Modbus Point Map. for the. Data Aire DAP-II
|
|
- Gertrude Lloyd
- 5 years ago
- Views:
Transcription
1 Modbus Point Map for the Data Aire DAP-II Revision 1 November 11, 2003 Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865
2 Table of Contents 1 Introduction Scope References Modbus Register Definitions Status Alarms Control Read/Write Configuration
3 1 Introduction 1.1 Scope This document describes the implementation of the point map for the Modbus protocol on the Data Alarm Processor II (DAP-II). 1.2 References MODBUS Application Protocol Specification V1.1, Modbus.org, December 6, Modicon Modbus Protocol Reference Guide - PI-MBUS-300 Rev. J, Modicon, Inc., June Open Modbus/TCP Specification Release 1.0, Andy Swales, Schneider Electric, 29 March
4 2 Modbus Register Definitions 2.1 Status Discrete Input 0 Unit is dehumidifying Discrete Input 1 Unit is humidifying Discrete Input 2 Energy saver is active Discrete Input 3 Needed cooling is inhibited Discrete Input 4 Needed heating is inhibited Discrete Input 5 Needed humidification is inhibited Discrete Input 6 Needed dehumidification is inhibited Discrete Input 47 Reheat mode during dehumidification Input Register 1 Current Return Temperature (0.1 F) Input Register 2 Current Humidity (0.1 %) Input Register 3 Current Discharge Temperature (0.1 F) Input Register 4 Cooling stages on (0-5) Input Register 5 Heating stages on (0-4) Input Register 6 Valve percent open (0-100) (255 = off) Input Register 7 H Valve percent open (0-100) (255 = off) Input Register 8 High temperature last 24 hours (0.1 F) Input Register 9 Low temperature last 24 hours (0.1 F) Input Register 10 High humidity last 24 hours (0.1 F) Input Register 11 Low humidity last 24 hours (0.1 F) Input Register 12 Cooling Utilization Last 24 Hours (0-100 %) Input Register 13 Heating Utilization Last 24 Hours (0-100 %) Input Register 14 Chilled Water Utilization Last 24 Hours (0-100 %) Input Register 15 Humidifier Utilization Last 24 Hours (0-100 %) Input Register 16 Compressor #1 Runtime Input Register 17 Compressor #2 Runtime Input Register 18 Compressor #3 Runtime Input Register 19 Compressor #4 Runtime Input Register 20 Heater #1 Runtime Input Register 21 Heater #2 Runtime Input Register 22 Heater #3 Runtime Input Register 23 Humidifier Runtime Input Register 24 Evap Blower Runtime Input Register 25 Condenser Runtime Input Register 26 Dehumidifier Runtime Input Register 27 Energy Saver Cooler Runtime Input Register 28 Chilled Water Cooling Runtime 4
5 2.2 Alarms Discrete Input 7 Water detected under floor: Check probe Discrete Input 8 No air flow: Check belt and motor Discrete Input 9 Dirty filter: Check filters Discrete Input 10 Humidifier problem: Check water pressure Discrete Input 11 Low voltage warning: Check unit Discrete Input 12 Fire stat alarm: Unit shutdown Discrete Input 13 Compressor short cycle warning Discrete Input 14 Power problem or unit restart Discrete Input 15 Humidity sensor problem Discrete Input 16 Temperature sensor problem Discrete Input 17 Scheduled maintenance due Discrete Input 18 High pressure/internal overload: Comp 1 Discrete Input 19 Low pressure C1: Automatic reset Discrete Input 20 High pressure/internal