PoolPak SWHP with CommandPak Control System CPCS BACnet IP User s Guide DOCUMENT #: SVW05-BACNETIP

Size: px
Start display at page:

Download "PoolPak SWHP with CommandPak Control System CPCS BACnet IP User s Guide DOCUMENT #: SVW05-BACNETIP"

Transcription

1 PoolPak SWHP with CommandPak Control System CPCS BACnet IP User s Guide DOCUMENT #: SVW05-BACNETIP UPDATED: MAY 2018

2 INTRODUCTION PoolPak dehumidifiers equipped with the CommandPak Control System (CPCS) can be directly connected to a BACnet/IP based Building Automation System (BAS). Based on Carel s pcoweb serial card, the interface allows connection to an Ethernet network. 80 control points, including all basic information and set points for the PoolPak dehumidification system, are available through the interface. BACnet Configuration Parameters The BACnet configuration parameters for the controller are accessed in the configuration menu. To access this menu: 1. Press the I button on the RIU (Esc on the CM1 module). 2. Enter the password Use the arrow keys to scroll down to the following parameters 062. BAUDRATE Sets the baud rate for the onboard serial port. It must be set to for use with the BACnet interface is the factory default setting for this parameter. BAS Addr Sets the address of the BACnet interface card in the serial slot of the controller. It must be set to 1 for proper operation of the BACnet interface. The factory default setting is 1. LonWorks Inst Sets the type of BAS interface board installed in the control module, CM1. It must be set to NO for use with a BACnet interface. Ser Port Proto Sets the protocol the control module will use with the installed BAS board. It must be set to RS485 for use with a BACnet interface. 4. After changing any of the above parameters, reboot the controller by cycling power with the unit control power switch. This switch is located within or adjacent to the main control panel of the dehumidifier. PHYSICAL NETWORK CONNECTION The 8P8C ( RJ-45 ) Ethernet socket is located on the pcoweb interface card. The pcoweb card occupies the BMS card slot directly below the keypad built into the CM1 control module. This control module is located in the main control panel of the PoolPak dehumidifier. The Ethernet connection to the interface card should comply with standard installation practices. Use care to route the cable away from sources of interference and keep the maximum cable length less than 300 feet. CONTROL POINTS MAPPING 80 objects are accessible through the BACnet interface. Set points, sensor values, and enumerated variables are shared as analog-value objects. Status information points are shared as binary-value objects. The interface card is pre-configured at the factory with a device instance number of To change this value, follow the instructions shown in the Interface Card Field Setup and Configuration section of this document PoolPak LLC. All rights reserved. Page 2

3 The following table lists the available points along with their object types and instance numbers OBJECT TYPE OBJECT INSTANCE OBJECT NAME DESCRIPTION UNITS AV 1 SplyFanCurr Supply Fan Current Amperes AV 2 RtnFanCurr Return Fan Current Amperes AV 3 Cmpr1Curr Compressor System1 Current Amperes AV 4 RtnAirTemp Return Air Temperature ºC AV 5 OutsAirTemp Outside Air Temperature ºC AV 6 ExhDprFdBk Actual Exhaust Damper Position (%) % Open AV 7 RecircDprFdBk Actual Recirc Damper Position (%) % Open AV 8 OutsDprFdBk Actual Outside Air Damper Position (%) % Open AV 9 AirOffEvapTemp Air Leaving Evaporator Temperature ºC AV 10 SurfTemp Cold Surface Temperature ºC AV 11 RtnAirRH Return Air Relative Humidity % AV 12 OutsAirRH Outside Air Relative Humidity % AV 13 AirOffEvapRH Air Leaving Evap Relative Humidity % AV 14 Cmpr2Curr Compressor System 2 Current Amperes AV 15 PoolTemp1 Pool Temperature 1 ºC AV 16 PoolTemp2 Pool Temperature 2 ºC AV 17 SplyAirTemp Supply Air Temperature ºC AV 18 RtnAirCO2Lvl Return Air CO2 Level PPM AV 19 FuzzyDprChg Fuzzy Logic Damper Control Variable N/A AV 20 FuzzyRatCmprChg2 Fuzzy Logic Space Temp Ctl Variable N/A AV 21 FuzzyDptCmprChg Fuzzy Logic Space Dewpt Ctl Variable N/A AV 22 ReqOutsDprPos Requested Outside Air Damper Position % Open AV 23 RtnAirTemp_F Return Air Temperature in Fahrenheit ºF AV 24 OutsAirTemp_F Outside Air Temperature in Fahrenheit ºF AV 25 AirOffEvapTemp_F Air Off Evap Temperature in Fahrenheit ºF AV 26 SurfTemp_F Cold Surface Temperature in Fahrenheit ºF AV 27 PoolTemp1_F Pool Temperature 1 in Fahrenheit ºF AV 28 PoolTemp2_F Pool Temperature 2 in Fahrenheit ºF AV 29 SplyAirTemp_F Supply Air Temperature in Fahrenheit ºF AV 60 Cmpr1SucPrs Compressor 1 Suction Pressure PSI AV 61 Cmpr1DisPrs Compressor 1 Discharge Pressure PSI AV 62 Cmpr1SucTmp Compressor 1 Suction Temperature ºF 2018 PoolPak LLC. All rights reserved. Page 3

