Using Non-Twisted Flat Cable in Analogue Addressable Retrofits

Size: px
Start display at page:

Download "Using Non-Twisted Flat Cable in Analogue Addressable Retrofits"

Transcription

1 Using NonTwisted Flat Cable in Analogue Addressable Retrofits Pertronic Industries NonTwisted Cable in AA Systems v

2 When upgrading a fire detection system from conventional detection to a Pertronic analogue addressable system, it may be desirable to reuse existing cabling. This avoids the expense of purchasing and installing new, twistedpair cable for AA signalling circuits. This document discusses the issues that should be considered when deciding whether or not to use existing, nontwisted twocore cable in Pertronic analogue addressable ( AA ) signalling circuits. Typical Existing Cabling A typical conventional detector zone would have nontwisted (flat) twocore cable linking the fire alarm control panel to one or more detectors. Usually, each zone is a spur, with the panel at one end. Typically the far end is fitted with an end of line termination. Typical Conventional Detection Zones 10k 10k 10k 10k FIGURE 1: Typical arrangement of conventional detection zones. Analogue Addressable Options Conventional detection zones can often be upgraded to analogue addressable (AA) by replacing the conventional detectors, detector bases, and other devices with AA devices. Analogue addressable fire system devices include smoke detectors, heat detectors, manual call points, monitor modules, loop responders, and loop relays. A mixture of device types may be connected to a single signalling circuit. For more information on the system capabilities, please refer to the datasheets and technical manuals for Pertronic analogue addressable panels. There are two popular configurations: Conventional zones may be connected as analogue addressable loops, or Conventional zones may be converted to analogue addressable spurs A single system may include a mix of loops and spurs. Fault (defect) supervision with Pertronic analogue addressable control panels works normally on both loop and spur circuits, because the control panel regularly polls each individual loop device and registers a fault (defect) if any device fails to respond when polled. Pertronic Industries Page 2

3 Loop Configuration Existing conventional detection zones may be converted to Pertronic AA loops. Each loop will consist of a singlepair cable connected from the loop driver A terminals, to each analogue addressable device in turn, and finally back to the loop driver B terminals. The loop is effectively driven from both ends. This means that an open circuit fault (defect), anywhere on the loop, will not affect its operation. In a typical loop conversion, multiple conventional zones are connected in series to create a continuous AA signalling circuit. The two ends of this circuit are connected to the loop driver outputs of Pertronic analogue addressable fire alarm control panel such as the Pertronic F220, F120A, or F100A. An analogue addressable loop isolator module should be installed in series with each link connecting one former conventional zone to another. This ensures that a shortcircuit in any zone will not affect normal operation of the other zones on the AA loop. Existing Cable Pertronic Loop Driver Twisted Cable Loop 1 Loop 2 FIGURE 2: Two conventional detection zones (red & black) connected as an analogue addressable loop, using a length of twistedpair cable (red & white). Note the isolator (see text). Spur Configuration A single spur may be connected directly to an AA loop driver output. No special interface is needed, provided that the AA loop driver output is not connected to any other signalling circuit. In this case, the A and A terminals (respectively) must be linked to the B and B terminals, otherwise the panel will show a loop fault (defect). (See Figure 3) Signalling Circuit Loop 1 A B FIGURE 3: Loop driver output connections for a singlespur Pertronic AA signalling circuit. When multiple spurs are to be connected to one AA loop driver output, each spur is connected to a spur isolator such as the Pertronic AA Board 8spur (8SAAIB). This module is connected to the panel s loop driver output, as shown in Figure 4. The isolator board ensures that a shortcircuit on any individual spur will not affect normal operation of any other spur. A spur may include only one detection zone. This is because an open or short circuit at any device will isolate all downstream devices from the analogue addressable loop. An analogue addressable spur does not need an endofline termination. Pertronic Industries Page 3

