PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN » INSTALLATION AND MAINTENANCE INSTRUCTIONS
|
|
- Johnathan Terry
- 6 years ago
- Views:
Transcription
1 AIR COMFORT AIR TREATMENT 9933 GB PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN» INSTALLATION AND MAINTENANCE INSTRUCTIONS contents Page Installation options Checks to be made prior to commissioning...2 Electrical connections Measures before starting Installation of separately supplied frequency inverters... 3 Airflow measurement.. 4 Maintenance... 5 Cleaning Picture shows the fan with integral motor. Other motor options are present. To remove the fan from the air handling unit casing To replace the motor
2 Installation and maintenance instructions 2 EQLP Fan, Installation options EQLZ-37 Safety guard, inlet EQLZ-36 Safety guard, outlet Connection Accessories for the outlet: EQAZ-26 Connection piece EQAZ-25 Flexible connection EQLZ-36 Protective screen EQLZ-24 Protective screen for door Checks to be made prior to commissioning Check that the fan complies with the EU machinery directive. All inspection doors on the fan section and other function is equipped with door locks with a key. Additional safety can be added. EQLZ-37 is a protective screen which can be placed at the inlet to the fan section. EQLZ-36 is a protective screen that can be added to the outlet of the fan section if another AHU function is placed downstream of the fan. EQLZ-36 is protective screen when the fan section is placed at the outlet of the AHU. EQLZ-24 is additional protection behind the inspection door at the fan section. Check that a qualified electrician has handed over written approval for commissioning. Check that the fan impeller rotates freely and that no objects which can be drawn in and damage the fan have been left in the installation. If the fan is equipped with steel spring anti-vibration mountings, the transport locking devices must be removed before starting the fan. Belastningsskad Deformation on bearing due to overloading. Electrical connections The motor of the fan must always be controlled by a frequency inverter. The frequency inverter permits control of the motor speed and slow starts. If the fans are idle for more than 3 months prior to or after installation, the fans should be occasionally rotated by hand at regular intervals. If this is not done, the bearings are liable to become damaged due to overloading as shown in the adjacent illustration. N.B.! The fan must not be started directly on-line! Read the MAX permissible frequency at which the fan motor may be controlled. You ll find this frequency specified on the rating plate. Under no circumstances is it permissible to supply the fan motor with power of a higher frequency.
3 xxx xxxx xxxxxx xxx xxxxx xxxxx xxx xxxx xxxxxx xxx xxxx xxxxxxx xxx xxxx xxxxxxx Installation and maintenance instructions 3 Airflow measurement xxx xxxx xxxxxx xxx xxx xxxx xxxxx Max frequency or max rotational speed Electric wiring must be carried out by a qualified electrician. Isolate the power supply and wait until the impeller has stopped rotating (approx. 1 minute) before inspecting and servicing the fan. Measures before starting The fan must not be started with the damper on the suction or delivery side closed. However the fan motor may be briefly energized with the inspection door open for checking that the direction of impeller rotation is correct. Check before starting the fan that the impeller rotates freely and that no objects, which can be drawn in and damage the fan, have been left in the installation. If the fan is equipped with steel spring anti-vibration mountings, the transport locking devices must be removed before starting the fan. The EQLK has equipment for measuring the airflow. The airflow, q, can be measured by applying a manometer reading of Δp (Pa), and a constant, k, using the following formula: q = 1 Δp m 3 /s k The manometer reading, Δp, which is the difference between the pressure in the suction chamber by the fan inlet and the pressure inside the inlet cone, can be read with a manometer (pressure range of up to 6000 Pa) which should be connected with a 4 mm dia. tube to 2 externally located pressure tappings. The value of the constant k is specified in the table below. For EQLZ-42 U-tube manometers, use only the red manometer fluid supplied with the instrument. Never use any other type of fluid. Precision-adjust the zero point with the zero adjustment screw. A flow indicator with built-in pressure transducer STAZ-23, STBZ-23 (available as an accessory) should be connected by means of tubes to the external pressure tappings. This instrument converts the mano-meter pressure reading to a flow (m 3 /s) which is shown on a display screen and transmits a 0 10 V output signal, linear with the flow.