4 AV 63 Cmpr1LiqTmp Compressor 1 Liquid Temperature ºF AV 64 Cmpr2SucPrs Compressor 2 Suction Pressure PSI AV 65 Cmpr2DisPrs Compressor 2 Discharge Pressure PSI AV 66 Cmpr2SuctTemp Compressor 2 Suction Temperature ºF AV 67 Cmpr2LiqTemp Compressor 2 Liquid Temperature ºF AV 68 Cmpr1SucSH Compressor 1 Suction Superheat ºF AV 69 Cmpr2SucSH Compressor 2 Suction Superheat ºF AV 70 Cmpr1LiqSC Compressor 1 Liquid Sub-cooling ºF AV 71 Cmpr2LiqSC Compressor 2 Liquid Sub-cooling ºF OBJECT TYPE OBJECT INSTANCE OBJECT NAME DESCRIPTION UNITS AV 1001 Cmpr1ActvFlt Cmpr System 1 Active Fault Code See Below AV 1002 Cmpr2ActvFlt Cmpr System 2 Active Fault Code See Below AV 1003 CmprStgsDesired Compressor Stages Desired Stages AV 1004 CmprStgsHtCool Cmpr Stages of Heating / Cooling Stages AV 1005 CmprstgsDpt Compressor Stages of Dehumidification Stages AV 1006 Spc1DprLim Damper Position Limit Code See Below AV 1007 Cmpr1FaultCount Cmpr System 1 Faults Since Powerup Faults AV 1008 Cmpr2FaultCount Cmpr System 2 Faults Since Powerup Faults AV 1009 RtnTempSetp_R Return Air Temp Set Point (Readable) ºF AV 1010 PoolTempSetp_R Pool 1 Temp Set Point (Readable) ºF AV 1011 PoolTemp2Setp_R Pool 2 Temp Set Point (Readable) ºF AV 1012 RtnRHSetp_R Return Air RH Set Point (Readable) % AV 1013 DprMinLimSetp_R Min Damper Limit Set Point (Readable) % Open AV 1014 DprMaxLimSetp_R Max Damper Limit Set Point (Readable) % Open AV 1015 RtnTempSetp_W Return Air Temp Set Point (Writable) ºF AV 1016 PoolTempSetp_W Pool 1 Temp Set Point ºF (Writable) ºF AV 1017 PoolTemp2Setp_W Pool 2 Temp Set Point ºF (Writable) ºF AV 1018 RtnRHSetp_W Return Air RH Set Point (Writable) % AV 1019 DprMinLimSetp_W Min Damper Limit Set Point (Writable) % Open AV 1020 DprMaxLimSetp_W Max Damper Limit Set Point (Writable) % Open AV 1021 AuxAirHtStgs Aux Air Heat Stages Active Stages AV 1022 Cmpr1Mode Compressor System 1 Mode See Below AV 1023 Cmpr2Mode Compressor System 2 Mode See Below 2018 PoolPak LLC. All rights reserved. Page 4

5 BV 1 WtrFlow1OK Cmpr System 1 Flow Switch Status On / Off BV 2 WtrFlow2OK Cmpr System 2 Flow Switch Status On / Off BV 3 OccMode Occupied Status On / Off BV 4 PurgeModeActv Purge Mode Status On / Off BV 5 Cmpr1ACCAllow Cmpr System 1 ACC Proof Status On / Off BV 6 Cmpr2ACCAllow Cmpr System 2 ACC Proof Status On / Off BV 7 AuxWtrHt1 Aux Pool Water Heater Status On / Off BV 8 AuxWtrHt2 Aux Pool Water Heater 2 Status On / Off BV 9 ForceOcc Force Occupied Mode (Writable) On / Off BV 10 ForceUnocc Force Unoccupied Mode (Writable) On / Off BV 11 ForcePurge Force Purge Mode (Writable) On / Off BV 12 ForceNoPurge Force Non-Purge Mode (Writable) On / Off BV 13 ActvAlmPres Active Alarm Present On / Off BV 14 NetMaster Indicates unit is master in multi-unit installation On / Off BV 15 ForceEvent Force System to Event Mode (Writable) On / Off BV 16 ForceNoEvent Force System to Non-Event Mode (Writable) On / Off COMPRESSOR ACTIVE FAULT CODE AV1001 and AV1002 are enumerated values indicating the most significant active fault in each compressor system of the dehumidifier. The present value for these objects can be decoded as follows: 0 Normal Operation - No Active Fault 1 Compressor System in OFF Mode 2 System Startup Active 3 Return Fan Not Running 4 Supply Fan Not Running 5 Fire Trip Active 6 Smoke Purge Active 7 Return Air Temp Out of Range (60 F < Normal < 105 F) 8 Both Fans Not Running 9 Freeze Alarm 11 Low Oil Pressure 13 Low Refrigerant Pressure 14 High Compressor Motor Temperature 15 High Refrigerant Pressure 16 Cmpr Current Transducer Failure 17 Crankcase Heater Breaker Off 50 Compressor Locked Out After 10 Faults 2018 PoolPak LLC. All rights reserved. Page 5

6 DAMPER POSITION LIMIT CODE AV1006 is an enumerated value indicating the reason for any current limitations on damper position. These limitations override the normal damper control routine under certain conditions. The present value of this object can be decoded as follows: 0 Normal Damper Limits Apply 1 Fire Trip Active All dampers closed. 2 Smoke Purge Active Exhaust damper 100% open, Outside and Recirc 0% Open 3 Unoccupied and No Dew Point Override Active Mixing Box Allowed to Close to 0% 4 Flywheel AC Mode Active Mixing Box Allowed to Open to 100% during Unoccupied 5 Outside Air Temperature Less Than 50 F Outside Air Damper Position Limited 6 Cooling Required and Compressor Running 7 Heating or Dehumidification and Compressor Running 8 Supply Temperature Less Than 40 F Mixing Box Forced to 0% Open 9 Heating and Outside Air Temperature Less Than Air Off Evaporator Temperature 10 System Startup Active Mixing Box Held at 0% Open COMPRESSOR SYSTEM MODE AV1022 and AV1023 are enumerated values indicating the operation mode of the corresponding compressor system. The present value for these objects can be decoded as follows: 0 Compressor Off 1 Air Heating Mode 3 Pool Water Heating Mode 4 Air Cooling Mode CHANGING A SET POINT Two analog value objects are allocated for each set point, a readable value and a writable value. To change a set point, set the present value of the writable object to the new set point value. Verify that the controller accepted the change by reading the value of the corresponding readable object. The controller applies limits to the set point values. If the BAS tries to set an inappropriate value, the readable object will show the min or max allowed value instead of the requested value. The BAS can detect this event by verifying the change in the readable object s present value. The following limits are applied by the controller: Return Air Temperature: 75 F 95 F Return Air Humidity: 40% - 65% Pool Water Temperature: 75 F - 95 F Damper Position: 0% - 100% Set points for temperature are represented by integer values in degrees Fahrenheit. CONTROLLING OCCUPANCY MODE The BAS can control the dehumidifier s occupancy mode directly. This control overrides all internal schedules. To force occupied mode, set the ForceOcc object value to the On state and the ForceUnocc object value to the Off state. To force unoccupied mode, set the value of the ForceOcc object to Off and the ForceUnocc object to On PoolPak LLC. All rights reserved. Page 6

