Climatix LON communication with POL SNVTs for eq zone application v1.x

Size: px
Start display at page:

Download "Climatix LON communication with POL SNVTs for eq zone application v1.x"

Transcription

1 Climatix SNVTs for eq zone application v1.x

2 Table of contents 1 About this document Revision history Before you start Reference documents Application General information Network variables Overview General Mandatory variables Optional input variables Optional output variables Configuration parameters Appendix Description of SNVTs

3 1 About this document 1.1 Revision history Version Date Changes Section Pages First edition 1.2 Before you start Validity This document applies to the following product: Name Type (ASN) Version Fläkt Woods standard application, eq POL63x.00/AHU x.xx zone LON image POLXXX_Std_AHU_V100 (ClimatixAHU) 1.00 This document is a supplement to the general integration guide: "" *) *) POL906.00: Climatix LON communication module That document must be read first and all general information such as document conventions, important information on safety, trademarks, copyright etc. are valid for this document as well. This document only contains the uniqe information for the product mentioned above. All general engineering information such as mounting modules, communication settings etc. are described in the integration guide. Prerequisite User has read the general LON integration guide for Climatix, 8971GB. 1.3 Reference documents Further information The following documents contain additional information on the products described in this manual: Document Order no. Data sheet "Communication module LON" CB1Q3931en Integration Guide "" 8971GB 3

4 2 Application 2.1 General information Standard application eq zone Standard application eq Zon v1.x is available at this time. It contains all common functions to control and monitor air conditioning in 4 zones and 4 associated fans. The following diagram provides an overview: Detailed information Contact Fläkt Woods support for a detailed description of standard application eq zon v1.x. Network variables The set of loadable files mentioned above also includes a mapping file for integration in a higher building automation and control system via communications module. The Climatix controller automatically assumes the network variables required for integration as per the plant data points and functions configured and parameterized previously. The following tables list all network variables as per the overview in Section 0. Network variables 4

5 3. Network variables 3.1 Overview Contents of LON image set AHU V1.x The LON module's Neuron application supports 62 network variables to integrate controllers with air handling applications in a management station, and allow controllers to exchange data over LON. The figure shows the variables for LON image set (XIF) POLXXX_Std_AHU_V100 (ClimatixAHU V1.x) and their SNVTs, grouped as follows: Mandatory network variables (A) Optional network variables (B) Configuration parameters (C) nvirequest SNVT_obj_request A nvostatus SNVT_obj_status P3931Z10 nvitemps SNVT_temp_setpt B nvotemps SNVT_temp_setpt nvotemp01 nvotemp02 nvitemp01 nvotemp03 nvotemp04 nvotemp05 nvitemp02 nvotemp06 nvotemp07 nvotemp08 nvihum00 SNVT_abs_humid nvohum00 SNVT_abs_humid nvohum01 SNVT_abs_humid nvihum01 SNVT_abs_humid nvoflow00 SNVT_flow nvoflow01 SNVT_flow nvippm00 nvoppm00 nvipress_flow00 nvopress00 SNVT_press_p nvopress01 SNVT_press_p nvopress02 SNVT_press_p nvipress_flow01 nvipress_flow02 nvipress_flow03 Neuron Application AHU V1.x nvopress_flow00 nvoperc00 nvoperc03 nvopress_flow01 nvoperc01 nvoperc04 nvoperc02 nvoperc05 nvipress_flow04 nvoperc06 nvoperc07 nvoperc08 nvipress_flow05 nvoperc09 nvoperc10 nvoperc11 nviresetalarm SNVT_switch nvoperc12 nvoperc13 nvoperc14 nviopmode SNVT_switch nvoopmode SNVT_switch nvicontrol SNVT_state nvoswitch00 SNVT_switch nviacttime SNVT_time_stamp nvostate SNVT_state_64 nvodo SNVT_state_64 nvodi SNVT_state_64 nvoalarm SNVT_state_64 ncimaxsndtime SNVT_time:sec C ncimaxrcvtime SNVT_time_sec ncistartupdelay SNVT_time_sec The sections below describe the network variables. 5

6 3.2 General Purpose SNVT handling The following sections describe the network variables used in the specific application and LON image (XIF), see Section 1.2 "Before you start". Pay attention to the following explanations concerning some specific characteristics of SNVTs and elements used: SNVT / Element Explanation Heartbeat All output (nvo) SNVTs send heartbeat. No SNVTs requires heartbeat from the network. All input (nvi) SNVTs write back changed values, from the controller, to the Neuron, means that a setpoint could be set from both the controller and the network, depending on BMS system. Min Send time Some output (nvo) SNVTs use the "Min send time". Means that this SNVT have fastest send interval of x seconds. SNVT_state Climatix are using SNVT_state binary counted from left to right and due to that some LON devices counts from right. In this case it is necessary to invert the bits, Bit0=Bit15, Bit1=Bit14... SNVT_switch The state part for SNVT_switch must be set to 1 (Active) to use the value part. SNVT_temp_setpt The SNVT_temp_setpt is used for different temperature set points and to show the actual set points, and it could be different set points than named within the SNVT due to these names are fixed. Example is the first value "occupied cool" used for Basic heating set point instead. See further in this document. Override I/Os Inputs that are possible to override via LON is marked with (I/O), theese must first be setup to be overridden via communication, see Integration guide. SNVT info The following tables briefly describe each variable used and it's SNVT. Thereby the "NV index" presents the network variable number in the XIF file (LON image). Refer to 4.1 "Description of SNVTs" for more information on the SNVTs. In the configuration mode it s possible to activate Zone 1 Zone 4 and Fan 1 4 in the same regulator. But the LON network variables are only 63 / regulator. This means that it s only possible to control 2 Zones or 2 Fans in 1 regulator. If there is a need to have 3 or 4 zones/fans it only possible with 2 regulators. Ex. Regulator 1 Zone 1 2, Fan 1 2 Regulator 2 Zone 3 4, Fan 3 4 Zone 1 and 3 use the same network variables. Fan 1 and 3 use the same network variables. Zone 2 and 4 use the same network variables. Fan 2 and 4 use the same network variables. 6

7 3.3 Mandatory variables Introduction Input variable nvirequest Two of the network variables supported by the LON module's Neuron application are mandatory. They are needed for system purposes: The two variables are: nvirequest nvostatus Requires a particular mode for a specific object in a device. nvirequest Object request SNVT_obj_request NV index: 0 Output variable nvostatus Signals the status of the requested object in the device. nvostatus Object status SNVT_obj_status NV index: 1 7

8 3.4 Optional input variables Introduction The LON module's Neuron application supports 62 network variables. 56 of these are optional. The following tables briefly describe each variable and its SNVT. The network variable tables are listed by: Input variables (23) Output variables (33) Input variables nvitemps Inputs variables sorted according to the overview of Section 0: nvitemps Names in SNVT Heating Setpoint Zone 1 or 3 Cooling deadzone Zone 1 or 3 Min limit Zone 1 or 3 Heating Setpoint Zone 2 or 4 Cooling deadzone Zone 2 or 4 Min limit Zone 2 or 4 NV index: 14 SNVT_temp_setpt Structured setpoint variable for 6 temperature setpoints. Different setpoint combinations are used depending on configuration. occupied_cool standby_cool unoccupied_cool occupied_heat standby_heat unoccupied_heat nvitemp02 nvitemp02 Outside air temperature NV index: 16 (I/O) 8

