. Anchorage, General: Install water-distribution piping with restrained joints. Anchorages and restrained-joint types that may be used include the following: FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING PN# Tl227-0l

30 1. Concrete thrust blocks. B. Install anchorages for tees, plugs and caps, bends, crosses, valves, and hydrant branches in firesuppression water-service piping according to NFP A 24 and the following: 1. Gasketed-Joint, Ductile-Iron, Water-Service Piping: According to A WW A C600. c. Apply full coat of asphalt or other acceptable corrosion-resistant material to surfaces of installed ferrous anchorage devices. 3.5 A. B. CONNECTIONS Connect fire-suppression water-service piping to utility water main. Connect fire-suppression water-service piping to interior fire-suppression piping. 3.6 A. B. C. FIELD QUALITY CONTROL Use test procedure prescribed by authorities having jurisdiction or, if method is not prescribed by authorities having jurisdiction, use procedure described below. Piping Tests: Conduct piping tests before joints are covered and after concrete thrust blocks have hardened sufficiently. Fill pipeline 24 hours before testing and apply test pressure to stabilize system. Use only potable water. Hydrostatic Tests: Test at not less than one-and-one-half times the working pressure for two hours. 1. Increase pressure in 50-psig (350-kPa) increments and inspect each joint between increments. Hold at test pressure for one hour; decrease to 0 psig (0 kpa). Slowly increase again to test pressure and hold for one more hour. Maximum allowable leakage is 2 quarts (1.89 L) per hour per 100 joints. Remake leaking joints with new materials and repeat test until leakage is within allowed limits. D. Prepare test and inspection reports. 3.7 IDENTIFICATION A. B. Install continuous underground detectable warning tape during backfilling of trench for underground fire-suppression water-service piping. Locate below finished grade, directly over piping. Permanently attach equipment nameplate or marker indicating plastic fire-suppression waterservice piping or fire-suppression water-service piping with electrically insulated fittings, on main electrical meter panel. Comply with requirements for identifying devices in Section "Identification for Plumbing Piping and Equipment." FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING PN# T1227-0l

31 3.8 CLEANING A. Clean and disinfect fire-suppression water-service piping as follows: 1. Purge new piping systems and parts of existing systems that have been altered, extended, or repaired before use. 2. Use purging and disinfecting procedure prescribed by authorities having jurisdiction or, if method is not prescribed by authorities having jurisdiction, use procedure described in A WW A C651 or do as follows: a. Fill system or part of system with water/chlorine solution containing at least 50 ppm of chlorine; isolate and allow to stand for 24 hours. b. Drain system or part of system of previous solution and refill with water/chlorine solution containing at least 200 ppm of chlorine; isolate and allow to stand for three hours. c. After standing time, flush system with clean, potable water until no chlorine remains in water coming from system. d. Submit water samples in sterile bottles to authorities having jurisdiction. Repeat procedure if biological examination shows evidence of contamination. B. Prepare reports of purging and disinfecting activities. END OF SECTION FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING PN# T1227-0l

32 THIS PAGE INTENTIONALLY LEFT BLANK

33 SECTION FACILITY GROUND-MOUNTED, POTABLE-WATER STORAGE TANKS PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes bolted-steel tank for storage of fire-suppression water. 1.3 PERFORMANCE REQUIREMENTS A. Structural Performance: Surface water-storage tank, including structural reinforcement and foundation, shall be capable of withstanding the effects of dead and live gravity loads and winds of 100 mph (161 km/h). B. Thermal Movements: Surface water-storage tank, including structural reinforcement and foundation, shall allow for thermal movements resulting from the following maximum change (range) in ambient and surface temperatures by preventing buckling, opening of joints, overstressing of components, failure of connections, and other detrimental effects. Base engineering calculations on surface temperatures of materials due to both solar heat gain and nighttime-sky heat loss. 1. Temperature Change (Range): 120 deg F (67 deg C), ambient; 180 deg F (100 deg C), material surfaces. 1.4 ACTION SUBMITTALS A. Product Data: Include rated capacities, accessories, appurtenances, and furnished specialties for each surface water-storage tank indicated. B. Shop Drawings: Signed and sealed by a qualified professional engineer. Show fabrication and installation details for each surface water-storage tank, including the following: 1. Tank, roof, and shell openings. 2. Safety railings and ladders. 3. Plans, elevations, sections, details, and attachments to other work. 4. Structural analysis data signed and sealed by the qualified professional engineer responsible for their preparation. 5. Power, signal, and control wiring. FACILITY GROUND-MOUNTED, PN# Tl POTABLE-WATER STORAGE TANKS

