Data Aire DAP TM III. LonWorks Protocol Integration Information

Size: px
Start display at page:

Download "Data Aire DAP TM III. LonWorks Protocol Integration Information"

Transcription

1 Data Aire DAP TM III LonWorks Protocol Integration Information Data Aire, Inc. 230 West BlueRidge Avenue Orange, California Document Number June 2009 Revision 1.0 Document Page 1 of 14

2 Table of Contents 1 Introduction Overview References Hardware Requirement Required Network Card Lontalk Network Card Installation Network Wiring XIF file Network Variable Summary Status Read/Write Configuration Control Network Variables Description nvoreturntemp NvoDiscTemp (optional) NvoWaterTemp (Optional) nvohumidity nvocoolstageson nvoheatstageson nvohumidifying nvodehumidifying nvovalve (Chilled Water Unit Only) nvohvalve (Optional) nvohitemphistory nvolotemphistory nvohihumhistory nvolohumhistory nvocoolutlz nvoheatutlz NvoChilledUtlz (Chilled Water Unit Only) nvohumidutlz...10 Document Page 2 of 14

3 5.19 nvocomp1runtime nvocomp2runtime nvocomp3runtime nvocomp4runtime nvoheat1runtime nvoheat2runtime nvoheat3runtime nvohumidruntime nvofanruntime nvocondruntime nvodehumruntime NvoESaverRuntime (Optional) NvoChillRuntime (Chilled Water Unit Only) nvoalarm nvifirelimit nvihitemplimit nvilotemplimit nvilodisclimit (Optional) NviWaterLimit (Optional) nvihihumidlimit nvilohumidlimit nvihumdeadband nvihumsetpoint nvitempdeadband nvitempsetpoint nviinhibitcool nviinhibitheat nviinhibithumid nviinhibitdehum nviinhibitfan nvistandby...14 Document Page 3 of 14

4 1 Introduction 1.1 Overview This document defines the Network Variables used by the Data Aire LonWorks protocol SNVT for the Data Air Processor III (DAP TM III) and the information of the Data Aire LonTalk Communication network card for LonTalk integration. 1.2 References Introduction to the LonWorks System Version 1.0, Echelon Corporation, 1999 ShortStack User s Guide Version 2, Echelon Corporation, March 2002 LonMark SNVT Master List, Version 12, June Hardware Requirement 2.1 Required Network Card The LonWorks protocol interface requires a Data Aire LonTalk communication network card to be installed into the DAP III panel. The LontalK card part number is See Figure 1 and 2 for card details. BOARD CONNECTOR Figure 1: Front side of the Data Aire LonTalk Communication Network card Tx and Rx LEDs SERVICE BUTTON Figure 2: Back side of the Data Aire LonTalk Communication Network card Document Page 4 of 14

5 2.2 LonTalk Network Card Installation IMPORTANT NOTE: The DAP III panel supports one network connection at a time therefore only one type of the network card can be installed For LonWorks interface, plug a LonTalk communication network card to the Communication Header J1 of the DAP III Display board. See Figure 3 below for the DAP III Display board with a LonTalk card installed. Before installing the network card, go to Menu 6-1 Unit & Network ID in Group Menu 6 Network to set the unit network ID number. Go to Menu 6-2 Network Protocol to configure to LonWorks. Menu 6-2 is locked menu; refer to the DAP III Operation Manual for the procedure of how to unlock this menu. Turn power OFF, plug the LonTalk card to the communication port J1 on the Display module of the DAP III panel. Turn the DAP III panel back ON; if the DAP III panel recognizes the Lontalk card it will display the card name during the self-test. It is recommended to reset the DAP III panel after changing network protocol or unit ID number. Tx and Rx LED Lon+ Lon_ Communication Header J1 LonTalk Communication card LonWorks TP/FT-10 Network Wiring Connections Figure 3: DAP III Display Board with a LonTalk Network Card 2.3 Network Wiring Data Aire LonTalk Network card complies with Lonworks TP/FT-10 network connections. The 18 AWG or 22 AWG shielded, twisted pair cable is recommended. The network wiring should be wired in the multidrop fashion. See Figure 3 above for the DAP III Lonworks network wiring terminations. Document Page 5 of 14

6 3 XIF file 3.1 The XIF file for Data Aire DAP III Lonworks interface can be downloaded from Data Aire website at: Recommend using this file when commissioning a Data Aire unit Lonworks interface. 4 Network Variable Summary 4.1 Status Network Variable Network Variable Type Description nvoreturntemp SNVT_temp_p Current Return Temperature nvodisctemp SNVT_temp_p Optional Current Discharge Temperature- Optional discharge air sensor required nvowatertemp SNVT_temp_p Optional Current Chilled Water Temperature Optional chilled water temperature sensor required. nvohumidity SNVT_lev_percent Current Humidity nvocoolstageson SNVT_count Cooling Stages on - DX unit only nvoheatstageson SNVT_count Heating Stages on nvohumidifying SNVT_switch Currently Humidifying nvodehumidifying SNVT_switch Currently Dehumidifying nvovalve SNVT_lev_cont Water Valve percent open. This applies to chilled water unit only nvohvalve SNVT_lev_cont Optional Humidifier Valve percent open. Optional modulating humidifier required nvohitemphistory SNVT_temp_p High Temperature Last 24 Hours nvolotemphistory SNVT_temp_p Low Temperature Last 24 Hours nvohihumhistory SNVT_lev_percent High Humidity Last 24 Hours nvolohumhistory SNVT_lev_percent Low Humidity Last 24 Hours nvocoolutlz SNVT_switch Cooling Utilization Last 24 Hours DX unit only nvoheatutlz SNVT_switch Heating Utilization Last 24 Hours nvochilledutlz SNVT_switch Chilled Water Utilization Last 24 Hours This applies to chilled water unit only nvohumidutlz SNVT_switch Humidifier Utilization Last 24 Hours nvocomp1runtime SNVT_time_hour Compressor 1 Runtime DX unit only nvocomp2runtime SNVT_time_hour Compressor 2 Runtime DX unit only nvocomp3runtime SNVT_time_hour Compressor 3 Runtime This only applies to four stages cooling unit nvocomp4runtime SNVT_time_hour Compressor 4 Runtime - This only applies to four stages cooling unit nvoheat1runtime SNVT_time_hour Heater 1 Runtime nvoheat2runtime SNVT_time_hour Heater 2 Runtime nvoheat3runtime SNVT_time_hour Heater 3 Runtime nvohumidruntime SNVT_time_hour Humidifier Runtime nvofanruntime SNVT_time_hour Blower Runtime nvocondruntime SNVT_time_hour Condenser Runtime nvodehumruntime SNVT_time_hour Dehumidifier Runtime Document Page 6 of 14