overload: Comp 2 Discrete Input 21 Low pressure C2: Automatic reset Discrete Input 22 Smoke detector: Unit shutdown Discrete Input 23 No water flow: Check pump Discrete Input 24 Discharge temperature sensor problem Discrete Input 25 High temperature warning Discrete Input 26 Low temperature warning Discrete Input 27 High humidity warning Discrete Input 28 Low humidity warning Discrete Input 29 Fan motor overload: Check motor amperage Discrete Input 30 Local alarm #1: See tag inside door Discrete Input 31 Local alarm #2: See tag inside door Discrete Input 32 Local alarm #3: See tag inside door Discrete Input 33 Local alarm #4: See tag inside door Discrete Input 34 Standby pump on: Check primary pump Discrete Input 35 UPS power on: Check main power supply Discrete Input 36 Custom alarm #1 Discrete Input 37 Custom alarm #2 Discrete Input 38 Custom alarm #3 Discrete Input 39 Custom alarm #4 Discrete Input 40 Humidification inhibited Discrete Input 41 Reheat inhibited Discrete Input 42 Reheat and humidification inhibited Discrete Input 43 Low discharge air temperature alarm Discrete Input 44 Manual override: Check bypass switches Discrete Input 45 High condensate water level Discrete Input 46 Unit in standby, all functions held off 5
6 2.3 Control Coil 0 Inhibit Cooling Coil 1 Inhibit Heating Coil 2 Inhibit Humidification Coil 3 Inhibit Dehumidification Coil 4 Inhibit Fan Holding Register 19 Unit Standby Mode (0-2) [0=on] [1=off] [2=standby] 6
7 2.4 Read/Write Configuration Holding Register 0 Time of day: Second (0-59) Holding Register 1 Time of day: Minute (0-59) Holding Register 2 Time of day: Hour (0-23) Holding Register 3 Time of day: Day (0-31) Holding Register 4 Time of day: Month (1-12) Holding Register 5 Time of day: Year Holding Register 6 Time of day: Day of week (0-6) [0 = Sunday] [1 = Monday] [2 = Tuesday] [3 = Wednesday] [4 = Thursday] [5 = Friday] [6 = Saturday] Holding Register 8 Fire Limit Temperature ( ) (F) Holding Register 9 High Humidity Limit (10-90) (%) Holding Register 10 High Temperature Limit (50-90) (F) Holding Register 11 Humidity Deadband (0-15) (%) Holding Register 12 Low Discharge Temperature Limit (45-61) (F) Holding Register 13 Low Humidity Limit (10-90) (%) Holding Register 14 Low Temperature Limit (50-90) (F) Holding Register 15 Humidity Setpoint (30-70) (%) Holding Register 16 Start Delay (5-600 seconds) Holding Register 17 Temperature Deadband (1-5) (F) Holding Register 18 Temperature Setpoint (60-80) (F) 7
Data Aire DAP TM III. LonWorks Protocol Integration Information
Data Aire DAP TM III LonWorks Protocol Integration Information Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-685 June 2009 Revision 1.0 Document 600-000-685
More informationData Aire DAP TM III. Metasys Control Points
Data Aire DAP TM III Metasys Control Points Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-703 September 2009 Rev. 5.0 Document 600-000-703 Page 1 of 7 Table
More informationData Aire DAP TM III. LonWorks Protocol Integration Information
Data Aire DAP TM III LonWorks Protocol Integration Information Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-685 Feb 2011 Revision 2.0 Table of Contents 1 Introduction...