7 CONTROLLING PURGE MODE The BAS can control the dehumidifier s Purge mode directly. This control overrides all internal schedules and controls except for the freeze protection algorithm. To force purge mode, set the ForcePurge object value to the On state and the ForceNoPurge object value to the Off state. To force non-purge mode, set the value of the ForcePurge object to Off and the ForceNoPurge object to On. ACTIVE ALARM FLAG CONTROL The ActvAlarmPres binary value object indicates the status of the system alarm flag. This status corresponds to the red light inside the alarm button of the control module, CM1. When the present value of this object is On, there is an uncleared alarm present in the controller. To clear the alarm flag, set the ActvAlarmPres object value to Off. If there are no active alarms present, the value of ActvAlarmPres will change to Off. If there are still active alarms present, the value of ActvAlarm will remain On. To determine the actual alarm condition, the BAS can examine the present value of the ActvFault objects. These enumerated values indicate the most significant active fault code. See the Compressor Active Fault Code section earlier in this document for a list of possible states. INTERFACE CARD FIELD SETUP AND CONFIGURATION The BACnet interface card is shipped from the factory with the following default settings: BACnet BACnet LAN Type: BACnetIP BACnet Device Instance: BACnet IP UDP: BAC0 APDU Timeout: 5000ms APDU Retries: 3 Password for Restart: 1234 TCP/IP IP Address: Obtain from DHCP Server Netmask: Obtain from DHCP Server Gateway: Obtain from DHCP Server The CM1 controller provides a the ability to change any of these settings. To make a change: 1. Connect the network cable to the network. 2. Connect the RJ-45 cable to the port on the pcoweb card located in the BMS card slot of the CM1 controller. 3. Press and hold the! (Alarm) and (Enter). Wait for the top line to display SYSTEM INFORMATION. 4. Arrow Down to put the crsor next to OTHER INFORMATION and press Enter. 5. Arrow down to place the cursor next to PCOWEB/NET CONFIG and press Enter. 6. Place the cursor next to PCOWEB settings and press Enter. 7. If the display shows DHCP: ON, press the Enter button to move the cursor under the ON and arrow Up to change it to Off. If the display shows DHCP: OFF, move to the next step below. 8. To change network settings, including the card s IP address, Netmask, Gateway, DNS1, DNS2 and BACnet ID, continue to press the Enter button to tab through all changeable fields and use the Up/Down arrows to set the desired settings PoolPak LLC. All rights reserved. Page 7

8 9. The last screen will say PCOWEB CONFIG ENABLE Update pcoweb? No. Change it to Yes then press Enter. 10. The screen should say PCOWEB CONFIG ENABLE Update complete. Reboot pcoweb to apply new setting. 11. Reboot the card by turning the Control Power Switch off. Wait about 20 seconds then turn the CPS on. 12. Wait approximately 5 minutes and then verify the new settings are saved on the card by repeating steps 2 through 7 above and viewing the setting match the changes that were made. If you experience problems during this procedure, please contact PoolPak Service at Ext. 2. TROUBLESHOOTING SYMPTOM POSSIBLE CAUSE SOLUTION The dehumidifier cannot be seen on the BACnet network. The variable values sent by the controller are different than those shown on the RIU. The interface card is not properly connected to the network. Power to the controller is off. The BAS is trying to access the interface with the wrong device instance number. Incorrect setting of the BAS configuration parameters in the service menu. Correct network wiring. If safe to do so, turn on the main disconnect and the control power switch (CPS) in the control compartment of the dehumidifier. Follow the instructions in this document to set the instance number to a value appropriate for the BAS. Correct the parameter values to match the settings shown in this document. The variable values sent by the controller are different than those shown on the RIU. Set point changes are different than requested by the BAS. The BAS Type parameter is not set to BACnet. The LonWorks Board parameter is set to Yes. Requested set point change is outside of the acceptable range. Set the BAS Type parameter to BACnet. Set the LonWorks Board parameter to No. Select set points based on the acceptable range. For questions about the interface that are not answered in this document, please contact PoolPak Service at Ext. 2. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). This trademark is used in the text, but for the sake of readability, it is not individually marked. With more than 45 years of experience in indoor pool dehumidification equipment manufacturing, PoolPak LLC is the most well-known brand in the industry. Our people and products work daily to improve the quality and comfort of indoor pool environments. PoolPak dehumidification solutions include a variety of heating, ventilation, and air conditioning systems, in addition to an industry-leading PoolPak support network. For more information, please visit Industrial Drive York, Pennsylvania USA Fax PoolPak LLC. All rights reserved. SVW05-BACNETIP

CPCS SWHP BACnet MS/TP Interface User s Guide DOCUMENT #: SVW05-BACNET-MSTP

CPCS SWHP BACnet MS/TP Interface User s Guide DOCUMENT #: SVW05-BACNET-MSTP CPCS SWHP BACnet MS/TP Interface User s Guide DOCUMENT #: SVW05-BACNET-MSTP-20170713 UPDATED: JULY 2017 INTRODUCTION PoolPak dehumidifiers equipped with the CommandPak Control System for PoolPak SWHP (CPCS-SWHP)

More information

ComPak Series with CommandPak Control System CPCS BACnet MS/TP BAS Interface User s Guide DOCUMENT #: SVW06-CPBACNETMSTP

