TopMaster Air Handling unit. Installation instructions

Size: px
Start display at page:

Download "TopMaster Air Handling unit. Installation instructions"

Transcription

1 Installation instructions

2 Safety Instructions Operation of Air Handling units and accessories WARNING Installation may only be carried out by qualified personnel. Before taking the air handling unit into operation fit any unused connections with protective mesh. In addition, all electrotechnical and mechanical safety devices must be installed before taking the air handling unit into operation. Before opening the unit check that its power has been disconnected. Take care when opening the isolating valves for the hot water to the air heater. There is a risk of water hammer or steam discharge. When servicing or inspecting the unit, switch off the main circuit breaker before opening the inspection doors. Reset all safety devices before restarting. The clearance in front of electric heaters and electrical cabinets shall conform to applicable electrical safety regulations. Use the control panel to stop the unit. The unit's hatches are fitted with locking handles. Ensure that the unit is always left locked, and that the keys cannot be accessed by unauthorized persons. Do not open inspection hatches when the unit is in operation. Fläkt Woods 8216 GB Subject to change without notice

3 Description of the unit Component parts The unit can be supplied in left-hand or right-hand configurations. Refer to the order code in Technical data. Heat recovery unit RDTO-aaa-b-c-d-e Connection (b) 1 = supply air right 2 = supply air left 1. Supply air fan 2. Extract air fan 3. Supply air filter 4. Extract air filter 5. Rotary heat exchanger 6. EC motor 7. Termination blocks for electric power and sensors 8. Control equipment 9. Heat recovery drive motor 10. Post-heating coil Components Left-hand configuration Fan The unit has two direct drive centrifugal fans. These fans are driven by EC motors. Rotary heat recovery unit The speed controlled rotor is fitted with a purge sector and rotation sensor. NOTE! The duct system and components must not weigh down the unit. Duct connection The unit has round duct connections with rubber seals. The distance between fan outlet/damper and air treatment components such as coils and silencers must fulfill the following: - Silencer, min 300mm - Cooling coil, min 600mm (must be mounted for a horizontal airflow) Technical data Electrical cabinet connection Right-hand configuration Size Electrical cabinet connection* 3 x 400 V, 50 Hz Motor 0.37 kw 0.80 kw EC motor IP 54 Unit fuse protection 10 A 16 A *Can also be connected to 1x230 V for a unit with a water coil. Connect electric power to the unit through the junction box on the top of the unit. The unit is supplied with 3 x 400 V (or 1 x 230 V with a water coil). The power supply cable shall be provided with an external switch disconnector. Weight Size 030 = 170 kg Size 050 = 175 kg NOTE! The cooling coil must be mounted for a horizontal air flow Fläkt Woods 8216 GB Subject to change without notice

4 Transport and installation Transport Transport the unit using a fork lift truck, pallet truck or platform trolley. Erection The unit can be mounted directly onto the surface if this is flat and horizontal. Use adjustable feet to make level the unit, these are available as accessories RDTZ Adjustable foot mm. Space requirement, etc. Size A B C D A = Unit width B = Filter replacement C = Inspection hatch D = Hatch for the control equipment Space requirements The space around the unit must be planned to take into account routine service work, such as replacing filters and cleaning the fan and casing. There should be a service aisle in front of the electrical cabinet with a width in accordance with applicable laws. The future replacement of the unit's components should also be taken into consideration. The planning of this work is a condition that must be fulfilled to make the CE marking of the installation possible. The unit must be positioned or arranged to facilitate the service of the electrical cabinet. Sound transmission When a unit is positioned next to a wall, low frequency sound can generate vibrations in the wall, even when the sound level from the fan room is acceptable. Generally the unit should be positioned against that wall in the fan room bordering a space that is not noise sensitive. When this is not possible the unit should be positioned mm from the wall. Duct lead-throughs must be designed with care so that rigid connections between the duct and wall do not occur. In addition, the seal around the duct must be carefully installed to prevent the transmission of sound to adjacent areas. For sensitive installations it may be a good idea to connect ducts using flexible connections. If the mass and rigidity of the floor are inadequate it can transmit sound in a similar manner. If the floor structure is light it can be improved using a heavy insulating mat under the entire surface area of the unit. The entire underside of the unit should rest on the mat, which can be fitted with a board to cover it. Fläkt Woods 8216 GB Subject to change without notice

5 Commissioning Connecting electrical components Read the instructions for the controls before connecting the unit to the electrical grid and taking it into operation. The unit has a fan with forward curved blades and must not be operated without being connected to the duct system. Connect components to terminal blocks in the electrical cabinet. There is a detailed description of this in a separate document: TopMaster - Control equipment. During commissioning the current date and time, along with the required setpoints and operating times, must be set using the Curo Touch control panel, See separate instructions. Mains connection Connect the incoming supply through an external switch disconnector located close to the unit. A size 030 unit is to have a 10 AT external fuse and a size 050 unit a 16 AT fuse. Connect the incoming supply to terminal block group L1, L2, L3, N and earth in the electrical cabinet. Secure the cable to the mounting rail using cable ties before refitting the electrical cabinet cover. Fläkt Woods 8216 GB Subject to change without notice