7 Network Variable Network Variable Type Description nvoesaverruntime SNVT_time_hour Energy Saver Runtime Optional. This applies to energy saver unit only nvochillruntime SNVT_time_hour Chilled Water Runtime This applies to the chilled water unit only. nvoalarm SNVT_state_64 Alarm Status See list below for details 4.2 Read/Write Configuration Network Variable Network Variable Type Description nvifirelimit SNVT_temp_p Fire Temperature Limit nvihitemplimit SNVT_temp_p High Return Air Temperature Limit nvilotemplimit SNVT_temp_p Low Return Air Temperature Limit nvilodisclimit SNVT_temp_p Low Discharge Air Temperature Limit - Optional discharge air sensor required nviwaterlimit SNVT_temp_p Chilled Water Temperature Limit Optional chilled water temperature sensor required. nvihihumidlimit SNVT_lev_percent High Humidity Limit nvilohumidlimit SNVT_lev_percent Low Humidity Limit nvihumdeadband SNVT_lev_percent Humidity Deadband nvihumsetpoint SNVT_lev_percent Humidity Setpoint nvitempdeadband SNVT_temp_diff_p Temperature Deadband nvitempsetpoint SNVT_temp_p Temperature Setpoint 4.3 Control Network Variable Network Variable Type Description nviinhibitcool SNVT_switch Inhibit Cooling nviinhibitheat SNVT_switch Inhibit Heating nviinhibithumid SNVT_switch Inhibit Humidification nviinhibitdehum SNVT_switch Inhibit Dehumidification nviinhibitfan SNVT_switch Inhibit Blower nvistandby SNVT_switch Standby Mode Unit on/off control. See the nvistandby description below for details. Document Page 7 of 14

8 5 Network Variables Description 5.1 nvoreturntemp nvoreturntemp contains the current return air temperature. 5.2 NvoDiscTemp (Optional) nvodisctemp contains the current discharge air temperature. This is an optional nvo, it requires a optional discharge air temperature sensor to be installed to the DAP III controller. 5.3 NvoWaterTemp (Optional) nvowatertemp contains the current chilled water temperature. This is an optional nvo, it requires an optional chilled water temperature sensor to be installed to the DAP III controller. 5.4 nvohumidity nvohumidity contains the current space humidity. 5.5 nvocoolstageson nvocoolstageson contains the current number of cooling stages in use. 5.6 nvoheatstageson nvoheatstageson contains the current number of heating stages in use. 5.7 nvohumidifying nvohumidifying contains the current state of the humidifier. 5.8 nvodehumidifying Humidifier value state Off 0 0 On >0 1 nvodehumidifying contains the current dehumidification state. Dehumidification value state Off 0 0 On >0 1 Document Page 8 of 14

9 5.9 nvovalve (Unit with a chilled water valve) nvovalve contains the current position of the chilled water valve. This nvo only applies to unit with a chilled water valve. 0% = Full closed 100% = Full open 5.10 nvohvalve (Optional) nvohvalve contains the current position of the humidifier valve. This is an optional nvo and only applied to unit with an optional modulating humidifier. 0% = Full closed 100% = Full open 5.11 nvohitemphistory nvohightemphistory contains the highest recorded return air temperature over the last 24 hours nvolotemphistory nvolotemphistory contains the lowest recorded return air temperature over the last 24 hours nvohihumhistory nvohighhumhistory contains the highest recorded humidity over the last 24 hours nvolohumhistory nvolohumhistory contains the lowest recorded humidity over the last 24 hours nvocoolutlz nvocoolutlz contains the average cooling utilization over the last 24 hours nvoheatutlz nvoheatutlz contains the average heating utilization over the last 24 hours NvoChilledUtlz (Unit with chilled water valve) nvochilledwaterutlz contains the average chilled water utilization over the last 24 hours. This nvo only applies to unit with a chilled water valve Document Page 9 of 14

10 5.18 nvohumidutlz nvohumidifierutlz contains the average humidifier utilization over the last 24 hours nvocomp1runtime nvocomp1runtime contains the total runtime for compressor nvocomp2runtime nvocomp2runtime contains the total runtime for compressor nvocomp3runtime (Optional) nvocomp3runtime contains the total runtime for compressor 3. This nvo only applies to DX units which have more than two stages of cooling such as unit with two tandem compressors nvocomp4runtime (Optional) nvocomp4runtime contains the total runtime for compressor 4. This nvo only applies to DX units which have more than two stages of cooling such as unit with two tandem compressors nvoheat1runtime nvoheat1runtime contains the total runtime for heater nvoheat2runtime nvoheat2runtime contains the total runtime for heater nvoheat3runtime nvoheat3runtime contains the total runtime for heater nvohumidruntime nvohumidruntime contains the total runtime for the humidifier nvofanruntime nvofanruntime contains the total runtime for the blower nvocondruntime nvocondruntime contains the total runtime for the condenser. Document Page 10 of 14