34 1.5 INFORMATIONAL SUBMITTALS A. Qualification Data: For fabricator. B. Welding certificates. C. Bacteriological test results. D. Field quality-control test reports. 1.6 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: For the following to include in emergency, operation, and maintenance manuals: 1.7 QUALITY ASSURANCE A. Fabricator Qualifications: Employ a qualified structural engineer to prepare calculations, Shop Drawings, and other structural data for fabrication and erection of surface water-storage tanks. 1. Engineering Responsibility: Preparation of data for surface water-storage tanks, accessories, specified appurtenances, and concrete supports and foundations, including Shop Drawings, based on testing and engineering analysis of manufacturer's standard units in assemblies similar to those indicated for this Project. B. Pipe Welding: Qualify procedures and personnel according to ASME Boiler and Pressure Vessel Code: Section IX, "Welding and Brazing Qualifications." C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. D. Comply with A WW A D103, "Factory-Coated Bolted Steel Tanks for Water Storage," and with A WW A M42, "Steel Water-Storage Tanks," for bolted-steel, surface water-storage tanks. E. Comply with NFPA 22, "Water Tanks for Private Fire Protection," for surface water-storage tanks for fire-suppression water supply. PART 2 -PRODUCTS 2.1 BOLTED-STEEL TANK A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1. American Tank Company, Inc.; Bolted Tank Sales and Service. 2. Columbian TecTank. 3. Faubian Tanlcs. FACILITY GROUND-MOUNTED, PN# Tl POTABLE-WATER STORAGE TANKS

35 4. Pittsburg Tank & Tower Co., Inc. 5. Superior Tank Co., Inc. B. Description: Bolted-steel plates, bolts, rods, and reinforcing steel; designed and fabricated according to A WW AD 100, A WW A M42, and NFP A Shell Roof: Comply with A WW AD Pipe Connection: Match size of water-distribution pipe. 3. Overflow Piping: ASTM A 53/A 53M, Grade B, Schedule 40, welded-steel pipe with ASTM A 234/A 234M, Grade W.B., Schedule 40, carbon-steel butt-weld fittings. 4. Roof Hatch: Steel, hinged cover with 4-inch (100-mm) neck and 2-inch (50-mm) downward overlap with hasp and lock, located over interior ladder and adjacent to exterior ladder. 5. Roof Manhole: Steel, removable,cover with 4-inch (100-mm) neck and 2-inch- (50-mm ) downward overlap with hasp and lock. Construct opening with capability of supporting ventilation fan. 6. Shell Sidewall Manhole: Steel, circular. 2.2 PAINT MATERIALS A. Paint: Comply with A WW A Dl02. B. Primer: Tank fabricator's standard epoxy-polyamide paint. C. Tank Shell Interior Finish Paint: Tank fabricator's standard epoxy-polyamide paint complying with NSF 61 and compatible with prime coat. D. Tank Shell Exterior Intermediate Paint: Tank fabricator's standard, two-component epoxy paint compatible with prime and finish paint. Intermediate coat shall have a slight color contrast with finish coat. E. Tank Shell Exterior Finish Paint: Tank fabricator's standard urethane paint. 1. Color: As selected by Owner from tank manufacturer's paint chart. 2.3 SHOP PAINTING A. Factory coating according to A WW AD 103. B. Tank Shell Interior Finish Coat: Comply with NSF 61. C. Tank Shell ~xterior Finish Coat: Factory coating according to A WW AD SURF ACE WATER-STORAGE TANK APPURTENANCES A. Water-Level Controls: Automatic controls for maintaining water level in tank, with valves, piping, and audible and visual alarms to indicate the following: 1. High- and low-water levels. FACILITY GROUND-MOUNTED, PN# Tl POTABLE-WATER STORAGE TANKS

