Centrifugal Fans maintenance manual

Size: px
Start display at page:

Download "Centrifugal Fans maintenance manual"

Transcription

1 Centrifugal Fans maintenance manual

2 Contents 1 Safety Explanations Basic safety rules Noise level General Fan types Use types Rotational and blow directions Wing types Accessories Sensors The marking of the fan Installation Dimensions, weight and lifting instructions The beam frame Concrete base Operating conditions Storage The introduction of the fan Introduction Start-up Monitoring during the operation Vibration Noise Bearing sound Vibration dampers Drive belt Flexible connectors Hub seal Maintenance Impeller General Impeller installation

3 4.1.3 Removing the impeller Bearings General Lubrication Lubrication intervals and amount of grease Electric motors Electrical connections Hub seal Switch V-belts Troubleshooting Maintenance intervals

4 1 Safety 1.1 Explanations The manual contains warnings. They indicate hazards that can cause injury and the likelihood of their occurrence. The warnings are divided according to the severity: DANGER! Warning! and Important! DANGER! Means the accident, which in case of non-compliance with the instructions will result in serious injury Warning! Means that an accident may occur, resulting in serious personal injury if the instructions are not followed Important! Means that an accident may occur, which results in personal injury or property damage Note! Means operational interference or damage due to improper use 1.2 Basic safety rules The use of the machine correctly and in the right circumstances guarantees the safe operation of the fan. The fan should be used only for the purposes for which it is made and the user must follow the general safety precautions. The fan should also be installed in accordance with the instructions. The fan is manufactured in compliance with safety standards, marked with the CE mark and is supplied with a declaration of conformity. Improper use may result in accidents and/or cause damage to the device. o the fan may only be used in its intended conditions o safety devices of the fan must not be removed under any circumstances and do not reach behind the protective covers o precaution of moving parts o the fan may only be maintained by the professional specialized to provide service o the fan must not be used for moving another kind of air or gas than what it is made to move o after maintenance, always check the structures and all the protective covers o the user must have the appropriate protective equipment 4

5 o after service all bolts and nuts should be checked, as well as their tension o Do not exceed the maximum speed specified for the fan 1.3 Noise level EU Machinery Directive 89/392/EEC requires a one-meter distance from the measured sound pressure and sound power level. Maximum sound pressure is measured at the front of the suction side. The sound power level is defined as the measurement methods BS 848 and VDI Sound pressure and power levels are indicated on the base of the fan case. 5

6 2 General This document contains the most common maintenance procedures of the product, instructions for proper use and safety instructions. These instructions are designed to ensure an efficient, correct and safe operation of the fan. Proper maintenance and operation extend the life cycle of the fan. Service documentation must be kept with the product, or in its vicinity, so that it will be easy to find. 2.1 Fan types The fans are classified according to the operating and the impeller type as well as the rotation and air flow direction of the fan Use types The impeller is mounted on the motor shaft (use Type-S), which is sometimes also called a direct-driven fan. In the belt driven fan (the use of type-h), engine power is transmitted to the impeller shaft using a V-belt. The motor is attached by the adjustment rails to the stand. In a switch operated fan, (use type-k) the power transmission is performed by the switch connecting the motor and impeller shafts and with the impeller shaft with separate bearings. 6

7 2.1.2 Rotational and blow directions When determining the blowing direction, the fan is considered from its operating side. The direction is shown in accordance with the drawings with letters indicating the direction of rotation (RD impeller rotates clockwise or LG impeller rotates counter-clockwise) and with numbers that indicate the angle between the air flow direction and the vertical Wing types direction in degrees. If the main directions indicated in the figure cannot be used, the fan may be produced to set any intermediate direction. The direction and the shape of the impeller blades influence the different characteristics of the fan. These characteristics are the yield of pressure and volume, the efficiency and the volume flow rate. The choice of the wing type also affects the particles moving with the gas entrained. 2.2 Accessories The instructions and documents of the accessories such as sensors, dampers, guide vane controls, vacuum boxes and engine accessories are submitted on a case by case basis. 7

8 2.2.1 Sensors The validity of the fan warranty requires the connection of the condition monitoring sensors supplied as the accessories of the fan and introduction of surveillance. The "standard" surveillance packet offered for fans as an option, contains at least one rotation monitor, one vibration monitor, two temperature sensors + converters and four 5 m extension cables. Upon the request of the customer, condition monitoring may be larger. Condition monitoring sensors as standard equipment are for the fans with oil lubricated bearings or the engine power of 250 kw and upwards. Oil lubricated bearings are always equipped at least in the impeller end bearing with vibration measurement and both bearings with temperature measurement (oil lubrication sensor packet includes VKV021, two TS229, two TP3237 and three EVC005). Fans equipped with motors of 250 kw and above include as standard accessories in addition to bearings monitoring (vibration and temperature monitoring in both bearings), also vibration and temperature monitor on D-end of the motor. Temperature sensor TS2229 Measurement signal converter Vibration guard Plug connector/cable 5m EVC005 TP3237 VKV021 Rotation monitor The speed monitor is DI6001 [M18] (if necessary, the DI5003 [M30] can also be used). In case of separate bearings (vertical bearing housings) the sensor is most commonly mounted between the bearings and the output gauge is attached to the shaft with a compression fitting. The sensor bracket is bolted to the base and the sensor is mounted so that the clearance between the output gauge is 6 mm (DI mm). 2.3 The marking of the fan In each fan is a shield, which is marked with the required information about the fan. The fan has an alphanumeric code that indicates the type of fan. The shield also indicates the year of manufacture, the serial number and the fan performance values. The shield also bears the CE marking. For example, DCKE-40/2-j-k RD90 8

9 DC Affix which is not relevant (Dust Control) KE K = marking of the series on the fan (M, D, E, H, B, C or D), E =wing type (E, T, S or L) -40 Nominal size of the fan / 2 Narrowing, if you have a narrowed impeller (/2 or /3) -j Included, if the fan has a cooling disc -k Type of use (-k = switch,-s = impeller on the shaft of The motor, -h = belt (not marked in the name)) RD Rotation direction (RD or LG) 90 Blow direction (0-359, 0 is up) W In belt drive motor position (W or Z) 2.4 Installation Dimensions, weight and lifting instructions Fan-specific assembly drawing includes dimensions, weight data and lifting instructions. Permitted lifting points are marked on the fan The beam frame The centrifugal fans are mounted horizontally on vibration dampers. Dampers should be installed only when the fan is at the level of the installation, in order to prevent damage to the dampers in the context of the drop, the Dampers should be able to flex freely. The sag is determined according to the damper type, for example, LV 10/200 will sag under load mm (75-90% of 10 mm), and deflection should be the same + / - 1 mm between all the dampers. 9

