INSTALLATION AND OPERATING MANUAL OF THE BASIC CONTROL PANEL (CCB) FOR THE FISAIR EVAPORATIVE HUMIDIFIERS
|
|
- Philip Ball
- 5 years ago
- Views:
Transcription
1 0 0 I INSTALLATI AND OPERATING MANUAL OF THE BASIC CTROL PANEL (CCB) FOR THE FISAIR EVAPORATIVE HUMIDIFIERS Software Version 8.0 MCCB-EN-17-1 In fulfilment of the Regulations of the European Union on Machine Safety, it is indispensable to read this protocol in detail prior to installing the equipment. FISAIR S.L. C/Uranio, 20; PoI. Ind. Aimayr, San Martín de la Vega (Madrid) España. Tel: (+34) Fax: (+34) info@fisair.com fisair.com
2 MANUAL Basic Control Panel CCB 2
3 MANUAL Basic Control Panel CCB 3 Index 1. General description Scope of installation Description of the hardware Connections Configuration Start up List of alarms...22
4 MANUAL Basic Control Panel CCB 4 1. General description The Basic Control Panel has been specifically designed for interconnection and supervision of the accessories supplied with the FISAIR Evaporative Humidifiers. The addition of the CCB makes it possible to obtain more precise, simple and reliable integration into air treatment units. The control panel manages all the accessories of the FISAIR Evaporative Humidifiers: Water re-circulation pump Minimum and maximum water level detector of the tank Water-supply electro-valve for the tank Motor-valve for purging/drainage of the tank The water treatment system by means of a UV lamp (optional) Water conductivity (optional) Max.25m Figure 1: Examples of installation of the BCP on a vertical wall and a BCP integrated in UTA
5 MANUAL Basic Control Panel CCB 5 2. Scope of installation The Basic Control Panel is supplied in an insulating box made up of a bottom and removable top in RAL coloured ABS 7035, with weatherproof top (according to standards IEC // ) with degree of protection IP56 according to EN60529 and shock-protection IK07 according to EN /96. Heat and humidity measuring conditions from the area of the installation: Relative Humidity [ 5%... 95% RH], without condensation. Temperature [ -10 C C ] During the installation, it is necessary to respect the recommended spaces for connections, inspection and maintenance. If the box is perforated in the places indicated for fixing, it must be ensured that the necessary degree of protection IP56 is maintained. The Basic Control Panel weighs 3.15 kg., and should be installed vertically on a wall (see Figure 1) to maintain the IP56 degree of protection. In figures 2.1 and 2.2, the minimum service spaces are shown which are to be respected and heights of the perforations which must be made for fixing. Mín Mín Mín Mín 50 Mín 50 0 Ø5 Ø5 Ø5 Mín 150 Mín 150 Figure 2.1: Right profile door open. Ø5 225 I Figure 2.2: Front view door open.
6 MANUAL Basic Control Panel CCB 3. Descriptionof the hardware Figura 3.1: Front view of the CCB cover 6
7 MANUAL Basic Control Panel CCB Figura 3.2: Bottom of the CCB 7
8 MANUAL Basic Control Panel CCB Figura 3.3: Interior of the CCB cover 8
9 MANUAL Basic Control Panel CCB LED / Key No. Description, Function anditemcode 1 Switch (l1) for the cutting and insulation of the supply voltage with the possibility of locking by padlock (not supplied) Cód. Art: HMI. Control and viewing interface SEF-027 Cód. Art: LED. Yellow. Indicates low-voltage equipment 4 LED. Red. Indicates general fault 5 Operating key in Manual mode 6 Change of state key from operation to stop 7 Operating key in Automatic mode. 8 Acceptance key (ENTER) 9 Key to return when browsing 10 Browsing keys 11 LED. Blue. Indicates the operativeness of the UV Lamp 12 LED. Yellow. Indicates that the water-feed electro-valve is powered 13 LED. Green. Indicates that the drainage moto-valve is powered 14 LED. Green. Indicates that the drainage moto-valve is open (requires feedback connection) 9
10 MANUAL Basic Control Panel CCB 10 LED / Key No Description, Function and Item Code LED of float switch state : Yellow: Indicates level below minimum Green: Indicates operating level Red: Indicates maximum level of water Flashing red: Indicates a defect LED of the water pump state: Green: Water pump in operation Red: Malfunction 17 Viewing display: Errors automatic mode manual mode Off state Value in µs of the conductivity of the water (only applicable with conductivity sensor installed) 18 Feed terminals (X1) Magneto-thermal circuit breaker (U1 in the electrical diagram) for protection of the water pump Cod. Art: (Pump 55W) Cod. Art: (Pump 60W) Cod. Art: (Pump 90W) Cod. Art: (Pump 125W) Cod. Art: (Pump 5250W) Electronic power card SEF-028 Item code:
11 MANUAL Basic Control Panel CCB 11 LED / Key Ref. Description, Function and Item Code 29 RL8 Relay for the drainage-purging moto-valve Item code: Fuse F1 for protection of the PCB. Item code: Fuse F2 for protection of the auxiliary power supply Item code: Fuse F3 for protection of the water supply electro-valve Item code: Fuse F4 for protection of the drainage/purging motovalve Item code: Fuse F5 for protection of the UV Lamp Item code: RL1 Relay for the water recirculation pump Item code: RL2 Relay for UV Lamp Item code: RL3 Relay for water supply electro-valve Item code: Central processing card SEF-025 Item code:
12 MANUAL Basic Control Panel CCB 12 LED / Key Ref. Description, Function and Item Code 31 3V Battery CR2032 Item code: Flat cable connector 33 Configuration switches 34 Features plate of the BCP 4. Connections 1) Connect the standard or optional accessories to the SEF-028 card as shown in figure 4.1. Figure 4.1: Card SEF-028
13 MANUAL Basic Control Panel CCB 13 Type of connection Symbol Connection Description Max. Power Max. Voltage Optional +24VDC J12 Auxiliary Source of Direct Current 5W 24Vdc Obligatory J13 Electro-valve for water supply 14VA 24Vac Obligatory J14 Moto-valve for drainage/purging of water 40VA Obligatory J15 Position feedback of the purging moto-valve (end of opening travel carried out) Free of potential Obligatory J16 Sensor of maximum water level (NC Contact) Free of potential Obligatory J17 Sensor of minimum water level (NA Contact) Free of potential Optional J18 Operation sensor of the UV Lamp (If applicable) Free of potential Optional J19 Bridge this contact in case of monophase pump and supply Free of potential Optional J20 Locking of external defect Free of potential Optional J21 Remote / locking in automatic mode. Free of potential - J22 Without use Optional J23 Remote defect signal. Optional J24 Remote operating signal. 24Vac 500VA 250V 500VA 250V 500VA 250V
14 MANUAL Basic Control Panel CCB 14 Type of connection Connection Description J25 Remote voltage signal. Optional J10 UV Lamp supply Obligatory J11 Water re-circulation pump Optional Symbol NO COM Max. Power Max. Voltage 500VA 250V 30W 230V 240W 400V 2) With the isolator in position 0, connect the mains power supply, as corresponds in each case, to the X1 terminals Connection of three-phase line Connection of single-phase line
15 MANUAL Basic Control Panel CCB Configuration Configure the basic control panel attending to the needs of its air treatment process to which the Fisair Evaporative Humidifier has been added. Give special attention to the quality of the water supply, to the hygienic demands of the application and to the required working cycles. 1) Configure the purging of the tank according to the following options:
16 MANUAL Basic Control Panel CCB 16 2) Confirmation and duration of the purging 3) Configuration of the delay for starting up the pump
17 MANUAL Basic Control Panel CCB 17 In the table, the selectable options can be observed for the different functions. The shaded values are the factory-configured times/options. POSITI OF SWITCHES FUNCTI SW1 A(1) B(2) DELAY IN START UP OF THE PUMP 15 s 30 s 60 s 300 s C(3) D(4) PURGING CYCLES PER HOUR Maximum 2 cycles Maximum 6 cycles Maximum 12 cycles Sin vaciado periódico SW2 A(1) B(2) TIME OF CFIRMATI OF PURGING 2 min 6 min 12 min 18 min C(3) D(4) ADDITIAL PURGING TIME 30 min 60 min 90 min 200 min SW3 A(1) B(2) PERIODIC PURGING DURING OPERATI Never 8h 12 h 24 h C(3) D(4) DELAY IN PURGING TO PUTTING IN THE POSITI 4h 8h 12 h 24 h SW4 A(1) B(2) PURGING OPTIS Never According to SW3 According to order SEF-026 C(3) D(4)
18 MANUAL Basic Control Panel CCB Start up When the installation premises are fulfilled and the purging options and the operating times are set, and when all the connections are made: 1st. Verify that the mains voltage corresponds to the supply voltage of the BCP according to its pertinent electrical diagram. (See the number of the electrical diagram on the characteristics plate in the interior of the CCB) 2nd. Change the state of the switch I1 from position 0 to position 1. A scan is carried out of the LEDs through the entire command and viewing interface and the low voltage remote signalling contact is activated (Connection J25).