4 Installation and maintenance instructions 4 If the air handling unit is supplied with a control system, the flow can be read directly in the control panel display. NB! In the case of air handling units supplied with a control system, the pressure tappings in the end connection panels of the unit are not connected to the airflow sensor of the fan. If you still want to read the manometer pressure with an external manometer, you can connect the tubes from the airflow sensor of the fan across T-nipples to the pressure tappings in the end connection panel of the air handling unit. If this external means of measuring flow will not be permanent, the tubes must be restored to their original condition. Size EQLP-aaa-b k-factor Impeller size , , , , , , , , 014-3, 018-2, , , , , , , 027-3, 032-2, , , 036-3, 041-2, 045-2, , , 045-3, 047-3, 050-2, 054-2, 9, , 063-2, , 054-3, 056-3, 063-3, 068-2, 7, , , 079-3, , , If two fans are installed in the fan section, the k-value is applicable to the total airflow generated by both fans Temperature correction The flow scale on the indicating instrument and the flow formula above apply to air with a temperature of +20 C. For other temperatures, the flow must be corrected using the following formula: q = (273 + t) q20, m 3 /s 293 where q = the actual flow through the fan, q20 = the flow reading and t = the current temperature in C. Maintenance Warning! In order to prevent personal injury and damage to machinery, the safety isolating switch must be switched off and the safety fuses of the fan must be removed before beginning work on the fan. The fan must be inspected and cleaned every 6/12th month. The length of the interval has been determined on the basis of approx hours of operation during a 12-month period and for a normal comfort installation. In environments where the dust content is high in the supply and/or extract air, the air handling unit will have to be inspected and cleanedmore often. The fan is accessible through the inspection door and cleaned with the fan in place. Cleaning Both the supply air and the extract air fan should be inspected and cleaned whenever the need arises. Dust tends to collect mainly on the inner side of the fan blades. The best way to clean the fan impeller is by using a vacuum cleaner equipped with a soft nozzle. Be careful to remove all the impurities from the fan blades so that the fan will not come out of balance. After adjusting or cleaning the fan, check that it runs free of vibration. To remove the fan from the air handling unit casing, Asynchronous and PM-motors The fan can be withdrawn from the casing in the following way: 1. Remove the frame of the inspection door including the door and the fixed panel by removing the bolts beneath the cover plenums. 2. Disconnect the motor cable/control cable to the frequency inverter and pull the cables through the rotor wall/filter wall. 3. If a shear absorber is fitted: Remove the bolts (2 bolts) that secure its brackets. Ignore the bolts on the rear side; they need not be backed off. If a pressure suppressor and steel spring anti-vibration mountings are fitted: Remove the bolts to the fan beams in the floor at both ends. 4. If steel spring anti-vibration mountings are fitted: Remove the bolts that hold the fan connection against the fan outlet.
5 xxx xxxx xxxxxx xxx xxx xxxx xxxxx Installation and maintenance instructions 5 5. Withdraw the fan unit. Be careful not to damage the gasket in the fan s inlet plate (applies to rubber antivibration mountings). The fan can be withdrawn maximally so far out that half the fan motor protrudes outside the unit casing without support. 6. Push in and reassemble the components in the reverse order. To replace the motor 1. Disconnect the electrical connections. 2. Remove the stop screw in the fan impeller hub. 3. Remove the motor from the motor base plate. 4. Extract the impeller from the motor shaft end with an extractor tool. Utilize the existing extraction grooves in the hub for this purpose. See the figure below. 5. Back the motor from the impeller. 6. Reassemble in the reverse order, using the tapped hole in the motor shaft end as a fixing point for the extractor tool. Locking bolt Carry out maintenance on the motor according to the instructions provided by the motor supplier. In cases where there is no possibility to carry out the entire fan or motor with impeller, alternatively there is no need for a complete disassembly, following procedure can be used: 1. NOTE! Turn off the power at themain switch and mark that work is ongoing in the fan section. 2. Disconnect all electrical connections in themotor terminal box. 3. Remove themotor bracket fromtheir bolted joints at the unit s bottom panel/guide rails. 4. Move themotor bracketwithmotor and impeller from the inlet cone far enough to enable removal of the impeller. 5. Alternatively loose the bolt joint on themotor and rotate the motor to enable removal of the impeller. 6. Remove the impeller fromthemotor shaft using a puller. 7. Lift the impeller out of the unit in a suitableway through the inspectiondoor or disconnect the motor bolted joints if this has not been done and lift themotor out of theunit in an appropriate way through the inspection door. Make sure that the fan inlet engages into the rear holder of the connection frame.
PLENUM FAN EQLK PLENUM FAN, DIRECT-DRIVEN
EQLK, DIRECT-DRIVEN INSTALLATION AND MAINTENANCE INSTRUCTIONS Contents Page Installation options...... 2 Checks to be made prior to commissioning...2 Electrical connections.....2 Measures before starting.....