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint. (816) 373-4878 U1208-01/FAI29-029 (573) 751-2624 SECTION 2 105 17 - SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the

More information

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS Ul611-0l SECTION 211316- DRY-PIPE SPRINKLER SYSTEMS PARTl-GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions, and Division 1 Specification

More information

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1 TO CONTRACT DOCUMENTS ENTITLED: PROJECT MANUAL FOR: Women s and Children s Hospital New Water Service Main PROJECT NUMBER: CP172631 ADVERTISEMENT DATE: July

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING

SECTION SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING SECTION 210517- SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No SECTION 213113 - ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure. SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

SPRINKLERS TABLE OF CONTENTS

SPRINKLERS TABLE OF CONTENTS SPRINKLERS TABLE OF CONTENTS SECTION 21 13 13 WET PIPE SPRINKLER SYSTEMS SECTION 211313 - WET PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,

More information

B. Utility-furnished products include water meters that will be furnished to the site, ready for installation.

B. Utility-furnished products include water meters that will be furnished to the site, ready for installation. SECTION 211100 - FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION SECTION 211200 - FIRE-SUPPRESSION STANDPIPES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Hose connections. 4. Fire-department connections.

More information

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings. DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS

More information

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No. SECTION 22 63 13 GAS PIPING FOR LABORATORY AND HEALTHCARE FACILITIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION SECTION 21 1301- FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY: A. This Section includes fire-suppression piping and equipment for the following building systems: 1. Wet-pipe, fire-suppression

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 1314D - AUTOMATIC SPRINKLER SYSTEMS (DRY-PIPE) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

B. Related Sections: The following Sections contain requirements that relate to this Section.

B. Related Sections: The following Sections contain requirements that relate to this Section. SECTION 211313- FIRE-SUPPRESSION PIPING PART1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general prov1s1ons of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5 DOC Cremer Heating and Hot Water Plant Project Number: M 1411-04 TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION 21 30 00- WATER BASED FIRE PROTECTION SYSTEMS... 5 SECTION 22 40 00 -PLUMBING

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 211313 WET-PIPE SPRINKLER SYSTEMS PRT 1 GENERL 1.01 RELTED DOCUMENTS. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Facility Fire-Suppression Water-Service Piping

Facility Fire-Suppression Water-Service Piping University of New Hampshire University of New Hampshire Scholars' Repository Division 21 Fire Supression Chapter 5 Technical Construction and Renovation Standards 4-23-2015 211100 - Facility Fire-Suppression

More information

WET-PIPE SPRINKLER SYSTEMS

WET-PIPE SPRINKLER SYSTEMS SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS PART 0 A/E INSTRUCTIONS 0.01 Design Requirements A. Pumping system design 1. A primary-secondary pumping system is preferred. Redundant pipes are required for chillers and boilers. 2. Select pumps to operate

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 1314W - AUTOMATIC SPRINKLER SYSTEMS (WET PIPE SYSTEMS) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

END OF SECTION

END OF SECTION SECTION 210553 ~IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT PART 1 -GENERAL 1.1 SUMMARY Section Includes: I. Equipment labels. 2. Warning signs and labels. 3. Pipe labels. 1.2 ACTION SUBMITTALS

More information

REFRIGERANT PIPING

REFRIGERANT PIPING SECTION 232300 - REFRIGERANT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION HYDRONIC PIPING

SECTION HYDRONIC PIPING SECTION 23 21 13 HYDRONIC PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes pipe and fitting materials, joining methods, special-duty valves, and specialties for the following: 1. Hot-water

More information

SECTION COMMON MOTOR REQUIREMENTS FOR FIRE SUPPRESSION EQUIPMENT

SECTION COMMON MOTOR REQUIREMENTS FOR FIRE SUPPRESSION EQUIPMENT Xl414-07 SECTION 210513- COMMON MOTOR REQUIREMENTS FOR FIRE SUPPRESSION EQUIPMENT PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals.

