Field Setting for Smart IOT Inverter Outdoor Unit
|
|
- Thomas Blankenship
- 5 years ago
- Views:
Transcription
1 1/9 Field Setting for Smart IOT Inverter Outdoor Unit
2 2/9 1 Default display LED on main control board can display the operating state of outdoor unit (ODU). 7 segment display instructions SEG1: Normally blank, but it displays codes 1~9 accordingly if there is damaged sensor and demand control requirement. State Codes Description 0 IOT sofeware is updating 1 High pressure sensor fault backup state 2 Low pressure sensor fault backup state 3 Discharge temperature sensor(td) fault backup state 4 IPM module temperature sensor(tf) fault backup state 5 Ambient temperature sensor(ta) fault backup state 6 Condenser coil sensor(th) fault backup state 7 Suction temperature sensor(ts) fault backup state 8 Liquid temperature sensor(tl) fault backup state 9 Demand response state SEG2: Normally blank, but it will display code accordingly as below if outdoor unit is running under limited condition. Protection State Codes Description 0 Running under high pressure limit 1 Running under low pressure limit 2 Running under discharge temperature limit 3 Running under IPM module temperature limit 4 Running under compressor current limit SEG3: It displays outdoor unit s operation mode. State Codes Description 0 Standby without running signal (Y signal=off) 1 Ready to start after receiving running signal (Y signal=on) *Note 2 Cooling mode 3 Heating mode 4 Oil return 5 Defrost 6 Forced defrost 7 Test mode 7 (high frequency) 8 Test mode 8 (low frequency) Note: Compressor waits 6 minutes to restart.
3 3/9 2 Setting by dip switches Outdoor unit s functions can be applied by pushing buttons and dialing switch on the job site. The following table shows the setting contents for SW1 switch. ON DIP Dip switch Description NO. Setting item State Content 1 Reserved - - ON 2 or 4Ton 2 Capacity selection *1 OFF(factory) 3 or 5Ton 3 AC only/heat pump selection ON AC only OFF(factory) Heat pump 4 Response for IOT ON Do not respond to IOT command OFF(factory) Respond to IOT command *1 Keep the ODU s dip switch when 5Ton matches with 2 or 3 Ton indoor unit for hyper heating. 3 Setting by pushing button Query and setting operation can be done by pushing buttons on PC board. Off Blinking On BS1 BS2 BS3 Push buttons BS1: Menu button BS2: UP button BS3: Spot check and confirm button Mode types 1 Default mode(push BS3) Used to spot check system operating states. (e.g. high pressure, compressor speed and error code, etc.) 2 Setting mode (push BS1 for 5 seconds) Used to set special functions. 3 Query setting mode (short push BS1) Used to query current setting mode.
4 4/9 Mode change procedure Push BS1 button, the modes can be changed as follows. Push and hold the BS1for 5 seconds. Default mode (Use BS3 button to query operating states.) Push BS1 once Setting mode Query setting mode Symbol selection (BS2 button) Setting item selection (BS2 button) Contents display Symbol selection (BS2 button) Contents display Push BS1 once
5 5/9 4 Default mode System state can be showed on the 7 segments display of outdoor unit. can get code number and corresponding detailed information with an interval of one second. Example: Code number Detailed information No. Number content Example Description (Round numbers) Default Refer to default display instructions 902 9:Demand 0:Running under high pressure 2:Cooling mode AC only or heat pump and outdoor unit C:AC only(h: heat pump) 01- C3 capacity 3:3Ton(2,3,4,5Ton) 02- Sub cooling 10 10F 03- Superheat 18 18F 04- Frequency of compressor 56 56rps 05- Electric expanse valve opening pls 06- Step of fan 8 8th Step 07- Low pressure (LP sensor) psig 08- High pressure (HP sensor) psig 09- TA temperature 95 95F 10- TS temperature 70 70F 11- TD temperature F 12- TH temperature 80 80F 13- TL temperature 70 70F 14- TF temperature F 15- Target evaporation temperature(tes) 43 43F 16- Current evaporation temperature(te) 43 43F 17- Target condensation temperature(tcs) F 18- Current condensation temperature(tc) F 19- Compressor current A 20- Less refrigerant signal 0 0: none 1: level 1 2: level Main software version A01 A01 version 22- Inverter software version b01 b01 version 23- Current fault E1 Display up to 5 *1 24- Last fault F1 --: none 25- The fault before last fault F2 --: none *1 When multi-error codes exist at the same time, with an interval of 1 second, each code will be displayed one by one.
