1 Electronic Control Manual 16 Sensors and Stats Section S Technical Bulletin Issue Date 0101 GCS-000- Multipoint Carbon Dioxide Gas Concentration Sampler Product Overview Page *3 Installation 5 Mounting Supplies Needed *5 Location Considerations *5 Mounting Procedure *6 Air Sampling Device Installation *7 Wiring *8 Maintenance *11 Servicing the CO Sensor *11 Ordering Information *11 * Indicates those sections where changes have occurred since the last printing. 001 Johnson Controls, Inc. 1 Part No , Rev. B Code No. LIT-1618T
2 S Sensors and Stats GCS-000- Multipoint Carbon Dioxide Gas Concentration Sampler
3 Product Overview The GCS-000- assembly consists of the following: a CO sensor two 3-way V11HGA-100 solenoid valves, which switch the input source of sampled air from one of three sampling tubes to the CO sensor a pump, which maintains proper airflow between the air sampling points and the CO sensor regardless of duct static pressure a 4 VAC transformer, which accepts 10 VAC line voltage to power the CO sensor and the pump an A filter, which inhibits contamination of the pump and the CO sensing chamber (installed) two front-mount wiring terminal blocks three air sampling devices, which can be mounted up to 30.5 m (100 ft) away from the unit (up to 9.1m [30 ft] for supply air) Upper Wiring Block 4 VAC Transformer Upper Mounting Hole HNG CO Sampling Tubes A Filter Solenoid Valves OUTDOOR SUPPLY RETURN 1 CO Sensor Pump Lower Wiring Block Lower Mounting Holes box Figure 1: GCS-000- Carbon Dioxide Gas Concentration Sampler (Shown with Door Open) S Sensors and Stats GCS-000- Multipoint Carbon Dioxide Gas Concentration Sampler 3
4 4 S Sensors and Stats GCS-000- Multipoint Carbon Dioxide Gas Concentration Sampler
5 Installation Mounting Supplies Needed Location Considerations To properly mount the GCS-000-, you need the following: 7 mm (1/4 in.) Outside Diameter (O.D.) polytubing pencil to mark the mounting holes 8 mm (5/16 in.) drill bit drill anchors and screws (provided) screwdriver, straight-slot Consider the following when deciding on a location for the GCS-000-: Stability: Mount the GCS-000- to a flat, stable, non-vibrating mounting surface (heavy-duty drywall or concrete) where the unit will not be subjected to moisture accumulation or drastic temperature variation. Anchors and screws are provided. Ambient Operating Conditions: Temperature: 0 to 40 C (3 to 104 F); humidity: 10 to 95% RH, non-condensing. Position: Mount the GCS-000- vertically. Air Sampling Locations: Remote or local sensing is acceptable; the outdoor and return air sampling devices can be mounted up to 30.5 m (100 ft) away from the unit. The supply air sampling device can be mounted up to 9.1 m (30 ft) away from the unit. Air Stratification: The air sampling devices must collect air that is sufficiently mixed in order to deliver accurate CO readings. Outdoor Air Flow: The outdoor air flow sampling device can be mounted in the outdoor air intake ductwork. However, if it is likely that exhaust air could affect the sensor in the outdoor air intake ductwork, then mount the sampling device outdoors (properly enclosed and free from exposure to the elements). S Sensors and Stats GCS-000- Multipoint Carbon Dioxide Gas Concentration Sampler 5
6 Mounting Procedure To mount the GCS-000-: 1. Carefully read the Location Considerations section of this bulletin.. Open the cover of the GCS-000- to access the inside of the unit. 3. Remove all packing material inside the unit, including the tie-wrap around the pump. 4. Use a pencil to mark the location for the upper mounting hole. 5. Use an 8 mm (5/16 in.) drill bit to make a pilot hole in either heavy-duty drywall or concrete. If the wall is concrete, make the hole at least 38 mm (1-1/ in.) deep. 6. Insert the anchor (provided) into the hole as shown in Figure. Turn the screw enough to hold it in place, but leave at least 7 mm (1/4 in.) of the screw sticking out of the wall. 7. Hang the GCS-000- on the screw, and level the unit. Mark the bottom mounting holes. 8. Drill pilot holes for the bottom mounting holes as in Step 4 above. 9. Insert anchors and install screws (see Figure ) into the bottom mounting holes. Tighten all three screws. 10. Remove appropriate knockouts for the power source, air sampling tubes, and low-voltage output from the CO sensor. 153 (6) 19 (0.75) Insert the anchor, then the screw. OUTDOOR SUPPLY RETURN 457 (18) (16) 108 (4.5) 5 (1) 305 (1) 54 (10) 3 (1.5) 3 Mounting Figure : Product and Mounting Hole Dimensions in mm (in.) Front and Bottom Views with Door Open 6 S Sensors and Stats GCS-000- Multipoint Carbon Dioxide Gas Concentration Sampler