4 Spur Configuration Cont d Spur 1 Spur8 Spur 1 Spur 8 8 WAY AA ISOLATOR Loop In Loop Out Pertronic Loop Driver Loop 1 A B Loop 2 A FIGURE 4: ultispur system using the Pertronic 8SAAIB. B General Requirements As with any other fire detection and alarm system, an installation using nontwisted cable must meet all applicable regulatory requirements. There are specific issues that must be taken into consideration when reusing existing nontwisted cable in AA circuits: Circuit length, and Interference immunity. Both loop and spur configurations are subject to the same design requirements, because the Pertronic AA signalling circuit is designed to function normally with only one end driven. Circuit Length The maximum length of a Pertronic analogue addressable spur or loop is subject to two factors: Series cable resistance, and The positions and current consumption of loop devices. The maximum endtoend cable resistance must not exceed 50 ohms. ax = 50Ω Twin Cable Temporary ShortCircuit Pertronic Industries Page 4

5 This leads to the following upper limits on the endtoend spur or loop length: Conductor Size aximum Spur or Loop Length 2.5 mm² 2500 metres 1.5 mm² 1500 metres 1.0 mm² 1000 metres Upper Limits on Loop Length In addition, Pertronic Industries provides a webbased calculator for checking loop configuration. This is available online at: Interference In most installations, nontwisted cable will provide satisfactory protection against interference. To prevent interference, the signalling line circuit should be separated from systems that may produce, or be susceptible to, electromagnetic interference. Pertronic Industries recommend that nontwisted cable used for AA signalling circuits should be kept at least 25 mm away from other cables. Long parallel runs should be avoided. Nontwisted cable should not be used in AA detection circuits if the detection cable will run alongside, and close to, other cables that may produce, or be susceptible to, interference. Earth leakage will increase susceptibility to interference. The resistance between each conductor and the system earth (ground) should be > 50 kω. Conclusion The reuse of nontwisted cable in Pertronic AA conversions has been wellproven in many projects throughout Australasia. When used according to the guidelines in this document, nontwisted cable should not lead to problems with electromagnetic interference. If there is any doubt about the applicability of flat, nontwisted cable in a proposed analogue addressable system, please consult Pertronic Industries. Pertronic Industries Page 5

6 Pertronic Industries

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

ZIOU/230 - MAINS IO INSTRUCTION MANUAL Description ZIOU/230 - MAINS IO INSTRUCTION MANUAL The Mains IO Modules are fully monitored loop powered devices which permit the interfacing of third party equipment with the Fire Alarm Control panel

More information

Input/Output Modules Data Sheet

Input/Output Modules Data Sheet Input/Output Modules Data Sheet The wide range of input and output modules available from NOTIFIER delivers exceptional flexibility to a NOTIFIER fire detection and alarm system. Using these modules enables

More information

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note Product Overview: The Pertronic F4 Remote LED Mimic / Aux Relay Module F4-RMAX is an optional extra for the Pertronic F4 conventional 4-zone fire alarm panel. This board enables the fire alarm panel to

More information

Interface Modules for SENTRI

Interface Modules for SENTRI EQUIPMENT INTERFACED Data and Installation Interface s for SENTRI Low voltage (LV) / SEN-INT-INPUT 1- Interface (low voltage) SEN-INT-OUTPUT 1- & 1- Interface (low voltage) SEN-INT-4IO # 4- / Interface

More information

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL PRODUCT Specification FEATURES Designed To Meet The Requirements Of EN54 Expandable From 1 To 5 Loops As Standard A Variety Of Networking Options

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

TECHNICAL DATA SHEET ADDRESSABLE FIRE ALARM SYSTEMS FIRE ALARM CONTROL PANEL LF-6100 A 1/2

TECHNICAL DATA SHEET ADDRESSABLE FIRE ALARM SYSTEMS FIRE ALARM CONTROL PANEL LF-6100 A 1/2 FEATURES: Closed Loop Design (Class A Wiring) Microprocessor Based System Intelligent Distributed System Structure Quick Response Time Fire Alarm in

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS)

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0)

More information

Sita200plus. 200detectors. Single loop analogue addressable System

Sita200plus. 200detectors. Single loop analogue addressable System Single loop analogue addressable System Fast short circuit isolator in every device 15 combinations of smoke & heat detection modes Loop length up to 2km long with spurs INTELLIGENT FIRE TECHNOLOGY A D

More information

IntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide

IntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide IntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide Product Overview The IntelliKnight 5820XL is an intelligent addressable fire alarm control panel designed for flexibility and reliability.