11 5.29 nvodehumruntime nvodehumruntime contains the total runtime for dehumidification NvoESaverRuntime (Optional) nvoesaverruntime contains the total runtime for energy saver. This nvo only applies to unit with an optional energy saver configuration NvoChillRuntime (Unit with a chilled water valve) nvochillruntime contains the total runtime for chilled water cooling. This nvo only applies to unit with chilled water valve nvoalarm nvoalarm is a SNVT_state_64 bitfield that contains the current unit alarms. The bits are defined in the following table. Bit Description 0 Water detected under floor: Check probe 1 No air flow: Check belt and motor 2 Dirty filter: Check filters 3 Humidifier problem: Check water pressure 4 Low voltage warning: Check unit 5 Fire stat alarm: Unit shutdown 6 Compressor short cycle warning DX unit only 7 Power problem or unit restart 8 Humidity sensor problem 9 Temperature sensor problem 10 Scheduled maintenance due 11 High pressure/internal overload: Comp 1 DX unit only 12 Low pressure C1: Automatic reset DX unit only 13 High pressure/internal overload: Comp 2 DX unit only 14 Low pressure C2: Automatic reset - DX unit only 15 Smoke detector: Unit shutdown - Optional 16 No water flow: Check pump - Optional 17 Discharge temperature sensor problem - Optional 18 High temperature warning 19 Low temperature warning 20 High humidity warning 21 Low humidity warning 22 Fan motor overload: Check motor amperage - Optional 23 Local alarm #1: See tag inside door Optional 24 Local alarm #2: See tag inside door - Optional 25 Local alarm #3: See tag inside door - Optional 26 Local alarm #4: See tag inside door - Optional Document Page 11 of 14

12 Bit Description 27 Standby pump on: Check primary pump - Optional 28 UPS power on: Check main power supply - Optional 29 Custom alarm #1 - Optional 30 Custom alarm #2 - Optional 31 Custom alarm #3 -Optional 32 Custom alarm #4 - Optional 33 Humidification inhibited - Optional 34 Reheat inhibited - Optional 35 Reheat and humidification inhibited - Optional 36 Low discharge air temperature alarm - Optional 37 Manual override: Check bypass switches 38 High condensate water level Optional on floor models, standard on ceiling models 39 Unit in standby, all functions held off Optional 5.33 nvifirelimit nvifiretemplimit contains the fire temperature limit. The valid range is o F (37-65 o C) nvihitemplimit nvihitemplimit contains the high return air temperature limit. The valid range is o F (21-32 o C) nvilotemplimit nvilotemplimit contains the low return air temperature limit. The valid range is o F (13-24 o C) nvilodisclimit (Optional) nvilodisclimit contains the low discharge air temperature limit. The valid range is o F (7-16 o C). Optional discharge air temperature sensor required. See nvodicstemp above NviWaterLimit (Optional) nviwaterlimit contains the chilled water temperature limit. The valid range is o F (5-15 o C). An optional chilled water temperature sensor required. This is only used when unit has an optional Energy saver chilled water cooling. See nvowatertemp above for details nvihihumidlimit nvihihumidlimit contains the high humidity limit. The valid range is 35-90% nvilohumidlimit nvilohumidlimit contains the low humidity limit. The valid range is 10-65%. Document Page 12 of 14

13 5.40 nvihumdeadband nvihumdeadband contains the humidity deadband setting. The valid range is 1-15% nvihumsetpoint nvihumsetpoint contains the humidity setpoint setting. The valid range is 25-70% nvitempdeadband nvitempdeadband contains the return air deadband setting. The valid range is 1-5 o F (1-2 o C) nvitempsetpoint nvitempsetpoint contains the return air setpoint setting. The valid range is o F (18-30 o C) nviinhibitcool nviinhibitcool contains the current cooling inhibit setting nviinhibitheat Inhibit Cooling value state Inhibit Off 0 0 Inhibit On >0 1 nviinhibitheat contains the current heating inhibit setting nviinhibithumid Inhibit Heating value state Inhibit Off 0 0 Inhibit On >0 1 nviinhibithumid contains the current humidification inhibit setting nviinhibitdehum Inhibit Humidification value state Inhibit Off 0 0 Inhibit On >0 1 nviinhibitdehum contains the current dehumidification inhibit setting. Inhibit Dehumidification value state Inhibit Off 0 0 Inhibit On >0 1 Document Page 13 of 14

14 5.48 nviinhibitfan nviinhibitfan contains the current blower inhibit setting nvistandby Inhibit Blower value state Inhibit Off 0 0 Inhibit On >0 1 nvistandby contains the current unit standby inhibit setting. Use this nvi for unit ON/OFF control. For instance, if the value of this nvi is changed to 2 and the state is changed to 1, the unit will be in standby mode (so called OFF mode) Mode value state On 0 0 Standby >0 1 Document Page 14 of 14

Data Aire DAP TM III. LonWorks Protocol Integration Information

Data Aire DAP TM III. LonWorks Protocol Integration Information Data Aire DAP TM III LonWorks Protocol Integration Information Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-685 Feb 2011 Revision 2.0 Table of Contents 1 Introduction...

More information

Modbus Point Map. for the. Data Aire DAP-II

Modbus Point Map. for the. Data Aire DAP-II Modbus Point Map for the Data Aire DAP-II Revision 1 November 11, 2003 Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Table of Contents 1 Introduction... 3 1.1 Scope... 3 1.2 References...

More information

Data Aire DAP TM III. Metasys Control Points

Data Aire DAP TM III. Metasys Control Points Data Aire DAP TM III Metasys Control Points Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-703 September 2009 Rev. 5.0 Document 600-000-703 Page 1 of 7 Table

More information

DAP III Zone Master User s Guide

DAP III Zone Master User s Guide DAP III Zone Master User s Guide Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-788 March 2010 Revision 1.0 Document # 600-000-788 1 Overview The Data Aire DAP

More information

Corp L (Supersedes 02/2008)

Corp L (Supersedes 02/2008) Service Literature Corp. 0627L5 0608 (Supersedes 02/2008) IMC LonTalk Module GENERAL The IMC LonTalk module allows communication between the Lennox IMC M17 (version 5.02 and higher) or M18 controller and

More information

DESCRIPTION NOTE. Temperature and Humidity Sensors MODEL 1260B

DESCRIPTION NOTE. Temperature and Humidity Sensors MODEL 1260B Wall mount/indoor transmitter for temperature, relative humidity and two dry contact inputs. Dual dry-contact inputs allow integration of light switches, motion and occupancy sensors in any combination.

