Electric Heat Inspection Form Revised September 2012
|
|
- Julianna Wheeler
- 5 years ago
- Views:
Transcription
1 Client name: Address: Primary Heat Source: Auxiliary Heat Application: Heat Pump Information: Equipment Information Electric Electric Heat Inspection Form Revised September 2012 Audit Existing furnace New Furnace Job/Client Information Client/Job number: Phone: Home: Work: Cell: Heat Pump Electric furnace Baseboard Gas Oil Other: If there are gas or oil appliances, include appropriate forms Cable ceiling Up flow Down flow Horizontal Site- built Mobile home Make: Serial: Furnace Information: Make: Serial: Model: Btuh: Model: Btuh/Kw: Coil Information(if coil is separate from furnace, e.g.. heat pump with gas or oil furnace) Make: Model: Serial: Electric Furnace Inspection Service disconnect/breaker in unit, or within reach of unit Breakers/fuses correct size Conductor(s) correct size Terminals/connections tight and good condition Wiring dark, discolored or burnt Unit properly grounded All elements operational Sequencer/heat relay/board operating properly All elements on for 5 minutes Blower on with first element, off with or after last Element Amperage: Auditor: E1: E2: E3: E4: E5: Tech: E1: E2: E3: E4: E5: Final: E1: E2: E3: E4: E5:
2 Airflow Calculation CFM = Btuh output (temperature difference x 1.08) Final airflow cfm must be calculated after duct sealing is performed Inspection Technician Final Total amps of elements : amps amps amps Voltage applied: volts volts volts Multiply volts and amps 0 watts 0 watts 0 watts Multiply watts x Btuh 0 Btuh 0 Btuh Supply air temperature: F F F Return air temperature: F F F Temperature rise 0 F Temp rise x F Divide Btuh output by the adjusted temp rise. cfm. cfm. cfm Minimum airflow for heat pump system 400 cfm per ton Blower, Coil, Ducts and Electric Water Heater Blower clean Filter clean, supported and user friendly Coil and condensate drain pan clean Secondary drain pan installed if above finished ceiling Condensate drain trapped and terminated properly Ducts outside thermal/pressure boundary sealed Ducts outside thermal/pressure boundary insulated Water heater level and free of leaks T & P correct and properly piped Water temperature set to 120 F or less Record water temperature Baseboard and Ceiling Cable Heat All base board heaters and ceiling cable heaters operational All base board heaters clean and free of obstructions All base board covers in place Properly sized breaker panel and circuit breakers F F F
3 Heat Pump Inspection Heat pump level and elevated above snow grade Entire vapor line insulated Outdoor coil clean Terminals, connections, wiring tight and good condition Crankcase heater or trickle circuit functional System wired to stage auxiliary heat correctly Reversing valve operational Outdoor metering device Expansion TEV valve Fixed orifice Fixed restrictor R410A Refrigerant: Indoor metering device Expansion valve Fixed restrictor R22 System tested in heating or cooling? Heat Pump Operation Only EPA Section 608 CFC certified technicians are permitted to attach gauges to systems Heat AC Heat AC Heat AC Outdoor temperature F F F Inspection Liquid line pressure N/A psig psig N/A psig Saturation temperature N/A F F N/A F Liquid line temperature N/A F F N/A F Calculated subcooling N/A F N/A F Required subcooling NA N/A F F N/A F Low pressure Suction pressure N/A psig psig N/A psig Saturation temperature N/A F F N/A F Suction line temperature N/A F F N/A F Calculated superheat N/A F N/A F Required superheat psig NA N/A F F Line temperaturen/a F Dry bulb return air High pressure Wet bulb r/a (superheat charging) Indoor air temperatures F F F NA N/A F F N/A F Supply air temperature F F F Temperature rise or drop(dry bulb) 0 F If in heating mode, meets factory charging specifications Meets expected indoor temp rise ± 2 F: (ODA F x.33)+ 9 F Meets expected indoor temp drop(14 F to 22 F dry bulb) Technician Heat pump indoor temp rise when 32 F outdoor = F, add/subtract 1 rise for every 3 ± outside Final
