MicroTech III Applied Air Handling Unit Controller Protocol Information

Size: px
Start display at page:

Download "MicroTech III Applied Air Handling Unit Controller Protocol Information"

Transcription

1 Engineering Data ED Group: Controls Part Number: ED Date: January 2009 Supersedes: ED MicroTech III Applied Air Handling Unit Controller Protocol Information Networks Networks 2009 McQuay International

2 Table of Contents Table of Contents... 2 Revision History...3 Software Revision...3 Reference Documents...3 Notice...4 Limited Warranty...4 Introduction... 5 Unit Controller Data Points...5 Protocol Definitions...5 Basic Protocol Information... 6 Setting Unit Controller Communications Parameters...6 Networks...6 MicroTech III Applied Air Handling Unit Controller Device Object...8 Network Considerations...9 Networks...11 Typical Application: Minimum Integration Set up the Unit for Network Control...16 Display Important Data Points...17 Network Off...17 Network Occupancy Scheduling...17 Alarms...18 Unit Controller Sequence of Operation...19 Comprehensive Data Point Tables Standard Objects...20 Variables...25 Detailed Data Point Information Application Mode...29 Airflow Switch...29 Airflow Switch (Warning)...30 Application Version...30 Building Static Pressure...30 Building Static Pressure Setpoint...31 Conductivity...31 Control Temperature...32 Cooling Capacity...32 Cooling Status...32 Date...33 Dew Point Setpoint...33 Dew Point Temperature...34 Dirty Filter Switch...34 Discharge Air Temperature...34 Duct High Limit Switch...35 Duct Static Pressure...35 Duct Static Pressure Setpoint...35 Economizer Capacity...36 Economizer Enable...36 Economizer Status...37 Effective Discharge Air Temperature Setpoint...38 Effective Setpoint Output...38 Emergency Off Switch...39 Emergency Override...39 Entering Fan Temperature / Leaving Coil Temp...40 Entering Water Temperature...40 Exhaust Fan Capacity...41 Exhaust Fan Capacity Input...41 Freeze Switch (Fault)...42 Freeze Switch (Problem)...42 Heating Capacity...42 Heating Status...43 High Pressure Circuit 1 Switch...43 High Pressure Circuit 2 Switch...44 High Pressure Circuit 3 Switch...44 High Pressure Circuit 4 Switch...45 High Pressure Circuit 5 Switch...45 High Pressure Circuit 6 Switch...45 HVAC Unit Type Identifier...46 Local OA Temperature...46 Local Space Temperature...47 Low Pressure Circuit 1 Switch...47 Low Pressure Circuit 2 Switch...47 Low Pressure Circuit 3 Switch...48 Low Pressure Circuit 4 Switch...48 Low Pressure Circuit 5 Switch...49 Low Pressure Circuit 6 Switch...49 Maximum Discharge Air Heating Setpoint...49 McQuay AHU Unit Status...50 Minimum Discharge Air Cooling Setpoint...51 Minimum Send Time...51 Mixed Air Temperature...52 Network Discharge Air Cooling Setpoint...52 Network Discharge Air Heating Setpoint...52 Object Request...53 Object Status...54 Occupancy...55 Occupancy Mode...56 Occupancy Scheduler Input...56 Occupied Cooling Setpoint...58 Occupied Heating Setpoint...59 Outdoor Air Damper Minimum Position Input...59 Outdoor Air Temperature...60 Outdoor Air Temperature Input...60 Outdoor Airflow...60 Primary Cool Enable...61 Primary Heat Enable...61 Receive Heartbeat...62 Reheat Capacity...63 Relative Humidity...64 Relative Humidity Input...64 Relative Humidity Setpoint...64 Remote Return/Exhaust Fan Capacity Control Flag...65 Remote Supply Fan Capacity Control Flag...65 Return Air Temperature...66 Return/Exhaust Fan Capacity...66 Exhaust Fan Status...67 Return Fan Capacity Input...67 Send Heartbeat...67 Space CO Space IAQ Input...68 Space Temperature...69 Space Temperature Input...69 Sump Pump Switch...70 Supply Fan Capacity...70 Supply Fan Capacity Input...70 Temperature Setpoint Input...71 Time...71 Unit State...71 Unit Support...72 Unoccupied Cooling Setpoint...73 Unoccupied Heating Setpoint...73 VAV Box Output...74 Water Flow Switch...75 Water Regulating Valve...75 Waterflow Switch Input...75 Alarms...77 Classes...77 Alarm Monitoring...79 Alarm Notification...80 Alarm Clearing...81 Objects...81 Clear Alarms...81 Notification Class - Faults...82 Notification Class - Problem...83 Notification Class - Warnings...83 Warning Alarm...86 Problem Alarm...87 Fault Alarm...88 Airflow Fault...89 Airflow Switch Warning...89 Conductivity Warning...90 Control Temp Fault ED

3 Dirty Filter Warning Mixed Air Temp Problem Discharge Sensor Fault Outdoor Temp Problem Duct High Limit Fault Return Temp Problem Emergency Off Fault Space Temp Problem Entering Fan Temp / Leaving Coil Temp Problem Sump Pump Fail Problem Entering Water Temp Problem Waterflow Switch Problem Freeze Fault Water Regulating Valve Problem Freeze Problem Device Management High Discharge Temp Fault DeviceCommunicationControl - Disable High Pressure Circuit 1 Problem DeviceCommunicationControl - Enable High Pressure Circuit 2 Problem ReinitializeDevice (Reset) High Pressure Circuit 3 Problem Appendix A: Protocol Implementation High Pressure Circuit 4 Problem Conformance Statement (PICS) High Pressure Circuit 5 Problem Protocol Implementation Conformance Statement High Pressure Circuit 6 Problem Product Description High Return Temp Fault Standardized Device Profile Low Discharge Temp Fault Standard Object Types Supported Low Pressure Circuit 1 Problem Data Link Layer Options Low Pressure Circuit 2 Problem Segmentation Capability Low Pressure Circuit 3 Problem Device Address Binding Low Pressure Circuit 4 Problem Networking Options Low Pressure Circuit 5 Problem Character Sets Supported Low Pressure Circuit 6 Problem Index Revision History ED15112 September 2008 Preliminary release. ED October 29, 2008 Added 2 notification class objects to. There are now a total of 3 objects (faults, problems & warnings). ED January 22, 2009 The only change was to the Networking Options section of the Protocol Information Conformance Statement (PICS). The BBMD does support registration by foreign devices. This was previously marked no. Changed the enumeration for the Water Regulating Valve object from 0=Open and 1=Closed to 0=normal and 1=alarm. Software Revision Keypad Menu Path Version Information\App Version= The software part number is encoded in the controller s memory and is available for display on the keypad/display. The part number is available via system integration tools. The software part number codification is as follows: Implied digits on all MicroTech III Air Handling software Base part number (6017 indicates standard software) Version Revision This edition documents Network Protocols for version of the standard MicroTech III Applied Air Handling Unit Controller application and all subsequent versions until otherwise indicated. However, if your software is of a later version (for example, ), some of the information in this document may not completely describe your application. You can determine the revision of the application software from the keypad/display. The path for this information from the main menu is Version Information\App Version=. Reference Documents Company Number Title Source McQuay International OM 920 MicroTech III Unit Controls for Applied Rooftop and Self- Contained Systems Operation Manual American Society of ANSI/ A Data Communication Protocol for Building Heating, Refrigerating and Air-Conditioning Engineers ASHRAE Automation and Control Networks LonMark Interoperability G LonMark Layers 1-6 Interoperability Guidelines, Version Association LonMark Interoperability Association G LonMark Application Layer Interoperability Guidelines, Version ED

4 LonMark Interoperability 8500_10 LonMark Functional Profile: Space Comfort Controller, Version Association 1.0 LonMark Interoperability 8600_10 LonMark Functional Profile: Discharge Air Controller, Version Association Echelon Corporation G FTT-10A Free Topology Transceiver Users Guide Notice 2009 McQuay International, Minneapolis MN. All rights reserved throughout the world McQuay International reserves the right to change any information contained herein without prior notice. The user is responsible for determining whether this product is appropriate for his or her application. The following are trademarks or registered trademarks of their respective companies: from American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Echelon,, LONMARK, and LonTalk from Echelon Corporation, Windows from Microsoft Corporation, and McQuay and MicroTech from McQuay International. Limited Warranty Consult your local McQuay Representative for warranty details. Refer to Form Y. To find your local McQuay Representative, go to 4 ED

