STATEMENT OF WORK I. SCOPE OF WORK:

Size: px
Start display at page:

Download "STATEMENT OF WORK I. SCOPE OF WORK:"

Transcription

1 STATEMENT OF WORK Purchase and Installation of Diesel Standby Generator Set and Service Entrance Rated Automatic Transfer Switch for Sewage Treatment Plant Nockamixon State Park (Bucks County) I. SCOPE OF WORK: The Pennsylvania Department of Conservation and Natural Resources, Bureau of State Parks, requires the services of a contractor for the purchase and the installation of a permanently installed diesel fueled standby generator equipped with self-monitoring and self-diagnostic features capable of network communication and remote annunciator and emergency stop system for the Nockamixon State Park Sewage Treatment Plant, which is located within Nockamixon State Park, 1775 Mink Road, Quakertown, Pennsylvania The awarded contractor shall provide the Department with the minimum recommended concrete pad dimensions with conduit stub-out areas required for the generator set. Maintenance personnel at the state park will install the concrete mounting pad. Questions regarding the technical aspects of this bid should be directed to Obie Derr, Park Manager, at Questions regarding the bidding or contracting procedures should be directed to Nancy Weibley at II. CONTRACT TASKS: The Contractor must furnish all supplies and equipment. Equipment to be installed must be approved by the Park Manager or a designated representative prior to installation. However, no equipment or material shall be delivered to the site by the awarded vendor until the awarded bidder has obtained prior shop submittal approval from the Department. The following specifications shall include minimum requirements, unless otherwise stated, to include all genuine parts, accessories, equipment and safety features considered standard whether mentioned herein or not. The generator and transfer switch shall comply with all applicable NEMA codes, NFPA fire prevention and electrical codes, and state and local regulations. All work and installations performed shall be completed per the manufacturer's specifications and in accordance with applicable Uniform Construction Code. Outdoor Diesel Emergency Generator (1 each) Furnish one (1) continuous, standby rated, outdoor, skid-mounted, diesel emergency generator set with sub-base fuel tank, weather-tight enclosure, and remote annunciator panel, to be delivered to the Sewage Treatment Plant at Nockamixon State Park, 1775 Mink Road, Quakertown, Pennsylvania. The incoming freight and placement of the generator at the Sewage Treatment Plant shall be included in the bid price. Standby Ratings at 130 degrees Celsius Rise: 125kW (156kVA) 480Y/277 Volts AC 3 phase, 60Hz, approximately 188 amps, 1800 rpm 1

2 Warranty: One year parts and labor from the date of site start-up. Manuals: Three (3) complete sets of Operators & Maintenance Manuals. Without intending to limit and/or restrict the equipment and materials required by these specifications, the diesel generator system shall be provided with, but is not limited to, the following: - Channel steel skid base. - UL-2200 Listed. - Certified by the Environmental Protection Agency (EPA) to conform to Tier 3 non-road emissions regulations and stationary emergency applications. - Outdoor UL-2200 listed weather housing with rodent guards and skid end caps. - Fully automatic generator set-mounted controller with, but not limited to, the following: Pre-Alarms. Dry contact (isolated alarm). Common Failure Relay. Automatic starting and stopping, and manual start/stop capabilities. Three-position (Automatic-OFF-TEST) selector switch. AC Meter and Instrumentation Panel for volts, amps, combined frequency meter and tachometer, coolant temperature, lube oil pressure, battery condition voltmeter, and hourmeter for engine run time. Automatic engine shutdown when signals for high coolant temperature, low oil pressure, or overspeed are received. Indicating lights/engine monitor. Vibration isolated control panel with lockable-hinged panel door. Remote starting contacts to interface with the new automatic transfer switch. Remote monitoring capabilities & communication thru a PC via network or modem. NFPA 110 Level 1 capability. Modbus protocol capability. - Float-type battery charger (12VDC) with alarms and equalizer. - Batteries, electrolyte, battery rack, and associated cables. - Engine block heater to operate at 120 volts AC single phase, thermostatically controlled to maintain engine coolant at proper temperature, and sized (approximately 1500 watts or greater) to meet the requirements of NFPA-110 regulation. - Flexible seamless stainless steel exhaust connector and solid nipple. - Level 2 (typical attenuation level of 25dBA) critical engine exhaust silencer system - Electronic Isochronous Governor. - Oil drain valve and extension line. - Cooling system to include a unit-mounted radiator with water pump, electric coolant heater, blower fan, thermostat, radiator duct flange, and 50% antifreeze mix. - Coolant drain. - Heavy-duty, dry type air cleaner. - AC generator to be brushless, permanent magnet. - Class H insulation material and 130 degrees Celsius standby temperature rise. - Anti-vibration isolators/pads between the engine-generator and the heavy duty steel mounting skid base to ensure vibration isolation - Flexible fuel lines. - Integral fuel transfer pump. - Mounted fuel solenoid valve and flexible connection. - Safeguard breaker. - One (1) engine mounted 3-pole, 200 amp mainline molded case circuit breaker. - Engine lube oil and antifreeze. - Three (3) sets of Operators & Maintenance Manuals including general maintenance and NFPA 110 literature. - Mushroom head push button emergency generator stop switch with push button guard to reduce the risk of accidental operation in a surface mounted enclosure. - Remote Annunciator Panel with single automatic transfer switch (ATS) control features including common alarm, remote testing of the ATS, and monitoring of the normal & emergency sources. 2