6 Performance testing Starting the unit Starting the unit for inspection After the connection of mains voltage and external control components, the unit is ready to be taken into operation in order to test its connections. 1. Turn the external switch disconnector to 1 (ON). 2. Start the unit. See separate instructions TopMaster Control equipment Dampers Check that the damper opens and closes correctly. Control valve Check that the control valve on the air heater/air cooler is working correctly. The direction of rotation of the rotating heat exchanger Check that the direction of rotation corresponds to the alternatives below. If not see the wiring diagram. Left-hand configuration: The rotor should rotate to the left as viewed from the front. The measuring pressure, Dp m, which is the difference between the pressure in the empty section at the fan inlet and the pressure inside the inlet cone. If exterior airflow display is requested a manometer (RDTZ-06) for flow rate display can be connected. A meauring pressure is obtained on the manometer pressure scale and is used as a reference for the monitoring of the plant. Hoses with 4 mm diameter is mounted between the nipples on the top of the unit andmanometer, see Fig. 1. Positive to positive and negative to negative. If the unit is supplied with flow control the air flow can be read off directly from the control panel. NOTE! Where the unit is supplied with flow control the test socket is used for the pressure sensor Temperature correction The flow scale on the display instrument and flow formula above apply to air at a temperature of +20 C. At other air temperatures the flow must be corrected using the equation: Right-hand configuration: The rotor should rotate to the right as viewed from the front. Air flow measurement The TopMaster has measuring nipples for air flow measurement. Using a measuring pressure Dp (Pa) and a constant (k) the air flow q (l/s) can be calculated using the following equation: q = 1000 x Dp k m The value of constant (k) is shown in the Table below. Size k-value extract air fan k-value supply air fan q = the actual flow through the fan q 20 = the flow reading t = current temperature in C Filter, final pressure drop The final pressure drop for the filter according to the table below, i.e. the pressure drop at which the filter cassette should be replaced, is 100 Pa above the pressure drop for a clean filter. Final pressure drop across the filter Size 030 Air flow m 3 /s Supply air Extract air Size 050 Air flow m 3 /s Supply air Extract air Pressure switch p Fig. 1. Location of measuring nipples on the unit. Where a pressure switch is used it must be set for the final pressure drop specified above. Where there is pressure regulation the pressure switch should be set for a pressure drop of +50Pa. Fläkt Woods 8216 GB Subject to change without notice

7 Performance testing Air heater, water Pipe connections The pipes to the heating coil are connected inside the unit in such a way that they do not prevent the disassembly of the fan. See the figures below. Draining Drain the unit through the pipe system. Fins Any deformed fins can be adjusted using fin comb EQAZ-14. Supply TF air fan WARNING! Wear protective gloves when work is being carried out using a fin comb Venting Vent the heat exchanger through the pipe system. WARNING! Warning - hot water! Remedial measures if there is a risk of freezing If the water freezes in a heat exchanger it will burst. This means that water will run out of the system and cause water damage. There is a risk of freezing in ventilation systems at low outdoor temperatures in the following cases: 1. The temperature of the heating medium is too high. There is a particular risk of freezing in the autumn and spring. Adjust the water temperature to the outdoor air temperature. 2. Oversized finned heat exchanger. Lower the water temperature to increase the water flow. 3. The heat supply ceases or decreases. If the supply of heat to the air heater can be expected to cease or decrease significantly, the outdoor air intake must be closed properly and all fans must be stopped. NOTE! Frost protection must not be set to so low a temperature that there is a risk of freezing. If the building is to be left unheated for long periods over the winter, the water must be drained from both the pipework and heat exchanger. Frost protection sensor Contact sensors are fitted to the return line. Apply heat conducting paste between the pipe and sensor to provide good contact between them. Important! When installing an air heater, in which the heating medium is water at a temperature above 100 C, take great care when opening vent cocks and shutoff valves in the system. Serious injuries can be caused by water hammer or steam discharge. Fläkt Woods AB takes no responsibility for the connection of air heaters to the heating system, nor for damage or injury caused by the incorrect planning, installation or maintenance of this system. Pipework and valves etc. are to be designed to take account of pressure drop and function, not the dimensions of the air heater connections. Route the pipes so that their weight does not subject the air heater to load. The air heater must not be subject to the expansion force of the heating system Fläkt Woods 8216 GB Subject to change without notice

8 We Bring Air to Life Fläkt Woods is a global leader in air management. We specialize in the design and manufacture of a wide range of air climate and air movement solutions. Our collective experience is unrivalled. We are constantly aiming to provide systems that precisely deliver required function and performance as well as maximum energy efficiency. FWG_TopMaster_Installation_EN_ _8216 Copyright 2014 Fläkt Woods Group Condesign_ABS5953 Fläkt Woods Group SA 18, avenue Louis Casaï, CH-1209 Geneva, Switzerland Tel info@flaktwoods.com See global website for international sales offices

TopMaster Air Handling unit. Technical data

TopMaster Air Handling unit. Technical data Technical data Contents Page Description of the unit... 3 Design... 4 Technical data Size 030... 5 Size 0... 6 Accessories... 7 Controls... 9 Control functions... 10 Order codes... 11 Fläkt Woods 8180

More information

TopMaster Air Handling Unit

TopMaster Air Handling Unit TopMaster Air Handling Unit Contents Page Contents......................................2 Unit description................................3 Design........................................4 Technical Details

More information

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D CENTRIFLOW 3D Plug fan GMEC >> Installation and Maintenance air comfort CentriFlow 3D 2 Plug Fan CentriFlow 3D GMEC Installation and Maintenance Important Information, Safety notes, Technical Description

More information

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes 50-120 1 General The heat exchanger control system is a control system for 380 W step motors

More information

Unit heater with accessories

Unit heater with accessories LVD Unit Heater Unit heater with accessories The type LVDV fan-assisted unit heaters are designed for space heating in shop entrances, lobbies, doorways, warehouses and workshops, garages and similar premises.