19 MANUAL Basic Control Panel CCB 19 3rd. Carry out the adjustments prior to the selection of the working mode. a) UV lamp Enable or disable the UV Lamp by means of the browsing keys. b) Conductivity meter (After Software Version 10.0)
20 MANUAL Basic Control Panel CCB 20 4th. Select the mode of work which is best adapted to your needs, automatic or manual
21 MANUAL Basic Control Panel CCB 21 5th. Operation I. If you have enabled the UV lamp, the LED will flash blue until the confirmation of the in operation sensor is received, at which point it ceases to flash and will be constantly illuminated in blue. II. Once the working mode is selected, the LED of the electro-valve for water supply to fill the tank lights up until the mechanical valve of the float/buoy is closed. In case of a fault in the mechanical valve, the tank continues to fill up until the level III. sensor detects the maximum level of water(led red). Once the minimum water level is reached (LED green), after 30s the water recirculation pump is supplied (LED IV. green). During the operation or after switch off, the LEDs will be lit depending on the configurations set down for purging. V. In the course of operation, whether MAN or AUT, under any anomaly, it will be possible to view an alarm code on the display.
22 MANUAL Basic Control Panel CCB Listof alarms. Alarm indication Element Description of the alarm Recommended action 40* CPU Internal fault of the SEF-025 card. Contact Technical Services 41* RAM Memory RAM Memory Replace the battery and/or contact Technical Services to reload the programme into the RAM memory 42* Conductivity probe Connection error or damaged element Review the connection and/or contact with Technical Services 43 Level switch Connection error or damaged element Contact Technical Services 44* Magneto-thermal circuit-breaker Connection error, on current or lack of phases Review the connection, ensure you have a correct supply network. Once the defect is solved, rearm the circuit breaker 45* UV Lamp Contact IN1 has not been closed by the lamp sensor Review the signal from the UV lamp sensor 46 Moto-valve for drainage/purging Once the time has passed for confirmation of purging the minimum level of water is not detected Verify the correct operation of the purging moto-valve 47 Water supply Once a set time has passed for filling a minimum level of water is not detected Verify the correct operation of the electro-valve for water supply 48 Moto-valve for drainage/purging Once a set time has passed the feedback from the moto-valve for draining/purging is not detected Verify the correct operation and connection of the moto-valve and of the feedback 49 Conductivity The conductivity of the water cannot be reduced Verify the correct operation of the conductivity sensor. Review the conductivity order 50 External fault IN3 open, in case of installing an external element. - These alarms impede the operation of the equipment. Once the defect has been solved, it is necessary to turn off the equipment and start it again to return it to its initial state.
Excel-EN Conventional Fire Control Panel
Available as 2, 4, 6, 8,10 or 12 zones Approved to EN54-2 & 4 Modular expansion zone cards Programmable relays and outputs Optional additional sounder circuits Optional additional programmable outputs
More informationTECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB
Summary 1 CONNECTIONS... 3 1.1 TEMPERATURE PROBES...3 1.2 LOW VOLTAGE DIGITAL INPUTS...3 1.3 LIVE DIGITAL INPUTS...4 1.4 RELAY OUTPUTS...5 2 POWER SUPPLY... 6 3 SERIAL CONNECTIONS... 6 4 SOFTWARE... 7
More informationBSR Addressable Fire Detection control panel. Installation operation manual
BSR-1116 Addressable Fire Detection control panel Installation operation manual ATTENTION!!! READ THE MANUAL BEFORE THE INSTALLATION AND PAY ATTENTION TO PARAGRAPH 2.6.3 AND 2.6.4. Page 2 from 36 Contents
More informationReplaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge
Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays
More informationFTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS
QUICK USER GUIDE FOR, 2 & 4 ZONE PANELS INDICATORS COLOUR INDICATION MON FAULT Yellow On when a fault condition has occurred, or if no other fault Led is on, this indicates 24v auxiliary fuse failure.
More informationSMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS
SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS CONTENTS 1. INTRODUCTION... 5 2. WARNINGS... 6 3. GENERAL DESCRIPTION... 7 4. INSTALLATION... 8 5. LUMINOUS INDICATORS AND COMMANDS... 9 6. DIP-SWITCH
More informationInstallation, Operating and Maintenance Manual
STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS
More informationREA 105 Arc Protection Module. Operator s Manual
REA 105 1MRS 751005-MUM Issued: 20.04.1998 Version: B2/26.5.2000 Checked: Approved: REA 105 We reserve the right to change data without prior notice. Contents: 1. General...4 1.1. Features...4 2. Safety...5
More informationApplications: 27. NETIChome mobile ios 28. NETIChome mobile Android. NETIChome basic elements
INDEX 1 NETIC... 2 2 Door/Window detector MINI... 2 3 FOUR sensor... 3 4 Smoke detector... 3 5 Flood detector... 4 6 ILLumination sensor... 4 7 Lamp holder... 5 8 Siren... 5 9 Power meter & switch... 6
More informationSyncro AS. Analogue Addressable Fire Control Panel. User Manual
Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level
More informationUSER GUIDE. DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER -
USER GUIDE DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER - II CONTENTS 1. SYMBOLS AND WARNINGS... 5 2. GENERAL INFORMATION... 6 3. WARNINGS... 7 4. GENERAL DESCRIPTION... 8 5. INSTALLATION...