9 Optional input variables, continued nvipress_flow00 nvipress_flow00 Fan1 or 3 step 1 setpoint NV index: 2 For Pressure, Flow and %, depending on configuration. (max Pa or l/sec) nvipress_flow01 nvipress_flow01 Fan1 or 3 step 2 setpoint NV index: 3 For Pressure, Flow and %, depending on configuration. (max Pa or l/sec) nvipress_flow02 nvipress_flow02 Fan1 or 3 step 3 setpoint NV index: 4 For Pressure, Flow and %, depending on configuration. (max Pa or l/sec) nvipress_flow03 nvipress_flow03 Fan2 or 4 step 1 setpoint NV index: 5 For Pressure, Flow and %, depending on configuration. (max Pa or l/sec) nvipress_flow04 nvipress_flow04 Fan2 or 4 step 2 setpoint NV index: 6 For Pressure, Flow and %, depending on configuration. (max Pa or l/sec) nvipress_flow05 nvipress_flow05 Fan2 or 4 step 3 setpoint NV index: 7 For Pressure, Flow and %, depending on configuration. (max Pa or l/sec) 9

10 Optional input variables, continued nviresetalarm nviresetalarm Reset/Acknowledge alarms SNVT_switch NV index: 11 Values: 0 Normal 1 ResetA/Acknowledge > 1 Not defined State: 0: Inactive 1: Active Default: Value: 0 State : 0 State part must be set to 1 to use the value part. 10

11 Optional input variables, continued nvicontrol nvicontrol Control signals SNVT_state (16 bit) NV index: 13 Bits: Bit [0...15] Emergency stop input (I/O) External control input 1 (I/O) External control input 2 (I/O) Summer/winter changeover switch (I/O) Fire alarm input (I/O) Fan 1 External control input Fan 2 External control input Fan 3 External control input Fan 4 External control input Communicationtest puls Binary: * Reverse: * On some LON tools the bits are named in the other direction, so take care nviacttime nviacttime System clock SNVT_time_stamp NV index: 57 11

12 3.5 Optional output variables Output variables Output variables sorted according to the overview on Section 0: nvotemps nvotemps Names in SNVT Actual heating setpoint Zone 1 or 3 Actual cooling setpoint Zone 1 or 3!!! Actual heating setpoint Zone 2 or 4 Actual cooling setpoint Zone 2 or 4!!! SNVT_temp_setpt NV index: 40 Structured setpoint variable for 6 setpoints. Actual main setpoints are depending on number of activated Zones. occupied_cool standby_cool unoccupied_cool occupied_heat (Uses Min Send time) standby_heat (Uses Min Send time) unoccupied_heat (COV 1.0) nvotemp01 nvotemp01 Supply air temperature Zon 1 or 3 NV index: 41 nvotemp02 nvotemp02 Actual room temperature Zone 1 or 3, or Return air temperature Zone 1 or 3 NV index: 42 Depending on configuration nvotemp03 nvotemp03 Heating frost temperature Zone 1 or 3 NV index: 43 Uses Min Send time nvotemp04 nvotemp04 External set point Zone 1 or 3 NV index: 44 Depending on configuration nvotemp05 nvotemp05 Supply air temperature Zon 2 or 4 NV index: 45 12

13 Optional output variables, continued nvotemp06 nvotemp06 Actual room temperature Zone 2 or 4, or Return air temperature Zone 2 or 4 NV index: 46 Depending on configuration nvotemp07 nvotemp07 Heating frost temperature Zone 2 or 4 NV index: 47 nvotemp08 nvotemp08 External set point Zone 2 or 4 NV index: 48 nvopress00 nvopress00 Supply air pressure Fan 1 or 3 Pa SNVT_press_p NV index: 19 COV 5.0 nvopress01 nvopress01 Supply air pressure Fan 2 or 4 Pa SNVT_press_p NV index: 20 COV 5.0 nvopress02 nvopress02 External Setpoint Fan 1 or 3 C SNVT_press_p NV index: 21 COV

14 Optional output variables, continued nvopress_flow00 nvopress_flow00 Actual setpoint Fan 1 or 3 NV index: 22 %, Pa or l/sec depending on configuration COV 1.0 nvopress_flow01 nvopress_flow01 Actual setpoint Fan 2 or 4 NV index: 23 %, Pa or l/sec depending on configuration COV 1.0 nvoflow00 nvoflow00 Supply air flow Fan 1 or 3 l/sec SNVT_flow NV index: 17 COV 10.0 nvoflow01 nvoflow01 Supply air flow Fan 2 or 4 l/sec SNVT_flow NV index: 18 COV 10.0 nvoperc00 nvoperc00 Heating / Electrical heating output signal Zone 1 or 3 NV index: 24 COV 1.0 nvoperc01 nvoperc01 Cooling output signal Zone 1 or 3 NV index: 25 COV 1.0 nvoperc02 nvoperc02 Heating / Electrical heating output signal Zone 2 or 4 NV index: 26 COV

15 Optional output variables, continued nvoperc03 nvoperc03 Cooling output signal Zone 2 or 4 NV index: 27 COV 1.0 nvoperc04 nvoperc04 Output signal Fan 1 or 3 NV index: 28 COV 1.0 nvoperc05 nvoperc05 Output signal Fan 2 or 4 NV index: 29 COV 1.0 nvoperc08 nvoperc08 Actual op mode Zone 1 or 3 NV index: 32 Off*Comfort*Economy*Na*FullHtg*FullClg*N a*stop COV 1.0 nvoperc09 nvoperc09 Actual op mode Zone 2 or 4 NV index: 33 Off*Comfort*Economy*Na*FullHtg*FullClg*N a*stop COV

16 Optional output variables, continued nvoperc10 nvoperc10 Actual Fan Op Mode Fan 1 or 3 NV index: 34 Off*On*Force*Na*Na*Na*Fire*Stop COV 1.0 nvoperc11 nvoperc11 Actual Fan Op Mode Fan 2 or 4 NV index: 35 Off*On*Force*Na*Na*Na*Fire*Stop COV 1.0 nvoperc13 nvoperc13 Actual Fan step Fan 1 or 3 NV index: 37 Off*Stage1*Stage2*Stage3 COV 1.0 nvoperc14 nvoperc14 Actual Fan step Fan 2 or 4 NV index: 38 Off*Stage1*Stage2*Stage3 COV

