PLENUM FAN EQLK PLENUM FAN, DIRECT-DRIVEN

Size: px
Start display at page:

Download "PLENUM FAN EQLK PLENUM FAN, DIRECT-DRIVEN"

Transcription

1 EQLK, DIRECT-DRIVEN INSTALLATION AND MAINTENANCE INSTRUCTIONS Contents Page Installation options Checks to be made prior to commissioning...2 Electrical connections Measures before starting Installation of separately supplied frequency inverters... 3 Airflow measurement.. 4 Maintenance... 5 Cleaning Picture shows the fan with integral motor. Other motor options are present. To remove the fan from the air handling unit casing To replace the motor

2 2 EQLK FAN, INSTALLATION OPTIONS EQLZ-37 Safety guard, inlet EQLZ-36 Safety guard, outlet Connection Accessories for the outlet: EQLZ-26 Connection piece EQLZ-25 Flexible connection EQLZ-27 Counterflange EQLZ-24 Protective screen for door EQLZ-28 Protective screen CHECKS TO BE MADE PRIOR TO COMMISSIONING Check that the fan complies with the EU machinery directive. All inspection doors on the fan section and other function is equipped with door locks with a key. Additional safety can be added. EQLZ-37 is a protective screen which can be placed at the inlet to the fan section. EQLZ-36 is a protective screen that can be added to the outlet of the fan section if another AHU function is placed downstream of the fan. EQLZ-28 is protective screen when the fan section is placed at the outlet of the AHU. EQLZ-24 is additional protection behind the inspection door at the fan section. Check that a qualified electrician has handed over written approval for commissioning. Check that the fan impeller rotates freely and that no objects which can be drawn in and damage the fan have been left in the installation. If the fan is equipped with steel spring anti-vibration mountings, the transport locking devices must be removed before starting the fan. Belastningsskad Deformations due to overloading ELECTRICAL CONNECTIONS The motor of the fan must always be controlled by a frequency inverter, i.e. either via a separate frequency inverter or with an integral motor. The frequency inverter permits control of the motor speed and slow starts. If the fans are idle for more than 3 months prior to or after installation, the fans should be occasionally rotated by hand at regular intervals. If this is not done, the bearings are liable to become damaged due to overloading as shown in the adjacent illustration. N.B.! The fan must not be started directly on-line! Read the MAX permissible frequency at which the fan motor may be controlled. You ll find this frequency specified on the rating plate. Under no circumstances is it permissible to supply the fan motor with power of a higher frequency.

3 xxx xxxx xxxxxx xxxx xxxxxxxx xx xxx xxxxx xxxxx xxx xxxx xxxxxx xxx xxxx xxxxxxx xxx xxxx xxxxxxx 3 INSTALLATION OF SEPARATELY SUPPLIED FREQUENCY INVERTER xxx xxxx xxxxxx xxx xxxx xxxxxxxx xx xxx xxxx xxxxx MAX frequency Electric wiring must be carried out by a qualified electrician. Warning! FIf the frequency inverter is not installed correctly, this may damage the motor bearings. FläktGroup s policy stipulates that we agree to accept guarantee liability only if the motor and frequency inverter have been supplied and installed by us. Guarantee liability will not be accepted by FläktGroup if the motor has been connected/ wired to a frequency inverter by another fitter, i.e. one who is not employed by or commissioned by FläktGroup. The cable between the terminal box of the motor and the separate frequency inverter must be shielded. A safety isolating switch must be installed between the mains supply and the frequency inverter. Install the safety isolating switch near the inspection door of the fan. Before beginning work on the fan, isolate the power supply by switching off the safety isolating switch. The EQLK plenum fan can be supplied with an external, factoryfitted frequency inverter, wired to the terminal box of the motor with a shielded cable. A prefitted safety isolating switch prewired to the frequency inverter is also available as an accessory. The EQLK plenum fan can also be supplied with a factory-fitted shielded cable run to an external shielded terminal box. Isolate the power supply and wait until the impeller has stopped rotating (approx. 1 minute) before inspecting and servicing the fan. The frequency inverter and motor shall be installed by a qualified electrician with adequate knowledge on how to install speedcontrolled drive systems (frequency inverters) and EMC safety. The following recommendations shall be regarded as a complement to the manufacturer s installation instructions. If the content of the instructions differ, the instructions furnished by the manufacturer shall have priority over those stated below, to enable compliance with the guarantee liability terms of the manufacturer of the equipment. GENERAL A continuous, shielded 4-wire cable designed for EMC installation to motorized drives should be installed between the motor and the frequency inverter. The optical density of the cable shield shall be at least 80 %, e.g. NCY or Olflex Classic. The shield must be in 360 º contact with the casing both in the motor and in the frequency inverter in order to achieve maximal surface contact. It is not advisable to install a safety isolating switch or junction boxes between the frequency inverter and the motor. MEASURES BEFORE STARTING The fan must not be started with the damper on the suction or delivery side closed. However the fan motor may be briefly energized with the inspection door open for checking that the direction of impeller rotation is correct. Check before starting the fan that the impeller rotates freely and that no objects, which can be drawn in and damage the fan, have been left in the installation. If the fan is equipped with steel spring anti-vibration mountings, the transport locking devices must be removed before starting the fan. Note! The frequency converter have been optimized for the duty point. The power could thus be lower than the motors rated power. FREQUENCY INVERTER The shielded cable must be led either through an EMC approved cable gland in the casing of the frequency inverter or through a cap intended for this purpose. The shielded cable must not be connected to an earth screw.