More information

LQE(E,G,S) Air heater for hot water

LQE(E,G,S) Air heater for hot water Fig. CAUTION! Use a pipe wrench to restrain the pipe connections of the heat exchanger when tightening the external pipe connections. LQE air heaters Connections to the pipework should be made by the pipework

More information

GLEB. >> Installation and Maintenance. Air Comfort. Air movement. Duct & Box Fans

GLEB. >> Installation and Maintenance. Air Comfort. Air movement. Duct & Box Fans Air Comfort Air movement Duct & Box Fans GLEB KITCHEN exhaust FAN >> Installation and Maintenance Kitchen Exhaust Fan GLEB Installation and Maintenance Important Information, Safety notes, Technical Description

More information

Supply air unit VEKA Installation & Maintenance

Supply air unit VEKA Installation & Maintenance November 2008 Safety instructions Operating the air treatment unit and accessory components WARNING Before the air treatment unit is taken into service, any free connections must be provided with protective

More information

PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN » INSTALLATION AND MAINTENANCE INSTRUCTIONS

PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN » INSTALLATION AND MAINTENANCE INSTRUCTIONS AIR COMFORT AIR TREATMENT 9933 GB 2016.05.25 PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN» INSTALLATION AND MAINTENANCE INSTRUCTIONS contents Page Installation options...... 2 Checks to be

More information

GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES GENERAL INSTRUCTION

GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES GENERAL INSTRUCTION GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES Using the air handling unit... Free space for service and repair work... GENERAL INSTRUCTION Checking prior to commissioning...3

More information

eco TOP INSTALLATION AND MAINTENANCE MANUAL

eco TOP INSTALLATION AND MAINTENANCE MANUAL eco TOP INSTALLATION AND MAINTENANCE MANUAL 2 eco TOP - Installation and Maintenance Manual CONTENTS Page 1. SAFETY INSTRUCTIONS...3 VDI 6022...3 2. DESCRIPTION OG THE UNIT...4 3. TRANSPORT AND PLACEMENT...5

More information

Ventilation Solutions Product Range > Box Fans

Ventilation Solutions Product Range > Box Fans Ventilation Solutions Product Range > Box Fans 1 Fläkt Woods Box Fans: A full-blown range of fans fulfilling every requirement from square one on. Fläkt Woods offers the widest range of fans in the market.

More information

ClimaFläkt. Chillers and condensing units

ClimaFläkt. Chillers and condensing units ClimaFläkt Chillers and condensing units Cooling Solutions Even the most efficient systems require addition of heating and cooling. For such needs Fläkt Woods provides thermodynamic solutions from 6 to

More information

The New Sorption Rotary Heat Exchanger

The New Sorption Rotary Heat Exchanger The New Sorption Rotary Heat Exchanger Two of the most important factors affecting indoor air climate are the air temperature and the humidity but achieving comfort conditions can be very expensive. Our

More information

eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction

eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction Air Comfort Air Treatment Energy Recovery eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction eco PREMIUM - Technical Instruction REDA 2 Contents Description Applications... 3 Quality & environment...

More information

VEX250H with rotary heat exchanger and EXact control system

VEX250H with rotary heat exchanger and EXact control system 3003433-2014-04-11 VEX250_EXact VEX250H with rotary heat exchanger and EXact control system Unit supplied with (factory fitted): Compact filter FP Filter bag FB Trim damper and blowout zone,tb250 The following

More information

EU Air Handling Units with SEMCO EXCLU-SIEVE

EU Air Handling Units with SEMCO EXCLU-SIEVE EU Air Handling Units with SEMCO EXCLU-SIEVE The acquisition of US based Semco has given us the opportunity to include a new range of rotary heat exchangers in our EU air handling unit range. Hygienic

More information

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE 2 GLEC-6 - Installation and maintenance CONTENTS 1 Important information... 3 2 Safety notes... 3 3 Technical description...4 4 Transport... 6 5

More information

PLENUM FAN EQLK PLENUM FAN, DIRECT-DRIVEN

PLENUM FAN EQLK PLENUM FAN, DIRECT-DRIVEN EQLK, DIRECT-DRIVEN INSTALLATION AND MAINTENANCE INSTRUCTIONS Contents Page Installation options...... 2 Checks to be made prior to commissioning...2 Electrical connections.....2 Measures before starting.....

More information

MODBUS RS485. » Technical instructions. Air Comfort. Housing ventilation

MODBUS RS485. » Technical instructions. Air Comfort. Housing ventilation Air Comfort Air Treatment Housing ventilation MODBUS RS485» Technical instructions 2 Modbus RS485 Technical instructions Description, Connections, Presentation, decimals Description RS485 has two connections,

More information

EC Box Fan www.flaktwoods.com/oandm Safety, Installation, Operation and Maintenance Instructions CONTENTS Paragraphs Safety 1 Handling/Storage 2 Installation (Mechanical) 3 Fig. 1: Fig. 2: Tilt Mechanism

More information

Smoke Control Ducts and Dampers For Single Compartment Applications. Fulfilling new requirements for EN product standards for CE Marking

Smoke Control Ducts and Dampers For Single Compartment Applications. Fulfilling new requirements for EN product standards for CE Marking Smoke Control Ducts and Dampers For Single Compartment Applications Fulfilling new requirements for EN product standards for CE Marking New Smoke Control Product Range Fläkt Woods Smoke Control Ducts and