More informationDAP III Zone Master User s Guide
DAP III Zone Master User s Guide Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-788 March 2010 Revision 1.0 Document # 600-000-788 1 Overview The Data Aire DAP
More informationModbus RTU RS485 Manual
Modbus RTU RS485 Manual AUTOMATED FUEL MAINTENANCE SYSTEMS FTI-5A, FTI-10A, FTI-20A FUEL TECHNOLOGIES INTERNATIONAL 06/10/2014 Rev B - Fuel Technologies - Modbus The Modbus Communications Setup Button
More informationModbus TCP Register List GreenManager for GreenMaster C-F Valid for firmware version 2.0 or later
Modbus TCP Register List GreenManager for GreenMaster C-F Valid for firmware version 2.0 or later Overview Modbus can access single adresses or multiple addresses simultaneously; either reading or writing
More informationModular Data Temp Systems Air Cooled Water/Glycol Cooled 8, 10 and 13 ton capacities R-410A. ISO 9001 Certified
Modular Data Temp Systems Air Cooled Water/Glycol Cooled 8, 10 and 13 ton capacities ISO 9001 Certified the pioneer and builder of the most complete line of precision cooling equipment Back in the late
More informationUser Guide. Color Touchscreen Programmable Residential Thermostat. ComfortSense Model: 13H /2015 Supersedes 7/2015
User Guide Color Touchscreen Programmable Residential Thermostat ComfortSense 7500 Model: 13H14 507503-01 10/2015 Supersedes 7/2015 TABLE OF CONTENTS Features... 2 Temperature Dial Indicator... 3 Home
More informationAPOGEE Open Processor with Airflow Dataguard Driver: CCT DX Unit
Point Map Rev. 2, July, 2002 Systems Integration APOGEE Open Processor with Airflow Dataguard Driver: CCT DX Unit Table 1. CCT DX Unit, Analog Points. 01 LAI Return Air Temperature F 02 LAI Supply Air
More informationATC32U03 igate Communicating, Programmable Thermostat
ATC32U03 igate Communicating, Programmable Thermostat User Manual 97B0055N02 Rev.: 11/3/17 Table of Contents Section Title Page Menu Navigation Shortcuts 3 1.0 Operating Mode Selection 3 2.0 Temperature
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References
More informationChilled Water 7 to 211 kw
Chilled Water 7 to 211 kw Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling system was developed by data processing facility
More informationData Aire LCS TM (Large Ceiling System) R-410A. 6, 8, 10, and 13 ton. ISO 9001 Certified
Data Aire LCS TM (Large Ceiling System) 6, 8, 10, and 13 ton ISO 9001 Certified LCS TM (LARGE CEILING SYSTEMS) DX Product Description Performance and Electrical Data 3 the pioneer and builder of the most
More informationLennox Climatic 50 and BMS Modbus, Trend or BACnet.
Lennox Climatic 50 and BMS Modbus, Trend or BACnet. Specification of the Bus: Type: RS485 Speed: (Adjustable on Climatic 50 via display ; Setting 3933) 1200 2400 4800 9600 19200 Parity: Fixed no parity
More informationComfortSense 7500 Thermostat. User Guide
ComfortSense 7500 Thermostat User Guide 507503-02 6/2018 Supersedes 5/2017 Table of Contents Features...2 Home Screen Temperature Indicator...3 Home Screen Information...3 Operating Mode Selection...6
More informationData Aire Series Chilled Water 7 through 50 ton
Data Aire Series Chilled Water 7 through 50 ton ISO 9001 Certified Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling system
More informationATC32U01 igate Communicating, Programmable Thermostat
ATC32U01 igate Communicating, Programmable Thermostat User Manual 97B0055N02 Rev.: 7/2/12 Table of Contents Section Title Page Menu Navigation Shortcuts 3 1.0 Operating Mode Selection 3 2.0 Temperature
More informationModular Data Temp Systems Air Cooled Water/Glycol Cooled R-407C. 8, 10 and 13 ton capacities. ISO 9001 Certified
Modular Data Temp Systems Air Cooled Water/Glycol Cooled 8, 10 and 13 ton capacities R-407C ISO 9001 Certified the pioneer and builder of the most complete line of precision cooling equipment Back in
More informationA-Tech-20 Advanced Microprocessor Controller
A-Tech-20 Controller Operation Manual (04/02/01) 1 C Y B E R A i R Product Division A-Tech-20 Advanced Microprocessor Controller Operations Manual Project: SATS Model: SATS SN: SATS JN: Unit Tags: REVISION
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section
More informationgforce GT R-407C Single Circuit Air Cooled, Water/Glycol Cooled 7-46 kw
gforce GT Single Circuit Air Cooled, Water/Glycol Cooled 7-46 kw 1 2 the pioneer and builder of the most complete line of precision cooling equipment Back in the late 1960 s and early 70 s with the advancement
More informationData Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits
Data Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits 1 Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision
More informationData Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits R-407C
Data Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits R-407C 1 Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision
More informationgforce - R-407C Air Cooled, Water/Glycol Cooled kw Dual Circuits
gforce - R-407C Air Cooled, Water/Glycol Cooled 21-106 kw Dual Circuits 1 2 Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling
More informationComfortSense 7500 Commercial Thermostat. User Guide
ComfortSense 7500 Commercial Thermostat User Guide 507505-02 6/2018 Supersedes 5/2017 Table of Contents Features...2 Home Screen Temperature Indicator...2 Home Screen Information...3 Operating Mode Selection...5
More informationData Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified
Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A ISO 9001 Certified Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first
More informationSeries 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.