10 2.4.3 Concrete base If the fan is mounted on a concrete base, it needs case bushings and a levelling partition if the base is not smooth enough. When the installation is clear, the concrete mixture is cast under the mounting flange. When the concrete mixture has dried, the bolts are tightened. 2.5 Operating conditions Operating conditions of a fan are largely determined by the choice of manufacturing material, surface treatment, outfitting and structure of the fan. As a result, the fan may only be used for the specified application/conditions. The fan is to be placed in a warm and dry internal space ( C), which is free from condensing, unless otherwise agreed with the fan manufacturer. Corrosives, high temperature, solids and external constraints such as air humidity can weaken the parts of the fan. If the operating conditions are different from normal, the fan has to be originally designed for use in these abnormal circumstances. 2.6 Storage Fan and motor must be protected from moisture and dust. Large temperature changes should be avoided. Otherwise, damage can occur to the electric motors, plastic fittings and bearings, painted surfaces or seals. All materials are not weather resistant. Suction and discharge openings must be closed during storage. Prolonged standstill may affect the lubrication properties of grease or oil. Corrosion may also affect the bearings. Certain components, such as bearing seals and V-belts in belt-driven fans can become brittle over time. The fan should be used at least about 10 min monthly. If this is not possible, it is recommended to rotate the impeller by hand. This maintains the operational condition of the bearings. 10

11 3 The introduction of the fan 3.1 Introduction 3.2 Start-up 1. Check the fan and motor mounts to the frame, anti-vibration mounting to the base, the suction and discharge opening connections to the duct and check the tightness of the bolts. 2. Check the belt guard or the connection guard mounting and clearance (at least 10 mm) in relation to the moving parts. 3. Check that the direction of rotation of the fan (motor) and the direction of the gas flows are in the direction of the arrows on the casing by switching on the fan for a while. 4. Check the fan bearings. If there is reason to suspect that condensation of water has entered the bearings e.g., during storage, the bearing is to be opened, cleaned and re-greased. 5. Check all guards and protective covers. 6. Check that there is nothing inside the fan. When starting cold a fan which carries hot gas, its power consumption is considerably greater than the operating conditions. If power consumption is determined in accordance with the operating conditions, the fan is to be started against the closed damper or regulator. The damper or regulator is gradually opened to the run position along with the increase of the gas temperature. 3.3 Monitoring during the operation In order to avoid the switch and motor load and overheating it is recommended up to four starting times per hour, unless otherwise specified in the documentation. Between start-up times should be at least ten minutes of cooling time. Excess vibration or noise are the signs of a faulty operation, in which case the operation of the fan is not allowed to continue until the fault is cleared and repaired Vibration Vibration is a significant factor in terms of performance and life-cycle of the fan, which is why vibration control is very important. Vibration can cause cracks, bearing failures, bolts loosening and noise. Periodic vibration measuring is recommended. Vibration is a great gauge of condition monitoring. The machine's operations can extensively be interpreted on its basis. For critical needs, tough conditions or larger than 50kW fans we recommend continuous vibration monitoring equipment. 11

12 Vibration can be caused by wear of the impeller, dirt accumulated in the impeller, contact of moving parts with other parts or an imbalance caused by the alignment of the fan. Good tools for vibration measurement are, for instance, the SPM Leonova Infinity or SPM Bearing Checker. Dust Control Systems Oy manufactured impellers are balanced dynamically according to ISO 1940 class Q 6.3. In operating conditions the fan vibration stress value must stay below the value of alarm limit. Once the value of alarm limit is exceeded, the impeller cleaning and bearing checking must be carried out as quickly as possible. If these measures do not help, the impeller must be re-balanced or other vibration removing repair must be performed. It is advisable to discontinue the use of the fan and to contact the manufacturer of the fan if, on use, the vibration stress values exceeds the value of trigger limit. If the reason for vibration is not recognized with certainty and are determined to be harmful, the fan cannot be used when the trigger limit is exceeded. Measurements are performed according to ISO standard, within the fan operation rotation frequency. The following table applies to fans that are equipped with vibration dampers (flexible platform). Specific instructions are presented in separate annex Sensor limits, or in separately defined fan-specific instructions. Assessment of fan vibration stress values (v r ms ) according to standard ISO Coupling operated/ Impeller mounted Belt operated on the motor shaft Trigger limit Alarm limit Noise The fan causes noise while operating. Noise levels and the frequency depend largely on the size and structure of the fan. The noise does not always reflect a defect in itself. If excessive fan noise becomes apparent during operation or some extra sound occurs, it may be a sign of a malfunction. In certain circumstances, the clearance between bearings may cause a rattling sound if the bearing temperature rises. 12

13 Bearing operating temperature is affected by the speed and environmental conditions. The maximum permissible operating temperature depends on the bearing structure, the used lubricant and the length of lubrication intervals. Normally, the greased bearing temperature must not exceed 65 C, measured from bearings housing, and never 110 C, measured from bearing. The rise of temperature may be due to a faulty bearing, lack of lubrication, or too generous amount of lubricant Bearing sound The bearings sound can be heard and measured with devices separately manufactured for this purpose. Vibration level measurement and measurement with bearings test devices are the right way to distinguish between the sound caused by the failure of the structure Vibration dampers Check that the dampers are in good, working order and evenly loaded. In addition, the dampers must be able to flex freely Drive belt Check the amount and tension of belts. Typically, stretched and worn belts vibrate and make a noise Flexible connectors Installation instructions and tolerances for the connectors are in the annex Hub seal The fan may be provided with a hub seal used for sealing of the impeller hub and the fan casing bushing/joint. If discharged gas leaks from the joint inside the fan, it is advisable to check the sealing operation. 4 Maintenance Service date and the length of the maintenance periods are determined by the maintenance and repair needs. Sufficient spare parts must be available. The attached table of the most common service and maintenance work periods. 13

14 4.1 Impeller General If the fan operates with exhaust gas or in dust containing air, or if in the impeller has been formed a deposit or unusual wear, it may cause a balance disorder. This can result in damage to the bearing or impeller failure. Impeller cleaning is carried out with a wire brush or scraper. The loose dirt should be removed from the fan housing before the fan is restarted. For inspection and cleaning of the impeller, in the fan casing is usually an inspection hatch. A worn impeller must be replaced or repaired by welding. After welding, the repair of the impeller is to be balanced again. Measure the vibration level from the frame of the motor and from each of the bearing housing, from three different directions Impeller installation Follow the instructions concerning the coupling and belt operated fans. If the fan has a V-grooved hub, its fitting is carried out by tightening against the shaft shoulder and preventing opening of the screws of the locking plate, for example, by welding the screw into the locking plate. 1. Remove cover and clean the impeller and shaft contact surfaces thoroughly. Detailed instructions are in the Annex labelled installing the clamping sleeve (EX- and SKF SHT- sleeve). 14

15 2. Set the friction joint sleeve in place so that the bolt positions do not exceed the front edge of the hub. 3. Place the impeller into the shaft. Make sure that the friction joint sleeve is still in place in the depth direction. It is recommended to install impeller with fan-specific impeller lift tool (available as accessory, with additional assembly drawing in fan-specific documentation). 15

16 4. Fit the inlet cone and check whether it fits into the place. Tighten the bolts of the friction joint sleeve according to the tightening instructions. The friction joint sleeve tightening instructions are attached. To achieve the right connection, tightening is to be carried out on all the bolts several times by gradually tightening each bolt in turn, until tightening the last bolt no longer loosens the first tightened bolt and the torque prescribed by instructions has been reached. 5. On the inner surface of the outer rim of the front panel of the fan are adjustment screws for the inlet cone position. 16