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw CHGV 22 CHGV 2 CHGV 32 CHGV 40 PHRV heat pump model also available September 2007 10 12 11 - GB - 02

More information

HEAT RECOVERY AIR HANDLING UNIT

HEAT RECOVERY AIR HANDLING UNIT HEAT RECOVERY AIR HANDLING UNIT OPERATION MANUAL KOMFORT_L v2(2)_en.indd 1 07.08.2015 15:0:44 CONTENTS Introduction General Safety regulations Transportation and storage regulations Manufacturer's warranty

More information

Indholdsfortegnelse. Danvent Air Handling Units SERVICE MANUAL

Indholdsfortegnelse. Danvent Air Handling Units SERVICE MANUAL Indholdsfortegnelse Danvent Air Handling Units SERVICE MANUAL Service Servicing of the Air Handling Unit Your ventilation system is equipped with a Danvent Air Handling Unit (AHU) which will contribute

More information

GLEC exhaust FAN. Air Comfort. Air movement. Duct & Box Fans

GLEC exhaust FAN. Air Comfort. Air movement. Duct & Box Fans Air Comfort Air movement Duct & Box Fans GLEC exhaust FAN» Technical CATALOUGE Technical catalouge Exhaust Fan GLEC 2 Contents Exhaust fan - GLEC... 3 Performance Data...4 Fan chart-explanation and definitions...

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

Smoke extract fan SMHA HATCH

Smoke extract fan SMHA HATCH 12.11.2012 Contents Product overview... 3 Construction... 4 Specification... 5 Selection... 6 Installation... 7 Electrical connections... 8 Dimensions and weights... 9 Product code and accessories... 10

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB -

More information

CIATCOOLER LJA. Chilled water production units USE. Attractive design, Compact and quiet

CIATCOOLER LJA. Chilled water production units USE. Attractive design, Compact and quiet Attractive design, Compact and quiet Many customisable configurations possible For indoor installation New reliable technologies Version with Plug and Cool hydraulic module Cooling capacity: 23 to 140

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION VALLOX-product code: HVAC code: 358500 L 35850 R 79076 L 79077 R SOUND ATTENUATOR (OPTIONAL) IVALLOX 252 WATER OPERATED POST- HEATING UNIT (OPTIONAL) ELECTRICAL POST-HEATING UNIT (OPTIONAL) ELECTRICAL

More information

Topvex SR 09, 11, Topvex TR Compact Air Handling Units

Topvex SR 09, 11, Topvex TR Compact Air Handling Units Topvex SR 09, 11, Topvex TR 09-15 Compact Air Handling Units Installation instructions Document in original language 125593 A003 GB Copyright Systemair AB All rights reserved E&OE Systemair AB reserves

More information

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Instructions for the fan motor control system with integrated wiring terminals SILVER C Instructions for the fan motor control system with integrated wiring terminals SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units.

More information

Instructions for the BASIC BCRW Fan, Sizes General

Instructions for the BASIC BCRW Fan, Sizes General Instructions for the BASIC BCRW Fan, Sizes 004 027 1. General The BCRW is a direct-driven fan of axi-centrifugal design. This fan offers excellent power efficiency, low, uniform air flow, low sound generation

More information

WHHR Midi & Midi Lite

WHHR Midi & Midi Lite WHHR Midi & Midi Lite Residential Whole House Heat Recovery Units with Low Energy EC Motors Optional - Integral LCD Installation, Operating and Maintenance Instructions Image of model with LCD screen Page

More information

Heat recovery unit RDKS

Heat recovery unit RDKS Heat recovery unit RDKS Heat recovery unit RDAS is based on our RDAR unit and develops this further. The unit has a rotary heat exchanger with stepless speed control. This allows for very precise temperature

More information

Series. Suspended air supply units with the air capacity up to 4100 m 3 /h in the sound- and heat-insulated casing with the water heater

Series. Suspended air supply units with the air capacity up to 4100 m 3 /h in the sound- and heat-insulated casing with the water heater SUPPLY UNITS Series VENTS PA E Series VENTS PA W A13 control panel A13 control panel Suspended air supply units with the air capacity up to 3350 m 3 /h in the sound- and heat-insulated casing with the

More information

VEX280H with rotary heat exchanger and EXact control system

VEX280H with rotary heat exchanger and EXact control system 3003206-2014-04-15 VEX280_EXact VEX280H with rotary heat exchanger and EXact control system Unit supplied with (factory fitted): VEX280-1 VEX280-2 FP compact filter FB filter bag TB280 trim damper and

More information

Product Catalogue CG-PRC002E-EN. CGAD Liquid Chillers Air-Cooled Scroll Compressor 20 to 150 Tons. July Models: 50 / 60 Hz

Product Catalogue CG-PRC002E-EN. CGAD Liquid Chillers Air-Cooled Scroll Compressor 20 to 150 Tons. July Models: 50 / 60 Hz Product Catalogue CGAD Liquid Chillers Air-Cooled Scroll Compressor 20 to Tons Models: 50 / 60 Hz CGAD CGAD CGAD CGAD CGAD CGAD CGAD CGAD CGAD CGAD CGAD CGAD July 2012 CG-PRC002E-EN Introduction IMPORTANT:

More information

Air Handling Unit. REC Temovex Blue 4 NEW! Experts on indoor climate in low-energy houses

Air Handling Unit. REC Temovex Blue 4 NEW! Experts on indoor climate in low-energy houses NEW! REC Temovex Blue 4 Experts on indoor climate in low-energy houses REC Temovex Blue 4 Third generation of our Temovex units! - Dual counterflow heat exchangers with over 9% efficiency * - SFP < 1,

More information

Liquid-coupled heat exchanger LQRT ECONET

Liquid-coupled heat exchanger LQRT ECONET ECONET includes the following: 1. Functional components with heat exchanger on the supply air side and the exhaust air side. 2. Pump unit (not installed). 3. Control unit for liquid circuit (not installed).