5 Introduction This document contains the necessary information you need to incorporate a MicroTech III Applied Air Handling Unit Controller (i.e. Rooftop or Self-Contained Unit) from McQuay International into a building automation system (BAS). It lists all properties, variables, and corresponding MicroTech III Applied Air Handling Unit Controller data points. It also contains the Protocol Implementation Conformance Statement (PICS). and terms are not defined. Refer to the respective specifications for definitions and details. Unit Controller Data Points The MicroTech III Applied Air Handling Unit Controller contains data points or unit variables that are accessible from three user interfaces: the unit keypad, a network (/IP or MS/TP), or a network. Not all points are accessible from each interface. This manual lists all important data points and the corresponding path for each applicable interface. Refer to OM 920 (available on for keypad details. This document contains the network details necessary to incorporate the MicroTech III Applied Air Handling Unit Controller into the network. Protocol Definitions The MicroTech III Applied Air Handling Unit Controller can be configured in either an interoperable or network. The controller must have the corresponding MicroTech III communication module installed for network integration (see Reference Document section for corresponding part numbers). There are three MicroTech III communication modules: /IP, MS/TP (Master/Slave Token Passing), and. There are two modules: one in accordance with the LonMark Space Comfort Controller (General) functional profile and one in accordance with the Discharge Air Controller functional profile. Protocol is a standard communication protocol for Building Automation and Control Networks developed by the American National Standards Institute (ANSI) and American Society of Heating, Refrigeration and Air-conditioning Engineers (ASHRAE) specified in ANSI/ASHRAE standard It addresses all aspects of the various systems that are applied to building control systems. provides the communication infrastructure needed to integrate products manufactured by different vendors and to integrate building services that are now independent. Networks A control network specification for information exchange built upon the use of LonTalk for transmitting data developed by the Echelon Corporation. LonTalk Protocol A protocol developed and owned by the Echelon Corporation. It describes how information should be transmitted between devices on a control network. LonMark Certification LonMark certification is an official acknowledgement by the LonMark Interoperability Association that a product communicates using the LonTalk protocol and transmits and receives data per a standard LonMark functional profile. The MicroTech III communication modules are LonMark 3.4 certified in accordance with the Space Comfort Controller (SCC) and Discharge Air Controller (DAC) functional profiles. ED

6 Basic Protocol Information Setting Unit Controller Communications Parameters There are 12 communication parameters involved in setting up the unit controller for proper communication with the four communication module options ( IP, MS/TP, SCC or DAC). These parameters are set differently depending on which communication module is ordered and shipped with the unit. The table below lists the three possible sets of default parameter settings. Not all the parameters apply to all the module options. The bold parameters can be changed using the keypad display located on the unit controller. Communication Setup Parameter Settings Parameter Name IP MS/TP LON (DAC or SCC) DHCP On N/A N/A IP Address DHCP Enabled N/A N/A IP Subnet Mask DHCP Enabled N/A N/A Given IP Address N/A N/A Given IP Subnet Mask N/A N/A Given Gateway Address N/A N/A UDP Port Number N/A N/A MSTP MAC Address 2 N/A 18 N/A MSTP Baud Rate N/A N/A Device Instance Number variable variable N/A Max APDU Length N/A Device Object Name POL908_FF2BEE 3 POL904_AD45EC28 4 N/A Receive Heartbeat 0Sec 0Sec 0Sec Max Master N/A 127 N/A Max Info Frames N/A 1 N/A Term Resistor N/A No 5 N/A Notes: 1. These addresses are used if DHCP is set to Off. For changes to these parameters to take effect, use the keypad display and set Apply IP Chg on the IP Setup menu to Yes and cycle power. 2. The MSTP MAC Address is set via the keypad/display. You must cycle power after changing it for the changes to take effect. 3. The last 6 digits are the last 6 digits of the MAC address. The MAC address is printed a sticker affixed to the communication module. 4. The last 8 digits are computed from the production number and date code. 5. Term Resistor is only changeable via the keypad/display. This item must be set to Yes for the first and last unit on the MS/TP network. On all other units, this variable should be set to No (default). Networks Compatibility The MicroTech III Applied Air Handling Unit Controller conforms to the Standard (ANSI/ASHRAE ) as stated in the Protocol Implementation and Conformance Statement (PICS). See Protocol Implementation Conformance Statement on page 89. Objects MicroTech III Applied Air Handling Unit Controllers incorporate standard object types (i.e., object types defined in the Standard) that conform to the Standard. Each object has properties that control unit variables or data points. Some object types occur more than once in the MicroTech III Applied Air Handling Unit Controller; each occurrence or instance has different properties and controls different unit variables or data points. Each instance is designated with a unique instance index. Some properties can be adjusted (read/write properties, e.g., setpoints) from the network and others can only be interrogated (read-only properties, e.g., status information). Each data point accessible from a network is described with a table that gives the, Identifier, Full Reference or path, and the Name enumeration of the property. 6 ED

7 Example of Data Point Keypad Menu Path Standard Menus\Flow Summary\Ret/Exh Fan= Binary Output 4 1 Present_Value 85 <Device Name>.ExhFanState.Present_Value 0 = Off 1 = On s are each designated with an Object type as defined in the specification. The first column of the data point definition gives the object type. This object happens to be Return/Exhaust Fan Status (See page 67.) The object identifier is a property of the object that you can read from the object. The name of the property is Object_Identifier and the property identifier is 75. Each object in the Air Handling controller has a unique identifier. object identifiers are two-part numbers of data type. The first part identifies the object type (the first 10 bits of the 32-bit Object Identifier [See ANSI/ASHRAE A Data Communication Protocol for Building Automation and Control Networks]). The first column of the data point definition gives the object type. The second part identifies the instances of that particular object type (the last 22 bits of the 32-bit ). The object identifier is shown in the data points listing as two numbers. The first number is shown in the Type ID column and designates the Object type enumeration. The second number is shown in the Instance column and designates the instance of that particular object type. The object identifier is a property of the object that you can read from the object code. The name of the property is Object_Identifier and the property identifier is 75. The ASHRAE specification reserves the first 128 numbers for ASHRAE defined objects. Manufacturers may define additional object types and assign a number above 127 as long as they conform to the requirements of the ASHRAE specification. Each object also has a name. Object names are character strings. The object name is a property of the object that you can read from the object. The name of the property is Object_Name and the property identifier is 77. Objects are sometimes referred to as an object type and instance number as they are in the specification. The example object above would be: Binary Output, Instance 1. Identifier Each object has a number of properties or attributes. Each property has a unique identifier of Identifier data type. identifiers are an enumerated set; a number identifies each member. The Identifier enumeration number is shown in the ID column. In the example above the property identifier is 85. Name Each property also has a unique name. names are character strings and shown in the Name column. In the example above the property name is Present Value. The full reference is the path of the property within the network where the MicroTech III Applied Air Handling Unit Controller resides. It is a character string equivalent to the object identifier and the property identifier. In the example above the full reference is <Device Name>.ExhFanState.Present_Value. Enumerated Values Some properties are standard data types and some are enumerated sets. If the property value is an enumerated set, all enumerated values and corresponding meaning are given in the column of the data point listing. ED

8 MicroTech III Applied Air Handling Unit Controller Device Object Each compatible device must have one and only one Device Object. Device The MicroTech III Applied Air Handling Unit Controller Device uniquely specifies the unit within the network. The device object type for all devices is fixed by ASHRAE at 8. Therefore the device object instance number must be unique. The initial Device Object identifier is set at manufacturing. The device object identifier can be read from the unit controller. The name of the property is Object_Identifier and the property identifier is 75. The initial device object instance number is This number must be unique on the entire network. The object instance number can be changed via the keypad display. You must cycle power for the change to take effect.! CAUTION If another device in the network already has this object identifier (instance number), you must change the instance number of one device object, so that all devices in the network have a unique device identifier. Device Object Name The Device Object Name uniquely specifies a device in the network. It must be unique in the network. The device name for the MicroTech III Applied Air Handling Unit Controller device is to be determined. The device name is the prefix of all object names in the MicroTech III Applied Air Handling Unit Controller. All objects include the device name and a period. preceding the object name. The Device Object name is also available to the network in the device. The property name is Object_Name and property identifier is 77. For a IP card, the default Object Name is POL908_###### where ###### is the last 6 digits of the MAC address. For a MS/TP card, the default Object Name is POL904_######## where ######## is computed from the production number and date code. Device Object Properties The device object contains many other informative properties as shown in Table 1. Table 1. MicroTech III Air Handling Unit Controller Device Object Properties Identifier Default Value Data Type 75 Device, variable ObjectIdentifier Object Name 77 1 POL908_FF2BEE Character String Object Type 79 8 ObjectType System Status 112 DeviceStatus Vendor Name 121 McQuay Character String Vendor Identifier Unsigned 16 Model Name 70 AHU Character String Firmware Version 44 variable Character String Application Software Revision 12 variable Character String Location 58 Character String Description 28 MTech III AHU Character String Protocol Version 98 1 Unsigned Protocol Revision Unsigned Protocol Services Supported 97 ServicesSupported 2 Protocol Object Types Supported 96 AI, AO, AV, BI, BO, BV, Cal, ObjectTypesSupported Device, MSI, MSO, NC, Sch, MSV Object List 76 Sequence of ObjectIdentifer Max APDU Length Accepted (IP) / 480 (MS/TP) Unsigned 16 8 ED