4 Mechanical Work Completed 1 Y N 2 Y N 3 Y N 4 Y N 5 Y N 6 Y N 7 Y N 8 Y N 9 Y N 10 Y N Additional Comments: Audit performed by: Mechanical work performed by: Mechanical inspection performed by: Final inspection performed by: Agency reviewer:
5
6 Worst Case Draft Testing Turn all combustion appliances off or to pilot Check for clean furnace filter or remove filter Close all exterior doors and windows Close all interior doors (except for rooms with exhaust and no supply) Open all supply registers (except supplies in CAZ) Close all fireplace and wood stove dampers Turn on dryer and all exhaust fans (clean or remove lint trap) Set- up blower door to exhaust 300 cfm for each working fireplace Set- up pressure to read CAZ pressure with reference to outside Is there a door between the CAZ and the rest of the house? Is there a forced air blower on the heating equipment? Yes Yes No No Determine Worst Case Configuration Open Closed Open Closed Open Closed Fan off Fan off Fan off Fan on Fan on Fan on Outdoor temp. Outdoor temp. Outdoor temp. Draft Test Water Heater ( Test) Fire the water heater Establishes flow in the vent within 5 seconds? Spillage disappears within 2 minutes? Record draft pressure after 5 minutes "w.c "w.c "w.c Record CO in flue gas after 5 minutes / ppm / ppm / ppm Draft Test Furnace ( Test) Fire the Furnace: Establishes flow in the vent within 5 seconds? Is there flame interference when blower starts? Spillage disappears within 2 minutes? Record draft pressure after 5 minutes "w.c "w.c "w.c Record CO in flue gas after 5 minutes ppm ppm ppm CO in each cell on draft hood furnace Re- test draft on water heater "w.c "w.c "w.c Did the heating appliance operation cause spillage or a reduction in draft on water heater? Measure Temperature Rise Supply air temperature deg. deg. deg. Return air temperature deg. deg. deg. Temperature rise deg. deg. deg. Is the temp. rise within manufacturer specs.?
Indiana WX Oil Furnace Inspection Guide
Indiana WX Oil Furnace Inspection Guide Client: Job # : Address: Phone: Client Interview: Oil Dealer: Date of last service: Comments/Billing information: Standard Inspection / Clean and Tune Follow-up:
More informationSA Series Start up Report
SA Series Start up Report Important To ensure warranty validation and continued customer satisfaction, complete this form and return it to Desert Aire immediately after start-up. Validation of this report
More informationMBPA Home Performance FIELD DATA COLLECTION FORM
MBPA Home Performance FIELD DATA COLLECTION FORM Customer Information Test Date: Name Address City State Zip Phone: ( ) Email: Electric Provider Heating Fuel Provider Account Number Account Number Customer
More informationSecond Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments:
Second Revision No. 3-NFPA 31-2015 [ Section No. 10.5.1 ] 10.5.1* Oil burners, other than oil stoves with integral tanks, shall be provided with some means for manually stopping the flow of oil to the
More informationState of ALASKA, Weatherization Assistance Program. Technical Support Document. Combustion Safety
5.3.1A(2) Page 1 of 2 State of ALASKA, Weatherization Assistance Program Technical Support Document Combustion Safety This document is intended to support in detail the Combustion Safety Test Report. The
More informationM2 Series Startup Form
M Series Startup Form Job Name: Date: Address: Model Number: Serial Number: Tag: Startup Contractor: Address: Phone: Pre Startup Checklist Installing contractor should verify the following items.. Is there
More informationINSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER
ASPEN MANUFACTURING 373 ATASCOCITA RD. HUMBLE, TX 77396 TEL (281) 441-6500 FAX (281) 441-6510 > INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER IMPORTANT: "The
More informationObjectives. Home Performance Diagnostics with the House of Pressure (Part 1) How can Pressure effect Building Performance?