More information

LF /2. Fire Alarm Control Panel. Features:

LF /2. Fire Alarm Control Panel. Features: LF-6100 1/2 Fire Alarm Control Panel Features: Microprocessor Based System Intelligent Distributed System Structure Quick Response Time Fire Alarm in less than 1 Second Capacity of 200/500 Addressable

More information

Addressable Loop Modules

Addressable Loop Modules Addressable Loop s Introduction FC10MIM The FC10MIM Mini Input module is designed to monitor fire contacts, such as extinguishing system control, ventilation control, fire door control etc. The module

More information

D326A/D334A/D339A. Installation Instructions. Point Contact Modules

D326A/D334A/D339A. Installation Instructions. Point Contact Modules D326A/D334A/D339A EN Installation Instructions Point Contact Modules D326A/D334A/D339A Installation Instructions 1.0 Description Notice Use these instructions to install the D326A, D334A, and D339A Point

More information

SINGLE MONITORED INPUT UNIT BN-303

SINGLE MONITORED INPUT UNIT BN-303 SINGLE MONITORED INPUT UNIT BN-303 Interactive fire detection system Product Datasheet Features Interactive For interfacing switches and 3rd party detectors with relay outputs to Autronica s interactive

More information

Alarmline Linear Heat Detection

Alarmline Linear Heat Detection Alarmline Linear Heat Detection Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by - Friction heat & sparks - Overheating of

More information

F220-B6PS/M. Installation Guide. Addressable Detector Bases

F220-B6PS/M. Installation Guide. Addressable Detector Bases F220-B6PS/M EN Installation Guide Addressable Detector Bases F220-B6PS/M Installation Guide 1.0 Overview 1.0 Overview These instructions cover the installation of the B6PS/M Addressable Detector Bases

More information

LOG BOOK & CERTIFICATES

LOG BOOK & CERTIFICATES M+48 LOG BOOK & CERTIFICATES. FIRE ALARM SYSTEM SUMMARY: FIRE ZONE INFORMATION ZONE NO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41

More information

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops... GUIDE MANUAL INDEX 1- Introduction...5...5...6 4- The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops...7 4.2- The Control Panel 4 and 8 Loops...9 5- Installation Guide...10 5.1- Pre-Installation

More information

SC-9 Controller INSTALLATION AND OPERATING INSTRUCTIONS. SC-9 Applications CONTENTS

SC-9 Controller INSTALLATION AND OPERATING INSTRUCTIONS. SC-9 Applications CONTENTS SC-9 Controller MODULAR BOILER CONTROLLER SERIES INSTALLATION AND OPERATING INSTRUCTIONS SC-9 Applications Space heat systems with outdoor reset Constant temperature setpoint control Any of these in combination

More information

Vigilant MX4428 Fire Alarm System

Vigilant MX4428 Fire Alarm System Vigilant MX4428 Fire Alarm System The Vigilant MX4428 is an intelligent fire alarm system, incorporating Tyco MX TECHNOLOGY to provide advanced, analogue addressable fire detection. It features support

More information

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 8-24 ZONE CONVENTIONAL FIRE ALARM PANEL LOG BOOK & CERTIFICATES

PREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 8-24 ZONE CONVENTIONAL FIRE ALARM PANEL LOG BOOK & CERTIFICATES 8-24 ZONE CONVENTIONAL FIRE ALARM PANEL LOG BOOK & CERTIFICATES Approved Document No: GLT.MAN-113 It is recommended that this LOG BOOK be maintained by the responsible person(s) on site, who should ensure

More information

LH-20S (RESISTANCE ALARM SYSTEM)

LH-20S (RESISTANCE ALARM SYSTEM) PORTABLE MOISTURE DETECTOR LH-20S (RESISTANCE ALARM SYSTEM) USER MANUAL levr Ver. 2.6 1. Moisture Measurements of Pre-Insulated Heating Pipelines with the Resistance Alarm System For the purpose of measurement,

More information

Linear Heat Detection Cable - Monitor

Linear Heat Detection Cable - Monitor /-Z/-G Digital Interface with Distance Display The module is designed to monitor a length of Digital (Non-resettable) Linear Heat Detecting Cable () for both Fire condition, and Fault status (open circuit).