9 Identifier Default Value Data Type Segmentation Supported 107 None Segmentation Max Segments Accepted Unsigned Local Time3 57 variable Time Local Date 3 56 variable Date UTC Offset (Range: ) Integer Daylight Savings Status 24 variable Boolean APDU Segment Timeout Unsigned APDU Timeout Unsigned Number of APDU Retries 73 3 Unsigned Device Address Binding 30 Sequence of AddressBinding Database Revision Unsigned Active COV Subscriptions 152 List of COVSubsriptions 1. For IP, the last 6 digits are the last 6 digits of the MAC address. The MAC address is printed a sticker affixed to the communication module. For MS/TP, the last 8 digit are computed from the production number printed on the bar code label affixed to the side of the module. 2. While the MicroTech III Applied Air Handling Unit Controller supports the entire set of object types, not all object types are used. See the Object List for details. 3. The communication module and the MicroTech III Applied Air Handling Unit Controller both have their own time clocks. The date and time read via could differ from the date and time in the unit controller the date or time is changed via the keypad display. The two time clocks resynchronize approximately every minutes and after every power cycle of the unit controller or communication module. Network Considerations Access to Properties Object properties are accessible from the network by specifying the device object identifier, object identifier, and the property identifier. To access a property, you must specify the object identifier including the device object identifier or the object name including the device object name and the property identifier. /IP Addressing The /Internet Protocol (/IP) address of the MicroTech III Applied Air Handling Unit Controller in a /IP network consists of the four-octet Internet Protocol address followed by the two-octet UDP (User Datagram Protocol) port number. The /IP address is a six-octet value analogous to a MAC address. The IP address portion of the /IP address must be unique in the /IP network segment. The default UDP port number in the MicroTech III Applied Air Handling Unit Controller is (BAC0 in hexadecimal). The device object of the MicroTech III Applied Air Handling Unit Controller contains a Given Internet Protocol Subnet Mask (Default is ) and a default Given IP address of The controller does support DHCP (Dynamic Host Configuration Protocol) IP addressing which is enabled by default. The keypad/display can be used to configure the /IP addressing. The keypad will display the current IP address only when the network is connected. The MicroTech III Applied Air Handling Unit Controller can be incorporated into a /IP network dedicated to devices only or an Ethernet network shared with devices and other devices. Shared Ethernet Networks Integrating the MicroTech III Applied Air Handling Unit Controller into a shared Ethernet LAN requires close cooperation with the network administrator of the shared Ethernet network. First, verify whether DHCP should or should not be enabled. If not, obtain the IP Subnet Mask of the shared network from the network administrator. Then, obtain static IP Addresses for all MicroTech III Applied Air Handling Unit Controllers you are integrating into the shared network. Finally obtain the address of an IP Router to use for sending IP messages to and from the IP subnets. Once you have these, refer to Setting Unit Controller Communication Parameters in the Basic Protocol Information section found previously in this document. ED

10 Configuring the Unit Controller The MicroTech III Applied Air Handling Unit Controller is designed, programmed, and configured to be a MicroTech III Rooftop or Self-Contained Unit Controller. The unit is ready to operate with the default values of the various parameters set at the factory. Default values may be changed with the unit s keypad or via the network. See the MicroTech III Applied Air Handling Unit Controller Operation Manual (OM 920). MS/TP Network Addressing The MS/TP device address (Media Access Control [MAC] address) of the MicroTech III Air Handling Unit Controller in a Master Slave/Token Passing (MS/TP) Local Area Network (LAN) is set using the keypad/display. Navigate to the Advanced Menus\MSTP Setup menu to change this value. You must cycle power (turn the unit controller off and then on again) in order for the new address to take effect. The BUS LED is green when the communication module is communicating with the network and is red when it is not communicating with the network. The default data transmission rate is set to 38,400 bps (baud). This rate can be changed to 9,600, 19,200 or 76,800 with the keypad/display. Refer to Setting Unit Controller Communications Parameters in the Basic Protocol Information section of this document. 10 ED

11 Networks technology, developed by Echelon Corporation, is the basis for LonMark interoperable systems. This technology is independent of the communications media. The LonMark Interoperable Association has developed standards for interoperable technology systems. In particular they have published standards for HVAC equipment including the Discharge Air Controller functional profile and the Space Comfort Controller functional profile. These profiles specify a number of mandatory and optional standard network variables and standard configuration parameters. This manual defines these variables and parameters available in the MicroTech III Applied Air Handling Unit Controller. Compatibility The MicroTech III Applied Air Handling Unit Controllers with the communications modules operate in accordance with the Discharge Air Controller (DAC) functional profile and the Space Comfort Controller (SCC) functional profile of the LonMark Interoperability standard. Variables MicroTech III Applied Air Handling Unit Controllers incorporate network variables to access unit data points. The unit controller uses Standard Network Variable Types (SNVT) from each profile. Some data points can be adjusted (input network variables, nvi) (read/write attributes, e.g., setpoints) from the network and others can only be interrogated (output network variables, nvo) (read only attributes, e.g., status information). Configuration variables (nci) are included with the read/write attributes. Each data point accessible from a network is described with a table that gives the Name, Profile, SNVT Type, and SNVT Index. If the variable is a configuration variable the table also includes the SCPT Reference and the SCPT Index. Example of Data Point LonWorks LonWorks Name Profile SNVT Type SNVT Index nvobldgstatpress DAC, SCC SNVT_press_p 113 Name Each network variable has a name that you use to access the data point. This is the name of the variable from the profile. In the example above the name network variable is nvobldgstatpress. Profile The profile column designates the MicroTech III Communication Module that incorporates this network variable. The variable itself may not be a standard component of that particular profile, but the communications module does implement and it is available to the network. SNVT Type This column gives the name of the standard network variable type from the master list. SNVT Index This column gives the number of the standard network variable type from the master list. SCPT Reference This column gives the name of the Standard Configuration Parameter Type (SCPT) from the master list. SCPT Index This column gives the number of the Standard Configuration Parameter Type (SCPT) from the master list. Network Considerations Network Topology Each MicroTech III Communication Module is equipped with an FTT-10A transceiver for network communications. This transceiver allows for (1) free topology network wiring schemes using twisted pair (unshielded) cable and (2) polarity insensitive connections at each node. These features greatly simplify installation and reduce network commissioning problems. Additional nodes may be added with little regard to existing cable routing. ED

12 Free Topology Networks A free topology network means that devices (nodes) can be connected to the network in a variety of geometric configurations. For example, devices can be daisy-chained from one device to the next, connected with stub cables branching off from a main cable, connected using a tree or star topology, or any of these configurations can be mixed on the same network as shown in Figure 1. Free topology segments require termination for proper transmission performance. Only one termination is required. It may be placed anywhere along the segment. Refer to Echelon FTT-10A Transceiver User s Guide for further details (see Reference Documents section). Free topology networks may take on the following topologies: Bus Ring Star Mixed - Any combination of Bus, Ring, and Star Note: Limitations to wire lengths apply and must be observed. Figure 1. Singly Terminated Free Topology Ring Topology Singly Terminated Bus Topology Stub Star Topology Termination Termination } Termination Mixed Topology Termination A network segment is any part of the free topology network in which each conductor is electrically continuous. Each of the four diagrams is a illustration of a network segment. Some applications may require two or more segments; see Free Topology Restrictions. If necessary, segments can be joined with FTT-10A-to-FTT-10A physical layer repeaters. See Figure 2. Refer to Echelon FTT-10A Transceiver User s Guide for further details. Figure 2. Combining Network Segments with a Repeater Termination FTT-10A FTT-10A Termination 12 ED

