Smoke Master SMPA Installation, operation and maintenance

Size: px
Start display at page:

Download "Smoke Master SMPA Installation, operation and maintenance"

Transcription

1

2 Contents Contents...2 Safety aspects...3 System overview...4 Installation...5 Installation of the fan unit...5 Electric installations...7 Stairwell smoke detectors...7 Relay unit for smoke detectors...7 Differential pressure transmitter...8 Control unit...9 Control panel...9 Electric connections...10 Connections to external systems (e.g. apartment air release paths or smoke detector system)...10 System operation...11 Pressurisation...11 Frequency converter...12 Tests and inspections...13 Initial inspection...13 Semi-annual inspections...13 Annual inspections...13 Maintenance...13 Electric components...14 Troubleshooting...15 Fläkt Woods FIFLO E

3 Safety aspects The control unit, the control panel, and the fan unit use a dangerously high voltage of 230V. The system should be made dead before any electrical or maintenance work. Electric installations should only be carried out by a suitably qualified electrician. Before any maintenance work is carried out on the fan unit, the safety switches for the fan and for the hatch opening motors should be turned to position 0. If the fan unit is installed in a place where it may cause danger, access to the unit should be prevented. The installer and the operator are jointly responsible for ensuring that the installation complies with all local rules and regulations. If the pressure side is not ducted, the product shall be provided with a safety mesh, e.g. BDKU. Fläkt Woods FIFLO E

4 System overview 1c 1a,1b or 1c 1b 2b/2c 4 SMPA-1 2a 1a Fan unit 2a, 2b or 2c 3 SMPZ-2 The SMOKE MASTER SMPA is an all-inclusive total solution for exit route pressurisation. The system has been designed and the components constructed to meet the E requirements. The system has been subjected to a variety of tests at Fläkt Woods own laboratories. SMPA has been designed for pressurisation of exit routes of different types, such as the stairwells of residential buildings, underground exit routes, and the exit routes from car parks. The SMPA-1 fan unit is available with three sizes which makes it suitable for use over a wide range of air volumes. Control unit 3 PRESSURISATIO PRESSURIS. STADBY SERVICE FA O MA Due to its compact structure, the SMPA fan unit (SMPA-1) has small overall dimensions and, therefore, it is also suitable for a variety of renovation projects. In blocks of flats, the fan unit can be installed in the upper or lower part of the stairwell. SMPZ-3 Control panel An SMPA total solution comprises a smoke hatch integrated into the encapsulated fan unit, a control panel, and a control unit. The apartment air release solutions with spindle motors, smoke detectors, and control units are supplied by our partners. 4 The distance between the fan unit SMPA-1 and the control unit SMPZ-2 should be less than 15 m. SMIZ-4 Differential pressure transmitter Fläkt Woods FIFLO E

5 Installation Installation of the fan unit Lifting SMPA at the installation site The unit is provided with three lifting lugs that should be used when lifting the unit with, for instance, lifting straps. If you remove the lifting lugs of the unit after installation, the lug fixing screws should be screwed back in when the lugs have been removed. Fläkt Woods FIFLO E

6 Installation 1. Wall mounting Threaded bar M10 **) Size A B b H h L Roof mounting Installation opening (b+50) x (h+50) Installation opening (b+50) x (h+50) **) Support brackets, e.g. L60x60x5 **) **) = not included Fläkt Woods FIFLO E

7 Electric installations Stairwell smoke detectors If the fire indication system of the building is used for alarm indication, no smoke detectors directly connected to the SMPA system are needed. The smoke detectors (FDRC-1-SMIA) allow direct connection to the SMPA system. There should be stairwell smoke detectors ceiling mounted at each landing, or according to a separate plan. The detectors (max. 32 units) should be connected in series, with a terminator connected to the last one (see wiring diagrams). The smoke detectors are supplied with plastic dust covers that should not be removed until the construction work is completed. Alternatively, the transmitters can be installed just before taking the system into use. The smoke detectors are optical and rated at 24 V. When a smoke detector detects smoke, the red LED on the detector is lit, and an alarm indication is provided to the control unit. The alarm remains active until reset at the relay unit included in the control unit. If no stairwell smoke detectors are installed, a 2.2 kohm terminator shall be connected to the control unit, in place of the indicator. Relay unit for smoke detectors The stairwell smoke detectors should be wired to the relay unit in the SMPA control unit. The relay unit monitors the operation of the smoke detectors. ormal operation: Green LED Operation illuminating. Service alarm: Yellow LED Service illuminating. Clean the smoke detector: the yellow LED should start flashing slowly. Reset the alarm using the Reset button: the yellow LED should go off. Error: Yellow LED Short circuit illuminating to indicate detector cable short circuit. Fix the problem: the yellow LED should start flashing slowly. Reset the alarm using the Reset button: the yellow LED should go off. Error: Yellow LED Broken line illuminating to indicate broken detector cable. Fix the problem: the yellow LED should start flashing slowly. Reset the alarm using the Reset button: the yellow LED should go off. Smoke alarm: Red LED Smoke alarm illuminating. Reset the alarm using the Reset button: the red LED should go off. Fläkt Woods FIFLO E

8 Electric installations Differential pressure transmitter The differential pressure transmitter should be installed in a sheltered place. The silicone hoses should not exceed 10m in length and should be shielded or otherwise replaced with pipes. Take the + hose to the stairwell and the hose outdoors. The end of the outdoor hose should be protected against wind and rain, however, without disturbing pressure measurement. The outdoor hose can be taken through a wall using a wall sleeve designed for overpressure meters (YM-1 + capped pipe + bend), available as an accessory. The differential pressure transmitter is set at the factory to 100 Pa range. Make sure the dip switch settings are as shown in the picture. The display of the pressure transmitter must be accessible to those conducting annual inspections. The display should be reset once a year. Disconnect the hoses and open the cover. Press and hold the Zero button for five seconds. The factory setting for the response time is 2s to ease off pressure control. The setting can be checked by placing dip switch PJ3 to the F position. Fläkt Woods FIFLO E