More informationGLEB Kitchen exhaust fan
GLEB Kitchen exhaust fan Installation and Maintenance??.1.2013 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance
More informationTopMaster Air Handling unit. Installation instructions
Installation instructions Safety Instructions Operation of Air Handling units and accessories WARNING Installation may only be carried out by qualified personnel. Before taking the air handling unit into
More informationKITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE
KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE 2 GLEC-6 - Installation and maintenance CONTENTS 1 Important information... 3 2 Safety notes... 3 3 Technical description...4 4 Transport... 6 5
More informationEnglish CNA-CNB. Centrifugal fans Installation and maintenance
916505-0 English CNA-CNB Centrifugal fans Installation and maintenance 916505-0 GB Centrifugal fans types CNA, CNB, CNA-M and CNB-M installation and maintenance 1. Application 2. Handling 2.1 Marking 2.2
More informationCENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D
CENTRIFLOW 3D Plug fan GMEC >> Installation and Maintenance air comfort CentriFlow 3D 2 Plug Fan CentriFlow 3D GMEC Installation and Maintenance Important Information, Safety notes, Technical Description
More informationACN SMOKE INSTALLATION AND MAINTENANCE
NovAx ACN SMOKE INSTALLATION AND MAINTENANCE 918149-0 English 918149-0 GB Installation and maintenance NovAx smoke exhaust fan type ACN smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport
More informationInstallation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke
918149-0 GB Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport 3. Storage 4. Installation 4.1 Prior to attachment 4.2 Attachment
More informationSupply air unit VEKA Installation & Maintenance
November 2008 Safety instructions Operating the air treatment unit and accessory components WARNING Before the air treatment unit is taken into service, any free connections must be provided with protective
More informationGLEB. >> Installation and Maintenance. Air Comfort. Air movement. Duct & Box Fans
Air Comfort Air movement Duct & Box Fans GLEB KITCHEN exhaust FAN >> Installation and Maintenance Kitchen Exhaust Fan GLEB Installation and Maintenance Important Information, Safety notes, Technical Description
More informationIndholdsfortegnelse. Danvent Air Handling Units SERVICE MANUAL
Indholdsfortegnelse Danvent Air Handling Units SERVICE MANUAL Service Servicing of the Air Handling Unit Your ventilation system is equipped with a Danvent Air Handling Unit (AHU) which will contribute
More informationGENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES GENERAL INSTRUCTION
GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES Using the air handling unit... Free space for service and repair work... GENERAL INSTRUCTION Checking prior to commissioning...3
More informationJet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance
916503-0 GB Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance 1. Main components 2. Application 3. Handling 3.1 Marking 3.2 Weight 3.3 Transport 4. Storage 1. Main components: Types ARC,
More informationHORIZONTAL MULTISTAGE CENTRIFUGAL PUMP
HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP WWPPCHLFT260 Instructions WWPPCHLFT260_Horizontal Multistage Centrifugal Pump_IB.indd 1 READ THIS MANUAL CAREFULL BEFORE INSTALL, START THE PUMP 1. Suction 2. Plug
More informationINSTALLATION, OPERATION & MAINTENANCE MANUAL
CENTRAL FANS COLASIT LTD Unit 12A, Palmers Road, East Moons Moat, Redditch. Worcs. B98 0RF Tel: 01527-517200 Fax: 01527-517195 Edition 04_13 INSTALLATION, OPERATION & MAINTENANCE MANUAL CIV Fan Range Valid
More informationInstructions for the BASIC BCRW Fan, Sizes General
Instructions for the BASIC BCRW Fan, Sizes 004 027 1. General The BCRW is a direct-driven fan of axi-centrifugal design. This fan offers excellent power efficiency, low, uniform air flow, low sound generation
More informationEQGA AND EQGB HYGIENIC VERSION, CODE SUFFIX I = 3 AND 4
EQGA AND EQGB HYGIENIC VERSION, CODE SUFFIX I = 3 AND 4 ASSEMBLY AND MAINTENANCE INSTRUCTIONS Contents Page Hygienic version..... 2 Delivery...... 2 Safety precautions...... 2 Mounting on the floor......