13 Free Topology Restrictions Although free topology wiring is very flexible, there are restrictions. A summary follows, refer to the Echelon FTT-10A User s Guide for details. 1. The maximum number of nodes per segment is The maximum total bus length depends on the wire size: Wire Size Maximum Node-to-Node Length Maximum Cable Length 24 AWG 820 ft (250 m) 1476 ft (450 m) 22 AWG 1312 ft (400 m) 1640 ft (500 m) 16 AWG 1640 ft (500 m) 1640 ft (500 m) The longest cable path between any possible pair of nodes on a segment must not exceed the maximum node-to-node distance. If two or more paths exist between a pair of nodes (e.g., a loop topology), the longest path should be considered. Note that in a bus topology, the longest node-to-node distance is equal to the total cable length. a. The total length of all cable in a segment must not exceed the maximum total cable length. 3. One termination is required in each segment. It may be located anywhere along the segment. Doubly Terminated Networks You can extend the maximum total cable length without using a repeater by using doubly-terminated network topology. See Figure 3. The trade-offs are (1) this network topology must be rigorously followed during the installation and subsequent retrofits and (2) two terminations must be installed at the ends of the bus for proper transmission performance. Refer to Echelon FTT-10A Transceiver User s Guide. Note: Limitations to wire lengths apply and must be observed. Figure 3. Doubly Terminated Network Topology Termination Termination Doubly Terminated Topology Restrictions The restrictions on doubly-terminated bus topology are as follows: 1. The maximum number of nodes per segment is The maximum total bus length depends on the wire size: Wire Size 24 AWG 2952 ft (900 m) 22 AWG 4590 ft (1400 m) 16 AWG 8855 ft (2700 m) Maximum Cable Length 3. The maximum stub length is 9.8 ft (3 m). The length of the MicroTech III Air Handling cable harness stub is 7.2 ft (2.19 m). A stub is a piece of cable that is wired between the node and the bus. See Figure 1. Note that if the bus is wired directly to the node, there is no stub, and thus the stub length is zero. If you are wiring to a field terminal strip on a unit, be sure to account for any factory wiring between the terminal strip and the controller. This wiring is considered part of the stub. 4. Two terminations are required in each segment. One must be located at each end of the bus. Network Cable Termination network segments require termination for proper data transmission performance. The type and number of terminations depend on network topology. Refer to Echelon FTT-10A Transceiver User s Guide. LonWorks Network Addressing Every Neuron Chip has a unique 48-bit Neuron ID or physical address. This address is generally used only at initial installation or for diagnostic purposes. For normal network operation, a device address is used. ED

14 Device addresses are defined at the time of network configuration. All device addresses have three parts. The first part is the Domain ID, designating the domain. Devices must be in the same domain in order to communicate with each other. The second part is the Subnet ID that specifies a collection of up to 127 devices that are on a single channel or a set of channels connected by repeaters. There may be up to 255 subnets in a domain. The third part is the Node ID that identifies an individual device within the subnet. A group is a logical collection of devices within a domain. Groups are assembled with regard for their physical location in the domain. There may be up to 256 groups in domain. A group address is the address that identifies all devices of the group. There may be any number of devices in a group when unacknowledged messaging is used. Groups are limited to 64 devices if acknowledged messaging is used. A broadcast address identifies all devices within a subnet or domain. network variables for both the Discharge Air Controller and the Space Comfort Controller are defined below. Variables are used in both the Space Comfort Controller and Discharge Air Controller profiles unless marked otherwise. Commissioning the Network Pressing the service pin, switch on the MicroTech III Communication Module, generates a service pin message, which contains the Neuron ID and the program code identification of the node. A service pin message is a network message that is generated by a node and broadcast on the network. It can be used to commission the network. A network configuration tool maps device Neuron IDs to the domain/subnet/node logical addressing scheme when it creates the network image, the logical network addresses and connection information for all devices (nodes) on the network. External Interface File (XIF) LonMark guidelines specify exact documentation rules so that proprietary configuration tools are not required to commission and configure devices. The MicroTech III Communication Module is selfdocumenting so that any network management tool can obtain all the information needed over the network to connect it into the system and to configure and manage it. An External Interface File (a specially formatted PC text file with an extension.xif) is also available so that any network tool can design and configure it prior to installation. XIF files are available on Configuring the Unit Controller 1. The MicroTech III Applied Air Handling Unit Controller is designed, programmed, and configured to be a rooftop or self-contained unit controller in accordance with either the LONMARK Discharge Air Controller (DAC) or LonMark Space Comfort Controller (SCC) functional profile. The unit is ready to operate with the default values of the various parameters set at the factory. Default values may be changed with the unit s keypad or via the network. See the MicroTech III Applied Air Handling Unit Controller Operation Manual (OM 920). Data Integrity The integrity of some data depends on a valid network connection to maintain current values. The following data points require a valid network connection if bound. If data points listed in Table 2 do not change after a given time, the controller reverts to local control. In the case of the LonWorks module, the variables will revert to their default values. The variables listed implement priority array. However, they can only be written at priority 8. Table 2. Receive HeartBeat Variables Data Point Variable LonWorks Variable Occupancy Scheduler Input CurrentState, NextState & TimeToNextState nvioccschedule Application Mode ApplicCmd nviappliccmd Supply Fan Capacity Input SupFanCapNetIn nvisupfancap 14 ED

15 Data Point Variable LonWorks Variable Outdoor Air Temperature OutdoorTempInput nvioutdoortemp Space Temperature SpaceTempInput nvispacetemp Primary Cool Enable nviprmclgenv & nviprmclgens nvipricoolenable Primary Heat Enable nviprmhtgenv & nviprmhtgens nvipriheatenable Economizer Enable nvieconenav & nvieconenas nvieconenable Exhaust Fan Capacity Input ExhFanCapNetIn nviexhfancap Return Fan Capacity Input RetFanCapNetIn nviretfancap Water Flow Switch Input WaterflowSwitch nvicwflow Space Indoor Air Quality (IAQ) Input SpaceIAQNetIn nvispaceiaq Relative Humidity Input SpaceRHNetIn nvispacerh ED

16 Typical Application: Minimum Integration When you have integrated the unit into your network, you can monitor and control unit operation from your workstation. At a minimum, you can: Display and monitor a minimum of important data points on your workstation display Turn the unit on or off from your workstation Set the schedule from your workstation and Operate the unit safely This section gives you the basic information and outlines a procedure to set up the unit for network control. Set up the Unit for Network Control To control the MicroTech III Applied Air Handling Unit Controller over the network, follow the setup steps below. 2. Set the S7 switch on the control panel to AUTO. Figure 4 shows the general location of a typical installation. Some models use variations of this switch panel, but all are in the same general location. Figure 4. Location of Switch S7 S7 Switch 3. On the unit keypad, set the Control Mode function to AUTO. The keypad password (2526) is required to edit this function. For a detailed description of how to use the keypad, refer to MicroTech III Applied Air Handling Unit Controller Operation Manual (OM 920). 16 ED

17 Display Important Data Points Typical workstation displays of MicroTech III Applied Air Handling Unit Controller attributes include the following significant data points (page number of detailed description in parenthesis). Each data point is identified with a number that also identifies it in the Comprehensive Data Point Tables. These data points are also shaded in the comprehensive tables so that you can distinguish them from the rest of the data points in the table. References in the text of this section also identify these data points with a number and shading. Table 3. Significant Data Points No Configuration No Temperatures/Pressures No Setpoints No Clear Alarms 1 Unit State (71) 5 Discharge Air Temperature (34) 2 Application Mode (29) 6 Return Air Temperature (66) 3 Occupancy (55) 7 Outdoor Air Temperature (60) 4 Occupancy Mode (56) 9 Duct Static Pressure Setpoint (35) 10 Unoccupied Cooling Setpoint (72) 11 Occupied Cooling Setpoint (58) 8 Duct Static Pressure (35) 12 Occupied Heating Setpoint (59) 13 Unoccupied Heating Setpoint (73) 14 Clear Alarms (81) You can display any number of additional data points based on job requirements or individual preference. See Variables on page 25 for lists of all Variables available to a network. See Standard Objects on page 20 for a list of all Standard Objects available to a network. For a more detailed description of all available data points, see the Detailed Data Point Information section on page 29. Network Off The unit can be turned off over the network by writing to the (2) Application Mode (see page 29). Writing AUTO to Application Mode allows the unit controller to determine its mode of operation based on input conditions. Writing OFF to Application Mode shuts down the unit, etc. The Emergency Override Mode Flag (see page 39) can also be used to shut down the unit from the network. Network Occupancy Scheduling Using the keypad, set the Occupancy Mode to Auto. Schedule unit operation over the network with the Occ Scheduler input. Switching from OCC, UNOCC, BYPASS (TntOvrd), or AUTO commands the unit into the mode you select. ED