6 5 Setting mode Hold BS1 button for 5 seconds to enter the parameter setting interface. Setting can be done from cloud if the unit is equipped with IOT gateway. The latest setting will be taken as the final one. Symbol Function Item Description n00 n01 n02 n03 n04 n05 n06 n07 n08 Mode choice Forced heating stop when ambient temperature is lower than specify value. Changing to heat by gas furnace or boiler instead in cold winter. Outdoor unit D/W terminal outputs 24V at defrost operation or forced heating stop. Outdoor unit D/W terminal outputs 24V when ambient temperature is lower than specify value for auxiliary heating resource to start. Defrost mode setting Silent mode setting Night time setting- start time Night time setting- end time Forced defrost 1 Dehumidification *1 2 High capacity mode *2 0 TA<-22F Forced heating stop 1(factory) TA<-3F Forced heating stop 2 TA<5F Forced heating stop 3 TA<10F Forced heating stop 4 TA<15F Forced heating stop ON (24VAC output) 1 OFF (No 24VAC output) TA<15F (24VAC output) 1 TA<10F (24VAC output) 2 TA<5F (24VAC output) 3 TA<-3F (24VAC output) 4 OFF (No 24VAC output) 0 Easy to defrost for high humidity area 1(factory) Standard mode 2 Hard to defrost for low humidity area None silent mode 1 Silent mode(level 1) 2 Super silent mode(level 2) 3 Night silent mode(level 1) 4 Night super silent mode(level 2) 0 17:00 1(factory) 18: : : :00 0 5:00 1(factory) 6:00 2 7:00 3 8:00 4 9:00 OFF 1 ON *3 *Note 1.The evaporation temperature of indoor coil can lower down to 28F. 2.The evaporation temperature of indoor coil can lower down to 28F, condensate temperature can go up to 122F. 3.System enters defrost after finishing the start up control. 6/9
7 Query Setting mode example 7/9 Check current silent mode setting (n05) Step1 Push BS1 to enter query mode. Step2 Push BS2 to select item (n05 for this case). Step3 to check current setting (n05 = 1). Step4 and go to Step 2 for other setting check. Push BS1 to return. Example for mode choice (n00) setting How to choose mode? Step1 Push and hold BS1 for 5 seconds. Step2 Push BS2 to select item (Factory default is n00). Step3 to enter sub-item setting. Step4 Push BS2 to change subitem(n00 = 1). Step5 to save setting. Step6 Push BS1 to return.
8 8/9 Example for n02 & n03 setting Y signal from thermostat Heat Pump Outdoor Unit Air Handler with Electric Heater R C W1 G W O Y D/W terminal outputs 24V is available when Y signal = ON. C Auxiliary heating call from outdoor unit to air handler with electric heater or gas furnace, or other third-party heat source using 24V control signal. n02 Outdoor unit D/W terminal outputs 24VAC at defrost operation or forced heating stop(n01). 0 (factory): ON (24V output) 1: OFF (No 24V output) n03 Outdoor unit D/W terminal outputs 24VAC once ambient temperature is lower than specific value for auxiliary heating resource to start. (Only available when n02 = 0 and Y signal = ON). : TA<15 F (24V output) 1: TA<10 F (24V output) 2: TA<5 F (24V output) 3: TA<-3 F (24V output) 4: OFF (No 24V output) Example: Y signal = ON n02 = 0 n03 = 1 Outdoor unit D/W terminal outputs 24VAC when ambient temperature is lower than 10 F. ambient temperature D/W output OFF ON
9 9/9 Illustration for n05~07 setting n05 Silent mode setting. 0 (Factory): none silent mode 1: Silent mode (level 1) 2: Super silent mode (level 2) 3: Night silent mode (level 1) 4: Super night silent mode (level 2) Noise of silent mode is 3 db lower than normal mode. Noise of super silent mode is 6 db lower than normal mode. n06 Night time setting - Start time. 0: 17:00 1: 18:00 (Factory) 2: 19:00 3: 20:00 4: 21:00 n07 Night time setting - End time. 0: 5:00 1: 6:00 (Factory) 2: 7:00 3: 8:00 4: 9:00 Example 1: n05 = 0 n06 = / n07 = / Example 2: n05 = 1 n06 = / n07 = / Silent mode (level 1) Example 3: n05 = 2 n06 = / n07 = / Super silent mode (level 2) Example 4: n05 = 3 n06 =0 n07 = 1 Silent mode (level 1) Example 5: n05 = 4 n06 =2 n07 = 3 Super silent mode (level 2)
CONTROL PANEL INSTRUCTIONS RSQ-4
CONTROL PANEL INSTRUCTIONS RSQ-4 FOR SIRAC AIR TO WATER HEAT PUMP (SINGLE COMPRESSOR, AIR TO WATER) 1) System Configuration This system is composed of mainboard and wire control panel. 146mm Φ4 4 Mainboard
More informationOPERATING INSTRUCTIONS
COMFORT CONTROL CENTER 2 THERMOSTAT OPERATING INSTRUCTIONS PROGRAMMABLE THERMOSTAT MODEL 3314080.000 BLACK 3314080.015 WHITE USA SERVICE OFFICE Dometic Corporation 1120 North Main Street Elkhart, IN 46514