More information

DESCRIPTION MODEL 1205/1205HA NOTE

DESCRIPTION MODEL 1205/1205HA NOTE Integrated Temperature, Relative Humidity and Dew Point Transmitter. Housed in a rugged stainless steel body offering excellent corrosion protection. RH Accuracy at 25 C:: Model 1205 2% typical / 3% maximum;

More information

Table of Contents. WSHP Open v3

Table of Contents. WSHP Open v3 WSHP Open v3 Integration Guide CARRIER CORPORATION 2012 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-500-01 11/29/2012 Table of Contents Introduction... 1

More information

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47 WSHP Open v3 CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-539-01 2/8/2017 Verify that you have the most current version of this document

More information

BACnet MODBUS N2 LON Description Type Point Description Name # Object Type Register Type ID SNVT # Name SNVT Read Only

BACnet MODBUS N2 LON Description Type Point Description Name # Object Type Register Type ID SNVT # Name SNVT Read Only Point Object Register SNVT SNVT Read Only 1 BAS CO 2 Sensor Value bas_co2_val_1 AV:49 float value 40001 data float 1 48 nvibasco2val SNVT_temp_p (105) BAS CO 2 Sensor Value in PPM 2 BAS Mixed Air Temperature

More information

Data Aire LCS TM (Large Ceiling System) R-410A. 6, 8, 10, and 13 ton. ISO 9001 Certified

Data Aire LCS TM (Large Ceiling System) R-410A. 6, 8, 10, and 13 ton. ISO 9001 Certified Data Aire LCS TM (Large Ceiling System) 6, 8, 10, and 13 ton ISO 9001 Certified LCS TM (LARGE CEILING SYSTEMS) DX Product Description Performance and Electrical Data 3 the pioneer and builder of the most

More information

Climatix LON communication with POL SNVTs for Twin Wheel application v1.x

Climatix LON communication with POL SNVTs for Twin Wheel application v1.x Climatix SNVTs for Twin Wheel application v1.x Table of contents 1 About this document...3 1.1 Revision history...3 1.2 Before you start...3 1.3 Reference documents...3 2 Application...4 2.1 General information...4

More information

Metasys Integrator Airflow Application

Metasys Integrator Airflow Application Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Airflow Application lntroduction Page Application Details * Component

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-538-01 2/8/2017 Verify that you have the most current version of this document

More information

Climatix LON communication with POL SNVTs for eq zone application v1.x

Climatix LON communication with POL SNVTs for eq zone application v1.x Climatix SNVTs for eq zone application v1.x Table of contents 1 About this document...3 1.1 Revision history...3 1.2 Before you start...3 1.3 Reference documents...3 2 Application...4 2.1 General information...4

More information

Document # R00

Document # R00 Viconics VT7200 Series PIR Ready Zoning Thermostats General The VT7200 series PIR Ready low-voltage microprocessor-based zoning thermostats have been specifically designed to control either 0-10Vdc, staged,

More information

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate

More information

Data Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits R-407C

Data Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits R-407C Data Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits R-407C 1 Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision

More information

Modular Data Temp Systems Air Cooled Water/Glycol Cooled 8, 10 and 13 ton capacities R-410A. ISO 9001 Certified

Modular Data Temp Systems Air Cooled Water/Glycol Cooled 8, 10 and 13 ton capacities R-410A. ISO 9001 Certified Modular Data Temp Systems Air Cooled Water/Glycol Cooled 8, 10 and 13 ton capacities ISO 9001 Certified the pioneer and builder of the most complete line of precision cooling equipment Back in the late

More information

Chilled Water 7 to 211 kw

Chilled Water 7 to 211 kw Chilled Water 7 to 211 kw Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling system was developed by data processing facility

More information

Modular Data Temp Systems Air Cooled Water/Glycol Cooled R-407C. 8, 10 and 13 ton capacities. ISO 9001 Certified

Modular Data Temp Systems Air Cooled Water/Glycol Cooled R-407C. 8, 10 and 13 ton capacities. ISO 9001 Certified Modular Data Temp Systems Air Cooled Water/Glycol Cooled 8, 10 and 13 ton capacities R-407C ISO 9001 Certified the pioneer and builder of the most complete line of precision cooling equipment Back in

More information

APOGEE Open Processor with Airflow Dataguard Driver: CCT DX Unit

APOGEE Open Processor with Airflow Dataguard Driver: CCT DX Unit Point Map Rev. 2, July, 2002 Systems Integration APOGEE Open Processor with Airflow Dataguard Driver: CCT DX Unit Table 1. CCT DX Unit, Analog Points. 01 LAI Return Air Temperature F 02 LAI Supply Air

More information

Data Aire Series Chilled Water 7 through 50 ton

Data Aire Series Chilled Water 7 through 50 ton Data Aire Series Chilled Water 7 through 50 ton ISO 9001 Certified Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling system

More information

Marvel S MICROPROCESSOR CONTROLLER. Installation, Operation and Maintenance Manual Effective October 2018 DISCONTINUED. For Reference Only

Marvel S MICROPROCESSOR CONTROLLER. Installation, Operation and Maintenance Manual Effective October 2018 DISCONTINUED. For Reference Only Marvel S MICROPROCESSOR CONTROLLER Installation, Operation and Maintenance Manual Effective October 2018 DISCONTINUED For Reference Only ***Interactive PDF*** Contents General Purpose...3 Standard And