18 Alarms Alarms in a MicroTech III Applied Air Handling Unit Controller are divided into three classes: Faults, Problems, and Warnings. Fault Alarms have the highest priority. Problem Alarms have medium priority. Warning Alarms have the lowest priority. Notification MicroTech III Applied Air Handling Unit Controllers may have their alarms monitored by one of four methods: 1) individually by Binary Values, 2) Alarm value using one Analog Value, 3) Alarm class, or 4) Notification Classes. 1. To monitor alarms individually, read the Present_Value of the desired Binary Value object. Each alarm has its own Binary Value object. If the Present_Value is Inactive (0), the alarm is not active. If the Present_Value is Active (1), the alarm is active. 2. To monitor alarms by alarm value, read the Present_Value property of the Alarm Value Analog Value object. The Present_Value displays a value that corresponds to the highest priority alarm that is active. It is possible to have multiple active alarms, but only the highest priority is displayed. For example, if there is a simultaneous Dirty Filter Warning (value of 24) and a Freeze Fault (value of 252), then the Freeze Fault value of 252 will display in the Present_Value because it is the higher priority alarm of the two. Once the Freeze Fault condition is corrected and the fault is cleared, the next priority active alarm value (in this example, value of 24 for Dirty Filter alarm) is displayed. The values for all alarms are described in the Alarms section tables. If the Present_Value displays a zero, there are no active alarms. 3. To monitor alarms by alarm class, read the Present_Value of the appropriate Analog Value object (Warnings, Problems and Faults). The Present_Value displays a value that corresponds to the highest priority alarm that is active for that particular alarm class. It is possible to have multiple active alarms, but only the highest priority is displayed. 4. To monitor alarms using the Notification Class objects, see the Alarm Notification section. MicroTech III Applied Air Handling Unit Controllers may have their alarms monitored by one of two methods: 1) by using the In_alarm attribute of nvounitstatus, or 2) by alarm class. 1. Alarms within MicroTech III Applied Air Handling Unit Controllers can be monitored individually by using the In Alarm attribute of the Unit Status Network Variable Output (i.e. nvounitstatus_in_alarm). This attribute displays a value that corresponds to the highest priority alarm that is active. It is possible to have multiple active alarms, but only the highest priority is displayed in this attribute. For example, if there is a simultaneous Dirty Filter Warning (value of 24) and a Freeze Fault (value of 252), then the Freeze Fault value of 252 will display in nvounitstatus_in_alarm because it is the higher priority alarm of the two. Once the Freeze Fault condition is corrected and the fault is cleared, the next priority active alarm value (in this example, value of 24 for Dirty Filter alarm) is displayed. The values for all alarms are described in the Alarms section tables. If the attribute nvounitstatus_in_alarm displays a zero, there are no active alarms. When the nvounitstatus_in_alarm attribute reads a value in the range of 1 to 99, a Warning Alarm is active. When the attribute reads a value in the range of 100 to 199, a Problem Alarm is active. When the attribute reads a value in the range of 200 to 255, a Fault Alarm is active. 2. To monitor alarms by alarm class, read nvowarnalarm, nvoprobalarm and nvofaultalarm. The value corresponds to the highest priority alarm that is active. It is possible to have multiple active alarms, but only the highest priority is displayed. Clearing MicroTech III Applied Air Handling Unit Controllers have one Multi-State Value objects that can be used to clear alarms; ClearAlarms (See page 81). All alarms of a particular class may be cleared by writing the appropriate value to the Present Value property of ClearAlarms (2=ClearAllFaults, 3=ClearAllProblems, 4=ClearAllWarnings). All alarms of all three 18 ED

19 classes can be cleared by writing a 5 (ClearAllAlarms) to Present_Value. Once the alarms are cleared, the Present_Value of this object goes back to None (1). MicroTech III Applied Air Handling Unit Controllers have one variable that can be used to clear alarms; nviclearalarms (See page 81). All alarms of a particular class may be cleared by writing the appropriate value to nviclearalarms (1=ClearAllFaults, 2=ClearAllProblems, 3=ClearAllWarnings). All alarms of all three classes can be cleared by writing a 4 (ClearAllAlarms) to nviclearalarms. Once the alarms are cleared, this variable goes back to None (0). Unit Controller Sequence of Operation The sequence of operation for a MicroTech III Applied Air Handling Unit Controller depends on the control type. Refer to the MicroTech III Applied Air Handling Unit Controller Operation Manual (OM 920) for sequence of operation details, including keypad operation. ED

20 Comprehensive Data Point Tables These comprehensive data point tables contain the significant parameters of specific data points. The shaded data points with numbers are the data points listed in Table 3. Standard Objects Network Control (Keypad attributes available as Standard Objects for network control of the unit) Page Read, Write, Command 1 Object Type Instance SCC DAC Description System Unit State 71 R MSV 15 1=Off, 2=Start, 3=Recirc, 4=FanOnly, 5=MinDAT, 6=Htg, 7=Econo, 8=Clg *(1) McQuay AHU Unit Status 50 R MSV 1 Mode: 1=Enabled, 2=OffMan, 3=OffManCtrl, 4=OffNet, 5=OffAlm, 6=OffFanRetry Cooling Status 32 R MSV 2 1=Enabled, 2=None, 3=OffAmb, 4=OffAlarm, 5=OffNet, 6=OffMan Heating Status 43 R MSV 4 1=Enabled, 2=None, 3=OffAmb, 4=OffAlarm (Not Used), 5=OffNet, 6=OffMan Economizer Status 37 R MSV 3 1=Enabled, 2=None, 3=OffAmb, 4=OffAlarm (Not Used), 5=OffNet, 6=OffMan Cooling Capacity 32 R AV 1 cooling capacity (%) Heating Capacity 42 R AV 2 heating capacity (%) Supply Fan Capacity 70 R AI 8 Current supply fan capacity (%) Return/Exhaust Fan Capacity 66 R AI 10 Current return or exhaust fan capacity (%) Economizer Capacity 36 R AV 15 Feedback value (%) Emergency Override 39 W MSV 10 1=Normal, 2=Off (Shuts unit off via a network signal, puts Unit Status = OffNet) *(2) Application Mode 29 C MSV 5 1=Off, 2=HeatOnly, 3=CoolOnly, 4=FanOnly, 5=Auto Occupancy *(3) Occupancy 55 R MSV 6 1=Occ, 2=Unocc, 3=TntOvrd *(4) Occupancy Mode 56 W MSV 7 1=Occ, 2=Unocc, 3=TntOvrd, 4=Standby (not used) 5=Auto. Temperature Control Temperature 32 R AI 14 Current reading of sensor *(5) Discharge Air Temperature 34 R AI 1 Current reading of sensor *(6) Return Air Temperature 66 R AI 2 Current reading of sensor Space Temperature 69 R AI 3 Current reading of sensor *(7) Outdoor Air Temperature 60 R AI 4 Current reading of sensor Entering Fan / Leaving Coil Temp 40 R AI 7 Current reading of sensor Entering Water Temperature 40 R AI 6 Current reading of sensor Mixed Air Temperature 52 R AI 5 Current reading of sensor Flow Summary Exhaust Fan Status 67 R BV 1 0=Off, 1=On VAV Box Output 74 R MSV 14 N/A 1=Heat (Off), 2=Cool (On) SAF Spd Control *(8) Duct Static Pressure 35 R AV 6 N/A Current reading of sensor. If unit has two sensors the lower of the two is displayed *(9) Duct Static Pressure Setpoint 35 W AV 7 N/A Default = 1.00 WC Remote Supply Fan Capacity 65 W MSV 11 1=DSP, 2=Speed Control Flag Supply Fan Capacity Input 70 C AV 21 N/A Default = (Null) RF/EF Spd Control Building Static Pressure 30 R AI 9 Current reading of sensor value or network input Building Static Pressure Setpoint 31 W AV 8 Default = WC Remote Return/Exhaust Fan 65 W MSV 12 1=None, 2=Tracking, 3=BldgP, 4=Speed 20 ED