MISSION CRITICAL Air Conditioning Systems Series 9 Commissioning Checklist S9-CL2017.doc ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 S9-CL2017.doc Commissioning
More informationR-410A Air, Water/Glycol Cooled 21 through 106 kw - Dual Circuits
R-410A Air, Water/Glycol Cooled 21 through 106 kw - Dual Circuits 1 Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling system
More informationShelf Units R-407C. 2, 3, and 4 ton. ISO 9001 Certified
Shelf Units 2, 3, and 4 ton R-407C ISO 9001 Certified the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling system was developed by data processing
More informationAPC APPLICATION NOTE #119
#119 InRow RP-CW and InRow RP-DX Environmental Control By Henry Jespersen Abstract The primary function of the InRow RP product is to cool air from the hot aisle and deliver it to the cold aisle at the
More informationAPOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller
Point Map Rev. 3, February, 2002 Systems Integration APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller Table 1. Series 200 Centrifugal Chiller. Point Type Range/Units 01
More informationReference Guide for Microprocessor Controller
Document 483232 Microprocessor Controller for Energy Recovery Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting
More informationModbus TCP/IP Version 4.0 and Modbus RTU Gateway Version 2.4
Modbus TCP/IP Version 4.0 and Modbus RTU Gateway Version 2.4 Overview ModBus can access single addresses or multiple addresses simultaneously; either reading or writing single bit values or 16-bit values.
More informationData Aire LCS TM (Large Ceiling System) R-407C. 6, 8, 10, and 13 ton. ISO 9001 Certified
Data Aire LCS TM (Large Ceiling System) 6, 8, 10, and 13 ton ISO 9001 Certified LCS TM (LARGE CEILING SYSTEMS) with refrigerant Product Description Performance and Electrical Data Dimensional Data Guide
More informationChilled Water 7 to 211 kw
Chilled Water 7 to 211 kw Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling system was developed by data processing facility
More informationTAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products
Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate
More information7.1 Data Guard 5.0 variable list
INTERNAL ONLY Issue: DG5 Modbus Register Map Product line: Airflow with DG5 Board Environment: Airflow with DG5 Board Cause: Resolution: 7.1 Data Guard 5.0 variable list BACNET MODBU S Airflow DG5 Binary
More informationT7351 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS
T7351 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS 63-2652 FEATURES Typically used in buildings (including: restaurants, shopping malls, office buildings and banks) under 55,000 square feet.
More informationSystemair UAB Linų st. 101, LT Ukmergė, LITHUANIA Phone: Fax:
SAVECair variable list (9) Information MODBUS is a serial communication protocol used for transmitting information over serial lines between electronic devices. The device requesting the information is
More informationBLAUAIR AUTOMATIC CONTROL SYSTEM
BLAUAIR AUTOMATIC CONTROL SYSTEM S30 (KVENT, TH-TUNE) S31 (KVENT) S32 (KVENT, PGDE) EN USER S MANUAL CONTENTS Safety requirements... 3 Purpose... 4 Technical data... 5 Installation and set-up... 6 Control...