More informationINVERTER 9-12 DC INVERTER 9 SF
INVERTER 9-12 DC 1. TECHNICAL DATA: DESCRIPTION OF PARAMETERS INVERTER 9 SF INVERTER 9 HP INVERTER 12 SF INVERTER 12 HP Cooling capacity (1) (min / rated / max) kw 1.4/2.3/2.7 1.4/2.3/2.7 1.8/2.7/3.1 1.8/2.7/3.1
More informationVRF D4 PLUS System. Highlights. Digital Scroll Series. Dealer information. Commercial Air Conditioner Business Units Midea Group
VRF D4 PLUS System Digital Scroll Series GD Midea Heating & Ventilating Equipment Co., Ltd. Is certified under the ISO 9001 International standard for quality assurance. NO.01 100 019209 GD Midea Heating
More informationEmad Chen. Head of Qatar Office Midea Commercial Air Conditioner
Welcome Emad Chen Head of Qatar Office Midea Commercial Air Conditioner World AC Market by value in 2017, US$103 billion/ 5% growth rate World Air Conditioning Market from 2014 to 2020(F)in unit terms
More informationProduct Line Introduction. Karl Zhang Technical support engineer
Product Line Introduction Karl Zhang Technical support engineer Air Conditioning Solutions Heating & Hot Water Solutions Control Solutions Air Conditioning Solutions Residential Application Commercial
More informationUser s Manual. THE iq Drive SYSTEM USER S INFORMATION IMPORTANT. Variable Speed Ultra-High SEER Split System IMPORTANT NOTE
User s Manual Variable Speed Ultra-High SEER Split System These units have been designed and tested for capacity and effi ciency in accordance with ARI standards. These outdoor air conditioning units are
More informationDC Inverter Smart VRF Products(R410A)
DC Inverter Smart VRF Products(R410A) General Description What is DC Inverter Smart? Inverter Smart system is YDS system: 1. With DC inverter compressor; 2. Condensing unit and heat pump type; 3. It is
More informationL SERIES UNITS 504,520M. 10/2001 Supersedes 504,413M
Litho U.S.A. 2 L SERIES UNITS 54,52M /2 Supersedes 54,4M M 6 VERSION 4. INTEGRATED MODULAR CONTROL (IMC) GUIDE TO THE M 6 VERSION 4. INTEGRATED MODULAR CONTROL USED IN L SERIES THROUGH TON UNITS TABLE
More informationSome alarms can be manually cleared from the current alarms list. This is indicated for the alarms where this is possible.
Alarm Descriptions This document describes all possible alarm types as listed in the alarm log. x indicates compressor circuit for compressor related alarms. Alarms are listed in alphabetical order. Some
More informationSEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR
SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR Printed in the USA ADSOOASHPOA 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located on its front
More informationTechnical Manual Binair Monobloc Heat Pump
Technical Manual Binair Monobloc Heat Pump MODEL BINAIR12 Introduction Disassembly of the machine must be carried out by any professional or any special agency assigned by us. All operation and maintenance
More informationOPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES
OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL 500644 FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES A047-001 FIGURE 1: Demand Defrost Control Module ANTI-SHORT CYCLE DELAY
More informationLENNOX MINI-VRF SYSTEMS. CONNECTING TECHNOLOGY WITH EXPERTISE.
LENNOX MINI-VRF SYSTEMS. CONNECTING TECHNOLOGY WITH EXPERTISE. LENNOX MINI-VRF MAKES MULTI-ZONE COMFORT EASY AND EFFICIENT. Available in 3- to 5-ton configurations, with options to control up to 9 zones,
More informationTechnicians Manual Single Compressor
Technicians Manual Single Compressor HAC-FF-D WALL PAD Operating Manual Version PCB Version V2.3.5 Version wall pad Version Manual Page 1 Contents 1. Main features 2. Main technical data 3. Wall pad 4.
More informationWARNING IMPORTANT. iharmony Zoning System CONTROLS KITS AND ACCESSORIES. Installation Instructions for the iharmony Zoning System (10C16)
CONTROLS KITS AND ACCESSORIES 2016 Lennox Industries Inc. Dallas, Texas, USA 9/2016 Supersedes11/2015 iharmony Zoning System Installation Instructions for the iharmony Zoning System (10C16) WARNING Improper
More informationDVM S Universal Communication Kit (UCK) Design Guide
DVM S Universal Communication Kit (UCK) Design Guide MCM-D211UN MXD-A24K100E MXD-A32K100E MXD-A40K100E MXD-A64K100E Version 11192018 Definition of Universal Communication Kit Technical Specification AHU
More informationAll alerts are still logged as alarms and also show up in the current alarm list.