17 Optional output variables, continued nvostate nvostate General status SNVT_state_64 (64 bit) NV index: 55 Bits Bit [0 63] Alarm class danger (A) Alarm class critical (A) Alarm class low (B) Alarm class warning (C) Manual control active Summer mode Communicationtest puls Preheating, heating Zone 1 Preheating, heating Zone 2 Preheating, heating Zone 3 Preheating, heating Zone 4 Zone 1 Room Control mode Zone 1 Return Control mode Zone 1 Supply Control mode Zone 2 Room Control mode Zone 2 Return Control mode Zone 2 Supply Control mode Zone 3 Room Control mode Zone 3 Return Control mode Zone 3 Supply Control mode Zone 4 Room Control mode Zone 4 Return Control mode Zone 4 Supply Control mode Fan 1 Alarm class danger (A) Fan 1 Alarm class critical (A) Fan 1 Alarm class low (B) Fan 1 Alarm class warning (C) Fan 2 Alarm class danger (A) Fan 2 Alarm class critical (A) Fan 2 Alarm class low (B) Fan 2 Alarm class warning (C) Fan 3 Alarm class danger (A) Binary: * Reverse: * On some LON tools the bits are named in the other direction, so take care 17

18 Optional output variables, continued nvostate, cont. nvostate Bit array for general status SNVT_state_64 (64 bit) NV index: 55 Bits Bit [0 63] Fan 3 Alarm class critical (A) Fan 3 Alarm class low (B) Fan 3 Alarm class warning (C) Fan 4 Alarm class danger (A) Fan 4 Alarm class critical (A) Fan 4 Alarm class low (B) Fan 4 Alarm class warning (C) Zone 1 Alarm class danger (A) Zone 1 Alarm class critical (A) Zone 1 Alarm class low (B) Zone 1 Alarm class warning (C) Zone 2 Alarm class danger (A) Zone 2 Alarm class critical (A) Zone 2 Alarm class low (B) Zone 2 Alarm class warning (C) Zone 3 Alarm class danger (A) Zone 3 Alarm class critical (A) Zone 3 Alarm class low (B) Zone 3 Alarm class warning (C) Zone 4 Alarm class danger (A) Zone 4 Alarm class critical (A) Zone 4 Alarm class low (B) Zone 4 Alarm class warning (C) Binary: * Reverse: * On some LON tools the bits are named in the other direction, so take care 18

19 Optional output variables, continued nvodo nvodo All digital outputs SNVT_state_64 (64 bit) NV index: 54 Bits: Bit [0 63] Zone 1 Cooling Pump Zone 1 Cooling DX, stage 1 Zone 1 Cooling DX, stage 2 Zone 1 Cooling DX, stage 3 Zone 1 Heating Pump Zone 1 Electrical Heating Stage 1 Zone 1 Electrical Heating Stage 2 Zone 1 Electrical Heating Stage 3 Zone 2 Cooling Pump Zone 2 Cooling DX, stage 1 Zone 2 Cooling DX, stage 2 Zone 2 Cooling DX, stage 3 Zone 2 Heating Pump Zone 2 Electrical Heating Stage 1 Zone 2 Electrical Heating Stage 2 Zone 2 Electrical Heating Stage 3 Zone 3 Cooling Pump Zone 3 Cooling DX, stage 1 Zone 3 Cooling DX, stage 2 Zone 3 Cooling DX, stage 3 Zone 3 Heating Pump Zone 3 Electrical Heating Stage 1 Zone 3 Electrical Heating Stage 2 Zone 3 Electrical Heating Stage 3 Zone 4 Cooling Pump Zone 4 Cooling DX, stage 1 Zone 4 Cooling DX, stage 2 Zone 4 Cooling DX, stage 3 Zone 4 Heating Pump Zone 4 Electrical Heating Stage 1 Zone 4 Electrical Heating Stage 2 Zone 4 Electrical Heating Stage 3 Fan 1 Running Fan 1 Stage 1 Fan 1 Stage 2 Fan 1 Stage 3 Fan 2 Running Fan 2 Stage 1 Fan 2 Stage 2 Fan 2 Stage 3 Fan 3 Running Binary: * Reverse: * On some LON tools the bits are named in the other direction, so take care 19

20 Optional output variables, continued nvodo, cont. nvodo All digital outputs SNVT_state_64 (64 bit) NV index: 54 Bits: Bit [0 63] Fan 3 Stage 1 Fan 3 Stage 2 Fan 3 Stage 3 Fan 4 Running Fan 4 Stage 1 Fan 4 Stage 2 Fan 4 Stage 3 Aux operation mode indication Alarm output, high ( and low ) Alarm output, low Binary: * Reverse: * On some LON tools the bits are named in the other direction, so take care 20

21 Optional output variables, continued nvodi nvodi All digital inputs SNVT_state_64 (64 bit) NV index: 53 Bits: Bit [0 63] Emergency stop Summer/winter changeover Alarm acknowledge Zone 1 External control Zone 2 External control Zone 3 External control Zone 4 External control Binary: * Reverse: * On some LON tools the bits are named in the other direction, so take care 21

22 Optional output variables, continued nvodi, cont. nvodi All digital inputs SNVT_state_64 (64 bit) NV index: 53 Bits: Bit [0 63] Binary: * Reverse: * On some LON tools the bits are named in the other direction, so take care 22

23 Optional output variables, continued nvoalarm nvoalarm All alarms SNVT_state_64 (64 bit) NV index: 56 Bits: Bit [0 63] Zone 1 Supply temperature Zone 1 Room/Return temperature Zone 1 Heating Frost Zone 1 External Set point Zone 1 Supply, Ret./ Room deviation Zone 1 Cooling Zone 1 Heating/ Electrical heating Zone 2 Supply temperature Zone 2 Room/Return temperature Zone 2 Heating Frost Zone 2 External Set point Zone 2 Supply, Ret./ Room deviation Zone 2 Cooling Zone 2 Heating/ Electrical heating Zone 3 Supply temperature Zone 3 Room/Return temperature Zone 3 Heating Frost Zone 3 External Set point Zone 3 Supply, Ret./ Room deviation Zone 3 Cooling Zone 3 Heating/ Electrical heating Zone 4 Supply temperature Zone 4 Room/Return temperature Zone 4 Heating Frost Zone 4 External Set point Zone 4 Supply, Ret./ Room deviation Zone 4 Cooling Zone 4 Heating/ Electrical heating Fan 1 Fan alarm Fan 1 Pressure/Flow/Deviation Fan 1 External set point Fan 2 Fan alarm Fan 2 Pressure/Flow/Deviation Fan 2 External set point Fan 3 Fan alarm Binary: * Reverse: * On some LON tools the bits are named in the other direction, so take care 23

24 Optional output variables, continued nvoalarm, cont. nvoalarm All alarms SNVT_state_64 (64 bit) NV index: 56 Bits: Bit [0 63] Fan 3 Pressure/Flow/Deviation Fan 3 External set point Fan 4 Fan alarm Fan 4 Pressure/Flow/Deviation Fan 4 External set point Outside temperature Manual control Communication test Modbus master Binary: * Reverse: * On some LON tools the bits are named in the other direction, so take care 24