More informationM15051) INSTRUCTION MANUAL
INSULATION GUARD MEG-1000 (Code M15051) INSTRUCTION MANUAL ( M98122001-20 / 05A ) (c) CIRCUTOR S.A. Insulation guard MEG-1000 1.- BASIC INSTRUCTIONS 1.1.- Delivery spot check This manual is issued to help
More informationFEC403EN Installation Manual
FEC403EN Installation Manual P/N 10-4101-501-2FC1-01 ISS 22JAN15 Copyright Trademarks and patents Manufacturer 2015 UTC Fire & Security. All rights reserved. The FEC403EN name and logo are trademarks of
More informationUser Operation Manual
APPROVED BY: JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL User Operation Manual PAGE 1 of 6 1 CONTENTS 1. FIRE - GENERAL... 3 2. FIRE - ZONES 1 OR 2 - AUTOMATIC MODE... 3 3. FIRE - ZONES
More informationM2500 Engine Controller Installation Manual
M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1 Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs...
More informationAnnuciator Logic Controllers
C B0 C C5 C C6 C C7 A B A B A B A B A5 B5 A6 B6 A7 B7 A8 B8 A9 B9 5 Annuciator Logic Controllers 68 c5 c6 c7 B B B B B5 B6 B7 B8 B9 B0 B B B B B5 B6 C0 BUZZER RETURN BZ M / BZ CTROL SIGNAL LAMP DC() DC()
More informationLAE10 LFE10. Use. Series 02
ISO 00 Flame Safeguards 7 7 LAE L Series 02 Supplementary data sheets 772 and 773 Flame safeguards for burners with intermittent operation. For safety reasons - self-test of flame supervision circuit,
More informationFEC400 Series. Installation Manual
FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea
More informationNU2 Smart Power Supply (SPS) Manual
GENERAL The Smart Power Supply (SPS) is an innovative Quad Output, field programmable power supply. Each of the four outputs can provide four Amps for a total of sixteen Amps in either 12VDC or 24VDC.
More information1F98EZ-1421, Easy Install
1F98EZ-1421, -1441 Easy Install For up to 4 Stages and 2 Stages Cool INSTALLATION INSTRUCTIONS APPLICATIONS Configuration Options Single Stage Multi Stage Pump Pump with Dual Fuel FAILURE TO READ AND FOLLOW
More informationEXTINGUISHING CONTROL PANEL PX2 SERIES
EXTINGUISHING CONTROL PANEL PX2 SERIES AE/PX2 AE/SA-PX2 AE/94-PX2 USER MANUAL VERSION 1.0 APR/2007 CONTENT PAGE 1 INTRODUCTION...3 1.1 PURPOSE OF THE MANUAL... 3 1.2 REMARKS... 3 1.3 WARNINGS AND PRECAUTIONS....
More informationCommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits
CommStat 4 PRODUCT DATA SHEET Controller for Redundant Telecom HVAC Systems General Description The CommStat 4 is an HVAC controller designed specifically for controlling two redundant air conditioners,
More information3. Intended use. 4. Function. 1. Product characteristics. 2. Safety. Functional description. Channel A light. Motion detector
EN Motion detector themova S360-101 DE WH 1030565 themova S360-101 DE GR 1030566 themova S360-101 AP WH 1030555 themova S360-101 AP GR 1030556 1. Product characteristics 307067 Passive infra-red motion
More informationSACE PR021/K SIGNALLING UNIT
SACE PR021/K SIGNALLING UNIT 1SDH000559R0002 L3016 1/52 EN CONTENTS 1. GENERAL INFORMATION...4 1.1. FOREWORD...4 1.2. APPLICABLE SCENARIOS...5 2. TECHNICAL SPECIFICATIONS...6 2.1. ELECTRICAL CHARACTERISTICS...6
More informationBS-316. Gas detection control panel up to 16 inputs. Installation operation manual
BS-316 Gas detection control panel up to 16 inputs Installation operation manual Page 1 from 21 Contents 1 Operation instructions--------------------------------------------------------------------------------------------------------------------3
More informationDIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)
DIESEL ENGINE CONTROL UNIT DCU 205 - USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) 64 84 52 00 Fax: (+47) 64 84 52 12 office@auto-maskin.no - 1 - TABLE OF CONTENTS 1. INTRODUCTION TO THE DCU 205...4
More informationMatrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1
Matrix2000 User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 s Version: 2.0 Revision: 1 IMPORTANT INFORMATION Limitation of liability It is mandatory, Matrix2000 panel to be installed in accordance
More informationINDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...