More informationReference Guide for Microprocessor Controller
Document 482641 Microprocessor Controller for Make-Up Air Products Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting
More informationVisionPRO 8000 with Wi-Fi
VisionPRO 8000 with Wi-Fi FEATURES PRODUCT DATA Thermostat acquires weather data through either a wired sensor or an Internet connection, making for a truly universal installation. U1 Terminals One set
More informationTOUCHSCREEN. COMFORTSENSE Day Programmable Thermostat. 4 Heat / 2 Cool Universal Multi Stage MODEL NUMBER IDENTIFICATION L U FEATURES
P R O D U C T S P E C I F I C AT I O N S C O N T R O L S TOUCHSCREEN COMFORTSENSE 7000 7-Day Programmable Thermostat Bulletin No. 210515 June 2009 Supersedes February 2008 HOME SCHEDULE OPTIONS SET AT
More informationNetworkAIR AFX. Operation and Maintenance AFX65 AFX18
NetworkAIR AFX Operation and Maintenance AFX65 AFX18 Contents Operation... 1 Display Interface.......................................... 1 Using the Display......................................... 3
More informationCOMcheck Software Version Mechanical Compliance Certificate
COMcheck Software Version 4.0.8.1 Mechanical Compliance Certificate Project Information Energy Code: Location: Climate Zone: Project Type: 90.1 (2013) Standard Buda, Texas 2a New Construction Construction
More informationInstallation Instructions / User s Manual TSTAT0406 and TSTAT0408
997-060180-5 Installation Instructions / User s Manual TSTAT0406 and TSTAT0408 4 HEAT 2 COOL DUAL FUEL TSTAT0406 & TSTAT0408-4 WIRE CAPABLE THERMOSTAT (NAXA00201DB Daughter Board sold separately) LEFT
More informationOPERATING MANUAL. This manual covers TopTech models: TT-S-755H
OPERATING MANUAL This manual covers TopTech models: TT-S-H Congratulations on purchasing a new thermostat. This thermostat was designed to the highest reliability and ease of use standards. Thank you for
More informationOPERATING MANUAL. Need Help? This manual covers the following models: T805. Table of Contents
OPERATING MANUAL This manual covers the following models: T80 Congratulations on purchasing a new thermostat. This thermostat was designed to the highest reliability and ease of use standards. Thank you
More informationBACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller
BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller All volatile (Output) type points will revert to the uncommanded values after a power interruption.
More informationContents. APC NetworkAIR CW. CW 020 C= Chilled Water BA= /3/60 D= Downflow. Capacity (kw) Configuration Voltage Air Pattern
Contents Overview.............................................................. 1 Standard Features....................................................... 2 Optional Features.......................................................
More informationMarvel S MICROPROCESSOR CONTROLLER. Installation, Operation and Maintenance Manual Effective October 2018 DISCONTINUED. For Reference Only
Marvel S MICROPROCESSOR CONTROLLER Installation, Operation and Maintenance Manual Effective October 2018 DISCONTINUED For Reference Only ***Interactive PDF*** Contents General Purpose...3 Standard And
More informationEvolution Control. Zone Control Homeowner s Guide
Evolution Control Zone Control Homeowner s Guide CONGRATULATIONS! Your decision to choose the Bryant Evolution Control puts you in a select group of homeowners who understand the value of precise comfort
More informationOPERATING MANUAL. Need Help? This manual covers: T955WH Wireless Thermostat System. Table of Contents
OPERATING MANUAL This manual covers: T955WH Wireless Thermostat System Your wireless thermostat system includes a master thermostat (T955WH) and base module. The T955WH thermostat communicates wirelessly
More informationDX-9100 Applications from Engineering Services
System 9100 Technical Manual 636.4 Application Examples Section Technical Bulletin Issue Date 0896 DX-9100 Applications from Engineering Services Introduction Page 3 Overview 3 Air Handling Unit Applications
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section
More informationLV CONTROLLER
SERVICE INSTRUCTIONS WITH REPLACEMENT PARTS LIST LV1000-200 CONTROLLER NOTE: LV1000 controller is required for operation when FUSION-TEC HR**BP wall-mount units are used. Bard Manufacturing Company, Inc.
More informationSeries 8. Guide Specification 60 Hz. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.