7 Air Sampling Device Installation Use the following instructions to install the air sampling devices. If needed, see Figure 3 for an air sampling device arrangement example. 1. Select a mounting location on the first duct (supply, return, or outdoor) for one of the air sampling devices. Be sure to read the Location Considerations section of this bulletin. Note: To ensure an acceptable response time, mount the GCS-000- so that it is less than 9.1 m (30 ft) from the air sampling device leading to supply air.. Install the air sampling device on the duct with the open end facing into the airstream (Figure 3). Seal the space between the tube and the duct to prevent air loss from the duct. Note: Outdoor Air Flow: The outdoor air flow sampling device can be mounted in the outdoor air intake ductwork. However, if it is likely that exhaust air could affect the sensor in the outdoor air intake ductwork, then mount the sampling device outdoors. 3. Use a length of 7 mm (1/4 in.) outside diameter flexible tubing to connect the air sampling tube to the appropriate port located inside the GCS Ports are labeled outdoor, supply, and return accordingly. 4. Install the other two air sampling devices in the other two locations specified by the engineering drawings. 5. Proceed to the Wiring section. Direction of Flow Air Sampling Location Air Sampling Device To Air Sampling Location 1 HNG OUTDOOR SUPPLY RETURN To Air Sampling Location 3 1 Figure 3: Sample Arrangement of the Wall-Mounted GCS-000- and an Air Sampling Device Installed on a Duct Airflow S Sensors and Stats GCS-000- Multipoint Carbon Dioxide Gas Concentration Sampler 7
8 Wiring Wire Gauge Designations! WARNING: Shock Hazard. Avoid serious personal injury by disconnecting the power supply before making wiring connections. Electrical connections are made to the screw terminals using 10 to AWG (5 mm -0.3 mm ) wire. The GCS-000- has two terminal blocks (see Figure 4 for terminal block locations): Upper terminal block (supply) accepts 10 V line voltage. See Table 1 for terminal designations. Lower terminal block (output) contains the terminals for the CO sensor and internal wiring connections for the solenoid valves. See Table for terminal designations. Note: Wiring connections must be made in accordance with the National Electrical Code and local regulations for low-voltage wiring. Upper Block 1 Lower Block Block Figure 4: Upper and Lower Block Locations 8 S Sensors and Stats GCS-000- Multipoint Carbon Dioxide Gas Concentration Sampler
9 ! CAUTION: Equipment Damage Hazard. The CO sensor power input (s 6 and 7) must be electrically isolated. Do not connect 6 or 7 (lower terminal block) to any other GCS-000- terminal. A connection between either 6 or 7 and the signal return ( of the lower terminal block) will permanently damage the unit. Also, do not use 6 or 7 to supply power to any other device, as this may overload GCS-000- s power transformer. Table 1: Upper Block (Supply) Designations for the GCS-000- Number Designation Description 1 Hot 10 VAC Neutral 10 VAC Return 3 Ground Ground Table : Lower Block Designations Number A B Designation 4 VAC Power 4 VAC Power Description Power from the Transformer to the CO Sensor, Pump, and Solenoid Valves C V11-1 Input 4 VAC Power Input to V11-1 D 4 VAC Return Transformer Secondary Return E 4 VAC Return Same as D F V11- Input 4 VAC Power Input to V11- S Sensors and Stats GCS-000- Multipoint Carbon Dioxide Gas Concentration Sampler 9
10 Outdoor Air VAV Air Handling System Return FAN Air Figure 5 shows an example of wiring connections using a GCS-000- and a digital control module. FAN AMS Supply Air Hot Neutral Ground 10 VAC Power Supply HNG (Properly Enclosed Outdoor Air or Duct Point) OUTDOOR SUPPLY RETURN GCS-000- A B C D E F A BCDEF FM-ORE () FM-IAN DCM 140 Installations (-channel Input) FM-IUN DCM 101 Installations (-channel Input) Metasys NCM101/DCM 101 (or DCM 140 installed as a DCM 101) CO Readings Monitor CO levels in return, supply, and outdoor air. Perform CO high-limit control using return air CO. Define high-limit CO alarm levels. Calculate outdoor air flow. Document supply, return, outdoor air flow, and CO levels. Control outdoor air flow per a user-defined rate. Provide an HVAC system diagnostics tool. Typical Figure 5: Typical Application of a GCS-000- with a Digital Control Module 10 S Sensors and Stats GCS-000- Multipoint Carbon Dioxide Gas Concentration Sampler
11 Federal Communications Commission (FCC) This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) device may not cause harmful interference, and () device must accept any interference received, including interference that may cause undesired operation. Maintenance Servicing the CO Sensor Ordering Information When properly installed, the GCS-000- is accurate to ±100 ppm per year. Verify the calibration of the CO sensor after the sensor has been in operation for one full year and annually thereafter. Whenever you suspect an accuracy problem, recalibrate the CO sensor using the single-point calibration procedure described in the CO sensor literature (packaged with the GCS-000-). When the A filter becomes dirty, order a replacement filter. See Table 3 below. The CO sensor is not field repairable. If the CO sensor fails verification, and subsequent field adjustments of the calibration settings do not correct the problem, contact your local Johnson Controls branch office and order a replacement (there is no product number for a replacement sensor listed in Table 3 because the number changes frequently). For further sensor replacement information, see the CO sensor literature (packaged with the GCS-000-). To order a GCS-000- Multipoint Carbon Dioxide Gas Concentration Sampler, contact your local Johnson Controls branch and specify the complete product code number. An accessory single-point calibration kit for the CO sensor also is available for order. See the CO sensor literature (packaged with the GCS-000-) for more information. Table 3: Ordering Information Product Code Number Product GCS-000- Replacement Components A V11HGA-100 Multipoint Carbon Dioxide Gas Concentration Sampler Filter 3-way Solenoid Air Valve A-303 Air Sampling Device PD Pump S Sensors and Stats GCS-000- Multipoint Carbon Dioxide Gas Concentration Sampler 11