9 Electric installations Control unit The control unit should be installed not more than 15 metres away from the fan unit. It should be located in an easily accessible space to facilitate, for instance, the resetting of smoke detectors. Control panel The control panel should be placed in the stairwell near the entrance door where the rescue authorities can easily find it. PRESSURISATIO STADBY SERVICE PRESSURIS. FA O PRESSURISATIO STADBY SERVICE PRESSURIS. FA O MA MA Test operation: To access the switch, open the cover for test operation. Pressurisation can be switched on in the MA position. Standby: ormally, the PRESSURISATIO switch is in the AUT position and the green STADBY light illuminates. In the event of a fire, PRESSURISATIO starts automatically, and a fire fighter can brake the glass and switch pressurisation off, if necessary. Fläkt Woods FIFLO E

10 Electric connections o fault current protector should be used in the power supply line, because the frequency converter may trip it. Connections to an external system, e.g. an apartment smoke extraction window or a fire indicator system Pressurisation can be switched on from an external system using potential free, normally open contacts. The contacts shall remain closed during pressurisation. The voltage in the circuit is 24 VAC. The control unit provides potential free run and alarm signals. The run signal is activated when pressurisation or smoke extraction is in operation. This signal can be used for activating the emergency stop function of building ventilation, for instance. A warning signal is given if the system has a fault that prevents its operation. SMPA COTROL UIT K x0,8+0,8 12x1, x1,5 4x1,5 2x0,8+0,8 2x1,5 SD1 2x0,8+0,8 SD2 SD max 32 COTROL PAEL WARIG K V 24V 2x0,8+0,8 2,2 kohm OT SUPPLIED BY FLÄKT WOODS dpt 01 MU RU KEVI 4 5 SAFE M M 2x28 VA 1X230VAC 24V 24V APARTMET SMOKE EXTRACT WIDOW COTROL UIT CABLIG BETWEE MOTORS AD SAFETY SWITCHES ICLUDED I FLÄKT WOODS SUPPLY OTHER CABLIG TO BE ISTALLED BY A ELECTRICIA AT SITE CABLIG SHALL BE FIRE RESISTAT OR OTHERWISE PROTECTED AGAIST FIRE L3 L Supply cable max 5x6mm 3x2,5+2,5 screen T-S, 3L + MAX. LEGTH Ue 400 Vac, 50 Hz 15 m Q SAFE V1 W1 U1 M 3x400VAC APARTMET SMOKE EXTRACT WIDOW COTROL UIT "FAULT SIGAL SD M 1x230 Vac, 50 Hz SUPPLY WIDOW L3 L SD M 1x230 Vac, 50 Hz SUPPLY WIDOW APARTMET SMOKE DETECTOR OIG MOTOR MAUAL WIDOW OIG APARTMET SMOKE DETECTOR OIG MOTOR MAUAL WIDOW OIG "FAULT SIGAL L1 L2 L3 SI FREQUECY COVERTER x1,5 STAIRWELL SMOKE DETECTORS L1 L2 L U V W X1 PRESSURISATIO FA TF01 LIEAR MOTORS STO1/02 PRESSURE TRASMITTER dpt 01 RU SIGAL Fläkt Woods FIFLO E

11 System operation The components controlling SMPA are: the fuses and switches in the power supply cable for the control unit the fuses, frequency converter, relay unit and hatch opening switch inside the control unit the control panel the pressure transmitter the smoke detectors the safety switches for the fan unit external systems, if any. Pressurisation Starting When an SMPA smoke detector becomes activated, pressurisation starts if the control panel pressurisation switch is in the AUT position. A pressurisation start signal may also come to the SMPA control unit from an external system, in which case the pressurisation switch in the control panel must be in the AUT position. The pressurisation switch in the control panel is turned to the MA position. The hatch opens. In about 20 seconds, the fan starts running and blowing air into the building. The frequency converter in the control unit adjusts the fan speed according to the differential pressure value measured by the pressure transmitter and tries to maintain an overpressure of, for instance, 50 Pa in the stairwell. Stopping Pressurisation activated by an SMPA smoke detector shall be stopped by resetting the ABAV relay unit inside the SMPA control unit. There must not be any smoke around the smoke detector any more. Pressurisation activated by an external system shall be stopped from that system. Pressurisation activated from the control panel shall be stopped by turning the pressurisation switch to the AUT or 0 position. Fläkt Woods FIFLO E

12 Frequency converter The frequency converter controls the pressure during pressurisation. The parameters of the frequency converter are set at the factory. A list of these parameters is attached to this document. Error code Read the displayed code and remove the cause of the problem. Resetting after an error To reset an error that has caused the fan to stop use the back-up fuse to cut off power to the frequency converter and wait until the display has gone blank. Then, switch on power again. To reset the error, press the Reset/OFF key and then the AUTO/O key. Control panel The frequency converter should always be in the AUTO/ O mode! Pressure controller adjustment The pressure controller (PI) has been preadjusted to respond fast but without oscillation. If the leakage air flow of the building is small and oscillation occurs, the controller can be adjusted less sensitive by decreasing gain (7-33) and extending the integral time (7-34) Process PI Proportional Gain * Process PI Integral Time s * 9999 s Fläkt Woods FIFLO E

13 Tests and inspections Initial inspection 1. First measures Turn the control unit fuses to position 1. Turn the safety switches to position 1. Turn the control panel switch to position 0. Switch on power to the control unit. Reset the pressure transmitter to read 0 Pa. The differential pressure transmitter must be switched on approx. 15 minutes before resetting. Check that only the green Operation LED on the relay unit is on. Check that the frequency converter is in the Auto/On mode and does not display any error messages. The yellow Service LED on the control panel should now be on. Turn the PRESSURISATIO switch on the control panel to the AUT position. The green STADBY light should now come on. 2. Checking the operation of the hatch To open the hatch, turn switch S3 inside the control unit to position 1. If the hatch does not open, the reason may be that the safety switch is in position 0 or the linear motor is incorrectly connected. To close the hatch, return the switch to position Checking the operation of pressurisation Close all stairwell doors. Start pressurisation by turning the PRESSURISATIO switch on the control panel to position MA. Alternatively, with the PRESSURISATIO switch in position AUT, pressurisation can be activated from an external system or by triggering a smoke detector using test gas. The red PRESSURISATIO light on the control panel should come on. The fan unit hatch opens. In approximately 20 seconds, the fan will start running and air will start flowing into the stairwell. If the flow of air is in the wrong direction, interchange the connection of two phase conductors to the fan motor. The frequency converter in the control unit adjusts the fan speed according to the differential pressure value measured by the pressure transmitter and tries to maintain an overpressure of, for instance, 50 (±5) Pa in the stairwell. If the pressure will not rise, check the transmitter hoses and make sure all doors are properly closed. If the pressure oscillates too much, adjust the pressure controller according to the instructions. The intended air release path has to be kept open during testing to reduce vibrating. With the PRESSURISATIO switch in position AUT, reset the relay unit in the control unit by pressing the RESET button. The fan stops and the hatch closes. Semi-annual inspections Use the control panel switches to check the operation of the unit by letting it run approx. 10 minutes (see Initial inspection). Annual inspections Carry out the measures described under Initial inspection. Check that the hatch of the fan unit opens without trouble. Remove any obstructions. On the hatch opening motors, the following should be checked. o Security of motor mountings o Protection against moisture o Operation (testing) and electrical connections of the motors Also check that the hinges of the hatch are properly secured, and that the seals are tight. Check the condition of the transmitter hoses. Replace hoses as necessary. For resetting the pressure transmitter the hoses need to be detached from the transmitter. See installation of pressure transmitter. Fläkt Woods FIFLO E