More information

Clarification. Summary of Changes. Summary of Changes. Alan Cavers Area Manager Fire & Security Systems Group

Clarification. Summary of Changes. Summary of Changes. Alan Cavers Area Manager Fire & Security Systems Group Summary of Changes CAN/ULC-S524-06 Installation of Fire Alarm Systems Alan Cavers Area Manager Fire & Security Systems Group Course Title Rev Date: Summary of Changes Correct Deficiencies noted CAN/ULC-S524-01

More information

DOMESTIC HEATING CONTROLS ARE EASY PART 1 - THE BASICS

DOMESTIC HEATING CONTROLS ARE EASY PART 1 - THE BASICS DOMESTIC HEATING CONTROLS ARE EASY PART 1 - THE BASICS Today s inescapable need to improve energy efficiency in UK homes has brought installers many opportunities to make extra earnings through the upgrading

More information

These instructions detail procedures to follow in order to avoid damage to equipment.

These instructions detail procedures to follow in order to avoid damage to equipment. D326A, D334A, D339A Point Contact Modules Installation Guide 1.0 Notice These instructions are for the installation of the D326A, D334A and D339A Point Contact Modules in an analog system controlled by

More information

FC330A-ECO1 Auto-addressing analogue 1-Loop fire detection panel

FC330A-ECO1 Auto-addressing analogue 1-Loop fire detection panel FC330A-ECO1 Auto-addressing analogue 1-Loop fire detection panel Synova Commissioning in no time thanks to automatic address allocation Auto-addressing makes setting dip switches, punch cards, etc. unnecessary

More information

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel Synova TM Commissioning in no time thanks to automatic address allocation Auto-addressing makes setting dip switches unnecessary Automatic

More information

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL Document No...G108WO1.DOC Serial No... Issue Date...17 th SEPTEMBER 1999 Software Version...1.4 APPROVED TO: NZS 4512:1997 AS/NZS 3548:1992 Fire Alarm

More information

30.45 Electric Release PDRP-2001

30.45 Electric Release PDRP-2001 The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or

More information

Print Specification. Publication. Instructions. Specific requirements. General requirements

Print Specification. Publication. Instructions. Specific requirements. General requirements Print Specification Publication GSA-CC1 Single Input Signal Module Installation Sheet P/N P-047550-1802-EN REV 04 ISS 23JUN15 Instructions This page is the print specification for the publication. It is

More information

ALARMLINE ANALOGUE Linear Heat Detection System

ALARMLINE ANALOGUE Linear Heat Detection System ALARMLINE ANALOGUE Linear Heat Detection System Alarmline Analogue cable senses temperature variations by continuously monitoring the resistance of specially doped Negative Temperature Coefficient (N.T.C.)

More information

INPUT / OUTPUT MINI MODULES

INPUT / OUTPUT MINI MODULES INPUT / OUTPUT MINI MODULES APPLICATION The Addressable Control and Monitor mini modules are the latest technology for a loop powered module. Installed on the same loop with other devices such as detectors

More information

Product Guide MAN7030-2

Product Guide MAN7030-2 MAN7030-2 Product Guide Ampac addressable range expansion Wireless Minimsies disruption to building and occupants Enables rapid retrofit or temporary solution AS4428-9 Dual batteries for enhanced integrity

More information

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS HVAC Upgrades Phase 2 Page 1 of 5 Part 1 General 1.1 SUMMARY.1 Section Includes:.1 Materials and installation for fire alarm systems upgrades..2 Audible signal devices..3 End-of-line devices..4 Sustainable

More information

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998

More information

Consultant Specification AGILE Wireless Fire Detection System

Consultant Specification AGILE Wireless Fire Detection System Contents Scope of Work... 2 The EN54 Part 2 & 4 Fire System... 2 Standards... 2 Wireless Intelligent Photoelectric Smoke Detector Specification... 4 Wireless Intelligent Thermal Heat Detector Specification...

More information

DUAL MONITORED INPUT/OUTPUT UNIT BN-305

DUAL MONITORED INPUT/OUTPUT UNIT BN-305 DUAL MONITORED INPUT/OUTPUT UNIT BN-30 Interactive fire detection systems Product Datasheet Features Interactive For interfacing and controlling external units to Autronica s interactive fire detection

More information

IFD-E Flame Detector User Manual

IFD-E Flame Detector User Manual IFD-E Flame Detector User Manual 2 Hochiki Europe (UK) Ltd General Description The flame detector is designed for use where open flaming fires may be expected. It responds to the light emitted from flames

More information

Control Panels. Control Panels for Commercial Applications. Control panels provide the central processing