17 6. Attach the inlet cone bolts and tighten them to the desired torque. 17

18 4.1.3 Removing the impeller EX Place heat-resistant silicone (e.g., Super RTV silicone, red C) between the surfaces of the impeller hub plate and the impeller hub and attach the hub plate evenly by tightening the torque. Remove the screws and screw them into the pull-out threads of the outer ring so that the inner ring is released and the sleeve comes off. Remove the screws from the pull-out threads only when the sleeve is removed from the hub. EX-60 Method 1: Remove the screws and screw them into the outer ring pullout threads and release the ring. Method 2: Remove the screws to the pull-out threads of the central flange and release the rear inner ring SKF SHT Detachment instructions in separate annex. V-grooved hub Remove the locking plate and pull the impeller off with a wheel puller. Sometimes, the impeller is so rugged that the damage of the shaft cannot be avoided. A damaged shaft must be replaced. 18

19 4.2 Bearings General The bearing types used in the fans produced by Dust Control Systems Oy are generally spherical ball or roller bearings and toroid bearings. They are attached to the shaft with a clamping sleeve. There are two bearings, one of which receives the compression load. This bearing locked to the axial direction must be marked when both bearings are replaced at the same time. In the fans are used mainly two vertical bearing housings (separate bearings), which are SKF manufactured SNL or SONL-bearing housings or ConCentra bearing units. SNL and ConCentra bearing housings are lubricated with grease and SONL bearing housings are lubricated with oil. ConCentra units are designed to facilitate installation and maintenance. ConCentra bearing units are assembled, greased and pre-sealed. ConCentra advantages include easy installation, longer service life, greater reliability and easy maintenance. In DCS fans are used ConCentra SYNT bearing units. ConCentra bearing units are used in small and medium-sized fans. DCS fan bearings are always determined in fan case bases taking into condition the design input data and the fan operating conditions to achieve optimal serviceability and reliability. The bearings must be handled with care and must be protected from dust and moisture. The bearings are therefore kept in the original packaging, which should be opened only upon installation. The rust-preventive agent in the new bearings does not need to be removed, if the bearing has not been contaminated. For cleaning of bearings use a white spirit or a similar detergent. After washing, the bearings are lubricated with oil immediately. The shaft pins, bearing housings, etc., must be thoroughly cleaned and soaked in oil prior to installation. Taper bushing surfaces must be only lightly lubricated. Achieving a suitable interference fit may otherwise be impaired. After installation, oil must also be entered into the bearings, in order to avoid dry running at start-up. After lubrication and the installation of the bearings, a test run is carried out, during which is monitored the temperature rise and operating noise of the bearings. 19

20 General installation instructions of the separate bearings are in the annex Installing and removing separate bearings. Temperature guard limits are presented in annex Sensor limits. Detailed installation instructions for different bearing and housing types can be found on the manufacturer's website Dust Control Systems Oy will assist in the acquisition of more detailed instructions Lubrication Before maintenance and repair measures, stop the fan from the maintenance switch and make sure e.g., by written notice or with a switch lock that the fan is not started accidentally during maintenance. Ball and roller bearings are usually greased (SNL bearing housings). Oil lubrication is used in special cases, such as when the speed is too high for greasing or if the bearings need cooling (SONL-bearing housings). Grease-lubricated bearing housings are equipped with grease nipples, from which grease is pressed in by a grease gun. If the bearing housings have to be replaced, make sure that the grease nipple place is positioned so that the grease can migrate into the bearing. For the first lubrication of fan-axis grease-bearings, grease type and amount is shown in the main assembly drawing. If the fan is not used for 20

21 a long period of time, add grease and check the condition of seals visually from time to time. In lubricated bearings there is an external level gauge, from which can be checked the oil level and visually also pollution. In the oil compartment is the so-called quit, which also splash lubricates the upper part of the bearing. The addition of oil is done through the hole in the cover of the bearing housing. At the bottom of the bearing housing has a plug from which the oil is retrieved if necessary. Clean the bearing housing and grease nipples before lubrication, so that no dirt reaches the bearing with grease. Too large amount of grease in the bearing housing can cause a sharp rise in temperature and bearing damage. Different types of oils should not be mixed with each other! Operating conditions are significantly associated with the choice of oil type. The user should pay particular attention to the final selection of the oil suitable for the purpose! On inquiry, the manufacturer will provide detailed instructions on the matter Lubrication intervals and amount of grease Lubrication interval depends on the rotational speed (n), the bearing structure and the size (d = bearing bore diameter). With grease-lubricated bearings, re-greasing interval is shown at the type shield (located at the fan base), and in bearing assembly drawing. With oil-lubricated bearings, Fuchs Renolin B15 (ISO VG 46) oil is normally used as first-fill oil. First-fill oil is recommended to be exchanged for the first time already after a few hours of operation, so that the potential impurities in the oil compartment can be removed. Fuchs Renolin B20 (ISO VG 68) or B15 (ISO VG 46) oil is normally used after first-fill oil. However, all fans and working conditions are individuals, so oil-types and oil-change intervals must be examined individually. Contact manufacturer for more info. More about lubrication of bearings and lubrication intervals can be found in the manufacturer's website ( 21

22 4.3 Electric motors Start-up and maintenance is done in accordance with the instructions prepared by the manufacturer of the motor. In the protection of the motor, the frequency converter enabled protections such as overload, over-current and stall protection, pump and fan applications, as well as the squared load must be taken into account. For more detailed maintenance and lubrication instructions, see the engine manufacturer's maintenance instructions. Instructions comes along the motor, and can also be found in the web site of the manufacturer of the motor. For the electric motor s re-lubricated bearings, first-lubrication must be performed during commissioning. First-lubrication must be performed according to motor manufacturers instructions. 4.4 Electrical connections Electrical work must only be performed by qualified personnel on machines when switched off, the power supply off and restart disabled. Electrical wiring to the motor must be flexibility so that any moisture does not enter the switch box. In addition, the fan should be equipped with the so-called maintenance switch. In the switching, installation and cable selection must be taken into account the frequency converter manufacturer's and the motor manufacturer's instructions for the approved implementation, which will prevent possible bearing damage. 4.5 Hub seal Normally a Teflon produced booklet type sheet ring seal which is compressed into the rear wall of the casing is used as a hub seal. In more demanding applications a tape box seal can be used wherein the sealing is achieved by graphite tape squeezed into the packing. Over time, the tape box may need to be tightened so that the graphite tape remains sufficiently tight. Clamping nuts should not be tightened all the way, because then the tape will tighten too tightly and create too much heat. The cover part of the box is tightened and at the same time the shaft is rotated by hand until resistance is felt on the shaft. Tightening nuts are locked with the lock thread, so that they do not open during operation. In the Purso air box, gas is conducted into the box to prevent the gas leaking from the inside of the casing from coming out. Different types of slip-ring seals are also possible to use. 22

23 If the hub seal will have to be adjusted, the cooling disc guard as well as the cooling disc must be removed, so you can access the hub seal. Sealing type is presented in fan-specific main assembly drawing. 4.6 Switch 4.7 V-belts Detailed instructions for installing the switch are attached. Detailed instructions for installing V-belts are attached. 23