Alarm Descriptions This document describes all possible alarm types as listed in the alarm log for software version 5.5.0 and later. x indicates compressor circuit for compressor related alarms. Alarms
More informationEC3-X33 Stand-alone Superheat Controller Technical Data
Technical Data EC3-X33 is a stand-alone universal superheat controller for air conditioning, refrigeration and industrial applications such as chillers, industrial process cooling, rooftops, heat pumps,
More informationUPM I. Unit Protection Module. Installation and Operation Manual (2015/06)
UPM I Unit Protection Module Installation and Operation Manual 6 720 220 321(2015/06) 2 Key to Symbols Contents Key To Symbols...2 Warnings...2 Specifications... 3 Unit Protection Module (UPM)....3 Power
More informationOPERATION MANUAL. Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system EKHBH007A EKHBX007A
OPERATION MANUAL Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system EKHBH007A EKHBX007A EKHBH007A*** EKHBX007A*** Indoor unit for air to water heat pump
More information3. INDOOR UNIT OPERATION
3. INDOOR UNIT OPERATION INDOOR UNIT OPERATION 3- FAN CONTROL 3-- Fan Speed Setting Fan speed setting Press the FAN CONTROL button to set the fan speed. AUTO HIGH MED LOW 3-- "AUTO" Position. COOL OPERATION
More informationRCS Residential Control Systems Inc.
RCS Residential Control Systems Inc. Model TZ16 Z-Wave Communicating Thermostat with Rev P HVAC Control Unit INSTALLATION AND OPERATION MANUAL DCN: 141-00882 Rev 02 5/18/06 This manual applies to the following
More informationREACH-IN SAFETEMP (-AAC)
Slide 1 REACH-IN SAFETEMP (-AAC) FH1-AAC RH2-AAC-HD The Hoshizaki line of reach-ins consists of two types of refrigerators and freezers. The high end TEMPGUARD (-SSB) and the mid-range SAFETEMP ( AAC).
More informationMRVIII-C MRVIII-C. 4 way air return heat exchanger design. Two stages heat exchanger design. Double EEV design. Special Heat Exchanger Design
Special Heat Exchanger Design 4 way air return heat exchanger design Reduce the heat exchanger height (6mm), and the upper and lower wind speed uniform and high efficiency. Air Supply Chamber and Equipment
More informationWired Controller XK60
Owner's Manual Commercial Air Conditioners Thank you for choosing Commercial Air Conditioners, please read this owner s manual carefully before operation and retain it for future reference. User Notice
More informationHEAT PUMPS SiOS SYSTEM TERMINAL UNITS UNICO CONDITIONER FIXED AIR PORTABLE AIR CONDITIONER AIR COOLER DEHUMIDIFIERS HUMIDIFIERS FAN HEATERS GAS STOVES
PERSONAL COMFORT 109 THE RANGE The air conditioner without outdoor unit, patented and designed by Olimpia Splendid in 1998. Unico, born with 15 years of experience. A complete range of solutions with no
More informationSLV CONTROLLER 105N46XX SERIES
WITH MORE THAN 50 YEARS OF EXPERIENCE IN COMPRESSOR TECHNOLOGY AND HIGHLY COMMITTED EMPLOYEES, OUR FOCUS IS TO DEVELOP AND APPLY THE ADVANCED COMPRESSOR TECHNOLOGIES TO ACHIEVE STANDARD SETTING PERFORMANCE
More informationInstallation Instructions / User s Manual TSTAT0406 and TSTAT0408
997-060180-5 Installation Instructions / User s Manual TSTAT0406 and TSTAT0408 4 HEAT 2 COOL DUAL FUEL TSTAT0406 & TSTAT0408-4 WIRE CAPABLE THERMOSTAT (NAXA00201DB Daughter Board sold separately) LEFT
More informationSTART UP FORM PACKET
START UP FORM PACKET Condensing Unit and Evaporator DIVISIONS OF RAE CORPORATION 4492 Hunt St. - Pryor, OK 74361 - (918) 825-7222 - Fax (918) 825-6366 www.rae-corp.com RAE Corporation Condensing Unit
More informationThe Book of AERMEC NRL Sequence of Operation
The Book of AERMEC NRL Sequence of Operation Heating and cooling operation. 2 Sequence of operation Aermec air to water chiller/heat pump use Hydronic s in conjunction with refrigerant to provide heating
More informationGLOBAL PROPERTY INSPECTIONS TECHNICAL BULLETIN August 1, 2002
TM TOPIC: Heat Pumps GLOBAL PROPERTY INSPECTIONS TECHNICAL BULLETIN August 1, 2002 This is the eighth in a series of technical bulletins in which an over-all examination of the home will be discussed as
More informationAdvance Split
Engineering Data Manual Aqu@Scop Advance Split Air-to-Water DC Inverter Split Heat Pumps Models 005, 008, 012 & 014 2 to 16 kw Strength Points Most efficient heating technology with variable speed compressor.
More informationController Manual. Technical Data. Model:LDRP1141 Independent Refrigeration Unit Controller
Controller Manual Model:LDRP1141 Independent Refrigeration Unit Controller Technical Data Rated voltage Voltage max. available range Rated current Voltage detecting range DC24V / 12V DC16V ~ DC32V / DC8V
More informationENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE
ENERGY LIGHT USER S GUIDE Release January 2001 CONTENTS 1.0 GENERAL CHARACTERISTICS... 4 1.1 MAIN CHARACTERIS TICS... 4 2.0 USER INTERFACE (CODE C5121230)... 5 2.1 DISPLAY... 5 2.2 MEANING OF THE LEDS...