3 - Incoming freight, start-up, training services, and generator testing. All required design prototype tests, final production tests, start-up site tests, including no-load, dynamic building load, and load bank testing. All function and time setting parameters associated with the corresponding automatic transfer switch shall be properly interfaced with the generator system. - One (1) year limited warranty program. The generator shall include a minimum 250 gallon U.L. listed double-walled skid mounted sub-base fuel tank or properly sized to provide a minimum 24-hour standby at full load capacity of the generator, whichever is greater, with, but not limited to, low fuel level alarm, fuel in basin/leak alarm, mounting rails, vent cap, fuel level gauge, fill port, drain, and all required piping and accessories. Reference: Kohler Model No. 125REOZJG Diesel Emergency Generator with Remote Serial Annunciator III (RSA III), or approved equal. Start-up Services: The manufacturer or manufacturer s representative shall be on-site during start-up to ensure that the generator is installed and operating properly, and to complete all necessary paperwork and forms required for commissioning and warranty registration. After final hook-up of the generator system (by others), the State Park will contact the Vendor to make arrangements for the official site start-up. Diesel fuel will be provided by the state park and is not part of this contract. The start-up services shall include a generator training session with operational and maintenance procedures, a no-load operational test, a minimum 1-hour building dynamic load test demonstration, and a load bank test. The load bank test shall be conducted with 100% of generator nameplate rating for two (2) continuous hours, or in accordance with NFPA 110 generator testing regulations, whichever is greater. Outdoor Service Entrance Automatic Transfer Switch (1 each) Furnish one (1) outdoor, service entrance rated automatic transfer switch to be utilized with the 125kW diesel emergency generator as described above. The switch shall have microprocessor logic control with programmed transition mode of operation, and shall be rated 3-pole, 4-wire, solid neutral, 400 amp, 480 volts, 60 Hertz, with a 3- pole, 400 amp molded case circuit breaker with electronic trip for the utility switching device, and a 3-pole, 200 amp molded case switch for the generator switching device. The switch shall have a NEMA Type 3R enclosure for installation outdoors. The switch shall be a mechanically held and electrically operated automatic transfer switch in a free standing, floor mounted type enclosure, to be used on a 480Y/277 volt, three phase, 4-wire, 60 hertz system. The incoming freight and placement of the automatic transfer switch, in addition to all required start-up and programming services, shall be included in the bid price. The transfer mechanism of the switch shall be mechanically designed to prevent both the normal and emergency sources from being connected at the same time, and to prevent the contacts from stopping in-between, so that no source is connected. The transfer switch/control panel for the automatic transfer switch shall be provided with, but is not limited to, the following: - Engine starting contacts, with adjustable Time Delay on Engine Starting to override momentary normal source outages. - Adjustable Time Delay Normal to Emergency load transfer. - Adjustable Time Delay Emergency to Normal load transfer (i.e. retransfer back to normal). - Unloaded running time delay for emergency engine generator cool-down after retransfer back to normal source. - Test switch to momentarily simulate normal source failure. - Adjustable close differential voltage sensing on all phases of normal source. - Over and underfrequency sensing on one phase of the normal source, and overvoltage and overfrequency sensing on one phase of the emergency source. - Phase rotation and phase loss monitoring. - Automatic 7-day mode exerciser with LOAD / NO LOAD selector switch and an override circuit. The manufacturer or manufacturer s representative shall program the exerciser on the site start-up date to 3

4 automatically perform a weekly thirty (30) minute no-load test on a particular day and time that is to the satisfaction of the Park Operations Manager. - Green indicator light for normal source switch position. - Red indicator light for emergency source switch position. - Solid Neutral bar. - Padlockable handle on the front door. - Hygrostat-controlled 120VAC strip heater to prevent condensation. - Two auxiliary contacts: one relay auxiliary contact (normal source 2 NO and 2 NC) that is energized when normal power is available, and the other relay auxiliary contact (emergency source 2 NO and 2 NC) that is energized when emergency power is available. The outdoor automatic transfer switch shall be compatible with the new emergency generator. Reference: Kohler Model No. KEP-DMTC-0400SNK with accessories as described above, or approved equal. Please Note: All bidders will be required to submit the following with their bid: catalog cuts, specification sheets, dimensional drawings, wiring diagrams, etc. for the emergency generator, generator enclosure, generator sub-base fuel tank, batteries, battery charger, remote annunciator panel, remote emergency stop switch, and automatic transfer switch. The generator manufacturer s air emissions data shall also be submitted. All work shall be subject to inspection and acceptance by the Park Manager or his designee. The Department may choose to exercise the right to cancel this contract at any time during the term of this contract if requirements are not satisfactorily completed. Ill. SITE INSPECTION: Prospective bidders are encouraged to visit the site prior to bidding. Contact the Park Office at to make arrangements. Questions concerning the contract should be directed to Obie Derr, Park Manager, at the above number. IV. CONTRACTOR REFERENCES: After bid opening, and prior to awarding of the contract, the Department has the right to request references (names, addresses and telephone numbers) of similar work performed in the previous two (2) years as proof of qualifications to perform the work involved in this contract. V. CONTRACT REQUIREMENTS: The contractor agrees to comply with Attachment A Reciprocal Limitations Act Requirements form, as attached. Either party, the Park Manager/representative or the Contractor, shall give at least ninety (90) days written notice prior to cancellation of this contract. VI. PERFORMANCE DEPOSIT: In order to secure performance of the conditions of this contract, awarded vendor agrees to furnish, in a form acceptable to the Department (certified or cashier s check, money order, corporate bond or letter of credit), a performance deposit in the amount of 10% of the bid amount. All checks and money orders must be made payable to the Commonwealth of Pennsylvania. Personal checks or money orders will not be accepted. 4