24 5 Troubleshooting Problem Cause Solution Rattle Wear of propeller blade Check/Change Smudging of the propeller blade Loose/Worn bearnings Loose parts Contact of moving parts Alignement errors Worn rattle dampers Instable installation location Twisted shaft Environment caused rattle Improperly installed flexible connector Clean with the steel brush Check/Change Check the mounting of the parts Check the mounting of the parts Realignement Check/replace Check/replace Check/replace Check instllation/installation location Check installation Noise Abrasive parts Check the mounting of the parts Loose parts Improperly installed bearing Excessive/improper lubrication Improperly installed flexible connector Check the mounting of the parts Check installation Check/remove the excessive lubricant Check installation Improper performance Wrong rotation direction Check Damaged flexible connector Improperly installed flexible connector Worn propeller blade Wrong rotation speed Check/repair Check installation Check/replace Check/adjust 24

25 6 Maintenance intervals Check the condition of the guards Check the condition of the flexible connections Check the condition of the accessories Check the condition of vibration absorbers In case of oil lubrication, check the oli level Make sure that the rattle of the fans has not increased Make sure that the fan does not emit abnormal noises Short explanation of maintenance works. Weekly visual check of all the appropriate parts. Also we recommend check coupling, belt parts and belt tightness, bolt tightness, impeller condition and cleaniness, bearing and motor bearing lubrication in 3 month intervalls. Recommended service intervals are part of the preventive maintenance program, the purpose of which is to prevent the breaking down and to predict failures. Compliance with maintenance intervals gives the customer valuable information about fan service, which can be used as part of the company's own maintenance. 25

English CNA-CNB. Centrifugal fans Installation and maintenance

English CNA-CNB. Centrifugal fans Installation and maintenance 916505-0 English CNA-CNB Centrifugal fans Installation and maintenance 916505-0 GB Centrifugal fans types CNA, CNB, CNA-M and CNB-M installation and maintenance 1. Application 2. Handling 2.1 Marking 2.2

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended

More information

AXPR Wall Mounted Axial Panel Fans

AXPR Wall Mounted Axial Panel Fans Bulletin 78-January-03-06 AXPR Wall Mounted Axial Panel Fans INSTALLATION, OPERATION, AND MAINTENANCE MANUAL This publication contains the installation, operation and maintenance instructions for the AXPR

More information

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE 2 GLEC-6 - Installation and maintenance CONTENTS 1 Important information... 3 2 Safety notes... 3 3 Technical description...4 4 Transport... 6 5

More information

GLEB Kitchen exhaust fan

GLEB Kitchen exhaust fan GLEB Kitchen exhaust fan Installation and Maintenance??.1.2013 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

Montageanleitung RLO (Original) Mounting Instructions RLO (Translation of the original)

Montageanleitung RLO (Original) Mounting Instructions RLO (Translation of the original) Montageanleitung (Original) (Translation of the original) DE MA_ 1.0 06/2014 Taperlock Clamping-bush system _0 _1 Fixed hub Inlet nozzle with IMV 1. Revision index Revision Date MA_ 1.0 06/2014 2. Safety

More information

ACN SMOKE INSTALLATION AND MAINTENANCE

ACN SMOKE INSTALLATION AND MAINTENANCE NovAx ACN SMOKE INSTALLATION AND MAINTENANCE 918149-0 English 918149-0 GB Installation and maintenance NovAx smoke exhaust fan type ACN smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport

More information

AZN ATEX INSTALLATION AND MAINTENANCE

AZN ATEX INSTALLATION AND MAINTENANCE ZerAx AZN ATEX INSTALLATION AND MAINTENANCE 924714-0 English 924714-0 GB ZerAx axial flow fans type AZN ATEX Installation and maintenance 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Temperature

More information

Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke

Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke 918149-0 GB Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport 3. Storage 4. Installation 4.1 Prior to attachment 4.2 Attachment

More information

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2 Cleaning unit for coolant :_decftez`_>r_fr] Book No.: 1271526-02 V2 Alfa Laval Separation AB Separator Manuals, dept. SKEL S-147 80 Tumba, Sweden Telephone: +46 8 53 06 50 00 Telefax: +46 8 53 03 10 40

More information

A Fläkt Woods Company 2933 Symmes Road, Fairfield, Ohio Phone: (513) Fax: (513)

A Fläkt Woods Company 2933 Symmes Road, Fairfield, Ohio Phone: (513) Fax: (513) A Fläkt Woods Company 2933 Symmes Road, Fairfield, Ohio 45014-2035 Phone: (513) 874-2400 Fax: (513) 870-6249 JM AEROFOIL FANS Installation, Operation and Maintenance Instructions Site Storage The fan must

More information

SMHA Hatch High temperature fan HT-fan Installation and Maintenance

SMHA Hatch High temperature fan HT-fan Installation and Maintenance High temperature fan HT-fan Installation and Maintenance 22.8.2012 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

XC-18. NOTE: *Machine shown without Lift-Up Safety Guard. This guard is included with machine. Machine should not be operated without this guard.

XC-18. NOTE: *Machine shown without Lift-Up Safety Guard. This guard is included with machine. Machine should not be operated without this guard. XC-18 NOTE: *Machine shown without Lift-Up Safety Guard. This guard is included with machine. Machine should not be operated without this guard. EXTREMA MACHINERY COMPANY, INC. PO BOX 1450, ALBANY, LOUISIANA

More information

GLEB. >> Installation and Maintenance. Air Comfort. Air movement. Duct & Box Fans

GLEB. >> Installation and Maintenance. Air Comfort. Air movement. Duct & Box Fans Air Comfort Air movement Duct & Box Fans GLEB KITCHEN exhaust FAN >> Installation and Maintenance Kitchen Exhaust Fan GLEB Installation and Maintenance Important Information, Safety notes, Technical Description

More information

STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE

STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE ISO 9001 : 2000 STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE CUSTOMER : 1 CONTENTS 1 SAFETY... 5 1.1 General... 6 1.2 Description of symbols and pictograms... 6

More information

FAN ENGINEERING. Sealing of Fan Housings

FAN ENGINEERING. Sealing of Fan Housings FAN ENGINEERING Information and Recommendations for the Engineer FE-700 Sealing of Fan Housings Introduction A variety of options are offered by fan manufacturers to seal fan housings. Sealing the housing

More information

VETO CLEANER 500 FLUE GAS CLEANER

VETO CLEANER 500 FLUE GAS CLEANER As of serial number 3100 0001 VETO CLEANER 500 FLUE GAS CLEANER USER MANUAL SPARE PARTS LIST Manufacturer: ALA TALKKARI Veljekset Ala-Talkkari Oy FI-62130 HELLANMAA TEL. +358 6 433 6333 FAX +358 6 437

More information

This label warns for risk of electrical shock when failing to observe.