More informationHOA Annunciator Load Programming and Monitoring Instructions
HOA Annunciator Load Programming and Monitoring Instructions Overview HOA Annunciator loads can be created in the ESS32 Load Directory for Novar s Savvy. Because the annunciator is built into the Savvy,
More informationUser & Installer Manual SMT-400 "Enterprise" Wi-Fi Thermostat
User & Installer Manual SMT-400 "Enterprise" Wi-Fi Thermostat Ver 1.01 May 2018 Great care has been taken in the preparation of this manual. Smart Temp Australia P/L takes no responsibility for errors
More informationSmall VRF system. for light commercial and home use SERVICE MANUAL
Small VRF system for light commercial and home use SERVICE MANUAL CONTENTS 1. TEST RUN 1-1 EXECUTION PROCEDURE AND EXECUTION PRECAUTIONS... 01-01 1-2 TEST RUN METHOD... 01-03 1-2-1 Check Items Before
More informationTH146-N-2H1C. 1. Introduction. 2. Installation. 1.1 Applications. 2.1 Control Module (CT280-2H1C) 1.2 Supplied Parts. 1.
TH146-N-2H1C Installation Guide Non-programmable H/C Controller Removable Connector * Removable Connector * TH146 User Console CT280-2H1C Control Module AC144-03 Outdoor Temperature Sensor * To remove
More informationDC INVERTER SERIES AIR TO WATER
DC INVERTER SERIES AIR TO WATER INSTALLATION AND OPERATING INSTRUCTIONS MODELS: KS50-DC / KS70-DC / KS90-DC / KS120-DC / KS150-DC Please read this instruction manual before using the heat pump Introduction
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section
More informationAIR-HANDLING UNIT (AHU) DESIGN GUIDELINE
INTERFACE AIR-HANDLING UNIT (AHU) DESIGN GUIDELINE September 2018 [Model Name] PAC-IF013B-E PAC-SIF013B-E Related document: Refer to the following manual PAC-IF013B-E/PAC-SIF013B-E INSTALLATION MANUAL
More informationSEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER
SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER Printed in the USA ADSOOASHPRAE 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located
More informationInstallation Instructions Read and become familiar with these instructions before beginning installation.
KSAIC020230 (208-230V) 24V Interface Kit for Ductless Outdoor Single Zone matched with Air Handler Installation Instructions Read and become familiar with these instructions before beginning installation.
More informationInstallation Instructions Read and become familiar with these instructions before beginning installation.
KSAIC005 (5V) KSAIC00230 (208-230V) 24V Interface Kit for Ductless Systems Installation Instructions Read and become familiar with these instructions before beginning installation. SAFETY CSIDERATIS Read
More informationOPERATION MANUAL. Indoor unit for hot water heat pump system and options EKHBH016AB EKHBX016AB
OPERATION MANUAL Indoor unit for hot water heat pump system and options EKHBH016AB EKHBX016AB EKHBH016AB*** EKHBX016AB*** Indoor unit for hot water heat pump system and options CONTENTS Page Introduction...1
More informationInstallation and Operation Manual
Beacon II Refrigeration Systems H-IM-79F April 2017 Part No. 25001401 Replaces H-IM-79E (6/11) Installation and Operation Manual Table of Contents Beacon II Board Layout... 2 Installation Tips... 3 Refrigerant
More informationAir to Water Heat Pump
E7- Air to Water Heat Pump Hydro Unit HWS-55XWHM-E HWS-805XWHM-E HWS-805XWHT6-E HWS-805XWHT9-E HWS-05XWHM-E HWS-05XWHT6-E HWS-05XWHT9-E HWS-P805XWHM-E HWS-P805XWHT6-E HWS-P805XWHT9-E HWS-P05XWHM-E HWS-P05XWHT6-E
More informationThe ultimate fresh air solution.