25 3.6 Configuration parameters Introduction The LON module's Neuron application supports 62 network variables. 4 3 of these must be used as configuration parameters as described below. ncimaxsndtime ncimaxsndtime Send heartbeat Max. time an output variable has to be sent even if there hasn't changed anything. SNVT_time_sec NV index: 58 ncimaxrcvtime ncimaxrcvtime Receive heartbeat Max. time an input variable has to be received. If it wasn't received during this time the value of this input variable is invalid. SNVT_time_sec NV index: 59 ncistartupdelay ncistartupdelay SNVT_time_sec NV index: 60 25

26 4 Appendix 4.1 Description of SNVTs You can find current descriptions of SNVTs (Standard Network Variable Types) used in set ClimatixAHU V1.x per Section 2.1, on the homepage of "LonMark International" at: "LONMARK Resource Files, version XX.XX" 26

27 We Bring Air to Life FWG Climatix GB Copyright 2011 Fläkt Woods Group Fläkt Woods is a global leader in air management. We specialise in the design and manufacture of a wide range of air climate and air movement solutions. And our collective experience is unrivalled. Our constant aim is to provide systems that precisely deliver required function and performance, as well as maximise energy efficiency. Solutions for all your air climate and air movement needs Fläkt Woods is providing solutions for ventilation and air climate for buildings as well as fan solutions for Industry and Infrastructure. Air Handling Units (AHUs) Modular, compact and small AHU units. Designed to ensure optimisation of indoor air quality, operational performance and service life. Air Terminal Devices and Ducts Supply and exhaust diffusers and valves for installation on walls, ceiling or floor are all included in our large range and fit all types of applications. Chilled Beams Active induction beams for ventilation, cooling and heating, and passive convection beams for cooling. For suspended or flushmounted ceiling installation and multiservice configuration. With unique Comfort Control and Flow Pattern Control features. Residential ventilation A complete range of products for residential ventilation. Consists of ventilation units, exhaust air fans and cooker hoods designed to optimise indoor comfort and save energy. Fläkt Woods Group SA 18, avenue Louis Casaï, CH1209 Geneva, Switzerland Tel info@flaktwoods.com See global web site for international sales offices Fans Advanced axial, centrifugal and boxed fans for general and specialist applications. Comprehensive range including high temperature and ATEX compliant options. Engineered for energy efficiency andminimised life cycle cost. Chillers Aircooled and watercooled chillers with cooling capacity up to 1800 kw. Designed tominimise annual energy consumption in all types of buildings. Controls and drives Variable speed drives and control systems, all tested to ensure total compatibility with our products. Specialist team can advise on energy saving and overall systemintegration.

Climatix LON communication with POL SNVTs for Twin Wheel application v1.x

Climatix LON communication with POL SNVTs for Twin Wheel application v1.x Climatix SNVTs for Twin Wheel application v1.x Table of contents 1 About this document...3 1.1 Revision history...3 1.2 Before you start...3 1.3 Reference documents...3 2 Application...4 2.1 General information...4

More information

Climatix Basic reference addresses for eq Fläkt application v1.x

Climatix Basic reference addresses for eq Fläkt application v1.x Climatix Basic reference addresses for eq Fläkt application v1.x Modbus communication, slave mode Table of contents 1 About this document...3 1.1 Revision history...3 1.2 Before you start...3 1.3 Reference

More information

Unit heater with accessories

Unit heater with accessories LVD Unit Heater Unit heater with accessories The type LVDV fan-assisted unit heaters are designed for space heating in shop entrances, lobbies, doorways, warehouses and workshops, garages and similar premises.

More information

Smoke Control Ducts and Dampers For Single Compartment Applications. Fulfilling new requirements for EN product standards for CE Marking

Smoke Control Ducts and Dampers For Single Compartment Applications. Fulfilling new requirements for EN product standards for CE Marking Smoke Control Ducts and Dampers For Single Compartment Applications Fulfilling new requirements for EN product standards for CE Marking New Smoke Control Product Range Fläkt Woods Smoke Control Ducts and

More information

ClimaFläkt. Chillers and condensing units

ClimaFläkt. Chillers and condensing units ClimaFläkt Chillers and condensing units Cooling Solutions Even the most efficient systems require addition of heating and cooling. For such needs Fläkt Woods provides thermodynamic solutions from 6 to

More information

EU Air Handling Units with SEMCO EXCLU-SIEVE

EU Air Handling Units with SEMCO EXCLU-SIEVE EU Air Handling Units with SEMCO EXCLU-SIEVE The acquisition of US based Semco has given us the opportunity to include a new range of rotary heat exchangers in our EU air handling unit range. Hygienic

More information

Smoke extract fan SMHA HATCH

Smoke extract fan SMHA HATCH 12.11.2012 Contents Product overview... 3 Construction... 4 Specification... 5 Selection... 6 Installation... 7 Electrical connections... 8 Dimensions and weights... 9 Product code and accessories... 10

More information

PFS Single stage axial fan The axial fan for modern boiler plants

PFS Single stage axial fan The axial fan for modern boiler plants PFS Single stage axial fan The axial fan for modern boiler plants This large axial fan, type PFS- 400-236, was installed in 1987 at the Salmisaari coal-fired power station in Helsinki, Finland. The photo

More information

Smoke Master SMIA Compact pressurisation and smoke exhaust system

Smoke Master SMIA Compact pressurisation and smoke exhaust system Smoke Master SMIA Compact pressurisation and smoke exhaust system Fläkt Woods FIFLO EN 2009.09 2 All rights reserved. Contents System overview... 4 Design and operation... 5 Technical specification...

More information

Smoke Master SMPA Compact pressurisation system

Smoke Master SMPA Compact pressurisation system Smoke Master SMPA Compact pressurisation system Fläkt Woods FILO E 2009.07 2 All rights reserved. Contents System overview...4 Design and operation...5 Technical specification...6 Electric and control

More information

Data Aire DAP TM III. LonWorks Protocol Integration Information

Data Aire DAP TM III. LonWorks Protocol Integration Information Data Aire DAP TM III LonWorks Protocol Integration Information Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-685 June 2009 Revision 1.0 Document 600-000-685

More information

Data Aire DAP TM III. LonWorks Protocol Integration Information

Data Aire DAP TM III. LonWorks Protocol Integration Information Data Aire DAP TM III LonWorks Protocol Integration Information Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-685 Feb 2011 Revision 2.0 Table of Contents 1 Introduction...