Home Performance Diagnostics with the House of Pressure (Part 1) Objectives Learn the basic rules of air flow and differences Begin to be able to recognize building problems related to airflow and differences
More informationINSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER
INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER IMPORTANT MASSAGE TO INSTALLER: "The United States Environmental Protection Agency ("EPA") has issued various regulations regarding the
More informationTASKS REGARDING COMBUSTION AIR
TASKS REGARDING COMBUSTION AIR DETERMINE IF THERE IS ENOUGH COMBUSTION AIR FOR THE TYPES OF APPLIANCES IN THE CAZ Use one of two methods, depending on appliance type and whether or not you have a blower
More informationTable of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)
Table of Contents Refrigeration Cycle Service Procedures Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Solving Problems Identifying Low System Charge (9-11) Identifying High
More informationInspection Checklist Mechanical Rough in
Property Owner Name: Property Address: Permit Number: Inspectors Name: Review Date: Permits and Plans 1. Job address is posted in a visible location. (R319.1) 2. Permit and approved plans are on site and
More informationInstructors: Contact information. Don Reynolds Doug McGee Factory Tech Support
Contact information Instructors: Don Reynolds 616-560-9903 Doug McGee 517-294-3932 Factory Tech Support 888-593-9988 Product Improvements for 2017 Todays Objectives Job Site Information Sheets Low Ambient
More informationService Step by Step Trouble-Shooting Check-List
WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS FCP2400D FCP3000D FCP3600D FCP4200D FCP4800D FCP6000D FCP2400C FCX2400C FCP3000C FCP3600C FCX3600C FCP4200C FCP4800C FCX4800C FCP6000C FCX6000C Require AMF001NHA Accessory No
More informationRetrofit Installer-Mechanical
Retrofit Installer-Mechanical Lesson Plan Section 1: Gas FurnaceFundamentals Learning Objectives By attending this session, participants will: Know the components of a gas furnace Understand the basic
More informationRheem High Efficiency Modulating EcoNet Enabled Air Handler
Air Handlers Series Rheem High Efficiency Modulating EcoNet Enabled Air Handler - Series Constant CFM (ECM) Electronic Expansion Valve (EEV) Efficiencies up to 20.5 SEER The is EcoNet Enabled: This allows
More informationCOMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES*
COMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES* *Vented appliances refer to natural draft appliances equipped with a barometric draft regulator or Category I appliances equipped with a draft
More informationMechanical Appliance and Equipment Inspection Checklist
34 2015 IRC Performing Residential Mechanical s Mechanical Appliance and Equipment Checklist Inspect Mechanical Appliance and Equipment Comments / I. Identify possible mechanical appliance and equipment
More informationTECHNICAL GUIDE MODELS: P*DH GAS-FIRED CONDENSING / HIGH EFFICIENCY DOWNFLOW / HORIZONTAL FURNACES 91 AFUE DESCRIPTION WARRANTY FEATURES
036-1354-001 Rev. D (110) Heating TECHNICAL GUIDE MODELS: P*DH GAS-FIRED CONDENSING / HIGH EFFICIENCY DOWNFLOW / HORIZONTAL FURNACES 91 AFUE NATURAL GAS 37-111 MBH OUTPUT Air Conditioning EFFICIENCY RATING
More informationINSTALLATION INSTRUCTIONS
2011 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS 13HPP UNITS PACKAGED HEAT PUMP UNIT (2 5 TONS) 506750 01 06/11 Supersedes 03/11 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE
More informationLiebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet
The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Installation
More informationRCTA Horizontal Evaporator Coil Installation Instructions
RCTA Horizontal Evaporator Coil Installation Instructions General: Rheem horizontal evaporator coils are designed for use with condensing units or heat pump units. These instructions are intended as a
More informationUSER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS.......................... 2 INTERMITTENT IGNITION DEVICE...........
More informationService Guide. Service Guide NATIONAL COMFORT PRODUCTS GAS & ELECTRIC MODELS. 2nd Edition
2nd Edition Service Guide Thru-the-Wall Packaged Heating & Cooling Units Service Guide GAS & ELECTRIC MODELS NATIONAL COMFORT PRODUCTS HEATING & A/C EQUIPMENT National Comfort Products A Division of National
More informationTECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)
DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of refrigerant-22 for storage
More informationMontana Weatherization Program WEATHERIZATION FINAL INSPECTION REPORT (Mobile Homes) Client Name Address Contact phone # Inspector Name and QCI#
EA #. Date Priority # HEALTH & SAFETY Hazardous Material Assessment Electrical Repairs Performed by Licensed Professional Solid Fuel Burning Appliance CO Detection/Warning, Occupant Education, # Installed.
More informationBUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS
BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used by
More informationUSER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY...................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS.......................... 2 INTERMITTENT IGNITION DEVICE..........
More informationFor an administrative fee of $9.97, you can get an un-locked, printable version of this book.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. For an administrative fee of
More informationM2 Series Startup Form
M Series Startup Form Job Name: Date: Address: Model Number: Serial Number: Tag: Startup Contractor: Address: Phone: Pre Startup Checklist Installing contractor should verify the following items.. Is there
More informationHVAC Equipment Access Equipment Location
City of Lancaster- Building Department 121 East Chestnut Street, Suite 102, Lancaster, Ohio 43130-3825 (740) 687-6649, Fax (740) 681-5030 Web site: www.ci.lancaster.oh.us/dept/building HVAC Heating, Ventilating,
More informationINSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER
INSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER MODEL (INCLUDING HEATER MODEL #) SERIAL # INSTALLER INSTALLATION DATE These instructions should
More informationEnergy Saver 101: Home Energy Audits
Energy Saver 101: Home Energy Audits Take the first step to improving your home s energy efficiency: get a home energy audit. What is a home energy audit? A home energy audit helps you pinpoint where your
More informationSERVICE FACTS WARNING M801-SF-1C. Gas Furnaces Upflow & Downflow Induced Draft 1 Stage Heat Models: DISCONNECT POWER BEFORE SERVICING M801P040AU24AA
SERVICE FACTS Gas Furnaces Upflow & Downflow Induced Draft Stage Heat Models: M80P00AU2AA M80P060AU2AA M80P060AU36AA M80P080BU36AA M80P080BU8AA M80P00BU36AA M80P00CU8AA M80P00CU60AA M80PDU60AA M80P0DU60AA
More informationLiebert Fin/Tube Condenser Warranty Inspection Check Sheet
The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Installation
More informationMortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS
Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS INTRODUCTION Please note that HUD Manufactured Home Construction and Safety Standard Section 3280.714, paragraph (a) and subparagraph
More informationRESNET National Conference New Orleans, LA. February 16, 2009 Presented by Rich Moore Invisible Energy Denver, CO
RESNET National Conference New Orleans, LA. February 16, 2009 Presented by Rich Moore Invisible Energy Denver, CO rgalenmoore1@msn.com This session will address the basics of combustion and the latest
More informationCombustion Safety. RESNET Conference San Antonio, TX February 27, Presented by Rich Moore Lightly Treading Energy & Design Denver, CO
Combustion Safety RESNET Conference San Antonio, TX February 27, 2006 Presented by Rich Moore Lightly Treading Energy & Design Denver, CO Goals of this session Recognize the need for combustion safety
More informationINSTRUCTIONS! DO NOT DISCARD!
INSTRUCTIONS! DO NOT DISCARD! CAUTION! Do NOT install where injury might occur due to Moving parts, Sharp corners, Hot surfaces or electrical components d N0417 Page 1 of 10 INSTALLATION INSTRUCTIONS CAUTION
More informationSnuggPro DATA COLLECTION FORM
SnuggPro DATA COLLECTION FORM Section 1: General Information Trade Ally: Trade Ally Telephone: Trade Ally Email: Auditor Name: Auditor Telephone: Auditor Email: Home Owner Name: Home Owner Telephone: Home
More informationTECHNICAL GUIDE HIGH EFFICIENCY, STANDARD ECM VERTICAL WALL MOUNT AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: EWX*18-36
TECHNICAL GUIDE HIGH EFFICIENCY, STANDARD ECM VERTICAL WALL MOUNT AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: EWX*18-36 Due to continuous product improvement, specifications are
More informationLiebert CRV Warranty Inspection Check Sheet
The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Date of Installation
More informationCommercial High-Efficiency Condensing Units