More information

Data Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits

Data Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits Data Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits 1 Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483232 Microprocessor Controller for Energy Recovery Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

gforce - R-407C Air Cooled, Water/Glycol Cooled kw Dual Circuits

gforce - R-407C Air Cooled, Water/Glycol Cooled kw Dual Circuits gforce - R-407C Air Cooled, Water/Glycol Cooled 21-106 kw Dual Circuits 1 2 Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling

More information

OWNER S MANUAL FreeWay. LiteConnector Lon FTT-10 LonWorks -gateway for Exvent AC-series

OWNER S MANUAL FreeWay. LiteConnector Lon FTT-10 LonWorks -gateway for Exvent AC-series OWNER S MANUAL FreeWay LiteConnector Lon FTT-10 LonWorks -gateway for Exvent AC-series Pajatie 8 06150 PORVOO Tel +358 19 529 700 Fax +358 19 529 7044 www.exvent.fi 2004_1 Table of contents TABLE OF CONTENTS...

More information

Introduction. What is the RTU Open controller?

Introduction. What is the RTU Open controller? TU Open v3 CAIE COPOATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-521-01 8/22/2017 Verify that you have the most current version of this document

More information

Tracer Controls. Tracer ZN.520: Unit Controller for Terminal Products TD-PRM001-EN

Tracer Controls. Tracer ZN.520: Unit Controller for Terminal Products TD-PRM001-EN Tracer Controls Tracer ZN.520: Unit Controller for Terminal Products TD-PRM001-EN 2 TD-PRM001-EN General Tracer ZN.520 unit controller is a microprocessor-based direct digital controller that controls

More information

Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified

Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A ISO 9001 Certified Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first

More information

R-410A Air, Water/Glycol Cooled 21 through 106 kw - Dual Circuits

R-410A Air, Water/Glycol Cooled 21 through 106 kw - Dual Circuits R-410A Air, Water/Glycol Cooled 21 through 106 kw - Dual Circuits 1 Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling system

More information

N M AirControl AHU. Control manual

N M AirControl AHU. Control manual N 10.63 M 03-2016 AirControl AHU Control manual EN CONTENTS PAGE 1 - MONITORING AND CONTROL 2 1.1 The program 2 1.2 The HMI terminal 2 1.3 The controller 4 1.4 Description of the air handling units 4

More information

gforce GT R-407C Single Circuit Air Cooled, Water/Glycol Cooled 7-46 kw

gforce GT R-407C Single Circuit Air Cooled, Water/Glycol Cooled 7-46 kw gforce GT Single Circuit Air Cooled, Water/Glycol Cooled 7-46 kw 1 2 the pioneer and builder of the most complete line of precision cooling equipment Back in the late 1960 s and early 70 s with the advancement

More information

Lennox Climatic 50 and BMS Modbus, Trend or BACnet.

Lennox Climatic 50 and BMS Modbus, Trend or BACnet. Lennox Climatic 50 and BMS Modbus, Trend or BACnet. Specification of the Bus: Type: RS485 Speed: (Adjustable on Climatic 50 via display ; Setting 3933) 1200 2400 4800 9600 19200 Parity: Fixed no parity

More information

MicroTech Self-Contained Air Conditioning System

MicroTech Self-Contained Air Conditioning System Open Protocol Data Information Packet Version 2.3 Group: Controls Date: October 1999 MicroTech Self-Contained Air Conditioning System Open Protocol Data Communications t 2002 McQuay International - C O

More information

Chilled Water 7 to 211 kw

Chilled Water 7 to 211 kw Chilled Water 7 to 211 kw Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling system was developed by data processing facility

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483586 Microprocessor Controller for Dedicated Outdoor Air System Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before

More information

Product Data. Voyager TM Rooftop air conditioner or heat pump unit with LonTalk communication interface for Voyager TM rooftop controls

Product Data. Voyager TM Rooftop air conditioner or heat pump unit with LonTalk communication interface for Voyager TM rooftop controls Voyager TM Rooftop air conditioner or heat pump unit with LonTalk communication interface for Voyager TM rooftop controls LonTalk Communication Interface April 2002 Overview Each Voyager rooftop air conditioner

More information

Metasys Integrator Compu-Aire Application

Metasys Integrator Compu-Aire Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0496 APPLICATION NOTE Metasys Integrator Compu-Aire Application lntroduction Page 3 Application Details

More information

Marvel J MICROPROCESSOR CONTROLLER

Marvel J MICROPROCESSOR CONTROLLER Marvel J MICROPROCESSOR CONTROLLER Installation, Operation and Maintenance Manual Effective August 2016 ***Interactive PDF*** Contents General Purpose... 3 Standard Components... 3 Number of I/O Allowable...

More information

SYSTEM 2500 S PROGRAMMABLE CONTROLLER -USER MANUAL-

SYSTEM 2500 S PROGRAMMABLE CONTROLLER -USER MANUAL- SYSTEM 2500 S PROGRAMMABLE CONTROLLER -USER MANUAL- 8167 Byron Road Whittier, CA 90606 Phone: (562) 945-8971 Fax: (562) 696-0724 Rev.01 03-27-17 Page 1 of 67 Compu-Aire SUBJECT TO CHANGE WITHOUT INCURRING

More information

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN April 2005 CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation

More information

MicroTech Unit Ventilator

MicroTech Unit Ventilator Open Protocol Data Information Packet Version 2.2 Group: Controls Date: April 1996 MicroTech Unit Ventilator Open Protocol Data Communications 2002 McQuay International - C O N F I D E N T I A L - This

More information

COMcheck Software Version Mechanical Compliance Certificate

COMcheck Software Version Mechanical Compliance Certificate COMcheck Software Version 4.0.8.1 Mechanical Compliance Certificate Project Information Energy Code: Location: Climate Zone: Project Type: 90.1 (2013) Standard Buda, Texas 2a New Construction Construction