This label warns for risk of electrical shock when failing to observe. MANUAL horizontal centrifugal pumps MB series ic drive SB series mechanical seal 1. Introduction 2. Safety precautions 3. Receipt 4. Installation / Operation and Maintenance 4.1 Installation 4.2 Operation

More information

Indholdsfortegnelse. Danvent Air Handling Units SERVICE MANUAL

Indholdsfortegnelse. Danvent Air Handling Units SERVICE MANUAL Indholdsfortegnelse Danvent Air Handling Units SERVICE MANUAL Service Servicing of the Air Handling Unit Your ventilation system is equipped with a Danvent Air Handling Unit (AHU) which will contribute

More information

HT650 TM FAN DRIVE SERVICE INSTRUCTIONS

HT650 TM FAN DRIVE SERVICE INSTRUCTIONS HT650 TM FAN DRIVE SERVICE INSTRUCTIONS When unpacking your product, remove all components and inspect them to ensure that no damage occurred during shipping. If any components are missing or damaged,

More information

OWNERS GUIDE TO INSTALLATION AND OPERATION

OWNERS GUIDE TO INSTALLATION AND OPERATION OWNERS GUIDE TO INSTALLATION AND OPERATION SPM SERIES HIGH POWER CENTRIFUGALS READ THESE INSTRUCTIONS CAREFULLY Read these installation instructions in detail before installing your pump. Be sure to check

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS PART # 538 Model BCF Belt Drive Centrifugal Cabinet Fans Installation, Operation, and Maintenance Manual Please read and save these instructions for future reference. Read

More information

ultra quiet fan USER MANUAL INSTALLATION OPERATION MAINTENANCE

ultra quiet fan USER MANUAL INSTALLATION OPERATION MAINTENANCE USER MANUAL ultra quiet fan INSTALLATION OPERATION MAINTENANCE Z0414808 rev A ISSUED 02/2014 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. safety and handling Safety Warning

More information

Marley Ultra Quiet Fan

Marley Ultra Quiet Fan USER MANUAL Marley Ultra Quiet Fan DESIGNED FOR INDUCED-DRAFT COOLING TOWER APPLICATIONS M2012-1165 ISSUED 8/2012 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. safety and

More information

1. Description INSTRUCTION FOR BLAST COOLER TYPE COOL 250. Material

1. Description INSTRUCTION FOR BLAST COOLER TYPE COOL 250. Material 1. Description General The cooler is used for cooling of water, oil or other liquid by use of air. The liquid is passing in the tubes where it transfere the energy to the air via the fins on the outside

More information

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers Bulletin 1200/4 (Revised 5/12) Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers INNOVATORS IN HEAT TRANSFER I. INSTALLATION OF HEAT EXCHANGERS A. HEAT EXCHANGER SETTINGS 1)

More information

Technical Data. Name: ERIKA Automat fully automatic machine to divide and to round dough pieces of the same size

Technical Data. Name: ERIKA Automat fully automatic machine to divide and to round dough pieces of the same size AUTOMAT MANUAL 1 Technical Data Name: ERIKA Automat fully automatic machine to divide and to round dough pieces of the same size Type Divisions Dough Portions (in ounces) Plate Nos. 3 30 1.0 3.5 #35 4/40A

More information

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING USER S MANUAL VCU/ Series CENTRIFUGAL FAN IN SCROLL CASING 2 CONTENTS Introduction Use Delivery set Designation key Technical data Safety requirements Design and operating logic Mounting and set-up Connection

More information

DAGNY LK. Ceiling Mounted Rotational Fan READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 110V~60Hz

DAGNY LK. Ceiling Mounted Rotational Fan READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 110V~60Hz DAGNY LK Ceiling Mounted Rotational Fan READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 110V~60Hz Please do not use any electric or battery powered tools in the assembly and installation of this or any

More information

52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V.

52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V. Irene 52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V. 60Hz TABLE OF CONTENTS Tools and Materials Required... 1 Package Contents... 1 Safety Rules... 2 Mounting Options... 3 Hanging

More information

Industrivej 3-9 DK 9460 Brovst KEF-MOTOR A/S. Fax Instruction Manual PSD 200 Industrial Grinders

Industrivej 3-9 DK 9460 Brovst KEF-MOTOR A/S. Fax Instruction Manual PSD 200 Industrial Grinders KEF-MOTOR A/S Industrivej 3-9 DK 9460 Brovst Tlf. +45 9823 6088 Fax. +45 9823 6144 1. Instruction Manual PSD 200 Industrial Grinders EU declaration of conformity KEF-MOTOR A/S Industrivej 3-9 DK-9460 Brovst

More information

A. Codes and Standards that are Standard at the University:

A. Codes and Standards that are Standard at the University: PART 1: GENERAL 1.01 Purpose: 1.02 References: 1.03 Requirements: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The

More information

CENTAFLEX Series A Assembly and operating instructions CF-AR M EN Rev. 2

CENTAFLEX Series A Assembly and operating instructions CF-AR M EN Rev. 2 Contents 1 General remarks... 5 2 Safety... 6 2.1 Safety remarks... 6 2.1.1 Signal words... 6 2.1.2 Pictograms... 7 2.2 Qualification of deployed personnel... 7 2.3 Intended application... 7 2.4 Application

More information

1. Description INSTRUCTION FOR AIR BLAST COOLER TYPE COOL 450

1. Description INSTRUCTION FOR AIR BLAST COOLER TYPE COOL 450 1. Description General The cooler is used for cooling of water, oil or other liquid by use of air. The liquid is passing in the tubes where it transfere the energy to the air via the fins on the outside

More information

MODEL 652A MODEL 654A MODEL 652A MODEL 653A MODEL 651A AURORA. 650 Series SINGLE STAGE SOLIDS HANDLING PUMPS

MODEL 652A MODEL 654A MODEL 652A MODEL 653A MODEL 651A AURORA. 650 Series SINGLE STAGE SOLIDS HANDLING PUMPS MODEL 652A MODEL 654A MODEL 652A MODEL 651A MODEL 653A AURORA 650 Series SINGLE STAGE SOLIDS HANDLING PUMPS WWW.AURORAPUMP.COM 2 AURORA 650 Series Single Stage Solids Handling Pumps Capacities to 2000

More information

Operating instructions

Operating instructions ebm-papst Mulfingen GmbH & Co. KG Bachmühle D-74673 Mulfingen Phone +49 (0) 793-0 Fax +49 (0) 793-0 info@de.ebmpapst.com www.ebmpapst.com CONTENTS. SAFETY REGULATIONS AND NOTES. Levels of hazard warnings.