4 4 The shield must be in 360º contact with the casing Shield Insulating tape CAPACITIES IN EXCESS OF 22 KW If the capacity exceeds 22 kw, a symmetrically shielded cable with concentric or in some other way symmetrically designed protective earth conductor should be used. For recommendations governing these installations we refer to the installation instructions for the frequency inverter. AIRFLOW MEASUREMENT TO CONNECT THE SHIELDED CABLE If the application requires you to wire the cable shield to an earthscrew inside the motor or the frequency inverter, this must be done in such a way that the impedance will be as low as possible. In these cases the length of this conductor must be restricted to 5 times the width of the conductor. For instance, the length of a 1 cm wide conductor should not exceed 5 cm. Insulating tape MOTOR The cable must be led into the terminal box of the motor through an EMC approved cable gland, e.g. through a Miltronic SKINTOPMS-SC. The shielded cable must only be connected via the EMC cable gland, not to an earth screw. The shield must be in 360º contact with the casing Casing Shield The EQLK has equipment for measuring the airflow. The airflow, q, can be measured by applying a manometer reading of Δp (Pa), and a constant, k, using the following formula: q = 1 Δp m 3 /s k The manometer reading, Δp, which is the difference between the pressure in the suction chamber by the fan inlet and the pressure inside the inlet cone, can be read with a manometer (pressure range of up to 6000 Pa) which should be connected with a 4 mm dia. tube to 2 externally located pressure tappings. The value of the constant k is specified in the table below. OTHER DETAILS In addition to the above, observe the following: type of mains power supply local electrical safety rules and regulations manufacturer s installation instructions for the frequency inverter. For EQLZ-42 U-tube manometers, use only the red manometer fluid supplied with the instrument. Never use any other type of fluid. Precision-adjust the zero point with the zero adjustment screw. A flow indicator with built-in pressure transducer (available as an accessory) should be connected by means of tubes to the external pressure tappings. This instrument converts the manometer pressure reading to a flow (m 3 /s) which is shown on a display screen and transmits a 0 10 V output signal, linear with the flow.

5 5 If the air handling unit is supplied with a control system, the flow can be read directly in the control panel display. NB! In the case of air handling units supplied with a control system, the pressure tappings in the end connection panels of the unit are not connected to the airflow sensor of the fan. If you still want to read the manometer pressure with an external manometer, you can connect the tubes from the airflow sensor of the fan across T-nipples to the pressure tappings in the end connection panel of the air handling unit. If this external means of measuring flow will not be permanent, the tubes must be restored to their original condition. Size EQLK, EQLT, aaa-b k- factor GPEB , , , , 014-3, 018-2, , , , 027-3, 032-2, , 036-3, 041-2, , 045-3, 050-2, 054-2, 063-2, , 054-3, 056-3, 068-2, 063-3, 072-3, , 079-3, If two fans are installed in the fan section, the k-value is applicable to the total airflow generated by both fans. TEMPERATURE CORRECTION The flow scale on the indicating instrument and the flow formula above apply to air with a temperature of +20 C. For other temperatures, the flow must be corrected using the following formula: q = q20, m 3 /s (273 + t) 293 where q = the actual flow through the fan, q20 = the flow reading and t = the current temperature in C. MAINTENANCE Warning! In order to prevent personal injury and damage to machinery, the safety isolating switch must be switched off and the safety fuses of the fan must be removed before beginning work on the fan. The fan must be inspected and cleaned every 6/12th month. The length of the interval has been determined on the basis of approx hours of operation during a 12-month period and for a normal comfort installation. In environments where the dust content is high in the supply and/or extract air, the air handling unit will have to be inspected and cleanedmore often. The fan is accessible through the inspection door and cleaned with the fan in place. CLEANING Both the supply air and the extract air fan should be inspected and cleaned whenever the need arises. Dust tends to collect mainly on the inner side of the fan blades. The best way to clean the fan impeller is by using a vacuum cleaner equipped with a soft nozzle. Be careful to remove all the impurities from the fan blades so that the fan will not come out of balance. After adjusting or cleaning the fan, check that it runs free of vibration. TO REMOVE THE FAN FROM THE AIR HANDLING UNIT CASING, SIZES The fan can be withdrawn from the casing in the following way: 1. Remove the frame of the inspection door including the door and the fixed panel by removing the bolts beneath the cover plenums. 2. Disconnect the motor cable/control cable to the frequency inverter and pull the cables through the rotor wall/filter wall. 3. If a shear absorber is fitted: Remove the bolts (2 bolts) that secure its brackets. Ignore the bolts on the rear side; they need not be backed off. If a pressure suppressor and steel spring anti-vibration mountings are fitted: Remove the bolts to the fan beams in the floor at both ends. 4. If steel spring anti-vibration mountings are fitted: Remove the bolts that hold the fan connection against the fan outlet.

6 6 5. Withdraw the fan unit. Be careful not to damage the gasket in the fan s inlet plate (applies to rubber antivibration mountings). The fan can be withdrawn maximally so far out that half the fan motor protrudes outside the unit casing without support. 6. Push in and reassemble the components in the reverse order. TO REPLACE THE MOTOR 1. Disconnect the electrical connections. 2. Remove the stop screw in the fan impeller hub. 3. Remove the motor from the motor base plate. 4. Extract the impeller from the motor shaft end with an extractor tool. Utilize the existing extraction grooves in the hub for this purpose. See the figure below. 5. Back the motor from the impeller. 6. Reassemble in the reverse order, using the tapped hole in the motor shaft end as a fixing point for the extractor tool. xxx xxxx xxxxxx xxx xxxx xxxxxxxx xx xxx xxxx xxxxx Locking bolt Carry out maintenance on the motor according to the instructions provided by the motor supplier. In cases where there is no possibility to carry out the entire fan or motor with impeller, alternatively there is no need for a complete disassembly, following procedure can be used: 1. NOTE! Turn off the power at themain switch and mark that work is ongoing in the fan section. 2. Disconnect all electrical connections in themotor terminal box. 3. Remove themotor bracket fromtheir bolted joints at the unit s bottom panel/guide rails. 4. Move themotor bracketwithmotor and impeller from the inlet cone far enough to enable removal of the impeller. 5. Alternatively loose the bolt joint on themotor and rotate the motor to enable removal of the impeller. 6. Remove the impeller fromthemotor shaft using a puller. 7. Lift the impeller out of the unit in a suitableway through the inspectiondoor or disconnect the motor bolted joints if this has not been done and lift themotor out of theunit in an appropriate way through the inspection door. Make sure that the fan inlet engages into the rear holder of the connection frame.

PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN » INSTALLATION AND MAINTENANCE INSTRUCTIONS

PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN » INSTALLATION AND MAINTENANCE INSTRUCTIONS AIR COMFORT AIR TREATMENT 9933 GB 2016.05.25 PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN» INSTALLATION AND MAINTENANCE INSTRUCTIONS contents Page Installation options...... 2 Checks to be

More information

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE 2 GLEC-6 - Installation and maintenance CONTENTS 1 Important information... 3 2 Safety notes... 3 3 Technical description...4 4 Transport... 6 5

More information

Instructions for the BASIC BCRW Fan, Sizes General

Instructions for the BASIC BCRW Fan, Sizes General Instructions for the BASIC BCRW Fan, Sizes 004 027 1. General The BCRW is a direct-driven fan of axi-centrifugal design. This fan offers excellent power efficiency, low, uniform air flow, low sound generation

More information

GLEB Kitchen exhaust fan

GLEB Kitchen exhaust fan GLEB Kitchen exhaust fan Installation and Maintenance??.1.2013 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

GLEB. >> Installation and Maintenance. Air Comfort. Air movement. Duct & Box Fans

GLEB. >> Installation and Maintenance. Air Comfort. Air movement. Duct & Box Fans Air Comfort Air movement Duct & Box Fans GLEB KITCHEN exhaust FAN >> Installation and Maintenance Kitchen Exhaust Fan GLEB Installation and Maintenance Important Information, Safety notes, Technical Description

More information

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes 50-120 1 General The heat exchanger control system is a control system for 380 W step motors

More information

TopMaster Air Handling unit. Installation instructions

TopMaster Air Handling unit. Installation instructions Installation instructions Safety Instructions Operation of Air Handling units and accessories WARNING Installation may only be carried out by qualified personnel. Before taking the air handling unit into

More information

ACN SMOKE INSTALLATION AND MAINTENANCE

ACN SMOKE INSTALLATION AND MAINTENANCE NovAx ACN SMOKE INSTALLATION AND MAINTENANCE 918149-0 English 918149-0 GB Installation and maintenance NovAx smoke exhaust fan type ACN smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport

More information

English CNA-CNB. Centrifugal fans Installation and maintenance

English CNA-CNB. Centrifugal fans Installation and maintenance 916505-0 English CNA-CNB Centrifugal fans Installation and maintenance 916505-0 GB Centrifugal fans types CNA, CNB, CNA-M and CNB-M installation and maintenance 1. Application 2. Handling 2.1 Marking 2.2

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL

INSTALLATION, OPERATION & MAINTENANCE MANUAL CENTRAL FANS COLASIT LTD Unit 12A, Palmers Road, East Moons Moat, Redditch. Worcs. B98 0RF Tel: 01527-517200 Fax: 01527-517195 Edition 04_13 INSTALLATION, OPERATION & MAINTENANCE MANUAL CIV Fan Range Valid

More information

Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke

Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke 918149-0 GB Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport 3. Storage 4. Installation 4.1 Prior to attachment 4.2 Attachment

More information

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D CENTRIFLOW 3D Plug fan GMEC >> Installation and Maintenance air comfort CentriFlow 3D 2 Plug Fan CentriFlow 3D GMEC Installation and Maintenance Important Information, Safety notes, Technical Description

More information

Supply air unit VEKA Installation & Maintenance

Supply air unit VEKA Installation & Maintenance November 2008 Safety instructions Operating the air treatment unit and accessory components WARNING Before the air treatment unit is taken into service, any free connections must be provided with protective

More information

Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance

Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance 916503-0 GB Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance 1. Main components 2. Application 3. Handling 3.1 Marking 3.2 Weight 3.3 Transport 4. Storage 1. Main components: Types ARC,

More information

Indholdsfortegnelse. Danvent Air Handling Units SERVICE MANUAL

Indholdsfortegnelse. Danvent Air Handling Units SERVICE MANUAL Indholdsfortegnelse Danvent Air Handling Units SERVICE MANUAL Service Servicing of the Air Handling Unit Your ventilation system is equipped with a Danvent Air Handling Unit (AHU) which will contribute

More information

GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES GENERAL INSTRUCTION

GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES GENERAL INSTRUCTION GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES Using the air handling unit... Free space for service and repair work... GENERAL INSTRUCTION Checking prior to commissioning...3

More information

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP WWPPCHLFT260 Instructions WWPPCHLFT260_Horizontal Multistage Centrifugal Pump_IB.indd 1 READ THIS MANUAL CAREFULL BEFORE INSTALL, START THE PUMP 1. Suction 2. Plug

More information

F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS

F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS Contents Page User instructions 3-5 General 3 Fan installation 3-4 Maintenance 3 Electrical installation 5 Troubleshooting 5 Technical description 6-8 General

More information

Instructions for the fan motor control system, SILVER C

Instructions for the fan motor control system, SILVER C Instructions for the fan motor control system, SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units. The motor control system is

More information

EC Box Fan www.flaktwoods.com/oandm Safety, Installation, Operation and Maintenance Instructions CONTENTS Paragraphs Safety 1 Handling/Storage 2 Installation (Mechanical) 3 Fig. 1: Fig. 2: Tilt Mechanism