GUIDE MANUAL INDEX 1- Introduction...5...5...6 4- The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops...7 4.2- The Control Panel 4 and 8 Loops...9 5- Installation Guide...10 5.1- Pre-Installation
More informationThe EN54 Part 2 & 4 Fire System
Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54
More informationRoom thermostats with LCD for wall mounting
s 3 181 RDG100 / RDG110 RDG140 / RDG100 RDG100/H Room thermostats with LCD for wall mounting for fan coil unit applications for universal applications for use with compressors in dx type equipment RDG1
More informationApplication, Installation, Operation & Maintenance Manual
APPROVED BY:JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL Application, Installation, Operation & Maintenance Manual PAGE 1 of 43 CONTENTS 1. INTRODUCTION... 3 2. GENERAL DESCRIPTION...
More information20 Light Remote Annunciator
Light Remote Annunciator Owner s Manual Surface Mount Flush Mount 94-95- Standard Annunciator 94-, 94-95-, 95-4- 4- Annunciator w/remote Relay Panel 4-, 4-4-, 4-49-, 49-49-, 49- Time Multiplexed Annunciator
More informationAddressable and Conventional Fire Protection
Addressable and Conventional Fire Protection Simply reliable F I R E P R O T E C T I O N The MAGPro and Fireline systems has been created to balance performance, reliability and aesthetics whilst being
More informationSYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System
SYSTEM MANUAL FT1-SB Single Zone Fire Alarm System DOCUMENT HISTORY Issue Date Description Written By Checked By Draft 0 2/9/2008 Original Document. A. Shenouda C. Orr Issue 1 4/11/2011 Update drawing
More informationCommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET
CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or
More informationFire control panels FC360
Cerberus TM FIT Fire control panels FC360 FC361-ZZ, FC361-ZA, FC361-YZ, FC361-YA Fire control panels (1-loop) for addressable peripheral devices with integrated operating unit One loop with 126 addresses
More informationIntelligent Security & Fire Ltd
full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04
More informationPNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel
PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum
More informationisopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)
T M 1 isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded) Technical Bulletin NAE1012372 / 03.2015 isopv
More informationOperator: Save these instructions for future use!
50V64-743 Integrated Furnace Control for Furnaces with Variable Fan Speed INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
More informationAS DIGITAL FIRE PUMP CONTROLLER
AS 2941-2013 DIGITAL FIRE PUMP CONTROLLER COMPLIANT WITH AS2941-2013 CLAUSES 9.4.1 9.4.22 OPERATION INSTRUCTIONS New South Wales Unit 2/1040 Canley Vale Road Wetherill Park NSW 2164 Ph: +61 2 9757 5800
More informationInstruction Manual August sitrans CU 02
Instruction Manual August 2005 sitrans CU 02 Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment.
More informationFC700A Fire detection control unit
FC700A Fire detection control unit Synova 4-16 Loop analogue addressable control panel 128 devices per loop (SynoLOOP) and up to 1000 devices per panel Up to 24 collective lines for Synova TM 600 serie
More informationRS 0021 DIGITAL GAS DETECTION CONTROL UNIT FOR SENSORS WITH S-BUS PROTOCOL. USER MANUAL Read carefully before use
RS 0021 DIGITAL GAS DETECTION CONTROL UNIT FOR SENSORS WITH S-BUS PROTOCOL USER MANUAL Read carefully before use GENERAL INFORMATION This device is a gas control unit with RS485 serial communication, based
More informationCHECKFIRE 210 Detection and Actuation System
DATA SHEET CHECKFIRE 210 Detection and Actuation System Features Supervised power, detection, release, and communication circuits Display module with LED system status indicators Adjustable mounting bracket
More informationDIGITAL LIGHT CONTROLLER
DIGITAL LIGHT CONTROLLER Manual - Model UD 0900 Modular lighting controller for 20 HPS or MH lamps Reading this manual will help you better understand the functions of your device and its potential. Keep
More informationOcean Breeze Model QU700 Programmable Digital Touchscreen Climate Control
Ocean Breeze Model QU700 Programmable Digital Touchscreen Climate Control Ocean Breeze 2951 SE Dominica Terrace, Stuart, Florida 34997 Tel: 772 2200038 obr@oceanbreezeac.com http://www.oceanbreezeac.com
More informationEmerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING
Emerson Inspire 1HDEZ-1521 Installation Instructions Thermostat/Interface Equipment Control TROUBLESHOOTING FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL
More informationIFP-2.32 Manual 1) DESCRIPTION ICAS FIRE PANEL IFP 2.32
1) DESCRIPTION IFP-2.2 Manual IFP-2.8 and IFP-2.2 is a microprocessor controlled Fire Panel with 2 loops intended either for privat Homes & Apartments or larger installations. The two loops are balanced
More informationRack Mount Series Installation Guide
Rack Mount Series Installation Guide Models Include: Maximal1RHV Maximal1RV - 12VDC @ 4 amp or 24VDC @ 3 amp. - 12VDC @ 4 amp or 24VDC @ 3 amp. - Eight (8) Fuse Protected Outputs. - Sixteen (16) Fuse Protected
More informationBX444-Mc Gas Detector
Installation and User Guide Rev.01. BX444-Mc Gas Detector Application Duomo is recognised within the gas industry for providing a comprehensive range of low cost, high reliability gas detection for many
More informationTHERMOSTATS 126. MECHANICAL THERMOSTATS 1C20 / 1C21 / 1C26 / 1E30 / 1E56 / 1F56... Wiring Diagrams / Configuration
INDEX THERMOSTATS 126 l (s) Description Page(s) EMERSON BI BLUE 12" TOUCHSCREEN 1F97-1277... Wiring Diagrams / Configuration... 126 131 1F95-1280 / 1F95-1291... Wiring Diagrams / Configuration... 128 131
More informationConsultant Specification AGILE Wireless Fire Detection System
Contents Scope of Work... 2 The EN54 Part 2 & 4 Fire System... 2 Standards... 2 Wireless Intelligent Photoelectric Smoke Detector Specification... 4 Wireless Intelligent Thermal Heat Detector Specification...
More informationGRUNDFOS INSTRUCTIONS LCD 108. Installation and operating instructions
GRUNDFOS INSTRUCTIONS LCD 08 Installation and operating instructions Installation and operating instructions Original installation and operating instructions CONTENTS Page. Symbols used in this document.
More informationEsmi Sense FDP Fire detection panel with ALC2 loop controller
Esmi Sense FDP Fire detection panel The intelligent and modular Esmi Sense FDP fire detection panel provides multiple new features for efficient and reliable fire safety. The Esmi Sense FDP fire detection
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL
PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if
More information1 measurement signal input 4-20 ma for connection to an external gas sensor 5 freely programmable alarm switching points per measuring point
Medium - Control - System Franke & Haqenest GmbH Borngasse 1a * 04600 Altenburg Tel: 03447-499 313-0 Fax: 03447-499 313-6 email: info@mcs-gaswarnanlagen.de MCS User Guide MCS GasController Microprocessor
More informationOcean Breeze Model QU700 Programmable Digital Touchscreen Climate Control
Ocean Breeze Model QU700 Programmable Digital Touchscreen Climate Control Ocean Breeze 2951 SE Dominica Terrace, Stuart, Florida 34997 Tel: 772 2200038 obr@oceanbreezeac.com http://www.oceanbreezeac.com
More informationUSE AND INSTALLATION HANDBOOK
Date : 10/02/14 Rev. 01 PR.T : FG006176 USE AND INSTALLATION HANDBOOK SIMPLEX-UP CONTROL PANEL FOR 1 ELECTRIC PUMP WITH CURRENT CONTROL. SIMPLEX-UP Via Enrico Fermi, 8-35020 Polverara PD Tel.049/9772407
More informationDUAL MONITORED INPUT/OUTPUT UNIT BN-305-2
DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2 Interactive fire detection systems Product Datasheet Features Interactive For interfacing and controlling external units to Autronica s interactive fire detection
More informationExcellence in Level Measurement
Technical Data Sheet No. Novaflo 2000 'Fail-Safe' Level Alarm System Excellence in Level Measurement Afriso Eurogauge Ltd Imberhorne Lane, East Grinstead West Sussex. RH19 1RF Tel: 01342 323641 Fax: 01342
More informationSERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION
R SERIES 35-61 24 VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay F-35-61 August 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge
More informationDIMENS. MIN TYPICAL MAX A 71.0 (2.795) 71.0 (2.795) 71.8 (2.826) B 29.0 (1.141) 29.0 (1.141) 29.8 (1.173)
Evco S.p.A. Code 104K204E05 page 1/5 EVK204 Digital controller for ventilated refrigerating units, with HACCP and Energy Saving functions version 1.05 GB ENGLISH 1 PREPARATIONS 1.1 Important Please read
More informationFire Damper Interface (230V)
Always READ this document BEFORE INSTALLATION. Please Retain for future reference. This product forms part of a life safety system. Failure to correctly store, handle, install and maintain the product
More informationSmoke Fire Damper Interface (230V)
Always READ this document BEFORE INSTALLATION. Please Retain for future reference. This product forms part of a life safety system. Failure to correctly store, handle, install and maintain the product
More informationSmoke Damper Interface (230V)