ComPak Series with CommandPak Control System CPCS BACnet MS/TP BAS Interface User s Guide DOCUMENT #: SVW06-CPBACNETMSTP ComPak Series with CommandPak Control System CPCS BACnet MS/TP BAS Interface User s Guide DOCUMENT #: SVW06-CPBACNETMSTP-20180529 UPDATED: MAY 2018 INTRODUCTION ComPak dehumidifiers equipped with the CommandPak

More information

POOLPAK SWHP SERIES (SR, S, SE, SEP)

POOLPAK SWHP SERIES (SR, S, SE, SEP) POOLPAK SWHP SERIES (SR, S, SE, SEP) ECCIII User s Guide For ECCII to ECCIII Controller Upgrade RPW05-EC3UPGUIDE-20140818 ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 IDC1 ID9 ID10 ID11 ID12 IDC9 ID13H ID13 IDC13 ID14

More information

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY A C-TRAC3 COMMUNICATION MANUAL FOR BACnet NOVEMBER 2010 TO JANUARY 2014 UNIT MODEL NO. UNIT SERIAL NO. SERVICED BY: TEL. NO: CANADIAN HEAD OFFICE AND FACTORY 1401 HASTINGS CRES. SE CALGARY, ALBERTA T2G

More information

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate

More information

LYNX Quick User Guide

LYNX Quick User Guide LYNX Quick User Guide AIR TEMPERATURE 58.1 WATER TEMPERATURE 61.2 HUMIDITY 75.3 86.0 82.4 82 60.0 65.0 HEAT RECLAIM OFF CURRENT MODE ALARM STATUS COOLING MODE LTHW TEMPERATURE UNOCCUPIED HEALTHY OFF 158

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483586 Microprocessor Controller for Dedicated Outdoor Air System Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483232 Microprocessor Controller for Energy Recovery Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting

More information

CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B

CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B 2 CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B CAUTION CAUTION - ONLY TRAINED, QUALIFIED PERSONNEL SHOULD INSTALL AND/OR SERVICE CLIMATEMASTER EQUIPMENT. SERIOUS

More information

Installation, Operation and Maintenance

Installation, Operation and Maintenance Installation, Operation and Maintenance PoolPak SWHP FORM #: SVW05-SWHPIOM-20171107 SUPERCEDES: MK5-IOMSWHP REV UPDATED: NOVEMBER 2017 2017 PoolPak LLC. All rights reserved. TABLE OF CONTENTS IMPORTANT...

More information

PoolPak MPK Series. PoolPak.com. Environmental Control Systems REDUCED FOOTPRINT & WEIGHT COMPARED TO EARLIER GENERATIONS

PoolPak MPK Series. PoolPak.com. Environmental Control Systems REDUCED FOOTPRINT & WEIGHT COMPARED TO EARLIER GENERATIONS PoolPak MPK Series Environmental Control Systems REDUCED FOOTPRINT & WEIGHT COMPARED TO EARLIER GENERATIONS PoolPak.com The PoolPak MPK Series Built using the PoolPak Proven Approach SM, the MPK Series

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 482641 Microprocessor Controller for Make-Up Air Products Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

POOLPAK R-410A MPK SERIES

POOLPAK R-410A MPK SERIES POOLPAK R-410A MPK SERIES MS (Supply Fan and Outside Air) MSE (Supply Fan, Exhaust Fan, and Outside Air) MSEP (Supply Fan, Exhaust Fan, Purge Fan, and Outside Air) Installation, Operation, Maintenance

More information

CONTROLS MANUAL For all Innovent and Valent air handling products

CONTROLS MANUAL For all Innovent and Valent air handling products CONTROLS MANUAL For all Innovent and Valent air handling products TABLE OF CONTENTS TABLE OF CONTENTS IMPORTANT INFORMATION Safety information...................................................................................

More information

ZIP Economizer Method of Operation Sequence of Operation States Virgin State The ZIP Economizer comes shipped from the factory in this state. Setup Incomplete will be displayed. No control will occur until

More information

MicroTech Self-Contained Air Conditioning System

MicroTech Self-Contained Air Conditioning System Open Protocol Data Information Packet Version 2.3 Group: Controls Date: October 1999 MicroTech Self-Contained Air Conditioning System Open Protocol Data Communications t 2002 McQuay International - C O

More information

Siemens Thermostats. RDY2000BN Thermostat

Siemens Thermostats. RDY2000BN Thermostat Siemens Thermostats RDY2000BN Thermostat Answers for infrastructure and cities. Introducing the RDY2000BN BACnet Commercial Thermostat Bring more buildings and zones under control Reduce energy costs BACnet

More information

SA Series Start up Report

SA Series Start up Report SA Series Start up Report Important To ensure warranty validation and continued customer satisfaction, complete this form and return it to Desert Aire immediately after start-up. Validation of this report

More information

Marvel J MICROPROCESSOR CONTROLLER

Marvel J MICROPROCESSOR CONTROLLER Marvel J MICROPROCESSOR CONTROLLER Installation, Operation and Maintenance Manual Effective August 2016 ***Interactive PDF*** Contents General Purpose... 3 Standard Components... 3 Number of I/O Allowable...

More information

Siemens RDY2000BN. Start Up Guide

Siemens RDY2000BN. Start Up Guide Siemens RDY2000BN Start Up Guide Answers for infrastructure and cities. What this slide set is about This is a start up guide for the RDY2000BN BACnet Commercial Thermostat. This procedure show how to

More information

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide Aurora Touch UPC Kit Instruction Guide For use in single compressor water-to-air equipment utilizing fi rmware UPCSWASTD01-01 Aurora Touch UPC Kit Instruction Guide *IG1583EW* IG1583EW 08/14 Aurora Touch

More information

GeneSys Air-Cooled Screw Compressor Chiller

GeneSys Air-Cooled Screw Compressor Chiller Operation Manual OM AGSB-5 Group: Chiller Part Number: 331373201 Date: June 2005 Supersedes: OM AGSB-4 GeneSys Air-Cooled Screw Compressor Chiller AGS 230A/B through AGS 475A/B, 60 Hertz AGS 206A/B through

More information

Standard Instructions For MC-2000/3000/4000 Controllers

Standard Instructions For MC-2000/3000/4000 Controllers Standard Instructions For MC-2000/3000/4000 Controllers Manual Update: 09/12/11 Version: 3.10 1 1 QUICK REFERENCE GUIDE 1.1 NAVIGATING THE DISPLAY Interacting with the AboveAir Technologies unit is accomplished

More information

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller All volatile (Output) type points will revert to the uncommanded values after a power interruption.