14 Tests and inspections Maintenance of electric components Maintenance of the automatic system: Reset the pressure transmitter once a year. Clean smoke detectors when an error message has occurred. Replace fuses in the control unit as necessary. Annually inspect the frequency controller fan, and replace as necessary. Check control panel glass once a year. Check and replace control panel LEDs as necessary. Operations for fan maintenance The fan bearings must be replaced every ten years. Before starting maintenance work, at the power supply cabinet switch off the power supply to the fan and make sure that it cannot be accidentally switched on. Also turn the safety switches to position 0. First, expose the impeller end of the fan (safety switches), remove the safety mesh (if applicable) and the impeller. Then, undo the screws visible at the end of the electric motor, and withdraw the motor end cover together with the rotor. Replace the bearings on the rotor shaft and assemble the parts in reversed disassembly order. Fläkt Woods FIFLO E

15 Troubleshooting Problem Cause Action Yellow light on. Fault in the relay unit for smoke detectors. Circuit breaker 1F1 has tripped. Frequency converter fault. Hatch opening switch S3 (in the control unit) in position 1. Check the condition of smoke detectors. Clean the detectors and reset. Find out the cause of tripping and reset the circuit breaker to position 1. Read the error code displayed by the frequency converter and check it in the frequency converter manual. Return the switch to position 0. TSafety switch in position 0. Return the switch to position 1. Fan does not start. Pressurisation switch (on the control panel) in position 0. Frequency converter set to Off from the panel. Frequency converter parameters incorrectly set. Time relays operate incorrectly. Supply voltage fault. Return the switch to position AUT. Return the frequency converter to Auto/On mode. Check that the parameter settings are as listed. Check the correct operation of control unit time relays in wiring diagrams. Measure all phase and neutral conductors. A fault current protector in supply line may cause problems with the frequency converter. Hatch not opening. Control unit fuse 1F2 blown. Find out the cause and replace the fuse. Pressurisation cannot be activated from a system external to SMPA. Control unit fuses 1F3 and 2F1 blown. / External contact did not close. Find out the cause and replace the fuses. Pressure does not reach 50 Pa. Pressure hoses blocked or disconnected. Check the hoses. Doors and windows open. Pressure oscillates and will not settle. Establish standards-compliant test conditions. Settle pressure control (see adjusting instructions). Open the intended air release path. Faulty start / Fan does not stop. Smoke detector fault. Check the smoke detectors. External system fault. Relay unit for smoke detectors not reset. Pressurisation switch (on the control panel) in position MA. Check if an external system has given a Start signal. Reset the unit (in the control unit) using the Reset button. Return the switch to position AUT. o lights on. o supply voltage. Measure all phase and neutral conductors. A control light off when it should be on. Control unit fuse 1F3 blown. LED blown. Find out the cause and replace the fuse. Replace the LED. ote: 230VAC. Fläkt Woods FIFLO E

16 We Bring Air to Life Fläkt Woods is a global leader in air management. We specialise in the design and manufacture of a wide rande of air climate and air movement solutions. And our collective experience is unrivalled. Our constant aim is to provide systems that precisely deliver required functions and performance, as well as maximise energy efficiency. Solutions for all your air climate and air movement needs Fläkt Woods is providing solutions for ventilation and air climate for buildings as well as fan solutions for industry and infrastructure. Air Handling Units (AHUs) Modular, compact and small AHU units. Designed to ensure optimisation of indoor air quality, operational performance and service life. Air Terminal Devices and Ducts Supply and exhaust diffusers and valves for installation on walls, ceiling or floor are all included in our large range and fit all types of applications. Chilled Beams Active induction beams for ventilation, cooling and heating, and passive convection beams for cooling. For suspended or flush-mounted ceiling installation - and multi-service configuration. With unique Comfort Control and Flow Pattern Control features. Residential ventilation A complete range of products for residential ventilation. Consists of ventilation units, exhaust air fans and cooker hoods designed to optimise indoor comfort and save energy. Fans Advanced axial, centrifugal and boxed fans for general and specialist applications. Comprehensive range including high temperature and ATEX compliant options. Engineered for energy efficiency and minimised life cycle cost. Chillers Air-cooled and water-cooled chillers with cooling capacity up to 1800 kw. Designed to minimise annual energy consumption in all types of buildings. Controls and drives Variable speed drives and control systems, all tested to ensure total compatibility with our products. Specialist team can advise on energy saving and overall system integration. SMPA / E / / Fläkt Woods Oy Kalevantie 39, FI Turku, FILAD Tel

Smoke Master SMPA Compact pressurisation system

Smoke Master SMPA Compact pressurisation system Smoke Master SMPA Compact pressurisation system Fläkt Woods FILO E 2009.07 2 All rights reserved. Contents System overview...4 Design and operation...5 Technical specification...6 Electric and control

More information

Smoke Master SMIA Compact pressurisation and smoke exhaust system

Smoke Master SMIA Compact pressurisation and smoke exhaust system Smoke Master SMIA Compact pressurisation and smoke exhaust system Fläkt Woods FIFLO EN 2009.09 2 All rights reserved. Contents System overview... 4 Design and operation... 5 Technical specification...