Always READ this document BEFORE INSTALLATION. Please Retain for future reference. This product forms part of a life safety system. Failure to correctly store, handle, install and maintain the product
More informationGE Security. FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring
GE Security FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring Version v2-2 / September 2005 Aritech and Kilsen are GE Security brands. http://www.geindustrial.com/ge-interlogix/emea
More information4100U City and Relay Cards Installation Instructions
4100U City and Relay Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-6031/6032 City Circuit Cards 4100-6033 Alarm Relay Card Inspecting
More informationKM300 Carbon Monoxide Detection System Installation Manual
GE Security KM300 Carbon Monoxide Detection System Installation Manual P/N 1068922 REV 2.0 16SEP09 Copyright Copyright 2009 GE Security, Inc. All rights reserved. This document may not be copied in whole
More informationINTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3
INTELLIGENT FIRE TECHNOLOGY Twinflex and Multipoint V3 User Guide (TO BE RETAINED BY USER) 26-0340 Issue 3 Rafiki Protection Limited Rafiki policy is one of continual improvement and the right to change
More informationTOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design
TOTAL SOLUTIONS Liquid Level Control Product Guide MATELEC innovative by design Liquid Level Control Contents Dual Pump Controllers Section 1 The Range Common Features Operating Data Control Logic Setup
More informationCommStat 4 Controller
CommStat 4 Controller CommStat 4 Telecom HVAC Controller The CommStat 4 is an HVAC controller designed specifically for controlling two redundant air conditioners, heat pumps and air conditioners with
More informationDUAL MONITORED INPUT/OUTPUT UNIT BN-305
DUAL MONITORED INPUT/OUTPUT UNIT BN-30 Interactive fire detection systems Product Datasheet Features Interactive For interfacing and controlling external units to Autronica s interactive fire detection
More informationSerie Rugghölzli 2 CH Busslingen. Tel. +41 (0) Fax +41 (0)
Serie 5000 Tel. +1 (0)5 222 Fax +1 (0)5 222 12 PRODUCT INTRODUCTI PRODUCT INTRODUCTI 5 Series programmable temperature controller is FineTek's mid-range series of controllers. It uses a 12bit analog /
More informationABLOY DA460 SWING DOOR OPERATOR. Installation and commissioning manual
ABLOY DA460 SWING DOOR OPERATOR Installation and commissioning manual APPROVALS / STANDARDS 73/23/EEC (Low Voltage directive) 93/68/EEC (Low Voltage directive) 89/336/EEC (EMC directive) Statement of fire
More information1. Product characteristics 4 2. Safety 5 3. Proper use 5 4. Operation 6
307214 1103107701 EN Presence detector theronda S360-101 DE WH 2080565 theronda S360-101 DE GR 2080566 theronda S360-101 AP WH 2080555 theronda S360-101 AP GR 2080556 1. Product characteristics 4 2. Safety
More informationBC-R10 Series. Burner Controllers
No. CP-SS-1885E BC-R10 Series Burner Controllers Summary BC-R10 Series burner controllers are combustion safety controllers specifically designed for batch operation (systems which start and stop at least
More informationUser Manual 120/240/300 Outdoor Motion Detector
User Manual 120/240/300 Outdoor Motion Detector Swiss Garde 4000 Warning! - Any work on the main power supply must only be completed by trained specialists. - The product must be installed in accordance
More informationE340 BOILER CONTROL INSTALLATION MANUAL
E-3451 JUNE 1999 E340 BOILER CONTROL INSTALLATION MANUAL DESCRIPTION The E340 Boiler Room Control is a microprocessor-based Boiler Management System designed to interface with existing Fireye D Series
More informationPANTHER. Condensate removal pump Installation and operating guide
PANTHER Condensate removal pump Installation and operating guide The PANTHER is a self-contained condensate removal system for use directly inside trunking and highwall-mount air conditioners.the small
More informationOperating Instructions. For. Alarm Control Module. Model SSR 500
SSR 500 LEVEL CONTROL RELAY MODULE Operating Instructions For Alarm Control Module Model SSR 500 SSR Operation Instructions Rev. 1 Jan 01 Page 1/7 1. Note Please read and take note of these operating instructions
More informationLubrication cycle IP Enclosure Rating. 110 VAC, 220/230 VAC (50/60 Hz) Alarm Fault Relay Contacts. IP-55 (Liquid tight connector)
SMAC Controller Industrial Lubrication Systems Operation The SMAC Controller is a multi-purpose programmable controller used with industrial lubrication systems. Controller settings are saved whenever
More informationMO n : 12JMC rév A
CTT8 MO n : rév A Page 2 / 18 MODIFICATIONS Rev. Description Date Checked by Approuved by Z Creation 2012/02/12 JMC LA A First issue 2012/02/14 JMC LA INDEX Page 3 / 18 GENERALITY 4 INTRODUCTION 4 ACCESSORIES