Fresh Access The ultimate fresh air solution. Introducing Fresh Access TM. Expertly designed, our innovative energy recovery ventilator (ERV) unit, split dedicated outside air system (DOAS), and packaged
More informationCommodity Description
A. Features 1. Defrosting System By using the patented technology, it is possible to keep the internal temperature of the refrigerator constant at all times, by preventing frost on the evaporator coil
More informationField Application of Advanced Residential Air Conditioning Systems
Field Application of Advanced Residential Air Conditioning Systems Presented By Greg Spencer, Residential Cooling Service Coordinator with Lennox Industries 1 How Ratings Are Established Size of Indoor
More informationSplit System Heat Pump Product Data
Split System Heat Pump Product Data XR 13 4TWR3018-060 1½ 5 Tons PUB. NO. 22-1795-06 Features and Benefits Climatuff compressor All aluminum Spine Fin coil Quick-Sess cabinet, service access and refrigerant
More information36,000-62,000 BTUH Nominal Capacity
36,000-62,000 BTUH Nominal Capacity STANDARD EQUIPMENT 2TEE3F62A, 4TEE3F62B VARIABLE SPEED AIR HANDLER Ships horizontal - converts to vertical by standing on end. Six-way convertibility-horizontal (left
More informationDANFOSS OPTYMA PLUS INVERTER UNITS
Optyma Plus Inverter Condensing Units Danfoss Optyma Plus Inverter Units are designed with the unique benefits of stepless inverter scroll technology resulting in a 20-30% higher energy efficiency in a
More informationHayward/Summit Heat Pump Troubleshooting Guide Hayward Industries
Hayward/Summit Heat Pump Troubleshooting Guide 2012 Hayward Industries Leave Blank- Inside Front Cover Heat Pumps Covered by This Guide HeatPro HP50TA, HP20654T, HP20654BT, HP20654TC, HP20854T, HP20854BT,
More informationSERVICE MANUAL IMPORTANT IMPORTANT 4SCU20LX 4SHP20LX ALLIED AIR ENTERPRISES I. GENERAL. August Electrical
ALLIED AIR ENTERPRISES SERVICE MANUAL August 2015 4SCU20LX 4SHP20LX IMPORTANT: Before applying any power (main or low voltage) to the outdoor unit, confirm the Comfort Sync thermostat has software Version
More informationEmerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING
Emerson Inspire 1HDEZ-1521 Installation Instructions Thermostat/Interface Equipment Control TROUBLESHOOTING FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL
More informationUnico Presentation. Introducing
Introducing Combines all the efficiencies and performance of inverter technology with all the features and benefits of The Unico System Made in conjunction with Argoclima Group is a European leader in
More informationAdvanced Installation and Configuration Instructions
TP-WEM01-A Performance Series AC/HP Wi- Fi Thermostat Carrier Côr Thermostat Advanced Installation and Configuration Instructions Table of contents How to Use This Document... 3 Wiring Diagrams... 4 Installations
More informationCDS 80. Continuous ventilation without dehumidification can be selected on the CDS 80 control panel.
DEHUMIDIFICATION 9 CDS 80 FUNCTION The CDS 80 works in accordance with the condensation principle. A fan draws the humid air into the dehumidifier and through an evaporator coil. When passing through the
More informationTo accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.
Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs the unwanted heat, this raises the refrigerant
More informationSplit System Cooling Product & Performance Data
Split System Cooling Product & Performance Data Three Phase 2TTA3048-060A3 4 5 Tons PUB. NO. 22-1770-03 Features and Benefits All aluminum Spine Fin coil Durable base, fast complete drain, weather proof
More informationOWNER S MANUAL DUCTED INVERTER. (English) (SDHV SERIES)
OWNER S MANUAL DUCTED INVERTER (English) (SDHV SERIES) IMPORTANT As with any product that has moving parts or is subject to wear and tear, it is VERY IMPORTANT that you maintain your air conditioner and
More informationfood-retail.danfoss.com Overview Brochure ADAP-KOOL Evaporator Controllers Achieve best-in-class energy efficiency and food safety
Overview Brochure ADAP-KOOL Evaporator s Achieve best-in-class energy efficiency and food safety Proven solutions based on 30 years of experience food-retail.danfoss.com Robust, Easy & Intelligent From
More informationHyperion Field Reference Data TAM8
Hyperion Field Reference Data TAM8 Air Handler - Convertible Models: Series 8 Air Handlers 2-5 Ton *AM8A0A24V21CA, *AM8A0B30V21CA *AM8A0C36V31CA, *AM8A0C42V31CA *AM8A0C48V41CA, *AM8A0C60V51CA * May be
More informationV4 Plus Heat Recovery VRF. Linda Lin Pre-sales Engineer
V4 Plus Heat Recovery VRF Linda Lin Pre-sales Engineer VRF Line-up DC inverter VRFs 2-pipe 3-pipe Combinable Individual Watercooled Mini Heat recovery V5 X 8-88HP V4+S 8-64HP V4+I (side) 20-45kW V4+I (top)
More informationDVPEC. Multi-Position, Variable-Speed air handler. Comfortnet Compatible ECM-based Internal EEV, Inverter-tuned 2 to 5 Tons
DVPEC Multi-Position, Variable-Speed air handler Comfortnet Compatible ECM-based Internal EEV, Inverter-tuned 2 to 5 Tons Contents Nomenclature... 2 Product Specifications... 3 Dimensions... 4 Airflow
More informationHEAT PUMP UNIT AVZC20 HEAT PUMP INSTALLATION & SERVICE REFERENCE
HEAT PUMP UNIT AVZC20 HEAT PUMP INSTALLATION & SERVICE REFERENCE CAPACITOR... 28 TROUBLESHOOTING... 33 SETTING THE MODE DISPLAY... 38 7-SEGMENT DISPLAY... 44 START-UP CHECKLIST... 47 IMPORTANT SAFETY INSTRUCTIONS
More informationC5-12 OPERATION MANUAL
C5-12 OPERATION MANUAL C5-12 Controls 1 Overview... 3 1.1 Introduction... 3 1.2 Model numbers explained... 3 1.3 Product series overview... 4 1.4 Hardware Controller... 4 1.5 Controller Inputs and Outputs...