More information

Document # R00

Document # R00 Viconics VT7200 Series PIR Ready Zoning Thermostats General The VT7200 series PIR Ready low-voltage microprocessor-based zoning thermostats have been specifically designed to control either 0-10Vdc, staged,

More information

MODBUS RS485. » Technical instructions. Air Comfort. Housing ventilation

MODBUS RS485. » Technical instructions. Air Comfort. Housing ventilation Air Comfort Air Treatment Housing ventilation MODBUS RS485» Technical instructions 2 Modbus RS485 Technical instructions Description, Connections, Presentation, decimals Description RS485 has two connections,

More information

Network Variables for Model CM4 LONWORKS Protocol Version 1.2

Network Variables for Model CM4 LONWORKS Protocol Version 1.2 Zellweger Analytics, Inc. 405 Barclay Boulevard Lincolnshire, IL 60069 USA Tel: 847-955-8200 Fax: 847-955-8208 Toll-free: 800-323-2000 Technical Note Network Variables for Model CM4 LONWORKS Protocol Version

More information

The New Sorption Rotary Heat Exchanger

The New Sorption Rotary Heat Exchanger The New Sorption Rotary Heat Exchanger Two of the most important factors affecting indoor air climate are the air temperature and the humidity but achieving comfort conditions can be very expensive. Our

More information

Climatix. BACnet/IP communication with POL Objects for standard IV Produkt EHP application v3.02.xx

Climatix. BACnet/IP communication with POL Objects for standard IV Produkt EHP application v3.02.xx Climatix BACnet/IP communication with POL908.00 s for standard IV Produkt EHP application v3.02.xx 2 / 20 BACnet/IP communication with POL908.00 CAB120910.02.EN Y3963en/20130610 Table of contents 1 About

More information

DESCRIPTION NOTE. Temperature and Humidity Sensors MODEL 1260B

DESCRIPTION NOTE. Temperature and Humidity Sensors MODEL 1260B Wall mount/indoor transmitter for temperature, relative humidity and two dry contact inputs. Dual dry-contact inputs allow integration of light switches, motion and occupancy sensors in any combination.

More information

DIF-OT Ceiling Filter. The optimized laminar airflow

DIF-OT Ceiling Filter. The optimized laminar airflow DIF-OT Ceiling Filter The optimized laminar airflow When hygiene is crucial The operating room is the most critical zone of the hospital. The operating theatre must be a clean room to protect the patient.

More information

recooler HP EQKR HEAT PUMP

recooler HP EQKR HEAT PUMP AIR COMFORT AIR TREATMENT 9566 GB 2016.03.17 recooler HP EQKR HEAT PUMP» TECHNICAL CATALOGUE 2 ReCooler HP EQKR Technical Catalogue Content ReCOOLER HP EQKR HEAT PUMP 3 product presentation. 3 applications.

More information

TopMaster Air Handling unit. Installation instructions

TopMaster Air Handling unit. Installation instructions Installation instructions Safety Instructions Operation of Air Handling units and accessories WARNING Installation may only be carried out by qualified personnel. Before taking the air handling unit into

More information

Smoke Master SMPA Installation, operation and maintenance

Smoke Master SMPA Installation, operation and maintenance 19.11.2009 Contents Contents...2 Safety aspects...3 System overview...4 Installation...5 Installation of the fan unit...5 Electric installations...7 Stairwell smoke detectors...7 Relay unit for smoke detectors...7

More information

iq Star by Fläkt Woods Multi-service Chilled Beam Guide Star by Fläkt Woods

iq Star by Fläkt Woods Multi-service Chilled Beam Guide Star by Fläkt Woods Star by Fläkt Woods iq Star by Fläkt Woods Multi-service Chilled Beam Guide The right cooling at the right time. Purposeful and energy efficient. The modern office is dynamic. With laptops and mobiles

More information

Product Data. Voyager TM Rooftop air conditioner or heat pump unit with LonTalk communication interface for Voyager TM rooftop controls

Product Data. Voyager TM Rooftop air conditioner or heat pump unit with LonTalk communication interface for Voyager TM rooftop controls Voyager TM Rooftop air conditioner or heat pump unit with LonTalk communication interface for Voyager TM rooftop controls LonTalk Communication Interface April 2002 Overview Each Voyager rooftop air conditioner

More information

OWNER S MANUAL FreeWay. LiteConnector Lon FTT-10 LonWorks -gateway for Exvent AC-series

OWNER S MANUAL FreeWay. LiteConnector Lon FTT-10 LonWorks -gateway for Exvent AC-series OWNER S MANUAL FreeWay LiteConnector Lon FTT-10 LonWorks -gateway for Exvent AC-series Pajatie 8 06150 PORVOO Tel +358 19 529 700 Fax +358 19 529 7044 www.exvent.fi 2004_1 Table of contents TABLE OF CONTENTS...

More information

Tracer Controls. Tracer ZN.520: Unit Controller for Terminal Products TD-PRM001-EN

Tracer Controls. Tracer ZN.520: Unit Controller for Terminal Products TD-PRM001-EN Tracer Controls Tracer ZN.520: Unit Controller for Terminal Products TD-PRM001-EN 2 TD-PRM001-EN General Tracer ZN.520 unit controller is a microprocessor-based direct digital controller that controls

More information

DESCRIPTION MODEL 1205/1205HA NOTE

DESCRIPTION MODEL 1205/1205HA NOTE Integrated Temperature, Relative Humidity and Dew Point Transmitter. Housed in a rugged stainless steel body offering excellent corrosion protection. RH Accuracy at 25 C:: Model 1205 2% typical / 3% maximum;

More information

TopMaster Air Handling unit. Technical data

TopMaster Air Handling unit. Technical data Technical data Contents Page Description of the unit... 3 Design... 4 Technical data Size 030... 5 Size 0... 6 Accessories... 7 Controls... 9 Control functions... 10 Order codes... 11 Fläkt Woods 8180

More information

Fire Damper Interface (24V)

Fire Damper Interface (24V) Always READ this document BEFORE INSTALLATION. Please Retain for future reference. This product forms part of a life safety system. Failure to correctly store, handle, install and maintain the product

More information

Fire Damper Interface (230V)

Fire Damper Interface (230V) Always READ this document BEFORE INSTALLATION. Please Retain for future reference. This product forms part of a life safety system. Failure to correctly store, handle, install and maintain the product

More information

Smoke Fire Damper Interface (230V)

Smoke Fire Damper Interface (230V) Always READ this document BEFORE INSTALLATION. Please Retain for future reference. This product forms part of a life safety system. Failure to correctly store, handle, install and maintain the product

More information

Smoke Damper Interface (230V)

Smoke Damper Interface (230V) Always READ this document BEFORE INSTALLATION. Please Retain for future reference. This product forms part of a life safety system. Failure to correctly store, handle, install and maintain the product

More information

Ventilation Solutions Product Range > Box Fans

Ventilation Solutions Product Range > Box Fans Ventilation Solutions Product Range > Box Fans 1 Fläkt Woods Box Fans: A full-blown range of fans fulfilling every requirement from square one on. Fläkt Woods offers the widest range of fans in the market.

More information

IPSUM OPTIMIZATION SYSTEM» DEMAND CONTROLLED VENTILATION OVERVIEW

IPSUM OPTIMIZATION SYSTEM» DEMAND CONTROLLED VENTILATION OVERVIEW AIR COMFORT AIR MANAGEMENT IPSUM IPSUM OPTIMIZATION SYSTEM» DEMAND CONTROLLED VENTILATION OVERVIEW IPSUM SYSTEM OPTIMIZER IPSUM SYSTEM ROUTER IPSUM CONNECTION UNIT IPSUM from Fläkt Woods a giant step forward!