More information

recooler HP EQKR HEAT PUMP

recooler HP EQKR HEAT PUMP AIR COMFORT AIR TREATMENT 9566 GB 2016.03.17 recooler HP EQKR HEAT PUMP» TECHNICAL CATALOGUE 2 ReCooler HP EQKR Technical Catalogue Content ReCOOLER HP EQKR HEAT PUMP 3 product presentation. 3 applications.

More information

WINDOW YORK TECHNICAL GUIDE. Single package Cooling only and Heat pump. Models YO-YM R407C YO V6 G YO V7 G

WINDOW YORK TECHNICAL GUIDE. Single package Cooling only and Heat pump. Models YO-YM R407C YO V6 G YO V7 G WINDOW TECHNICAL GUIDE Single package Cooling only and Heat pump Models YO-YM 09-24 R407C YM 09 V6 G YM 09 V7 G YO 12-19-24 V6 G YO 12-19-24 V7 G YORK List of Contents Page 1 - Safety...2 2 - Unit packaging...2

More information

Topvex SR03, SR04, SR06 Compact Air Handling Unit

Topvex SR03, SR04, SR06 Compact Air Handling Unit Compact Air Handling Unit GB GB Corrigo ver. no. 1.2-1-00 Manufacturer Our products are manufactured in compliance with applicable international standards and regulations. Systemair AB Industrivägen 3

More information

Hodge Clemco Ltd. MJC Mini Cartridge Filters Owners Manual. TSOM 556 Date of issue 13/07/04. Hodge Clemco Ltd

Hodge Clemco Ltd. MJC Mini Cartridge Filters Owners Manual. TSOM 556 Date of issue 13/07/04. Hodge Clemco Ltd 1 MJC Mini Cartridge Filters Owners Manual TSOM 556 Date of Issue: 13.07.04 Orgreave Drive, Sheffield South Yorkshire. S13 9NR Tel:0114 254 0600 Fax: 0114 2540250 Email:sales@hodgeclemco.co.uk www.hodgeclemco.co.uk

More information

AHU INSTALLATION & OPERATION MANUAL

AHU INSTALLATION & OPERATION MANUAL AHU INSTALLATION & OPERATION MANUAL VERSION 2 AIR HANDLING UNIT MODELS: AHU 500, AHU 900, AHU 1200, AHU 1700, AHU 2000, AHU 2500, AHU3500, AHU 4500, AHU 5000, AHU 6000, AHU 7000, AHU 8000, AHU 10000, AHU

More information

GLEB Kitchen exhaust fan

GLEB Kitchen exhaust fan GLEB Kitchen exhaust fan Installation and Maintenance??.1.2013 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

Air handling unit. REC Temovex 400S-EC-RS. Experts on indoor climate in low-energy houses

Air handling unit. REC Temovex 400S-EC-RS. Experts on indoor climate in low-energy houses REC Temovex 4S-EC-RS Experts on indoor climate in low-energy houses RT 4S-EC-RS REC Temovex 4S-EC-RS ECO2 control system for low-energy and passive houses Comprises: - Air flow boost for warm and cold

More information

Instructions for the fan motor control system, SILVER C

Instructions for the fan motor control system, SILVER C Instructions for the fan motor control system, SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units. The motor control system is

More information

Instructions for the BASIC Air Handling System, Sizes General 1.1 Description of the System

Instructions for the BASIC Air Handling System, Sizes General 1.1 Description of the System Instructions for the BASIC Air Handling System, Sizes 004 055 1. General 1.1 Description of the System The BASIC System is a complete modular air handling unit. The unit consists of blocks, i.e. a number

More information

Purge Ventilation Unit. Product Manual. ventilation systems TP625

Purge Ventilation Unit. Product Manual. ventilation systems TP625 EN Purge Ventilation Unit TP625 Product Manual ventilation systems Warnings, Safety Information and Guidance Important Information Important: read these instructions fully before the installation of this

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL

INSTALLATION, OPERATION & MAINTENANCE MANUAL CENTRAL FANS COLASIT LTD Unit 12A, Palmers Road, East Moons Moat, Redditch. Worcs. B98 0RF Tel: 01527-517200 Fax: 01527-517195 Edition 04_13 INSTALLATION, OPERATION & MAINTENANCE MANUAL CIV Fan Range Valid

More information

Climatix Basic reference addresses for eq Fläkt application v1.x

Climatix Basic reference addresses for eq Fläkt application v1.x Climatix Basic reference addresses for eq Fläkt application v1.x Modbus communication, slave mode Table of contents 1 About this document...3 1.1 Revision history...3 1.2 Before you start...3 1.3 Reference

More information

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module SPECIFICATION GUIDE FLEXAIR Air-cooled packaged Rooftop unit Cooling only or Heat Pump Nominal cooling capacity: 85 to 234 kw Nominal heating capacity: 83 to 226 kw Possibility to add auxiliary heaters:

More information

Air handling units KLASIK. Unique solutions available Flexible performance & economy Reliable, stable & efficient Tight casing & perfect insulation

Air handling units KLASIK. Unique solutions available Flexible performance & economy Reliable, stable & efficient Tight casing & perfect insulation Air handling units KLASIK Unique solutions available Flexible performance & economy Reliable, stable & efficient Tight casing & perfect insulation KLASIK air handling units Customer oriented and unique

More information

EHH SERIES DRAW THROUGH FAN COILS CFM

EHH SERIES DRAW THROUGH FAN COILS CFM EHH SERIES DRAW THROUGH FAN COILS 400-5000 CFM TABLE OF CONTENTS TABLE OF CONTENTS 2 INTRODUCTION 3 GUIDE SPECIFICATIONS 4 UNIT OVERVIEW 6 TECHNICAL DATA 8 DIMENSIONS 10 COMPUTER SELECTION 11 GEMCOOL PROFILE

More information

SERIES FAN VAV TERMINAL BOXES TYPE CVFB & SFTB

SERIES FAN VAV TERMINAL BOXES TYPE CVFB & SFTB SERIES FAN VAV TERMINAL BOXES TYPE CVFB & SFTB TROX (U.K.) LTD CAXTON WAY GB-THETFORD NORFOLK IP24 3SQ TEL: 01842 754545 CONTENTS 1. INTRODUCTION 1. 1 DESCRIPTION 1.2 PACKAGING AND STORAGE 1.3 HANDLING

More information

Submittal Data Performance Data Electrical Data

Submittal Data Performance Data Electrical Data ERMS Series Submittal Data Submittal Data Unit Designation: Job name: Architect: Engineer: Contractor: Performance Data Revision: 07/01/11 Cooling Capacity: EER: Heating Capacity: COP: Ambient Air Temp:

More information

290 on. 286 on. Comfortable climate with pre-heated, filtered supply air. Fresh air boxes ALB WW MODEL WITH WARM WATER HEATING

290 on. 286 on. Comfortable climate with pre-heated, filtered supply air. Fresh air boxes ALB WW MODEL WITH WARM WATER HEATING Fresh air boxes ALB Comfortable climate with pre-heated, filtered supply air. Ingeniously practical: Supply air, heating and filter in a single unit. For direct in-duct mounting. The fresh air boxes ALB

More information

USER S MANUAL. Heat (Energy) Recovery Ventilator. Vents Frigate HRV 120 S Vents Frigate ERV 120 S

USER S MANUAL. Heat (Energy) Recovery Ventilator. Vents Frigate HRV 120 S Vents Frigate ERV 120 S USER S MANUAL Heat (Energy) Recovery Ventilator Vents Frigate HRV 120 S Vents Frigate ERV 120 S 2 Frigate HRV(ERV) 120 S CONTENT Introduction... 3 Application... 3 Delivery set... 3 Unit designation key...

More information

Smoke Master SMIA Compact pressurisation and smoke exhaust system

Smoke Master SMIA Compact pressurisation and smoke exhaust system Smoke Master SMIA Compact pressurisation and smoke exhaust system Fläkt Woods FIFLO EN 2009.09 2 All rights reserved. Contents System overview... 4 Design and operation... 5 Technical specification...

More information

Installation and Maintenance

Installation and Maintenance 1.0 INTRODUCTION MRXBOXAB-ECO-LP1SW (Standard Unit) MRXBOXAB-ECO-LP1-OHSW (Opposite Hand Unit) Mechanical Ventilation Unit with Heat Recovery for Ceiling Void Mounting Installation and Maintenance The

More information

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE TEcHnIcal InsTRucTIons PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE PHRIE 095 PHRIE 1 PHIE 095 PHIE 1 PHRIE 155 PHRIE 157 PHRIE 175 PHRIE 177 PHRIE 195 PHRIE 197 PHRIE 7 PHRIE

More information

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL WM150 OWNERS MANUAL Page 1 of 9 INTRODUCTION Designed for a wide range of applications, the WM150 is a rugged, industrial unit, which utilizes an

More information

Series VENTS VUT R WH ЕС

Series VENTS VUT R WH ЕС AIR HANDLING UNITS WITH HEAT RECOVERY Series VENTS EH ЕС Series VENTS WH ЕС Air handling units with the air capacity up to 1500 m 3 /h in soundand heat-insulated casing with integrated electric heater.

More information

OPERATING & MAINTENANCE INSTRUCTIONS FOR EXHEAT RFA-OS TYPE FLAMEPROOF OVERSINK WATER HEATER

OPERATING & MAINTENANCE INSTRUCTIONS FOR EXHEAT RFA-OS TYPE FLAMEPROOF OVERSINK WATER HEATER OPERATING & MAINTENANCE INSTRUCTIONS FOR EXHEAT RFA-OS TYPE FLAMEPROOF OVERSINK WATER HEATER 1 1.0 GENERAL 1.1 All work should be carried out by suitable qualified personnel. 1.2 Heaters must be handled

More information

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side s Frost detectors for use on the air side QAF63.2-J QAF63.6-J Active capillary tube sensor for acquiring the lowest temperature within a range of 0 15 C Operating voltage AC 24 V Signal output DC 0...10

More information

PFS Single stage axial fan The axial fan for modern boiler plants

PFS Single stage axial fan The axial fan for modern boiler plants PFS Single stage axial fan The axial fan for modern boiler plants This large axial fan, type PFS- 400-236, was installed in 1987 at the Salmisaari coal-fired power station in Helsinki, Finland. The photo