More information

BLAST-IT-ALL BUMPER BLASTER

BLAST-IT-ALL BUMPER BLASTER LARRY HESS AND ASSOCIATES, INC 185 PIPER LANE / SALISBURY, NC 28147 PHONE: 1-800-535-2612 / FAX: 1-704-638-9311 WWW.BLAST-IT-ALL.COM BLAST-IT-ALL BUMPER BLASTER SUCTION BLAST CABINET NOTE: It is the responsibility

More information

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance

Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance 916503-0 GB Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance 1. Main components 2. Application 3. Handling 3.1 Marking 3.2 Weight 3.3 Transport 4. Storage 1. Main components: Types ARC,

More information

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL SWP (Models SWP08 through SWP20) OPERATION & MAINTENANCE MANUAL IMPORTANT! Read before proceeding! Read carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

568X, 587X, 588X Series

568X, 587X, 588X Series Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

COOLING SYSTEM 1. Section V CONTENTS DATA AND SPECIFICATIONS. Page. Fluid Fan Drive (Silent Flite) 3. Water Pump 4. Radiator 5

COOLING SYSTEM 1. Section V CONTENTS DATA AND SPECIFICATIONS. Page. Fluid Fan Drive (Silent Flite) 3. Water Pump 4. Radiator 5 Section V COOLING SYSTEM CONTENTS Fluid Fan Drive (Silent Flite) 3 Water Pump 4 Radiator 5 Water Temperature Gauge 6 Thermostat 7 Radiator Pressure Cap 7 Service Diagnosis 7 DATA AND SPECIFICATIONS COOLING

More information

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT Technical Data SD 4511A SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 TYPE T14 & T14D TEMPERATURE PILOT PRINTED IN U.S.A. SD 4511A/9811 5 13 /16 D 4 7 /8 1 13 /16 T14 PILOT

More information

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP WWPPCHLFT260 Instructions WWPPCHLFT260_Horizontal Multistage Centrifugal Pump_IB.indd 1 READ THIS MANUAL CAREFULL BEFORE INSTALL, START THE PUMP 1. Suction 2. Plug

More information

PLENUM FAN EQLK PLENUM FAN, DIRECT-DRIVEN

PLENUM FAN EQLK PLENUM FAN, DIRECT-DRIVEN EQLK, DIRECT-DRIVEN INSTALLATION AND MAINTENANCE INSTRUCTIONS Contents Page Installation options...... 2 Checks to be made prior to commissioning...2 Electrical connections.....2 Measures before starting.....

More information

INSTALLATION MANUAL FOR ROTARY TWIN LOBE (ROOTS) BLOWERS / COMPRESSORS

INSTALLATION MANUAL FOR ROTARY TWIN LOBE (ROOTS) BLOWERS / COMPRESSORS INSTALLATION MANUAL FOR ROTARY TWIN LOBE (ROOTS) BLOWERS / COMPRESSORS AIRVAC INDUSTRIES & PROJECTS CORPORATE OFFICE: H-2/111, SECTOR-16, ROHINI, DELHI-110 085 PHONE: +91-11-32958731, 27298061 FAX: +91-11-27298061

More information

Enviro KES INSTALLATON MANUAL

Enviro KES INSTALLATON MANUAL Enviro KES INSTALLATON MANUAL Spring Air Systems Inc., Oakville, Ontario Phone (905) 338-2999, Fax (905) 338-0179, info@springairsystems.com www.springairsystems.com KES Installation Manual. This publication

More information

IEC- Direct-driven radial fans with IEC-Standardmotor

IEC- Direct-driven radial fans with IEC-Standardmotor EHND / ERND / ERNE / Contents. / Page 1. / Safety... 2 2. / Description... 4 3. / Condition of use... 4 4., / Storage, Transport... 5 5. / installation... 6 6. / operation... 8 7. / maintenance... 9 8.

More information

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP)

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) Our Expertise, Your Air-Moving Solution ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) PART# 0601710001_rev_A INSTALLATION, OPERATION & MAINTENANCE MANUAL Please read and save these instructions for future reference.

More information

REF. NO Clamp Assembly 8 1 set Gasket (4 per set) S.S. Lock-washer 3/8 x 1/ Brass Impeller 3.

REF. NO Clamp Assembly 8 1 set Gasket (4 per set) S.S. Lock-washer 3/8 x 1/ Brass Impeller 3. 4.4 SUPPLY PUMPAK ASSEMBLY NOTE: This section applies only to systems, which include a supply pumpak. Only the H6, XA, and XC series systems contain a supply pumpak. If your system is a single zone, H6

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL

INSTALLATION, OPERATION & MAINTENANCE MANUAL CENTRAL FANS COLASIT LTD Unit 12A, Palmers Road, East Moons Moat, Redditch. Worcs. B98 0RF Tel: 01527-517200 Fax: 01527-517195 Edition 04_13 INSTALLATION, OPERATION & MAINTENANCE MANUAL CIV Fan Range Valid

More information

USER S MANUAL ATH WH220

USER S MANUAL ATH WH220 USER S MANUAL ATH WH220 INDEX INTRODUCTION... - 3 - General information s... - 3 - Description of pneumatic jack... - 4 - Operation of jack... - 5 - Technical data... - 6 - Dimension drawing... - 6 - INSTALLATION...

More information

10 and 12 Meat Slicer MS250 & MS300 Operating Manual

10 and 12 Meat Slicer MS250 & MS300 Operating Manual 10 and 12 Meat Slicer MS250 & MS300 Operating Manual Introduction Thank you for purchasing a Pantheon Catering Equipment product. In this booklet you will find instructions for safe operation so please

More information

INSTALLATION & OPERATING INSTRUCTIONS

INSTALLATION & OPERATING INSTRUCTIONS INSTALLATION & OPERATING INSTRUCTIONS WARNING RISK OF ELECTRIC SHOCK. CONNECT ONLY TO A CIRCUIT PROTECTED BY A GROUND-FAULT CIRCUIT-INTERRUPTER. THE UNIT SHOULD BE INSTALLED BY A QUALIFIED SERVICE REPRESENTATIVE.

More information

C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz

C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V. 60Hz Please do not use any electric or battery powered tools in the assembly and installation of this or any Matthews Fan Company

More information

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59 SOUND-INSULATED FAN OPERATION MANUAL _v.1(2)-en.indd 1 10.08.2015 15:20:59 CONTENT Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 3 Fan design 4 Delivery

More information

Fig. 1. Bottle Height---Top of bottle MUST be at this height or slightly higher.

Fig. 1. Bottle Height---Top of bottle MUST be at this height or slightly higher. P12 Corker Addendum: Setup and Maintenance Read this addendum and the MEP manual carefully before operating the corker. One person should be assigned to maintain the corker. Only this primary operator

More information

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT Carrier International Sdn. Bhd. Malaysia INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT 40LM 120-200 50Hz CONTENTS: Physical Data & Dimension 1-3 Safety Considerations 4 Rigging

More information

OPERATION AND MONTAGE MANUAL ROOF FANS

OPERATION AND MONTAGE MANUAL ROOF FANS NO RFEC/U/2017-1 (EN) (valid since 18.08.2017) ROOF FANS RF/EC...-... / RFV/EC...-... Venture Industries Sp. z o.o. is not responsible for any damage caused by improper use of the fan and reserves the

More information

57" Fiberglass Exhaust Fan with Cone

57 Fiberglass Exhaust Fan with Cone OPERATORS MANUAL Fiberglass Exhaust Fan IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble, install, operate or service the product described. Failure

More information

Part 2: Installation Instructions cl

Part 2: Installation Instructions cl Contents Page: Part 2: Installation Instructions cl. 381-382 1. Delivery scope............................... 3 2. General and Transportation safety precautions........... 3 3. Stand installation 3.1 Installing

More information

DS series STERLING PUMPS. Industrial End Suction Pumps ISO/DP

DS series STERLING PUMPS. Industrial End Suction Pumps ISO/DP DS series Industrial End Suction Pumps ISO/DP 5199 www.sterlingpumps.com.au DS series Capacities from: Heads from: 340 to 5,680 m3/h (1,500 to 25,000 USPGM) 21 to 106 metres (70 to 350 feet) Power range

More information

Owner's Manual. Please read this document carefully before installing and/or using your vacuum cleaning system.