More information

Smoke extract fan SMHA HATCH

Smoke extract fan SMHA HATCH 12.11.2012 Contents Product overview... 3 Construction... 4 Specification... 5 Selection... 6 Installation... 7 Electrical connections... 8 Dimensions and weights... 9 Product code and accessories... 10

More information

Smoke Control Ducts and Dampers For Single Compartment Applications. Fulfilling new requirements for EN product standards for CE Marking

Smoke Control Ducts and Dampers For Single Compartment Applications. Fulfilling new requirements for EN product standards for CE Marking Smoke Control Ducts and Dampers For Single Compartment Applications Fulfilling new requirements for EN product standards for CE Marking New Smoke Control Product Range Fläkt Woods Smoke Control Ducts and

More information

PFS Single stage axial fan The axial fan for modern boiler plants

PFS Single stage axial fan The axial fan for modern boiler plants PFS Single stage axial fan The axial fan for modern boiler plants This large axial fan, type PFS- 400-236, was installed in 1987 at the Salmisaari coal-fired power station in Helsinki, Finland. The photo

More information

Unit heater with accessories

Unit heater with accessories LVD Unit Heater Unit heater with accessories The type LVDV fan-assisted unit heaters are designed for space heating in shop entrances, lobbies, doorways, warehouses and workshops, garages and similar premises.

More information

ClimaFläkt. Chillers and condensing units

ClimaFläkt. Chillers and condensing units ClimaFläkt Chillers and condensing units Cooling Solutions Even the most efficient systems require addition of heating and cooling. For such needs Fläkt Woods provides thermodynamic solutions from 6 to

More information

EU Air Handling Units with SEMCO EXCLU-SIEVE

EU Air Handling Units with SEMCO EXCLU-SIEVE EU Air Handling Units with SEMCO EXCLU-SIEVE The acquisition of US based Semco has given us the opportunity to include a new range of rotary heat exchangers in our EU air handling unit range. Hygienic

More information

Climatix LON communication with POL SNVTs for Twin Wheel application v1.x

Climatix LON communication with POL SNVTs for Twin Wheel application v1.x Climatix SNVTs for Twin Wheel application v1.x Table of contents 1 About this document...3 1.1 Revision history...3 1.2 Before you start...3 1.3 Reference documents...3 2 Application...4 2.1 General information...4

More information

Climatix LON communication with POL SNVTs for eq zone application v1.x

Climatix LON communication with POL SNVTs for eq zone application v1.x Climatix SNVTs for eq zone application v1.x Table of contents 1 About this document...3 1.1 Revision history...3 1.2 Before you start...3 1.3 Reference documents...3 2 Application...4 2.1 General information...4

More information

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP WWPPCHLFT260 Instructions WWPPCHLFT260_Horizontal Multistage Centrifugal Pump_IB.indd 1 READ THIS MANUAL CAREFULL BEFORE INSTALL, START THE PUMP 1. Suction 2. Plug

More information

DRI-ECO-HEAT-HCS Whole House Ventilation Unit with Hall Control

DRI-ECO-HEAT-HCS Whole House Ventilation Unit with Hall Control Whole House Ventilation Unit with Hall Control Installation & Maintenance The EMC Directive 2014/30/EU The ow Voltage Directive 2014/35/EU 1.0 ITRODUCTIO The provides whole home ventilation using the Positive

More information

VETO CLEANER 500 FLUE GAS CLEANER

VETO CLEANER 500 FLUE GAS CLEANER As of serial number 3100 0001 VETO CLEANER 500 FLUE GAS CLEANER USER MANUAL SPARE PARTS LIST Manufacturer: ALA TALKKARI Veljekset Ala-Talkkari Oy FI-62130 HELLANMAA TEL. +358 6 433 6333 FAX +358 6 437

More information

Instructions for the BASIC BCRW Fan, Sizes General

Instructions for the BASIC BCRW Fan, Sizes General Instructions for the BASIC BCRW Fan, Sizes 004 027 1. General The BCRW is a direct-driven fan of axi-centrifugal design. This fan offers excellent power efficiency, low, uniform air flow, low sound generation

More information

The CAB & DAB Air Curtains

The CAB & DAB Air Curtains The CAB & DAB Air Curtains Frequently Asked Questions General Positioning Page 2 Electrical & Connection Page 4 Electric Heated Page 5 Electronic door triggered shutdown feature (Electric) Page 5 Electronic

More information

GLEB. >> Installation and Maintenance. Air Comfort. Air movement. Duct & Box Fans

GLEB. >> Installation and Maintenance. Air Comfort. Air movement. Duct & Box Fans Air Comfort Air movement Duct & Box Fans GLEB KITCHEN exhaust FAN >> Installation and Maintenance Kitchen Exhaust Fan GLEB Installation and Maintenance Important Information, Safety notes, Technical Description

More information

TopMaster Air Handling unit. Installation instructions

TopMaster Air Handling unit. Installation instructions Installation instructions Safety Instructions Operation of Air Handling units and accessories WARNING Installation may only be carried out by qualified personnel. Before taking the air handling unit into

More information

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE 2 GLEC-6 - Installation and maintenance CONTENTS 1 Important information... 3 2 Safety notes... 3 3 Technical description...4 4 Transport... 6 5

More information

Original instructions AR

Original instructions AR Original instructions SE... 8 GB... 22 NO... 27 FR... DE... 6 ES... 4 NL... 46 IT... 5 RU... 56 Dimensions and connections AR20/AR25 M8 002/52 940/450 494 449 92 20 98 042/552 42 20 AR20/25A/E 40 275 DN5

More information

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter VALLOX Product Code: 3158400 L 3158410 R SILENCER (OPTIONAL) INSTRUCTIONS FOR USE AND MAINTENANCE WATER CIRCULATED POST-HEATING UNIT (OPTIONAL) ELECTRIC POST-HEATING UNIT (OPTIONAL)) PREHEATER (OPTIONAL)

More information

Snifter ATEX22 VERSION. User Manual. Distributor

Snifter ATEX22 VERSION. User Manual. Distributor Snifter ATEX22 VERSION User Manual Distributor Version 1.4 09/09/2009 Table of Contents 1. INTRODUCTION... 3 1.1. Safety... 3 1.2. Product overview... 4 1.3. How does it work?... 4 2. INSTALLATION... 5

More information

Instructions for the fan motor control system, SILVER C

Instructions for the fan motor control system, SILVER C Instructions for the fan motor control system, SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units. The motor control system is

More information

Table of Contents. 1. Mounting Tips... 2

Table of Contents. 1. Mounting Tips... 2 Table of Contents 1. Mounting Tips............................................. 2 1.1. Connections and DIP switch settings................................... 3 1.2. Mounting the Fireray 50/100RV........................................