Control Panels. Control Panels for Commercial Applications. Control panels provide the central processing Control Panels Control Panels for Commercial Applications Control panels provide the central processing and logic for an integrated system. In a typical system, there are four major functions: inputs,

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

Interface and EOL Modules 8

Interface and EOL Modules 8 Interface and EOL Modules Interface Modules Series 420 25 Interface Modules Series 100 291 EOL Modules 293 254 Interface and EOL Modules Interface Modules Series 420 Interface Modules Serie 420 Interface

More information

FDMM01S - FDMM02 - FDMM10- FDMM11S FDMM12 - Input / output mini modules

FDMM01S - FDMM02 - FDMM10- FDMM11S FDMM12 - Input / output mini modules Application The Addressable Control and Monitor mini modules are the latest technology for a loop powered module. Installed on the same loop with other devices such as detectors and manual call points,

More information

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

Combining Old and New Systems in Existing Buildings and Other Retrofit Tales. By Paul Jewett CFAA Technician Number 11

Combining Old and New Systems in Existing Buildings and Other Retrofit Tales. By Paul Jewett CFAA Technician Number 11 Combining Old and New Systems in Existing Buildings and Other Retrofit Tales By Paul Jewett CFAA Technician Number 11 Combining Old and New Systems in Existing Buildings and Other Retrofit Tales Disclaimer

More information

Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator

Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator TECHNICAL GUIDE Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator The XPlorer Range XPlorer is a new range of analogue addressable detectors and interfaces developed for all who

More information

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE General Description This guide provides a summary for installing and configuring the Centaur TM Cube Slave Alarm Signalling Equipment

More information

THE INTELLIGENCE BEHIND THE MOST INNOVATIVE FIRE DETECTION SYSTEMS

THE INTELLIGENCE BEHIND THE MOST INNOVATIVE FIRE DETECTION SYSTEMS AU TO C A L L CO N T RO L PA N E L S THE INTELLIGENCE BEHIND THE MOST INNOVATIVE FIRE DETECTION SYSTEMS THE SMART CHOICE, NO MATTER WHAT YOUR ROLE When it comes to fire systems, no choice is more important

More information

Multi-Application Peripherals and Accessories

Multi-Application Peripherals and Accessories ON UL, ULC Listed FM Approved MultiApplication Peripherals and Accessories Communicating Devices Communications Individually Addressable Devices FEATURES Individually addressable communications over a

More information

Booster Power Supply Manual

Booster Power Supply Manual Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation

More information

IFD-E Flame Detector User Manual

IFD-E Flame Detector User Manual IFD-E Flame Detector User Manual 2 Hochiki Europe (UK) Ltd General Description The flame detector is designed for use where open flaming fires may be expected. It responds to the light emitted from flames

More information

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63 Fire Extinguishing Control Panel FS5200Е INSTRUCTION MANUAL Revision 8/01.17 Instruction Manual Page 1 1. 2. 3. 4. 4.1. 4.2. 4.2.1. 4.2.2. 4.2.3. 4.2.4. 4.2.5. 4.2.6. 4.2.7. 4.2.8. 4.2.9. 4.2.10. 4.2.11.

More information

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

ICS Regent. Fire Detector Input Modules PD-6032 (T3419) ICS Regent Fire Detector Input Modules (T3419) Issue 1, March, 06 Fire detector input modules provide interfaces for 16 fire detector inputs such as smoke detectors, flame detectors, temperature detectors,

More information

2000 Series Sensors Installation Guide

2000 Series Sensors Installation Guide 2000 Series Sensors Installation Guide Revision 5.1: August 2000 (unreleased) Aritech is a trademark of SLC Technologies B.V. COPYRIGHT SLC Technologies B.V. 2000. All rights reserved. SLC Technologies

More information

Addressable NAC Output Module D327A

Addressable NAC Output Module D327A Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,

More information

POL-200-TS User Manual

POL-200-TS User Manual User Manual POL-200-TS ANALOGUE LOOP VERIFICATION TOOL 1/16 Security Information Several damage! Please, before to connect any external cable, ensure that loop cable has been disconnected from panel loop

More information

Radiant Thermostat 519

Radiant Thermostat 519 106103_dl_02 Radiant Thermostat 519 Installation & Operation Manual Introduction The Radiant Thermostat 519 accurately controls the room and/or floor temperature for a hydronic heating zone using Pulse

More information

REPAIR INSTRUCTIONS. TUMBLE DRYER Vented WTA34.. / WTA35..