More information

Manual for the integration in BMS/GTC

Manual for the integration in BMS/GTC Manual for the integration in BMS/GTC Communication parameters MODBUS RTU and BACNET COMMUNICATION UTBS PRO-REG Software Version 3.6 EN ÍNDEX 1. GENERALITIES...2 1.1. Introduction...2 1.2. signals types...2

More information

Instruction, Operation, and Maintenance: Controls Software Versions: R37+

Instruction, Operation, and Maintenance: Controls Software Versions: R37+ Instruction, Operation, and Maintenance: Controls Software Versions: R37+ VPR Series VPRX Series VPRE Series VPRP Series Version October 2011 Table of Contents Safety... 3 Special Design Requests... 3

More information

IntesisBox BACnet/IP Server - Notifier ID3000 series

IntesisBox BACnet/IP Server - Notifier ID3000 series IntesisBox Server - Notifier ID3000 series Gateway for integration of Notifier ID3000, ID3002, ID50 and ID60 fire panels into enabled control systems. Integrate your Notifier fire panels into your BACnet

More information

InfinityPro. Control System for Rapid Engineering, LLC Air Handlers. User, Operation & Troubleshooting Manual

InfinityPro. Control System for Rapid Engineering, LLC Air Handlers. User, Operation & Troubleshooting Manual InfinityPro Control System for Rapid Engineering, LLC Air Handlers User, Operation & Troubleshooting Manual Depending upon the date of shipment of your air handler(s), you will have received one of the

More information

MicroTech Series 200 Centrifugal Chiller

MicroTech Series 200 Centrifugal Chiller Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History

More information

DAP III Zone Master User s Guide

DAP III Zone Master User s Guide DAP III Zone Master User s Guide Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-788 March 2010 Revision 1.0 Document # 600-000-788 1 Overview The Data Aire DAP

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

Marvel S MICROPROCESSOR CONTROLLER. Installation, Operation and Maintenance Manual Effective October 2018 DISCONTINUED. For Reference Only

Marvel S MICROPROCESSOR CONTROLLER. Installation, Operation and Maintenance Manual Effective October 2018 DISCONTINUED. For Reference Only Marvel S MICROPROCESSOR CONTROLLER Installation, Operation and Maintenance Manual Effective October 2018 DISCONTINUED For Reference Only ***Interactive PDF*** Contents General Purpose...3 Standard And

More information

Daikin Loop Water Manager Protocol Information

Daikin Loop Water Manager Protocol Information Engineering Data ED 19015 Group: Controls Part Number: ED 19015 Date: August 2012 Supersedes: New Daikin Loop Water Manager Protocol Information BACnet Networks 2012 Daikin Table of Contents Table of Contents...

More information

PIR Ready VT76xx Series Programmable & Non-Programmable Thermostats For Commercial HVAC Applications. BACnet Integration Manual September 1, 2010

PIR Ready VT76xx Series Programmable & Non-Programmable Thermostats For Commercial HVAC Applications. BACnet Integration Manual September 1, 2010 PIR Ready VT76xx Series Programmable & Non-Programmable Thermostats For Commercial HVAC Applications BACnet Integration Manual September 1, 2010 1 Product Overview The VT76xx PI thermostat family is specifically

More information

ICC INDUSTRIAL CONTROL COMMUNICATIONS, INC.

ICC INDUSTRIAL CONTROL COMMUNICATIONS, INC. ETH-1000 Chillgard LC Quick Start Guide for BACnet MS/TP This document provides a brief overview of the connections and settings that must be used to connect a preconfigured ETH-1000 gateway to a MSA Chillgard

More information

ENTOUCH ONE USER GUIDE

ENTOUCH ONE USER GUIDE ENTOUCH ONE USER GUIDE v4.0 MEASURE. MANAGE. SAVE. Contents Getting Started 3 Installation 7 Using the Setup Wizard 11 Using the Home Screen 12 Using the Main Menu 16 The Setup Menu 19 Using the Web Management

More information

Controls Lite. Controls Instruction, Operation, and Maintenance. IOM-C Part Number

Controls Lite. Controls Instruction, Operation, and Maintenance. IOM-C Part Number Controls Lite Controls Instruction, Operation, and Maintenance Part Number 481331 Page 1 Table of Contents Valent Overview... 5 Controls Lite Strategy... 5 Equipment and Control... 6 Third-Party Control

More information

Cultivator & Hybrid Cultivator

Cultivator & Hybrid Cultivator Cultivator & Hybrid Cultivator Precision Temperature & Humidity Packaged Unit INTRODUCTION The Cultivator Series package unit is the industry s MOST ENERGY EFFICIENT and HIGHEST capacity dehumidifier on

More information

1.0 Digital Controller

1.0 Digital Controller Form CP-AHU D19_D21_D22 (11-17) D303072-A Obsoletes Forms CP-Preeva-D21 (1-16) Doc No 303072, CP-Preeva-D19 (1-16) Doc No 303071 Applies to: Preeva, MAPS, MAPS II, RPB, RPBL & SSCBL Series For Air Handler

More information

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include: Model Number: 8680-N2 Product/System Title: Room Pressure AOC Controller with N2 Communications Protocol Contents of this manual supplement include: 1) Sequence of Operation 2) Variable map 3) Description

More information

VPR Series VPRE Series VPRC/P Series VPRX Series. IOM-C Software Version 4 Part Number

VPR Series VPRE Series VPRC/P Series VPRX Series. IOM-C Software Version 4 Part Number C ON TROLS I N STRUCTION O PERATION & MA I NTENANCE VPR Series VPRE Series VPRC/P Series VPRX Series IOM-C1-0616 Software Version 4 Valent Controls IOM 2 IOM-C1-0616 Table of Contents Table of Contents...