More information

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes 50-120 1 General The heat exchanger control system is a control system for 380 W step motors

More information

Climatix Basic reference addresses for eq Fläkt application v1.x

Climatix Basic reference addresses for eq Fläkt application v1.x Climatix Basic reference addresses for eq Fläkt application v1.x Modbus communication, slave mode Table of contents 1 About this document...3 1.1 Revision history...3 1.2 Before you start...3 1.3 Reference

More information

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Instructions for the fan motor control system with integrated wiring terminals SILVER C Instructions for the fan motor control system with integrated wiring terminals SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units.

More information

DIF-OT Ceiling Filter. The optimized laminar airflow

DIF-OT Ceiling Filter. The optimized laminar airflow DIF-OT Ceiling Filter The optimized laminar airflow When hygiene is crucial The operating room is the most critical zone of the hospital. The operating theatre must be a clean room to protect the patient.

More information

GLEB Kitchen exhaust fan

GLEB Kitchen exhaust fan GLEB Kitchen exhaust fan Installation and Maintenance??.1.2013 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

GLEC exhaust FAN. Air Comfort. Air movement. Duct & Box Fans

GLEC exhaust FAN. Air Comfort. Air movement. Duct & Box Fans Air Comfort Air movement Duct & Box Fans GLEC exhaust FAN» Technical CATALOUGE Technical catalouge Exhaust Fan GLEC 2 Contents Exhaust fan - GLEC... 3 Performance Data...4 Fan chart-explanation and definitions...

More information

Reflective Optical Beam Smoke Detector User Guide

Reflective Optical Beam Smoke Detector User Guide Reflective Optical Beam Smoke Detector User Guide 1. Installation IMPORTANT NOTE: The infrared beam path MUST be kept clear of obstructions at all times! Failure to comply may result in the system initiating

More information

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998

More information

AC25. Art.nr:

AC25. Art.nr: GB Installation and maintenance instruction for air curtains IMPORTANT: Read these instructions before the product is installed and used. Save the instructions for future use...2 Art.nr: 172785-01 Assembly

More information

DRI-ECO-LINK-HC 1.0 INTRODUCTION 4.0 DIFFUSER INSTALLATION 2.0 IMPORTANT NOTES TO INSTALLERS 3.0 LOFT INSPECTION

DRI-ECO-LINK-HC 1.0 INTRODUCTION 4.0 DIFFUSER INSTALLATION 2.0 IMPORTANT NOTES TO INSTALLERS 3.0 LOFT INSPECTION 1.0 ITRODUCTIO DRI-ECO-IK-HC Whole House Ventilation Unit with Hall Control Installation and Maintenance The DRI-ECO-IK-HC provides whole home ventilation using the Positive Input Ventilation principle.

More information

EBC20. Instructions for fitting, installation and operation. Read and save these instructions!

EBC20. Instructions for fitting, installation and operation. Read and save these instructions! EBC20 UK Instructions for fitting, installation and operation Read and save these instructions! 2 3002878 EBC20 UK 290415 1. Product information............................................... 4 1.1 Delivery.............................................................

More information

Top tip No. 21 Fireman s override

Top tip No. 21 Fireman s override Top tip No. Fireman s override Low voltage AC drives 30 TOP TIPS Not all variable-speed drives (VSDs) have a fireman s override Not all variable-speed drives (VSDs) have a fireman s override simply because

More information

Sintrol Snifter A1+ Manual. Version 1.2.2

Sintrol Snifter A1+ Manual. Version 1.2.2 Sintrol Snifter A1+ Manual Version 1.2.2 Table of Contents 1 INTRODUCTION... 3 1.1 Safety... 3 1.2 Product overview... 3 1.3 How does it work?... 3 2 INSTALLATION... 4 2.1 Selecting the installation location...

More information

30 top tips to tackle HVAC challenges No.21 - Fireman s override

30 top tips to tackle HVAC challenges No.21 - Fireman s override ABB DRIVES AND MOTORS 30 top tips to tackle HVAC challenges - Fireman s override 1 Not all variable-speed drives (VSDs) have a fireman s override Not all variable-speed drives (VSDs) have a fireman s override

More information

PLENUM FAN EQLK PLENUM FAN, DIRECT-DRIVEN

PLENUM FAN EQLK PLENUM FAN, DIRECT-DRIVEN EQLK, DIRECT-DRIVEN INSTALLATION AND MAINTENANCE INSTRUCTIONS Contents Page Installation options...... 2 Checks to be made prior to commissioning...2 Electrical connections.....2 Measures before starting.....

More information

more than just a fan supplier more than just a fan supplier Axair Fans UK Limited

more than just a fan supplier more than just a fan supplier Axair Fans UK Limited 1 more than just a fan supplier The most diverse range of industrial fans & accessories available from a single source... 2 products oem & industrial 3 single inlet centrifugal backward curved centrifugal

More information

TopMaster Air Handling unit. Technical data

TopMaster Air Handling unit. Technical data Technical data Contents Page Description of the unit... 3 Design... 4 Technical data Size 030... 5 Size 0... 6 Accessories... 7 Controls... 9 Control functions... 10 Order codes... 11 Fläkt Woods 8180

More information

SERIES 4000 AUTO GATE MANUAL

SERIES 4000 AUTO GATE MANUAL SERIES 4000 AUTO GATE MANUAL Website: www.turnstilesecurity.com Page 1 of 27 Table of Contents 1.0 Warranty... 4 2.0 Safety... 5 2.1 Designated Use... 5 2.2 Areas of Application... 5 2.3 Warning Notes...