More informationUSER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES
USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES Bucket Fan 420 Bucket Fan 1055 Bucket Fan 1460 420 1055 1460 2 Bucket Fan CONTENT INTRODUCTION 3 USE 3 WHAT S INCLUDED IN THE BOX 3 DESIGNATION
More informationInstructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes
Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes 50-120 1 General The heat exchanger control system is a control system for 380 W step motors
More informationINSTALLATION, OPERATION, AND MAINTENANCE MANUAL
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended
More informationEC Box Fan www.flaktwoods.com/oandm Safety, Installation, Operation and Maintenance Instructions CONTENTS Paragraphs Safety 1 Handling/Storage 2 Installation (Mechanical) 3 Fig. 1: Fig. 2: Tilt Mechanism
More informationOwner s manual for. Venco 87mm & 100mm. (3 1/ 2 & 4 ) De-airing Pugmill
Owner s manual for Venco 87mm & 100mm (3 1/ 2 & 4 ) De-airing Pugmill Venco Products 29 Owen Road Kelmscott, Western Australia 6111 ph +61 8 9399-5265 fax +61 8 9 497 1335 email: venwest@iinet.net.au www.venco.com.au
More informationEnvistar Operation and Maintenance Instructions
Air Handling Unit Envistar Instructions Project:... Air handling with the focus on LCC Address and Telephone Register for Service Supplier: IV Produkt AB Box 3103 SE-350 43 VÄXJÖ, Sweden Street address:
More informationLC Series - Light Commercial Pump Station Installation and Operation Manual
LC Series - Light Commercial Pump Station Installation and Operation Manual Please keep this manual with the pump station Content Rain Bird LC Series Overview... Safety Instruction... Operation... 3 Pump
More informationXB-EFA-8L-BK & XB-EFA-8R-BK
Supply & Extract Ventilation Unit with Heat Recovery The EMC Directive 2014/30/EU The Low Voltage Directive 2014/35/EU The information contained in this document provides details of installation, operation
More informationCOOLING SYSTEM 1. Section V CONTENTS DATA AND SPECIFICATIONS. Page. Fluid Fan Drive (Silent Flite) 3. Water Pump 4. Radiator 5
Section V COOLING SYSTEM CONTENTS Fluid Fan Drive (Silent Flite) 3 Water Pump 4 Radiator 5 Water Temperature Gauge 6 Thermostat 7 Radiator Pressure Cap 7 Service Diagnosis 7 DATA AND SPECIFICATIONS COOLING
More informationDESCRIPTION IMPELLER INSPECTION MAINTENANCE POWER CORD REPLACEMENT IMPELLER REPLACEMENT MECHANICAL SEAL REPLACEMENT IMPELLER INSPECTION /REPLACEMENT
Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect
More informationVenco 75mm (3 ) Standard and De-airing Pugmill
Owner s manual for Venco 75mm (3 ) Standard and De-airing Pugmill Venco Products 29 Owen Road Kelmscott, Western Australia 6111 ph +61 8 9399-5265 fax +61 8 9 497 1335 email: venwest@iinet.net.au www.venco.com.au
More informationCentrifugal Fans maintenance manual
Centrifugal Fans maintenance manual www.dcs.fi Contents 1 Safety... 4 1.1 Explanations... 4 1.2 Basic safety rules... 4 1.3 Noise level... 5 2 General... 6 2.1 Fan types... 6 2.1.1 Use types... 6 2.1.2
More informationZETA MAGNETIC AGITATORS
ZETA MAGNETIC AGITATORS For sterile liquid processing www.zeta.com ZETA AGITATORS A VERSATILE PRODUCT FAMILY Proven agitator technology that meets the highest standards of sterile design and reliability.
More informationAir Handling Units. T F E.
Air Handling Units Extract from BS EN ISO 15138:2007 Petroleum & natural gas industries- Offshore production installations-heating, ventilation & air-conditioning. A.12.1 Function Installations provided
More informationA AD Oil burners fuel unit. deltapumps.com. DE A-AD_en_0709.pdf Page 1/1
A AD Oil burners fuel unit deltapumps.com DE116-0709 A-AD_en_0709.pdf - 16.11.09 Page 1/1 Oil burners fuel unit Type A, AD 1- Applications The DELTA aluminium fuel unit type A is an efficient and modern
More informationInstallation, Operation and Maintenance Manual. 3AV 1 to 3AV 430
Installation, Operation and Maintenance Manual 3AV 1 to 3AV 430 3AV Close-Coupled Liquid Ring Pump Installation, Operation, and Maintenance Manual Table of Contents 1. General... 3 1.1 Application Fields...