12 Notes Controls Group E. Michigan Street FAN 16 P.O. Box 43 Electronic Controls Manual Milwaukee, WI 5301 Printed in U.S.A. 1 S Sensors and Stats GCS-000- Multipoint Carbon Dioxide Gas Concentration Sampler
TRUERH Series HE-67xx Humidity Element with Temperature Sensor
Installation Instructions HE-67xx Issue Date 0501 TRUERH Series HE-67xx Humidity Element with Temperature Sensor Installation IMPORTANT: The HE-67xx Series Humidity Element with Temperature Sensor is designed
More informationMR3CCUHV Temperature/Defrost Control
Master Catalog 125 Temperature Controls Section A Product/Technical Bulletin Issue Date 0401 MR3CCUHV Temperature/Defrost Control The MR3CCUHV Temperature/Defrost Control is designed to control the temperature
More informationW43A Humidistat. Features and Benefits
Master Catalog 125 Humidity Controls Section W Product/Technical Bulletin W43A Issue Date 1095 W43A The W43A controls humidifying and/or dehumidifying equipment. Typical uses include the control of humidity
More informationYork 25-Ton VAV Rooftop Unit
HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 0996 York 25-Ton VAV Rooftop Unit Introduction Page 3 Overview *3 Configuration 5 Sequence of Operation 7 Modes of Operation
More informationRLD-H10G Refrigerant Leak Detectors
FANs 125, 121 Product/Technical Bulletin RLD-H10G Issue Date 0396 RLD-H10G Refrigerant Leak Detectors The RLD-H10G is a professional grade leak detector for use by refrigeration and air conditioning technicians.
More informationInstallation and Maintenance Manual IM 1038
Installation and Maintenance Manual IM 1038 BACnet VAV Actuator Room Sensor Group: Controls Part Number: IM 1038 Date: March 2010 Models 2508031 and 2508032 Table of Contents Introduction.... 2 Revision
More informationMS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack
Product/Technical MS4PMUHVT Issue Date 09/30/02 MS4PMUHVT Multi-Stage Electronic Control with Relay Pack The MS4PMUHVT Multi-Stage Electronic Control is intended for multi-stage temperature control applications.
More informationRoom Sensor for BACnet VAV Actuator
BACnet VAV Actuator Room Sensor Installation Manual IM 1038 Group: Controls Part Number: IM 1038 Date: 3/4/2010 Supersedes: New Room Sensor for BACnet VAV Actuator Model(s): 2508031 & 2508032 2010 McQuay
More informationRLD-H10P Refrigerant Leak Detector
FANs 125, 121 Product/Technical Bulletin RLD-H10P Issue Date 0396 RLD-H10P Refrigerant Leak Detector The RLD-H10P is a professional grade leak detector for use by refrigeration and air conditioning technicians.
More informationTEC1100 Series Thermostats
Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 0601 TEC1100 Series Thermostats TEC1100 is a series of non-programmable thermostats with a
More informationInstallation and Operation Manual
Model 8120X Digital Ventilation Controller CODE MIN/ HR Installation and Operation Manual TABLE OF CONTENTS WARNINGS AND CAUTIONS Warnings and Cautions... 3 Package Contents... 4 Specifications.... 4 Mounting
More informationT500 Series Non-Programmable Thermostats
FANs 216, 1628.3 Product/Technical Bulletin T500 Issue Date 0899 T500 Series Non-Programmable Thermostats T500 Series Thermostats provide an economical control solution for single-stage, multi-stage, or
More informationMR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack
Master Catalog 125 Temperature Controls Section A Product/Technical Bulletin Issue Date 1098 MR4PMUHV Electronic Temperature/Defrost Control with Relay Pack The MR series temperature controls are designed
More informationTEC2100 Series Networked Thermostats
Product Bulletin Issue Date February 11, 2004 TEC2100 Series Networked Thermostats The TEC2100 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment
More informationACT2-CS Convenience Store Controller
Refrigeration Systems Technical Manual 804 Product Bulletins Section Product Bulletin Issue Date 0899 ACT2-CS Convenience Store Controller The ACT2-CS Convenience Store Controller is a fully programmable,
More informationA99B Series Temperature Sensors
FANs 125, 121, 930, 930.5 Product/Technical Bulletin A99 Issue Date 1118 A99B Series Temperature s The A99B Series Temperature s are passive PTC (Positive Temperature Coefficient) sensors. The A99B sensors
More informationBooster Fan Ducting Kit Installation Instruction for Hybrid Electric Heat Pump Water Heaters
Booster Fan Ducting Kit Installation Instruction for Hybrid Electric Heat Pump Water Heaters This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety
More informationSafety & Installation Instructions
Premium Programmable Thermostat Safety & Installation Instructions Model 8570 READ AND SAVE THESE INSTRUCTIONS TABLE OF CONTENTS PAGE SPECIFICATIONS............................. 1 WIRE REQUIREMENTS.........................