More information

AIR HEATING UNIT HEATMASTER ACJB INSTALLATION, OPERATION, MAINTENANCE AND SPARE PARTS

AIR HEATING UNIT HEATMASTER ACJB INSTALLATION, OPERATION, MAINTENANCE AND SPARE PARTS AIR HEATING UNIT HEATMASTER ACJB INSTALLATION, OPERATION, MAINTENANCE AND SPARE PARTS 2 Air Heating unit ACJB - Technical manual CONTENTS OPERATION AND MAINTENANCE (FOR USER) System, functions, main components...3

More information

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D CENTRIFLOW 3D Plug fan GMEC >> Installation and Maintenance air comfort CentriFlow 3D 2 Plug Fan CentriFlow 3D GMEC Installation and Maintenance Important Information, Safety notes, Technical Description

More information

AIR TREATMENT. ReCOOLER HP» INTEGRATED COOLING/HEATING FUNCTION WITH REVERSIBLE HEAT PUMP IN THE eq AIR HANDLING UNIT

AIR TREATMENT. ReCOOLER HP» INTEGRATED COOLING/HEATING FUNCTION WITH REVERSIBLE HEAT PUMP IN THE eq AIR HANDLING UNIT AIR TREATMENT ReCOOLER HP ReCOOLER HP» INTEGRATED COOLING/HEATING FUNCTION WITH REVERSIBLE HEAT PUMP IN THE eq AIR HANDLING UNIT Energy efficiency the essence of our solutions All our research, development

More information

USER S MANUAL. Heat (Energy) Recovery Ventilator. Vents Frigate HRV 120 S Vents Frigate ERV 120 S

USER S MANUAL. Heat (Energy) Recovery Ventilator. Vents Frigate HRV 120 S Vents Frigate ERV 120 S USER S MANUAL Heat (Energy) Recovery Ventilator Vents Frigate HRV 120 S Vents Frigate ERV 120 S 2 Frigate HRV(ERV) 120 S CONTENT Introduction... 3 Application... 3 Delivery set... 3 Unit designation key...

More information

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS CONTENTS 1. INTRODUCTION... 5 2. WARNINGS... 6 3. GENERAL DESCRIPTION... 7 4. INSTALLATION... 8 5. LUMINOUS INDICATORS AND COMMANDS... 9 6. DIP-SWITCH

More information

SET-2000 Hi Level/Oil

SET-2000 Hi Level/Oil Labkotec Oy Labkotie 1 FI-36240 KANGASALA FINLAND Tel: + 358 29 006 260 Fax: + 358 29 006 1260 13.03.2008 Internet: www.labkotec.fi Alarm Device for Oil Separators Copyright 2008 Labkotec Oy We reserve

More information

OilSET Installation and Operating Instructions. Oil Separator Alarm Device

OilSET Installation and Operating Instructions. Oil Separator Alarm Device Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 18.11.2010 Internet: www.labkotec.fi 1/10 OilSET-1000 Oil Separator Alarm Device Copyright 2010 Labkotec

More information

RE-PR3-E-27 3-Phase Panel Mount 27kW

RE-PR3-E-27 3-Phase Panel Mount 27kW Page 1 of 6 RE-PR3-E-27 3-Phase Panel Mount 27kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting

More information

Installation, Operation & Maintenance Instructions Annealing Ovens TLD models

Installation, Operation & Maintenance Instructions Annealing Ovens TLD models Installation, Operation & Maintenance Instructions Annealing Ovens TLD models This manual is for the guidance of operators of the above Carbolite products and should be read before the oven is connected

More information

Snifter. User Manual. Distributor

Snifter. User Manual. Distributor Snifter User Manual Distributor Version 1.3 08/09/2009 1 Table of Contents 1. INTRODUCTION... 3 1.1 Safety... 3 1.2 Product overview... 3 1.3 How does it work?... 3 2. INSTALLATION... 4 2.1 Selecting the

More information

Model 17A00 Expansion Enclosure

Model 17A00 Expansion Enclosure HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number

More information

SMOKE CONTROL - NEW DIRECTIONS

SMOKE CONTROL - NEW DIRECTIONS SMOKE CONTROL - NEW DIRECTIONS Nuaire provides the total package for smoke control with schemes designed to fully comply with statutory and regulatory requirements. Our team of skilled engineers include

More information

MD12-1 Vehicle Loop Detector

MD12-1 Vehicle Loop Detector MD12-1 Vehicle Loop Detector Features Supply 12VDC Adjustable sensitivity (16 levels via a trimpot) 2 x Relay outputs (each can be configured individually) Power up and loop activation LED indicator. Industry

More information

IMPORTANT. PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times!

IMPORTANT. PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times! USER GUIDE English IMPORTANT PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times! Failure to comply may result in the Detector initiating a Fire or Fault signal. Contents

More information

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices. FireCell Radio Hub Fully addressable Wireless activation Third party approved (EN54) 2-way radio communication Loop powered Diagnostics port Range in excess of 150 metres Overview The model FCX-500-001

More information

Superior. A Compact Floor Standing Gas Fired, High Efficiency Condensing Hot Water Boiler. Outputs 120, 160, 200, 240, 280 kw

Superior. A Compact Floor Standing Gas Fired, High Efficiency Condensing Hot Water Boiler. Outputs 120, 160, 200, 240, 280 kw Superior A Compact Floor Standing Gas Fired, High Efficiency Condensing Hot Water Boiler Outputs 120, 160, 200, 240, 280 kw 1 The Superior is a, pre-assembled floor standing, gas fired high efficiency

More information

NOTICE . SAFE SERVICING PRACTICES. Electric Wall Oven with Electronic Oven Control

NOTICE . SAFE SERVICING PRACTICES. Electric Wall Oven with Electronic Oven Control SERVICE DATA SHEET 318047418 (0504) Rev. A Electric Wall Oven with Electronic Oven Control NOTICE This service data sheet is intended for use by persons having electrical and mechanical training and a

More information

Installation instructions for the optical detector with built-in control unit, TBLZ-1-72-a GOLD/COMPACT

Installation instructions for the optical detector with built-in control unit, TBLZ-1-72-a GOLD/COMPACT Installation instructions for the optical detector with built-in control unit, TBLZ-1-72-a GOLD/COMPACT 1. General The TBLZ-1-72-a optical smoke detector with built-in control unit is used for measuring

More information

CONTROL DEVICE SLIDETRONIC HD

CONTROL DEVICE SLIDETRONIC HD CONTROL DEVICE SLIDETRONIC HD to control gravity self-closing fire gates Producer: Somati system s.r.o. Jihlavská 510/2c 664 41 Troubsko, okr.brno - venkov Tel.: 547 427 011 Fax: 547 427 013 E-mail: export@somati-system.cz

More information

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor Labkotec UK Ltd Adminicle House 1 Lumb Lane Audenshaw Manchester M34 5WH GREAT BRITAIN Tel: 0844 3350 477 Fax: 0161 4281 179 E-mail: info@labkotec.co.uk 10.8.2012 Internet: www.labkotec.co.uk 1/13 OilSET-1000

More information

Indoor Infrascan Passive Infrared Motion Sensor. Series. Installation Instructions. Please leave these instructions at the installation site.