More information

Hodge Clemco Ltd. MJC Mini Cartridge Filters Owners Manual. TSOM 556 Date of issue 13/07/04. Hodge Clemco Ltd

Hodge Clemco Ltd. MJC Mini Cartridge Filters Owners Manual. TSOM 556 Date of issue 13/07/04. Hodge Clemco Ltd 1 MJC Mini Cartridge Filters Owners Manual TSOM 556 Date of Issue: 13.07.04 Orgreave Drive, Sheffield South Yorkshire. S13 9NR Tel:0114 254 0600 Fax: 0114 2540250 Email:sales@hodgeclemco.co.uk www.hodgeclemco.co.uk

More information

A Fläkt Woods Company 2933 Symmes Road, Fairfield, Ohio Phone: (513) Fax: (513)

A Fläkt Woods Company 2933 Symmes Road, Fairfield, Ohio Phone: (513) Fax: (513) A Fläkt Woods Company 2933 Symmes Road, Fairfield, Ohio 45014-2035 Phone: (513) 874-2400 Fax: (513) 870-6249 JM AEROFOIL FANS Installation, Operation and Maintenance Instructions Site Storage The fan must

More information

DS series STERLING PUMPS. Industrial End Suction Pumps ISO/DP

DS series STERLING PUMPS. Industrial End Suction Pumps ISO/DP DS series Industrial End Suction Pumps ISO/DP 5199 www.sterlingpumps.com.au DS series Capacities from: Heads from: 340 to 5,680 m3/h (1,500 to 25,000 USPGM) 21 to 106 metres (70 to 350 feet) Power range

More information

1. Description INSTRUCTION FOR BLAST COOLER TYPE COOL 250. Material

1. Description INSTRUCTION FOR BLAST COOLER TYPE COOL 250. Material 1. Description General The cooler is used for cooling of water, oil or other liquid by use of air. The liquid is passing in the tubes where it transfere the energy to the air via the fins on the outside

More information

Energy Conservation with PARAG Energy Efficient Axial Flow FRP Fans

Energy Conservation with PARAG Energy Efficient Axial Flow FRP Fans PARAG FANS & COOLING SYSTEMS LTD. Energy Conservation with PARAG Energy Efficient Axial Flow FRP Fans Registered Office & Works Plot No.1/2B & 1B/3A, Industrial Area No.1 A.B.Road, Dewas 455001 (M.P.)

More information

AZN ATEX INSTALLATION AND MAINTENANCE

AZN ATEX INSTALLATION AND MAINTENANCE ZerAx AZN ATEX INSTALLATION AND MAINTENANCE 924714-0 English 924714-0 GB ZerAx axial flow fans type AZN ATEX Installation and maintenance 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Temperature

More information

XB-EFA-8L-BK & XB-EFA-8R-BK

XB-EFA-8L-BK & XB-EFA-8R-BK Supply & Extract Ventilation Unit with Heat Recovery The EMC Directive 2014/30/EU The Low Voltage Directive 2014/35/EU The information contained in this document provides details of installation, operation

More information

LC Series - Light Commercial Pump Station Installation and Operation Manual

LC Series - Light Commercial Pump Station Installation and Operation Manual LC Series - Light Commercial Pump Station Installation and Operation Manual Please keep this manual with the pump station Content Rain Bird LC Series Overview... Safety Instruction... Operation... 3 Pump

More information

1. Description INSTRUCTION FOR AIR BLAST COOLER TYPE COOL 450

1. Description INSTRUCTION FOR AIR BLAST COOLER TYPE COOL 450 1. Description General The cooler is used for cooling of water, oil or other liquid by use of air. The liquid is passing in the tubes where it transfere the energy to the air via the fins on the outside

More information

Ceiling swirl diffusers

Ceiling swirl diffusers X X testregistrierung Ceiling swirl diffusers Type Plenum box with damper blade and square diffuser face Horizontal swirling air discharge For comfort zones, with fixed air control blades Circular and

More information

Ceiling swirl diffusers

Ceiling swirl diffusers X X testregistrierung Ceiling swirl diffusers Type Plenum box with damper blade (optional) Horizontal swirling air discharge With very low sound power level for comfort zones, with fixed air control blades

More information

USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES

USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES Bucket Fan 420 Bucket Fan 1055 Bucket Fan 1460 420 1055 1460 2 Bucket Fan CONTENT INTRODUCTION 3 USE 3 WHAT S INCLUDED IN THE BOX 3 DESIGNATION

More information

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance TOP ECOSMART TWINFANS (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use Installation and Maintenance The EMC Directive 2014/30/EU The Low Voltage directive 2014/35/EU INDOOR USE ONLY Introduction

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended

More information

Series PX. Installation & Maintenance. Models: PX-3 PX-5 PX-7 1/2-HF PX-10-HF PX-15-HF. Materials: A - CPVC

Series PX. Installation & Maintenance. Models: PX-3 PX-5 PX-7 1/2-HF PX-10-HF PX-15-HF. Materials: A - CPVC Series PX Installation & Maintenance Models: PX-3 PX-5 PX-7 /2-HF PX-0-HF PX-5-HF Materials: A - CPVC Introduction Penguin Pumps are designed to handle a large range of chemicals without difficulty. Completely

More information

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Instructions for the fan motor control system with integrated wiring terminals SILVER C Instructions for the fan motor control system with integrated wiring terminals SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units.