More informationEXAMPLES OF HOW TO ORDER
E 3 Point PRODUCT SUBMITTAL Toxic and Combustible Gas Detector Standalone Platform (Single or Dual-Gas Monitoring) ORDERING INFORMATION Single-Gas or Dual-Gas Configuration: Base Unit, Surface-Mount Base
More informationEXAMPLES OF HOW TO ORDER
E 3 Point PRODUCT SUBMITTAL Toxic and Combustible Gas Detector Standalone Platform (Single or Dual-Gas Monitoring) ORDERING INFORMATION Single-Gas or Dual-Gas Configuration: Base Unit, Surface-Mount Base
More informationTEC210x-2 Series Networked Thermostats
Product Bulletin Issue Date February 1, 2005 TEC210x-2 Series Networked Thermostats The TEC210x-2 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment
More informationSystem 350 S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules
System 350 S350A Temperature, S351A Humidity, and S352A Pressure Stage s FANs 930, 125 Product/Technical Bulletin S350 Issue Date 0300 The S350A, S351A, and S352A Stage s are intended to be used with System
More informationLocation Requirements
24-7701- 136, Rev. B FANs 216, 1628.3 Installation Instructions HH-6705 Issue Date 0316 TRUERH Series HH-6705 Duct Humidistat I nstallation IMPORTANT: Use this HH-6705 Series Duct Humidistat only as an
More informationJohnson Controls Fan Coil Units and Direct Digital Controls
Product Bulletin Issue Date August 12, 2005 Johnson Controls Fan Coil Units and Direct Digital Controls This offering includes Johnson Controls fan coil units with a factory-installed Johnson Controls
More informationTrueAlarm Analog Sensing
TrueAlarm Analog Sensing UL, ULC Listed* Addressable Duct Sensor Housings with TrueAlarm Photoelectric Sensor; Available with Multiple Relay Features Compact air duct sensor housing with clear cover to
More informationModel Smart Digital Humidistat
Model 072000 Smart Digital Humidistat Installation and Owner's Manual TB 213 P/N 090375A0213 REV. E December 5, 2006 Copyright 2004-2006, EWC Controls Inc., All Rights Reserved RH OD %RH TEMP Package includes:
More informationMetasys System Extended Architecture Smoke Control UL 864 UUKL Compliance
Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist Code No. LIT-1201754 Release 1.2 Issued February 10, 2005 Document Introduction.................................................
More informationIMPORTANT WARNINGS IMPORTANT SAFETY INSTRUCTIONS
IMPORTANT WARNINGS IMPORTANT SAFETY INSTRUCTIONS Suncourt recommends professional installation of the Airiva (or by an accomplished DIY person) Please read and save these entire instructions before starting
More informationDuct and Rough Service Carbon Monoxide Sensor
Product Identification and Overview Duct and Rough Service Carbon Monoxide Sensor BAPI s Carbon Monoxide Sensor offers enhanced electrochemical sensing with outstanding accuracy at low concentrations.
More informationPECO. WavePRO Wireless System INSTALLATION GUIDE: T2500 THERMOSTAT AND R2500 RECEIVER. The Peco WavePRO Wireless System
PECO WavePRO Wireless System INSTALLATION GUIDE: T2500 THERMOSTAT AND R2500 RECEIVER Wireless control for up to 3-HEAT/ 2-COOL heat pump and conventional systems (gas,oil,electric). Benefits: Reduced installation
More informationLiebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet
The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Installation
More informationT8190A/191108AJ Heating or Cooling Thermostat/Wallplate; T8190A/Q682B Heating/Cooling Thermostat/Subbase
M3375 M3375 T890A/908AJ Heating or Cooling Thermostat/Wallplate; T890A/Q68B Heating/Cooling Thermostat/Subbase Installation Instructions for the Trained Service Technician. Preparation NOTE: Order Q68B
More informationHigh Power Range Hood
High Power Range Hood Pictured Model: CW500 Installation and Operating Instructions Please read all instructions before installing and operating. All wiring and installation must be in accordance with
More informationInstallation Instructions
Installation Instructions For Fully Integrated NoFrost Combined Refrigerator-Freezers HC 2062 HCB 2062 HC/HCB 20 7082 373-00 Important PLEASE READ AND FOLLOW THESE INSTRUCTIONS These instructions contain
More informationDual Column Dehydrating Breather Manual
Dual Column Dehydrating Breather Manual DCB-MANUAL 1.6 Read and understand this manual prior to operating or servicing the products. SPX Transformer Solutions, Inc., Service & Components Division U.S.