MISSION CRITICAL Air Conditioning Systems Series 8 Guide Specification 60 Hz S8-GS-602017.doc 2014 ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 Series 8 Guide Specification-60
More informationHEAT COOL. Meets Commercial California Title 24
Digital Thermostat commercial THERMOSTAT T2900 7-DAY MABLE up to 3-heat & 2-cool HEAT COOL HEAT PUMP Control up to 3 Heat & 2 Cool Stages 3 Configurable Outputs Adjustable 2nd & 3rd Stage Timers & Deadbands
More informationInfinity Control. Homeowner s Guide. The New Feeling of Comfort
TM Infinity Control Homeowner s Guide The New Feeling of Comfort CONGRATULATIONS! Your decision to choose the Carrier Infinity Control puts you in a select group of homeowners who understand the value
More informationSYSTEM 2500 PROGRAMMABLE CONTROLLER -USER MANUAL-
SYSTEM 2500 PROGRAMMABLE CONTROLLER -USER MANUAL- 8167 Byron Road Whittier, CA 90606 Phone: (562) 945-8971 Fax: (562) 696-0724 SUBJECT TO CHANGE WITHOUT INCURRING OBLIGATION Rev.01 03-27-17 Page 1 of 71
More informationMicroTech Series-200 Flooded Screw Chiller
Open Protocol Data Infomation Packet Version 1.0 Group: Controls Date: February 1997 MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Communications 2002 McQuay International - C O N F I D
More informationOPERATING MANUAL. This manual covers TopTech models: TT-S-855 and T855
OPERATING MANUAL This manual covers TopTech models: TT-S-8 and T8 Congratulations on purchasing a new thermostat. This thermostat was designed to the highest reliability and ease of use standards. Thank
More informationUser s Manual
997-060180-4e User s Manual 8403-060 Menu Driven Display 1120-445 I. CONTROLLER OPERATION ADJUSTING TEMPERATURE (Temporary Override when in Programmable mode) 1. Before you can adjust the temperature,
More informationFieldServer Driver - Serial FS McQuay Microtech Open Protocol
Description FieldServer Driver - Serial FS-8700-80 McQuay Microtech Open Protocol This is an active client protocol. The driver is capable of acting as a master or slave. As a master, the Fieldserver polls
More informationASD Installation On A P&H 4100 Electric Rope Shovel
ASD Installation On A P&H 4100 Electric Rope Shovel 1 Installation Driver 2 An international mining company conducted a company wide review of the fire protection systems on their Ultra- Class mobile mining
More informationI/O ZONE 560/583 USERS GUIDE
I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6
More informationT855S. Caution. Page. Table of Contents Table of Contents Thermostat Operation Thermostat Quick Reference Programming Features Warranty Information
Operation Manual Operation Manual Pro1 Technologies 1111 S. Glenstone Ave., Suite 2-100 Springfield, MO 65804 Toll Free: 888-776-1427 Web: www.pro1iaq.com Hours of Operation: M-F 9AM - 6PM Eastern T855S
More informationStrategies for Building Energy Efficiency
Strategies for Building Energy Efficiency Ben Sliwinski Technical Director SEDAC University of Illinois at Urbana-Champaign How Buildings Use Energy Building Envelope (Walls, Roof, Windows, Floors) Lighting
More informationYEAR-ROUND COMFORT EVOLUTION CONTROL ZONE CONTROL HOMEOWNER S GUIDE. The Ultimate Home Comfort System.
YEAR-ROUND COMFORT EVOLUTION CONTROL ZONE CONTROL HOMEOWNER S GUIDE The Ultimate Home Comfort System. CONGRATULATIONS! Your decision to choose the Bryant Evolution Control puts you in a select group of
More informationUSER CODES. User Codes (1-6 digits) Access Levels + Access Levels. Time Control Address Address Address Address User 1 (Master)
User Codes (1-6 digits) Access Levels Access Levels + Time Control User 1 (Master) 1 1 2 3 25 49 73 0 User 2 2 26 50 74 0 User 3 3 27 51 75 0 User 4 4 28 52 76 0 User 5 5 29 53 77 0 User 6 6 30 54 78 0
More informationEdge Data Center - DSE CRAC Settings w/monochrome Display v6.4 Revision Date 12/12/2016
Edge Data Center - DSE CRAC Settings w/monochrome Display v6.4 Revision Date 12/12/2016 Parameter (Line User Display Set-up (Page 1) U409 Display Shows Data Of Unit Set to the U2U Address on each Unit
More informationReference Guide for Microprocessor Controller
Document 483586 Microprocessor Controller for Dedicated Outdoor Air System Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before
More informationT7350 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS
Contents T7350 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS OWNER S GUIDE Features... 2 Settings... 3 Programming... 5 63-2638 FEATURES Typically used in buildings (including: restaurants,
More informationRTU. Roof Top Units 8 30 Ton. Maxi-Kool.