More information

GOLD_E_LonWorks_140611

GOLD_E_LonWorks_140611 FUNCTIONAL PROFILE: GOLDen GATE Lonworks FTT-10, TBLZ-3-1-1-41, Version 1.00 GOLD RX/PX/CX/SD, GENERATION E Applicable to program version 1.10 and newer versions Specifications are subject to alteration

More information

eq PRIME » ENERGY EFFICIENCY AND FLEXIBILITY STRAIGHT OUT OF THE BOX AIR COMFORT AIR TREATMENT AIR HANDLING UNITS

eq PRIME » ENERGY EFFICIENCY AND FLEXIBILITY STRAIGHT OUT OF THE BOX AIR COMFORT AIR TREATMENT AIR HANDLING UNITS AIR COMFORT AIR TREATMENT AIR HANDLING UNITS eq PRIME» ENERGY EFFICIENCY AND FLEXIBILITY STRAIGHT OUT OF THE BOX ENVIRONMENT ECONOMICAL EXPERTISE In its simplicity the e 3 captures what makes us attractive

More information

AIR TREATMENT. ReCOOLER HP» INTEGRATED COOLING/HEATING FUNCTION WITH REVERSIBLE HEAT PUMP IN THE eq AIR HANDLING UNIT

AIR TREATMENT. ReCOOLER HP» INTEGRATED COOLING/HEATING FUNCTION WITH REVERSIBLE HEAT PUMP IN THE eq AIR HANDLING UNIT AIR TREATMENT ReCOOLER HP ReCOOLER HP» INTEGRATED COOLING/HEATING FUNCTION WITH REVERSIBLE HEAT PUMP IN THE eq AIR HANDLING UNIT Energy efficiency the essence of our solutions All our research, development

More information

TopMaster Air Handling Unit

TopMaster Air Handling Unit TopMaster Air Handling Unit Contents Page Contents......................................2 Unit description................................3 Design........................................4 Technical Details

More information

MODBUS RS485 TECHNICAL INSTRUCTIONS

MODBUS RS485 TECHNICAL INSTRUCTIONS MODBUS RS485 TECHNICAL INSTRUCTIONS 2 Modbus RS485 - Technical instruction DESCRIPTION, CONNECTIONS, PRESENTATION, DECIMALS DESCRIPTION RS485 has two connections, A and B. Often there is also a protective

More information

Air Management for Food Applications

Air Management for Food Applications Air Management for Food Applications Specialised solutions to meet the challenging requirements of food production, storage and preparation Air quality has a direct impact on quality of food production,

More information

Applications Application is compatible with Q1 Hardware. Compatible with Heat Pump Unit equipment up to 4 stages of cooling or heating, analog or floating-point valves or digital stages, discharge pressure/variable

More information

Applications Application is compatible with Q1 Hardware. Compatible with Fan Coil Unit equipment up to 4 stages of cooling or heating, analog or floating-point valves or digital stages, discharge pressure/variable

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

Database for CTS6000 MODBUS

Database for CTS6000 MODBUS Database for CTS6000 MODBUS Valid for: LONcard SW1.7.4B, Variable List V2.02 Version 1.08-4, 01-05-2016 Contents Contents... 2 1. Installation... 3 1.1. Installation and operating instructions... 3 2.

More information

Climatix. BACnet/IP communication with POL Objects for standard IV Produkt EHP application v3.02.xx

Climatix. BACnet/IP communication with POL Objects for standard IV Produkt EHP application v3.02.xx Climatix BACnet/IP communication with POL908.00 s for standard IV Produkt EHP application v3.02.xx 2 / 28 BACnet/IP communication with POL908.00 CAB180109.03.EN Y3963en/20130610 Table of contents 1 About

More information

DX SYSTEM HEAT RECOVERY ENHANCED BY DEMAND CONTROLLED VENTILATION

DX SYSTEM HEAT RECOVERY ENHANCED BY DEMAND CONTROLLED VENTILATION DX SYSTEM HEAT RECOVERY ENHANCED BY DEMAND CONTROLLED VENTILATION 2 AERECO DX system DX SYSTEM A COMPLETELY NEW HEAT RECOVERY VENTILATION RANGE With the experience of a very innovative room-by-room demand

More information

Lonworks Damper Interface Catalogue

Lonworks Damper Interface Catalogue Lonworks Damper Interface catalogue Release: 1.9 AUGUST 2017 Lonworks Damper Interface Catalogue Two Position, Three Position & Hot Smoke Fire Damper Interface This product forms part of a life safety

More information

Installation Guide. Bacharach HGM300 to LonWorks FT-10 Communications Adapter

Installation Guide. Bacharach HGM300 to LonWorks FT-10 Communications Adapter 3015-4568 Revision 0 9/11/03 Installation Guide Bacharach HGM300 to LonWorks FT-10 Communications Adapter Introduction The Bacharach HGM300 to LonWorks Communications Adapter enables an HGM300 Refrigerant

More information

Integrated VarIable refrigerant flow ahu/pau (r410a)

Integrated VarIable refrigerant flow ahu/pau (r410a) Integrated Variable Refrigerant Flow AHU/PAU (R410A) CONTENTS Features of VRF AHU/PAU 2 WELAIRE i-gt Concept 9 VRF Outdoor Unit Performance Data 10 Drawings & Performance Data 12 Dimensions 13 Notes 14

More information

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include: Model Number: 8680-N2 Product/System Title: Room Pressure AOC Controller with N2 Communications Protocol Contents of this manual supplement include: 1) Sequence of Operation 2) Variable map 3) Description

More information

FUNCTIONAL DESIGN SPECIFICATION

FUNCTIONAL DESIGN SPECIFICATION Issue Date: Issued To: Revision: FUNCTIONAL DESIGN SPECIFICATION Specification Number: SP-XXXX Company Name Signature Date Issued By: Manutec Ltd. Approved By: Approved By: Approved By: Approved By: Authorised

More information

Premium Efficiency Heat Recovery Unit. D-AHU Modular L. Air Handling Units

Premium Efficiency Heat Recovery Unit. D-AHU Modular L. Air Handling Units Premium Efficiency Heat Recovery Unit D-AHU Modular L Air Handling Units About Daikin Our promise is to ensure that customers can depend on Daikin for the ultimate in comfort, so that they are free to

More information

GLEC exhaust FAN. Air Comfort. Air movement. Duct & Box Fans

GLEC exhaust FAN. Air Comfort. Air movement. Duct & Box Fans Air Comfort Air movement Duct & Box Fans GLEC exhaust FAN» Technical CATALOUGE Technical catalouge Exhaust Fan GLEC 2 Contents Exhaust fan - GLEC... 3 Performance Data...4 Fan chart-explanation and definitions...

More information

ReCooler Heat-Pump Energy efficient cooling unit for eq Air Handling Unit

ReCooler Heat-Pump Energy efficient cooling unit for eq Air Handling Unit ReCooler Heat-Pump Energy efficient cooling unit for eq Air Handling Unit 28 May 2013 Agenda Introduction to Fläkt Woods Our Product Solution Technical Features Benefits Fläkt Woods Index We save energy!