More informationModel 1820 Dehumidifier
Model 1820 Dehumidifier Installation Instructions SAFETY INSTRUCTIONS WARNING 1. 120 Volts may cause serious injury from electric shock. Disconnect electrical power before starting installation or servicing.
More informationSafety and Installation Instructions Model 1700
Dehumidifier Filter Access Humidity Control Inlet Filter Access Outlet Service Access Port Wiring Access Wire Routing Port Drain On/Off Switch Safety and Installation Instructions Model 1700 INSTALLER
More informationP266 Series Single-Phase Condenser Fan Speed Control
P266 Series Single-Phase Condenser Fan Speed Control Product Bulletin P266xxx-x Code No. LIT-12011534 Issued June 24, 2009 The P266 Single-Phase Condenser Fan Speed Control is a cost-effective, weather-resistant,
More informationWT-4000 Series Pneumatic-to-Direct Digital Control (DDC)
WT-4000 Series Pneumatic-to-Direct Digital Control (DDC) Room Thermostats Product Bulletin WT-4002-MCR, WT-4002-MCM, WT-4002-MFR, WT-4002-MFM, WT-ROUTER, WT-BAC-IP Code No. LIT-12011890 Issued August 31,
More informationSAFETY AND INSTALLATION MANUAL MODEL 8100
SAFETY AND INSTALLATION MANUAL ENERGY RECOVERY VENTILATORS MODEL 8100 Provides year-round fresh air Recovers 77% of the apparent heating or cooling energy from the exhausted air See Warnings Page 3 Table
More informationTM-3100 Series Room Temperature Sensor
PB_TM-3100_12 2009 TM-3100 Series Room Temperature Sensor The Johnson Controls TM-3100 Series Room Temperature Sensor provide passive sensing of temperature in HVAC application. The TM-3100 is equipped
More informationModel 76 Dehumidifier Control Installation Instructions
Model 76 Dehumidifier Control Installation Instructions READ AND SAVE THESE INSTRUCTIONS The Model 76 is for use with any dehumidifier as an EXTERNAL CONTROL, including Aprilaire Models 1830, 1850(F)(W),
More informationMANUAL RESET ALARM RELEASE
Fire Door Release MODEL AR-D MANUAL RESET ALARM RELEASE INSTRUCTION MANUAL AR-D GENERAL INFORMATION 1. Review all installation instructions, procedures, cautions and warnings contained within this manual
More informationInstallation Instructions Preference Wall Mount Range Hood
Installation Instructions Preference Wall Mount Range Hood For use with models PHW30 and PHW36 Part No. 101745 Rev. D Table of Contents Important Safety Instructions... 1 Important Information About Safety
More informationInstallation Instructions. Millennia Island (Ceiling Mount) Range Hoods. Models: DHI361, DHI421, DHI482 and DHI542
Millennia Island (Ceiling Mount) Range Hoods Models: DHI361, DHI421, DHI482 and DHI542 Installation Instructions Approved for use with all dacor ranges and cooktops. IMPORTANT: INSTALLATION OF THIS HOOD
More informationINSTALLER'S GUIDE. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
11-AC11D2-5 INSTALLER'S GUIDE ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES Models: Condensing Units 2A7A5024-048, 2A7A4018-060, 2A7A2018-060 & 2A7A1018-060 IMPORTANT
More informationMiniCO, MiniH 2 S, MiniOX, MiniOX Remote, MiniCl 2. , and MiniClO 2. Responder Detectors Instruction Manual "! WARNING
MiniCO, MiniH 2 S, MiniOX, MiniOX Remote, MiniCl 2 TM, and MiniClO 2 TM Responder Detectors Instruction Manual "! WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE
More informationInstallation Guide. Dehumidification. Fresh Air Ventilation. Compact Size. Energy Efficient. RXID-AW90A Whole House Dehumidifier
RXID-AW90A Whole House Dehumidifier with fresh air ventilation Installation Guide Dehumidification Fresh Air Ventilation Compact Size Energy Efficient The whole house dehumidifier integrates highcapacity
More informationGARAGE HEATER WITH REMOTE INSTRUCTION MANUAL MODEL: HA24-100E HA24-150E. Figure 1
GARAGE HEATER WITH REMOTE INSTRUCTION MANUAL MODEL: HA24-100E HA24-150E Figure 1 PET OWNERS WARNING: Health warning for some small pets, including birds, as they are extremely sensitive to the fumes produced
More informationInterrogator 200 Audio Verification Module (AVM)
Interrogator 200 Audio Verification Module (AVM) Document Number: 466-1153 Rev. B July 1996 Audio Verification Module Use a maximum of 500 feet of cable for all speakers and microphones. For example, if
More informationQ7800H Integrated Burner Control Subpanel
Q7800H Integrated Burner Control Subpanel INSTALLATION INSTRUCTIONS FEATURES Unique subpanel design eliminates extensive wiring in the OEM control panel. One subpanel design covers multiple applications.