More informationHigh Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)
High Plume Blowers Suggested Specification Section 15500 (Master Format 1996) Suggested Specification Section 23 38 16 (Master Format 2004) PART 1 GENERAL 1.01 WORK INCLUDED High Plume Laboratory Exhaust
More informationBRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01
b cool manufacturers of air-conditioning equipment ltd BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION Ver. 1.01 Ver. 3.02 01_18 BCool# 1 brt c/h r407c / r410a
More informationSPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS
SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification
More informationINLET DAMPER WALL FAN UNIT
FARM PRODUCTS DIVISION MEMBER OF AMCA AMERICAN COOLAIR CORPORATION P.O. BOX 2300 JACKSONVILLE, FLORIDA 32203 PHONE (904) 389-3646 FAX (904) 387-3449 E-MAIL - agfans@coolair.com INLET DAMPER WALL FAN UNIT
More informationSAM TURBO INDUSTRY LIMITED
INSTRUCTIONS ON INSTALLATION, OPERATION AND MAINTENANACE FOR SAM TURBO PUMP TYPE MD SAM TURBO INDUSTRY LIMITED NEELAMBUR, COIMBATORE-641 014. INDIA PH: 0422-3058899(50 LINES), FAX: 3058000, E-MAIL: mktg@sampumps.com,
More informationInstallation and maintenance instructions for cabin units type vertical IDAC (V50)
GB Installation and maintenance instructions for cabin units type vertical IDAC (V50). Application. Bundled parts. Handling. Marking. Weight. Transport. Storage 5. Installation 5. Mounting 5. Water trap
More informationSeries PX. Installation & Maintenance. Models: PX-3 PX-5 PX-7 1/2-HF PX-10-HF PX-15-HF. Materials: A - CPVC
Series PX Installation & Maintenance Models: PX-3 PX-5 PX-7 /2-HF PX-0-HF PX-5-HF Materials: A - CPVC Introduction Penguin Pumps are designed to handle a large range of chemicals without difficulty. Completely
More informationSOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59
SOUND-INSULATED FAN OPERATION MANUAL _v.1(2)-en.indd 1 10.08.2015 15:20:59 CONTENT Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 3 Fan design 4 Delivery
More information1. Description INSTRUCTION FOR AIR BLAST COOLER TYPE COOL 450
1. Description General The cooler is used for cooling of water, oil or other liquid by use of air. The liquid is passing in the tubes where it transfere the energy to the air via the fins on the outside
More informationOperation and Maintenance Manual Chamber Conditioning Unit, CCU 06. Document Number: EC OM 6847 Revision: 3
Operation and Maintenance Manual Chamber Conditioning Unit, CCU 06 Part Number: KI40053 Document Number: EC OM 6847 Revision: 3 TABLE OF CONTENTS Table Of Contents Approval Sheet List of Abbreviations
More informationGroup 7 COOLING SYSTEM CONTENTS
Group 7 COOLING SYSTEM CONTENTS COOLING SYSTEM 1 Paragraph Page Engine Water Temperature Gauge 9 7 Instrument Panel Unit 7 Temperature Sending Unit ; 8 Electrical Circuit (Testing) 8 Pressure Testing Cooling
More informationModels Series Series
Models 31800-Series 31801-Series INDUSTRIAL DIAPHRAGM PUMPS 4 GPM/15 LPM FEATURES Self-Priming Easy Installation Can run dry without damage Low Amp Draw Flow to 4 GPM/15 LPM Compact Size Thermal Overload
More informationHodge Clemco Ltd. MJC Mini Cartridge Filters Owners Manual. TSOM 556 Date of issue 13/07/04. Hodge Clemco Ltd
1 MJC Mini Cartridge Filters Owners Manual TSOM 556 Date of Issue: 13.07.04 Orgreave Drive, Sheffield South Yorkshire. S13 9NR Tel:0114 254 0600 Fax: 0114 2540250 Email:sales@hodgeclemco.co.uk www.hodgeclemco.co.uk
More informationMODEL MC-UL592 MC-UL594 POWER SOURCE. 230V - 240V ~ 50 Hz MAX INPUT 1400 W 1500 W NOMINAL INPUT DIMENSIONS (W x L x H)
Order Number: PMMA091040CE Vacuum Cleaner MC-UL592/MC-UL594 SPECIFICATION MODEL MC-UL592 MC-UL594 POWER SOURCE 230V - 240V ~ 50 Hz MAX INPUT 1400 W 1500 W NOMINAL INPUT DIMENSIONS (W x L x H) 1200-1300
More informationGRIND PRO DUAL OR DISC SANDER. Operator Manual
GRIND PRO DUAL OR DISC SANDER Operator Manual 2 GRIND PRO DUAL OR DISC ORTHO-SANDER INTRODUCTION The Grind Pro Dual or Disc Sander is a compact, durable machine designed for fast, complete finishing work.