More information

MicroTech Series-200 Flooded Screw Chiller

MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Infomation Packet Version 1.0 Group: Controls Date: February 1997 MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Communications 2002 McQuay International - C O N F I D

More information

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1 NGC-40 Bridge Overview Raychem-AR-H58862-NGC40BridgeOV-EN-1805 nvent.com 1 Table of Contents 1. NGC-40 Overview... 9 1.1 Example NGC-40 System... 10 2. Legal stuff... 11 3. Protocols... 12 3.1 Data es...

More information

BACnet Integration Manual ITG-VH72xx-BAC-E00 ( _R0 Issue Date: October 21, 2008)

BACnet Integration Manual ITG-VH72xx-BAC-E00 ( _R0 Issue Date: October 21, 2008) VH7200 Humidistat Series For Humidification & Dehumidification Control For Commercial HVAC Applications BACnet Integration Manual ITG-VH72xx-BAC-E00 (028-6017_R0 Issue Date: October 21, 2008) 1 Product

More information

Installation and Operation Manual for QS/QV and Aura Units

Installation and Operation Manual for QS/QV and Aura Units Advanced program capabilities. Installation and Operation Manual for QS/QV and Aura Units Standard controller with interface mounted in unit. Optional hand-held user interface available. Multiple communication

More information

Installation, Configuration and User Manual

Installation, Configuration and User Manual Model 8826 System Controller Model 8826 System Controller Installation, Configuration and User Manual READ AND SAVE THESE INSTRUCTIONS WELCOME Thank you for choosing the Aprilaire HVAC Automation System.

More information

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING Tempered Water Logic Control OPERATION l TROUBLE SHOOTING English For MPE Multiple Chiller Units Control Panel TEMPERED WATER SYSTEMS L-2199 Rev. 20080223 Revision: L-2199 20101104 *** IMPORTANT NOTICE

More information

Danfoss gas detection unit Type GD Heavy Duty

Danfoss gas detection unit Type GD Heavy Duty Data sheet Danfoss gas detection unit Type GD Heavy Duty The Heavy Duty gas detection units are used for monitoring and warning of hazardous Ammonia gas concentrations. They are intended for ATEX/ IECEx

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Modbus Supplemental Manual for LC6000 Controller The LC6000 is capable of being remotely monitored through the integrated Ethernet port. Through this port the controller will

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-538-01 2/8/2017 Verify that you have the most current version of this document

More information

MicroTech III Applied Air Handling Unit Controller Protocol Information

MicroTech III Applied Air Handling Unit Controller Protocol Information Engineering Data ED 15112-2 Group: Controls Part Number: ED 15112-2 Date: January 2009 Supersedes: ED 15112-1 MicroTech III Applied Air Handling Unit Controller Protocol Information Networks Networks 2009

More information

ibox Modbus Server Gateway for the integration of Notifier ID3000 / ID3002 / ID60 / ID50 fire panels in Modbus enabled monitoring and control systems

ibox Modbus Server Gateway for the integration of Notifier ID3000 / ID3002 / ID60 / ID50 fire panels in Modbus enabled monitoring and control systems Honeywell Life Safety Iberia C/Pau Vila 15-19; 08911 Badalona Barcelona T. 902 03 05 45; Internacional:+34932424236 www.honeywelllifesafety.es infohlsiberia@honeywell.com ibox Modbus Server Gateway for

More information

Networkable Fan Coil Controller Specification and Installation Instructions

Networkable Fan Coil Controller Specification and Installation Instructions Controller Models EFCB10T-OE1 (24Vac / 0 relays) EFCB12T-OE1 (240Vac / 0 relays) EFCB10TU4-OE1 (24Vac / 4 relays) EFCB12TU2-OE1 (240Vac / 2 relays) EFCB12TU4-OE1 (240Vac / 4 relays) TFL Series Thermostat

More information

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication Description The TFHB24F3XYZ1 is a fully configurable controller designed specifically for 2 pipe and 4 pipe fan coil applications.

More information

MicroTech Rooftop/RMC

MicroTech Rooftop/RMC Open Protocol Data Communications Packet Version 4.1 Group: Controls Date: March 1999 MicroTech Rooftop/RMC Data Information Packet for Open Protocol 1999 McQuay International Revision History Version

More information

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems X X testregistrierung Type Web server, also for mobile devices Zone modules Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems X-AIRCONTROL zone

More information

ARO Series. Description. Features. Modbus CO2 VOC. Networkable* ARO AROB24TGVH AROB24TGH. room controller. (AROB series only) or network

ARO Series. Description. Features. Modbus CO2 VOC. Networkable* ARO AROB24TGVH AROB24TGH. room controller. (AROB series only) or network ARO Series Universal Room Controller s Models ARO24T ARO24TH ARO24TGH ARO24TGVH Temp RH CO2 VOC Networkable* AROB24T AROB24TH AROB24TGH AROB24TGVH * Networkable: BACnet MS/TP or Modbus (selectable using

More information

AQUATROL Zone Synchronizing Universal Injection/Mixing Boiler Reset Controls AQ252

AQUATROL Zone Synchronizing Universal Injection/Mixing Boiler Reset Controls AQ252 AQUATROL Zone Synchronizing Universal Injection/Mixing Boiler Reset Controls AQ252 USER OPERATION AND MAINTENANCE WARNING Risk of electrical shock. Can cause severe injury, property damage or death. Only

More information

NE Series TM. Indoor Pool Dehumidifiers The industry benchmark in quality and customer satisfaction

NE Series TM. Indoor Pool Dehumidifiers The industry benchmark in quality and customer satisfaction NE Series TM Indoor Pool Dehumidifiers The industry benchmark in quality and customer satisfaction standard components hotel residential spa/whirlpool competition swim insitutional school/university fitness