More information

Centrifugal Fans maintenance manual

Centrifugal Fans maintenance manual Centrifugal Fans maintenance manual www.dcs.fi Contents 1 Safety... 4 1.1 Explanations... 4 1.2 Basic safety rules... 4 1.3 Noise level... 5 2 General... 6 2.1 Fan types... 6 2.1.1 Use types... 6 2.1.2

More information

AXUS - SC Short Cased Axial Flow Fans Installation and Maintenance

AXUS - SC Short Cased Axial Flow Fans Installation and Maintenance 1.0 INTRODUCTION AXUS - SC Short Cased Axial Flow Fans Installation and Maintenance The Nuaire Short Cased Axial Fan range is produced in a range of sizes from 250mm to 1600mm diameter. Cases are manufactured

More information

SAM TURBO INDUSTRY LIMITED

SAM TURBO INDUSTRY LIMITED INSTRUCTIONS ON INSTALLATION, OPERATION AND MAINTENANACE FOR SAM TURBO PUMP TYPE MD SAM TURBO INDUSTRY LIMITED NEELAMBUR, COIMBATORE-641 014. INDIA PH: 0422-3058899(50 LINES), FAX: 3058000, E-MAIL: mktg@sampumps.com,

More information

568X, 587X, 588X Series

568X, 587X, 588X Series Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

Operating Instruction Centrifugal fans without scroll (Translation of the Original) BA-RLE-AC /2014 RLE RLA

Operating Instruction Centrifugal fans without scroll (Translation of the Original) BA-RLE-AC /2014 RLE RLA Operating Instruction Centrifugal fans without scroll (Translation of the Original) EN RLE RLA Content 1. Important information 2. Safety notes 3.Technical description 4. Transport 5. Mounting / Installation

More information

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to

More information

INSTALLATION FB T: +44 (0) F: +44 (0) E: W:

INSTALLATION FB T: +44 (0) F: +44 (0) E: W: INSTALLATION FB 1 Contents User instructions General Fan installation Maintenance Electrical installation Troubleshooting Technical description General Classification Technical specification Manufacturer

More information

Installation and Wiring Instructions

Installation and Wiring Instructions Powerline (TDF) Installation and Wiring Instructions TDF32014 TDF38014 TDF42014 TDF48014 TDF38034 TDF42034 TDF48034 TDF52034 TDF52036 TDF60034 TDF60036 PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE STARTING

More information

SELF-PRIMING CENTRIFUGAL PUMPS BMLS-M & BMLS-H

SELF-PRIMING CENTRIFUGAL PUMPS BMLS-M & BMLS-H SELF-PRIMING CENTRIFUGAL PUMPS BMLS-M & BMLS-H INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS HP Phase Medium Head High Head 3 1 BMLS 300 M BMLS 300 H 3 3 BMLS 300 M3 BMLS 300 H3 5 1 BMLS 500 M BMLS

More information

TIDALWAVE I/G POOL PUMP INSTRUCTION MANUAL

TIDALWAVE I/G POOL PUMP INSTRUCTION MANUAL TIDALWAVE I/G POOL PUMP INSTRUCTION MANUAL READ THIS MANUAL CAREFULLY BEFORE USING YOUR PUMP 88 PUMP PARTS BREAKDOWN REF # Order # Mfr # Description 1 NEP4 AC 348 Lid Knobs NEP AC 380 Strainer Lid 3 NEP6

More information

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004) High Plume Blowers Suggested Specification Section 15500 (Master Format 1996) Suggested Specification Section 23 38 16 (Master Format 2004) PART 1 GENERAL 1.01 WORK INCLUDED High Plume Laboratory Exhaust

More information

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

OWNERS GUIDE TO INSTALLATION AND OPERATION

OWNERS GUIDE TO INSTALLATION AND OPERATION OWNERS GUIDE TO INSTALLATION AND OPERATION SPM SERIES HIGH POWER CENTRIFUGALS READ THESE INSTRUCTIONS CAREFULLY Read these installation instructions in detail before installing your pump. Be sure to check

More information

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01 b cool manufacturers of air-conditioning equipment ltd BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION Ver. 1.01 Ver. 3.02 01_18 BCool# 1 brt c/h r407c / r410a

More information

Air Handling Units. T F E.

Air Handling Units.  T F E. Air Handling Units Extract from BS EN ISO 15138:2007 Petroleum & natural gas industries- Offshore production installations-heating, ventilation & air-conditioning. A.12.1 Function Installations provided

More information

Installation, Operation and Maintenance Manual. 3AV 1 to 3AV 430

Installation, Operation and Maintenance Manual. 3AV 1 to 3AV 430 Installation, Operation and Maintenance Manual 3AV 1 to 3AV 430 3AV Close-Coupled Liquid Ring Pump Installation, Operation, and Maintenance Manual Table of Contents 1. General... 3 1.1 Application Fields...

More information

MODEL MC-UL592 MC-UL594 POWER SOURCE. 230V - 240V ~ 50 Hz MAX INPUT 1400 W 1500 W NOMINAL INPUT DIMENSIONS (W x L x H)

MODEL MC-UL592 MC-UL594 POWER SOURCE. 230V - 240V ~ 50 Hz MAX INPUT 1400 W 1500 W NOMINAL INPUT DIMENSIONS (W x L x H) Order Number: PMMA091040CE Vacuum Cleaner MC-UL592/MC-UL594 SPECIFICATION MODEL MC-UL592 MC-UL594 POWER SOURCE 230V - 240V ~ 50 Hz MAX INPUT 1400 W 1500 W NOMINAL INPUT DIMENSIONS (W x L x H) 1200-1300

More information

CHIPPER PC1 INSTRUCTIONS FOR INSTALLATION OPERATION AND MAINTENANCE. Series 35

CHIPPER PC1 INSTRUCTIONS FOR INSTALLATION OPERATION AND MAINTENANCE. Series 35 Cl/SfB (73.4) X CHIPPER PC1 INSTRUCTIONS FOR INSTALLATION OPERATION AND MAINTENANCE Series 35 Imperial Machine Company (Peelers) Limited Harvey Road, Croxley Green, Herts WD3 3AX, England Telephone: 01923