21 Network Control (Keypad attributes available as Standard Objects for network control of the unit) Page Read, Write, Command 1 Object Type Instance SCC DAC Description Capacity Control Flag Return Fan Capacity Input 67 C AV 22 Default = (Null) Exhaust Fan Capacity Input 41 C AV 23 Default = (Null) Cooling *(11) Occupied Cooling Setpoint 58 W AV 9 Default = 72 F / C *(10) Unoccupied Cooling Setpoint 73 W AV 10 Default = 85 F / C Network Discharge Air Cooling 52 W AV 13 N/A Default = 55 F / C Setpoint Min Discharge Air Cooling Setpoint 51 W AV 14 N/A Default = 55 F / C Evap Condensing Conductivity 31 R AI 12 This variable provides the conductivity of the water in the sump of an evaporative cooled condenser. Min OA Damper Space CO 2 68 R AI 13 This variable provides the concentration of CO 2 in the space (PPM). Outdoor Airflow 60 R AV 42 Heating *(12) Occupied Heating Setpoint 59 W AV 11 Default = 68 F / 20 C *(13) Unoccupied Heating Setpoint 73 W AV 12 Default = 55 F / C Network Discharge Air Heating 52 W AV 17 N/A Default = 100 F / C Setpoint Max Discharge Air Heating Setpoint 49 W AV 18 N/A Default = 120 F / C Dehumidification Relative Humidity 64 R AI 11 N/A Displays value of optional relative humidity sensor Dew Point Temperature 34 R AV 20 N/A Indicates current calculated dew point Relative Humidity Setpoint 64 W AV 40 Dew Point Setpoint 33 W AV 41 Reheat Capacity 63 R AV % Setup: IP or MS/TP Receive Heartbeat 62 W AV 43 Default is 0 seconds. This disables this feature. Unit Support 72 W MSV 16 1=No (Metric), 2=Yes (Default) Network Variables Outdoor Air Temperature Input 60 C AV 29 Network input of Outdoor Air Temp ( 10 C to 50 C) default = (Null) Space Temperature Input 69 C AV 28 Network input of Space Temp ( 10 C to 50 C) default = (Null) Occupancy Scheduler Input Current State Next State Time To Next State 56 C MSV 8 1=Occ, 2=Unocc, 3=TntOvrd (not used), 4=Standby (not used), 5=Auto (default). MSV 9 1=Occ, 2=Unocc, 3=TntOvrd (not used), 4=Standby (not used), 5=Auto (default). AV 3 Default = (Null) Primary Cool Enable 61 C AV 34 & 35 Allows the network to partially or completely disable cooling. Primary Heat Enable 61 C AV 36 & 37 Allows the network to partially or completely disable heating. Economizer Enable 36 C AV 32 & 33 Allows the network to partially or completely disable economizer functions. Waterflow Switch Input 75 C AV 38 Allows the network to set the waterflow status. 0=No Flow, 1=Flow. Space IAQ Input 68 C AV 31 This input may be set by the network and is used for minimum OA damper control ( PPM). Default=32767 (Null) Relative Humidity Input 64 C AV 19 N/A Network relative humidity value. Default= (Null) Outdoor Air Damper Min Position 59 W AV 16 Current OA damper min position setpoint (%) Input Eff Discharge Air Temp Setpoint 38 R AV 39 N/A This parameter will equal the Effective Heating Discharge Temperature Setpoint if the unit is in the heating state. ED

MicroTech III Rooftop and Self Contained Unit Controller Protocol Information

MicroTech III Rooftop and Self Contained Unit Controller Protocol Information Engineering Data ED 15112-8 Group: Controls Part Number: ED 15112 Date: February 2011 Supersedes: ED 15112-7 MicroTech III Rooftop and Self Contained Unit Controller Protocol Information Networks Networks

More information

Daikin Loop Water Manager Protocol Information

Daikin Loop Water Manager Protocol Information Engineering Data ED 19015 Group: Controls Part Number: ED 19015 Date: August 2012 Supersedes: New Daikin Loop Water Manager Protocol Information BACnet Networks 2012 Daikin Table of Contents Table of Contents...

More information

McQuay Microtech III BACnet MS/TP Application 4181 Point Map

McQuay Microtech III BACnet MS/TP Application 4181 Point Map Point Map June 2009 Systems Integration McQuay Microtech III BACnet MS/TP Application 4181 Point Map APOGEE Open Processor with McQuay Microtech III BACnet MS/TP Driver: Microtech III Applied Rooftop Unit

More information

MicroTech III Unit Controller for Applied Rooftop and Self-Contained Systems

MicroTech III Unit Controller for Applied Rooftop and Self-Contained Systems Operation and Maintenance Manual OM 920-1 MicroTech III Unit Controller for Applied Rooftop and Self-Contained Systems Group: Applied Systems Part Number: OM 920-1 Date: October 2009 RAH, RCS, RDS, RDT,

More information

BACnet Integration Manual ITG-VH72xx-BAC-E00 ( _R0 Issue Date: October 21, 2008)

BACnet Integration Manual ITG-VH72xx-BAC-E00 ( _R0 Issue Date: October 21, 2008) VH7200 Humidistat Series For Humidification & Dehumidification Control For Commercial HVAC Applications BACnet Integration Manual ITG-VH72xx-BAC-E00 (028-6017_R0 Issue Date: October 21, 2008) 1 Product

More information

IMC BACnet Module. Service Literature. Table of Contents. General. Field Connections. Physical

IMC BACnet Module. Service Literature. Table of Contents. General. Field Connections. Physical Service Literature Corp. 0808 L6 06/08 IMC BACnet Module General The IMC BACnet Module (BP1) allows communication between the Lennox IMC M1 8 controller and a BACnet MS/TP network. This module is mounted

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-538-01 2/8/2017 Verify that you have the most current version of this document

More information

PIR Ready VT76xx Series Programmable & Non-Programmable Thermostats For Commercial HVAC Applications. BACnet Integration Manual September 1, 2010

PIR Ready VT76xx Series Programmable & Non-Programmable Thermostats For Commercial HVAC Applications. BACnet Integration Manual September 1, 2010 PIR Ready VT76xx Series Programmable & Non-Programmable Thermostats For Commercial HVAC Applications BACnet Integration Manual September 1, 2010 1 Product Overview The VT76xx PI thermostat family is specifically

More information

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47 WSHP Open v3 CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-539-01 2/8/2017 Verify that you have the most current version of this document

More information

MicroTech Rooftop/RMC

MicroTech Rooftop/RMC Open Protocol Data Communications Packet Version 4.1 Group: Controls Date: March 1999 MicroTech Rooftop/RMC Data Information Packet for Open Protocol 1999 McQuay International Revision History Version

More information

Manual for the integration in BMS/GTC

Manual for the integration in BMS/GTC Manual for the integration in BMS/GTC Communication parameters MODBUS RTU and BACNET COMMUNICATION UTBS PRO-REG Software Version 3.6 EN ÍNDEX 1. GENERALITIES...2 1.1. Introduction...2 1.2. signals types...2

More information

MicroTech Self-Contained Air Conditioning System

MicroTech Self-Contained Air Conditioning System Open Protocol Data Information Packet Version 2.3 Group: Controls Date: October 1999 MicroTech Self-Contained Air Conditioning System Open Protocol Data Communications t 2002 McQuay International - C O

More information

Introduction. What is the RTU Open controller?

Introduction. What is the RTU Open controller? TU Open v3 CAIE COPOATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-521-01 8/22/2017 Verify that you have the most current version of this document

More information

Corp L (Supersedes 02/2008)

Corp L (Supersedes 02/2008) Service Literature Corp. 0627L5 0608 (Supersedes 02/2008) IMC LonTalk Module GENERAL The IMC LonTalk module allows communication between the Lennox IMC M17 (version 5.02 and higher) or M18 controller and

More information

Table of Contents. WSHP Open v3

Table of Contents. WSHP Open v3 WSHP Open v3 Integration Guide CARRIER CORPORATION 2012 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-500-01 11/29/2012 Table of Contents Introduction... 1

More information

C5 controller Bacnet

C5 controller Bacnet Date: September 02, 2013 Vendor Name: Amalva UAB Product Name: C5 Firmware Revision: 1.000 BACnet Protocol Revision: 12 C5 controller Bacnet BACnet Protocol Implementation Conformance Statement Communication:

More information

MRMS Multi-Room Monitoring Station

MRMS Multi-Room Monitoring Station Technical Specification Sheet Document. 149-213 October 2, 2014 MRMS Multi-Room Monitoring Station High Definition Color (TFT) Touchscreen Display Meets CE Conformance Standards Immediate feedback on room

More information

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN April 2005 CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation

More information

Document # R00

Document # R00 Viconics VT7200 Series PIR Ready Zoning Thermostats General The VT7200 series PIR Ready low-voltage microprocessor-based zoning thermostats have been specifically designed to control either 0-10Vdc, staged,

More information

MicroTech Unit Ventilator

MicroTech Unit Ventilator Open Protocol Data Information Packet Version 2.2 Group: Controls Date: April 1996 MicroTech Unit Ventilator Open Protocol Data Communications 2002 McQuay International - C O N F I D E N T I A L - This

More information

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY A C-TRAC3 COMMUNICATION MANUAL FOR BACnet NOVEMBER 2010 TO JANUARY 2014 UNIT MODEL NO. UNIT SERIAL NO. SERVICED BY: TEL. NO: CANADIAN HEAD OFFICE AND FACTORY 1401 HASTINGS CRES. SE CALGARY, ALBERTA T2G

More information

Sales and Engineering Data Sheet ED

Sales and Engineering Data Sheet ED Sales and Engineering Data Sheet ED 15121-7 Group: Controls Part Number: ED 15121 Date: July 2017 MicroTech III Chiller Unit Controller Protocol Information Modbus Networks ANSI/ASHRAE 135-2004, BACnet

More information

Delta ORCAview 3.40 BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT

Delta ORCAview 3.40 BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT Date: December 12, 2012 Vendor Name: Delta Controls Inc. Product Name: ORCAview Product Model Number: DOW-340 Product Version: 3.40 BACnet Protocol Revision: 6 Product Description: ORCAview is an industry

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

MicroTech Series 200 Centrifugal Chiller

MicroTech Series 200 Centrifugal Chiller Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History

More information

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Technical Bulletin Code No. LIT-12011956 Issued November 23, 2015 Refer to the QuickLIT website for the most up-to-date