More information

Trident User s Manual

Trident User s Manual Labkotec Oy Myllyhaantie 6 33960 Pirkkala FINLAND Tel. +358 (0)29 006 260 18.05.2017 Fax +358 (0)29 006 1260 Internet: www.labkotec.fi 34 pages Trident Copyright 2017 Labkotec Oy 1/34 TABLE OF CONTENTS

More information

The system shall be described in the following specification as manufactured by Schneider Electric

The system shall be described in the following specification as manufactured by Schneider Electric Guide Specifications Uniflair LE Air-Cooled Direct Expansion (DX) Cooling Systems THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI) MASTER FORMAT. THIS

More information

NetworkAIR AFX. Operation and Maintenance AFX65 AFX18

NetworkAIR AFX. Operation and Maintenance AFX65 AFX18 NetworkAIR AFX Operation and Maintenance AFX65 AFX18 Contents Operation... 1 Display Interface.......................................... 1 Using the Display......................................... 3

More information

MicroTech Water-Cooled Screw Chiller Controller

MicroTech Water-Cooled Screw Chiller Controller BACnet Data Information Packet BD 02-8 Group: Controls Date: January 2003 MicroTech Water-Cooled Screw Chiller Controller Point mapping data for the MicroTech BACdrop Gateway with PMF version 1.10 software

More information

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs TEC2620 Series Non-Programmable Fan Coil Network Thermostat ler and Remote I/O Relay Packs TEC2620H-0, TEC2620C-0, TEC2620H-0+PIR, TEC2620C-0+PIR, TEC2621H-0, TEC2621C-0, TEC2621H-0+PIR, TEC2621C-0+PIR

More information

IMC BACnet Module. Service Literature. Table of Contents. General. Field Connections. Physical

IMC BACnet Module. Service Literature. Table of Contents. General. Field Connections. Physical Service Literature Corp. 0808 L6 06/08 IMC BACnet Module General The IMC BACnet Module (BP1) allows communication between the Lennox IMC M1 8 controller and a BACnet MS/TP network. This module is mounted

More information

Sales and Engineering Data Sheet ED

Sales and Engineering Data Sheet ED Sales and Engineering Data Sheet ED 15121-7 Group: Controls Part Number: ED 15121 Date: July 2017 MicroTech III Chiller Unit Controller Protocol Information Modbus Networks ANSI/ASHRAE 135-2004, BACnet

More information

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47 WSHP Open v3 CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-539-01 2/8/2017 Verify that you have the most current version of this document

More information

BACnet MODBUS N2 LON Description Type Point Description Name # Object Type Register Type ID SNVT # Name SNVT Read Only

BACnet MODBUS N2 LON Description Type Point Description Name # Object Type Register Type ID SNVT # Name SNVT Read Only Point Object Register SNVT SNVT Read Only 1 BAS CO 2 Sensor Value bas_co2_val_1 AV:49 float value 40001 data float 1 48 nvibasco2val SNVT_temp_p (105) BAS CO 2 Sensor Value in PPM 2 BAS Mixed Air Temperature

More information

TWLC - Tempered Water Logic Controller. The Intelligent Control

TWLC - Tempered Water Logic Controller. The Intelligent Control TWLC - Tempered Water Logic Controller The Intelligent Control Chiller Controls Features: Up to six (6) stages: individual board for each stage maximizes redundancy. Menu driven access and programming.

More information

PLC / HMI Modbus (Slave) Addressing

PLC / HMI Modbus (Slave) Addressing Made in the USA PLC / HMI Modbus (Slave) Addressing Legacy - HMI touch screen with built in Legacy - Pentra PLC with Expandable I/O Legacy Chiller Systems, Inc. General Information IMPORTANT READ BEFORE

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

C5 controller Bacnet

C5 controller Bacnet Date: September 02, 2013 Vendor Name: Amalva UAB Product Name: C5 Firmware Revision: 1.000 BACnet Protocol Revision: 12 C5 controller Bacnet BACnet Protocol Implementation Conformance Statement Communication:

More information

C5-12 OPERATION MANUAL

C5-12 OPERATION MANUAL C5-12 OPERATION MANUAL C5-12 Controls 1 Overview... 3 1.1 Introduction... 3 1.2 Model numbers explained... 3 1.3 Product series overview... 4 1.4 Hardware Controller... 4 1.5 Controller Inputs and Outputs...

More information

Air and Water cooled inverter chillers

Air and Water cooled inverter chillers OPERATION MANUAL Air cooled: EWAD TZ EWAD TZ-B Water cooled: EWWD VZ EWWH VZ 1/85 TABLE OF CONTENTS 1 SAFETY CONSIDERATIONS... 7 1.1 General... 7 1.2 Avoid electrocution... 7 1.3 Safety Devices... 7 1.3.1

More information

EMERSON BLUE Wireless Comfor t Inter face 1F98EZ-1621 HOMEOWNER USER GUIDE

EMERSON BLUE Wireless Comfor t Inter face 1F98EZ-1621 HOMEOWNER USER GUIDE EMERSON BLUE Wireless Comfor t Inter face 1F98EZ-1621 HOMEOWNER USER GUIDE Emerson Blue Wireless Comfort Interface - Homeowner User Guide Message to Homeowners Congratulations on choosing the Emerson Blue

More information

Daikin ENVi Thermostat installation overview

Daikin ENVi Thermostat installation overview Daikin ENVi Thermostat installation overview RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL Presenter s Name Presenter s Title Daikin ENVi system overview (web based thermostat) Slide 2 Daikin ENVi System Overview

More information

FieldServer Driver - Serial FS McQuay Microtech Open Protocol

FieldServer Driver - Serial FS McQuay Microtech Open Protocol Description FieldServer Driver - Serial FS-8700-80 McQuay Microtech Open Protocol This is an active client protocol. The driver is capable of acting as a master or slave. As a master, the Fieldserver polls

More information

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide SE8600 Series Room Controllers 2 TABLE OF CONTENTS Overview 2 SE8600 Rooftop Unit and Indoor Air Quality Controllers 3 SE8600UxBxx 2 Heating

More information

RSC 1000 User Manual. Rev /25/16

RSC 1000 User Manual. Rev /25/16 RSC 1000 User Manual Rev 2.2 10/25/16 CRITICAL APPLICATIONS DISCLAIMER QUEST CONTROLS PRODUCTS ARE NOT INTENDED OR AUTHORIZED FOR USE IN ANY APPLICATION THAT REQUIRES FAIL-SAFE OPERATION, OR ANY SYSTEM

More information

Introduction. What is the RTU Open controller?