More information

A AD Oil burners fuel unit. deltapumps.com. DE A-AD_en_0709.pdf Page 1/1

A AD Oil burners fuel unit. deltapumps.com. DE A-AD_en_0709.pdf Page 1/1 A AD Oil burners fuel unit deltapumps.com DE116-0709 A-AD_en_0709.pdf - 16.11.09 Page 1/1 Oil burners fuel unit Type A, AD 1- Applications The DELTA aluminium fuel unit type A is an efficient and modern

More information

OWNERS INSTRUCTION MANUAL

OWNERS INSTRUCTION MANUAL OWNERS INSTRUCTION MANUAL 132CM/52 Classic INSTALLATION OPERATION MAINTENANCE CAUTION READ INSTRUCTIONS CAREFULLY FOR SAFE INSTALLATION AND FAN OPERATION. IF UNSURE CONSULT A QUALIFIED ELECTRICIAN SUITABLE

More information

Envistar Operation and Maintenance Instructions

Envistar Operation and Maintenance Instructions Air Handling Unit Envistar Instructions Project:... Air handling with the focus on LCC Address and Telephone Register for Service Supplier: IV Produkt AB Box 3103 SE-350 43 VÄXJÖ, Sweden Street address:

More information

COOLING SYSTEM 1. Section V CONTENTS DATA AND SPECIFICATIONS. Page. Fluid Fan Drive (Silent Flite) 3. Water Pump 4. Radiator 5

COOLING SYSTEM 1. Section V CONTENTS DATA AND SPECIFICATIONS. Page. Fluid Fan Drive (Silent Flite) 3. Water Pump 4. Radiator 5 Section V COOLING SYSTEM CONTENTS Fluid Fan Drive (Silent Flite) 3 Water Pump 4 Radiator 5 Water Temperature Gauge 6 Thermostat 7 Radiator Pressure Cap 7 Service Diagnosis 7 DATA AND SPECIFICATIONS COOLING

More information

STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE

STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE ISO 9001 : 2000 STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE CUSTOMER : 1 CONTENTS 1 SAFETY... 5 1.1 General... 6 1.2 Description of symbols and pictograms... 6

More information

RK Hydrogen Sulfide Transmitter Operator s Manual

RK Hydrogen Sulfide Transmitter Operator s Manual 65-2331RK Hydrogen Sulfide Transmitter Operator s Manual Part Number: 71-0176RK Revision: B Released: 11/26/14 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction

More information

Series P. Installation & Maintenance. Materials: A - CPVC B - Polypropylene C - PVDF

Series P. Installation & Maintenance. Materials: A - CPVC B - Polypropylene C - PVDF Series P Installation & Maintenance Models: P-/5 P-/6 P-/4 P-/ P-/-HP P-3/4 P-3/4HP P- P- / P- P-3 P-5 P-7 / Materials: A - CPVC B - Polypropylene C - PVDF Introduction Penguin Pumps are designed to handle

More information

CODE MODEL TYPE PRESS 60 N 616 T PRESS 60 N 616 T80

CODE MODEL TYPE PRESS 60 N 616 T PRESS 60 N 616 T80 Installation, use and maintenance instructions Heavy oil burner CODE MODEL TYPE 3434985 PRESS 60 N 616 T80 3434986 PRESS 60 N 616 T80 291 (2) - 01/2009 Thermal power - Output Operation Fuel Electrical

More information

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version for ATEX/IECEx hazardous areas or in non-atex version * Non contractual picture Warning It is imperative to read these instructions carefully before installing or maintaining the equipment. MI200EN 09/2017

More information

Varofoil Controllable Pitch in Motion Fans Compared to Variable Frequency Controlled Fans

Varofoil Controllable Pitch in Motion Fans Compared to Variable Frequency Controlled Fans Varofoil Controllable Pitch in Motion Fans Compared to Variable Frequency Controlled Fans A look at two accepted technologies.. System Characteristics In general, the pressure developed by a fan is a function

More information

SELF-PRIMING JET PUMPS

SELF-PRIMING JET PUMPS SS Anti-Rust SS Shaft Copper & Cold-rolled SELF-PRIMING JET PUMPS CONTENTS 1. Applications.... Model Description.... Technical Data... 4. Implementation Standards... 5. Safety Precautions... 6. Product

More information

THERMAL SYSTEMS, INC. Installation and Operation Manual

THERMAL SYSTEMS, INC. Installation and Operation Manual THERMAL SYSTEMS, INC. Installation and Operation Manual Revised September 2016 1. GENERAL SAFETY INFORMATION 1.1 Specification Never exceed the maximum allowable temperature or pressure ratings. Never

More information

INLET DAMPER WALL FAN UNIT

INLET DAMPER WALL FAN UNIT FARM PRODUCTS DIVISION MEMBER OF AMCA AMERICAN COOLAIR CORPORATION P.O. BOX 2300 JACKSONVILLE, FLORIDA 32203 PHONE (904) 389-3646 FAX (904) 387-3449 E-MAIL - agfans@coolair.com INLET DAMPER WALL FAN UNIT

More information

MACHINERY BLOCKING RECOMMENDATIONS

MACHINERY BLOCKING RECOMMENDATIONS MACHINERY BLOCKING RECOMMENDATIONS Blocking machinery is very easy if you use a little common sense. Defined rules will not always work as machine configurations and possibilities of local obstructions

More information

Novenco Air Handling Units

Novenco Air Handling Units Novenco Air Handling Units Climaster ZCF Guide 919432-0 GB Important This document is provided As is and is subject to change without notice. Novenco reserves this right due to continuous product development.