Indoor Infrascan Passive Infrared Motion Sensor. Series. Installation Instructions. Please leave these instructions at the installation site. Indoor Infrascan Passive Infrared Motion Sensor 751 Series Installation Instructions Please leave these instructions at the installation site. Table of Contents 1.0 Product Range...3 2.0 Description...3

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

DRI-ECO-HEAT-HC. Whole House Ventilation Unit with Hall Control. Installation, Maintenance and Operation

DRI-ECO-HEAT-HC. Whole House Ventilation Unit with Hall Control. Installation, Maintenance and Operation Whole House Ventilation Unit with Hall Control Installation, Maintenance and Operation The EMC Directive 2014/30/EU The ow Voltage Directive 2014/35/EU 1.0 SAFETY IFORMATIO The provision of the electrical

More information

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TRACON MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TABLE OF CONTENTS FPT 130 Overview... 2 Installation... 3 Power Source and Load Connections... 4 Temperature Sensor... 5 External

More information

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h PRODUCT DATA COMFORT 40 BY NILAN Ventilation & passive heat recovery Domestic Passive heat recovery Ventilation < 40 m /h COMFORT 40 Product description The Comfort 40 is an energy-efficient ventilation

More information

MANUAL. OEM (Unit) OZONE GENERATOR (100VA, 200VA and 300VA) INDEX

MANUAL. OEM (Unit) OZONE GENERATOR (100VA, 200VA and 300VA) INDEX MANUAL OEM (Unit) OZONE GENERATOR (100VA, 200VA and 300VA) INDEX 1) Technical Specifications: (100VA, 200VA, 300VA) 2) Introduction 3) Construction 4) Operation and maintenance a) Operating Procedure b)

More information

Cleaning doors. Good indoor air also means cleanability of ductwork

Cleaning doors. Good indoor air also means cleanability of ductwork Good indoor air also means cleanability of ductwork General An AC plant must be designed, constructed and installed so that its interior, all of its components, including those inside ducts, and the ductwork

More information

Instruction Manual WARNINGS

Instruction Manual WARNINGS Instruction Manual LARGE COMMERCIAL RECESSED AIR CURTAIN HSACR9000, 12000 & 18000 ELECTRICALLY HEATED RECESSED AIR CURTAINS WITH ENERGY SAVING CONTROLS INSTALLATION AND OPERATING MANUAL INDEX Section General

More information

7 YEAR. The DRIMASTEReco Range DRI-ECO-HC NUAIRE S PIV: HALL CONTROL

7 YEAR. The DRIMASTEReco Range DRI-ECO-HC NUAIRE S PIV: HALL CONTROL NUAIRE S PIV: HALL CONTROL The DRIMASTEReco Range The DRIMASTER-ECO range provides whole home ventilation using the Positive Input Ventilation principle, which introduces fresh filtered air into the dwelling

More information

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual We manage heat MANUAL Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations: F1! 44487023 These instructions cover the following parts: PS902 Power Supply Installation Instructions! DANGER: To avoid risk of electric shock, turn off AC power before installing or servicing PS902

More information

Analog Room Pressure Monitor RPC Series

Analog Room Pressure Monitor RPC Series Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the

More information

MD12-2 Vehicle Loop Detector

MD12-2 Vehicle Loop Detector MD12-2 Vehicle Loop Detector Features Supply 12VDC Adjustable sensitivity (8 levels via dip switch) 2 x Relay outputs (each can be configured individually) Power up and loop activation LED indicator. Industry

More information

2

2 Installation Operation Commissioning Maintenance N 11.47A 2 3 1 g c e f b j d h a i 4 2 1 2 3 4 9 5 8 10 6 7 3 5 4 6 5 6 7 8 7 9 a b 10 8 11 12 9 13 14 15 2 16 1 17 a 10 18 rep.2 rep.1 rep.3 rep.4 19 11

More information

Products documentation (REVISION DATE: 03/10/2011) OMFP6010 (60cm PIROLITIC OVEN)

Products documentation (REVISION DATE: 03/10/2011) OMFP6010 (60cm PIROLITIC OVEN) Products documentation (REVISION DATE: 03/10/2011) OMFP6010 (60cm PIROLITIC OVEN) Ovens Service Manual Models OMFP6010 CONTENTS This document has been published to be used for service only. The contents

More information

EC Box Fan www.flaktwoods.com/oandm Safety, Installation, Operation and Maintenance Instructions CONTENTS Paragraphs Safety 1 Handling/Storage 2 Installation (Mechanical) 3 Fig. 1: Fig. 2: Tilt Mechanism

More information

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0) Overview of the Water Detection System 2 Components of a System 4 Design & Planning 5 System Installation Notes 7 Control Panel Installation - HSCPI-K3000 8 Control Panel Commissioning HSCPC-K3000 11 Front

More information

SMARTELEC 2 ENERGY SAVING CONTROL INSTALLATION AND OPERATING MANUAL

SMARTELEC 2 ENERGY SAVING CONTROL INSTALLATION AND OPERATING MANUAL Instruction Manual. SMARTELEC 2 SmartElec ENERGY SAVING CONTROL INSTALLATION AND OPERATING MANUAL 0 F1 INDEX Section General information ------------------------------------------------------------ 1 Dimensions

More information

EVAPORATIVE COOLER PUMPS

EVAPORATIVE COOLER PUMPS EVAPORATIVE COOLER PUMPS ebmpapst Evaporative Cooler Pump EBMALPHA $144.65 @ 1. metre Head @ 2. metre Head Power Supply 32 litres/min 25 litres/min 24V/1/5Hz Nominal Watts 5 watts Outlet Connection 2mm

More information

Screw Water Cooled Chiller SCW210

Screw Water Cooled Chiller SCW210 Screw Water Cooled Chiller SCW210 Nominal Cooling Capacity 185.1 to1480.8 kw Refrigerant: R407C and R134a Contents Features 1 MV7 Control 3 Physical Data 5 Unit Performance 8 Chiller Selection 9 Physical

More information

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions SET-000 Oil/Sludge Alarm Device for Oil Separators Copyright 007 Labkotec Oy We reserve the right for changes without notice TABLE OF CONTENTS GENERAL... INSTALLATION... 4. SET-000 Oil/Sludge Control Unit...