Introduction. What is the RTU Open controller? TU Open v3 CAIE COPOATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-521-01 8/22/2017 Verify that you have the most current version of this document

More information

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR Printed in the USA ADSOOASHPOA 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located on its front

More information

AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System

AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin AD-1272 Code No. LIT-12012477 Issued December 2017 Refer to the QuickLIT website for the most up-to-date version of

More information

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5

More information

MARVEL PREMIUM HVAC MICROPROCESSOR CONTROLLER

MARVEL PREMIUM HVAC MICROPROCESSOR CONTROLLER MARVEL PREMIUM HVAC MICROPROCESSOR CONTROLLER Installation, Operation and Maintenance Manual Effective May 2017 ***Interactive PDF*** CONTENTS GENERAL PURPOSE 3 MARVEL PREMIUM - CONTROLLABLE SYSTEM COMPONENT

More information

TECHNOLOGY GUIDE. :: the dawn of a new era in commercial HVAC technology. The all-new Rheem Commercial Renaissance Line featuring:

TECHNOLOGY GUIDE. :: the dawn of a new era in commercial HVAC technology. The all-new Rheem Commercial Renaissance Line featuring: COMMERCIAL 7.5 12.5 TON HVAC LINE :: the dawn of a new era in commercial HVAC technology The all-new Rheem Commercial Renaissance Line featuring: VFD Technology Rheem HumidiDry Rheem ClearControl 7.5 12.5

More information

CT224 Setup Tutorial

CT224 Setup Tutorial CT224 Setup Tutorial Table of Contents 1. Introduction 2. Configuring Controller for Operation A. Example 1 Over Temp Operation with Hysteresis @ 5º F. B. Example 2 Under Temp Operation with Hysteresis

More information

Wilo CO-Helix Booster Systems. Product Presentation July, 2017

Wilo CO-Helix Booster Systems. Product Presentation July, 2017 Wilo CO-Helix Booster Systems Product Presentation July, 2017 Pioneering for You Intelligent Pumps Save energy & optimize performance Technological innovation focus largest R&D development facility in

More information

CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMAC00A10-12EN

CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMAC00A10-12EN CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER Table of Contents - 2 - INTRODUCTION... 3 OPERATING LIMITS:... 4 CONTROLLER FEATURES... 4 GENERAL DESCRIPTION... 5 CONTROL

More information

Air and Water cooled scroll chillers & heat pump

Air and Water cooled scroll chillers & heat pump OPERATION MANUAL Water cooled ranges: EWWQ090G EWWQ720L - R410a - Water-cooled scroll chillers Air cooled ranges: G 075155 SS G 080170 XS G 075160 XS 1 G Table of Contents 1 SAFETY CONSIDERATIONS... 5

More information

Installation Instructions / User s Manual TSTAT0406 and TSTAT0408

Installation Instructions / User s Manual TSTAT0406 and TSTAT0408 997-060180-5 Installation Instructions / User s Manual TSTAT0406 and TSTAT0408 4 HEAT 2 COOL DUAL FUEL TSTAT0406 & TSTAT0408-4 WIRE CAPABLE THERMOSTAT (NAXA00201DB Daughter Board sold separately) LEFT

More information

Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls

Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls Specification General The Powerex Laboratory Scroll Enclosed Air Compressor System is designed to provide clean, dry air for

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 482584 Grease Trapper ESP Kitchen Exhaust Pollution Control System Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before

More information

Operation manual. Rooftop Packaged Unit

Operation manual. Rooftop Packaged Unit Operation manual Rooftop Packaged Unit odels: UATYQ20ABAY1 UATYQ25ABAY1 UATYQ30ABAY1 UATYQ45ABAY1 UATYQ50ABAY1 UATYQ55ABAY1 UATYQ65ABAY1 UATYQ75ABAY1 UATYQ90ABAY1 UATYQ110ABAY1 UATYQ115ABAY1 UATYQ20AFC2Y1

More information

Some alarms can be manually cleared from the current alarms list. This is indicated for the alarms where this is possible.

Some alarms can be manually cleared from the current alarms list. This is indicated for the alarms where this is possible. Alarm Descriptions This document describes all possible alarm types as listed in the alarm log. x indicates compressor circuit for compressor related alarms. Alarms are listed in alphabetical order. Some

More information

CONTROLS MANUAL. CARRIERrtc basic & medium electronic control 48/50 EN/EH 50 HB/HF/NZ/NF. Original document

CONTROLS MANUAL. CARRIERrtc basic & medium electronic control 48/50 EN/EH 50 HB/HF/NZ/NF. Original document CONTROLS MANUAL CARRIERrtc basic & medium electronic control 48/50 EN/EH 50 HB/HF/NZ/NF Original document Contents 1. General description....5 2. Set-up... 6 2.1. micropc control board... 6 2.2. TCO user

More information

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers TABLE OF CONTENTS Overview 2 VT8600 Rooftop Unit Heat Pump and Indoor Air Quality Controllers 3 VT86X0U5X00B

More information

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification February 11, 2019 Master Panel Product Description The Master Panel shall provide lead/lag control and time based, automatic rotation of up to eight (8) boilers, when used in conjunction with LMV3 or LMV5

More information

MicroTech Unit Ventilator

MicroTech Unit Ventilator Open Protocol Data Information Packet Version 2.2 Group: Controls Date: April 1996 MicroTech Unit Ventilator Open Protocol Data Communications 2002 McQuay International - C O N F I D E N T I A L - This

More information