More information

Heat pump & cooling unit in one

Heat pump & cooling unit in one + + Heat pump & cooling unit in one The reversible ThermoCooler HP heat pump can be integrated in our Envistar Flex units. All parts of the cooling/heating pump are incorporated in a module section, which

More information

User and maintenance manual

User and maintenance manual GB User and maintenance manual IMPORTANT SAFETY INSTRUCTIONS These instructions shall also be available on website: docs.whirlpool.eu. YOUR SAFETY AND THAT OF OTHERS IS HIGHLY IMPORTANT. This manual and

More information

VERSO Air Handling Units

VERSO Air Handling Units Energy efficient solutions for profitable indoor climate VERSO-S air supply units VERSO-R air handling units equipped with regeneration system VERSO-P air handling units equipped with recuperation system

More information

INSTALLATION OPERATION & MAINTENANCE INSTRUCTION HEAT RECOVERY UNITS VHR MODELS

INSTALLATION OPERATION & MAINTENANCE INSTRUCTION HEAT RECOVERY UNITS VHR MODELS INSTALLATION OPERATION & MAINTENANCE INSTRUCTION HEAT RECOVERY UNITS VHR MODELS TSEK VENCO Havalandırma ve Makina San.ve Tic. A.Ş. 2004. Cad. No:5 45400 OSB Turgutlu MANISA / TURKİYE Tel: +90 (236) 332

More information

TSEK VHR EC HEAT RECOVERY UNITS

TSEK VHR EC HEAT RECOVERY UNITS TSEK EC HEAT RECOVERY UNITS TS EN ISO 9001:2008 SN: 01 100 901925 General Information TSEK VENCO Heat Recovery Ventilation Units () are designed for saving energy and also improving indoor air quality.

More information

Installation and Maintenance

Installation and Maintenance 1.0 INTRODUCTION MRXBOXAB-ECO-LP1 (Standard Unit) MRXBOXAB-ECO-LP1-OH (Opposite Hand Unit) Mechanical Ventilation Unit with Heat Recovery for Ceiling Void Mounting Installation and Maintenance The LP1

More information

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2 Cleaning unit for coolant :_decftez`_>r_fr] Book No.: 1271526-02 V2 Alfa Laval Separation AB Separator Manuals, dept. SKEL S-147 80 Tumba, Sweden Telephone: +46 8 53 06 50 00 Telefax: +46 8 53 03 10 40

More information

CRU 200 and 500 Series Condensate Recovery Unit Installation and Maintenance Instructions

CRU 200 and 500 Series Condensate Recovery Unit Installation and Maintenance Instructions 6810850/1 IM-P681-07 ST Issue 1 CRU 200 and 500 Series Condensate Recovery Unit Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning

More information

Air handling units KLASIK. Unique solutions available Flexible performance & economy Reliable, stable & efficient Tight casing & perfect insulation

Air handling units KLASIK. Unique solutions available Flexible performance & economy Reliable, stable & efficient Tight casing & perfect insulation Air handling units KLASIK Unique solutions available Flexible performance & economy Reliable, stable & efficient Tight casing & perfect insulation KLASIK air handling units Customer oriented and unique

More information

INFRARED IP55 HEATER INSTRUCTIONS FOR: MODEL:- QZWP45N 1. SAFETY INSTRUCTIONS

INFRARED IP55 HEATER INSTRUCTIONS FOR: MODEL:- QZWP45N 1. SAFETY INSTRUCTIONS INSTRUCTIONS FOR: INFRARED IP55 HEATER MODEL:- QZWP45N Thank you for purchasing a Consort Claudgen product. Manufactured to a high standard this product will, if used according to these instructions and

More information

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side s Frost detector for use on the air side QAF64.2-J QAF64.6-J With active capillary tube sensing element for acquiring the lowest temperature within a range of 0 15 C With startup function Operating voltage

More information

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw Air-Cooled Liquid Chillers Nominal cooling capacity 21-94 kw Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. The

More information

Advance Split

Advance Split Engineering Data Manual Aqu@Scop Advance Split Air-to-Water DC Inverter Split Heat Pumps Models 005, 008, 012 & 014 2 to 16 kw Strength Points Most efficient heating technology with variable speed compressor.

More information

PRODUCT DATA COMFORT 5000 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 5300 m 3 /h

PRODUCT DATA COMFORT 5000 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 5300 m 3 /h PRODUCT DATA COMFORT 5000 BY NILAN Ventilation & passive heat recovery Commercial Passive heat recovery Ventilation < 5300 m 3 /h COMFORT 5000 The Comfort 5000 is a ventilation unit suitable for central

More information

Original instructions AR

Original instructions AR Original instructions SE... 8 GB... 22 NO... 27 FR... DE... 6 ES... 4 NL... 46 IT... 5 RU... 56 Dimensions and connections AR20/AR25 M8 002/52 940/450 494 449 92 20 98 042/552 42 20 AR20/25A/E 40 275 DN5

More information

Xcell 270 Longlife DC wholehouse heat recovery unit

Xcell 270 Longlife DC wholehouse heat recovery unit Xcell 270 Longlife DC wholehouse heat recovery unit Installation and maintenance instructions Xpelair Xcell 270 Longlife DC wholehouse heat recovery unit Xcell 270, Xcell 270BP Please leave this leaflet