More informationADC-T2000. Smart Thermostat v1.5
ADC-T2000 ADC-T2000 Smart Thermostat User Product Guide Manual 170308 v1.5 Smart Thermostat Product Manual 1 Before installing or servicing the thermostat, turn off power to the system at the circuit breaker.
More informationWD7664 / WD7663 Maxon Burner Ellis Whisper Dryer Installation & Start UP
WD7664 / WD7663 Maxon Burner Ellis Whisper Dryer Installation & Start UP Receiving Do a quick visual inspection on the truck for any major damage prior to signing the paperwork. Damage should be noted
More information/9308 External Battery Chargers Installation Instructions
4081-9306/9308 External Battery Chargers Installation Instructions Introduction This publication describes the installation procedure for an External Battery Charger used with the 4100U or 4100ES System.
More information72 ONYX XL FLAT PANEL ELECTRIC FIREPLACE
72 ONYX XL FLAT PANEL ELECTRIC FIREPLACE Model Numbers: 80005 OWNER S MANUAL WARNING Read and understand this entire owner s manual, including all safety information, before plugging in or using this product.
More informationDESIGN MANUAL. The information in this doucment is applicable to sensors built in September, 2009 or later (Firmware 3.0)
DESIGN MANUAL MODEL GIR910 INFRARED CARBON DIOXIDE (CO 2 ) GAS SENSOR 70091 The information in this doucment is applicable to sensors built in September, 2009 or later (Firmware 3.0) The information and
More informationDWYER INSTRUMENTS, INC. P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Series 670 Hood Monitor. Bulletin AV-670
Bulletin AV-670 Series 670 Hood Monitor Specifications - Installation and Operating Instructions DWYER INSTRUMENTS, INC. P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Phone: 219/879-8000 Fax: 219/872-9057
More informationDirect Gas-Fired Make-Up Air
Direct Gas-Fired Make-Up Air Model TSU Heavy Duty, High Airflow Applications Manufacturing and Industrial Facilities Up to 64,000 cfm August 2012 Products Model TSU Direct Gas-Fired Make-Up Air Unit The
More informationELECTRIC FLAT PANEL FIREPLACE HEATER
ELECTRIC FLAT PANEL FIREPLACE HEATER Model Numbers: WM50; WM-50-W; WS-G-01;WS-G-02 OWNER S MANUAL WARNING Read and understand this entire owner s manual, including all safety information, before plugging
More informationCooktop Chimney Ventilation Hoods
INSTALLATION GUIDE Cooktop Chimney Ventilation Hoods Contents Wolf Cooktop Chimney Ventilation Hoods.......... 3 Cooktop Chimney Hood Specifications............ 4 Cooktop Chimney Hood Installation.............
More informationHT-1300 Series. Temperature and Humidity Duct Sensor. Product Bulletin. Power Supply VDC / 24 VAC. Humidity Accuracy 2.5% RH from 10 to 95% RH
HT-1300 Series Temperature and Humidity Duct Sensor Product Bulletin Specifically designed for HVAC application, the HT-130x-UD1 sensor is a highly accurate and reliable for measuring relative air humidity
More informationCOMcheck Software Version Mechanical Compliance Certificate
COMcheck Software Version 4.0.8.1 Mechanical Compliance Certificate Project Information Energy Code: Location: Climate Zone: Project Type: 90.1 (2013) Standard Buda, Texas 2a New Construction Construction
More informationInstallation Instructions
53DS --- 900 --- --- --- 092 Duct---Free Systems Accessory Power Ventilation Kit for In --- Ceiling Cassette Fan Coil Units Size 018 --- 036 Installation Instructions NOTE: Read and become familiar with
More information180 Degree Ceiling Mounted Occupancy Sensors
Instruction Bulletin 63249-420-386A 2/202 80 Degree Ceiling Mounted Occupancy Sensors PS-CDS800 and PS-CUS800 INTRODUCTION The 80 Degree Ceiling Mount Occupancy Sensors are ideal for use in business and
More informationSurface-Mounted NS Series Network Sensors without LCD
Surface-Mounted NS Series Network Sensors without LCD Installation Instructions NS-AHP7001-0, NS-AHN700x-x, NS-ATN700x-x, NS-ATP700x-x 24-10094- 17, Rev. P Part No. 24-10094-17, Rev. P Issued March 2016
More informationStatic Pressure Alarm For Hazardous Location Fume Hoods