More information

GOLD_E_LonWorks_140611

GOLD_E_LonWorks_140611 FUNCTIONAL PROFILE: GOLDen GATE Lonworks FTT-10, TBLZ-3-1-1-41, Version 1.00 GOLD RX/PX/CX/SD, GENERATION E Applicable to program version 1.10 and newer versions Specifications are subject to alteration

More information

LONWORKS Solution for Orion PT-LON-Link

LONWORKS Solution for Orion PT-LON-Link Point Map February 5, 2008 Systems Integration LONWORKS Solution for Orion PT-LON-Link Table 1. Orion PT-Link-LON APOGEE Points, Application Number: 9158, Program ID: 90:00:95:47:1E:02:04:B3. 1 LAI AppSoftVer

More information

Installation and Operation Manual for QS/QV and Aura Units

Installation and Operation Manual for QS/QV and Aura Units Advanced program capabilities. Installation and Operation Manual for QS/QV and Aura Units Standard controller with interface mounted in unit. Optional hand-held user interface available. Multiple communication

More information

SYSTEM 2500 PROGRAMMABLE CONTROLLER -USER MANUAL-

SYSTEM 2500 PROGRAMMABLE CONTROLLER -USER MANUAL- SYSTEM 2500 PROGRAMMABLE CONTROLLER -USER MANUAL- 8167 Byron Road Whittier, CA 90606 Phone: (562) 945-8971 Fax: (562) 696-0724 SUBJECT TO CHANGE WITHOUT INCURRING OBLIGATION Rev.01 03-27-17 Page 1 of 71

More information

Data Aire LCS TM (Large Ceiling System) R-407C. 6, 8, 10, and 13 ton. ISO 9001 Certified

Data Aire LCS TM (Large Ceiling System) R-407C. 6, 8, 10, and 13 ton. ISO 9001 Certified Data Aire LCS TM (Large Ceiling System) 6, 8, 10, and 13 ton ISO 9001 Certified LCS TM (LARGE CEILING SYSTEMS) with refrigerant Product Description Performance and Electrical Data Dimensional Data Guide

More information

DX-9100 Applications from Engineering Services

DX-9100 Applications from Engineering Services System 9100 Technical Manual 636.4 Application Examples Section Technical Bulletin Issue Date 0896 DX-9100 Applications from Engineering Services Introduction Page 3 Overview 3 Air Handling Unit Applications

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

LV CONTROLLER

LV CONTROLLER SERVICE INSTRUCTIONS WITH REPLACEMENT PARTS LIST LV1000-200 CONTROLLER NOTE: LV1000 controller is required for operation when FUSION-TEC HR**BP wall-mount units are used. Bard Manufacturing Company, Inc.

More information

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer Installation and interface must be performed by a qualified controls technician. IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, INTERFACE AND CONFIGURATION OF THIS EQUIPMENT. READ

More information

D A R A - 4. Data Aire Relay Auto-Changeover

D A R A - 4. Data Aire Relay Auto-Changeover D A R A - 4 Data Aire Relay Auto-Changeover WARNING: If adding the DARA-4 panel to existing units that did not include a DARA-4 panel when originally purchased it will be necessary to add a relay or relays.

More information

MicroTech Rooftop/RMC

MicroTech Rooftop/RMC Open Protocol Data Communications Packet Version 4.1 Group: Controls Date: March 1999 MicroTech Rooftop/RMC Data Information Packet for Open Protocol 1999 McQuay International Revision History Version

More information

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems Series 9 Commissioning Checklist S9-CL2017.doc ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 S9-CL2017.doc Commissioning

More information

Predator Controller Hardware Family

Predator Controller Hardware Family Predator Controller Hardware Family Figure1: Predator Controller Only. Figure 2: Predator VAV Actuator. The LONMARK certified configurable Predator Controller provides direct digital control of a variety

More information

FieldServer Driver - Serial FS McQuay Microtech Open Protocol

FieldServer Driver - Serial FS McQuay Microtech Open Protocol Description FieldServer Driver - Serial FS-8700-80 McQuay Microtech Open Protocol This is an active client protocol. The driver is capable of acting as a master or slave. As a master, the Fieldserver polls

More information

7.1 Data Guard 5.0 variable list

7.1 Data Guard 5.0 variable list INTERNAL ONLY Issue: DG5 Modbus Register Map Product line: Airflow with DG5 Board Environment: Airflow with DG5 Board Cause: Resolution: 7.1 Data Guard 5.0 variable list BACNET MODBU S Airflow DG5 Binary

More information

WaterFurnace FX10 Application Guide Reversible Chiller

WaterFurnace FX10 Application Guide Reversible Chiller 2011 WaterFurnace FX10 Application Guide Reversible Chiller Introduction This manual provides information about the FX10 Water Source Heat Pump (WSHP) controller as it relates to dual compressor water

More information

RSMSD Technical Guide

RSMSD Technical Guide RSMSD Technical Guide www.aaon.com AAON/WattMaster Controls Inc. 8500 NW River Park Drive Parkville, MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 FAX: (816) 505-1101 E-mail: mail@wattmaster.com

More information

Shelf Units R-407C. 2, 3, and 4 ton. ISO 9001 Certified

Shelf Units R-407C. 2, 3, and 4 ton. ISO 9001 Certified Shelf Units 2, 3, and 4 ton R-407C ISO 9001 Certified the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling system was developed by data processing

More information

Control Systems. Design & Manufacturing. Eco-Friendly. High Performance

Control Systems. Design & Manufacturing. Eco-Friendly. High Performance Temperature & Humidity Control Systems Design & Manufacturing DX Air / Water / Glycol Cooled Air and Water Side Economizer Chilled Water Systems Eco-Friendly High Performance OPTIMAL COOLING SOLUTIONS

More information

LC6000 Controller used with MULTI-TEC Wall Mount Units Specification Sheet & Application Guide