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals. SECTION 23 21 23 - HYDRONIC PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

A. This Section includes the following domestic water piping specialties:

A. This Section includes the following domestic water piping specialties: SECTION 221119 DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements. SECTION 21 13 13 FIRE PROTECTION SPRINKLER SYSTEMS PART 1 - GENERAL 1.01 SUMMARY A. Section includes labor and materials for the installation of a hydraulically calculated automatic, wet-pipe sprinkler

More information

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN DIVISION 21 - FIRE SUPPRESSION (REFER TO SECTION 23 05 00 FOR BASIC FIRE SUPPRESSION REQUIREMENTS) 21 05 00 Common Work Results for Fire Suppression 21 13 13 Wet-Pipe Sprinkler Systems END OF SECTION FIRE

More information

B. Standard-Pressure Standpipe Piping: Fire-suppression standpipe piping designed to operate at working pressure 175 psig (1200 kpa) maximum.

B. Standard-Pressure Standpipe Piping: Fire-suppression standpipe piping designed to operate at working pressure 175 psig (1200 kpa) maximum. Page 211200-1 SECTION 211200 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION SPRINKLER SYSTEMS

SECTION SPRINKLER SYSTEMS SECTION 15325 SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Wet-pipe sprinkler systems. B. Preaction sprinkler systems. C. System design, installation, and certification. D. Fire department

More information

North Hanover Township School District North Hanover Township, New Jersey

North Hanover Township School District North Hanover Township, New Jersey SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

WATERSTONE ASSISTED LIVING AND MEMORY CARE COMMON WORK FIRE SUPPRESSION BATON ROUGE, LOUISIANA SECTION

WATERSTONE ASSISTED LIVING AND MEMORY CARE COMMON WORK FIRE SUPPRESSION BATON ROUGE, LOUISIANA SECTION WATERSTONE ASSISTED LIVING AND MEMORY CARE COMMON WORK FIRE SUPPRESSION BATON ROUGE, LOUISIANA SECTION 21 05 00 SECTION 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 - GENERAL 1.1 RELATED DOCUMENTS

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION ELECTRIC WATER HEATERS

SECTION ELECTRIC WATER HEATERS SECTION 22 36 01 ELECTRIC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

SECTION FAN COIL UNITS

SECTION FAN COIL UNITS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers. SECTION 22 10 00 PLUMBING PIPING AND PUMPS PART 1 - GENERAL 1.1 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018 SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION (15530) - REFRIGERANT PIPING

SECTION (15530) - REFRIGERANT PIPING SECTION 23 23 00 (15530) - REFRIGERANT PIPING PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Tubes. 2. Fittings. 3. Joining Materials. 4. Specialties. B. Related Sections: 1. Section 07 92 00 (07920)

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 23 2113 - HYDRONIC PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes pipe and fitting materials, joining methods, special-duty valves, and certain specialties for the following: 1. Chilled

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM SECTION 21 0000 AUTOMATIC FIRE SPRINKLER SYSTEM PART 1 GENERAL 1.1 QUALITY ASSURANCE A. Codes and Standards: 1. FBC (Florida Building Code 2015) 2. FBC (Florida Fire Code 2015) 3. NFPA #13R (Standard for

More information

SECTION FIRE-SUPPRESSION PIPING

SECTION FIRE-SUPPRESSION PIPING SECTION 211313 FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. Page 238219-1 SECTION 238219 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 10 - SPECIALTIES

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 10 - SPECIALTIES SECTION 105200 - FIRE-PROTECTION SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING

D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION WET-PIPE FIRE SUPPRESSION SPRINKLERS

SECTION WET-PIPE FIRE SUPPRESSION SPRINKLERS SECTION 15932 WET-PIPE FIRE SUPPRESSION SPRINKLERS PART 1 - GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred

More information

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements. FIRE PROTECTION GENERAL INFORMATION 1.1 Refer to Section 230000 for General Mechanical Requirements. 1.2 Refer to Section 230529 for Hangers and Supports. 1.3 Refer to Section 230553 for Pipe and Equipment

More information

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Construction Standards Page 233423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING. A. This Section includes the following sanitary drainage piping specialties:

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING. A. This Section includes the following sanitary drainage piping specialties: SECTION 221319 - SANITARY WASTE PIPING SPECIALTIES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following sanitary drainage piping specialties: 1. Backwater valves. 2. Cleanouts. 3. Floor

More information

DIVISION 21 FIRE PROTECTION ISSUE DATE REVISION

DIVISION 21 FIRE PROTECTION ISSUE DATE REVISION Table of Contents TOC Page 1 DIVISION 21 FIRE PROTECTION ISSUE DATE REVISION 210517 SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING 08/15/18 0 210523 GENERAL-DUTY VALVES FOR FIRE PROTECTION PIPING

More information

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016 SECTION 23 21 23 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions and Division 01 Specification Sections, apply to this Section.

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING SECTION 221123 - DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following all-bronze and bronze-fitted centrifugal pumps for domestic cold- and hot-water circulation: 1.

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14 SECTION 210523 - GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

NATURAL GAS PIPING

NATURAL GAS PIPING SECTION 15496 - NATURAL GAS PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Council Bluffs, Iowa Division TOC 1 TABLE OF CONTENTS DIVISION 21 FIRE SUPPRESSION

Council Bluffs, Iowa Division TOC 1 TABLE OF CONTENTS DIVISION 21 FIRE SUPPRESSION Bluffs Tower Apartments Section TOC Council Bluffs, Iowa Division TOC 1 TABLE OF CONTENTS DIVISION 21 FIRE SUPPRESSION 211000 WATER-BASED FIRE-SUPPRESSION SYSTEMS 213113 ELECTRIC-DRIVE, CENTRIFUGAL FIRE

More information

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 238126 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Construction Standards Page

Construction Standards Page Construction Standards Page 236313-1 SECTION 236313 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Ratio Architects, Inc. Section Refrigerant Piping

Ratio Architects, Inc. Section Refrigerant Piping SECTION 232300 - REFRIGERANT PIPING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Refrigerant pipes and fittings. 2. Refrigerant piping valves and specialties. 3. Refrigerants. 1.2 ACTION SUBMITTALS

More information

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components. Page 238126-1 SECTION 238126 - This Section includes requirements for the LEED Rating System. However, equipment specified in this Section may not qualify for LEED Rating System prerequisites and credits.

More information

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Pipe and Pipe Fittings. B. Air compressor. C. Air receiver and accessories. D. Aftercooler. E. Refrigerated air dryer. F. Pressure reducing station. 1.02 RELATED

More information

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section PART 1 - GENERAL 1.00 GENERAL PROVISIONS A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section 1.01 DESCRIPTION OF WORK A. Work Included: Provide

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 22 3300 - ELECTRIC, DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

PROJ. NO SECTION REFRIGERANT PIPING

PROJ. NO SECTION REFRIGERANT PIPING SECTION 23 23 00 REFRIGERANT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION ELECTRIC WATER HEATERS

SECTION ELECTRIC WATER HEATERS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant. SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this

More information

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from

More information

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - Systems and Equipment. Page 238239-1 SECTION 238239 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

B. HI Compliance: Design, manufacture, and install pumps in accordance with HI "Hydraulic Institute Standards."

B. HI Compliance: Design, manufacture, and install pumps in accordance with HI Hydraulic Institute Standards. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

SECTION PREACTION SPRINKLER SYSTEMS

SECTION PREACTION SPRINKLER SYSTEMS PART 1 GENERAL SECTION 211316 - PREACTION SPRINKLER SYSTEMS 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR September 2012, rev. 00 26 0553 Identification for Electrical Systems PART 1. GENERAL 1.01 Summary A. Section Includes: 1.02 Submittals 1. Identification for raceways. 2. Identification of power and control

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

SECTION REFRIGERANT PIPING

SECTION REFRIGERANT PIPING SECTION 23783 REFRIGERANT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

SECTION (15530) - REFRIGERANT PIPING

SECTION (15530) - REFRIGERANT PIPING PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Tubes. 2. Fittings. SECTION 23 23 00 (15530) - REFRIGERANT PIPING 3. Joining Materials. 4. Specialties. B. Related Sections: 1.02 REFERENCES 1. Section