Maxi-Kool RTU Roof Top Units 8 30 Ton www.compu-aire.com MK A-3 034 -RTU Maxi-Kool Type Air Cooled - A Chilled Water Cooled - C Glycol Cooled - G Water Cooled - W Nominal Tonnage 8 30 Ton Voltage 2-208
More informationMicroTech Self-Contained Air Conditioning System
Open Protocol Data Information Packet Version 2.3 Group: Controls Date: October 1999 MicroTech Self-Contained Air Conditioning System Open Protocol Data Communications t 2002 McQuay International - C O
More informationOWNER S MANUAL Venstar Inc. 08/07
Digital Thermostat commercial SCHOOL THERMOSTAT T2900SCH MABLE up to 3-heat & 2-cool HEAT COOL HEAT PUMP Energy Saving Operation Morning Warm-up Period Programmable Override Unoccupied until button press
More informationEMERSON BLUE Wireless Comfor t Inter face 1F98EZ-1621 HOMEOWNER USER GUIDE
EMERSON BLUE Wireless Comfor t Inter face 1F98EZ-1621 HOMEOWNER USER GUIDE Emerson Blue Wireless Comfort Interface - Homeowner User Guide Message to Homeowners Congratulations on choosing the Emerson Blue
More informationHVAC Mandatory Provisions Part II, Page 1
HVAC Mandatory Provisions Part II, Page 1 Mandatory Equipment Efficiency Worksheet (6.4.1.1) System Equipment Type Size Category (Tables 6.8.1A through K) Sub-Category or Rating Condition Units of Efficiency
More informationComputer Room Air-Conditioning 60 Hz. Technical Data
TM Computer Room Air-Conditioning 60 Hz 10 kw (3 tons) Technical Data Contents Overview.............................................................. 1 Standard Features.......................................................
More informationTRX MAINS CONNECTION DIAGRAM
TRX MAINS CONNECTION DIAGRAM Switch 230VAC 10A Neutral Out Phase Out TRX MAINS Phase In Neutral In LOAD 8A MAX. Specifications: Operating Voltage: 220-240VAC 50Hz Current Draw: 5mA Max. Switching Current:
More informationFor Raychem ACS-30 Controls Systems
ACS-30 Protocol Interface Mapping For Raychem ACS-30 Controls Systems Firmware Version 5.05 THERMAL BUILDING SOLUTIONS EN-RaychemACS30-AR-H58324 03/16 Table of Content Section 1. Introduction... 3 1.1
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS Modbus Supplemental Manual for LC6000 Controller The LC6000 is capable of being remotely monitored through the integrated Ethernet port. Through this port the controller will
More information81M26 81M27 81M28. User's Manual. Menu Driven Display DELUXE PROGRAMMABLE THERMOSTATS
110-1052F 5/12/05 11:59 AM Page 1 81M26 81M27 81M28 DELUXE PROGRAMMABLE THERMOSTATS with Humidity Control User's Manual Menu Driven Display Fully Programmable 24 VAC with Worry-Free Memory Storage 1 Heat
More informationOPERATION AND MAINTENANCE MANUAL
OPERATION AND MAINTENANCE MANUAL Prg Sel line alarm on on/off alarm enter Clear EMIpro MICROPROCESSOR CONTENTS 1 GENERAL CHARACTERISTICS Page 2 1.1 General description Page 2 2 EMIPRO USER INTERFACE Page
More informationPOLICY. Carbon Monoxide (CO) is an odorless, colorless gas that can cause sudden illness and death. 1
POLICY Number: 7311-20-020 Title: Carbon Monoxide Monitoring and Reporting Overnight Stay Facilities Authorization [ ] President and CEO [X] Vice President, Finance and Corporate Services Source: Director,
More informationD A R A - 4. Data Aire Relay Auto-Changeover
D A R A - 4 Data Aire Relay Auto-Changeover WARNING: If adding the DARA-4 panel to existing units that did not include a DARA-4 panel when originally purchased it will be necessary to add a relay or relays.