LC6000 Controller used with MULTI-TEC Wall Mount Units Specification Sheet & Application Guide LC6000 Controller used with MULTI-TEC Wall Mount Units Specification Sheet & Application Guide FEATURES OF THE LC6000 CONTROLLER Control up to 14 units with a single LC6000 controller. Complete control

More information

MARVEL PREMIUM HVAC MICROPROCESSOR CONTROLLER

MARVEL PREMIUM HVAC MICROPROCESSOR CONTROLLER MARVEL PREMIUM HVAC MICROPROCESSOR CONTROLLER Installation, Operation and Maintenance Manual Effective May 2017 ***Interactive PDF*** CONTENTS GENERAL PURPOSE 3 MARVEL PREMIUM - CONTROLLABLE SYSTEM COMPONENT

More information

CONTROLS MANUAL For all Innovent and Valent air handling products

CONTROLS MANUAL For all Innovent and Valent air handling products CONTROLS MANUAL For all Innovent and Valent air handling products TABLE OF CONTENTS TABLE OF CONTENTS IMPORTANT INFORMATION Safety information...................................................................................

More information

Network Variables for Model CM4 LONWORKS Protocol Version 1.2

Network Variables for Model CM4 LONWORKS Protocol Version 1.2 Zellweger Analytics, Inc. 405 Barclay Boulevard Lincolnshire, IL 60069 USA Tel: 847-955-8200 Fax: 847-955-8208 Toll-free: 800-323-2000 Technical Note Network Variables for Model CM4 LONWORKS Protocol Version

More information

MicroTech III Applied Air Handling Unit Controller Protocol Information

MicroTech III Applied Air Handling Unit Controller Protocol Information Engineering Data ED 15112-2 Group: Controls Part Number: ED 15112-2 Date: January 2009 Supersedes: ED 15112-1 MicroTech III Applied Air Handling Unit Controller Protocol Information Networks Networks 2009

More information

HeatNet Manual Control Adjustment and Operation Instructions for Hydrotherm Firmware Version 2.8

HeatNet Manual Control Adjustment and Operation Instructions for Hydrotherm Firmware Version 2.8 KN-2/4-CM2-313 42-9452 Cast Iron Condensing Boilers Models KN-2 and KN-4 HeatNet Manual Control Adjustment and Operation Instructions for Hydrotherm Firmware Version 2.8 Also read and follow: KN Boiler

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 482641 Microprocessor Controller for Make-Up Air Products Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting

More information

Flexible & Innovative. Cooling Solutions

Flexible & Innovative. Cooling Solutions Flexible & Innovative Cooling Solutions Flexible & Innovative Compu-Aire Inc. offers a variety of high performance precision cooling systems that can adapt to your application needs. With today s rapidly

More information

Mechanical Compliance Certificate

Mechanical Compliance Certificate COMcheck Software Version 4.0.7.0 Mechanical Compliance Certificate Project Information Energy Code: Location: Climate Zone: Project Type: 90.1 (2013) Standard Austin, Texas 2a (weather data: TBD) New

More information

NetworkAIR AFX. Operation and Maintenance AFX65 AFX18

NetworkAIR AFX. Operation and Maintenance AFX65 AFX18 NetworkAIR AFX Operation and Maintenance AFX65 AFX18 Contents Operation... 1 Display Interface.......................................... 1 Using the Display......................................... 3

More information

OWNER S MANUAL Venstar Inc. 08/07

OWNER S MANUAL Venstar Inc. 08/07 Digital Thermostat residential THERMOSTAT T1 800 7-DAY PROGRAMMABLE up to 3-heat & 2-cool HEAT COOL HEAT PUMP Control up to 3 Heat & 2 Cool Stages 3 Configurable Outputs Adjustable 2nd & 3rd Stage Timers

More information

Installation Guide. Bacharach HGM300 to LonWorks FT-10 Communications Adapter

Installation Guide. Bacharach HGM300 to LonWorks FT-10 Communications Adapter 3015-4568 Revision 0 9/11/03 Installation Guide Bacharach HGM300 to LonWorks FT-10 Communications Adapter Introduction The Bacharach HGM300 to LonWorks Communications Adapter enables an HGM300 Refrigerant

More information

DXM CONTROLS. DXM Digital Heat Pump Controllers. Application, Operation, & Maintenance. Table of Contents

DXM CONTROLS. DXM Digital Heat Pump Controllers. Application, Operation, & Maintenance. Table of Contents Table of Contents DXM CONTROLS DXM Electronic Controls Features Comparison 2 DXM Electronic Heat Pump Controls 3 DXM Physical Dimensions & Layout 4 DXM Controls 5 DXM Service & Application Notes 13 Troubleshooting

More information

gforce Units Data Aire and Data Temp Series

gforce Units Data Aire and Data Temp Series gforce Units gforce gforce is the most advanced mission critical cooling equipment available on the market today. These units are the most efficient and economical while complying with strict environmental

More information

DC 60 & DM 60 displays

DC 60 & DM 60 displays USER MANUAL DC 60 & DM 60 displays BALTIC FLEXAIR ENERGY AIRCOOLAIR COMPACTAIR FLATAIR (& Inverter) AQUALEAN DC60-DM60-IOM-1310-E www.lennoxemea.com Summaries 1 Display DC60 1.1 Introduction... 2 1.2

More information

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide Aurora Touch UPC Kit Instruction Guide For use in single compressor water-to-air equipment utilizing fi rmware UPCSWASTD01-01 Aurora Touch UPC Kit Instruction Guide *IG1583EW* IG1583EW 08/14 Aurora Touch

More information

Modbus RTU RS485 Manual

Modbus RTU RS485 Manual Modbus RTU RS485 Manual AUTOMATED FUEL MAINTENANCE SYSTEMS FTI-5A, FTI-10A, FTI-20A FUEL TECHNOLOGIES INTERNATIONAL 06/10/2014 Rev B - Fuel Technologies - Modbus The Modbus Communications Setup Button