5 VII. INSURANCE REQUIREMENTS: The contractor shall purchase and maintain, at its expense, the following types of insurance, issued by companies acceptable to the Commonwealth. a. Workmen s Compensation Insurance for all of the Contractor s employees and those of any subcontractor, engaged in work at the site of the project as required by law. b. Public Liability and Property Damage Insurance to protect the Commonwealth, the Contractor, and any and all subcontractors from claims for damages for personal injury (including bodily injury), sickness or disease, accidental death and damage to property including the loss of use resulting from any property damage, which may arise from the activities performed under the Contract, or the failure to perform under the Contract, whether such performance or non-performance be by the Contractor, by any subcontractor, or by anyone directly or indirectly employed by either. The minimum amounts of coverage shall be $250,000 per person and $1,000,000 per occurrence for bodily injury, including death, and $250,000 per person and $1,000,000 per occurrence for property damage. Such policies shall be occurrence rather than claims-made policies and shall not contain any endorsements or any other form designated to limit and restrict any action by the Commonwealth, as an additional insured, against the insurance coverage in regard to work performed for the Commonwealth. Prior to commencement of the work under the Contract and at each insurance renewal date during the term of the Contract, the Contractor shall provide the Commonwealth with current certificates of insurance. These certificates or policies shall name The Commonwealth of PA-DCNR as an additional insured and shall contain a provision that the coverage s afforded under the policies will not be cancelled or changed until at least thirty (30) days written notice has been given to the Commonwealth. These certificates shall include the location and a brief description of the work to be performed under the contract. The Commonwealth shall be under no obligation to obtain such certificates from the Contractor(s). Failure by the Commonwealth to obtain the certificates shall not be deemed a waiver of the Contractor s obligation to obtain and furnish certificates. The Commonwealth shall have the right to inspect the original insurance policies. VIII. CONTRACT TERM: The contract shall commence upon receipt of the purchase order and Notice to Proceed notification, and terminates December 31, IX. BID AWARD: The bidder shall complete and/or attach the following for award of the bid: complete the electronic Invitation for Bid to be found at complete and electronically attach the Reciprocal Limitations Act Requirements form (attached); and, submit catalog cuts, specification sheets, dimensional drawings, wiring diagrams, etc., for the emergency generator, generator enclosure, generator sub-base fuel tank, batteries, battery charger, remote annunciator panel, remote emergency stop switch, and automatic transfer switch. The generator manufacturer s air emissions data shall also be submitted. Bids will be awarded based on a total sum. The contract quantities herein are estimated only and may increase or decrease depending on the needs of the Department. The Contractor shall be paid at the unit price for actual work performed. 5

6 NOTE: The Department will only accept out to two (2) decimal points when entering your "Unit Price" bid. X. PAYMENT TERMS: Payment shall be made upon satisfactory completion of each line item listed on the IFB (Invitation for Bid). The Department representative must be in agreement with the contractor and the Department representative must authorize the partial payment. A line item will be deemed complete when all items listed in the line item have been met. XI. INVOICES: All invoices for the contract MUST be sent to the following address: Commonwealth of PA- PO Invoice P.O. Box Harrisburg, PA All invoices MUST have the Purchase Order Number, as well as your SAP Vendor Number on each invoice. Failure to provide this will result in a delay of your payment. XII. RECEIPT AND OPENING OF BID: Bids will be submitted via PA Supplier Portal, to be found at Faxed bids and mailed bids will not be accepted. No responsibility will be attached to any employee of the Department for the premature opening of, or the failure to open, a bid not properly addressed and identified, or for any other reason whatsoever. XIII. BID RESULTS: Bidder can obtain bid results by accessing The bids will be posted no later than 3 business days following the bid opening. The results are the apparent bidders and all bids are under review until final award of the purchase order. Attachments 6

STATEMENT OF WORK ELECTRICAL REPAIR / MAINTENANCE BUILDING PROJECT FDC RACCOON CREEK STATE PARK (BEAVER COUNTY)

STATEMENT OF WORK ELECTRICAL REPAIR / MAINTENANCE BUILDING PROJECT FDC RACCOON CREEK STATE PARK (BEAVER COUNTY) STATEMENT OF WORK ELECTRICAL REPAIR / MAINTENANCE BUILDING PROJECT FDC-213-100797 RACCOON CREEK STATE PARK (BEAVER COUNTY) I. SCOPE OF WORK: The Commonwealth of Pennsylvania, Department of Conservation