More information

Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2

Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2 Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2 john.woollett@swegon.se, jonas.akesson@swegon.se SUMMARY The main focus of the paper will be on active beam technology regarding

More information

Mounting and Operating Instructions EB 5610 EN. TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller

Mounting and Operating Instructions EB 5610 EN. TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller Mounting and Operating Instructions Electronics from SAMSON EB 5610 EN Firmware version 1.40 Edition December 2014 Controller

More information

VMX DEMAND CONTROLLED VENTILATION FOR NON RESIDENTIAL BUILDINGS

VMX DEMAND CONTROLLED VENTILATION FOR NON RESIDENTIAL BUILDINGS VMX DEMAND CONTROLLED VENTILATION FOR NON RESIDENTIAL BUILDINGS 2 AERECO VMX VMX, A UNIQUE SOLUTION TO RECONCILE AIR QUALITY AND ENERGY SAVINGS IN NON RESIDENTIAL BUILDINGS AERECO VMX 3 In developed countries,

More information

Job Name Control Systems Description Date

Job Name Control Systems Description Date Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In

More information

N M AirControl AHU. Control manual

N M AirControl AHU. Control manual N 10.63 M 03-2016 AirControl AHU Control manual EN CONTENTS PAGE 1 - MONITORING AND CONTROL 2 1.1 The program 2 1.2 The HMI terminal 2 1.3 The controller 4 1.4 Description of the air handling units 4

More information

MicroTech III Applied Air Handling Unit Controller Protocol Information

MicroTech III Applied Air Handling Unit Controller Protocol Information Engineering Data ED 15112-2 Group: Controls Part Number: ED 15112-2 Date: January 2009 Supersedes: ED 15112-1 MicroTech III Applied Air Handling Unit Controller Protocol Information Networks Networks 2009

More information

DAIKIN Air Handling Unit Modular

DAIKIN Air Handling Unit Modular DAIKIN Air Handling Unit Modular Compact ventilation unit with heat recovery Energy efficiency and air quality Daikin air handling units, with their plug-and-play design and inherent flexibility, can be

More information

Daikin Applied UK Technically better... D-AHU Modular R. Air handling units. Compact air handling unit with heat recovery wheel

Daikin Applied UK Technically better... D-AHU Modular R. Air handling units. Compact air handling unit with heat recovery wheel Daikin Applied UK Technically better... D-AHU Modular R Air handling units Compact air handling unit with heat recovery wheel Energy efficiency and air quality With their Plug & Play design and inherent

More information

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D CENTRIFLOW 3D Plug fan GMEC >> Installation and Maintenance air comfort CentriFlow 3D 2 Plug Fan CentriFlow 3D GMEC Installation and Maintenance Important Information, Safety notes, Technical Description

More information

Table of Contents. W2W Open

Table of Contents. W2W Open W2W Open Points and Properties CARRIER CORPORATION 2013 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-457-01 3/27/2013 Table of Contents Introduction... 1

More information

MicroTech Unit Ventilator

MicroTech Unit Ventilator Open Protocol Data Information Packet Version 2.2 Group: Controls Date: April 1996 MicroTech Unit Ventilator Open Protocol Data Communications 2002 McQuay International - C O N F I D E N T I A L - This

More information

MECHANICAL SERVICES 101. Ian White

MECHANICAL SERVICES 101. Ian White MECHANICAL SERVICES 101 Ian White Contents 1. Ventilation 2. Heat Gains & Losses 3. Heating Ventilation Air Conditioning (HVAC) Systems What are Building Services Building Services incorporate all aspects

More information

VAV CHILLED BEAMS Pi FUNCTION DESIGN GUIDE

VAV CHILLED BEAMS Pi FUNCTION DESIGN GUIDE VAV CHILLED BEAMS Pi FUNCTION DESIGN GUIDE 2 VAV Chilled beams with function - Design Guide CONTENT Dimensioning of VAV Chilled beam Function...3 Operation levels... 4 Heating...5 Dimensioning of chilled

More information

MARINE APPLICATIONS MARINE» PRODUCTS AND SOLUTIONS FOR MARINE APPLICATIONS

MARINE APPLICATIONS MARINE» PRODUCTS AND SOLUTIONS FOR MARINE APPLICATIONS MARINE APPLICATIONS MARINE» PRODUCTS AND SOLUTIONS FOR MARINE APPLICATIONS MEETING THE HIGHEST DEMANDS - EFFICIENT HVAC SOLUTIONS FOR ARCTICAL TO TROPICAL CONDITIONS AT FLÄKTGROUP WE WANT TO EXCEED the

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

SEMCO CHILLED BEAMS INDOOR AIR QUALITY AND ENERGY SAVINGS FANLESS FILTERLESS SPACE CONDITIONING

SEMCO CHILLED BEAMS INDOOR AIR QUALITY AND ENERGY SAVINGS FANLESS FILTERLESS SPACE CONDITIONING FANLESS FILTERLESS SPACE CONDITIONING SEMCO CHILLED BEAMS INDOOR AIR QUALITY AND ENERGY SAVINGS IQHC Active Chilled Beam An intelligently designed active chilled beam that has the highest industry cooling

More information

ROOM-BY-ROOM DEMAND CONTROLLED HEAT RECOVERY VENTILATION

ROOM-BY-ROOM DEMAND CONTROLLED HEAT RECOVERY VENTILATION ROOM-BY-ROOM DEMAND CONTROLLED HEAT RECOVERY VENTILATION 2 AERECO Room-by-room demand controlled heat recovery ventilation REVOLUTION IN THE WORLD OF HEAT RECOVERY VENTILATION Through its new ventilation

More information

Corrigo E Ventilation

Corrigo E Ventilation Corrigo E Ventilation Modbus communication guide Contains the most commonly used variables. Covers all versions of Corrigo E Ventilation from 3.2 The challenger in building automation Revision: 2 Date:

More information

ROOM THERMOSTATS KNX BASIC DOCUMENTATION

ROOM THERMOSTATS KNX BASIC DOCUMENTATION ROOM THERMOSTATS KNX BASIC DOCUMENTATION Contents 2 2 2 2 ABOUT THIS DOCUMENT Document use / request to the reader Target audience, prerequisites Glossary 59 59 60 62 63 HANDLING Mounting and installation

More information

Demand-controlled Ventilation Leading edge products for demand-controlled ventilation

Demand-controlled Ventilation Leading edge products for demand-controlled ventilation Overview Demand-controlled Ventilation Leading edge products for demand-controlled ventilation Demand-controlled ventilation offers great comfort and low operating costs When the room is in use, ventilation

More information

Modbus RTU RS485 Manual

Modbus RTU RS485 Manual Modbus RTU RS485 Manual AUTOMATED FUEL MAINTENANCE SYSTEMS FTI-5A, FTI-10A, FTI-20A FUEL TECHNOLOGIES INTERNATIONAL 06/10/2014 Rev B - Fuel Technologies - Modbus The Modbus Communications Setup Button

More information

4 in 1 Digital Thermostat Control

4 in 1 Digital Thermostat Control 4 in 1 Digital Thermostat Control Models: VS10W and VS10B INSTALLER / USER MANUAL Contents Contents Box contents Introduction Product Compliance System options overview Installation Parameter Settings

More information

FORM EG2 (502) FlexSys Configured Packaged Rooftop Air Conditioning Units

FORM EG2 (502) FlexSys Configured Packaged Rooftop Air Conditioning Units FORM 100.50-EG2 (502) TM FlexSys Configured Packaged Rooftop Air Conditioning Units TABLE OF CONTENTS PAGE TOTAL INTEGRATED HVAC SYSTEM... 3 AN INTEGRATED SOLUTION... 4 INTRODUCTION... 6 System Description...