More information

OPERATION MANUAL. Move it. Hang it. Rack it. Stack it. MaxPower Corporation 230 Yuma Street Denver, CO

OPERATION MANUAL. Move it. Hang it. Rack it. Stack it. MaxPower Corporation 230 Yuma Street Denver, CO OPERATION MANUAL Complete Instructions for and Operation MaxPower Corporation 230 Yuma Street Denver, CO 80223 800-576-3966 www.coolcube10.com Move it. Hang it. Rack it. Stack it. 05/05 P/N: 5-TC600-2510

More information

recooler HP EQKR HEAT PUMP

recooler HP EQKR HEAT PUMP AIR COMFORT AIR TREATMENT 9566 GB 2016.03.17 recooler HP EQKR HEAT PUMP» TECHNICAL CATALOGUE 2 ReCooler HP EQKR Technical Catalogue Content ReCOOLER HP EQKR HEAT PUMP 3 product presentation. 3 applications.

More information

OSA 3. Level alarm for oil separator. Afriso Ema AB. Kilvägen 2 SE Arlöv Sweden T +46-(0) F +46-(0)

OSA 3. Level alarm for oil separator. Afriso Ema AB. Kilvägen 2 SE Arlöv Sweden T +46-(0) F +46-(0) Level alarm for oil separator CONTENTS: Functional description... 2 Component parts... 3 Spare parts... 5 Safety regulations... 6 Checklist... 7 Installation... 8 Commissioning... 11 Operation... 14 Maintenance...

More information

User Manual 120/240/300 Outdoor Motion Detector

User Manual 120/240/300 Outdoor Motion Detector User Manual 120/240/300 Outdoor Motion Detector Swiss Garde 4000 Warning! - Any work on the main power supply must only be completed by trained specialists. - The product must be installed in accordance

More information

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl enproteko.com Temperature Monitoring Relay K8AB-TH Compact and Slim Relay Ideal for Temperature Alarms and Monitoring Excessive increases can be prevented and abnormal s can be monitored. Temperature monitoring

More information

MARINE APPLICATIONS MARINE» PRODUCTS AND SOLUTIONS FOR MARINE APPLICATIONS

MARINE APPLICATIONS MARINE» PRODUCTS AND SOLUTIONS FOR MARINE APPLICATIONS MARINE APPLICATIONS MARINE» PRODUCTS AND SOLUTIONS FOR MARINE APPLICATIONS MEETING THE HIGHEST DEMANDS - EFFICIENT HVAC SOLUTIONS FOR ARCTICAL TO TROPICAL CONDITIONS AT FLÄKTGROUP WE WANT TO EXCEED the

More information

INSTALLATION AND OPERATION INSTRUCTIONS FOR ZERO CLEARANCE AND INSERT UNITS

INSTALLATION AND OPERATION INSTRUCTIONS FOR ZERO CLEARANCE AND INSERT UNITS INSTALLATION AND OPERATION INSTRUCTIONS FOR ZERO CLEARANCE AND INSERT UNITS ZECL-26-2923-BG ZECL-30-3226-BG ZECL-33-3624-BG ZECL-39-4134-BG ZECL-2939-BG INSERT-26-3825-BG INSERT-30-4026-BG INSERT-33-4230-BG

More information

Supply air unit VEKA Installation & Maintenance

Supply air unit VEKA Installation & Maintenance November 2008 Safety instructions Operating the air treatment unit and accessory components WARNING Before the air treatment unit is taken into service, any free connections must be provided with protective

More information

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59 SOUND-INSULATED FAN OPERATION MANUAL _v.1(2)-en.indd 1 10.08.2015 15:20:59 CONTENT Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 3 Fan design 4 Delivery

More information

INSTALLATION & USER MANUAL

INSTALLATION & USER MANUAL INSTALLATION & USER MANUAL HC Digital Automatic Humidistat (Y3760) CONTROLS 506808-01 3/2016 Supersedes 6/2011 picture goes here THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE NOTICE

More information

LC2200 Level Controller Installation and Maintenance Instructions

LC2200 Level Controller Installation and Maintenance Instructions 4025250/9 IM-P402-77 AB Issue 9 LC2200 Level Controller Installation and Maintenance Instructions LC2200 ALARM TEST >50% >100%

More information

5000 INSTALLATION GUIDE

5000 INSTALLATION GUIDE 5000 INSTALLATION GUIDE Table of Contents Section Page No 1. INTRODUCTION... 3 2. WARNINGS AND CAUTIONS... 3 3. UNPACKING... 3 4. INSTALLATION... 4 5. CONTROL PANEL - REMOVING ITEMS BEFORE MOUNTING...

More information

Chapter 3 Cooling, heating and ventilation systems

Chapter 3 Cooling, heating and ventilation systems 3 1 Chapter 3 Cooling, heating and ventilation systems Contents Antifreeze mixture..............................see Chapter 1 Cooling fan assembly - testing, removal and refitting.............8 Cooling

More information

HEAT RECOVERY AIR HANDLING UNIT

HEAT RECOVERY AIR HANDLING UNIT HEAT RECOVERY AIR HANDLING UNIT OPERATION MANUAL KOMFORT_L v2(2)_en.indd 1 07.08.2015 15:0:44 CONTENTS Introduction General Safety regulations Transportation and storage regulations Manufacturer's warranty

More information

Sintrol Snifter A2 EX. Manual. Version 1.2.3

Sintrol Snifter A2 EX. Manual. Version 1.2.3 Sintrol Snifter A2 EX Manual Version 1.2.3 Table of Contents 1 INTRODUCTION... 3 1.1 Safety... 3 1.2 Product overview... 4 1.3 How does it work?... 4 2 INSTALLATION... 4 2.1 Selecting the installation

More information

5, SE GÅNGHESTER,

5, SE GÅNGHESTER, KSUB Control and monitoring unit Valid from week of manufacture 48/2005 Description The KSUB is a control and monitoring unit designed to control various types of fire/smoke dampers and fans in a flexible

More information

SET-2000 Oil/Sludge 12 VDC

SET-2000 Oil/Sludge 12 VDC Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: + 358 29 006 260 Fax: + 358 29 006 1260 12.2.2015 Internet: www.labkotec.fi 1/14 SET-2000 Oil/Sludge 12 VDC Alarm Device for Oil Separators with

More information

GS100M Gas Detector. Technical Specification

GS100M Gas Detector. Technical Specification GS00M Detector Application Duomo is recognised within the Gas industry for providing a comprehensive range of low cost, high reliability gas detection for many applications. We have installed and commissioned

More information