More information

SMALL WORKS PROJECT REQUEST FOR SEALED BIDS

SMALL WORKS PROJECT REQUEST FOR SEALED BIDS SMALL WORKS PROJECT REQUEST FOR SEALED BIDS PIERCE COUNTY FIRE PROTECTION DISTRICT #22 18421 OLD BUCKLEY HIGHWAY BONNEY LAKE, WA 98391 (253) 863-1800 (253) 863-1848 (FAX) Date Bid Requested: 5/24/2012

More information

B. Section Transfer Switches: Automatic transfer switch.

B. Section Transfer Switches: Automatic transfer switch. SECTION 263213 - ENGINE GENERATORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Packaged engine generator set. B. Exhaust silencer and fittings. C. Remote control panel. D. Battery and charger. E. Weatherproof

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S.

CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S. CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S. NAME OF TENDER: CONSTRUCT, DELIVER AND COMMISSION 3 (THREE) LIFT STATION ELECTRICAL LOCATION OF WORK: 3 Separate work sites in

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

ENGINE GENERATORS AND ACCESSORIES

ENGINE GENERATORS AND ACCESSORIES ENGINE GENERATORS AND ACCESSORIES GENERAL INFORMATION 1.1 This section applies to engine generators and accessories. DESIGN REQUIREMENTS 2.1 The Engineer of Record will consult with the University s Engineering

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps. Issued 2006/08/01 Section 13920 Packaged Fire Pumps and Controllers Page 1 of 7 PART 1 GENERAL 1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1

More information

Guide Specification Model CTG Automatic Transfer Switch

Guide Specification Model CTG Automatic Transfer Switch Guide Specification Model CTG Automatic Transfer Switch PART 1 GENERAL 1.1 Scope A. It is the intent of this specification to secure a transfer switch that has been prototype tested, factory built, production

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

SECTION EMERGENCY POWER SYSTEMS

SECTION EMERGENCY POWER SYSTEMS SECTION 16620 EMERGENCY POWER SYSTEMS A. Standby Engine/Generator Systems 1. Installations of stationary engine/generator (e/g) systems shall be designed in strict accordance with ANSI/NFPA 70 - National

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

Replacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus

Replacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus ADDENDUM FORM INVITATION TO TENDER: 2016-067 ADDENDUM NO: 1 DATE ISSUED: June 23, 2016 ISSUED BY: Monty Thibeault DESCRIPTION: Replacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

Spectron LSN (Life Safety Network) Suggested Specifications

Spectron LSN (Life Safety Network) Suggested Specifications 1. General 1.1 Scope A Dual-Lite Spectron LSN (Life Safety Network) Series Inverter System shall be furnished to provide a reliable source of power, and shall operate during a utility line deficiency without

More information

SECTION AUTOMATIC TRANSFER SWITCH

SECTION AUTOMATIC TRANSFER SWITCH SECTION 26 36 23 AUTOMATIC TRANSFER SWITCH PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install automatic transfer switch (ATS) with number of poles, amperage, voltage and withstand current ratings as shown

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

This Addendum includes the following changes and clarifications to the Contract Documents:

This Addendum includes the following changes and clarifications to the Contract Documents: August 17, 2018 IFB#: 2018-01 IFB Closing on: August 28, 2018 ADDENDUM NO. FIVE TO THE CONTRACT DRAWINGS AND SPECIFICATIONS FOR THE REFERENCED PROJECT, DATED JULY 11, 2018, AS PREPARED BY GRIMM + PARKER

More information

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification

More information

SUGGESTED SPECIFICATION For Series 300 Manual Transfer Switches (3MTS)

SUGGESTED SPECIFICATION For Series 300 Manual Transfer Switches (3MTS) SUGGESTED SPECIFICATION For Series 300 Manual Transfer Switches (3MTS) PART 1 GENERAL 1.01 Scope Furnish and install manual transfer switches (3MTS) with number of poles, amperage, voltage, and withstand

More information

16620 EMERGENCY POWER SYSTEMS

16620 EMERGENCY POWER SYSTEMS 16620 EMERGENCY POWER SYSTEMS PART 1: GENERAL 1.01 SUMMARY A. This Section provides the University guidelines for the installation of Emergency Power Systems. B. This standard is developed primarily to

More information

Sheetz Inc. Fire Protection Service Guidelines

Sheetz Inc. Fire Protection Service Guidelines Sheetz Inc. Fire Protection Service Guidelines Overview The following are guidelines for Sheetz Fire Protection Services for the 2016/2018 contract year. Each key area is listed below with the appropriate

More information

Baldor Electric ProSPEC MASTERFORMAT SPECIFICATION 10/26/05

Baldor Electric ProSPEC MASTERFORMAT SPECIFICATION 10/26/05 SECTION 16230 - GENERATOR ASSEMBLIES PART 1 - GENERAL 1.1 SUMMARY A. Provide factory test, startup by a supplier authorized by the manufacturer, and on-site testing of the system. B. The generator set