More information

Anti-sweat Energy Saver Installation guide

Anti-sweat Energy Saver Installation guide MTA installation and operation Parker Hannifin Canada Micro Thermo Technologies TM 12855 Brault Street Mirabel, QC J7J 0C4 Office phone 450-668-3033 Introduction. Anti-sweat Energy Saver Installation guide

More information

Control manual. Series. Gas-fired direct vent Cast iron boilers. Control adjustment and Operation instructions

Control manual. Series. Gas-fired direct vent Cast iron boilers. Control adjustment and Operation instructions KNCT2-808 KN Series Gas-fired direct vent Cast iron boilers Models KN-6, -10, -20 only (HeatNet control firmware edition 45 ) Control manual Control adjustment and Operation instructions Also read and

More information

HVAC Mandatory Provisions Part II, Page 1

HVAC Mandatory Provisions Part II, Page 1 HVAC Mandatory Provisions Part II, Page 1 Mandatory Equipment Efficiency Worksheet (6.4.1.1) System Equipment Type Size Category (Tables 6.8.1A through K) Sub-Category or Rating Condition Units of Efficiency

More information

ICC INDUSTRIAL CONTROL COMMUNICATIONS, INC.

ICC INDUSTRIAL CONTROL COMMUNICATIONS, INC. ETH-1000 Chillgard LC Quick Start Guide for BACnet MS/TP This document provides a brief overview of the connections and settings that must be used to connect a preconfigured ETH-1000 gateway to a MSA Chillgard

More information

BAC-4000 Series AppStat

BAC-4000 Series AppStat BAC-4000 Series AppStat Description The KMC AppStat combines the power of a space mounted equipment controller with the convenience of built-in temperature, humidity and motion sensors. The controllers

More information

Application Guide. HPL1 Water Source Heat Pump Controller. Self-Contained Interoperable Controller Model UCP-1 for Software Version 3

Application Guide. HPL1 Water Source Heat Pump Controller. Self-Contained Interoperable Controller Model UCP-1 for Software Version 3 Application Guide 505-040-3 HPL1 Water Source Heat Pump Controller Self-Contained Interoperable Controller Model UCP-1 for Software Version 3 SUPERSEDES: March 10, 2015 EFFECTIVE: October 26, 2015 Plant

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

Installation Instructions

Installation Instructions SYSTXCCUIZ01-- V Infinityt Control Installation Instructions ZONE HOLD INFINITY SYSTEM Fig. 1 - Infinityt Zone Control HEAT COOL OFF A04031 NOTE: Read the entire instruction manual before starting the

More information

opti-visor ultra-efficient chiller plant automation Typical specification

opti-visor ultra-efficient chiller plant automation Typical specification opti-visor ultra-efficient chiller plant automation Typical File No: 90.893 Date: february 9, 2015 Supersedes: 90.893 Date: april 20, 2012 contents 1.0 Chilled water plant 4 1.1 General system requirements

More information

RTU. Roof Top Units 8 30 Ton. Maxi-Kool.

RTU. Roof Top Units 8 30 Ton. Maxi-Kool. Maxi-Kool RTU Roof Top Units 8 30 Ton www.compu-aire.com MK A-3 034 -RTU Maxi-Kool Type Air Cooled - A Chilled Water Cooled - C Glycol Cooled - G Water Cooled - W Nominal Tonnage 8 30 Ton Voltage 2-208

More information

MicroTech Series-200 Flooded Screw Chiller

MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Infomation Packet Version 1.0 Group: Controls Date: February 1997 MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Communications 2002 McQuay International - C O N F I D

More information

OWNER S MANUAL Venstar Inc. 08/07

OWNER S MANUAL Venstar Inc. 08/07 Digital Thermostat commercial SCHOOL THERMOSTAT T2900SCH MABLE up to 3-heat & 2-cool HEAT COOL HEAT PUMP Energy Saving Operation Morning Warm-up Period Programmable Override Unoccupied until button press

More information

User Guide. Color Touchscreen Programmable Residential Thermostat. ComfortSense Model: 13H /2015 Supersedes 7/2015

User Guide. Color Touchscreen Programmable Residential Thermostat. ComfortSense Model: 13H /2015 Supersedes 7/2015 User Guide Color Touchscreen Programmable Residential Thermostat ComfortSense 7500 Model: 13H14 507503-01 10/2015 Supersedes 7/2015 TABLE OF CONTENTS Features... 2 Temperature Dial Indicator... 3 Home

More information

VisionPRO 8000 with Wi-Fi

VisionPRO 8000 with Wi-Fi VisionPRO 8000 with Wi-Fi FEATURES PRODUCT DATA Thermostat acquires weather data through either a wired sensor or an Internet connection, making for a truly universal installation. U1 Terminals One set

More information

HEAT COOL. Meets Commercial California Title 24

HEAT COOL. Meets Commercial California Title 24 Digital Thermostat commercial THERMOSTAT T2900 7-DAY MABLE up to 3-heat & 2-cool HEAT COOL HEAT PUMP Control up to 3 Heat & 2 Cool Stages 3 Configurable Outputs Adjustable 2nd & 3rd Stage Timers & Deadbands

More information

Networkable Fan Coil Controller Specification and Installation Instructions

Networkable Fan Coil Controller Specification and Installation Instructions Controller Models EFCB10T-OE1 (24Vac / 0 relays) EFCB12T-OE1 (240Vac / 0 relays) EFCB10TU4-OE1 (24Vac / 4 relays) EFCB12TU2-OE1 (240Vac / 2 relays) EFCB12TU4-OE1 (240Vac / 4 relays) TFL Series Thermostat

More information

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY A C-TRAC3 COMMUNICATION MANUAL FOR BACnet NOVEMBER 2010 TO JANUARY 2014 UNIT MODEL NO. UNIT SERIAL NO. SERVICED BY: TEL. NO: CANADIAN HEAD OFFICE AND FACTORY 1401 HASTINGS CRES. SE CALGARY, ALBERTA T2G

More information