More information

RK-05 Combustible Gas Transmitter Operator s Manual

RK-05 Combustible Gas Transmitter Operator s Manual 65-2405RK-05 Combustible Gas Transmitter Operator s Manual Part Number: 71-0180RK Revision: 0 Released: 2/16/11 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction

More information

KQ Series. Multistage Booster Pump System. Installation Manual. ISO 9001 Certified KQ200/400 KQ800

KQ Series. Multistage Booster Pump System. Installation Manual. ISO 9001 Certified KQ200/400 KQ800 KQ Series Multistage Booster Pump System Installation Manual KQ200/400 KQ800 ISO 9001 Certified Description The KQ series booster pump is an all-in-one compact and reliable automatic multistage centrifugal

More information

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD425 (1018110) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com

More information

ECOSMART XTRACTOR. (ESX-X/R/B) 1 phase, Direct Drive For External, Roof Mounted and Internal use Installation and Maintenance.

ECOSMART XTRACTOR. (ESX-X/R/B) 1 phase, Direct Drive For External, Roof Mounted and Internal use Installation and Maintenance. ESX-X Figure 1. ESX-X units. Removable top panel A D Control module located internally External Commissioning box Table 1. ESX-X Dimensions (mm) Spigot Weight Code A B C D dia (kg) ESX1-X 705 505 355 125

More information

Owner s manual for. Venco 87mm & 100mm. (3 1/ 2 & 4 ) De-airing Pugmill

Owner s manual for. Venco 87mm & 100mm. (3 1/ 2 & 4 ) De-airing Pugmill Owner s manual for Venco 87mm & 100mm (3 1/ 2 & 4 ) De-airing Pugmill Venco Products 29 Owen Road Kelmscott, Western Australia 6111 ph +61 8 9399-5265 fax +61 8 9 497 1335 email: venwest@iinet.net.au www.venco.com.au

More information

Specifications Information and Repair Parts Manual 316A-95, 316B-95, 393A-95, 393B A-95 thru 394D-95, 399A-95

Specifications Information and Repair Parts Manual 316A-95, 316B-95, 393A-95, 393B A-95 thru 394D-95, 399A-95 Specifications Information and Repair Parts Manual 316A-95, 316B-95, 393A-95, 393B-95 394A-95 thru 394D-95, 399A-95 Please read and save this Repair Parts Manual. Read this manual and the General Operating

More information

READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS

READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS Bifurcated Axial Fan Installation and Wiring Instructions 220-240V/1/50Hz & 380-415V/3/50Hz RAD INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLAS SAV THS INSTRUCTIONS Installation and Wiring Instructions

More information

QUICK PRIME INSTALLATION AND SERVICE MANUAL

QUICK PRIME INSTALLATION AND SERVICE MANUAL QUICK PRIME INSTALLATION AND SERVICE MANUAL NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system. Part #

More information

CT-7 Series Toxic Gas Transmitter Operator s Manual

CT-7 Series Toxic Gas Transmitter Operator s Manual 65-2341 CT-7 Series Toxic Gas Transmitter Operator s Manual Part Number: 71-0424 Revision: P1 Released: 6/8/17 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction

More information

Primo Hotel. General. Indoor climate units for hotel rooms

Primo Hotel. General. Indoor climate units for hotel rooms Indoor climate units for hotel rooms General Primo Hotel indoor climate unit Ceiling-mounted indoor climate units for ventilation, cooling and heating High capacity; occupies little space Dry system without

More information

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Important: To protect the unit and avoid damage to the heat exchanger, the blower speed

More information

INSTALLATION AND OPERATION MANUAL FOR HUUM DROP ELECTRIC SAUNA HEATER

INSTALLATION AND OPERATION MANUAL FOR HUUM DROP ELECTRIC SAUNA HEATER INSTALLATION AND OPERATION MANUAL FOR HUUM DROP ELECTRIC SAUNA HEATER 2 Table of Contents 1. THINGS TO CHECK BEFORE INSTALLATION... 2 2. INSTALLATION... 2 3. CONTROLLING THE HEATER... 5 4. GUARD RAILS...

More information

DOMEKT ReGO 400VE(W)-B Series Air Handling Units Installation and Maintenance Service Manual

DOMEKT ReGO 400VE(W)-B Series Air Handling Units Installation and Maintenance Service Manual DOMEKT ReGO 400VE(W)-B Series Air Handling Units EN Content Safety Requirements...3 Transportation...3 Brief Description of the Unit...5 Installation...6 Maintenance...11 Technical Information......13

More information

OPERATING & MAINTENANCE MANUAL INDUSTRIAL DIRECT FIRED DIESEL/KEROSENE HEATERS IC 25

OPERATING & MAINTENANCE MANUAL INDUSTRIAL DIRECT FIRED DIESEL/KEROSENE HEATERS IC 25 OPERATING & MAINTENANCE MANUAL INDUSTRIAL DIRECT FIRED DIESEL/KEROSENE HEATERS IC 25 NOT FOR DOMESTIC USE SPACE HEATING ONLY Made By: Spitwater Australia Pty Ltd 953 Metry St North Albury, NSW, Australia

More information

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC!

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC! COIL Manufacturing Inc. When you want Quality, specify COLMAC! Installation, Operation, and Maintenance ENG00018621 Rev A Air Cooled Fluid Coolers Contents 1. SAFETY INSTRUCTIONS... 1 2. MODEL NOMECLATURE...

More information

This appliance must be installed and serviced by a competent person as stipulated by the Gas Safety (Installation & Use) Regulations.