More information

SECTION GENERATOR PARALLELING CONTROLS

SECTION GENERATOR PARALLELING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 13 GENERATOR PARALLELING CONTROLS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase General Specification 550 VA/Watts 1300 VA/Watts 1.0 GENERAL This specification defines the electrical and mechanical characteristics

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps TT-1023 1/97 INSTALLATION INSTRUCTIONS Original Issue Date: 2/94 Model: 6-2000 kw Market: Industrial Subject: Flush- or Surface-Mount Remote Annunciator Kits PA-293991 and PA-293991-SD The remote annunciator

More information

A. This Section includes transfer switches rated 600 V and less, including the following:

A. This Section includes transfer switches rated 600 V and less, including the following: SECTION 16415 - TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

REQUEST FOR PROPOSALS Grand Traverse County Board of Public Works (BPW) Department of Public Works (DPW) Shop Generator Set

REQUEST FOR PROPOSALS Grand Traverse County Board of Public Works (BPW) Department of Public Works (DPW) Shop Generator Set REQUEST FOR PROPOSALS Grand Traverse County Board of Public Works (BPW) Department of Public Works (DPW) Shop Generator Set Proposals Due: 3:00 P.M., Friday October 7, 2016 Address Proposals to: DPW Shop

More information

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings. SECTION 15481 COMPRESSED AIR SYSTEM PART 1 - GENERAL 1.1 SECTION INCLUDES A. Pipe and pipe fittings, including valves, unions and couplings. B. Air compressor. C. After cooler. D. Refrigerated air dryer.

More information

TM Series. Induced Draft, Counter Flow Optional Accessories

TM Series. Induced Draft, Counter Flow Optional Accessories ANTIFREEZE PACKAGE / RESISTANCE HEATING OPTION The antifreeze package is supplied to provide protection against freezing of standing water in the cooling tower sump due to shutdown during winter operation.

More information

Generator Set Specification. City of Jeffersontown Police Department

Generator Set Specification. City of Jeffersontown Police Department Generator Set Specification City of Jeffersontown Police Department 1 1. Scope of Work 2. General Requirements 3. Submittal 4. Codes and Standards 5. Testing 6. Warranty and Maintenance 7. Equipment 8.

More information

Across-the-Line SERIES MP300 Combined Manual and Automatic

Across-the-Line SERIES MP300 Combined Manual and Automatic Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps

More information

BULLETIN. Temperature Controls (VAV) (3/11/2010)

BULLETIN. Temperature Controls (VAV) (3/11/2010) BULLETIN Temperature Controls (VAV) (3/11/2010) This bulletin is to advise you of the fees and responsibilities associated with Tenant s temperature controls. Tenant Responsibility: 1. Unit power is by

More information

Special Provision No. 682S27 June This Special Provision refers to the following standards, specifications or publications:

Special Provision No. 682S27 June This Special Provision refers to the following standards, specifications or publications: CONTROLLER CABINETS, POLE MOUNTED - Item No. Special Provision No. 682S27 June 2017 1. SCOPE This Special Provision covers the requirements for the installation of pole mounted controller cabinets and

More information

B. Provide factory test, startup by a supplier authorized by the equipment manufacturer(s), and on-site testing of the system.

B. Provide factory test, startup by a supplier authorized by the equipment manufacturer(s), and on-site testing of the system. SECTION 480V PACKAGED GENERATOR SYSTEMS 1.01 SCOPE PART 1 - GENERAL A. Provide complete factory assembled EPA certified low emission stand-by generator set equipment compatible for paralleling with the

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi 50 addressable detection and control system.

More information

CHAPTER 20 SERVICE EQUIPMENT

CHAPTER 20 SERVICE EQUIPMENT SERVICE EQUIPMENT CHAPTER 20 SERVICE EQUIPMENT Service equipment includes service cabinets and the equipment and materials necessary for installation. 20.1 Signal Service Cabinet For MnDOT traffic control

More information

DIESEL Engine Fire Pump Controllers Features

DIESEL Engine Fire Pump Controllers Features 1-1 Product Description The FD100 Diesel Engine Controller is designed to control and monitor 12 or 24 volt, diesel fire pump engines. All models are listed by UL and ULC, and approved by Factory Mutual

More information

Soft Start Series MP700 Solid State, Reduced Voltage

Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controls and Accessories Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s

More information

Katherine Sirotin, Assist. Director of Purchasing, September 17, 2:00PM. Bids will be opened in public at this time.

Katherine Sirotin, Assist. Director of Purchasing, September 17, 2:00PM. Bids will be opened in public at this time. Purchasing Department 4400 University Drive, Mailstop 3C5 Fairfax, VA 22030 Voice: 703.993.2580 Fax: 703.993.2589 http://fiscal.gmu.edu/purchasing/ INVITATION FOR BID IFB GMU-1522-19 ISSUE DATE: August

More information

Process Protection. MFA 4P Motion Failure Alarm

Process Protection. MFA 4P Motion Failure Alarm Process Protection MFA 4P Motion Failure Alarm Part 1. General 1.1 Scope A. This section describes the requirements for a motion alarming system. B. Under this item, the contractor shall furnish and install

More information

DGC-500 DIGITAL GENSET CONTROLLER

DGC-500 DIGITAL GENSET CONTROLLER DGC-500 DIGITAL GENSET CONTROLLER Basler Electric s Digital Genset Controller (DGC-500) offers a low cost microprocessor based integrated alternative for the control and monitoring of small to medium sized

More information

UC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK. 40 Dale Street West Babylon, NY Ph: Fx:

UC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK. 40 Dale Street West Babylon, NY Ph: Fx: UC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK 40 Dale Street West Babylon, NY 11704 Ph: 631-753-9550 Fx: 631-753-9560 www.unionconnector.com Emergency Automatic Transfer System STANDARD SPECIFICATIONS

More information

SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING.

SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING. SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING Table of Contents Section Title Page 1 Introduction 2 2 Proposed Schedule 2 3 Instructions

More information

EMERGENCY POWER SYSTEMS

EMERGENCY POWER SYSTEMS 263213 EMERGENCY POWER SYSTEMS PART 1: GENERAL 1.01 SUMMARY A. Section includes: 1. University guidelines for the installation of Emergency Power Systems (EPS). 2. Addresses the design and installation

More information

HEATING AND COOLING REBATES

HEATING AND COOLING REBATES Thank you for choosing to increase your customer's home energy efficiency with heating and cooling rebates. Follow the steps below to ensure eligibility to receive a rebate from the ComEd Energy Efficiency

More information

HEATING AND COOLING REBATES

HEATING AND COOLING REBATES Thank you for choosing to increase your customer's home energy efficiency with heating and cooling rebates. Follow the steps below to ensure eligibility to receive a rebate from the ComEd Energy Efficiency

More information

ADDENDUM TO RFP DOCUMENTS ADDENDUM #01. Project: Solano Community College District Building 100 Generator Project (Project # )

ADDENDUM TO RFP DOCUMENTS ADDENDUM #01. Project: Solano Community College District Building 100 Generator Project (Project # ) ADDENDUM TO RFP DOCUMENTS ADDENDUM #01 Project: Solano Community College District Building 100 Generator Project (Project # 18-003) Date: October 27, 2017 Addendum # 01 The following clarifications are

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION POWER SUPPLIES AND DISTRIBUTION

SECTION POWER SUPPLIES AND DISTRIBUTION SECTION 17460 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for Power Supplies and Power Distribution for Station communications. 1.02 REFERENCE STANDARDS A. American National Standards

More information

DIESEL Engine Fire Pump Controllers Features

DIESEL Engine Fire Pump Controllers Features September 007 DIESEL Engine Fire Pump Controllers Features FD0 Diesel Engine Controllers 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller.

More information

Model R060 Installation - Operation Manual

Model R060 Installation - Operation Manual Residential Heat Pump Water Heaters Model R060 Installation - Operation Manual Important Note Read this entire manual before beginning installation Manufactured By: 6670-A Corners Industrial Court Norcross,

More information

MODEL 8143 SIGNAL SELECTOR INSTALLATION AND OPERATION MANUAL

MODEL 8143 SIGNAL SELECTOR INSTALLATION AND OPERATION MANUAL MODEL 8143 SIGNAL SELECTOR INSTALLATION AND OPERATION MANUAL 95 Methodist Hill Drive Rochester, NY 14623 Phone: US +1.585.321.5800 Fax: US +1.585.321.5219 www.spectracomcorp.com Part Number 8143-5000-0050

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

ROSWELL INDEPENDENT SCHOOL DISTRICT P.O. Box 1437 Roswell, New Mexico General Bid Conditions

ROSWELL INDEPENDENT SCHOOL DISTRICT P.O. Box 1437 Roswell, New Mexico General Bid Conditions ROSWELL INDEPENDENT SCHOOL DISTRICT P.O. Box 1437 Roswell, New Mexico 88202-1437 General Bid Conditions BID # 19-06 Fire Sprinkler Systems Inspections, Testing and Maintenance SEALED BIDS will be opened

More information

SECTION Fire Pumps

SECTION Fire Pumps SECTION 21 30 00 Fire Pumps PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish, install and test a motor-driven fire pump, jockey pump, and controllers in the space provided and as shown in the contract drawings.

More information

FDF Foam Pump Controllers Features

FDF Foam Pump Controllers Features FDF100 Diesel Engine Foam Pump Controllers 1-1 Product Description The FDF Series of Foam Pump Controllers are designed for use with foam concentrate injection, foam transfer and water mist systems for

More information

Variable Frequency Drive SERIES MP800 VFD

Variable Frequency Drive SERIES MP800 VFD Metron Fire Pump Controls and Accessories Variable Frequency Drive SERIES MP800 VFD Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for

More information

BID PROPOSAL-REVISED

BID PROPOSAL-REVISED BID PROPOSAL-REVISED PROJECT: B17-13, Bldg 1300 HVAC ( the Work ) CABRILLO COMMUNITY COLLEGE DISTRICT Bidder Name Bidder Representative(s) Bidder Representative(s) Contact Information Bidder Mailing Address

More information

HEATING AND COOLING REBATES

HEATING AND COOLING REBATES Thank you for choosing to increase your customer's home energy efficiency with heating and cooling rebates. Follow the steps below to ensure eligibility to receive a rebate from the ComEd Energy Efficiency