FORM NO. A22-193 REV. 3 Supersedes Form No. A22-193 Rev. 2 Commercial High-Efficiency Condensing Units 15 & 20 TON MODEL [52.8 & 70.3 kw] 10 & 12.5 TON MODEL [35.2 & 44.0 kw] 10 THROUGH 20 NOMINAL TON
More informationSEVEN STEPS TO EFFECTIVE PRE- SEASON COOLING CHECKUPS
SEVEN STEPS TO EFFECTIVE PRE- SEASON COOLING CHECKUPS by Dennis Kalchuk While temperatures are still tolerable, it's time to prepare your customers' systems to deal with the blasts of summer heat and humidity
More informationATTACHMENT D #1 - HVAC (OIL) - SINGLE FAMILY DWELLINGS Category C: OIL
LINE ITEM # ATTACHMENT D #1 - HVAC (OIL) - SINGLE FAMILY DWELLINGS Category C: OIL LINE ITEM DETAIL Labor Material FURNACE COMPONENTS 1 Furnish & Install Sight-Impaired Thermostat For Heating and Cooling
More informationBPI ANALYST ENVELOPE AUDIT FIELD EXAM CHECKLIST
BPI ANALYST ENVELOPE AUDIT FIELD EXAM CHECKLIST 1. Pre-Inspection Homeowner Interview (3 minutes) A. Turn on & zero CO Meters. Determine ambient CO : B. Record Outside Temperature: C. Homeowner interview:
More informationCased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit
18-AD32D1-3 Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit Upflow models: 4PXCAU24BS3HAA 4PXCBU24BS3HAA 4PXCBU30BS3HAA 4PXCCU30BS3HAA 4PXCBU36BS3HAA
More informationVNE GAS FURNACE 2- STAGE VARIABLE SPEED UPFLOW/HORIZONTAL
VNE GAS FURNACE 2- STAGE VARIABLE SPEED UPFLOW/HORIZONTAL 25--21--65 Representative photo only, some models may vary in appearance. MANUFACTURED FOR NATURAL GAS CONVERTIBLE TO (LP) PROPANE GAS NOTE: These
More informationCBX32MV (HFC-410A) SERIES UNITS
Service Literature Corp. 005-L2 Revised November 5, 202 (HFC-40A) SERIES UNITS (icomfort-enabled) NOTICE A thermostat is not included and must be ordered separately. The Lennox icomfort thermostat must
More informationEnergyMeasure HOME DATA COLLECTION FORM
EnergyMeasure HOME DATA COLLECTION FORM Section 1: General Information Customer Name: Site ID: Assessment Date: Street Address: City: State: Zip Code: Alternate Address: City: State: Zip Code: Telephone
More informationHVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS
HVAC Systems What the Rater Needs to Know in the Field This presentation used CASE* studies from the following *CASE Copy And Steal Everything HVAC Systems - What the Rater Needs to Know in the Field This
More informationINSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA
TXV Coils for Manufactured Housing EMA NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance,
More informationRheem High Efficiency Two-Stage EcoNet Enabled Air Handler
Air Handlers Rheem High Efficiency Two-Stage EcoNet Enabled Air Handler RHT- Series Constant Torque (ECM) Electronic Expansion Valve (EEV) Efficiencies up to 17 SEER The RHT is EcoNet Enabled: This allows
More informationWineZone Ceiling Mount Ductless Split 15
WineZone Ceiling Mount Ductless Split 15 Requires an HVAC technician to install and charge with R-22 refrigerant. Easy to install. Unit plugs into wall outlet. Industrial grade unit for longer life. Indoor
More informationBCE4 PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER WITH VARIABLE SPEED APPLICATION INSTALLATION CABINET COMPONENTS CONTROLS WARRANTY
PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER WITH VARIABLE SPEED FORM NO. -100 (11/2015) APPLICATION 2-5 ton sizes Upflow, horizontal, and downflow capable Sequenced for demand management External access
More informationRheem High Efficiency Two-Stage EcoNet Enabled Air Handler
Air Handlers Rheem High Efficiency Two-Stage EcoNet Enabled Air Handler RHT- Series Constant Torque (ECM) Efficiencies up to 17 SEER The RHT is EcoNet Enabled: This allows the RHT to directly communicate
More informationSunny Hills. HVAC Maintenance Checklist Template. conducted for. Conducted on 31 Oct :40 PM. Prepared by Jon Nieve
HVAC Maintenance Checklist Template conducted for Sunny Hills Conducted on 31 Oct 2018 03:40 PM Prepared by Jon Nieve Location 102 S Mendel St, Fort Stockton, TX 79735, USA Completed on 31 Oct 2018 04:11
More informationM3RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace
TECHNICAL SPECIFICATIONS M3RL Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 90+ AFUE Input 60,000 & 80,000 Btuh The high efficiency downflow gas furnace is especially
More informationCOPPER INSERT INSTALLATION INSTRUCTIONS, USE AND CARE GUIDE
COPPER INSERT INSTALLATION INSTRUCTIONS, USE AND CARE GUIDE DESIGNER SERIES MODELS Model Width CFM Type of Motor & Blower VSL430 BF 28-3/8" * Remote VSL436 BF 34-3/8" * Remote VSL442 BF 40-3/8" * Remote
More informationHIGH EFFICIENCY TWO-STAGE ECONET ENABLED AIR HANDLER
FORM NO. HFJ-6 Supersedes Form No. PTZ-789 HIGH EFFICIENCY TWO-STAGE ECONET ENABLED AIR HANDLER Features The FH**TTT is EcoNet Enabled: This allows the FH**TTT to directly communicate with the EcoNet Smart
More informationDesiccant Dehumidifier
Since the 1950s Desiccant Dehumidifier Dry Spaces With NO Added Heat BMIL Technologies, LLC 4915 Arendell St., #313 Morehead City, NC 28557 PH 252-727-0994 FAX 252-727-0996 WWW.BMIL.COM Product Description
More informationPL Series Premier Indoor Plenum Coils
IM-PLC-0667392-04 April 2016 PL Series Premier Indoor Plenum Coils Installation Instructions GENERAL ADP evaporator coils are designed for use with condensing units or heat pump units. These instructions
More information1-1/2 THRU 2-1/2 TONS SPLIT SYSTEM FWM Series
1-1/2 THRU 2-1/2 TONS SPLIT SYSTEM FWM Series Rated in accordance with ARI Standard 210. Certification applies only when used with proper components as listed with ARI. FEATURES Designed as an upflow indoor
More informationProduct Data. 95% AFUE Single Stage Furnace Upflow / Downflow / Horizontal. ama ! WARNING
DIRECT OR NON -DIRECT VENT 4-WAY MULTIPOISE CONDENSING GAS FURNACE 95% AFUE Single Stage Furnace Upflow / Downflow / Horizontal FLEXIBILITY S Dual certified venting (1 or 2 pipes) Direct Vent furnace S
More information40 SERIES GAS BURNER CONTROLLER TROUBLESHOOTING Before a new controller is installed in gas burner the following tests must be performed. If not damage to controller may occur and void warranty! Step 1.
More informationSpecial Topics on Residential HVAC
Special Topics on Residential HVAC by Armin Rudd USDOE Building America Program for EEBA Conference 2002 Phoenix, Arizona 10 October 2002 Page 1 of 25 Two Main Topics: 1. Cyclical trade-offs between building
More informationINSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES
C US INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES Made in the USA by: Goodman Manufacturing Company, L.P. I0-240B 2550 North Loop West, Suite 400, Houston, TX 77092 www.goodmanmfg.com
More informationINSTALLATION INSTRUCTIONS TXV Coils EBD, EBA
TXV Coils EBD, EBA These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system to operate
More informationIntegrated Ventilation System
Integrated Ventilation System For use with models: IVS1, IVSR1, IVS2, IVSR2 Installation Instructions Part No. 65278 Rev. K Table of Contents Important Safety Instructions... 1 Important Information About
More informationOIL-FIRED CENTRAL FURNACE
OIL-FIRED CENTRAL FURNACE Installation, Operation, and Service Manual With Users Information Section Models: CSHB60-90XE CSHB60-90XP c WARNING: Do NOT store or use gasoline or other flammable vapors and
More informationISERIES VERTICAL AHU ENGINEERING SPECIFICATIONS
ISERIES VERTICAL AHU ENGINEERING SPECIFICATIONS BULLETIN 20-131.001 Page 1 Copyright 2017 Unico Inc. TABLE OF CONTENTS APPLICATIONS... 3 CABINET CONSTRUCTION... 3 FEATURES AND CONTROLS... 3 DIMENSIONAL
More informationPVE SERIES POWER VENTER SYSTEM MANUAL
PVE SERIES POWER VENTER SYSTEM MANUAL Contents Page I. Typical Venting System Components 2 II. System Operation 3 III. Power Venter Sizing 3,4 IV. Installation Safety Instructions 5,6 V. Installation of
More informationPOWER VENTER. Model: PVE Series
POWER VENTER Model: PVE Series CONTENTS Typical Venting System Components... System Operation... Power Venter Sizing... Installation Safety Instructions... Installation of Power Venter... Connecting Power
More informationCooling Capacity CFM in. w.c. (125 Pa)