Static Pressure Alarm For Hazardous Location Fume Hoods Models: XPA1-0715 Class 1, Division 1, Group C, D 120V/15A/60Hz Pressure range 0.07 to 0.15 in-wg XPA1-1550 Class 1, Division 1, Group C, D 120V/15A/60Hz
More informationMacurco CM-21A Carbon Monoxide
Macurco CM-21A Carbon Monoxide Detector and Controller User Instructions for 3M Macurco CM-21A - Low voltage, dual relay Carbon Monoxide (CO) detector and controller Important: Keep these User Instructions
More informationAprilaire Dehumidifier Troubleshooting Manual Models 1830 & 1850
Aprilaire Dehumidifier Troubleshooting Manual Models 1830 & 1850 Table of Contents Troubleshooting Diagnostic Codes... 2 E1, E2... 2 E3, E4... 3 E5, E6 & E7... 7 E8... 8 E9 9 Verifying Capacity... 10 Water
More informationWD7664 / WD7663 Maxon Burner. Ellis Whisper Dryer Installation & Start UP
Title WD7664 / WD7663 Maxon Burner Ellis Whisper Dryer Procedure No. Installation & Start UP Procedure Author Chris Giordano Effective 1/23/17 Revision A Submitted By Chris Giordano Supersedes Date Revision
More informationModel gffoz Process Ozone Sensor (In-Line)
Date ECO# Rev Description Originator 9/15/97 1.0 First Publication DB 10/8/97 2.0 Miscelaneous corrections DB 10/28/97 3.0 Minor changes BM 5/1/98 3.1 Added CE compliance BM TM IN USA, INCORPORATED 87
More informationInstallation Instructions. For the 18 Built-In Dishwasher and Front Color Panels
Installation Instructions For the 18 Built-In Dishwasher and Front Color Panels Printed in USA 154232102 Before You Begin DO NOT INSTALL DISHWASHER UNTIL YOU HAVE READ ALL INSTRUCTIONS. FOR YOUR SAFETY,
More information15R HARDWARE INSTALLATION GUIDE
15R HARDWARE INSTALLATION GUIDE Table of Contents Section 1 Ratings....................................................................... 3 Section 2 Site Preparation................................................................
More informationInstallation and Maintenance Manual IM Single Duct VAV Terminals. Group: Controls Part Number: IM 1093 Date: February 2015
Installation and Maintenance Manual IM 1093-1 Single Duct VAV Terminals Group: Controls Part Number: IM 1093 Date: February 2015 Table of Contents Introduction.... 3 Revision History...3 Reference Documents...3
More informationAir Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)
FORM ASX-40020 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS SL-2000 Series Smoke Detectors, Model EXSAA and EXSAB (Ionization), EXSAG and EXSAH (Photoelectric) Air Specialties Express, 448 S. Main
More informationNetworX NX-548E Receiver Installation Instructions
NetworX NX-548E Receiver Installation Instructions Content Introduction... 1 Internal mounting... 1 External mounting... 2 Wiring... 3 DIP switch settings... 3 Power up... 3 Programming... 4 Testing and
More informationINSTALLATION MANUAL AND USER GUIDE
LIFT BRIDGE KITCHEN & BATH MODELS: DSQR110BN and DSQR110ORB INSTALLATION MANUAL AND USER GUIDE Bathroom Ventilation Fan with Light READ AND SAVE THESE INSTRUCTIONS This residential series bathroom fan
More informationRH & T Sensors & Humidistats. RH-DT Duct Mount RH & T Sensors. Description
RH & T Sensors & Humidistats RH-DT Duct Mount RH & T Sensors Description RH-DT Duct Mount RH & T Sensors The RH-DT Duct Mounted Humidity and Temperature Sensors offer the latest technology for high accuracy
More informationInstallation and Maintenance Manual IM 1102
Installation and Maintenance Manual IM 1102 Parallel Fan Powered Variable Air Volume (VAV) Terminal Box Group: Applied Air Systems Part Number: IM 1102 Date: October 2010 Model MQFVI5 Table of Contents
More informationModel 8140 and 8140NC Fresh Air Ventilator Installation and Operating Instructions
Model 8140 and 8140NC Fresh Air Ventilator Installation and Operating Instructions MODEL 8140 FRESH AIR ILATOR MODEL 8140NC FRESH AIR ILATOR FILTER COVER ILATION CONTROLLER FILTER COVER ILATION TERMINALS
More informationThermostats. Digital Non-Programmable. GEAppliances.com. Owner s Manual & Installation Instructions RAK148D2 RAK164D2
GEAppliances.com Digital Non-Programmable Thermostats Owner s Manual & Installation Instructions RAK148D2 RAK164D2 Configuration Mode... 8 9 Important Safety Information... 2 Installation Instructions...