More information

SECTION NURSE CALL SYSTEM

SECTION NURSE CALL SYSTEM NURSE CALL SMARTCARE NURSE CALL SOLUTION Architectural Specifications Part 1 General SECTION 275223 - NURSE CALL SYSTEM 1.0 Summary 1.1 This section includes nurse call system and requirements for system

More information

SPECIFICATIONS FOR TENDER # SUPPLY OF A FIRE ALARM SYSTEMS SERVICE AGREEMENT FOR WESTERN HEALTH

SPECIFICATIONS FOR TENDER # SUPPLY OF A FIRE ALARM SYSTEMS SERVICE AGREEMENT FOR WESTERN HEALTH SPECIFICATIONS FOR TENDER #0371-0739 SUPPLY OF A FIRE ALARM SYSTEMS SERVICE AGREEMENT FOR WESTERN HEALTH CLOSING DATE: 8 June 2007 CLOSING TIME: 11:00 AM (Newfoundland Time) Invitation to Tender for a

More information

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi 50 CONTROL PANEL SECTION 1 GENERAL CONDITIONS I. SCOPE: SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System utilizing

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125 as the fire extinguishing agent

More information

Paragon. Induced Draft, Counter Flow Optional Accessories

Paragon. Induced Draft, Counter Flow Optional Accessories ANTIFREEZE PACKAGE / RESISTANCE HEATING OPTION The antifreeze package is supplied to provide protection against freezing of standing water in the cooling tower sump due to shutdown during winter operation.

More information

DGC-1000 DIGITAL GENSET CONTROLLER

DGC-1000 DIGITAL GENSET CONTROLLER DGC-1000 DIGITAL GENSET CONTROLLER Basler Electric s Digital Genset Controller (DGC-1000) offers a low cost microprocessor based integrated alternative for small to medium sized genset control and monitoring.

More information

SECTION LOW VOLTAGE LIGHTING CONTROLS

SECTION LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

SECTION ENCLOSED CONTROLLERS

SECTION ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes ac,

More information

CP1-C5 COMPACTOR SPECS 2009

CP1-C5 COMPACTOR SPECS 2009 SECTION 11172 / 14560 TRASH COMPACTOR This section is based on a system produced by: Architectural Refuse Solutions, LLC 525 Kennedy Road Akron, Ohio 44305 Part 1 GENERAL 1.1 RELATED DOCUMENTS A. The general

More information

SECTION SECURITY TESTING AND COMMISSIONING

SECTION SECURITY TESTING AND COMMISSIONING SECTION 280800 - SECURITY TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 WORK INCLUDES A. General Description: This specification section covers the provision of preliminary testing, acceptance testing,

More information

The following information shall become and form part of the contract documents.

The following information shall become and form part of the contract documents. October 4, 206 To: Attention: Re: All Bidders All Bidders JCBE Gymnasium HVAC Upgrades BC#: 206433 Edmonds Project No.: BHM6090 All bidders, The following information shall become and form part of the

More information

Tenant Heat Pump Bulletin Temperature Controls Buildings A1, C1, and H1

Tenant Heat Pump Bulletin Temperature Controls Buildings A1, C1, and H1 12/4/2017 Tenant Heat Pump Bulletin Temperature Controls Buildings A1, C1, and H1 This bulletin is to advise you of the fees and responsibilities associated with the tenant s temperature controls. Tenant

More information

A. Product Data: Include rated capacities, furnished specialties and accessories.

A. Product Data: Include rated capacities, furnished specialties and accessories. BASE BID: SECTION 15542 FUEL-FIRED RADIANT HEATERS PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install a Co-Ray-Vac Low Intensity Vented Infrared Radiant Vacuum Gas Heating System. System must be certified

More information

Utility Battery Chargers DC Power Systems Custom Design

Utility Battery Chargers DC Power Systems Custom Design Utility Battery Chargers DC Power Systems Custom Design Hindle Transformer Company founded 1948 Hitran Corporation Flemington, NJ HindlePower, Inc. Easton, PA, Incorporated 2000 40,000 sq. ft. Facility

More information

Installation and Operations Manual

Installation and Operations Manual Installation and Operations Manual H-IM-LLC February 2018 Part No. 25092501 Replaces H-IM-LLC (01/2014) Lead Lag Control System Table of Contents General Safety Information 2 Inspection 2 Warranty Statement

More information

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual ITC 2000 HEATING CONTROL CABINET Installation & Operation Manual VTI, Incorporated 24 McMillan Way Newark, DE 19713 Phone (302) 738 0500 FAX (302) 738 6594 Revision Level 0.03 Manual No. 90003314 June,

More information

ILLUMINATOR E & IE CENTRAL INVERTER FOR EMERGENCY LIGHTING

ILLUMINATOR E & IE CENTRAL INVERTER FOR EMERGENCY LIGHTING ILLUMINATOR E & IE CENTRAL INVERTER FOR EMERGENCY LIGHTING THE ILLUMINATOR ILLUMINATOR SERIES IE The Illuminator Series IE is an interruptible lighting inverter. It transfers to inverter mode (battery