More information

TELLUS. Complete HVAC substation for air handling, cooling, heating and hot tap water. Main advantages. General

TELLUS. Complete HVAC substation for air handling, cooling, heating and hot tap water. Main advantages. General Complete HVAC substation for air handling, cooling, heating and hot tap water Text and figures in red are preliminary and may be adjusted General TELLUS is a complete, modular substation that can be installed

More information

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h PRODUCT DATA COMFORT 40 BY NILAN Ventilation & passive heat recovery Domestic Passive heat recovery Ventilation < 40 m /h COMFORT 40 Product description The Comfort 40 is an energy-efficient ventilation

More information

DOMEKT ReGO 400VE(W)-B Series Air Handling Units Installation and Maintenance Service Manual

DOMEKT ReGO 400VE(W)-B Series Air Handling Units Installation and Maintenance Service Manual DOMEKT ReGO 400VE(W)-B Series Air Handling Units EN Content Safety Requirements...3 Transportation...3 Brief Description of the Unit...5 Installation...6 Maintenance...11 Technical Information......13

More information

Topvex SF02-SF12 Air Handling Unit

Topvex SF02-SF12 Air Handling Unit Topvex SF02-SF12 Air Handling Unit Installation instructions Document in original language 130324 A004 GB Copyright Systemair AB All rights reserved E&OE Systemair AB reserves the rights to alter their

More information

Smoke Master SMPA Compact pressurisation system

Smoke Master SMPA Compact pressurisation system Smoke Master SMPA Compact pressurisation system Fläkt Woods FILO E 2009.07 2 All rights reserved. Contents System overview...4 Design and operation...5 Technical specification...6 Electric and control

More information

OWNER S MANUAL. High-Wall Fan Coil Unit CONTENTS

OWNER S MANUAL. High-Wall Fan Coil Unit CONTENTS OWNER S MANUAL High-Wall Fan Coil Unit Page GENERAL 2,3 OPERATING MODES 2 REMOTE CONTROL 2 OPERATION 3-9 REMOTE CONTROL OPERATION 3 INDOOR UNIT DISPLAY 5 EMERGENCY OPERATION 5 PRESSING THE ON/OFF BUTTON

More information

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59 SOUND-INSULATED FAN OPERATION MANUAL _v.1(2)-en.indd 1 10.08.2015 15:20:59 CONTENT Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 3 Fan design 4 Delivery

More information

Technical Manual. New Water Cassette. Series BREZZA DOUBLE

Technical Manual. New Water Cassette. Series BREZZA DOUBLE Technical Manual New Water Cassette Series BREZZA DOUBLE AERTESI srl Cassetta BREZZA DOUBLE Tecnical manual AER.MT.I.BREDOPPIA.000.02.15 Pag.2 INDEX 1-INTRODUCTION 4 2- WORKING CONDITION LIMITS..4 3- COANDA

More information

EDD61 & EDD91 Extractors

EDD61 & EDD91 Extractors EDD61 & EDD91 Extractors Installation, Use and Maintenance Customer Care Department The Group Ltd. Harby Road Langar Nottinghamshire NG13 9HY T : 01949 862 012 F : 01949 862 003 E : customer.care@cda.eu

More information

SAM. Small Air Handling. VES SMALL AIR HANDLERS part of a complete range of innovative, flexible products from the HVAC experts

SAM. Small Air Handling. VES SMALL AIR HANDLERS part of a complete range of innovative, flexible products from the HVAC experts Small Air Handling units SAM W i d e d u t y r a n g e 0.05m 3 /sec to 2.4m 3 /sec Powerful yet quiet Extensive options VES SMALL AIR HANDLERS part of a complete range of innovative, flexible products

More information

DANVENT CATALOGUE 1999

DANVENT CATALOGUE 1999 DANVENT CATALOGUE 1999 CONTENTS Contents TC 7-10 Combi-unit 11-15 Combination examples with dimensions and weights 16 Transportation & installation 17-18 Roof unit 19-26 Damper sections 27-30 Filter sections

More information

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4 Installation Operation Maintenance Ductable water unit FWD 08-12 - 20-30 - 45 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice

More information

INSTALLATION & MAINTENANCE

INSTALLATION & MAINTENANCE INSTALLATION AND MAINTENANCE INSTRUCTIONS 1 INSTALLATION & MAINTENANCE FIBRE-REINFORCED PLASTIC AIR HANDLING UNITS fibre-reinforced plastic AHU 2 INSTALLATION AND MAINTENANCE INSTRUCTIONS Table of contents

More information

FLOWAY. Floway Range. The dual-flow air handling unit with heat recovery guaranteeing an Economical and Durable solution. use.

FLOWAY. Floway Range. The dual-flow air handling unit with heat recovery guaranteeing an Economical and Durable solution. use. The dual-flow air handling unit with heat recovery guaranteeing an Economical and Durable solution use Air flow rate: 500 to 8500 m 3 /h is a PLUG & PLAY dual-flow ventilation unit equipped with a highly

More information

CLIMASTER ZCF AIR HANDLING UNITS

CLIMASTER ZCF AIR HANDLING UNITS CLIMASTER ZCF AIR HANDLING UNITS From 1 September 2013, EXHAUSTO has taken over Novenco s activities within sales and production of land-based climate control systems. Inquiries relating to the products

More information

EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 700 Thimble Shoals Boulevard Newport News VA 23606-2575 Telephone (757) 873-6800 Fax (757) 873-3632 Website: www.ebacusa.com INTRODUCTION

More information