More informationQuick Reference. Air to Water Heat Pump Series 4 Lot 1 Standard & Powerful Types
Quick Reference Air to Water Heat Pump Series 4 Lot Standard & Powerful Types Estia Series 4 Standard Type Models: Hydro unit HWS-804XWHM3-E HWS-804XWHT6-E HWS-804XWHT9-E HWS-404XWHM3-E HWS-404XWHT6-E
More informationProdigy Flaked and Nugget Ice Machines Technical Review
CM 3 Control System Update Prodigy Flaked and Nugget Ice Machines Technical Review Evaporator Assembly Behind Ice Chute Assembly Fan Blade Control Panel Water Reservoir Air Filter Compressor Ice Chute
More informationInstallation and Operation Manual
Beacon II Refrigeration Systems H-IM-79G April 2018 Part No. 25001401 Replaces H-IM-79F (08/17) Installation and Operation Manual Table of Contents Beacon II Board Layout... 2 Installation Tips... 3 Refrigerant
More informationInverter scroll compressors VZH hybrid manifold
Application guidelines Inverter scroll compressors VZH hybrid manifold R410A http://cc.danfoss.com Contents...4 Scope...4 Benefits...4...5 Oil management concept...5 System configuration...5 Dimensions...8
More information1.0 Digital Controller
Form CP-AHU D19_D21_D22 (11-17) D303072-A Obsoletes Forms CP-Preeva-D21 (1-16) Doc No 303072, CP-Preeva-D19 (1-16) Doc No 303071 Applies to: Preeva, MAPS, MAPS II, RPB, RPBL & SSCBL Series For Air Handler
More informationInstallation Instructions
TP --- PRH --- A, TP --- NRH --- A PerformancetSeries Edger Thermidistatt Control Installation Instructions Programmable Control A07049 A07048 Non---Programmable Control NOTE: Read the entire instruction
More informationDVPVC. Multi-Position, Variable-Speed Air Handler. Comfortnet - Compatible ECM-based Inverter-tuned Internal TXV
DVPVC Multi-Position, Variable-Speed Air Handler Comfortnet - Compatible ECM-based Inverter-tuned Internal TXV Contents Air Handler Nomenclature... Heater Kit Nomenclature... Product Specifications...3
More information40KMC KMQ
40KMC------301 40KMQ------301 OWNER S MANUAL Split system Global cassette indoor unit IR Remote Control Room Controller Zone Manager The unit can be used with infrared Remote Control, with the Carrier
More informationKSIM20912-H216 KSIM30912-H216 KSIM40912-H216
SERVICE MANUAL KLIMAIRE AIRCONDITIONER KSIM DC INVERTER MULTI TYPE KSIM20912-H216 KSIM30912-H216 KSIM40912-H216 DC MULTI OUTDOOR UNITS CONTENTS 1. General information of Outdoor Units...3 2 Features...4
More informationSplit System Cooling Product Data
Split System Cooling Product Data XB16 4TTB6 1 1 / 2-5 Tons PUB. NO. 22-1888-01 Features and Benefits Efficiency up to 16.0 SEER All aluminum SPINE FIN coil WEATHERGUARD fasteners QUICK-SESS cabinet, service
More informationNA G µair CONNECT 2
NA 9.41 G 7-216 µair CONNECT 2 Control manual EN CONTENTS PAGE 1. GENERAL INFORMATION 2 2. COMPONENTS 3 2.1 On the front: 3 2.2 On the rear: 4 3. MENU TREE 7 4. ACCESS LEVEL (menu 8) 1 5. CONFIGURING
More informationDPC-1 Programmable digital thermostat with communication Versión 2.0. Technical Information. Ref: N
DPC-1 Programmable digital thermostat with communication Versión 2.0 Ref: N-27360 1108 Technical Information I S O 9 0 0 1 ER-0028/1991 Johnson Controls Manufacturing España, S.L. is participating in the
More informationT-32-TS Touchscreen Thermostat. Installation Manual
T-32-TS Touchscreen Thermostat Installation Manual TABLE OF CONTENTS Introduction...4 Getting Started...5 Installing the Thermostat...6, 8 Disassembly...6 Thermostat Location...6 Mounting the Subbase...6,
More informationIce Rink (Single and Dual Configurations) Custom Control Features
& M&M Refrigeration, Inc. Computer Control System Ice Rink (Single and Dual Configurations) Custom Control Features REVISION DATE DESCRIPTION - 4/20/05 Original release. A 09/21/98 Update Chiller Pump
More informationDaikin ENVi Thermostat installation overview
Daikin ENVi Thermostat installation overview RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL Presenter s Name Presenter s Title Daikin ENVi system overview (web based thermostat) Slide 2 Daikin ENVi System Overview
More information*9MAC TROUBLESHOOTING GUIDE
Variable Speed, Modulating Electronic Condensing Four-Way Multipoise Gas Furnace *9MAC TROUBLESHOOTING GUIDE INDEX PAGE Safety Considerations... 1 Instructions... 1 Example... 2 General... 2 Sequence of