More informationClimaster ZerAx. Eco-designkrav. Climaster ZerAx type ZCN-M guide GB
Climaster ZerAx Climaster ZerAx type ZCN-M guide 924784-0 GB Eco-designkrav Important This document is made available as it is. Novenco reserves the right to make changes without prior notice due to further
More informationMJC Cartridge Filter Unit Operation & Maintenance
1 of 19 Hodge Clemco Ltd MJC Cartridge Filter Unit Operation & Maintenance Owner s Manual Date of Issue: 19.07.04 TSSM536.1a Hodge Clemco Ltd Orgreave Drive Sheffield S13 9NR Tel: 0114 254 8811 Fax: 0114
More informationVEX250H with rotary heat exchanger and EXact control system
3003433-2014-04-11 VEX250_EXact VEX250H with rotary heat exchanger and EXact control system Unit supplied with (factory fitted): Compact filter FP Filter bag FB Trim damper and blowout zone,tb250 The following
More informationModels Series Series
Models 3180-Series 3181-Series INDUSTRIAL DIAPHRAGM PUMPS Commercial Duty, 3 GPM/1 LPM FEATURES Sealless Easy Installation Run Dry Ability Flow to 3 GPM/1 LPM Self-Priming Low Amp Draw Thermal Overload
More informationF17W44_MFB_F_EN INSTALLATION INSTRUCTIONS
F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS Contents Page User instructions 3-5 General 3 Fan installation 3-4 Maintenance 3 Electrical installation 5 Troubleshooting 5 Technical description 6-8 General
More informationQZHW Fan Coil Unit. Key features. Specifications
Key features High wall installation Cooling ( pipes) Low noise level Electrical heating coil ECM version for low energy consumption QZHW is a high wall fan coil unit available in sizes and many different
More information568X, 587X, 588X Series
Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect
More informationThis label warns for risk of electrical shock when failing to observe.
MANUAL horizontal centrifugal pumps MB series ic drive SB series mechanical seal 1. Introduction 2. Safety precautions 3. Receipt 4. Installation / Operation and Maintenance 4.1 Installation 4.2 Operation
More informationPatterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.
Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect
More informationMNEFDD54 & MNBCDD54 GALVANIZED WALL FANS Installation, Operation, and Maintenance Instructions
FARM PRODUCTS DIVISION MEMBER OF AMCA AMERICAN COOLAIR CORPORATION P.O. BOX 2300 JACKSONVILLE, FLORIDA 32203 PHONE (904) 389-3646 FAX (904) 387-3449 E-MAIL - fans@coolair.com MNEFDD54 & MNBCDD54 GALVANIZED
More informationVarofoil Controllable Pitch in Motion Fans Compared to Variable Frequency Controlled Fans
Varofoil Controllable Pitch in Motion Fans Compared to Variable Frequency Controlled Fans A look at two accepted technologies.. System Characteristics In general, the pressure developed by a fan is a function
More informationCeiling swirl diffusers
X X testregistrierung Ceiling swirl diffusers Type Plenum box with damper blade and square diffuser face Horizontal swirling air discharge For comfort zones, with fixed air control blades Circular and
More informationISOLATED DIRECT DRIVE PLENUM FAN (IDDP)
Our Expertise, Your Air-Moving Solution ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) PART# 0601710001_rev_A INSTALLATION, OPERATION & MAINTENANCE MANUAL Please read and save these instructions for future reference.
More informationVETO CLEANER 500 FLUE GAS CLEANER
As of serial number 3100 0001 VETO CLEANER 500 FLUE GAS CLEANER USER MANUAL SPARE PARTS LIST Manufacturer: ALA TALKKARI Veljekset Ala-Talkkari Oy FI-62130 HELLANMAA TEL. +358 6 433 6333 FAX +358 6 437
More information1. Description INSTRUCTION FOR BLAST COOLER TYPE COOL 250. Material
1. Description General The cooler is used for cooling of water, oil or other liquid by use of air. The liquid is passing in the tubes where it transfere the energy to the air via the fins on the outside
More informationCeiling swirl diffusers
X X testregistrierung Ceiling swirl diffusers Type Plenum box with damper blade (optional) Horizontal swirling air discharge With very low sound power level for comfort zones, with fixed air control blades
More informationMontageanleitung RLO (Original) Mounting Instructions RLO (Translation of the original)
Montageanleitung (Original) (Translation of the original) DE MA_ 1.0 06/2014 Taperlock Clamping-bush system _0 _1 Fixed hub Inlet nozzle with IMV 1. Revision index Revision Date MA_ 1.0 06/2014 2. Safety
More informationRemoval. CAUTION: Do not let tensioner arm snap back to the freearm position, sever damage may occur to the tensioner.
Removal 3.7L/4.7L ENGINE CAUTION: Do not let tensioner arm snap back to the freearm position, sever damage may occur to the tensioner. 1. Disconnect negative battery cable from battery. 2. Rotate belt
More informationDS series STERLING PUMPS. Industrial End Suction Pumps ISO/DP
DS series Industrial End Suction Pumps ISO/DP 5199 www.sterlingpumps.com.au DS series Capacities from: Heads from: 340 to 5,680 m3/h (1,500 to 25,000 USPGM) 21 to 106 metres (70 to 350 feet) Power range
More informationA Fläkt Woods Company 2933 Symmes Road, Fairfield, Ohio Phone: (513) Fax: (513)
A Fläkt Woods Company 2933 Symmes Road, Fairfield, Ohio 45014-2035 Phone: (513) 874-2400 Fax: (513) 870-6249 JM AEROFOIL FANS Installation, Operation and Maintenance Instructions Site Storage The fan must
More information1 - Donkin Fans. Majax-2 Aerofoil Axial Flow Fans
1 - mj,, Donkin Fans Majax-2 Aerofoil Axial Flow Fans - IW '~AJAX-2 GENERAL SPF ~IFICATION Majax-2 axial flow fans are manufactured in diameters ranging from 315mm to 2000mm (available in 2250mm on request),
More informationNovenco Air Handling Units
Novenco Air Handling Units Climaster ZCF Guide 919432-0 GB Important This document is provided As is and is subject to change without notice. Novenco reserves this right due to continuous product development.