More information

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. H 2015 Pentair Equipment Protection P/N

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. H 2015 Pentair Equipment Protection P/N CLIMAGUARD Air-to-Air Outdoor Heat Exchangers TX23, TX33, TX38, TX52 Model INSTRUCTION MANUAL Rev. H 2015 Pentair Equipment Protection P/N 10-1008-221 87976519 TABLE OF CONTENTS RECEIVING THE HEAT EXCHANGER...3

More information

Save energy at home residential natural gas rebate form

Save energy at home residential natural gas rebate form New York City (Brooklyn, Queens & Staten Island) Save energy at home residential natural gas rebate form Energy saving offers for residential natural gas heating customers from National Grid. High-Efficiency

More information

Prefunctional Checklist

Prefunctional Checklist Prefunctional Checklist This Prefunctional Checklist should be completed as part of startup and initial checkout of the equipment in preparation for Functional Performance testing. PC: 16231 ITEM: Generator

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G E SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF DATE: 11/13/06 2/1/07 1 Copyright, E, Inc. E 1. ENERAL...4 1.1 Scope Of Work... 4 1.2 Codes and Standards... 4 2. PRODUCTS...5

More information

BULLETIN. Temperature Controls (10/2013)

BULLETIN. Temperature Controls (10/2013) BULLETIN Temperature Controls (10/2013) This bulletin is to advise you of the fees and responsibilities associated with the tenant s temperature controls. This applies to Phase I & II only. Tenant Responsibility:

More information

REQUEST FOR PROPOSALS CLEANING SERVICES

REQUEST FOR PROPOSALS CLEANING SERVICES REQUEST FOR PROPOSALS CLEANING SERVICES Jeffrey Gray City Manager City of Jonesville 265 E. Chicago Street Jonesville, MI 49250 manager@jonesville.org (517) 849-2104 Overview The City of Jonesville is

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC2 THRU NVC6 ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx WITH CONTROLINKS CONTROLS THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas

More information

SECTION GAS-FIRED RADIANT HEATERS

SECTION GAS-FIRED RADIANT HEATERS SECTION 23 55 23 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

TLS-300 UST Monitoring and Leak Detection System

TLS-300 UST Monitoring and Leak Detection System Part 1 General System Requirements 1.1 Description TLS-300 UST Monitoring and Leak Detection System A. These Specifications are intended to provide information by which prospective bidders may understand

More information

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts Figure 1Document: SPEC-112 Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts construction requirements of UL approved Class H (180 C) insulation system. Transformers

More information

BOARD OF EXAMINERS OF LANDSCAPE ARCHITECTS

BOARD OF EXAMINERS OF LANDSCAPE ARCHITECTS STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS BOARD OF EXAMINERS OF LANDSCAPE ARCHITECTS RULES AND REGULATIONS Revised RHODE ISLAND STATE BOARD OF EXAMINERS OF LANDSCAPE ARCHITECTS RULES OF THE BOARD

More information

Drawing Submittal Package

Drawing Submittal Package Project: Customer: Engineer: Pump Manufacturer: Drawing Submittal Package Model GPL + GLU Limited Service Full Voltage Across the Line Start Electric Pump Controller with Automatic Power Transfer Switch

More information

FLORIDA SHERIFFS ASSOCIATION & FLORIDA ASSOCIATION OF COUNTIES

FLORIDA SHERIFFS ASSOCIATION & FLORIDA ASSOCIATION OF COUNTIES FLORIDA SHERIFFS ASSOCIATION & FLORIDA ASSOCIATION OF COUNTIES Name of Dealership Type of Vehicle Zone 600 AMP AUTOMATIC TRANSFER SWITCH (Specification #75) Base Unit Price Mid Florida Diesel, Inc 2018

More information

ELECTRIC FIRE PUMP CONTROLLER

ELECTRIC FIRE PUMP CONTROLLER ELECTRIC FIRE PUMP CONTROLLER INSTRUCTION MANUAL CONTENTS 1. INTRODUCTION 1.1 Safety 1.2 Warranty 1.3 Safety Precautions 1.4 Product Overview 1.5 AS2941-2008 Requirements 2. FEATURES 3. FUNCTIONS AND OPERATIONS

More information

MERAMEC VALLEY R-III SCHOOL DISTRICT 126 North Payne Street Pacific, MO

MERAMEC VALLEY R-III SCHOOL DISTRICT 126 North Payne Street Pacific, MO MERAMEC VALLEY R-III SCHOOL DISTRICT 126 North Payne Street Pacific, MO 63069 636-271-1400 REQUEST FOR PROPOSAL FIRE EXTINGUISHER/KITCHEN HOOD INSPECTIONS FOR ADDITIONAL INFORMATION CONTACT: Joel Cracchiolo,

More information

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps Note: The A/E must choose all design values in brackets below before using in project specifications 1 General 1.1 Provide UL listed and FM approved fire pump complete with pump, driver, controller and

More information

Save energy at home residential natural gas rebate form

Save energy at home residential natural gas rebate form Long Island & Rockaway Peninsula Save energy at home residential natural gas rebate form Energy saving offers for residential natural gas heating customers from National Grid. High-Efficiency Heating Equipment

More information