More informationDIGITAL ALARM UNIT Model ALU-AP
DIGITAL ALARM UNIT Model ALU-AP Description Digital alarm unit ALU-AP has the following characteristics: 1. Operates in MASTER or SLAVE mode. 2. It can connect with other devices through a RS485 network
More informationLa Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual
La Marche Manufacturing Company www.lamarchemfg.com Option 16 Series Digital Combined Accessory Package Installation and Operation Manual This manual is subject to change without notice. You may obtain
More informationSigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009
Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009 CONTENTS Contents... Page Safety & Installation...2 Installation - continued...3
More informationI/O ZONE 560/583 AND OPERATION MANUAL
UPM I I/O ZONE 560/583 INSTALLATION AND OPERATION MANUAL 1 UNIT PROTECTION MODULE HARDWARE OPERATION IMPORTANT: This manual is for UPM board part numbers 8733 800 259. See controller label as shown in
More informationModel A2100 Series Annunciator
Seekirk Model A2100 Series Annunciator Applications: For usage within transformers, switchgear, breakers and/or within any processing equipment or control room applications either attended or unattended
More informationANALOGUE ADDRESSABLE FIRE CONTROL PANELS FIREQUEST FAMILY. Section 6 Trouble Shooting Issue 1.1
FIREQUEST FAMILY ANALOGUE ADDRESSABLE FIRE CONTROL PANELS FIREQUEST FAMILY Section 6 Trouble Shooting Issue 1.1 FireQuest - trading as Luminos Lighting Ltd Unit F1, Grafton Way Basingstoke, Hampshire RG22
More informationCU-IQ MANUAL 1. DESCRIPTION Radio Control Panel CU-IQ
1. DESCRIPTI CU-IQ MANUAL The small control panel CU-IQ is one component of the new ICAS IQ wireless system. IQ System is an intelligent radio system, which works at 868 MHz frequency band. The IQ System
More informationDryer Controller M720
User Manual Dryer Controller M720 Hardware version 2.00 Software version 2.00 Manual M720 Dryer controller Page 1 of 60 Document history Preliminary version: - Created in April, 2009 Hardware Version 2.00,
More information03.03.mmm REV.2 09/01
03.03.mmm REV.2 09/01 Via del Lavoro, 80-40056 CRESPELLANO (Bologna) ITALY - ( +39 051/733.383 - Fax. +39 051/733.620 P.O. BOX, 150-40011 ANZOLA EMILIA (Bologna) - ITALY Power Factor Regulator cosφ V A
More informationFlame Safeguards LFE10. Building Technologies HVAC Products
7 71 Flame Safeguards LAE LFE Flame safeguards for burners with intermittent operation The LAE is used for the supervision and indication of oil flames The LFE is used for the supervision and indication
More informationCarbon Monoxide (CO) detection system
1973 Carbon Monoxide (CO) detection system CARB MOXIDE Presentation DESIGN GUIDE AND SELECTI OF CO SYSTEMS The basic purpose of a CO detection system, resides in ensuring a minimum conditions of sanitation
More informationNZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL
NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL Document No...G108WO1.DOC Serial No... Issue Date...17 th SEPTEMBER 1999 Software Version...1.4 APPROVED TO: NZS 4512:1997 AS/NZS 3548:1992 Fire Alarm
More informationInstallation Guide for AL800UL-ADA. NAC Power Extender. Rev
Installation Guide for AL800UL-ADA NAC Power Extender Rev. 090500 Overview: The Altronix AL800UL-ADA is an extremely cost effective 8 amps voltage regulated remote power supply /battery charger. The AL800UL-ADA
More informationRooftop Thermostat Controller Specification and Installation Instructions. Model TRT2422
ºF / º C Rooftop Thermostat Controller Model TRT2422 Description The TRT2422 is a combination controller and thermostat with a built-in scheduler, which is designed for simple and accurate control of single
More informationIncident resolution workflow
Incident resolution workflow Code Alarm Reason for shutdown Description 0001H Grid frequency Grid frequency out of The measured grid frequency is outside the specified limits out of range range 0002H Grid
More informationGeneral Alarm System. User Manual. Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND
General Alarm System User Manual Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0) 1282 717171 www.protec.co.uk sales@protec.co.uk Document Revision Details
More information3. Proper use. 4. Function. 1. Product characteristics. 2. Safety. Function description. Channel A light. Motion detector
307021 3. Proper use EN Motion detector themova P360-100 UP WH 1030600 themova P360-100 UP GR 1030601 The motion detector is intended for interior. The motion detector is eclusively intended for the use
More information