More informationSECTION PACKAGED COMPRESSOR AND CONDENSER UNITS
SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply
More informationHalton Rex 600 Basic R6B - Active chilled beam
Halton Rex 600 Basic R6B - Active chilled beam Halton Rex 600 Basic chilled beam is: A base version to the combined cooling, heating, and supply air unit for flush installation within a suspended ceiling.
More informationEnergy Conservation with PARAG Energy Efficient Axial Flow FRP Fans
PARAG FANS & COOLING SYSTEMS LTD. Energy Conservation with PARAG Energy Efficient Axial Flow FRP Fans Registered Office & Works Plot No.1/2B & 1B/3A, Industrial Area No.1 A.B.Road, Dewas 455001 (M.P.)
More informationContents. Getting Started. Operation. Maintenance and Care. Problem Solving Guide. Warranty 13
OWNER S MANUAL Contents Getting Started Important Safety Instructions 2 Polarization Instructions 3 State of California Proposition 65 Warnings 3 Decription of the Vacuum 4 Assembling the Vacuum 5 Operation
More informationAXUS - SC Short Cased Axial Flow Fans Installation and Maintenance
1.0 INTRODUCTION AXUS - SC Short Cased Axial Flow Fans Installation and Maintenance The Nuaire Short Cased Axial Fan range is produced in a range of sizes from 250mm to 1600mm diameter. Cases are manufactured
More informationINSTRUCTION AND REPAIR MANUAL
SECTION 6 ITEM 390 DATED JANUARY 2003 SUPERSEDES SECTION 6 ITEM 390 DATED OCTOBER 2000 INSTRUCTION AND REPAIR MANUAL SERIES 390 6 The 390 Series is a superior commercial Multi-Stage Vertical In-Line Centrifugal
More informationInstallation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing
Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Important: To protect the unit and avoid damage to the heat exchanger, the blower speed
More informationBELT DRIVEN STATIONARY AGITATOR
BELT DRIVEN STATIONARY AGITATOR INSTRUCTION MANUAL www.usfarmsystems.com 2955 S. K Street Tulare, CA. 93274 (559)685-0340 (800)811-9462 Fax (559)685-9160 Revision Date 9/7/2017 TABLE OF CONTENTS How to
More informationCHIPPER PC1 INSTRUCTIONS FOR INSTALLATION OPERATION AND MAINTENANCE. Series 35
Cl/SfB (73.4) X CHIPPER PC1 INSTRUCTIONS FOR INSTALLATION OPERATION AND MAINTENANCE Series 35 Imperial Machine Company (Peelers) Limited Harvey Road, Croxley Green, Herts WD3 3AX, England Telephone: 01923
More informationInterSeptor Centrifugal Separators Operating & Maintenance Manual
General Information: This manual was prepared to assist in the installation, operation, and maintenance of PEP ICS centrifugal separator systems. For immediate response to questions not covered in this
More informationSeries P. Installation & Maintenance. Materials: A - CPVC B - Polypropylene C - PVDF
Series P Installation & Maintenance Models: P-/5 P-/6 P-/4 P-/ P-/-HP P-3/4 P-3/4HP P- P- / P- P-3 P-5 P-7 / Materials: A - CPVC B - Polypropylene C - PVDF Introduction Penguin Pumps are designed to handle
More informationSMHA Hatch High temperature fan HT-fan Installation and Maintenance
High temperature fan HT-fan Installation and Maintenance 22.8.2012 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance
More informationEBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL
EBAC MODEL CD425 (1018110) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com
More informationSpecifications Information and Repair Parts Manual 316A-95, 316B-95, 393A-95, 393B A-95 thru 394D-95, 399A-95
Specifications Information and Repair Parts Manual 316A-95, 316B-95, 393A-95, 393B-95 394A-95 thru 394D-95, 399A-95 Please read and save this Repair Parts Manual. Read this manual and the General Operating
More informationMACHINE SHOP ACCESSORIES CLEVER, TIME-SAVING PRODUCTS TO MAKE YOUR LIFE EASIER
MACHINE SHOP ACCESSORIES CLEVER, TIME-SAVING PRODUCTS TO MAKE YOUR LIFE EASIER ROYAL R8 QUICK-CHANGE TOOLING SYSTEM Unit only protrudes 11 8" beyond spindle. 1. Loading the Quick-Change Body into a standard
More informationIMPORTANT SAFETY INSTRUCTIONS