REPAIR INSTRUCTIONS. TUMBLE DRYER Vented WTA34.. / WTA35.. REPAIR INSTRUCTIONS TUMLE DRYER Vented WTA34.. / WTA35.. I. SAFETY INFORMATION Page 1 II. OPERATION Page 1 III. DESCRIPTION OF FUNCTION / TECHNICAL INFORMATION Page 2 IV. CONSUMPTION RATES / ENERGY REQUIREMENT

More information

GE Security. FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring

GE Security. FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring GE Security FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring Version v2-2 / September 2005 Aritech and Kilsen are GE Security brands. http://www.geindustrial.com/ge-interlogix/emea

More information

CODESEC FIRE ALARM SYSTEMS. security technologies

CODESEC FIRE ALARM SYSTEMS. security technologies CODESEC FIRE ALARM SYSTEMS security technologies AA402 ADRESSABLE FIRE ALARM CONTROL PANEL AA402 Electronic Addressable Intelligent Fire Alarm Control Panel Onboard one loop, 250 nodes per loop, Metal

More information

PSN-1000 & PSN 1000(E) Installation Manual

PSN-1000 & PSN 1000(E) Installation Manual PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com

More information

OPERATION / INSTALLATION

OPERATION / INSTALLATION OPERATION / INSTALLATION & PROGRAMMING MANUAL AFP-2800 LCD-80 Fire Alarm Panel Revision 1.01 November 16, 2004 NSW (Head Office) 7 Columbia Court Norwest Business Park Baulkham Hills NSW 2153 Ph: (02)

More information

SIGA-CC1 Single Input Signal Module Installation Sheet

SIGA-CC1 Single Input Signal Module Installation Sheet SIGA-CC1 Single Input Signal Module Installation Sheet Personality codes Use the personality codes described below to configure the SIGA-CC1 module. See Table 1 for listing information Table 1: Personality

More information

AU MX Digital Loop Card Installation Instructions

AU MX Digital Loop Card Installation Instructions 4100-6077AU MX Digital Loop Card Installation Instructions Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS - Follow the instructions in this installation manual. These instructions must be followed

More information

MINERVA MZX125 Digital Addressable Fire Detection System

MINERVA MZX125 Digital Addressable Fire Detection System DATASHEET MINERVA MZX125 Digital Addressable Fire Detection System The Minerva MZX125 is a highly featured digital addressable panel with a comprehensive but easy to operate user interface. The system

More information

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2 DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2 Interactive fire detection systems Product Datasheet Features Interactive For interfacing and controlling external units to Autronica s interactive fire detection

More information

ADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE

ADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE K3179V2 2/11 Rev. A ADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE FEATURES The ADEMCO 4208SNF Universal Class A Module can be used in either of two different applications.

More information

DS7400Xi Addressable Control/ Communicator

DS7400Xi Addressable Control/ Communicator DS7400Xi Addressable Control/ Communicator DS7400Xi DS7400Xi-EXP 110VAC operation 220VAC operation Remotely Programmable WDSRP (Windows Detection Systems Remote Programming Software), allows the systems

More information

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option SM3000 Videographic Recorder User Guide (RTU) Communications Option ABB The Company We are an established world force in the design and manufacture of instrumentation for industrial process control, flow

More information

ID3000 intelligent. fire alarm panel

ID3000 intelligent. fire alarm panel ID3000 intelligent fire alarm panel features certified to EN54 parts 2 and 4 expandable from 2 to 8 loop capacity up to 198 per loop (99 sensor and 99 modules) 255 fire zones per panel modular design supports

More information

561-MB256 plus. Intruder alarm control panel. Performance features

561-MB256 plus. Intruder alarm control panel. Performance features 561-MB256 plus Intruder alarm control panel The intruder alarm control panel 561-MB256 plus is designed for use in private and commercial zones and is highly suitable for setting up medium to large-sized

More information

FEC403EN Installation Manual

FEC403EN Installation Manual FEC403EN Installation Manual P/N 10-4101-501-2FC1-01 ISS 22JAN15 Copyright Trademarks and patents Manufacturer 2015 UTC Fire & Security. All rights reserved. The FEC403EN name and logo are trademarks of