More information

Tebis application software

Tebis application software 5 Tebis application software STCC530E 2-channel presence detector 360 A faire Product reference Description TP device RF devices TCC530E Bi-zone presence detector TCC530E Output module: Dimmer Loads connected

More information

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection. Volume 5, Issue 1 CARRIER edesign SUITE NEWS Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC Equipment Selection A design challenge sometimes occurs when computing design loads using

More information

Contents. Box contents: JGSTAT2B (Black) Fixing screws (White) Icons used in this manual:

Contents. Box contents: JGSTAT2B (Black) Fixing screws (White) Icons used in this manual: Contents Box contents: Instruction Manual Instruction manual: Box contents Introduction Product compliance System options overview Installation Parameter settings Error codes User guide Installers notes

More information

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

Technical Report #3 Mechanical Systems Existing Conditions Evaluation Mechanical Option Technical Report #3 Technical Report #3 Mechanical Systems Existing Conditions Evaluation Instructor: Dr. Bahnfleth 11.15.04 Building Sponsor: CCG Facilities Integration Table of Contents

More information

Description of the functions, IQlogic

Description of the functions, IQlogic , IQlogic General Control...168 Status...168 IQnavigator hand-held terminal and image management...169 Dashboard...169 Main setup...170 Air flow Regulation mode...171 Boost...171 Unit...171 Air adjustment...171

More information

Manual for the integration in BMS/GTC

Manual for the integration in BMS/GTC Manual for the integration in BMS/GTC Communication parameters MODBUS RTU and BACNET COMMUNICATION UTBS PRO-REG Software Version 3.6 EN ÍNDEX 1. GENERALITIES...2 1.1. Introduction...2 1.2. signals types...2

More information

Corp L (Supersedes 02/2008)

Corp L (Supersedes 02/2008) Service Literature Corp. 0627L5 0608 (Supersedes 02/2008) IMC LonTalk Module GENERAL The IMC LonTalk module allows communication between the Lennox IMC M17 (version 5.02 and higher) or M18 controller and

More information

2013 innovation. Room-by-room demand controlled heat recovery ventilation

2013 innovation. Room-by-room demand controlled heat recovery ventilation 2013 innovation Room-by-room demand controlled heat recovery ventilation 2 Revolution in the world of heat recovery ventilation Through its new ventilation system, which combines heat recovery and room-by-room

More information

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems X X testregistrierung Type Web server, also for mobile devices Zone modules Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems X-AIRCONTROL zone

More information

Modbus TCP Register List GreenManager for GreenMaster C-F Valid for firmware version 2.0 or later

Modbus TCP Register List GreenManager for GreenMaster C-F Valid for firmware version 2.0 or later Modbus TCP Register List GreenManager for GreenMaster C-F Valid for firmware version 2.0 or later Overview Modbus can access single adresses or multiple addresses simultaneously; either reading or writing

More information

P/N f. HomeWorks QS Palladiom Thermostat Configuration Guide

P/N f. HomeWorks QS Palladiom Thermostat Configuration Guide HomeWorks QS Palladiom Thermostat Configuration Guide Table of Contents Description...4 Step : Identify the HVAC Equipment and Confirm Device Installation...5 Identify the HVAC Equipment...5 Confirm Device

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483586 Microprocessor Controller for Dedicated Outdoor Air System Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before

More information

Ice Rink (Single and Dual Configurations) Custom Control Features

Ice Rink (Single and Dual Configurations) Custom Control Features & M&M Refrigeration, Inc. Computer Control System Ice Rink (Single and Dual Configurations) Custom Control Features REVISION DATE DESCRIPTION - 4/20/05 Original release. A 09/21/98 Update Chiller Pump

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

ENERGY EFFICIENCY WITH SUPERIOR INDOOR AIR QUALITY

ENERGY EFFICIENCY WITH SUPERIOR INDOOR AIR QUALITY SUPERIOR IAQ LOW FIRST COST BEST ROI ENERGY EFFICIENCY WITH SUPERIOR INDOOR AIR QUALITY Pinnacle manages 100% of a building s ventilation and indoor humidity load in a single package. Chilled beams have

More information

Operation Manual. Programmable Logic Controller

Operation Manual. Programmable Logic Controller Operation Manual Programmable Logic Controller Part No. 9983-0000-E01 / January 2018 OPERATION MANUAL TABLE OF CONTENTS CUSTOMER SERVICE 3 CONTACT INFORMATION 3 ORDER INFORMATION 3 INTRODUCTION 4 THE PROCESS

More information

MicroTech Rooftop/RMC

MicroTech Rooftop/RMC Open Protocol Data Communications Packet Version 4.1 Group: Controls Date: March 1999 MicroTech Rooftop/RMC Data Information Packet for Open Protocol 1999 McQuay International Revision History Version

More information

Netbiter Tank Sensor

Netbiter Tank Sensor For Netbiter Tank Sensor HMS Industrial Networks AB Post address: Box 4126 300 04 Halmstad SWEDEN Visitor s address: Stationsgatan 37 302 45 Halmstad SWEDEN Telephone: + 46 35 17 29 00 Fax: + 46 35 17

More information

eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction

eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction Air Comfort Air Treatment Energy Recovery eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction eco PREMIUM - Technical Instruction REDA 2 Contents Description Applications... 3 Quality & environment...

More information

200i/KN2, KN4 Firmware Revision Sheet

200i/KN2, KN4 Firmware Revision Sheet 200i/KN2, KN4 Firmware Revision Sheet Revision 2.9 Special Release 1- November 2013 1. Added an external boiler Failsafe feature. The J6 Analog Output can be used to enable a SSR which can be used to enable

More information

Aircooled Units. AirPLUS Aircooled scroll chiller. Freecooling options: liquid control. Freecooling options: fans control. Noise \\ Efficiency options

Aircooled Units. AirPLUS Aircooled scroll chiller. Freecooling options: liquid control. Freecooling options: fans control. Noise \\ Efficiency options 2017 Products Foreword Felzer is one of the Scandinavian & BS leading providers of heating, ventilation, air conditioning and refrigeration solutions for industrial, commercial and residential applications.

More information

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN April 2005 CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-538-01 2/8/2017 Verify that you have the most current version of this document

More information