93% AFUE, Single Stage, PSC Gas Furnace EASIER TO SELL 93% AFUE, all models all positions F9MES 50 Hz Product Specifications Certified to leak 2% or less of nominal air conditioning CFM delivered when
More informationRESNET National Conference New Orleans, La. February 15, 2009 Presented by Rich Moore Invisible Energy Denver, CO
RESNET National Conference New Orleans, La. February 15, 2009 Presented by Rich Moore Invisible Energy Denver, CO rgalenmoore1@msn.com Effective insulation and air sealing treatments can make a huge difference
More informationReference Guide REFRIGERATION INFORMATION
REFRIGERATION INFORMATION SPLIT TROUBLESHOOTING AC GUIDE Reference Company name Technician name Date Customer name Indoor wet bulb Indoor dry bulb Outdoor dry bulb Design suction pressure on charging chart
More informationCWA4 Chilled & Hot Water Fan Coil
CWA4 Chilled & Hot Water Fan Coil 4-Pipe Heat & Cool Fan Coil 24,000-60,000 BTUH 259 CWA4 NOMENCLATURE BREAKDOWN 4-Pipe Heat & Cool Multiposition Fan Coil Nominal BTUH 24=24,000 36=36,000 48=48,000 60=60,000
More informationAnticipating Depressurization Issues Due to Air Tightness and Ventilation Needs
Anticipating Depressurization Issues Due to Air Tightness and Ventilation Needs Rebecca Olson Neighborhood Energy Connection Duluth Energy Design Conference February 26 th, 2013 Duluth, MN Learning Objectives
More informationClearFire - Hydronic Startup Report
ClearFire - Hydronic Startup Report Date Serial No. THIS FORM IS FOR MODEL CFC / CFW CLEARFIRE BOILERS Customer s Name Location Model Design Pressure Working Pressure Rated Input (nameplate rating) BTU/hr
More informationINSTALLATION INSTRUCTIONS
2016 Lennox Industries Inc. Dallas, Texas, USA THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE WARNING This product contains a chemical known to the State of California to cause cancer,
More information80% and 95% furnace models feature aluminized steel heat exchangers to conduct heat quickly and increase durability.
FURNACES The Ameristar line of heating and cooling products offer you flexible and affordable options for HVAC equipment replacement. The Ameristar product line should complement the national brand you
More informationINSTALLATION, OPERATION & MAINTENANCE MANUAL INDIRECT GAS-FIRED DUCT FURNACE
INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR COMMERCIAL APPLICATIONS IN-KI INDOOR SERIES RT-NO ROOFTOP SERIES WWW.RENEWAIRE.COM IMPORTANT SAFETY INFORMATION WARNING WARNING Risk of fire or explosion!
More informationSeries 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.
MISSION CRITICAL Air Conditioning Systems Series 9 Commissioning Checklist S9-CL2017.doc ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 S9-CL2017.doc Commissioning
More informationSTART UP FORM PACKET
START UP FORM PACKET Condensing Unit and Evaporator DIVISIONS OF RAE CORPORATION 4492 Hunt St. - Pryor, OK 74361 - (918) 825-7222 - Fax (918) 825-6366 www.rae-corp.com RAE Corporation Condensing Unit
More informationDOMESTIC WATER HEATER OIL FIRED
DOMESTIC WATER HEATER OIL FIRED Models : CMO32-II CMO32-II-R CMO50-II CMO32-II & CMO32-II-R INSTALLER / SERVICE TECHNICIAN: USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION AND SERVICING OF THE
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS 13CHPX SERIES UNITS PACKAGED HEAT PUMPS (2 5 TONS) 505,136M (38152A071) 12/09 Supersedes 05/09 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING Improper installation,
More information28 1/2"* 72.4 cm. (*28 1/2 " to include hinges.) 41 3/4" 106 cm. 27" 68.6 cm. 28 1/2"* 72.4 cm. (includes hinges.) 28 1/2"* 41 3/4" 106 cm
Commercial Single Load Dryers 28 1/2"* 72.4 cm PRODUCT DIMENSIONS (*28 1/2 " to include hinges.) 28 1/2"* 72.4 cm (*28 1/2 " to include hinges.) Models MDE/MDG21PD MDE/MDG21PS MDE/MDG21PR MDE/MDG21PN 43
More informationInstallation Instructions
Installation Instructions PAM3 SERIES PACKAGE AIR CONDITIONERS TABLE OF CONTENTS SAFETY LABELING AND SIGNAL WORDS... 2 UNIT DIMENSIONS... 3 SAFE INSTALLATION REQUIREMENTS... 3 LOCATING THE UNIT... 3 CLEARANCES...