More information

ACHIEVING REDUNDANT INTRINSICALLY-SAFE FIELDBUS SEGMENTS FOR FISCO & ENTITY DEVICES

ACHIEVING REDUNDANT INTRINSICALLY-SAFE FIELDBUS SEGMENTS FOR FISCO & ENTITY DEVICES Foundation Fieldbus End Users Council Australia Inc. P.O. Box Z5546 Perth AUSTRALIA 6831 ACHIEVING REDUNDANT INTRINSICALLY-SAFE FIELDBUS SEGMENTS FOR FISCO & ENTITY DEVICES Mike O Neill Director, MooreHawke

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

UEI-1 UNIVERSAL END-OF-LINE / ISOLATOR TESTER

UEI-1 UNIVERSAL END-OF-LINE / ISOLATOR TESTER UEI1 UNIVERSAL ENDOFLE / ISOLATOR TESTER With Easy Testing Technology STALLATION & OPERATG STRUCTIONS These instructions are provided to ensure compliance with the installation requirements of NFPA72 (National

More information

Honeywell Combination Fire & Burglary Control Panel

Honeywell Combination Fire & Burglary Control Panel Honeywell Combination Fire & Burglary Control Panel Agenda VISTA 128FBPT Fire & Burglary Design & Scalability of VISTA Fire TURBO (FBPT) Honeywell Fire & Intrusion panel USP 5800 Series Wireless Sensor

More information

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable Protec Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE Protec Protec Algo-TecTM 6100 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL

More information

ID50series. intelligent fire alarm panels

ID50series. intelligent fire alarm panels ID50series intelligent fire alarm panels features LPCB approved to EN54 parts 2 and 4 One loop capacity (99 sensors and 99 modules) 16 fire zones, 16 non fire zones Supports NOTIFIER advanced range of

More information

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description MODUL-R FIRE ALARM CONTROL PANELS MR-2900/MR-2920 Addressable Fire Alarm Control Panels Description MR-2900 Fire Alarm Control Panel The MR-2900 fire alarm system control unit is the heart of a sophisticated

More information

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features 990-052, Issue 6 20 March 2006 ID50 Series Single Loop Intelligent Fire Alarm Panels Section: Intelligent Fire Alarm Panels GENERAL The NOTIFIER ID50 series single loop intelligent fire alarm panels, has

More information

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5 Construction Standards Page 1 of 5.1 General Description.1 The University requires that all new fire alarm system control panel, components, and devices, as required for the project, be Secutron 2900 Series

More information

FC700A Fire detection control unit

FC700A Fire detection control unit FC700A Fire detection control unit Synova 4-16 Loop analogue addressable control panel 128 devices per loop (SynoLOOP) and up to 1000 devices per panel Up to 24 collective lines for Synova TM 600 serie

More information

Installation & Operation Manual

Installation & Operation Manual 519_D Radiant Thermostat 519 03/13 Zoning Replaces: New Installation & Operation Manual Introduction The Radiant Thermostat 519 accurately controls the room and/or floor temperature for a hydronic heating

More information

SC-3 Controller INSTALLATION AND OPERATING INSTRUCTIONS FOR GAS-FIRED, OIL FIRED AND DUAL FUEL HOT WATER HEATING PLANTS. SC-3 Applications CONTENTS

SC-3 Controller INSTALLATION AND OPERATING INSTRUCTIONS FOR GAS-FIRED, OIL FIRED AND DUAL FUEL HOT WATER HEATING PLANTS. SC-3 Applications CONTENTS FOR GAS-FIRED, OIL FIRED AND DUAL FUEL HOT WATER HEATING PLANTS SC-3 Controller MODULAR BOILER CONTROLLER SERIES INSTALLATION AND OPERATING INSTRUCTIONS SC-3 Applications Space Heat Systems With Outdoor

More information

R A D I O N I C S. READYKEY K2015A Alarm Event Manager. Installation Data Sheet. Description

R A D I O N I C S. READYKEY K2015A Alarm Event Manager. Installation Data Sheet. Description R A D I O N I C S READYKEY K2015A Alarm Event Manager Installation Data Sheet READER CONTROLLER INPUTS INPUTS RLY 8 RLY 7 RLY 6 RLY 5 RLY 4 RLY 3 RLY 2 RLY 1 8 Supervised Inputs (Normally Open or Normally