This appliance must be installed and serviced by a competent person as stipulated by the Gas Safety (Installation & Use) Regulations. G3512 and G3532 DOMINATORPLUS Grills INSTALLATION and SERVICING INSTRUCTIONS This appliance must be installed and serviced by a competent person as stipulated by the Gas Safety (Installation & Use) Regulations.

More information

Models Series Series

Models Series Series Models 31800-Series 31801-Series INDUSTRIAL DIAPHRAGM PUMPS 4 GPM/15 LPM FEATURES Self-Priming Easy Installation Can run dry without damage Low Amp Draw Flow to 4 GPM/15 LPM Compact Size Thermal Overload

More information

DESCRIPTION IMPELLER INSPECTION MAINTENANCE POWER CORD REPLACEMENT IMPELLER REPLACEMENT MECHANICAL SEAL REPLACEMENT IMPELLER INSPECTION /REPLACEMENT

DESCRIPTION IMPELLER INSPECTION MAINTENANCE POWER CORD REPLACEMENT IMPELLER REPLACEMENT MECHANICAL SEAL REPLACEMENT IMPELLER INSPECTION /REPLACEMENT Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

DAGNY LK. Ceiling Mounted Rotational Fan READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 110V~60Hz

DAGNY LK. Ceiling Mounted Rotational Fan READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 110V~60Hz DAGNY LK Ceiling Mounted Rotational Fan READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 110V~60Hz Please do not use any electric or battery powered tools in the assembly and installation of this or any

More information

BELT DRIVEN STATIONARY AGITATOR

BELT DRIVEN STATIONARY AGITATOR BELT DRIVEN STATIONARY AGITATOR INSTRUCTION MANUAL www.usfarmsystems.com 2955 S. K Street Tulare, CA. 93274 (559)685-0340 (800)811-9462 Fax (559)685-9160 Revision Date 9/7/2017 TABLE OF CONTENTS How to

More information

This label warns for risk of electrical shock when failing to observe.

This label warns for risk of electrical shock when failing to observe. MANUAL horizontal centrifugal pumps MB series ic drive SB series mechanical seal 1. Introduction 2. Safety precautions 3. Receipt 4. Installation / Operation and Maintenance 4.1 Installation 4.2 Operation

More information

INDOOR USE ONLY. Installation and Maintenance XTRACTOR. (ESX) 1 and 3 phase, Direct Drive, Fans for indoor use

INDOOR USE ONLY. Installation and Maintenance XTRACTOR. (ESX) 1 and 3 phase, Direct Drive, Fans for indoor use TOP INDOOR USE ONLY Introduction Units are rectangular in section and have circular/rectangular rigid spigots at each end. Four matching mounting feet are supplied with the unit. Full size access panels

More information

CBC - Active Chilled Beam. Halton CBC. Active Chilled Beam

CBC - Active Chilled Beam. Halton CBC. Active Chilled Beam Halton CBC Active Chilled Beam Combined cooling, heating, and supply air unit for flush installation within a suspended ceiling Well suited for spaces with high cooling loads and low humidity load Ideal

More information

Models Series Series

Models Series Series Models 3180-Series 3181-Series INDUSTRIAL DIAPHRAGM PUMPS Commercial Duty, 3 GPM/1 LPM FEATURES Sealless Easy Installation Run Dry Ability Flow to 3 GPM/1 LPM Self-Priming Low Amp Draw Thermal Overload

More information

Operation and Maintenance Manual Chamber Conditioning Unit, CCU 06. Document Number: EC OM 6847 Revision: 3

Operation and Maintenance Manual Chamber Conditioning Unit, CCU 06. Document Number: EC OM 6847 Revision: 3 Operation and Maintenance Manual Chamber Conditioning Unit, CCU 06 Part Number: KI40053 Document Number: EC OM 6847 Revision: 3 TABLE OF CONTENTS Table Of Contents Approval Sheet List of Abbreviations

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

Venco 75mm (3 ) Standard and De-airing Pugmill

Venco 75mm (3 ) Standard and De-airing Pugmill Owner s manual for Venco 75mm (3 ) Standard and De-airing Pugmill Venco Products 29 Owen Road Kelmscott, Western Australia 6111 ph +61 8 9399-5265 fax +61 8 9 497 1335 email: venwest@iinet.net.au www.venco.com.au

More information

MJC Cartridge Filter Unit Operation & Maintenance

MJC Cartridge Filter Unit Operation & Maintenance 1 of 19 Hodge Clemco Ltd MJC Cartridge Filter Unit Operation & Maintenance Owner s Manual Date of Issue: 19.07.04 TSSM536.1a Hodge Clemco Ltd Orgreave Drive Sheffield S13 9NR Tel: 0114 254 8811 Fax: 0114

More information

InterSeptor Centrifugal Separators Operating & Maintenance Manual

InterSeptor Centrifugal Separators Operating & Maintenance Manual General Information: This manual was prepared to assist in the installation, operation, and maintenance of PEP ICS centrifugal separator systems. For immediate response to questions not covered in this

More information

ZETA MAGNETIC AGITATORS

ZETA MAGNETIC AGITATORS ZETA MAGNETIC AGITATORS For sterile liquid processing www.zeta.com ZETA AGITATORS A VERSATILE PRODUCT FAMILY Proven agitator technology that meets the highest standards of sterile design and reliability.

More information

Homepage > Products > Grilles and Diffusers > Ceiling diffusers > Design ceiling swirl diffusers > Type ADD. Type ADD

Homepage > Products > Grilles and Diffusers > Ceiling diffusers > Design ceiling swirl diffusers > Type ADD. Type ADD Homepage > Products > Grilles and Diffusers > Ceiling diffusers > Design ceiling swirl diffusers > Type ADD Type ADD FOR THE CREATIVE DESIGN OF CEILINGS IN COMFORT ZONES, WITH FIXED AIR CONTROL BLADES

More information