More information

MicroTech Water-Cooled Screw Chiller Controller

MicroTech Water-Cooled Screw Chiller Controller BACnet Data Information Packet BD 02-8 Group: Controls Date: January 2003 MicroTech Water-Cooled Screw Chiller Controller Point mapping data for the MicroTech BACdrop Gateway with PMF version 1.10 software

More information

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer Installation and interface must be performed by a qualified controls technician. IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, INTERFACE AND CONFIGURATION OF THIS EQUIPMENT. READ

More information

ESAC ebacgw Tecnoalarm

ESAC ebacgw Tecnoalarm Date: Feb 28,2011 Vendor Name: ESAC srl Product Name: ebacgw-tecnoalarm Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3 Product Description: ebacgw is a BACnet gateway for Tecnoalarm

More information

PoolPak SWHP with CommandPak Control System CPCS BACnet IP User s Guide DOCUMENT #: SVW05-BACNETIP

PoolPak SWHP with CommandPak Control System CPCS BACnet IP User s Guide DOCUMENT #: SVW05-BACNETIP PoolPak SWHP with CommandPak Control System CPCS BACnet IP User s Guide DOCUMENT #: SVW05-BACNETIP-20180529 UPDATED: MAY 2018 INTRODUCTION PoolPak dehumidifiers equipped with the CommandPak Control System

More information

ESAC ebacgw Siemens. Date: Oct 15,2008. Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3. Product Description:

ESAC ebacgw Siemens. Date: Oct 15,2008. Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3. Product Description: Date: Oct 15,2008 Vendor Name: ESAC srl Product Name: ebacgw-siemens Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3 Product Description: ebacgw is a BACnet gateway to Siemens WSM

More information

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling DataSheet ev 1.12.304/4.0 June 14, 2016 Operating Sequence

More information

Metasys Integrator TITUS Application

Metasys Integrator TITUS Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date October 12, 2005 APPLICATION NOTE Metasys Integrator TITUS Application lntroduction Page 3 Application

More information

Database for CTS6000 MODBUS

Database for CTS6000 MODBUS Database for CTS6000 MODBUS Valid for: LONcard SW1.7.4B, Variable List V2.02 Version 1.08-4, 01-05-2016 Contents Contents... 2 1. Installation... 3 1.1. Installation and operating instructions... 3 2.

More information

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller All volatile (Output) type points will revert to the uncommanded values after a power interruption.

More information

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C DataSheet ev 1.10.403/4.02 November 6, 2012 Operating Sequence Standard Occupied During

More information

Data Aire DAP TM III. LonWorks Protocol Integration Information

Data Aire DAP TM III. LonWorks Protocol Integration Information Data Aire DAP TM III LonWorks Protocol Integration Information Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-685 June 2009 Revision 1.0 Document 600-000-685

More information

Installation Guide. Bacharach HGM300 to LonWorks FT-10 Communications Adapter

Installation Guide. Bacharach HGM300 to LonWorks FT-10 Communications Adapter 3015-4568 Revision 0 9/11/03 Installation Guide Bacharach HGM300 to LonWorks FT-10 Communications Adapter Introduction The Bacharach HGM300 to LonWorks Communications Adapter enables an HGM300 Refrigerant

More information

Metasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway

Metasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway Metasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway Code No. LIT-1201993 Software Release 2.1 Issued April 12, 2006 Supersedes July 20, 2005 Document Introduction.................................................

More information

MicroTech Series-200 Flooded Screw Chiller

MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Infomation Packet Version 1.0 Group: Controls Date: February 1997 MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Communications 2002 McQuay International - C O N F I D

More information

Sales and Engineering Data Sheet ED

Sales and Engineering Data Sheet ED Sales and Engineering Data Sheet ED 15121-6 Group: Controls Part Number: ED 15121 Date: March 2017 MicroTech III Chiller Unit Controller Protocol Information Modbus Networks ANSI/ASHAE 135-2004, BACnet

More information

Data Aire DAP TM III. LonWorks Protocol Integration Information

Data Aire DAP TM III. LonWorks Protocol Integration Information Data Aire DAP TM III LonWorks Protocol Integration Information Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-685 Feb 2011 Revision 2.0 Table of Contents 1 Introduction...

More information

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom Viconics VT7350 Series PIR Ready Fan-coil Controllers General The VT7350 series are PIR Ready low-voltage microprocessor-based fan-coil controllers. Models are available controlling single speed and multi-speed

More information

P2267 NETWORK INTERFACE

P2267 NETWORK INTERFACE P2267 NETWORK INTERFACE USER MANUAL FOR OPERATING SYSTEMS: 22031-03 23636-01 October 2009 Associated Controls (Australia) Pty. Limited 2-4 Norfolk Road Greenacre, NSW, 2190. PH +61 2 9642 4922, FAX +61

More information

FieldServer Driver - Serial FS McQuay Microtech Open Protocol

FieldServer Driver - Serial FS McQuay Microtech Open Protocol Description FieldServer Driver - Serial FS-8700-80 McQuay Microtech Open Protocol This is an active client protocol. The driver is capable of acting as a master or slave. As a master, the Fieldserver polls

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

Table of Contents. W2W Open

Table of Contents. W2W Open W2W Open Points and Properties CARRIER CORPORATION 2013 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-457-01 3/27/2013 Table of Contents Introduction... 1

More information

Document # R01

Document # R01 Viconics VT7600 Series PIR-Ready Rooftop Unit Controllers Part 1 General The VT7600 series is designed for single-stage and multi-stage control of heating/cooling equipment such as rooftop and self-contained

More information

ESAC ebacgw Meteo. Date: Nov 25,2008. Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3. Product Description:

ESAC ebacgw Meteo. Date: Nov 25,2008. Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3. Product Description: Date: Nov 25,2008 Vendor Name: ESAC srl Product Name: ebacgw-meteo Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3 Product Description: ebacgw is a BACnet gateway to the weather

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet DataSheet ev 1.2.008/4.1 July 30, 2013 Operating Sequence Standard Occupied During normal occupied operation the display will show

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include: Model Number: 8680-N2 Product/System Title: Room Pressure AOC Controller with N2 Communications Protocol Contents of this manual supplement include: 1) Sequence of Operation 2) Variable map 3) Description

More information

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide Aurora Touch UPC Kit Instruction Guide For use in single compressor water-to-air equipment utilizing fi rmware UPCSWASTD01-01 Aurora Touch UPC Kit Instruction Guide *IG1583EW* IG1583EW 08/14 Aurora Touch

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483586 Microprocessor Controller for Dedicated Outdoor Air System Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before

More information

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Code No. LIT-1201743 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

Network Variables for Model CM4 LONWORKS Protocol Version 1.2

Network Variables for Model CM4 LONWORKS Protocol Version 1.2 Zellweger Analytics, Inc. 405 Barclay Boulevard Lincolnshire, IL 60069 USA Tel: 847-955-8200 Fax: 847-955-8208 Toll-free: 800-323-2000 Technical Note Network Variables for Model CM4 LONWORKS Protocol Version

More information

Metasys Integrator Airflow Application

Metasys Integrator Airflow Application Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Airflow Application lntroduction Page Application Details * Component

More information

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel Manual# 1006494 User s Manual 200E Series DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel User's Manual Rev. 1.0 Marine Pro 200E Series ~~~ DCU 210E Diesel Engine Control Unit DCU 208E Diesel

More information

Instruction, Operation, and Maintenance: Controls Software Versions: R37+

Instruction, Operation, and Maintenance: Controls Software Versions: R37+ Instruction, Operation, and Maintenance: Controls Software Versions: R37+ VPR Series VPRX Series VPRE Series VPRP Series Version October 2011 Table of Contents Safety... 3 Special Design Requests... 3

More information

FlameGard 5 UV/IR HART

FlameGard 5 UV/IR HART FlameGard 5 UV/IR HART HART Communication Manual The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized

More information

Manual# User s Manual. 200 Series. DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel

Manual# User s Manual. 200 Series. DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel Manual# 1100334 User s Manual 200 Series DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel Rev. March 2012 User's Manual for the Marine Pro 200 Series ~~~ DCU 210 Diesel Engine Control Unit DCU

More information

Installation and Maintenance Manual IM Single Duct VAV Terminals. Group: Controls Part Number: IM 1093 Date: February 2015

Installation and Maintenance Manual IM Single Duct VAV Terminals. Group: Controls Part Number: IM 1093 Date: February 2015 Installation and Maintenance Manual IM 1093-1 Single Duct VAV Terminals Group: Controls Part Number: IM 1093 Date: February 2015 Table of Contents Introduction.... 3 Revision History...3 Reference Documents...3