More informationV48 Series 3-Way Water Regulating Valves For Cooling Tower Systems
Product/Technical Bulletin V48 Issue Date 0512 V48 Series 3-Way Water Regulating Valves For Cooling Tower Systems Application IMPORTANT: The V48 Series Water Regulating Valve is intended to control water
More informationSafety, Installation, and Operation Manual
Automatic Steam Humidifier Control Safety, Installation, and Operation Manual READ COMPLETE INSTALLATION INSTRUCTIONS BEFORE STARTING. WARNING This product must be installed by a qualified heating and
More informationProliphix Thermostat Installation Guide. Release 2.0
Proliphix Thermostat Installation Guide Release 2.0 July 2006 Beta Draft Confidential Technical Support When contacting Proliphix for technical assistance, please have the following information available:
More informationBOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:
4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XIN INSTALLATION AND OPERATION MANUAL BOOK 1 OVERVIEW ABOUT BOOK 1: This
More informationModel 8120 and 8126 Safety & Installation Instructions
Ventilation Controller Model 8120 and 8126 Safety & Installation Instructions FAMILIARIZE YOURSELF WITH THE INSTALLATION INSTRUCTIONS BEFORE STARTING DANGER ATTENTION INSTALLER: To prevent serious injury
More informationInstallation Instructions. Instructions de montage. Instrucciones de instalación HC
Installation Instructions For Fully Integrated NoFrost Combined Refrigerator-Freezers Instructions de montage Pour le réfrigérateurs-congélateurs combinés NoFrost encastrés, pour une utilisation intégrée
More informationModel NT20e Installation Guide
Model NT20e Installation Guide Rev 1.4 Page 2 of 14 1. Preparing for Installation CAUTION Do not remove the NT20e from the Electro-static bag until instructed from this installation guide. The NT20e is
More informationInstallation Instructions
Installation Instructions For Fully Integrated NoFrost Combined Refrigerator-Freezers HC 2060/2061 7082 485-00 Important PLEASE READ AND FOLLOW THESE INSTRUCTIONS These instructions contain Warning and
More informationA-4400 Series Refrigerated Air Dryers for Pneumatic Control Systems
Pneumatic Air Supply Manual 718 Air Dryers Section Product Bulletin A-4400 Issue Date 1213 A-4400 Series Refrigerated Air Dryers for Pneumatic Control s The A-4400 Series Refrigerated Air Dryers are designed
More informationWall Mount Electric Fireplace
Wall Mount Electric Fireplace User Guide Thank you for purchasing the Ivation Wall Mount Electric Fireplace. This User Guide is intended to provide you with guidelines to ensure that operation of this
More informationInstallation Instructions
2 or 4 pipe systems model T701DFP-1 Fan Coil Thermostat 7-Day Programmable Thermostat Remote sensor ready Self-prompting programming Auto 2-pipe changeover when used with accessory changeover sensor Dry
More informationCAUTION signals a situation where minor injury or product damage may occur if you do not follow instructions.
S I N S T A L L A T I O N I N S T R U C T I O N S I M P O R T A N T I N F O R M A T I O N IMPORTANT NOTE: This installation must be completed by a qualified installer or service agency. Before you begin
More informationMetasys Integrator Cleaver-Brooks Application
Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0900 APPLICATION NOTE Metasys Integrator Cleaver-Brooks Application lntroduction Page Application Details
More informationCD-Px Series Duct Mount CO 2 Transmitters
CD-Px0-00-0 Series Duct Mount CO 2 Transmitters Product Bulletin CD-P00-00-0, CD-PR0-00-0 Code No. LIT-216525 Issued October 2016 Johnson Controls offers a complete line of carbon dioxide (CO 2 ) transmitters
More informationSafety & Installation Instructions
Model 6303 & 6302 Zoned Comfort Control Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS 61001212A 6302-6303 Zoned Comfort Control Install.indd 1 TABLE OF CONTENTS SAFETY INSTRUCTIONS..........................................
More informationINSTALLATION MANUAL AND USER GUIDE
MODEL: BPT14-13A-BG110 Menard s SKU: 611-3051 INSTALLATION MANUAL AND USER GUIDE Bathroom Ventilation Fan READ AND SAVE THESE INSTRUCTIONS This residential series bathroom fan uses state-of-the-art technology
More informationDMFPM-2R MULTIFUNCTIONAL
Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND
More informationTP970 Series CONVERTASTAT Kits
TP970 Series CONVERTASTAT Kits APPLICATION REPLACEMENT DATA Each CONVERTASTAT Kit includes a universal wall plate adapter, cover, and a TP970 Series Thermostat to replace various manufacturer s thermostats.
More informationGas Fired Humidifier. SKG Series Combustion Field Adjustment Instructions. SKG Combustion Field Adjustment Instructions
Fired Humidifier SKG Series SKG - 180301 Standard Combustion Adjustment SKG Fired Humidifier All installation work must be carried out by suitably qualified personnel and must conform to local codes and
More informationA19, A28 Series Thermostats for Agricultural Buildings
A19, A28 Series Thermostats for Agricultural Buildings FANs 121, 125 Temperature Controls Section A Product Bulletin A19, A28 Issue Date 1088 Application These thermostats are designed for heating and
More information