More informationTECHNICAL GUIDE MODELS: P*UR GAS-FIRED CONDENSING / HIGH EFFICIENCY UPFLOW FURNACES 92 AFUE DESCRIPTION WARRANTY FEATURES Rev.
036-1349-001 Rev. A (30) Heating TECHNICAL GUIDE MODELS: P*UR GAS-FIRED CONDENSING / HIGH EFFICIENCY UPFLOW FURNACES 9 AFUE NATURAL GAS 37-130 MBH OUTPUT Air Conditioning EFFICIENCY RATING CERTIFIED R
More informationCOMBUSTION SAFETY BASICS
COMBUSTION SAFETY BASICS Joe Konopacki Why Combustion Safety? Hydrocarbon fuels are hazardous Explosion or fire is possible Poor indoor air quality Exhaust byproducts are harmful or deadly Safe and efficient
More informationInternet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #
INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #238-39387-00 THIS INSTRUCTION SUPPLEMENT IS ONLY INTENDED TO GIVE INSTALLATION INSTRUCTIONS AND INFORMATION RELATED TO THE INDUCED
More informationML180UH SERIES GAS FURNACE WARNING WARNING
2017 Lennox Industries Inc. Dallas, Texas, USA 506525-01 04/2017 Supersedes 10/2015 ML180UH SERIES GAS FURNACE Improper installation, adjustment, alteration, service or maintenance can cause property damage,
More informationCWA2 Chilled Water Fan Coil With or Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000-60,000 BTUH
CWA2 Chilled Water Fan Coil With or Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000-60,000 BTUH 233 CWA2 NOMENCLATURE BREAKDOWN 2-Pipe Heat/Cool with Electric Heat Multiposition Fan Coil Nominal
More informationEL SERIES INSTALLATION INSTRUCTIONS
EL SERIES INSTALLATION INSTRUCTIONS Restrictor Orifice Coils These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be
More informationMIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/
1 of 3 Cooling Capacity [Btuh] 24,800 * Condensing Unit SEER: 13.0 ** Condensing Unit CFM: 1,600 Condenser Fan No./Type: 1/CENTRIFUGAL Diameter x Width [in]: 10x10 Drive: Adjustable Belt Motor HP: 0.5
More informationPAJ3. Product Specifications
13 SEER, R 410A PACKAGE AIR CONDITIONER FOR MANUFACTURED HOUSING, RESIDENTIAL, AND LIGHT COMMERCIAL APPLICATIONS 2 5 TONS Single Phase, 208/230 V, 60 Hz BUILT TO LAST, EASY TO INSTALL AND SERVICE Compact,
More informationInstallation, Operation and Service Manual
Installation, Operation and Service Manual KLF-100 85% + EFFICIENCY OIL FIRED LOWBOY FURNACE INSTALLATIONS MUST MEET ALL LOCAL AND FEDERAL CODES THAT MAY DIFFER FROM THIS MANUAL Please read the manual
More informationPreventative Maintenance Tables
Preventative Maintenance Tables Table of Contents I. Table : Gas Fired Domestic Hot Water Heater II. III. IV. Table : Circulating Pump Table : Convectors Table 4: Grille and Diffusors V. Table 5: Unit
More informationSH, VH & SE Models. SH, VH & SE Series Heat & Energy Recovery Ventilators IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT
SH, VH & SE Series Heat & Energy Recovery Ventilators IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT CAUTION - Before installation, careful consideration must be given to how this system will
More information