More information

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above Surveyor Excel Fire Alarm Control Equipment Network version Programming Manual VERSION 14.0 and Above MASTER MANUAL Drawing S1606. PCB Layout guide for XLK range of control panels FCPXLK-2/4/6/8 & FCPXLK2/4/6/8TW

More information

Scope. Warning sounders except specific requirements. Intercom Systems for Emergency Purposes. Sound Systems for Emergency Purposes

Scope. Warning sounders except specific requirements. Intercom Systems for Emergency Purposes. Sound Systems for Emergency Purposes Scope Section 6 covers all Control and Indicating Equipment including Local Alarm systems. Section 6 also covers all detectors and input/output devices, including Occupant Warning sounders except specific

More information

Fire Alarm Panels. Product Manual.

Fire Alarm Panels. Product Manual. Fire Alarm Panels Product Manual The operation and functions described in this manual are available from Software Version 5000-050-04 onwards. Specifications: Item Specification Details Part Number: Mx-5100

More information

1) This manual covers 4400, 5400 and 6400 fire alarm systems. The differences are described in the appropriate sections.

1) This manual covers 4400, 5400 and 6400 fire alarm systems. The differences are described in the appropriate sections. ISSUES ISSUE DATE DETAILS OF CHANGE CHANGED BY 1 16/02/00 ORIGINAL ISSUE - 2 16/01/01 TABLES 2 & 3 UPDATED, ADDED TABLE 4 PWD 3 12/09/01 ADDITIONAL INFORMATION PWD 4 29/11/02 TABLES 2, 3 & 4 UPDATED &

More information

CZ-6A Six Zone Interface Module

CZ-6A Six Zone Interface Module INSTALLATION AND MAINTENANCE INSTRUCTIONS CZ-6A Six Zone Interface Module 658 Kitimat Rd. Unit #6 Mississauga, Ontario L5N T5-800-SENSOR, FAX: 905-8-077 www.systemsensor.ca SPECIFICATIONS Normal Operating

More information

Installation & Operation Manual

Installation & Operation Manual Installation & Operation Manual Radiant Thermostat 519 519_D 06/16 Zoning Replaces: 03/13 Introduction The Radiant Thermostat 519 accurately controls the room and/or floor temperature for a hydronic heating

More information

Model 17A00 Expansion Enclosure

Model 17A00 Expansion Enclosure HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number

More information

GE Security EST Fire & Life Safety. Sophisticated io-series. Intelligent Life Safety Systems for small to mid-size buildings

GE Security EST Fire & Life Safety. Sophisticated io-series. Intelligent Life Safety Systems for small to mid-size buildings GE Security EST Fire & Life Safety Sophisticated io-series Intelligent Life Safety Systems for small to mid-size buildings io Series Supports Signature Series intelligent detectors and modules Electronic

More information

BAC-4000 Series AppStat

BAC-4000 Series AppStat BAC-4000 Series AppStat Description The KMC AppStat combines the power of a space mounted equipment controller with the convenience of built-in temperature, humidity and motion sensors. The controllers

More information

SOUNDER CONTROL MODULE SCM-AS4

SOUNDER CONTROL MODULE SCM-AS4 1 of 9 INTRODUCTION DESCRIPTION The forms part of the Nittan (UK)'s SENSORTEC-ANALOGUE range of Analogue Addressable Devices. This module is designed to control a group of bells or sounders from the detection

More information

Building Technologies

Building Technologies Building Technologies Synova TM fire protection The FC700A network system. The Synova TM network system. Synova TM detectors Attractive, environmentally aware design Individual identification of detectors

More information

IGD.CO.UK

IGD.CO.UK APPLICATION DATA SHEET S p e c i f i c a t i o n 2 SO22 WWW.-..UK Control Systems Transmitters Sensors Accessories TOCSIN 700+ D e t e c t o r Website: C o n t r o l P a n e l - Wall mounting or 19 Rack

More information

Different types of Fire Alarm System

Different types of Fire Alarm System Different types of Fire Alarm System Conventional Fire System Generally comes with Zones. Each zone can have max 20 detectors. Addressable Fire Alarm System This comes in loops. Different manufacturer

More information