More information*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide
Aurora Touch UPC Kit Instruction Guide For use in single compressor water-to-air equipment utilizing fi rmware UPCSWASTD01-01 Aurora Touch UPC Kit Instruction Guide *IG1583EW* IG1583EW 08/14 Aurora Touch
More informationLiebert DataMate (1-3 Ton) Warranty Inspection Check Sheet
The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Installation
More informationHomeowner s Guide / 1
Overview Options Programming Your Homeowner s / 1 Message to the Homeowners Your premium Comfort Control 2 HD Communicating is designed to give you and your family the indoor comfort you desire. It s easy
More informationDigital Precise Air Control - DPAC
Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options
More informationParts Diagram. Up button. Down button. Right (fan) button. Left (system) button. RC/RH Jumper. Field programming pins
Table of Contents Parts Diagram........................................................... 1 Icon Descriptions......................................................... 2 Specifications...........................................................
More informationSeries 6. Guide Specification 60 Hz. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.
MISSION CRITICAL Air Conditioning Systems Series 6 Guide Specification 60 Hz S6-GS-602017.doc ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 Series 6 Guide Specification-60
More informationT-Series Air Conditioner T15 Model
INSTRUCTION MANUAL T-Series Air Conditioner T15 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200
More informationMechanical Compliance Certificate
COMcheck Software Version 4.0.7.0 Mechanical Compliance Certificate Project Information Energy Code: Location: Climate Zone: Project Type: 90.1 (2013) Standard Austin, Texas 2a (weather data: TBD) New
More informationManual for the integration in BMS/GTC
Manual for the integration in BMS/GTC Communication parameters MODBUS RTU and BACNET COMMUNICATION UTBS PRO-REG Software Version 3.6 EN ÍNDEX 1. GENERALITIES...2 1.1. Introduction...2 1.2. signals types...2
More informationCM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B
2 CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B CAUTION CAUTION - ONLY TRAINED, QUALIFIED PERSONNEL SHOULD INSTALL AND/OR SERVICE CLIMATEMASTER EQUIPMENT. SERIOUS
More informationOwner s Manual. Digital. Heat Pump. 5+2 Day Programmable. Model S1-THEH21P5S HVAC SERVICE PARTS TM
Owner s Manual Model S1-THEH21P5S HVAC SERVICE PARTS TM Heat Pump 5+2 Programmable Digital T h e rm ostats t a t BACKLIT DISPLAY Use with most Heat Pump systems: 1-Heat, 1-Cool 2-Heat, 1-Cool Control up
More informationH3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog
H3/V3 Series Horizontal and Vertical Indoor Air Handling Units Engineering Catalog Table of Contents AAON H3/V3 Series Features and Options Introduction... 6 H3/V3 Base Model Description... 7 Unit Size...
More informationECL Comfort 210 / 296 / 310
User Guide ECL Comfort 210 / 296 / 310 English version www.danfoss.com Safety Note Necessary assembly, start-up, and maintenance work must be performed by qualified and authorized personnel only. 2 Danfoss
More informationL SERIES UNITS 504,520M. 10/2001 Supersedes 504,413M
Litho U.S.A. 2 L SERIES UNITS 54,52M /2 Supersedes 54,4M M 6 VERSION 4. INTEGRATED MODULAR CONTROL (IMC) GUIDE TO THE M 6 VERSION 4. INTEGRATED MODULAR CONTROL USED IN L SERIES THROUGH TON UNITS TABLE
More information