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES SECTION 23 23 00 REFRIGERANT PIPING AND SPECIALITIES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Refrigerant piping. 2. Unions, flanges, and couplings. 3. Pipe hangers and supports. 4. Refrigerant

More information

SECTION SPRINKLER SYSTEMS

SECTION SPRINKLER SYSTEMS SECTION 13900 SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO SECTION 210523 - GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

FIRE SUPPRESSION SPRINKLER SYSTEM

FIRE SUPPRESSION SPRINKLER SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this

More information

SECTION DUCTWORK. A. Section Painting: Weld priming, weather resistant, paint or coating.

SECTION DUCTWORK. A. Section Painting: Weld priming, weather resistant, paint or coating. SECTION 15890 DUCTWORK PART 1 - GENERAL 1.1 SECTION INCLUDES A. Metal ductwork. B. Duct cleaning. 1.2 RELATED SECTIONS A. Section 09900 - Painting: Weld priming, weather resistant, paint or coating. B.

More information

Lucy s Pizza 100% CD Specification 06/22/2018

Lucy s Pizza 100% CD Specification 06/22/2018 DIVISION 21: FIRE SUPPRESSION 210500 COMMON REQUIREMENTS FOR FIRE SUPPRESSION 210548 VIBRATION & SEISMIC CONTROLS FOR FIRE SUPPRESSION PIPING & EQUIPMENT 210553 IDENTIFICATION FOR FIRE SUPPRESSION PIPING

More information

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University. 15500 - FIRE PROTECTION PART I DESIGN GUIDELINES A. General 1. Vertical fire pumps shall not be used at the University. 2. coupling piping shall be permitted for sprinkler and standpipe systems only. B.

More information

SECTION BASIC MATERIALS AND METHODS

SECTION BASIC MATERIALS AND METHODS SECTION 15050 BASIC MATERIALS AND METHODS PART 1 1.1 SECTION INCLUDES A. General Conditions B. Supplementary Conditions C. Division 1 D. Mechanical basic requirements E. Electric Motors F. Pipe, Valve,

More information

DLKF. EBARA Submersible Sewage Pumps Specifications Project: Model: Chk d: Date:

DLKF. EBARA Submersible Sewage Pumps Specifications Project: Model: Chk d: Date: DLKF A. General: Provide submersible sewage pumps suitable for continuous duty operation underwater without loss of watertight integrity to a depth of 65 feet. Pump system design shall include a guide

More information

SECTION ENCLOSED CONTROLLERS

SECTION ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes ac,

More information

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following: SECTION 21 10 00 - WATER-BASED FIRE-SUPPRESSION PART I - GENERAL 1.1 SUMMARY A. Inclusion of sprinkler and standpipe systems shall be as determined by NFPA National Fire Code pamphlet 101 and program statement.

More information

SECTION FIRE-SUPPRESSION SYSTEMS

SECTION FIRE-SUPPRESSION SYSTEMS SECTION 13900 FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Automatic wet-type, Class I, fire-suppression standpipes and branches for sprinklers. 2. Wet-pipe, fire-suppression

More information

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM SECTION 21 10 00 PART 1 - GENERAL 1.1 CODES A. Work shall conform to NFPA 13 Sprinkler Systems, 2002 Edition and NFPA 24 Outside Protection, 2002 Edition. NFPA 14 Standpipe Systems, 2000 Edition and International

More information

SECTION STEAM CONDENSATE PUMPS

SECTION STEAM CONDENSATE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 22 23 STEAM CONDENSATE PUMPS SPEC WRITER NOTES: 1. Delete between // ---- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

Essex County College - West Essex Campus Addition And Renovations dib # / SECTION HYDRONIC PIPING SPECIALTIES PART 1- GENERAL

Essex County College - West Essex Campus Addition And Renovations dib # / SECTION HYDRONIC PIPING SPECIALTIES PART 1- GENERAL Essex County College - West Essex Campus Addition And Renovations dib # 54292 / 11-14 SECTION 232116 - HYDRONIC PIPING SPECIALTIES PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions

More information