More informationPROFESSIONAL - SSE. Stainless steel interior and exterior (with galvanized back and bottom)
PROFESSIONAL SERIES PROFESSIONAL - SSE PROFESSIONAL - SSE PROFESSIONAL - SSE Stainless steel interior and exterior (with galvanized back and bottom) Innovative variable speed compressor with adaptive control
More informationACCESSORY ITEMS FOSSIL FUEL KITS RXPF- SERIES. Model RXPF-F01 Model RXPF-F02
FORM NO. X11-1117 REV. 7 Supersedes Form No. X11-1117 Rev. 6 ACCESSORY ITEMS FOSSIL FUEL KITS RXPF- SERIES Model RXPF-F01 Model RXPF-F02 IMPORTANT: The RXPF-F01 & RXPF-F02 are designed for use with Rheem
More informationSplit System Cooling Product Data
Split System Cooling Product Data XR 13 4TTR3018-060 1½ 5 Tons PUB. NO. 22-1842-07 Features and Benefits Climatuff compressor Efficiency up to 14.00 SEER All aluminum Spine Fin coil WeatherGuard fasteners
More informationUser manual CLIMATIC 200/400 - Controller. Providing indoor climate comfort
User manual CLIMATIC 2/4 - Controller Providing indoor climate comfort MUL35E-56 9-26 INDEX CONTENTS PAGE INDEX 1 GENERAL DESCRIPTION 2 THE KEYPAD, Climatic 2 3 THE KEYPAD, Climatic 4 4 THE KEYPAD REMOTE
More informationFast Track Troubleshooting
Fast Track Troubleshooting Model: RH22** Bulletins: IMPORTANT SAFETY NOTICE For Technicians Only This service data sheet is intended for use by persons having electrical, electronic, and mechanical experience
More informationWired controller KJR-08B/BE. Run. Fault. TB Tot. Out. Query. Heat. Net-On. Turn-On Mode
R0A (kw-0kw) 0Hz KJR-0B/BE is a human-machine interaction(hmi) used for the communication between chiller operator and main board on the chiller itself. The setting and operation order can be send to the
More informationProduct Data. Split System Heat Pump B-EN. February A6H6024H1000A
Product Data Split System Heat Pump 4A6H6024H1000A Note: Graphics in this document are for representation only. Actual model may differ in appearance. February 2015 12-1202-1B-EN Product Specifications
More informationSPLIT SYSTEM COOLING 1½ 5 TON ALLEGIANCE 14 MODELS 4A7A C/30-060B American Standard Heating & Air Conditioning
SPLIT SYSTEM COOLING 1½ 5 TON ALLEGIANCE 14 MODELS 4A7A4018-24C/30-060B 2009 American Standard Heating & Air Conditioning PUB.. 12-1173-04 April 2009 Features and Benefits Duration compressor Efficiency
More informationAVPTC. Air Handlers 1½ to 5 Tons
Multi-Position, Variable-Speed Air Handlers ½ to Tons Standard Features Compatible with the ComfortNet Communicating System family of products R-0A refrigerant-compatible Factory-installed thermal expansion
More informationController for Condensing unit Optyma Plus Evo 3 REFRIGERATION AND AIR CONDITIONING. Manual
Controller for Condensing unit Optyma Plus Evo 3 REFRIGERATION AND AIR CONDITIONING Manual Introduction Application Condensing unit control Advantages Condensing pressure control in relation to outside
More informationEasyTech.Full Temperature Controller for Pellet Stove. Idro
EasyTech.Full Temperature Controller for Pellet Stove EasyTech.One is a Pellet stoves control system available in Air and Hydro version. Is characterised by: Installing and use simplicity Simple and direct
More informationER52 - Evaporator Controller
ER52 - Evaporator Controller Electronic Refrigeration Line Product Bulletin Devices are standalone digital controller for static or ventilated refrigeration units working at positive temperatures. They
More informationW1/B, O, W2/E, Y1, Y2, G. Gas or electric. Wireless, 915MHz, proprietary protocol. Up to 100 feet 24VAC, 2.4VA. Molded plastic
Wireless COMF TTM Made in the USA Application Installation Manual Model WCT-32 The WCT-32 is a 7-day programmable, battery powered thermostat that communicates via an F wireless data link to a relay control
More informationTVR 5G GUIDE SPECS. TVR 5G GUIDE SPECS - JUL.2014 Page 1
TVR 5G GUIDE SPECS TVR 5G GUIDE SPECS - JUL.2014 Page 1 Part 1 TRANE VARIABLE REFRIGERANT FLOW SYSTEM 1.1 General PRODUCT Unit shall be air cooled variable refrigerant flow system, module split type multi-system
More informationtechnical bulletin Control Link RSC Installation Instructions
COMPU TER PROCE SS CONTRO L S Overview The Control Link Refrigeration System Controller (CL-RSC) is an electronic device that can control all functions of a single-compressor refrigeration system, including
More information