More information

Enterprise Buildings Integrator R500 Protocol Implementation

Enterprise Buildings Integrator R500 Protocol Implementation June 2017 Enterprise Buildings Integrator R500 Protocol Implementation Conformance Statement (PICS) Topic: BACnet Protocol Implementation Conformance Statement (PICS) Date: June 2017 Version 1 Applicable

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT-1201739 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

IntesisBox BACnet/IP Server - Notifier ID3000 series

IntesisBox BACnet/IP Server - Notifier ID3000 series IntesisBox Server - Notifier ID3000 series Gateway for integration of Notifier ID3000, ID3002, ID50 and ID60 fire panels into enabled control systems. Integrate your Notifier fire panels into your BACnet

More information

VT8000 Series Replacement Procedure to Replace VT8000 Series Room Controller and Pair with ZigBee Pro Sensors

VT8000 Series Replacement Procedure to Replace VT8000 Series Room Controller and Pair with ZigBee Pro Sensors VT8000 Series Replacement Procedure to Replace VT8000 Series Room Controller and Pair with ZigBee Pro Sensors Overview 2 This procedure shows how to replace VT8000 Room Controllers already installed, as

More information

Open Protocol Data Communications

Open Protocol Data Communications MicroTech Series-100 Centrifugal Chiller Open Protocol Data Communications Information Packet Version 3.2 April, 1996 - C O N F I D E N T I A L - This Document may not be copied or reproduced in any way

More information

CPCS SWHP BACnet MS/TP Interface User s Guide DOCUMENT #: SVW05-BACNET-MSTP

CPCS SWHP BACnet MS/TP Interface User s Guide DOCUMENT #: SVW05-BACNET-MSTP CPCS SWHP BACnet MS/TP Interface User s Guide DOCUMENT #: SVW05-BACNET-MSTP-20170713 UPDATED: JULY 2017 INTRODUCTION PoolPak dehumidifiers equipped with the CommandPak Control System for PoolPak SWHP (CPCS-SWHP)

More information

Refrigeration and Air Conditioning Controls. User s manual. ClimaTech Environmental Controller ADAP-KOOL REFRIGERATION AND AIR CONDITIONING

Refrigeration and Air Conditioning Controls. User s manual. ClimaTech Environmental Controller ADAP-KOOL REFRIGERATION AND AIR CONDITIONING Refrigeration and Air Conditioning Controls User s manual ClimaTech Environmental Controller ADAP-KOOL REFRIGERATION AND AIR CONDITIONING Table of Contents Introduction... 3 Models and part numbers...

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2018 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-537-01 1/9/2018 Verify that you have the most current version of this document

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483232 Microprocessor Controller for Energy Recovery Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting

More information

LG ELECTRONICS Air Conditioning Technologies LG Guide Specifications Controls

LG ELECTRONICS Air Conditioning Technologies LG Guide Specifications Controls LG ELECTRONICS Air Conditioning Technologies LG Guide Specifications Controls 1 Article I. General Section 1.01 Section 1.02 Section 1.03 System Description Quality Assurance Storage and Handling Article

More information

IndigoVision Alarm Panel. User Guide

IndigoVision Alarm Panel. User Guide IndigoVision Alarm Panel User Guide THIS MANUAL WAS CREATED ON 2/21/2017. DOCUMENT ID: IU-AP-MAN002-4 Legal considerations LAWS THAT CAN VARY FROM COUNTRY TO COUNTRY MAY PROHIBIT CAMERA SURVEILLANCE. PLEASE

More information

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT SEQUENCE OF OPERATION GUIDELINE AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT Document: VAV-HTG rev1 Revision: 1.0 Rev. Date: July 22, 2011 NOTES: 1. THIS SEQUENCE

More information

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers TABLE OF CONTENTS Overview 2 VT8600 Rooftop Unit Heat Pump and Indoor Air Quality Controllers 3 VT86X0U5X00B

More information

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA HART Field Device Specification Meridian wiredhart 4320 Goldmine Rd. Monroe, NC 28110 USA HART is a registered trademark of the HART Communication Foundation TABLE OF CONTENTS 1. Introduction...5 1.1 Scope...5

More information

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1 NGC-40 Bridge Overview Raychem-AR-H58862-NGC40BridgeOV-EN-1805 nvent.com 1 Table of Contents 1. NGC-40 Overview... 9 1.1 Example NGC-40 System... 10 2. Legal stuff... 11 3. Protocols... 12 3.1 Data es...

More information

Yokogawa DX Ethernet Driver Help Kepware Technologies

Yokogawa DX Ethernet Driver Help Kepware Technologies Yokogawa DX Ethernet Driver Help 2012 Kepware Technologies 2 Table of Contents Table of Contents 2 4 Overview 4 Device Setup 5 Communications Parameters 7 Optimizing Your Ethernet Communications 9 Data

More information

InfinityPro. Control System for Rapid Engineering, LLC Air Handlers. User, Operation & Troubleshooting Manual

InfinityPro. Control System for Rapid Engineering, LLC Air Handlers. User, Operation & Troubleshooting Manual InfinityPro Control System for Rapid Engineering, LLC Air Handlers User, Operation & Troubleshooting Manual Depending upon the date of shipment of your air handler(s), you will have received one of the

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a fieldselectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

Installation, Configuration and User Manual

Installation, Configuration and User Manual Model 8826 System Controller Model 8826 System Controller Installation, Configuration and User Manual READ AND SAVE THESE INSTRUCTIONS WELCOME Thank you for choosing the Aprilaire HVAC Automation System.

More information

Halton SAFE / 7.14 user guide and installation instructions

Halton SAFE / 7.14 user guide and installation instructions Halton SAFE / 7.14 user guide and installation instructions VERIFIED SOLUTIONS BY H A LTO N Enabling Wellbeing Table of contents 1 System description 3 2 User Accounts 4 3 Main menu 7 3.1 Main menu - Change

More information

Corrigo E Ventilation

Corrigo E Ventilation Corrigo E Ventilation Modbus communication guide Contains the most commonly used variables. Covers all versions of Corrigo E Ventilation from 3.2 The challenger in building automation Revision: 2 Date:

More information

DAP III Zone Master User s Guide

DAP III Zone Master User s Guide DAP III Zone Master User s Guide Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-788 March 2010 Revision 1.0 Document # 600-000-788 1 Overview The Data Aire DAP

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

York 25-Ton VAV Rooftop Unit

York 25-Ton VAV Rooftop Unit HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 0996 York 25-Ton VAV Rooftop Unit Introduction Page 3 Overview *3 Configuration 5 Sequence of Operation 7 Modes of Operation

More information

Installation and Maintenance Manual IM

Installation and Maintenance Manual IM Installation and Maintenance Manual IM 1234-1 BACnet Thermostat Group: Applied Air Systems Part Number: IM 1234 Date: December 2014 Use with Daikin MicroTech Integrated Systems or as standalone Table of

More information

USER MANUAL FOR OPERATING SYSTEM

USER MANUAL FOR OPERATING SYSTEM P2262 ALARM PANEL USER MANUAL FOR OPERATING SYSTEM 21765-07 September 1999 Associated Controls (Aust) PTY. LTD. 29 Smith Street, Hillsdale, NSW, 2036. PH (02) 9311 3255, FAX (02) 9311 3779 Page 1 of 177

More information

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide SE8600 Series Room Controllers 2 TABLE OF CONTENTS Overview 2 SE8600 Rooftop Unit and Indoor Air Quality Controllers 3 SE8600UxBxx 2 Heating

More information

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers TABLE OF CONTENTS Overview 2 VT86X0U5X00B 2 heating / 2 Cooling for Rooftop unit and Indoor air quality 3

More information

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application 2236 Application Note 140-1228 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 10 Hardware Outputs... 10

More information

ibox Modbus Server Gateway for the integration of Notifier ID3000 / ID3002 / ID60 / ID50 fire panels in Modbus enabled monitoring and control systems

ibox Modbus Server Gateway for the integration of Notifier ID3000 / ID3002 / ID60 / ID50 fire panels in Modbus enabled monitoring and control systems Honeywell Life Safety Iberia C/Pau Vila 15-19; 08911 Badalona Barcelona T. 902 03 05 45; Internacional:+34932424236 www.honeywelllifesafety.es infohlsiberia@honeywell.com ibox Modbus Server Gateway for

More information

Tracer Controls. Tracer ZN.520: Unit Controller for Terminal Products TD-PRM001-EN

Tracer Controls. Tracer ZN.520: Unit Controller for Terminal Products TD-PRM001-EN Tracer Controls Tracer ZN.520: Unit Controller for Terminal Products TD-PRM001-EN 2 TD-PRM001-EN General Tracer ZN.520 unit controller is a microprocessor-based direct digital controller that controls

More information

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657 BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657 140-1158 Building Technologies Table of Contents Overview... 5 BACnet 14 Hardware Inputs... 14 Room Unit Identification...

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information