Power Shovel Form No. 3362-567 Rev A Model No. 38361 Serial No. 310000001 and Up Operator's Manual If you have questions or problems, call toll free 1-800-808-2963 (US) or 1-800-208-3072 (Canada) before
More informationR10S, R10D, R10P & R10SAND. Owner s Manual
R10S, R10D, R10P & R10SAND Owner s Manual . Contents Getting Started Important Safety Instructions 2 Polarization Instructions 3 State of California Proposition 65 Warnings 3 Description of the Vacuum
More informationOil burners fuel unit with solenoid valve
Oil burners fuel unit with solenoid valve Type VM www.deltapumps.com VM1 - VM4U flanged Certified Quality System Printed in Germany VM_e.pdf - 18.05.08 Page 1/6 Oil burners fuel unit with solenoid valve
More informationSTORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE
ISO 9001 : 2000 STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE CUSTOMER : 1 CONTENTS 1 SAFETY... 5 1.1 General... 6 1.2 Description of symbols and pictograms... 6
More informationINLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL
INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL CONTENT 3 Introduction 3 General 3 Safety rules 3 Storage and transportation rules 3 Manufacturer s warranty 4 Fan design 4 Delivery set 5 Technical data
More informationECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance
TOP ECOSMART TWINFANS (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use Installation and Maintenance The EMC Directive 2014/30/EU The Low Voltage directive 2014/35/EU INDOOR USE ONLY Introduction
More informationOil burners fuel unit with solenoid valve
Oil burners fuel unit with solenoid valve Type VM www.deltapumps.com VM1 - VM4U flanged Certified Quality System Printed in Italy - DE112/0404 Oil burners fuel unit with solenoid valve Type VM The DELTA
More informationAZN ATEX INSTALLATION AND MAINTENANCE
ZerAx AZN ATEX INSTALLATION AND MAINTENANCE 924714-0 English 924714-0 GB ZerAx axial flow fans type AZN ATEX Installation and maintenance 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Temperature
More informationCODE MODEL TYPE PRESS 60 N 616 T PRESS 60 N 616 T80
Installation, use and maintenance instructions Heavy oil burner CODE MODEL TYPE 3434985 PRESS 60 N 616 T80 3434986 PRESS 60 N 616 T80 291 (2) - 01/2009 Thermal power - Output Operation Fuel Electrical
More informationICED CAPPUCCINO MACHINE Taylor MODEL: 390
4.8.6.3 ICED CAPPUCCINO MACHINE Taylor MODEL: 390 LOCATION: Front of House WHEN CLEANED: Daily, Weekly, Monthly, Seasonal TOOLS/SUPPLIES REQUIRED: Salmon Cloth 2 or 3-Compartment Sink Sink Detergent Sanitizer
More informationECOSMART XTRACTOR. (ESX-X/R/B) 1 phase, Direct Drive For External, Roof Mounted and Internal use Installation and Maintenance.
ESX-X Figure 1. ESX-X units. Removable top panel A D Control module located internally External Commissioning box Table 1. ESX-X Dimensions (mm) Spigot Weight Code A B C D dia (kg) ESX1-X 705 505 355 125
More informationp Permanent magnet water cooled motors Additional manual
p Permanent magnet water cooled motors Additional manual Safety Instructions 1 General General safety regulations, safety precautions and specific agreements made for each work site shown in this document
More informationMC-V Vacuum Cleaner. Specifications are subject to change without notice for further improvement.
Order Number MAC0507002C1 Vacuum Cleaner MC-V5210-00 Specifications are subject to change without notice for further improvement. 2005 PANASONIC HOME APPLIANCES COMPANY OF NORTH AMERICA, DIVISION OF PANASONIC
More informationQUICK PRIME INSTALLATION AND SERVICE MANUAL
QUICK PRIME INSTALLATION AND SERVICE MANUAL NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system. Part #
More informationOil TRIANCO. EuroStar Range BURNER DETAILS TRIANCO - OIL BURNER. To be retained by householder
TRIANCO Oil TRIANCO - OIL BURNER BURNER DETAILS EuroStar Range To be retained by householder TECHNICAL DATA NOZZLE OUTPUT MODEL Output Burner Nozzle Pump Model pressure CO 2 (%) EUROSTAR UTILITY 50/65
More information