Owner's Manual. Please read this document carefully before installing and/or using your vacuum cleaning system. Owner's Manual for household use only Please read this document carefully before installing and/or using your vacuum cleaning system. Model : Serial No : Important Safety Instructions When using an electrical

More information

Panel Fan Series Operators Manual (Galvanized and Polymer)

Panel Fan Series Operators Manual (Galvanized and Polymer) Panel Fan Series Operators Manual (Galvanized and Polymer) 52" Belt Drive, Galvanized Panel Fan with Three Wing Blade IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before

More information

BELT DRIVEN STATIONARY AGITATOR

BELT DRIVEN STATIONARY AGITATOR BELT DRIVEN STATIONARY AGITATOR INSTRUCTION MANUAL www.usfarmsystems.com 2955 S. K Street Tulare, CA. 93274 (559)685-0340 (800)811-9462 Fax (559)685-9160 Revision Date 9/7/2017 TABLE OF CONTENTS How to

More information

Tornado Operations & Maintenance Manual

Tornado Operations & Maintenance Manual TORNADO INDUSTRIES 7401 W. LAWRENCE AVENUE CHICAGO, IL 60706 (708) 867-5100 FAX (708) 867-6968 www.tornadovac.com Tornado Operations & Maintenance Manual MODEL NO. 99690 BD 22/14, 99720 BD 26/14 L9722

More information

MNEFDD54 & MNBCDD54 GALVANIZED WALL FANS Installation, Operation, and Maintenance Instructions

MNEFDD54 & MNBCDD54 GALVANIZED WALL FANS Installation, Operation, and Maintenance Instructions FARM PRODUCTS DIVISION MEMBER OF AMCA AMERICAN COOLAIR CORPORATION P.O. BOX 2300 JACKSONVILLE, FLORIDA 32203 PHONE (904) 389-3646 FAX (904) 387-3449 E-MAIL - fans@coolair.com MNEFDD54 & MNBCDD54 GALVANIZED

More information

Linear drive component Maintenance

Linear drive component Maintenance 1 P age Service and Maintenance Caution (1) Maintenance shall be performed by qualified personnel. (2) Switch off the main power supply before servicing. If power supply is needed, have qualified personnel

More information

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Construction Standards Page 233423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified

More information

INLET DAMPER WALL FAN UNIT

INLET DAMPER WALL FAN UNIT FARM PRODUCTS DIVISION MEMBER OF AMCA AMERICAN COOLAIR CORPORATION P.O. BOX 2300 JACKSONVILLE, FLORIDA 32203 PHONE (904) 389-3646 FAX (904) 387-3449 E-MAIL - agfans@coolair.com INLET DAMPER WALL FAN UNIT

More information

OPERATION AND MONTAGE MANUAL ROOF FANS

OPERATION AND MONTAGE MANUAL ROOF FANS NO RF/U/2017 (ENGLISH) (valid since 13.10.2017) ROOF FANS RF / RFV Venture Industries Sp. z o.o. is not responsible for any damage caused by improper use of the fan and reserves the right to modify this

More information

our contribution for Sealless Magnetic Coupled, Heavy Duty Side-Channel Pumps environmental protection Type SCM PN40

our contribution for Sealless Magnetic Coupled, Heavy Duty Side-Channel Pumps environmental protection Type SCM PN40 Sealless Magnetic Coupled, Heavy Duty Side-Channel Pumps our contribution for environmental protection Type SCM PN40 General The DICKOW-pump, type SCM, is a selfpriming horizontal side-channel pump with

More information

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size)

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size) we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size) www.blowtech.in we make air move Blowtech Air Devices Pvt. Ltd. was founded in 1988 and quickly established

More information

Owners Manual. SM-HP A SM-HP8-10 Meter. Manual D

Owners Manual. SM-HP A SM-HP8-10 Meter. Manual D DuraCore TM Fan Owners Manual SM-HP8-64-360A SM-HP8-10 Meter Manual 9-1473D 1 4 5 7 8 9 6 MONEL HARDWARE 7 8 9 STAINLESS HARDWARE 00 FAN BLADE FAN HUB 3 Fan Components Marley Order No. Trial Pitch Angle

More information

CENTRIFUGAL FAN IN SCROLL CASING. Helix S-Vent OPERATION MANUAL

CENTRIFUGAL FAN IN SCROLL CASING. Helix S-Vent OPERATION MANUAL CENTRIFUGAL FAN IN SCROLL CASING Helix S-Vent EN OPERATION MANUAL Helix / S-Vent www.blaubergventilatoren.de CONTENTS CONTENTS 3 Introduction 3 Use 3 Delivery set 4 Technical data 10 Safety requirements

More information

XB-EFA-8L-BK & XB-EFA-8R-BK

XB-EFA-8L-BK & XB-EFA-8R-BK Supply & Extract Ventilation Unit with Heat Recovery The EMC Directive 2014/30/EU The Low Voltage Directive 2014/35/EU The information contained in this document provides details of installation, operation

More information

SAM TURBO INDUSTRY LIMITED

SAM TURBO INDUSTRY LIMITED INSTRUCTIONS ON INSTALLATION, OPERATION AND MAINTENANACE FOR SAM TURBO PUMP TYPE MD SAM TURBO INDUSTRY LIMITED NEELAMBUR, COIMBATORE-641 014. INDIA PH: 0422-3058899(50 LINES), FAX: 3058000, E-MAIL: mktg@sampumps.com,

More information

SuperKlean Washdown Products

SuperKlean Washdown Products DURAREEL DR8 & DR8S INSTALLATION AND MAINTENANCE INSTRUCTIONS **DO NOT THROW AWAY AFTER INSTALLATION** **SAVE AND DISPLAY PROMINENTLY WHERE THIS EQUIPMENT IS USED** GENERAL WARNINGS High pressure and hot

More information

ANLAGENBAU HEAT EXCHANGER w w w. a nla g enba u-b oehm er. d e Version 05/2015

ANLAGENBAU HEAT EXCHANGER w w w. a nla g enba u-b oehm er. d e Version 05/2015 ANLAGENBAU HEAT EXCHANGER Table of Contents 1.0 General Information 1.2 User Instructions 1.3 Proper Use 1.4 General Safety Rules 2.0 Design and Function 3.0 Installation 3.1 Setting up the Plate Heat

More information

OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN.

OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN. INSTALLATION, OPERATION & SERVICE MANUAL FOR COOLER TYPES OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN. 1. Introduction This manual is a guide for the installation, maintenance

More information

Acquaer Ltd. H-4900, Fehérgyarmat, Szatmári út 11. CENTRIFUGAL PUMP Instruction Manual ACm60 / ACm75 / ACm150 / ACm150B2

Acquaer Ltd. H-4900, Fehérgyarmat, Szatmári út 11. CENTRIFUGAL PUMP Instruction Manual ACm60 / ACm75 / ACm150 / ACm150B2 CENTRIFUGAL PUMP Instruction Manual ACm60 / ACm75 / ACm150 / ACm150B2 Congratulations on your purchase of a LEO Centrifugal Pump It is important that you read, fully understand and observe the following

More information

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to

More information

Vibration Of Cooling Tower Fans. Barry T. Cease Cease Industrial Consulting Vibration Institute 2015

Vibration Of Cooling Tower Fans. Barry T. Cease Cease Industrial Consulting Vibration Institute 2015 Vibration Of Cooling Tower Fans Barry T. Cease Cease Industrial Consulting Vibration Institute 2015 ceasevibration@icloud.com (843) 200-9705 1 WHAT IS A COOLING TOWER AND WHAT DOES IT DO? All cooling towers

More information

SECTION (15833) - HVAC POWER VENTILATORS

SECTION (15833) - HVAC POWER VENTILATORS PART 1 GENERAL 1.01 SUMMARY SECTION 23 34 23 (15833) - HVAC POWER VENTILATORS A. Section Includes: 1. Centrifugal Roof Ventilators. 2. Up-blast Roof Exhaust Fans (Kitchen Hood Exhaust). 3. Ceiling-Mounted

More information

PUMPS FOR INDUSTRY. The Vertical Pump Specialists CONTENTS: Introduction & User List. Product Overview. Vertical Process Pumps...

PUMPS FOR INDUSTRY. The Vertical Pump Specialists CONTENTS: Introduction & User List. Product Overview. Vertical Process Pumps... PUMPS FOR INDUSTRY CONTENTS: The Vertical Pump Specialists Introduction & User List Product Overview Vertical Process Pumps... Series 600 Vertical Sewage Pumps... Series 700 Vertical Sump Pumps... Series

More information

Semi-Automatic Suction Screen Filters 3"-4 Angle. Service & Maintenance Manual

Semi-Automatic Suction Screen Filters 3-4 Angle. Service & Maintenance Manual Semi-Automatic Suction Screen Filters 3"-4 Angle Service & Maintenance Manual Safety Instructions Prior to installation or handling of the filter, read the Installation and Operation instructions carefully.

More information

Installation Manual PS-200 & PS-201

Installation Manual PS-200 & PS-201 Installation Manual PS-200 & PS-201 Table of Contents Pre-Uncrating Checklist... 1 Verifying System Requirements... 2 Verifying System Direction... 2 Verifying the Electrical Requirements... 2 Removal

More information

Axial flow fan AXICO ANTI-STALL

Axial flow fan AXICO ANTI-STALL Product data sheet: AXICO ANTI-STALL Axial flow fan AXICO ANTI-STALL Model FPAC and FPMC axial flow fans with controllable pitch blades. Air flow range: 3-110 m³/s (10.000 400.000 m³/h). Pressure rise:

More information

Centrifugal Fans, Non-Overloading, Backward Inclined

Centrifugal Fans, Non-Overloading, Backward Inclined BACKWARD INCLINED CENTRIFUGAL FANS Centrifugal Fans, Non-Overloading, Backward Inclined MVA, MVZ, MVX & MVW Series with laminar blades MAVA, MAVZ & MAVX Series with aerofoil blades Features The combination

More information

USER S MANUAL. Centrifugal inline fan. VKMz 100 Q VKMz 100 VKMz 125 Q VKMz 125. VKMz 250 Q VKMz 250 VKMz 315 Q VKMz 315

USER S MANUAL. Centrifugal inline fan. VKMz 100 Q VKMz 100 VKMz 125 Q VKMz 125. VKMz 250 Q VKMz 250 VKMz 315 Q VKMz 315 USER S MANUAL VKMz 100 Q VKMz 100 VKMz 125 Q VKMz 125 VKMz 150 VKMz 160 VKMz 200 Q VKMz 200 VKMz 250 Q VKMz 250 VKMz 315 Q VKMz 315 Centrifugal inline fan VKMz CONTENTS Contents... 2 Safety requirements...

More information

PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN » INSTALLATION AND MAINTENANCE INSTRUCTIONS

PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN » INSTALLATION AND MAINTENANCE INSTRUCTIONS AIR COMFORT AIR TREATMENT 9933 GB 2016.05.25 PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN» INSTALLATION AND MAINTENANCE INSTRUCTIONS contents Page Installation options...... 2 Checks to be

More information

π H-2268 SANITAIRE UPRIGHT VACUUM SAFETY uline.com

π H-2268 SANITAIRE UPRIGHT VACUUM SAFETY uline.com π H-2268 SANITAIRE UPRIGHT VACUUM 1-800-295-5510 uline.com SAFETY PAGE 1 OF 7 NOTE: When using an electrical appliance, basic precautions should always be followed, including the following: READ ALL INSTRUCTIONS

More information

PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer)

PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer) PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer) Galvanized Panel Fan IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble, install, operate

More information

"S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16

S SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16 Webster Pumps "S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16 PLEASE READ THE FOLLOWING INFORMATION PRIOR TO INSTALLING AND USING Webster PUMPS or HAYWARD VALVES,

More information

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance TOP ECOSMART TWINFANS (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use Installation and Maintenance The EMC Directive 2014/30/EU The Low Voltage directive 2014/35/EU INDOOR USE ONLY Introduction

More information

Audi-Larm Audible Alarm

Audi-Larm Audible Alarm Audi-Larm Audible Alarm MAINTENANCE AND REPAIR TAL 1706 (L) Rev. 7 MSA 2017 Prnt. Spec. 10000005389(I) Mat. 10093084 Doc. 10093084 REPLACEMENT KITS AND PARTS LIST TAL 1706 (L) Rev. 7-10093084 2 Exploded

More information

Installation Manual PS-225 & PS-275

Installation Manual PS-225 & PS-275 Installation Manual PS-225 & PS-275 Table of Contents Pre-Uncrating Checklist... 1 Verifying System Requirements... 2 Verifying System Direction... 2 Verifying the Electrical Requirements... 2 Removal

More information

MANUAL COVER. To expedite parts ordering or technical questions, please include your Model and Serial Number listed below in all correspondence.

MANUAL COVER. To expedite parts ordering or technical questions, please include your Model and Serial Number listed below in all correspondence. MANUAL COVER We at Larry Hess & Associates, Inc. would like to take this opportunity to thank you for your patronage. The machine you have purchased has been manufactured and assembled in the USA with

More information

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D CENTRIFLOW 3D Plug fan GMEC >> Installation and Maintenance air comfort CentriFlow 3D 2 Plug Fan CentriFlow 3D GMEC Installation and Maintenance Important Information, Safety notes, Technical Description

More information

Oil burners fuel unit with solenoid valve

Oil burners fuel unit with solenoid valve Oil burners fuel unit with solenoid valve Type VM www.deltapumps.com VM1 - VM4U flanged Certified Quality System Printed in Italy - DE112/0404 Oil burners fuel unit with solenoid valve Type VM The DELTA

More information